LOW PROFILE UNIT COOLERS


Technical Guide
Including models meeting DOE minimum AWEF
LOW PROFILE UNIT COOLERS

TABLE OF CONTENTS
3 Nomenclature
3 Preferred Option Packages
5 Features & Benefits
7 Air Defrost
7 Performance Data
7 Application Capacity: Air Defrost- 60 Hz
8 Application Capacity: Air Defrost- 60 Hz (CO2 DX)
9 Application Capacity: Air Defrost- 50 Hz (For PSC Motors) †
10 Application Capacity: Air Defrost- 50 Hz (CO2 DX)
11 Unit Specifications
14 Electric Defrost
14 Performance Data
14 Application Capacity: Low Temperature Electric Defrost- 60 Hz
16 Application Capacity: Low Temperature Electric Defrost- 60 Hz (CO2 DX)
17 Application Capacity: Low Temperature Electric Defrost- 50 Hz (For PSC Motors) †
19 Application Capacity: Low Temperature Electric Defrost- 50 Hz (CO2 DX)
20 Application Capacity: Medium Temperature Electric Defrost- 60 Hz
22 Application Capacity: Medium Temperature Electric Defrost- 60 Hz (CO2 DX)
23 23 Unit Specifications
Hot Gas Defrost
27 27 Performance Data
27 Application Capacity: Low Temperature Hot Gas Defrost- 60 Hz
29 Application Capacity: Low Temperature Hot Gas Defrost- 50 Hz (For PSC Motors) †
31 Application Capacity: Medium Temperature Hot Gas Defrost- 60 Hz
33 33 Unit Specifications
39 Physical Data
42 Dimensional Drawings
DOE Rated AWEF
43 43 AWEF
43 Air Defrost 1-Speed EC Motors
44 Electric Defrost 1-Speed EC Motors
45 Electric Defrost 2-Speed EC Motors
46 Hot Gas Defrost 1-Speed EC Motors
47 Hot Gas Defrost 1-Speed EC Motors
48 Hot Gas Defrost Reverse Cycle
48 Hot Gas Reverse Cycle Kits
48 Reverse Cycle Piping
51 Replacement Parts
51 Motor/Motor Mounts
51 Fan Blade/Fan Guard
51 Cabinet Components
53 Drain Pan Heaters
53 Coil Defrost Heaters
53 Electrical Components
53 Drain Fitting
55 Standard Nozzle Selection
55 Air Defrost
56 Electric Defrost
57 Hot Gas Defrost

2
NOMENCLATURE

REFRIGERANT
DESIGNATOR DEFROST
S = Standard STYLE
Refrigerants A = Air
(R-404A, R-448A/ Defrost
R-449A, R-407A/ E = Electric
PRODUCT NOMINAL R-407F, R-407C) Defrost
IDENTIFIER CAPACITY G = Glycol H = Hot DESIGN
E = Evaporator x100 = BTU/h C = CO2 DX Gas Defrost REVISION

B E L 0095 A S 6 A M A B0000
BRAND EVAPORATOR ELECTRICAL CODE FINS PER MOTOR TYPE FACTORY-INSTALLED
B = Bohn STYLE A = 115/1/60 INCH (fpi) M = 2-Speed EC OPTION PACKAGES
L = Low Profile B = 208-230/1/60 E = Single B#### = Preferred
C = 208-230/3/60 Speed EC Option Packages
M = 460/1/60 C = PSC Totally D#### = A la Carte
Q = 220/1/50 Enclosed Options
Y#### = Custom
Option Packages

3
LOW PROFILE UNIT COOLERS

PREFERRED OPTION PACKAGES


(HFC Refrigerants)
Description
Package
(standard base model features + indicated options below)

B0000 Standard Base

B0100 Beacon II (R-404A/R-448A/R-449A)

B0101 Beacon II (R-407A/R-407C/R-407F)

B0200 intelliGen Refrigeration Controller (R-404A/R-448A/R-449A)

B0201 intelliGen Refrigeration Controller (R-407A/R-407C/R-407F)

B0300 Quick Response Controller (R-404A/R-448A/R-449A)

B0301 Quick Response Controller (R-407A/R-407C/R-407F)

B0403 Mounted Components (TXV, Solenoid Valve, Electronic T’Stat – R-404A)

B0404 Mounted Components (TXV, Solenoid Valve, Electronic T’Stat – R-407A/C/F)

B0405 Mounted Components (TXV, Solenoid Valve, Electronic T’Stat – R-448A/R-449A)

PREFERRED OPTION PACKAGES


(CO2 DX)
Description
Package
(standard base model features + indicated options below)

B0500 Danfoss EEV (120V) with 1/4”MPT Transducer Connection


Standard Base (Pressure Transducer not included)

Danfoss EEV (120V) with 1/4”MPT Transducer Connection


B0501
(Pressure Transducer not included) + Filter Drier

Sporlan EEV (120V) with 1/4”MPT Transducer Connection


B0502
(Pressure Transducer not included) + Filter Drier

B0503 Danfoss EEV (120V) with Danfoss Pressure Transducer

B0504 Danfoss EEV (120V) with Danfoss Pressure Transducer + Filter Drier

B0505 Danfoss EEV (120V) with CPC Pressure Transducer

B0506 Danfoss EEV (120V) with CPC Pressure Transducer + Filter Drier

B0507 Sporlan EEV (120V) with Microthermo Pressure Transducer + Filter Drier

4
FEATURES & BENEFITS
CABINET
■■ Cabinet design features hinged, removable front access MOTORS
panels on each side for easy access to electrical and
refrigeration components. ■■ Motors plug into wiring harness for easier servicing.

■■ Molded fan guard and access panels are made of ■■ 2-Speed EC motors standard on Air Defrost models.
strong, durable, NSF and UL Sanitation rated lightweight ■■ Single Speed EC motors standard on Electric Defrost & Hot
and damage-resistant molded plastic material. Gas Defrost models.
■■ Quick-removal fan guard/motor assembly for easier
servicing of air mover parts. DRAIN PAN
■■ Sweat connections to reduce potential for leaks. ■■ Large diameter drain hole (3/4” ID) is located towards
the back of the unit.
■■ Liquid line solenoid wire harness is factory-installed for
quick installation. ■■ Extended drain pan heaters for more uniform defrost
throughout the drain pan and additional heat in end
COIL compartments.
■■ Internally enhanced tubing and fin design for higher ■■ Hinged, removable drain pans allow for easy and safe
efficiency. access (3-6 fan units only).
■■ Coil heater slots have been enlarged for easier
installation and replacement. OTHER OPTIONS
■■ Hot gas loop on bottom of coil for easier access is ■■ Units available with factory installed mounted
standard on hot gas defrost models. components: Expansion Valve, Mechanical Room
■■ Fixed defrost termination for electric, adjustable Thermostat, Solenoid Valve with Dual Voltage Coil.
defrost termination for hot gas.
■■ Units available with mounted TXV and mounted TXV
CONTROLS OPTIONS with solenoid valve.
–– Pre-assembled units come with mounted TXV,
■■ intelliGen™ Refrigeration Controller (iRC)
liquid line solenoid valve and room thermostat.
–– Factory mounted, tested and calibrated with an
–– Available in a master liquid line configuration.
electronic expansion valve, pressure transducer,
temperature sensors, control board and User –– Pre-charged units come with mounted TXV, liquid
Interface. Standard features include Door Sensor, line solenoid valve, room thermostat and quick
Product Load Input and Alarm Output. connect fittings.
–– Optional Field installable intelliGen™ Webserver ■■ Units available with stainless steel housing and drain
Card (iWC) enables local and remote monitoring on pan.
any smart phone, tablet or PC.
■■ All units come standard with aluminum fin, copper
–– Optional Field installable intelliGen™ Integration Card
tube coils. Units available with various coil material
(iIC) enables connectivity to BACnet and Modbus.
/ coating options including polyester fin coating,
■■ Quick Response Controller units include factory black electrostatic fin coating, copper fins and Bronz-
mounted electronic expansion valve, pressure Glow coil coating. Please review our price book for
transducer, temperature sensors and control board. availability.

■■ Beacon II™ units include factory mounted electronic ■■ Units available with insulated drain pan.
expansion valve, pressure transducer, temperature
sensors and control board.

5
LOW PROFILE UNIT COOLERS

FEATURES & BENEFITS


OUTSTANDING FEATURES

Optional Factory Mounted Components Composite Molded Access Panels have undergone
Choose from Heatcraft’s industry-leading intelliGen™ extensive engineering and laboratory testing to ensure they
Refrigeration Controller, Quick Response Controller, Beacon II are damage resistant from drops, dents, and bangs.
Control or traditional mechanical components.

Hinged &
Removeable Access
Panels allow for
easy access to both
refrigeration and
electrical end of Low
Profile units.

Easy Service Motor Re-Engineered Fan


Mount quickly and Guards have been
easily allows motor redesigned for optimized
to be removed air circulation and comply
Hinged Drain Pan improves access to for service or to new UL60335 safety
service and clean the drain pan and coil. replacement. standard.
(3-6 fan models only)

Table 1: Capacity Correction Factors


Electric and Hot Gas Defrost Units
Saturated Suction Temperature °F +20 -10 -20 -30

Saturated Suction Temperature °C -7 -23 -29 -34

Multiply Capacity By 1.15 1.04 1.00 0.90

6
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Air Defrost- 60 Hz
Please consult AWEF table on page 43 to confirm model meets DOE minimum AWEF

R-404A/R-507A R-448A/R-449A
Application Capacity 1
Application Capacity1
507A Legacy 10°F TD/25°F SST 6°C TD/-4°C SST 10°F TD/25°F SST 6°C TD/-4°C SST Fan Data
Model No. of
New Model BTUH Watts BTUH Watts Fans CFM m3H
BEL0045*S6A^A ADT040 4,000 1,200 4,600 1,300 1 653 1,109
BEL0055*S6A^A ADT052 5,200 1,500 6,100 1,800 1 610 1,036
ADT065
BEL0060*S6A^A ADT070 6,500 1,900 7,800 2,300 1 610 1,036
ADT070
BEL0095*S6A^A 8,000 2,300 10,000 2,900 2 1,305 2,217
ADT090

BEL0105*S6A^A ADT090 9,200 2,650 12,500 3,600 2 1,305 2,217


ADT104
BEL0115*S6A^A ADT120 11,700 3,370 14,500 4,180 2 1,220 2,073
BEL0125*S6A^A ADT130 13,000 3,800 15,500 4,500 2 1,220 2,073
BEL0155*S6A^A ADT140 14,000 4,100 16,800 4,900 3 1,958 3,327
ADT156
BEL0190*S6A^A ADT180 18,000 5,300 21,200 6,200 3 1,830 3,109

BEL0250*S6A^A ADT208 20,800 6,100 24,600 7,200 4 2,440 4,146


BEL0295*S6A^A ADT260 26,000 7,600 30,700 9,000 5 3,050 5,182
BEL0350*S6A^A ADT312 31,200 9,100 36,800 10,800 6 3,660 6,218
BEL0380*S6A^A ADT370 37,000 10,800 44,400 13,000 6 3,660 6,218

R-407A/R-407F R-407C
Application Capacity 1
Application Capacity1
507A Legacy 10°F TD/25°F SST 6°C TD/-4°C SST 10°F TD/25°F SST 6°C TD/-4°C SST Fan Data
Model No. of
New Model BTUH Watts BTUH Watts Fans CFM m3H

BEL0045*S6A^A ADT040 4,600 1,300 4,600 1,300 1 653 1,109


BEL0055*S6A^A ADT052 6,100 1,800 6,100 1,800 1 610 1,036
ADT065
BEL0060*S6A^A 7,800 2,300 7,800 2,300 1 610 1,036
ADT070
ADT070
BEL0095*S6A^A 10,000 2,900 10,000 2,900 2 1,305 2,217
ADT090
ADT090
BEL0105*S6A^A 12,500 3,600 12,500 3,600 2 1,305 2,217
ADT104
BEL0115*S6A^A ADT120 14,500 4,180 14,500 4,180 2 1,220 2,073
BEL0125*S6A^A ADT130 15,500 4,500 15,500 4,500 2 1,220 2,073
BEL0155*S6A^A ADT140 16,800 4,900 16,800 4,900 3 1,958 3,327
ADT156
BEL0190*S6A^A 21,200 6,200 21,200 6,200 3 1,830 3,109
ADT180
BEL0250*S6A^A ADT208 24,600 7,200 24,600 7,200 4 2,440 4,146
BEL0295*S6A^A ADT260 30,700 9,000 30,700 9,000 5 3,050 5,182
BEL0350*S6A^A ADT312 36,800 10,800 36,800 10,800 6 3,660 6,218
BEL0380*S6A^A ADT370 44,400 13,000 44,400 13,000 6 3,660 6,218

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

7
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Air Defrost- 60 Hz
Please consult AWEF table on page 43 to confirm model meets DOE minimum AWEF

CO2 DX
Application Capacity1
507A Legacy 10°F TD/25°F SST 6°C TD/-4°C SST Fan Data
Model
New Model BTUH Watts No. of Fans CFM m3H
BEL0045*C6A^A ADTY040 4,600 1,348 1 653 1,109
BEL0055*C6A^A ADTY052 6,100 1,788 1 610 1,036
ADTY065
BEL0060*C6A^A ADTY070 7,800 2,286 1 610 1,036
ADTY070
BEL0095*C6A^A 10,000 2,931 2 1,305 2,217
ADTY090

BEL0105*C6A^A ADTY090 12,500 3,663 2 1,305 2,217


ADTY104
BEL0115*C6A^A ADTY120 14,500 4,250 2 1,220 2,073
BEL0125*C6A^A ADTY130 15,500 4,543 2 1,220 2,073
BEL0155*C6A^A ADTY140 16,800 4,924 3 1,958 3,327
ADTY156
BEL0190*C6A^A ADTY180 21,200 6,213 3 1,830 3,109

BEL0250*C6A^A ADTY208 24,600 7,210 4 2,440 4,146


BEL0295*C6A^A ADTY260 30,700 8,997 5 3,050 5,182
BEL0350*C6A^A ADTY312 36,800 10,785 6 3,660 6,218
BEL0380*C6A^A ADTY370 44,400 13,012 6 3,660 6,218

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

8
PERFORMANCE DATA – R-448A/R-449A
Application Capacity: Air Defrost- 50 Hz (For PSC Motors) †
Please consult AWEF table on page 43 to confirm model meets DOE minimum AWEF

R-404A/R-507A R-448A/R-449A
Application Capacity 1
Application Capacity1
507A Legacy 10°F TD/25°F SST 6°C TD/-4°C SST 10°F TD/25°F SST 6°C TD/-4°C SST Fan Data
Model No. of
New Model BTUH Watts BTUH Watts Fans CFM m3H
BEL0045*S6A^A ADT040 3,800 1,140 4,370 1,235 1 588 999
BEL0055*S6A^A ADT052 4,940 1,425 5,795 1,710 1 549 933
ADT065
BEL0060*S6A^A 6,175 1,805 7,410 2,185 1 549 933
ADT070
ADT070
BEL0095*S6A^A 7,600 2,185 9,500 2,755 2 1,175 1,995
ADT090
ADT090
BEL0105*S6A^A 8,740 2,518 11,875 3,420 2 1,175 1,995
ADT104
BEL0115*S6A^A ADT120 11,115 3,202 13,775 3,971 2 1,098 1,866
BEL0125*S6A^A ADT130 12,350 3,610 14,725 4,275 2 1,098 1,866
BEL0155*S6A^A ADT140 13,300 3,895 15,960 4,655 3 1,762 2,994
ADT156
BEL0190*S6A^A 17,100 5,035 20,140 5,890 3 1,647 2,798
ADT180
BEL0250*S6A^A ADT208 19,760 5,795 23,370 6,840 4 2,196 3,731
BEL0295*S6A^A ADT260 24,700 7,220 29,165 8,550 5 2,745 4,664
BEL0350*S6A^A ADT312 29,640 8,645 34,960 10,260 6 3,294 5,597
BEL0380*S6A^A ADT370 35,150 10,260 42,180 12,350 6 3,294 5,597

R-407A/R-407F R-407C
Application Capacity 1
Application Capacity1
507A Legacy 10°F TD/25°F SST 6°C TD/-4°C SST 10°F TD/25°F SST 6°C TD/-4°C SST Fan Data
Model No. of
New Model BTUH Watts BTUH Watts Fans CFM m3H
BEL0045*S6A^A ADT040 4,370 1,235 4,370 1,235 1 588 999
BEL0055*S6A^A ADT052 5,795 1,710 5,795 1,710 1 549 933
ADT065
BEL0060*S6A^A 7,410 2,185 7,410 2,185 1 549 933
ADT070
ADT070 2,755 9,500 2,755 2 1,175 1,995
BEL0095*S6A^A 9,500
ADT090
ADT090 11,875 3,420 11,875 3,420 2 1,175 1,995
BEL0105*S6A^A
ADT104
BEL0115*S6A^A ADT120 13,775 3,971 13,775 3,971 2 1,098 1,866
BEL0125*S6A^A ADT130 14,725 4,275 14,725 4,275 2 1,098 1,866
BEL0155*S6A^A ADT140 15,960 4,655 15,960 4,655 3 1,762 2,994
ADT156
BEL0190*S6A^A 20,140 5,890 20,140 5,890 3 1,647 2,798
ADT180
BEL0250*S6A^A ADT208 23,370 6,840 23,370 6,840 4 2,196 3,731
BEL0295*S6A^A ADT260 29,165 8,550 29,165 8,550 5 2,745 4,664
BEL0350*S6A^A ADT312 34,960 10,260 34,960 10,260 6 3,294 5,597
BEL0380*S6A^A ADT370 42,180 12,350 42,180 12,350 6 3,294 5,597

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request
† = For single speed and 2-speed EC motors, use 60 Hz capacity and airflow values. (units with EC motors operating at 50 Hz will not see a reduction in performance
due to the electronic control of the motor)

9
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-448A/R-449A


Application Capacity: Air Defrost- 50 Hz (For PSC Motors) †
Please consult AWEF table on page 43 to confirm model meets DOE minimum AWEF

CO2 DX
Application Capacity1
507A Legacy 10°F TD/25°F SST 6°C TD/-4°C SST Fan Data
Model
New Model BTUH Watts No. of Fans CFM m3H
BEL0045*C6A^A ADTY040 4,370 1,281 1 588 999
BEL0055*C6A^A ADTY052 5,795 1,698 1 549 933
ADTY065
BEL0060*C6A^A ADTY070 7,410 2,172 1 549 933
ADTY070
BEL0095*C6A^A 9,500 2,784 2 1,175 1,996
ADTY090

BEL0105*C6A^A ADTY090 11,875 3,480 2 1,175 1,996


ADTY104
BEL0115*C6A^A ADTY120 13,775 4,037 2 1,098 1,866
BEL0125*C6A^A ADTY130 14,725 4,315 2 1,098 1,866
BEL0155*C6A^A ADTY140 15,960 4,677 3 1,762 2,994
ADTY156
BEL0190*C6A^A ADTY180 20,140 5,902 3 1,647 2,798

BEL0250*C6A^A ADTY208 23,370 6,849 4 2,196 3,731


BEL0295*C6A^A ADTY260 29,165 8,547 5 2,745 4,664
BEL0350*C6A^A ADTY312 34,960 10,246 6 3,294 5,597
BEL0380*C6A^A ADTY370 42,180 12,362 6 3,294 5,597

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request
† = For single speed and 2-speed EC motors, use 60 Hz capacity and airflow values. (units with EC motors operating at 50 Hz will not see a reduction in performance
due to the electronic control of the motor)

10
SPECIFICATIONS– R-407A/R-407F
Air Defrost- 60 Hz
Please consult AWEF table on page 43 to confirm model meets DOE minimum AWEF

2-Speed EC Motor (Totally Enclosed)


507A 115/1/60 208-230/1/60
New Model HP Amps Watts MCA MOPD Amps Watts MCA MOPD
BEL0045*±6A^A 1/20 0.9 55 1.1 20 0.5 55 0.6 15
BEL0055*±6A^A 1/20 0.9 55 1.1 20 0.5 55 0.6 15
BEL0060*±6A^A 1/20 0.9 55 1.1 20 0.5 55 0.6 15
BEL0095*±6A^A 1/20 1.8 110 2.0 20 1.0 110 1.1 15
BEL0105*±6A^A 1/20 1.8 110 2.0 20 1.0 110 1.1 15
BEL0115*±6A^A 1/20 1.8 110 2.0 20 1.0 110 1.1 15
BEL0125*±6A^A 1/20 1.8 110 2.0 20 1.0 110 1.1 15
BEL0155*±6A^A 1/20 2.7 165 2.9 20 1.5 165 1.6 15
BEL0190*±6A^A 1/20 2.7 165 2.9 20 1.5 165 1.6 15
BEL0250*±6A^A 1/20 3.6 220 3.8 20 2.0 220 2.1 15
BEL0295*±6A^A 1/20 4.5 275 4.7 20 2.5 275 2.6 15
BEL0350*±6A^A 1/20 5.4 330 5.6 20 3.0 330 3.1 15
BEL0380*±6A^A 1/20 5.4 330 5.6 20 3.0 330 3.1 15

1-Speed EC Motor (Totally Enclosed)


507A 115/1/60 208-230/1/60
New Model HP Amps Watts MCA MOPD Amps Watts MCA MOPD
BEL0045*±6A^A 1/20 0.9 55 1.1 20 0.5 59 0.6 15
BEL0055*±6A^A 1/20 0.9 55 1.1 20 0.5 59 0.6 15
BEL0060*±6A^A 1/20 0.9 55 1.1 20 0.5 59 0.6 15
BEL0095*±6A^A 1/20 1.8 110 2.0 20 1.0 118 1.1 15
BEL0105*±6A^A 1/20 1.8 110 2.0 20 1.0 118 1.1 15
BEL0115*±6A^A 1/20 1.8 110 2.0 20 1.0 118 1.1 15
BEL0125*±6A^A 1/20 1.8 110 2.0 20 1.0 118 1.1 15
BEL0155*±6A^A 1/20 2.7 165 2.9 20 1.5 177 1.6 15
BEL0190*±6A^A 1/20 2.7 165 2.9 20 1.5 177 1.6 15
BEL0250*±6A^A 1/20 3.6 220 3.8 20 2.0 236 2.1 15
BEL0295*±6A^A 1/20 4.5 275 4.7 20 2.5 295 2.6 15
BEL0350*±6A^A 1/20 5.4 330 5.6 20 3.0 354 3.1 15
BEL0380*±6A^A 1/20 5.4 330 5.6 20 3.0 354 3.1 15

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)

11
LOW PROFILE UNIT COOLERS

SPECIFICATIONS– R-407A/R-407F
Air Defrost- 60 Hz
Please consult AWEF table on page 43 to confirm model meets DOE minimum AWEF

PSC Motor (Totally Enclosed)


507A 115/1/60 208-230/1/60 460/1/60
New Model HP Amps Watts MCA MOPD Amps Watts MCA MOPD Amps Watts MCA MOPD
BEL0045*±6A^A 1/20 1.0 82 1.3 20 0.5 91 0.6 15 0.4 117 0.5 15
BEL0055*±6A^A 1/20 1.0 82 1.3 20 0.5 91 0.6 15 0.4 117 0.5 15
BEL0060*±6A^A 1/20 1.0 82 1.3 20 0.5 91 0.6 15 0.4 117 0.5 15
BEL0095*±6A^A 1/20 2.0 164 2.3 20 1.0 182 1.1 15 0.8 234 0.9 15
BEL0105*±6A^A 1/20 2.0 164 2.3 20 1.0 182 1.1 15 0.8 234 0.9 15
BEL0115*±6A^A 1/20 2.0 164 2.3 20 1.0 182 1.1 15 0.8 234 0.9 15
BEL0125*±6A^A 1/20 2.0 164 2.3 20 1.0 182 1.1 15 0.8 234 0.9 15
BEL0155*±6A^A 1/20 3.0 246 3.3 20 1.5 273 1.6 15 1.2 351 1.3 15
BEL0190*±6A^A 1/20 3.0 246 3.3 20 1.5 273 1.6 15 1.2 351 1.3 15
BEL0250*±6A^A 1/20 4.0 328 4.3 20 2.0 364 2.1 15 1.6 468 1.7 15
BEL0295*±6A^A 1/20 5.0 410 5.3 20 2.5 455 2.6 15 2.0 585 2.1 15
BEL0350*±6A^A 1/20 6.0 492 6.3 20 3.0 546 3.1 15 2.4 702 2.5 15
BEL0380*±6A^A 1/20 6.0 492 6.3 20 3.0 546 3.1 15 2.4 702 2.5 15

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)

12
SPECIFICATIONS– R-407A/R-407F
Air Defrost- 50 Hz
Please consult AWEF table on page 43 to confirm model meets DOE minimum AWEF

2-Speed EC Motor 1-Speed EC Motor PSC Motor


(Totally Enclosed) (Totally Enclosed) (Totally Enclosed)
507A 220/1/50 220/1/50 220/1/50
New Model HP Amps Watts MCA MOPD Amps Watts MCA MOPD Amps Watts MCA MOPD
BEL0045*±6A^A 1/20 0.5 55 0.6 15 0.5 59 0.6 15 0.5 65 0.6 15
BEL0055*±6A^A 1/20 0.5 55 0.6 15 0.5 59 0.6 15 0.5 65 0.6 15
BEL0060*±6A^A 1/20 0.5 55 0.6 15 0.5 59 0.6 15 0.5 65 0.6 15
BEL0095*±6A^A 1/20 1.0 110 1.1 15 1.0 118 1.1 15 1.0 130 1.1 15
BEL0105*±6A^A 1/20 1.0 110 1.1 15 1.0 118 1.1 15 1.0 130 1.1 15
BEL0115*±6A^A 1/20 1.0 110 1.1 15 1.0 118 1.1 15 1.0 130 1.1 15
BEL0125*±6A^A 1/20 1.0 110 1.1 15 1.0 118 1.1 15 1.0 130 1.1 15
BEL0155*±6A^A 1/20 1.5 165 1.6 15 1.5 177 1.6 15 1.5 195 1.6 15
BEL0190*±6A^A 1/20 1.5 165 1.6 15 1.5 177 1.6 15 1.5 195 1.6 15
BEL0250*±6A^A 1/20 2.0 220 2.1 15 2.0 236 2.1 15 2.0 260 2.1 15
BEL0295*±6A^A 1/20 2.5 275 2.6 15 2.5 295 2.6 15 2.5 325 2.6 15
BEL0350*±6A^A 1/20 3.0 330 3.1 15 3.0 354 3.1 15 3.0 390 3.1 15
BEL0380*±6A^A 1/20 3.0 330 3.1 15 3.0 354 3.1 15 3.0 390 3.1 15

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)

13
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Low Temperature Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-404A/R-507A R-448A/R-449A
Application Capacity 1
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
LET035
6 BEL0040*S6E^A 3,500 1,000 3,900 1,000 1 685 1,164
LET040
LET040
6 BEL0045*S6E^A 4,700 1,400 5,300 1,600 1 641 1,088
LET047
6 BEL0065*S6E^A LET065 6,500 1,900 7,200 2,100 2 1,371 2,329
6 BEL0080*S6E^A LET075 7,500 2,200 8,400 2,500 2 1,371 2,329
6 BEL0100*S6E^A LET090 9,000 2,600 9,900 2,900 2 1,281 2,176
6 BEL0130*S6E^A LET120 12,000 3,500 13,500 4,000 3 2,056 3,493
6 BEL0155*S6E^A LET140 14,000 4,100 16,000 4,700 3 1,922 3,265
6 BEL0170*S6E^A LET160 16,000 4,700 17,900 5,200 4 2,741 4,658
6 BEL0205*S6E^A LET180 18,000 5,300 20,100 5,900 4 2,562 4,353
6 BEL0240*S6E^A LET200 20,000 5,900 22,800 6,600 5 3,203 5,441
6 BEL0255*S6E^A LET240 24,000 7,000 26,900 7,900 6 4,112 6,986
6 BEL0310*S6E^A LET280 28,000 8,200 31,400 9,200 6 3,843 6,529
4 BEL0045*S4E^A LLE041 4,100 1,200 4,500 1,300 1 667 1,132
4 BEL0070*S4E^A LLE068 6,800 2,000 7,400 2,200 2 1,425 2,422
4 BEL0090*S4E^A LLE080 8,000 2,300 8,800 2,600 2 1,332 2,263
4 BEL0135*S4E^A LLE102 10,200 3,000 12,800 3,700 3 1,998 3,395
4 BEL0180*S4E^A LLE136 13,600 4,000 17,300 5,000 4 2,664 4,527
4 BEL0220*S4E^A LLE170 17,000 5,000 19,500 5,600 5 3,331 5,659
LLE204
4 BEL0275*S4E^A 23,500 6,900 25,900 7,600 6 3,997 6,790
LLE235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

14
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Low Temperature Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-407A/R-407F R-407C
Application Capacity 1
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
LET035
6 BEL0040*S6E^A 3,900 1,000 - - 1 685 1,164
LET040
LET040
6 BEL0045*S6E^A 5,300 1,600 - - 1 641 1,088
LET047
6 BEL0065*S6E^A LET065 7,200 2,100 - - 2 1,371 2,329
6 BEL0080*S6E^A LET075 8,400 2,500 - - 2 1,371 2,329
6 BEL0100*S6E^A LET090 9,900 2,900 - - 2 1,281 2,176
6 BEL0130*S6E^A LET120 13,500 4,000 - - 3 2,056 3,493
6 BEL0155*S6E^A LET140 16,000 4,700 - - 3 1,922 3,265
6 BEL0170*S6E^A LET160 17,900 5,200 - - 4 2,741 4,658
6 BEL0205*S6E^A LET180 20,100 5,900 - - 4 2,562 4,353
6 BEL0240*S6E^A LET200 22,400 6,500 - - 5 3,203 5,441
6 BEL0255*S6E^A LET240 26,900 7,900 - - 6 4,112 6,986
6 BEL0310*S6E^A LET280 31,400 9,200 - - 6 3,843 6,529
4 BEL0045*S4E^A LLE041 4,500 1,300 - - 1 667 1,132
4 BEL0070*S4E^A LLE068 7,400 2,200 - - 2 1,425 2,422
4 BEL0090*S4E^A LLE080 8,800 2,600 - - 2 1,332 2,263
4 BEL0135*S4E^A LLE102 12,100 3,500 - - 3 1,998 3,395
4 BEL0180*S4E^A LLE136 16,300 4,700 - - 4 2,664 4,527
4 BEL0220*S4E^A LLE170 19,600 5,600 - - 5 3,331 5,659
LLE204
4 BEL0275*S4E^A 25,900 7,600 - - 6 3,997 6,790
LLE235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

15
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Low Temperature Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

CO2 DX
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data


Legacy
Model
FPI New Model BTUH Watts No. of Fans CFM m3H
LETC035
6 BEL0040*C6E^A 3,900 1,143 1 685 1,164
LETC040
LETC040
6 BEL0045*C6E^A 5,300 1,553 1 641 1,088
LETC047
6 BEL0065*C6E^A LETC065 7,200 2,110 2 1,371 2,329
6 BEL0080*C6E^A LETC075 8,400 2,462 2 1,371 2,329
6 BEL0100*C6E^A LETC090 9,900 2,901 2 1,281 2,176
6 BEL0130*C6E^A LETC120 13,500 3,956 3 2,056 3,493
6 BEL0155*C6E^A LETC140 16,000 4,689 3 1,922 3,265
6 BEL0170*C6E^A LETC160 17,900 5,246 4 2,741 4,657
6 BEL0205*C6E^A LETC180 20,100 5,891 4 2,562 4,353
6 BEL0240*C6E^A LETC200 22,400 6,565 5 3,203 5,441
6 BEL0255*C6E^A LETC240 26,900 7,884 6 4,112 6,986
6 BEL0310*C6E^A LETC280 31,400 9,202 6 3,843 6,529
4 BEL0045*C4E^A LLEC041 4,500 1,319 1 667 1,132
4 BEL0070*C4E^A LLEC068 7,400 2,169 2 1,425 2,422
4 BEL0090*C4E^A LLEC080 8,800 2,579 2 1,332 2,263
4 BEL0135*C4E^A LLEC102 12,100 3,546 3 1,998 3,395
4 BEL0180*C4E^A LLEC136 16,300 4,777 4 2,664 4,527
4 BEL0220*C4E^A LLEC170 19,600 5,744 5 3,331 5,659
LLEC204
4 BEL0275*C4E^A 25,900 7,591 6 3,997 6,790
LLEC235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

16
PERFORMANCE DATA – R-448A/R-449A
Application Capacity: Low Temperature Electric Defrost- 50 Hz (For PSC Motors) †
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-404A/R-507A R-448A/R-449A
Application Capacity 1
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
LET035
6 BEL0040*S6E^A 3,325 950 3,705 950 1 617 1,048
LET040
LET040
6 BEL0045*S6E^A 4,465 1,330 5,035 1,520 1 576 979
LET047
6 BEL0065*S6E^A LET065 6,175 1,805 6,840 1,995 2 1,234 2,096
6 BEL0080*S6E^A LET075 7,125 2,090 7,980 2,375 2 1,234 2,096
6 BEL0100*S6E^A LET090 8,550 2,470 9,405 2,755 2 1,153 1,959
6 BEL0130*S6E^A LET120 11,400 3,325 12,825 3,800 3 1,850 3,144
6 BEL0155*S6E^A LET140 13,300 3,895 15,200 4,465 3 1,729 2,938
6 BEL0170*S6E^A LET160 15,200 4,465 17,005 4,940 4 2,467 4,192
6 BEL0205*S6E^A LET180 17,100 5,035 19,095 5,605 4 2,306 3,918
6 BEL0240*S6E^A LET200 19,000 5,605 21,660 6,270 5 2,882 4,897
6 BEL0255*S6E^A LET240 22,800 6,650 25,555 7,505 6 3,701 6,288
6 BEL0310*S6E^A LET280 26,600 7,790 29,830 8,740 6 2,459 5,876
4 BEL0045*S4E^A LLE041 3,895 1,140 4,275 1,235 1 600 1,019
4 BEL0070*S4E^A LLE068 6,460 1,900 7,030 2,090 2 1,283 2,180
4 BEL0090*S4E^A LLE080 7,600 2,185 8,360 2,470 2 1,199 2,037
4 BEL0135*S4E^A LLE102 9,690 2,850 12,160 3,515 3 1,799 3,056
4 BEL0180*S4E^A LLE136 12,920 3,800 16,435 4,750 4 2,398 4,074
4 BEL0220*S4E^A LLE170 16,150 4,750 18,525 5,320 5 2,998 5,093
LLE204
4 BEL0275*S4E^A 22,325 6,555 24,605 7,220 6 3,597 6,111
LLE235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request
† = For single speed and 2-speed EC motors, use 60 Hz capacity and airflow values. (units with EC motors operating at 50 Hz will not see a reduction in performance
due to the electronic control of the motor)

17
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-448A/R-449A


Application Capacity: Low Temperature Electric Defrost- 50 Hz (For PSC Motors) †
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-407A/R-407F R-407C
Application Capacity 1
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
LET035
6 BEL0040*S6E^A 3,705 950 - - 1 617 1,048
LET040
LET040
6 BEL0045*S6E^A 5,035 1,520 - - 1 576 979
LET047
6 BEL0065*S6E^A LET065 6,840 1,995 - - 2 1,234 2,096
6 BEL0080*S6E^A LET075 7,980 2,375 - - 2 1,234 2,096
6 BEL0100*S6E^A LET090 9,405 2,755 - - 2 1,153 1,959
6 BEL0130*S6E^A LET120 12,825 3,800 - - 3 1,850 3,144
6 BEL0155*S6E^A LET140 15,200 4,465 - - 3 1,729 2,938
6 BEL0170*S6E^A LET160 17,005 4,940 - - 4 2,467 4,192
6 BEL0205*S6E^A LET180 19,095 5,605 - - 4 2,306 3,918
6 BEL0240*S6E^A LET200 21,280 6,175 - - 5 2,882 4,897
6 BEL0255*S6E^A LET240 25,555 7,505 - - 6 3,701 6,288
6 BEL0310*S6E^A LET280 29,830 8,740 - - 6 2,459 5,876
4 BEL0045*S4E^A LLE041 4,275 1,235 - - 1 600 1,019
4 BEL0070*S4E^A LLE068 7,030 2,090 - - 2 1,283 2,180
4 BEL0090*S4E^A LLE080 8,360 2,470 - - 2 1,199 2,037
4 BEL0135*S4E^A LLE102 11,495 3,325 - - 3 1,799 3,056
4 BEL0180*S4E^A LLE136 15,485 4,465 - - 4 2,398 4,074
4 BEL0220*S4E^A LLE170 18,620 5,320 - - 5 2,998 5,093
LLE204
4 BEL0275*S4E^A 24,605 7,220 - - 6 3,597 6,111
LLE235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request
† = For single speed and 2-speed EC motors, use 60 Hz capacity and airflow values. (units with EC motors operating at 50 Hz will not see a reduction in performance
due to the electronic control of the motor)

18
PERFORMANCE DATA – R-448A/R-449A
Application Capacity: Low Temperature Electric Defrost- 50 Hz (For PSC Motors) †
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

CO2 DX
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data


Legacy
Model
FPI New Model BTUH Watts No. of Fans CFM m3H
LETC035
6 BEL0040*C6E^A 3,705 1,086 1 617 1,048
LETC040
LETC040
6 BEL0045*C6E^A 5,035 1,476 1 576 979
LETC047
6 BEL0065*C6E^A LETC065 6,840 2,005 2 1,234 2,096
6 BEL0080*C6E^A LETC075 7,980 2,339 2 1,234 2,096
6 BEL0100*C6E^A LETC090 9,405 2,756 2 1,153 1,959
6 BEL0130*C6E^A LETC120 12,825 3,759 3 1,850 3,144
6 BEL0155*C6E^A LETC140 15,200 4,455 3 1,729 2,938
6 BEL0170*C6E^A LETC160 17,005 4,984 4 2,467 4,192
6 BEL0205*C6E^A LETC180 19,095 5,596 4 2,306 3,918
6 BEL0240*C6E^A LETC200 21,280 6,237 5 2,882 4,897
6 BEL0255*C6E^A LETC240 25,555 7,489 6 3,701 6,288
6 BEL0310*C6E^A LETC280 29,830 8,742 6 2,459 5,876
4 BEL0045*C4E^A LLEC041 4,275 1,253 1 600 1,019
4 BEL0070*C4E^A LLEC068 7,030 2,060 2 1,283 2,180
4 BEL0090*C4E^A LLEC080 8,360 2,450 2 1,199 2,037
4 BEL0135*C4E^A LLEC102 11,495 3,369 3 1,799 3,056
4 BEL0180*C4E^A LLEC136 15,485 4,538 4 2,398 4,074
4 BEL0220*C4E^A LLEC170 18,620 5,457 5 2,998 5,093
LLEC204
4 BEL0275*C4E^A 24,605 7,211 6 3,597 6,111
LLEC235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request
† = For single speed and 2-speed EC motors, use 60 Hz capacity and airflow values. (units with EC motors operating at 50 Hz will not see a reduction in performance
due to the electronic control of the motor)

19
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Medium Temperature Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-404A/R-507A R-448A/R-449A
Application Capacity 1
Application Capacity1

507A 10°F TD/25°F SST 6°C TD/-4°F SST 10°F TD/25°F SST 6°C TD/-4°F SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
LET035
6 BEL0040*S6E^A 4,000 1,200 4,500 1,300 1 685 1,164
LET040
LET040
6 BEL0045*S6E^A 5,400 1,550 6,100 1,750 1 641 1,088
LET047
6 BEL0065*S6E^A LET065 7,450 2,150 8,300 2,400 2 1,371 2,329
6 BEL0080*S6E^A LET075 8,650 2,500 9,650 2,800 2 1,371 2,329
6 BEL0100*S6E^A LET090 10,350 3,000 11,400 3,300 2 1,281 2,176
6 BEL0130*S6E^A LET120 13,800 4,000 15,500 4,500 3 2,056 3,493
6 BEL0155*S6E^A LET140 16,100 4,650 18,400 5,300 3 1,922 3,265
6 BEL0170*S6E^A LET160 18,400 5,300 20,600 5,950 4 2,741 4,658
6 BEL0205*S6E^A LET180 20,700 6,000 23,100 6,650 4 2,562 4,353
6 BEL0240*S6E^A LET200 23,000 6,650 25,750 7,450 5 3,203 5,441
6 BEL0255*S6E^A LET240 27,600 7,950 30,950 8,950 6 4,112 6,986
6 BEL0310*S6E^A LET280 32,200 9,300 36,100 10,400 6 3,843 6,529
4 BEL0045*S4E^A LLE041 4,700 1,400 5,200 1,500 1 667 1,132
4 BEL0070*S4E^A LLE068 7,800 2,250 8,500 2,450 2 1,425 2,422
4 BEL0090*S4E^A LLE080 9,200 2,650 10,100 2,900 2 1,332 2,263
4 BEL0135*S4E^A LLE102 11,750 3,400 13,050 3,800 3 1,998 3,395
4 BEL0180*S4E^A LLE136 15,650 4,500 17,650 5,100 4 2,664 4,527
4 BEL0220*S4E^A LLE170 19,550 5,650 21,850 6,300 5 3,331 5,659
LLE204
4 BEL0275*S4E^A 27,000 7,800 29,800 8,600 6 3,997 6,790
LLE235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

20
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Medium Temperature Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-407A/R-407F R-407C
Application Capacity 1
Application Capacity1

507A 10°F TD/25°F SST 6°C TD/-4°F SST 10°F TD/25°F SST 6°C TD/-4°F SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
LET035
6 BEL0040*S6E^A 4,500 1,300 - - 1 685 1,164
LET040
LET040
6 BEL0045*S6E^A 6,100 1,750 - - 1 641 1,088
LET047
6 BEL0065*S6E^A LET065 8,300 2,400 - - 2 1,371 2,329
6 BEL0080*S6E^A LET075 9,650 2,800 - - 2 1,371 2,329
6 BEL0100*S6E^A LET090 11,400 3,300 - - 2 1,281 2,176
6 BEL0130*S6E^A LET120 15,500 4,500 - - 3 2,056 3,493
6 BEL0155*S6E^A LET140 18,400 5,300 - - 3 1,922 3,265
6 BEL0170*S6E^A LET160 20,600 5,950 - - 4 2,741 4,658
6 BEL0205*S6E^A LET180 23,100 6,650 - - 4 2,562 4,353
6 BEL0240*S6E^A LET200 25,750 7,450 - - 5 3,203 5,441
6 BEL0255*S6E^A LET240 30,950 8,950 - - 6 4,112 6,986
6 BEL0310*S6E^A LET280 36,100 10,400 - - 6 3,843 6,529
4 BEL0045*S4E^A LLE041 5,200 1,500 - - 1 667 1,132
4 BEL0070*S4E^A LLE068 8,500 2,450 - - 2 1,425 2,422
4 BEL0090*S4E^A LLE080 10,100 2,900 - - 2 1,332 2,263
4 BEL0135*S4E^A LLE102 13,050 3,800 - - 3 1,998 3,395
4 BEL0180*S4E^A LLE136 17,650 5,100 - - 4 2,664 4,527
4 BEL0220*S4E^A LLE170 21,850 6,300 - - 5 3,331 5,659
LLE204
4 BEL0275*S4E^A 29,800 8,600 - - 6 3,997 6,790
LLE235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

21
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Medium Temperature Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

CO2 DX
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data


Legacy
Model
FPI New Model BTUH Watts No. of Fans CFM m3H
LETY035
6 BEL0040*C6E^A 4,500 1,319 1 685 1,164
LETY040
LETY040
6 BEL0045*C6E^A 6,100 1,788 1 641 1,089
LETY047
6 BEL0065*C6E^A LETY065 8,300 2,432 2 1,371 2,329
6 BEL0080*C6E^A LETY075 9,650 2,828 2 1,371 2,329
6 BEL0100*C6E^A LETY090 11,400 3,341 2 1,281 2,176
6 BEL0130*C6E^A LETY120 15,500 4,543 3 2,056 3,493
6 BEL0155*C6E^A LETY140 18,400 5,393 3 1,922 3,265
6 BEL0170*C6E^A LETY160 20,600 6,037 4 2,741 4,657
6 BEL0205*C6E^A LETY180 23,100 6,770 4 2,562 4,353
6 BEL0240*C6E^A LETY200 25,750 7,547 5 3,203 5,442
6 BEL0255*C6E^A LETY240 30,950 9,071 6 4,112 6,986
6 BEL0310*C6E^A LETY280 36,100 10,580 6 3,843 6,529
4 BEL0045*C4E^A NA 5,200 1,524 1 641 1,089
4 BEL0070*C4E^A NA 8,500 2,491 2 1,425 2,421
4 BEL0090*C4E^A NA 10,100 2,960 2 1,332 2,263
4 BEL0135*C4E^A NA 13,050 3,825 3 1,998 3,395
4 BEL0180*C4E^A NA 17,650 5,173 4 2,664 4,526
4 BEL0220*C4E^A NA 21,850 6,404 5 3,331 5,659

4 BEL0275*C4E^A NA 29,800 8,734 6 3,997 6,791

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

22
SPECIFICATIONS– R-407A/R-407F
Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF

2-Speed EC Motor (Totally Enclosed) Defrost Heaters-230V Defrost Heaters-460V


507A 208-230/1/60 230/1/60 230/3/60 460/1/60
Watts Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps Total Amps
6 BEL0040*±6E^A 1/20 0.5 55 0.6 15 1,050 4.6 2.8 900 2.0
6 BEL0045*±6E^A 1/20 0.5 55 0.6 15 1,050 4.6 2.8 900 2.0
6 BEL0065*±6E^A 1/20 1.0 110 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0080*±6E^A 1/20 1.0 110 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0100*±6E^A 1/20 1.0 110 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0130*±6E^A 1/20 1.5 165 1.6 15 3,150 13.7 8.5 2,700 5.9
6 BEL0155*±6E^A 1/20 1.5 165 1.6 15 3,150 13.7 8.5 2,700 5.9
6 BEL0170*±6E^A 1/20 2.0 220 2.1 15 4,200 18.3 11.4 3,600 7.8
6 BEL0205*±6E^A 1/20 2.0 220 2.1 15 4,200 18.3 11.4 3,600 7.8
6 BEL0240*±6E^A 1/20 2.5 275 2.6 15 5,250 22.8 14.2 4,500 9.8
6 BEL0255*±6E^A 1/20 3.0 330 3.1 15 6,300 27.4 17.1 5,400 11.7
6 BEL0310*±6E^A 1/20 3.0 330 3.1 15 6,300 27.4 17.1 5,400 11.7
4 BEL0045*±4E^A 1/20 0.5 55 0.6 15 1,050 4.6 2.8 900 2.0
4 BEL0070*±4E^A 1/20 1.0 110 1.1 15 2,100 9.1 5.7 1,800 3.9
4 BEL0090*±4E^A 1/20 1.0 110 1.1 15 2,100 9.1 5.7 1,800 3.9
4 BEL0135*±4E^A 1/20 1.5 165 1.6 15 3,150 13.7 8.5 2,700 5.9
4 BEL0180*±4E^A 1/20 2.0 220 2.1 15 4,200 18.3 11.4 3,600 7.8
4 BEL0220*±4E^A 1/20 2.5 275 2.6 15 5,250 22.8 14.2 4,500 9.8
4 BEL0275*±4E^A 1/20 3.0 330 3.1 15 6,300 27.4 17.1 5,400 11.7

1-Speed EC Motor (Totally Enclosed) Defrost Heaters-230V Defrost Heaters-460V


507A 208-230/1/60 230/1/60 230/3/60 460/1/60
Watts Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps Total Amps
6 BEL0040*±6E^A 1/20 0.5 59 0.6 15 1,050 4.6 2.8 900 2.0
6 BEL0045*±6E^A 1/20 0.5 59 0.6 15 1,050 4.6 2.8 900 2.0
6 BEL0065*±6E^A 1/20 1.0 118 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0080*±6E^A 1/20 1.0 118 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0100*±6E^A 1/20 1.0 118 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0130*±6E^A 1/20 1.5 177 1.6 15 3,150 13.7 8.5 2,700 5.9
6 BEL0155*±6E^A 1/20 1.5 177 1.6 15 3,150 13.7 8.5 2,700 5.9
6 BEL0170*±6E^A 1/20 2.0 236 2.1 15 4,200 18.3 11.4 3,600 7.8
6 BEL0205*±6E^A 1/20 2.0 236 2.1 15 4,200 18.3 11.4 3,600 7.8
6 BEL0240*±6E^A 1/20 2.5 295 2.6 15 5,250 22.8 14.2 4,500 9.8
6 BEL0255*±6E^A 1/20 3.0 354 3.1 15 6,300 27.4 17.1 5,400 11.7
6 BEL0310*±6E^A 1/20 3.0 354 3.1 15 6,300 27.4 17.1 5,400 11.7
4 BEL0045*±4E^A 1/20 0.5 59 0.6 15 1,050 4.6 2.8 900 2.0
4 BEL0070*±4E^A 1/20 1.0 118 1.1 15 2,100 9.1 5.7 1,800 3.9
4 BEL0090*±4E^A 1/20 1.0 118 1.1 15 2,100 9.1 5.7 1,800 3.9
4 BEL0135*±4E^A 1/20 1.5 177 1.6 15 3,150 13.7 8.5 2,700 5.9
4 BEL0180*±4E^A 1/20 2.0 236 2.1 15 4,200 18.3 11.4 3,600 7.8
4 BEL0220*±4E^A 1/20 2.5 295 2.6 15 5,250 22.8 14.2 4,500 9.8
4 BEL0275*±4E^A 1/20 3.0 354 3.1 15 6,300 27.4 17.1 5,400 11.7

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)

23
LOW PROFILE UNIT COOLERS

SPECIFICATIONS– R-407A/R-407F
Electric Defrost- 60 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF

PSC Motor (Totally Enclosed) Defrost Heaters-230V Defrost Heaters-460V


507A 208-230/1/60 230/1/60 230/3/60 460/1/60
Watts Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps Total Amps
6 BEL0040*±6E^A 1/20 0.5 91 0.6 15 1,050 4.6 2.8 900 2.0
6 BEL0045*±6E^A 1/20 0.5 91 0.6 15 1,050 4.6 2.8 900 2.0
6 BEL0065*±6E^A 1/20 1.0 182 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0080*±6E^A 1/20 1.0 182 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0100*±6E^A 1/20 1.0 182 1.1 15 2,100 9.1 5.7 1,800 3.9
6 BEL0130*±6E^A 1/20 1.5 273 1.6 15 3,150 13.7 8.5 2,700 5.9
6 BEL0155*±6E^A 1/20 1.5 273 1.6 15 3,150 13.7 8.5 2,700 5.9
6 BEL0170*±6E^A 1/20 2.0 364 2.1 15 4,200 18.3 11.4 3,600 7.8
6 BEL0205*±6E^A 1/20 2.0 364 2.1 15 4,200 18.3 11.4 3,600 7.8
6 BEL0240*±6E^A 1/20 2.5 455 2.6 15 5,250 22.8 14.2 4,500 9.8
6 BEL0255*±6E^A 1/20 3.0 546 3.1 15 6,300 27.4 17.1 5,400 11.7
6 BEL0310*±6E^A 1/20 3.0 546 3.1 15 6,300 27.4 17.1 5,400 11.7
4 BEL0045*±4E^A 1/20 0.5 91 0.6 15 1,050 4.6 2.8 900 2.0
4 BEL0070*±4E^A 1/20 1.0 182 1.1 15 2,100 9.1 5.7 1,800 3.9
4 BEL0090*±4E^A 1/20 1.0 182 1.1 15 2,100 9.1 5.7 1,800 3.9
4 BEL0135*±4E^A 1/20 1.5 273 1.6 15 3,150 13.7 8.5 2,700 5.9
4 BEL0180*±4E^A 1/20 2.0 364 2.1 15 4,200 18.3 11.4 3,600 7.8
4 BEL0220*±4E^A 1/20 2.5 455 2.6 15 5,250 22.8 14.2 4,500 9.8
4 BEL0275*±4E^A 1/20 3.0 546 3.1 15 6,300 27.4 17.1 5,400 11.7

PSC Motor (Totally Enclosed) Defrost Heaters-230V Defrost Heaters-460V


507A 460/1/60 230/1/60 230/3/60 460/1/60
Watts Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps Total Amps
6 BEL0040*±6E^A 1/20 0.4 117 0.5 15 1,050 4.6 2.8 900 2.0
6 BEL0045*±6E^A 1/20 0.4 117 0.5 15 1,050 4.6 2.8 900 2.0
6 BEL0065*±6E^A 1/20 0.8 234 0.9 15 2,100 9.1 5.7 1,800 3.9
6 BEL0080*±6E^A 1/20 0.8 234 0.9 15 2,100 9.1 5.7 1,800 3.9
6 BEL0100*±6E^A 1/20 0.8 234 0.9 15 2,100 9.1 5.7 1,800 3.9
6 BEL0130*±6E^A 1/20 1.2 351 1.3 15 3,150 13.7 8.5 2,700 5.9
6 BEL0155*±6E^A 1/20 1.2 351 1.3 15 3,150 13.7 8.5 2,700 5.9
6 BEL0170*±6E^A 1/20 1.6 468 1.7 15 4,200 18.3 11.4 3,600 7.8
6 BEL0205*±6E^A 1/20 1.6 468 1.7 15 4,200 18.3 11.4 3,600 7.8
6 BEL0240*±6E^A 1/20 2.0 585 2.1 15 5,250 22.8 14.2 4,500 9.8
6 BEL0255*±6E^A 1/20 2.4 702 2.5 15 6,300 27.4 17.1 5,400 11.7
6 BEL0310*±6E^A 1/20 2.4 702 2.5 15 6,300 27.4 17.1 5,400 11.7
4 BEL0045*±4E^A 1/20 0.4 117 0.5 15 1,050 4.6 2.8 900 2.0
4 BEL0070*±4E^A 1/20 0.8 234 0.9 15 2,100 9.1 5.7 1,800 3.9
4 BEL0090*±4E^A 1/20 0.8 234 0.9 15 2,100 9.1 5.7 1,800 3.9
4 BEL0135*±4E^A 1/20 1.2 351 1.3 15 3,150 13.7 8.5 2,700 5.9
4 BEL0180*±4E^A 1/20 1.6 468 1.7 15 4,200 18.3 11.4 3,600 7.8
4 BEL0220*±4E^A 1/20 2.0 585 2.1 15 5,250 22.8 14.2 4,500 9.8
4 BEL0275*±4E^A 1/20 2.4 702 2.5 15 6,300 27.4 17.1 5,400 11.7

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)

24
SPECIFICATIONS– R-407A/R-407F
Electric Defrost- 50 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF

2-Speed EC Motor (Totally Enclosed) Defrost Heaters


507A 220/1/50 220/1/50
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*±6E^A 1/20 0.5 55 0.6 15 960 4.4
6 BEL0045*±6E^A 1/20 0.5 55 0.6 15 960 4.4
6 BEL0065*±6E^A 1/20 1.0 110 1.1 15 1,920 8.7
6 BEL0080*±6E^A 1/20 1.0 110 1.1 15 1,920 8.7
6 BEL0100*±6E^A 1/20 1.0 110 1.1 15 1,920 8.7
6 BEL0130*±6E^A 1/20 1.5 165 1.6 15 2,880 13.1
6 BEL0155*±6E^A 1/20 1.5 165 1.6 15 2,880 13.1
6 BEL0170*±6E^A 1/20 2.0 220 2.1 15 3,845 17.5
6 BEL0205*±6E^A 1/20 2.0 220 2.1 15 3,845 17.5
6 BEL0240*±6E^A 1/20 2.5 275 2.6 15 4,805 21.8
6 BEL0255*±6E^A 1/20 3.0 330 3.1 15 5,765 26.2
6 BEL0310*±6E^A 1/20 3.0 330 3.1 15 5,765 26.2
4 BEL0045*±4E^A 1/20 0.5 55 0.6 15 960 4.4
4 BEL0070*±4E^A 1/20 1.0 110 1.1 15 1,920 8.7
4 BEL0090*±4E^A 1/20 1.0 110 1.1 15 1,920 8.7
4 BEL0135*±4E^A 1/20 1.5 165 1.6 15 2,880 13.1
4 BEL0180*±4E^A 1/20 2.0 220 2.1 15 3,845 17.5
4 BEL0220*±4E^A 1/20 2.5 275 2.6 15 4,805 21.8
4 BEL0275*±4E^A 1/20 3.0 330 3.1 15 5,765 26.2

1-Speed EC Motor (Totally Enclosed) Defrost Heaters


507A 220/1/50 220/1/50
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*±6E^A 1/20 0.5 59 0.6 15 960 4.4
6 BEL0045*±6E^A 1/20 0.5 59 0.6 15 960 4.4
6 BEL0065*±6E^A 1/20 1.0 118 1.1 15 1,920 8.7
6 BEL0080*±6E^A 1/20 1.0 118 1.1 15 1,920 8.7
6 BEL0100*±6E^A 1/20 1.0 118 1.1 15 1,920 8.7
6 BEL0130*±6E^A 1/20 1.5 177 1.6 15 2,880 13.1
6 BEL0155*±6E^A 1/20 1.5 177 1.6 15 2,880 13.1
6 BEL0170*±6E^A 1/20 2.0 236 2.1 15 3,845 17.5
6 BEL0205*±6E^A 1/20 2.0 236 2.1 15 3,845 17.5
6 BEL0240*±6E^A 1/20 2.5 295 2.6 15 4,805 21.8
6 BEL0255*±6E^A 1/20 3.0 354 3.1 15 5,765 26.2
6 BEL0310*±6E^A 1/20 3.0 354 3.1 15 5,765 26.2
4 BEL0045*±4E^A 1/20 0.5 59 0.6 15 960 4.4
4 BEL0070*±4E^A 1/20 1.0 118 1.1 15 1,920 8.7
4 BEL0090*±4E^A 1/20 1.0 118 1.1 15 1,920 8.7
4 BEL0135*±4E^A 1/20 1.5 177 1.6 15 2,880 13.1
4 BEL0180*±4E^A 1/20 2.0 236 2.1 15 3,845 17.5
4 BEL0220*±4E^A 1/20 2.5 295 2.6 15 4,805 21.8
4 BEL0275*±4E^A 1/20 3.0 354 3.1 15 5,765 26.2

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)

25
LOW PROFILE UNIT COOLERS

SPECIFICATIONS– R-407A/R-407F
Electric Defrost- 50 Hz
Please consult AWEF table on pages 44 & 45 to confirm model meets DOE minimum AWEF

PSC Motor (Totally Enclosed) Defrost Heaters


507A 220/1/50 220/1/50
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*±6E^A 1/20 0.5 65 0.6 15 960 4.4
6 BEL0045*±6E^A 1/20 0.5 65 0.6 15 960 4.4
6 BEL0065*±6E^A 1/20 1.0 130 1.1 15 1,920 8.7
6 BEL0080*±6E^A 1/20 1.0 130 1.1 15 1,920 8.7
6 BEL0100*±6E^A 1/20 1.0 130 1.1 15 1,920 8.7
6 BEL0130*±6E^A 1/20 1.5 195 1.6 15 2,880 13.1
6 BEL0155*±6E^A 1/20 1.5 195 1.6 15 2,880 13.1
6 BEL0170*±6E^A 1/20 2.0 260 2.1 15 3,845 17.5
6 BEL0205*±6E^A 1/20 2.0 260 2.1 15 3,845 17.5
6 BEL0240*±6E^A 1/20 2.5 325 2.6 15 4,805 21.8
6 BEL0255*±6E^A 1/20 3.0 390 3.1 15 5,765 26.2
6 BEL0310*±6E^A 1/20 3.0 390 3.1 15 5,765 26.2
4 BEL0045*±4E^A 1/20 0.5 65 0.6 15 960 4.4
4 BEL0070*±4E^A 1/20 1.0 130 1.1 15 1,920 8.7
4 BEL0090*±4E^A 1/20 1.0 130 1.1 15 1,920 8.7
4 BEL0135*±4E^A 1/20 1.5 195 1.6 15 2,880 13.1
4 BEL0180*±4E^A 1/20 2.0 260 2.1 15 3,845 17.5
4 BEL0220*±4E^A 1/20 2.5 325 2.6 15 4,805 21.8
4 BEL0275*±4E^A 1/20 3.0 390 3.1 15 5,765 26.2

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
± = Refrigerant Designator (see Nomenclature details)

26
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Low Temperature Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-404A/R-507A R-448A/R-449A
Application Capacity 1
Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
HGT035
6 BEL0040*S6H^A 3,500 1,000 3,900 1,000 1 685 1,164
HGT040
HGT040
6 BEL0045*S6H^A 4,700 1,400 5,300 1,600 1 641 1,088
HGT047
6 BEL0065*S6H^A HGT065 6,500 1,900 7,200 2,100 2 1,371 2,329
6 BEL0080*S6H^A HGT075 7,500 2,200 8,400 2,500 2 1,371 2,329
6 BEL0100*S6H^A HGT090 9,000 2,600 9,900 2,900 2 1,281 2,176
6 BEL0130*S6H^A HGT120 12,000 3,500 13,500 4,000 3 2,056 3,493
6 BEL0155*S6H^A HGT140 14,000 4,100 16,000 4,700 3 1,922 3,265
6 BEL0170*S6H^A HGT160 16,000 4,700 17,900 5,200 4 2,741 4,658
6 BEL0205*S6H^A HGT180 18,000 5,300 20,100 5,900 4 2,562 4,353
6 BEL0240*S6H^A HGT200 20,000 5,900 22,800 6,600 5 3,203 5,441
6 BEL0255*S6H^A HGT240 24,000 7,000 26,900 7,900 6 4,112 6,986
6 BEL0310*S6H^A HGT280 28,000 8,200 31,400 9,200 6 3,843 6,529
4 BEL0045*S4H^A HGT041 4,100 1,200 4,500 1,300 1 667 1,132
4 BEL0070*S4H^A HGT068 6,800 2,000 7,400 2,200 2 1,425 2,422
4 BEL0090*S4H^A HGT080 8,000 2,300 8,800 2,600 2 1,332 2,263
4 BEL0135*S4H^A HGT102 10,200 3,000 12,800 3,700 3 1,998 3,395
4 BEL0180*S4H^A HGT136 13,600 4,000 17,300 5,000 4 2,664 4,527
4 BEL0220*S4H^A HGT170 17,000 5,000 19,500 5,600 5 3,331 5,659
HGT204
4 BEL0275*S4H^A 23,500 6,900 25,900 7,600 6 3,997 6,790
HGT235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

27
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Low Temperature Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-407A/R-407F R-407C
Application Capacity1 Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
HGT035
6 BEL0040*S6H^A 3,900 1,000 - - 1 685 1,164
HGT040
HGT040
6 BEL0045*S6H^A 5,300 1,600 - - 1 641 1,088
HGT047
6 BEL0065*S6H^A HGT065 7,200 2,100 - - 2 1,371 2,329
6 BEL0080*S6H^A HGT075 8,400 2,500 - - 2 1,371 2,329
6 BEL0100*S6H^A HGT090 9,900 2,900 - - 2 1,281 2,176
6 BEL0130*S6H^A HGT120 13,500 4,000 - - 3 2,056 3,493
6 BEL0155*S6H^A HGT140 16,000 4,700 - - 3 1,922 3,265
6 BEL0170*S6H^A HGT160 17,900 5,200 - - 4 2,741 4,658
6 BEL0205*S6H^A HGT180 20,100 5,900 - - 4 2,562 4,353
6 BEL0240*S6H^A HGT200 22,400 6,500 - - 5 3,203 5,441
6 BEL0255*S6H^A HGT240 26,900 7,900 - - 6 4,112 6,986
6 BEL0310*S6H^A HGT280 31,400 9,200 - - 6 3,843 6,529
4 BEL0045*S4H^A HGT041 4,500 1,300 - - 1 667 1,132
4 BEL0070*S4H^A HGT068 7,400 2,200 - - 2 1,425 2,422
4 BEL0090*S4H^A HGT080 8,800 2,600 - - 2 1,332 2,263
4 BEL0135*S4H^A HGT102 12,100 3,500 - - 3 1,998 3,395
4 BEL0180*S4H^A HGT136 16,300 4,700 - - 4 2,664 4,527
4 BEL0220*S4H^A HGT170 19,600 5,500 - - 5 3,331 5,659
HGT204
4 BEL0275*S4H^A 25,900 7,600 - - 6 3,997 6,790
HGT235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

28
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Low Temperature Hot Gas Defrost- 50 Hz (For PSC Motors) †
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-404A/R-507A R-448A/R-449A
Application Capacity1 Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
HGT035
6 BEL0040*S6H^A 3,325 950 3,705 950 1 617 1,048
HGT040
HGT040
6 BEL0045*S6H^A 4,465 1,330 5,035 1,520 1 576 979
HGT047
6 BEL0065*S6H^A HGT065 6,175 1,805 6,840 1,995 2 1,234 2,096
6 BEL0080*S6H^A HGT075 7,125 2,090 7,980 2,375 2 1,234 2,096
6 BEL0100*S6H^A HGT090 8,550 2,470 9,405 2,755 2 1,153 1,959
6 BEL0130*S6H^A HGT120 11,400 3,325 12,825 3,800 3 1,850 3,144
6 BEL0155*S6H^A HGT140 13,300 3,895 15,200 4,465 3 1,729 2,938
6 BEL0170*S6H^A HGT160 15,200 4,465 17,005 4,940 4 2,467 4,192
6 BEL0205*S6H^A HGT180 17,100 5,035 19,095 5,605 4 2,306 3,918
6 BEL0240*S6H^A HGT200 19,000 5,605 21,660 6,270 5 2,882 4,897
6 BEL0255*S6H^A HGT240 22,800 6,650 25,555 7,505 6 3,701 6,288
6 BEL0310*S6H^A HGT280 26,600 7,790 29,830 8,740 6 2,459 5,876
4 BEL0045*S4H^A HGT041 3,895 1,140 4,275 1,235 1 600 1,019
4 BEL0070*S4H^A HGT068 6,460 1,900 7,030 2,090 2 1,283 2,180
4 BEL0090*S4H^A HGT080 7,600 2,185 8,360 2,470 2 1,199 2,037
4 BEL0135*S4H^A HGT102 9,690 2,850 12,160 3,515 3 1,799 3,056
4 BEL0180*S4H^A HGT136 12,920 3,800 16,435 4,750 4 2,398 4,074
4 BEL0220*S4H^A HGT170 16,150 4,750 18,525 5,320 5 2,998 5,093
HGT204
4 BEL0275*S4H^A 22,325 6,555 24,605 7,220 6 3,597 6,111
HGT235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request
† = For single speed and 2-speed EC motors, use 60 Hz capacity and airflow values. (units with EC motors operating at 50 Hz will not see a reduction in performance
due to the electronic control of the motor)

29
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Low Temperature Hot Gas Defrost- 50 Hz (For PSC Motors) †
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-407A/R-407F R-407C
Application Capacity1 Application Capacity1

507A 10°F TD/-20°F SST 6°C TD/-29°C SST 10°F TD/-20°F SST 6°C TD/-29°C SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
HGT035
6 BEL0040*S6H^A 3,705 950 - - 1 617 1,048
HGT040
HGT040
6 BEL0045*S6H^A 5,035 1,520 - - 1 576 979
HGT047
6 BEL0065*S6H^A HGT065 6,840 1,995 - - 2 1,234 2,096
6 BEL0080*S6H^A HGT075 7,980 2,375 - - 2 1,234 2,096
6 BEL0100*S6H^A HGT090 9,405 2,755 - - 2 1,153 1,959
6 BEL0130*S6H^A HGT120 12,825 3,800 - - 3 1,850 3,144
6 BEL0155*S6H^A HGT140 15,200 4,465 - - 3 1,729 2,938
6 BEL0170*S6H^A HGT160 17,005 4,940 - - 4 2,467 4,192
6 BEL0205*S6H^A HGT180 19,095 5,605 - - 4 2,306 3,918
6 BEL0240*S6H^A HGT200 21,280 6,175 - - 5 2,882 4,897
6 BEL0255*S6H^A HGT240 25,555 7,505 - - 6 3,701 6,288
6 BEL0310*S6H^A HGT280 29,830 8,740 - - 6 2,459 5,876
4 BEL0045*S4H^A HGT041 4,275 1,235 - - 1 600 1,019
4 BEL0070*S4H^A HGT068 7,030 2,090 - - 2 1,283 2,180
4 BEL0090*S4H^A HGT080 8,360 2,470 - - 2 1,199 2,037
4 BEL0135*S4H^A HGT102 11,495 3,325 - - 3 1,799 3,056
4 BEL0180*S4H^A HGT136 15,485 4,465 - - 4 2,398 4,074
4 BEL0220*S4H^A HGT170 18,620 5,225 - - 5 2,998 5,093
HGT204
4 BEL0275*S4H^A 24,605 7,220 - - 6 3,597 6,111
HGT235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request
† = For single speed and 2-speed EC motors, use 60 Hz capacity and airflow values. (units with EC motors operating at 50 Hz will not see a reduction in performance
due to the electronic control of the motor)

30
PERFORMANCE DATA – R-404A/R-507A
Application Capacity: Medium Temperature Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-404A/R-507A R-448A/R-449A
Application Capacity 1
Application Capacity1

507A 10°F TD/25°F SST 6°C TD/-4°F SST 10°F TD/25°F SST 6°C TD/-4°F SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
HGT035
6 BEL0040*S6H^A 4,000 1,200 4,500 1,300 1 685 1,164
HGT040
HGT040
6 BEL0045*S6H^A 5,400 1,550 6,100 1,750 1 641 1,088
HGT047
6 BEL0065*S6H^A HGT065 7,450 2,150 8,300 2,400 2 1,371 2,329
6 BEL0080*S6H^A HGT075 8,650 2,500 9,650 2,800 2 1,371 2,329
6 BEL0100*S6H^A HGT090 10,350 3,000 11,400 3,300 2 1,281 2,176
6 BEL0130*S6H^A HGT120 13,800 4,000 15,500 4,500 3 2,056 3,493
6 BEL0155*S6H^A HGT140 16,100 4,650 18,400 5,300 3 1,922 3,265
6 BEL0170*S6H^A HGT160 18,400 5,300 20,600 5,950 4 2,741 4,658
6 BEL0205*S6H^A HGT180 20,700 6,000 23,100 6,650 4 2,562 4,353
6 BEL0240*S6H^A HGT200 23,000 6,650 25,750 7,450 5 3,203 5,441
6 BEL0255*S6H^A HGT240 27,600 7,950 30,950 8,950 6 4,112 6,986
6 BEL0310*S6H^A HGT280 32,200 9,300 36,100 10,400 6 3,843 6,529
4 BEL0045*S4H^A HGT041 4,700 1,400 5,200 1,500 1 667 1,132
4 BEL0070*S4H^A HGT068 7,800 2,250 8,500 2,450 2 1,425 2,422
4 BEL0090*S4H^A HGT080 9,200 2,650 10,100 2,900 2 1,332 2,263
4 BEL0135*S4H^A HGT102 11,750 3,400 13,050 3,800 3 1,998 3,395
4 BEL0180*S4H^A HGT136 15,650 4,500 17,650 5,100 4 2,664 4,527
4 BEL0220*S4H^A HGT170 19,550 5,650 21,850 6,300 5 3,331 5,659
HGT204
4 BEL0275*S4H^A 27,000 7,800 29,800 8,600 6 3,997 6,790
HGT235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

31
LOW PROFILE UNIT COOLERS

PERFORMANCE DATA – R-404A/R-507A


Application Capacity: Medium Temperature Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF
Please refer to Table 1: Capacity Correction Factors (page 6) if using Saturated Suction Temperatures different than listed in the
information below

R-407A/R-407F R-407C
Application Capacity 1
Application Capacity1

507A 10°F TD/25°F SST 6°C TD/-4°F SST 10°F TD/25°F SST 6°C TD/-4°F SST Fan Data
Legacy
Model No. of
FPI New Model BTUH Watts BTUH Watts CFM m3H
Fans
HGT035
6 BEL0040*S6H^A 4,500 1,300 - - 1 685 1,164
HGT040
HGT040
6 BEL0045*S6H^A 6,100 1,750 - - 1 641 1,088
HGT047
6 BEL0065*S6H^A HGT065 8,300 2,400 - - 2 1,371 2,329
6 BEL0080*S6H^A HGT075 9,650 2,800 - - 2 1,371 2,329
6 BEL0100*S6H^A HGT090 11,400 3,300 - - 2 1,281 2,176
6 BEL0130*S6H^A HGT120 15,500 4,500 - - 3 2,056 3,493
6 BEL0155*S6H^A HGT140 18,400 5,300 - - 3 1,922 3,265
6 BEL0170*S6H^A HGT160 20,600 5,950 - - 4 2,741 4,658
6 BEL0205*S6H^A HGT180 23,100 6,650 - - 4 2,562 4,353
6 BEL0240*S6H^A HGT200 25,750 7,450 - - 5 3,203 5,441
6 BEL0255*S6H^A HGT240 30,950 8,950 - - 6 4,112 6,986
6 BEL0310*S6H^A HGT280 36,100 10,400 - - 6 3,843 6,529
4 BEL0045*S4H^A HGT041 5,200 1,500 - - 1 667 1,132
4 BEL0070*S4H^A HGT068 8,500 2,450 - - 2 1,425 2,422
4 BEL0090*S4H^A HGT080 10,100 2,900 - - 2 1,332 2,263
4 BEL0135*S4H^A HGT102 13,050 3,800 - - 3 1,998 3,395
4 BEL0180*S4H^A HGT136 17,650 5,100 - - 4 2,664 4,527
4 BEL0220*S4H^A HGT170 21,850 6,300 - - 5 3,331 5,659
HGT204
4 BEL0275*S4H^A 29,800 8,600 - - 6 3,997 6,790
HGT235

Notes:
1 = Capacities shown are Application Capacities reflecting nominal operation at 10°F TD. For models within the scope of the DOE AWEF (Annual Walk-in Energy Factor) standard, the

Net Capacity is determined by the AHRI 1250 test method. DOE will publish this compliance data at www.regulations.doe.gov
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
Net Capacity is available upon request

32
SPECIFICATIONS – R-404A/R-507A
Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF

2-Speed EC Motor (Totally Enclosed) Drain Pan Heaters


507A 115/1/60 115/1/60 230/1/60 460/1/60
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.9 55 1.1 20 150 1.3 0.7 0.3
6 BEL0045*S6H^A 1/20 0.9 55 1.1 20 150 1.3 0.7 0.3
6 BEL0065*S6H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
6 BEL0080*S6H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
6 BEL0100*S6H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
6 BEL0130*S6H^A 1/20 2.7 165 2.9 20 450 3.9 2.0 1.0
6 BEL0155*S6H^A 1/20 2.7 165 2.9 20 450 3.9 2.0 1.0
6 BEL0170*S6H^A 1/20 3.6 220 3.8 20 600 5.2 2.6 1.3
6 BEL0205*S6H^A 1/20 3.6 220 3.8 20 600 5.2 2.6 1.3
6 BEL0240*S6H^A 1/20 4.5 275 4.7 20 750 6.5 3.3 1.6
6 BEL0255*S6H^A 1/20 5.4 330 5.6 20 900 7.8 3.9 2.0
6 BEL0310*S6H^A 1/20 5.4 330 5.6 20 900 7.8 3.9 2.0
4 BEL0045*S4H^A 1/20 0.9 55 1.1 20 150 1.3 0.7 0.3
4 BEL0070*S4H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
4 BEL0090*S4H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
4 BEL0135*S4H^A 1/20 2.7 165 2.9 20 450 3.9 2.0 1.0
4 BEL0180*S4H^A 1/20 3.6 220 3.8 20 600 5.2 2.6 1.3
4 BEL0220*S4H^A 1/20 4.5 275 4.7 20 750 6.5 3.3 1.6
4 BEL0275*S4H^A 1/20 5.4 330 5.6 20 900 7.8 3.9 2.0

2-Speed EC Motor (Totally Enclosed) Drain Pan Heaters


507A 208-230/1/60 115/1/60 230/1/60 460/1/60
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.5 55 0.6 15 150 1.3 0.7 0.3
6 BEL0045*S6H^A 1/20 0.5 55 0.6 15 150 1.3 0.7 0.3
6 BEL0065*S6H^A 1/20 1.0 110 1.1 15 300 2.6 1.3 0.7
6 BEL0080*S6H^A 1/20 1.0 110 1.1 15 300 2.6 1.3 0.7
6 BEL0100*S6H^A 1/20 1.0 110 1.1 15 300 2.6 1.3 0.7
6 BEL0130*S6H^A 1/20 1.4 165 1.6 15 450 3.9 2.0 1.0
6 BEL0155*S6H^A 1/20 1.4 165 1.6 15 450 3.9 2.0 1.0
6 BEL0170*S6H^A 1/20 1.9 220 2.1 15 600 5.2 2.6 1.3
6 BEL0205*S6H^A 1/20 1.9 220 2.1 15 600 5.2 2.6 1.3
6 BEL0240*S6H^A 1/20 2.4 275 2.6 15 750 6.5 3.3 1.6
6 BEL0255*S6H^A 1/20 2.9 330 3.1 15 900 7.8 3.9 2.0
6 BEL0310*S6H^A 1/20 2.9 330 3.1 15 900 7.8 3.9 2.0
4 BEL0045*S4H^A 1/20 0.5 55 0.6 15 150 1.3 0.7 0.3
4 BEL0070*S4H^A 1/20 1.0 110 1.1 15 300 2.6 1.3 0.7
4 BEL0090*S4H^A 1/20 1.0 110 1.1 15 300 2.6 1.3 0.7
4 BEL0135*S4H^A 1/20 1.4 165 1.6 15 450 3.9 2.0 1.0
4 BEL0180*S4H^A 1/20 1.9 220 2.1 15 600 5.2 2.6 1.3
4 BEL0220*S4H^A 1/20 2.4 275 2.6 15 750 6.5 3.3 1.6
4 BEL0275*S4H^A 1/20 2.9 330 3.1 15 900 7.8 3.9 2.0

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)

33
LOW PROFILE UNIT COOLERS

SPECIFICATIONS – R-404A/R-507A
Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF

1-Speed EC Motor (Totally Enclosed) Drain Pan Heaters


507A 115/1/60 115/1/60 230/1/60 460/1/60
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.9 55 1.1 20 150 1.3 0.7 0.3
6 BEL0045*S6H^A 1/20 0.9 55 1.1 20 150 1.3 0.7 0.3
6 BEL0065*S6H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
6 BEL0080*S6H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
6 BEL0100*S6H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
6 BEL0130*S6H^A 1/20 2.7 165 2.9 20 450 3.9 2.0 1.0
6 BEL0155*S6H^A 1/20 2.7 165 2.9 20 450 3.9 2.0 1.0
6 BEL0170*S6H^A 1/20 3.6 220 3.8 20 600 5.2 2.6 1.3
6 BEL0205*S6H^A 1/20 3.6 220 3.8 20 600 5.2 2.6 1.3
6 BEL0240*S6H^A 1/20 4.5 270 4.7 20 750 6.5 3.3 1.6
6 BEL0255*S6H^A 1/20 5.4 330 5.6 20 900 7.8 3.9 2.0
6 BEL0310*S6H^A 1/20 5.4 330 5.6 20 900 7.8 3.9 2.0
4 BEL0045*S4H^A 1/20 0.9 55 1.1 20 150 1.3 0.7 0.3
4 BEL0070*S4H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
4 BEL0090*S4H^A 1/20 1.8 110 2.0 20 300 2.6 1.3 0.7
4 BEL0135*S4H^A 1/20 2.7 165 2.9 20 450 3.9 2.0 1.0
4 BEL0180*S4H^A 1/20 3.6 220 3.8 20 600 5.2 2.6 1.3
4 BEL0220*S4H^A 1/20 4.5 275 4.7 20 750 6.5 3.3 1.6
4 BEL0275*S4H^A 1/20 5.4 330 5.6 20 900 7.8 3.9 2.0

1-Speed EC Motor (Totally Enclosed) Drain Pan Heaters


507A 208-230/1/60 115/1/60 230/1/60 460/1/60
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.5 59 0.6 15 150 1.3 0.7 0.3
6 BEL0045*S6H^A 1/20 0.5 59 0.6 15 150 1.3 0.7 0.3
6 BEL0065*S6H^A 1/20 1.0 118 1.1 15 300 2.6 1.3 0.7
6 BEL0080*S6H^A 1/20 1.0 118 1.1 15 300 2.6 1.3 0.7
6 BEL0100*S6H^A 1/20 1.0 118 1.1 15 300 2.6 1.3 0.7
6 BEL0130*S6H^A 1/20 1.5 177 1.6 15 450 3.9 2.0 1.0
6 BEL0155*S6H^A 1/20 1.5 177 1.6 15 450 3.9 2.0 1.0
6 BEL0170*S6H^A 1/20 2.0 236 2.1 15 600 5.2 2.6 1.3
6 BEL0205*S6H^A 1/20 2.0 236 2.1 15 600 5.2 2.6 1.3
6 BEL0240*S6H^A 1/20 2.5 295 2.6 15 750 6.5 3.3 1.6
6 BEL0255*S6H^A 1/20 3.0 354 3.1 15 900 7.8 3.9 2.0
6 BEL0310*S6H^A 1/20 3.0 354 3.1 15 900 7.8 3.9 2.0
4 BEL0045*S4H^A 1/20 0.5 59 0.6 15 150 1.3 0.7 0.3
4 BEL0070*S4H^A 1/20 1.0 118 1.1 15 300 2.6 1.3 0.7
4 BEL0090*S4H^A 1/20 1.0 118 1.1 15 300 2.6 1.3 0.7
4 BEL0135*S4H^A 1/20 1.5 177 1.6 15 450 3.9 2.0 1.0
4 BEL0180*S4H^A 1/20 2.0 236 2.1 15 600 5.2 2.6 1.3
4 BEL0220*S4H^A 1/20 2.5 295 2.6 15 750 6.5 3.3 1.6
4 BEL0275*S4H^A 1/20 3.0 354 3.1 15 900 7.8 3.9 2.0

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)

34
SPECIFICATIONS – R-404A/R-507A
Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF

PSC Motor (Totally Enclosed) Drain Pan Heaters


507A 115/1/60 115/1/60 230/1/60 460/1/60
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 1.0 82 1.3 20 150 1.3 0.7 0.3
6 BEL0045*S6H^A 1/20 1.0 82 1.3 20 150 1.3 0.7 0.3
6 BEL0065*S6H^A 1/20 2.0 164 2.3 20 300 2.6 1.3 0.7
6 BEL0080*S6H^A 1/20 2.0 164 2.3 20 300 2.6 1.3 0.7
6 BEL0100*S6H^A 1/20 2.0 164 2.3 20 300 2.6 1.3 0.7
6 BEL0130*S6H^A 1/20 3.0 246 3.3 20 450 3.9 2.0 1.0
6 BEL0155*S6H^A 1/20 3.0 246 3.3 20 450 3.9 2.0 1.0
6 BEL0170*S6H^A 1/20 4.0 328 4.3 20 600 5.2 2.6 1.3
6 BEL0205*S6H^A 1/20 4.0 328 4.3 20 600 5.2 2.6 1.3
6 BEL0240*S6H^A 1/20 5.0 410 5.3 20 750 6.5 3.3 1.6
6 BEL0255*S6H^A 1/20 6.0 492 6.3 20 900 7.8 3.9 2.0
6 BEL0310*S6H^A 1/20 6.0 492 6.3 20 900 7.8 3.9 2.0
4 BEL0045*S4H^A 1/20 1.0 82 1.3 20 150 1.3 0.7 0.3
4 BEL0070*S4H^A 1/20 2.0 164 2.3 20 300 2.6 1.3 0.7
4 BEL0090*S4H^A 1/20 2.0 164 2.3 20 300 2.6 1.3 0.7
4 BEL0135*S4H^A 1/20 3.0 246 3.3 20 450 3.9 2.0 1.0
4 BEL0180*S4H^A 1/20 4.0 328 4.3 20 600 5.2 2.6 1.3
4 BEL0220*S4H^A 1/20 5.0 410 5.3 20 750 6.5 3.3 1.6
4 BEL0275*S4H^A 1/20 6.0 492 6.3 20 900 7.8 3.9 2.0

PSC Motor (Totally Enclosed) Drain Pan Heaters


507A 208-230/1/60 115/1/60 230/1/60 460/1/60
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.5 91 0.6 15 150 1.3 0.7 0.3
6 BEL0045*S6H^A 1/20 0.5 91 0.6 15 150 1.3 0.7 0.3
6 BEL0065*S6H^A 1/20 1.0 182 1.1 15 300 2.6 1.3 0.7
6 BEL0080*S6H^A 1/20 1.0 182 1.1 15 300 2.6 1.3 0.7
6 BEL0100*S6H^A 1/20 1.0 182 1.1 15 300 2.6 1.3 0.7
6 BEL0130*S6H^A 1/20 1.5 273 1.6 15 450 3.9 2.0 1.0
6 BEL0155*S6H^A 1/20 1.5 273 1.6 15 450 3.9 2.0 1.0
6 BEL0170*S6H^A 1/20 2.0 364 2.1 15 600 5.2 2.6 1.3
6 BEL0205*S6H^A 1/20 2.0 364 2.1 15 600 5.2 2.6 1.3
6 BEL0240*S6H^A 1/20 2.5 455 2.6 15 750 6.5 3.3 1.6
6 BEL0255*S6H^A 1/20 3.0 546 3.1 15 900 7.8 3.9 2.0
6 BEL0310*S6H^A 1/20 3.0 546 3.1 15 900 7.8 3.9 2.0
4 BEL0045*S4H^A 1/20 0.5 91 0.6 15 150 1.3 0.7 0.3
4 BEL0070*S4H^A 1/20 1.0 182 1.1 15 300 2.6 1.3 0.7
4 BEL0090*S4H^A 1/20 1.0 182 1.1 15 300 2.6 1.3 0.7
4 BEL0135*S4H^A 1/20 1.5 273 1.6 15 450 3.9 2.0 1.0
4 BEL0180*S4H^A 1/20 2.0 364 2.1 15 600 5.2 2.6 1.3
4 BEL0220*S4H^A 1/20 2.5 455 2.6 15 750 6.5 3.3 1.6
4 BEL0275*S4H^A 1/20 3.0 546 3.1 15 900 7.8 3.9 2.0

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)

35
LOW PROFILE UNIT COOLERS

SPECIFICATIONS – R-404A/R-507A
Hot Gas Defrost- 60 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF

PSC Motor (Totally Enclosed) Drain Pan Heaters


507A 460/1/60 115/1/60 230/1/60 460/1/60
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.4 117 0.5 15 150 1.3 0.7 0.3
6 BEL0045*S6H^A 1/20 0.4 117 0.5 15 150 1.3 0.7 0.3
6 BEL0065*S6H^A 1/20 0.8 234 0.9 15 300 2.6 1.3 0.7
6 BEL0080*S6H^A 1/20 0.8 234 0.9 15 300 2.6 1.3 0.7
6 BEL0100*S6H^A 1/20 0.8 234 0.9 15 300 2.6 1.3 0.7
6 BEL0130*S6H^A 1/20 1.2 351 1.3 15 450 3.9 2.0 1.0
6 BEL0155*S6H^A 1/20 1.2 351 1.3 15 450 3.9 2.0 1.0
6 BEL0170*S6H^A 1/20 1.6 468 1.7 15 600 5.2 2.6 1.3
6 BEL0205*S6H^A 1/20 1.6 468 1.7 15 600 5.2 2.6 1.3
6 BEL0240*S6H^A 1/20 2.0 585 2.1 15 750 6.5 3.3 1.6
6 BEL0255*S6H^A 1/20 2.4 702 2.5 15 900 7.8 3.9 2.0
6 BEL0310*S6H^A 1/20 2.4 702 2.5 15 900 7.8 3.9 2.0
4 BEL0045*S4H^A 1/20 0.4 117 0.5 15 150 1.3 0.7 0.3
4 BEL0070*S4H^A 1/20 0.8 234 0.9 15 300 2.6 1.3 0.7
4 BEL0090*S4H^A 1/20 0.8 234 0.9 15 300 2.6 1.3 0.7
4 BEL0135*S4H^A 1/20 1.2 351 1.3 15 450 3.9 2.0 1.0
4 BEL0180*S4H^A 1/20 1.6 468 1.7 15 600 5.2 2.6 1.3
4 BEL0220*S4H^A 1/20 2.0 585 2.1 15 750 6.5 3.3 1.6
4 BEL0275*S4H^A 1/20 2.4 702 2.5 15 900 7.8 3.9 2.0

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)

36
SPECIFICATIONS – R-404A/R-507A
Hot Gas Defrost- 50 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF

2-Speed EC Motor (Totally Enclosed) Drain Pan Heaters


507A 220/1/50 220/1/50
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.5 55 0.6 15 135 0.6
6 BEL0045*S6H^A 1/20 0.5 55 0.6 15 135 0.6
6 BEL0065*S6H^A 1/20 1.0 110 1.1 15 275 1.2
6 BEL0080*S6H^A 1/20 1.0 110 1.1 15 275 1.2
6 BEL0100*S6H^A 1/20 1.0 110 1.1 15 275 1.2
6 BEL0130*S6H^A 1/20 1.5 165 1.6 15 410 1.9
6 BEL0155*S6H^A 1/20 1.5 165 1.6 15 410 1.9
6 BEL0170*S6H^A 1/20 2.0 220 2.1 15 550 2.5
6 BEL0205*S6H^A 1/20 2.0 220 2.1 15 550 2.5
6 BEL0240*S6H^A 1/20 2.5 275 2.6 15 690 3.1
6 BEL0255*S6H^A 1/20 3.0 330 3.1 15 825 3.7
6 BEL0310*S6H^A 1/20 3.0 330 3.1 15 825 3.7
4 BEL0045*S4H^A 1/20 0.5 55 0.6 15 135 0.6
4 BEL0070*S4H^A 1/20 1.0 110 1.1 15 275 1.2
4 BEL0090*S4H^A 1/20 1.0 110 1.1 15 275 1.2
4 BEL0135*S4H^A 1/20 1.5 165 1.6 15 410 1.9
4 BEL0180*S4H^A 1/20 2.0 220 2.1 15 550 2.5
4 BEL0220*S4H^A 1/20 2.5 275 2.6 15 690 3.1
4 BEL0275*S4H^A 1/20 3.0 330 3.1 15 825 3.7

1-Speed EC Motor (Totally Enclosed) Drain Pan Heaters


507A 220/1/50 220/1/50
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.5 59 0.6 15 135 0.6
6 BEL0045*S6H^A 1/20 0.5 59 0.6 15 135 0.6
6 BEL0065*S6H^A 1/20 1.0 118 1.1 15 275 1.2
6 BEL0080*S6H^A 1/20 1.0 118 1.1 15 275 1.2
6 BEL0100*S6H^A 1/20 1.0 118 1.1 15 275 1.2
6 BEL0130*S6H^A 1/20 1.5 177 1.6 15 410 1.9
6 BEL0155*S6H^A 1/20 1.5 177 1.6 15 410 1.9
6 BEL0170*S6H^A 1/20 2.0 236 2.1 15 550 2.5
6 BEL0205*S6H^A 1/20 2.0 236 2.1 15 550 2.5
6 BEL0240*S6H^A 1/20 2.5 295 2.6 15 690 3.1
6 BEL0255*S6H^A 1/20 3.0 354 3.1 15 825 3.7
6 BEL0310*S6H^A 1/20 3.0 354 3.1 15 825 3.7
4 BEL0045*S4H^A 1/20 0.5 59 0.6 15 135 0.6
4 BEL0070*S4H^A 1/20 1.0 118 1.1 15 275 1.2
4 BEL0090*S4H^A 1/20 1.0 118 1.1 15 275 1.2
4 BEL0135*S4H^A 1/20 1.5 177 1.6 15 410 1.9
4 BEL0180*S4H^A 1/20 2.0 236 2.1 15 550 2.5
4 BEL0220*S4H^A 1/20 2.5 295 2.6 15 690 3.1
4 BEL0275*S4H^A 1/20 3.0 354 3.1 15 825 3.7

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)

37
LOW PROFILE UNIT COOLERS

SPECIFICATIONS – R-404A/R-507A
Hot Gas Defrost- 50 Hz
Please consult AWEF table on pages 46 & 47 to confirm model meets DOE minimum AWEF

PSC Motor (Totally Enclosed) Drain Pan Heaters


507A 220/1/50 220/1/50
Watts
FPI New Model HP Amps Watts MCA MOPD Total Amps
6 BEL0040*S6H^A 1/20 0.5 65 0.6 15 135 0.6
6 BEL0045*S6H^A 1/20 0.5 65 0.6 15 135 0.6
6 BEL0065*S6H^A 1/20 1.0 130 1.1 15 275 1.2
6 BEL0080*S6H^A 1/20 1.0 130 1.1 15 275 1.2
6 BEL0100*S6H^A 1/20 1.0 130 1.1 15 275 1.2
6 BEL0130*S6H^A 1/20 1.5 195 1.6 15 410 1.9
6 BEL0155*S6H^A 1/20 1.5 195 1.6 15 410 1.9
6 BEL0170*S6H^A 1/20 2.0 260 2.1 15 550 2.5
6 BEL0205*S6H^A 1/20 2.0 260 2.1 15 550 2.5
6 BEL0240*S6H^A 1/20 2.5 325 2.6 15 690 3.1
6 BEL0255*S6H^A 1/20 3.0 390 3.1 15 825 3.7
6 BEL0310*S6H^A 1/20 3.0 390 3.1 15 825 3.7
4 BEL0045*S4H^A 1/20 0.5 65 0.6 15 135 0.6
4 BEL0070*S4H^A 1/20 1.0 130 1.1 15 275 1.2
4 BEL0090*S4H^A 1/20 1.0 130 1.1 15 275 1.2
4 BEL0135*S4H^A 1/20 1.5 195 1.6 15 410 1.9
4 BEL0180*S4H^A 1/20 2.0 260 2.1 15 550 2.5
4 BEL0220*S4H^A 1/20 2.5 325 2.6 15 690 3.1
4 BEL0275*S4H^A 1/20 3.0 390 3.1 15 825 3.7

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)

38
PHYSICAL DATA – R-404A/R-507A
Electric Defrost
Air Defrost (R-404A/R-507A, R-448A/R-449A, R-407A/R-407F, R-407C)
507A 220/1/50 Approx. Net Weight

Model No. of Fans Coil Inlet OD Suction OD Equalizer OD Drain MPT Lbs. Kg

BEL0045*S6A^A 1 1/2 1/2 1/4 3/4 33 15


BEL0055*S6A^A 1 1/2 5/8 1/4 3/4 36 16
BEL0060*S6A^A 1 1/2 5/8 1/4 3/4 36 16
BEL0095*S6A^A 2 1/2 5/8 1/4 3/4 51 23
BEL0105*S6A^A 2 1/2 5/8 1/4 3/4 52 24
BEL0115*S6A^A 2 1/2 7/8 1/4 3/4 56 26
BEL0125*S6A^A 2 1/2 7/8 1/4 3/4 56 26
BEL0155*S6A^A 3 1/2 7/8 1/4 3/4 67 30
BEL0190*S6A^A 3 1/2 7/8 1/4 3/4 73 33
BEL0250*S6A^A 4 1/2 7/8 1/4 3/4 94 43
BEL0295*S6A^A 5 1/2 7/8 1/4 3/4 115 52
BEL0350*S6A^A 6 1/2 1-1/8 1/4 3/4 133 60
BEL0380*S6A^A 6 1/2 1-1/8 1/4 3/4 137 62

Air Defrost (CO2 DX)


507A 220/1/50 Approx. Net Weight

Model No. of Fans Coil Inlet 2 Suction OD 2 Drain MPT Lbs. Kg

BEL0045*C6A^A 1 3/8 3/8 3/4 33 15


BEL0055*C6A^A 1 3/8 3/8 3/4 36 16
BEL0060*C6A^A 1 3/8 3/8 3/4 36 16
BEL0095*C6A^A 2 3/8 3/8 3/4 51 23
BEL0105*C6A^A 2 3/8 3/8 3/4 52 24
BEL0115*C6A^A 2 3/8 3/8 3/4 56 26
BEL0125*C6A^A 2 3/8 3/8 3/4 56 26
BEL0155*C6A^A 3 3/8 3/8 3/4 67 30
BEL0190*C6A^A 3 3/8 3/8 3/4 73 33
BEL0250*C6A^A 4 3/8 1/2 3/4 94 43
BEL0295*C6A^A 5 3/8 1/2 3/4 115 52
BEL0350*C6A^A 6 3/8 1/2 3/4 133 60
BEL0380*C6A^A 6 1/2 5/8 3/4 137 62

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
2
= Connection sizes may vary, if TD is lesser or greater than 10⁰F

39
LOW PROFILE UNIT COOLERS

PHYSICAL DATA – R-404A/R-507A


Electric Defrost (R-404A/R-507A, R-448A/R-449A, R-407A/R-407F, R-407C)
507A 220/1/50 Approx. Net Weight
No. of
FPI Model Coil Inlet OD Suction OD Equalizer OD Drain MPT Lbs. Kg
Fans
6 BEL0040*S6E^A 1 1/2 5/8 1/4 3/4 36 16
6 BEL0045*S6E^A 1 1/2 5/8 1/4 3/4 38 17
6 BEL0065*S6E^A 2 1/2 5/8 1/4 3/4 54 24
6 BEL0080*S6E^A 2 1/2 5/8 1/4 3/4 54 24
6 BEL0100*S6E^A 2 1/2 7/8 1/4 3/4 59 27
6 BEL0130*S6E^A 3 1/2 7/8 1/4 3/4 71 32
6 BEL0155*S6E^A 3 1/2 1-1/8 1/4 3/4 78 35
6 BEL0170*S6E^A 4 1/2 7/8 1/4 3/4 91 41
6 BEL0205*S6E^A 4 1/2 1-1/8 1/4 3/4 100 45
6 BEL0240*S6E^A 5 1/2 1-1/8 1/4 3/4 120 54
6 BEL0255*S6E^A 6 1/2 1-1/8 1/4 3/4 134 61
6 BEL0310*S6E^A 6 1/2 1-1/8 1/4 3/4 146 66
4 BEL0045*S4E^A 1 1/2 5/8 1/4 3/4 38 17
4 BEL0070*S4E^A 2 1/2 5/8 1/4 3/4 53 24
4 BEL0090*S4E^A 2 1/2 7/8 1/4 3/4 59 27
4 BEL0135*S4E^A 3 1/2 7/8 1/4 3/4 77 35
4 BEL0180*S4E^A 4 1/2 1-1/8 1/4 3/4 100 45
4 BEL0220*S4E^A 5 1/2 1-1/8 1/4 3/4 119 54
4 BEL0275*S4E^A 6 1/2 1-1/8 1/4 3/4 142 64

Electric507A
Defrost (CO2 DX) 220/1/50 Approx. Net Weight
No. of
FPI Model Coil Inlet 2 Suction OD 2 Drain MPT Lbs. Kg
Fans
6 BEL0040*C6E^A 1 3/8 3/8 3/4 36 16
6 BEL0045*C6E^A 1 3/8 3/8 3/4 38 17
6 BEL0065*C6E^A 2 3/8 3/8 3/4 54 24
6 BEL0080*C6E^A 2 3/8 1/2 3/4 54 24
6 BEL0100*C6E^A 2 3/8 1/2 3/4 59 27
6 BEL0130*C6E^A 3 3/8 1/2 3/4 71 32
6 BEL0155*C6E^A 3 3/8 1/2 3/4 78 35
6 BEL0170*C6E^A 4 3/8 1/2 3/4 91 41
6 BEL0205*C6E^A 4 3/8 1/2 3/4 100 45
6 BEL0240*C6E^A 5 3/8 5/8 3/4 120 54
6 BEL0255*C6E^A 6 3/8 5/8 3/4 134 61
6 BEL0310*C6E^A 6 3/8 5/8 3/4 146 66
4 BEL0045*C4E^A 1 3/8 3/8 3/4 38 17
4 BEL0070*C4E^A 2 3/8 3/8 3/4 53 24
4 BEL0090*C4E^A 2 3/8 1/2 3/4 59 27
4 BEL0135*C4E^A 3 3/8 1/2 3/4 77 35
4 BEL0180*C4E^A 4 3/8 1/2 3/4 100 45
4 BEL0220*C4E^A 5 3/8 1/2 3/4 119 54
4 BEL0275*C4E^A 6 3/8 5/8 3/4 142 64

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)
2
= Connection sizes may vary, if TD is lesser or greater than 10⁰F

40
PHYSICAL DATA – R-404A/R-507A
Electric Defrost
Hot Gas Defrost
507A 220/1/50 Approx. Net Weight
No. of Coil Inlet Suction Equalizer Drain Side Port Hot Gas Pan
FPI Model Lbs. Kg
Fans OD OD OD MPT OD Connection OD
6 BEL0040*S6H^A 1 1/2 5/8 1/4 3/4 1/2 5/8 38 17
6 BEL0045*S6H^A 1 1/2 5/8 1/4 3/4 1/2 5/8 40 18
6 BEL0065*S6H^A 2 1/2 5/8 1/4 3/4 1/2 5/8 56 25
6 BEL0080*S6H^A 2 1/2 5/8 1/4 3/4 1/2 5/8 56 25
6 BEL0100*S6H^A 2 1/2 7/8 1/4 3/4 1/2 5/8 61 27
6 BEL0130*S6H^A 3 1/2 7/8 1/4 3/4 1/2 5/8 73 33
6 BEL0155*S6H^A 3 1/2 1-1/8 1/4 3/4 1/2 5/8 80 36
6 BEL0170*S6H^A 4 1/2 7/8 1/4 3/4 1/2 5/8 93 42
6 BEL0205*S6H^A 4 1/2 1-1/8 1/4 3/4 1/2 5/8 102 46
6 BEL0240*S6H^A 5 1/2 1-1/8 1/4 3/4 1/2 5/8 122 55
6 BEL0255*S6H^A 6 1/2 1-1/8 1/4 3/4 1/2 5/8 136 62
6 BEL0310*S6H^A 6 1/2 1-1/8 1/4 3/4 1/2 5/8 148 67
4 BEL0045*S4H^A 1 1/2 5/8 1/4 3/4 1/2 5/8 40 18
4 BEL0070*S4H^A 2 1/2 5/8 1/4 3/4 1/2 5/8 55 25
4 BEL0090*S4H^A 2 1/2 7/8 1/4 3/4 1/2 5/8 61 28
4 BEL0135*S4H^A 3 1/2 7/8 1/4 3/4 1/2 5/8 79 36
4 BEL0180*S4H^A 4 1/2 1-1/8 1/4 3/4 1/2 5/8 102 46
4 BEL0220*S4H^A 5 1/2 1-1/8 1/4 3/4 1/2 5/8 121 55
4 BEL0275*S4H^A 6 1/2 1-1/8 1/4 3/4 1/2 5/8 144 65

Notes:
* = Electrical Code Designator (see Nomenclature details)
^ = Motor Code Designator (see Nomenclature details)

41
LOW PROFILE UNIT COOLERS

DIMENSIONAL DRAWINGS

No. of A B C D
Fans in. mm in. mm in. mm in. mm
1 29.5 749 17.25 438 - - - -

2 45.5 1,156 33.25 845 - - - -

3 61.5 1,562 49.25 1,251 - - - -

4 77.5 1,969 65.25 1,657 - - - -

5 93.5 2,375 81.25 2,064 48.63 1,235 32.63 829

6 109.5 2,781 97.25 2,470 48.63 1,235 48.63 1,235

Note:
Hanger brackets will accept 3/8” / 9.5 mm hanger rods

42
DOE Rated AWEF
AWEF DATA
Air Defrost - 2-Speed EC Motors

Air Defrost/2-Speed EC Motors


Cooler

FPI Model R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F R-407C CO2 DX

AWEF AWEF AWEF AWEF AWEF

6 BEL0045*±6AMA 9.00 9.00 9.00 9.00 9.00


6 BEL0055*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0060*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0095*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0105*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0115*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0125*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0155*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0190*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0250*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0295*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0350*±6AMA 9.00 9.00 9.00 9.00 9.00
6 BEL0380*±6AMA 9.00 9.00 9.00 9.00 9.00

43
LOW PROFILE UNIT COOLERS

DOE Rated AWEF


AWEF DATA
Electric Defrost - Single Speed EC Motors

Electric Defrost/1-Speed EC Motors


Freezer

FPI Model R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F R-407C CO2 DX

AWEF AWEF AWEF AWEF AWEF

6 BEL0040*±6EEA 3.96 3.96 3.96 - 3.96


6 BEL0045*±6EEA 3.96 3.96 3.96 - 3.96
6 BEL0065*±6EEA 4.00 4.03 4.02 - 4.00
6 BEL0080*±6EEA 4.03 4.03 4.03 - 4.03
6 BEL0100*±6EEA 4.00 4.06 4.06 - 4.00
6 BEL0130*±6EEA 4.09 4.09 4.09 - 4.09
6 BEL0155*±6EEA 4.10 4.10 4.10 - 4.10
6 BEL0170*±6EEA 4.14 4.14 4.14 - 4.14
6 BEL0205*±6EEA 4.15 4.15 4.15 - 4.15
6 BEL0240*±6EEA 4.15 4.15 4.15 - 4.15
6 BEL0255*±6EEA 4.15 4.15 4.15 - 4.15
6 BEL0310*±6EEA 4.15 4.15 4.15 - 4.15
4 BEL0045*±4EEA 3.96 3.96 3.96 - 3.96
4 BEL0070*±4EEA 3.99 3.99 3.99 - -
4 BEL0090*±4EEA 4.02 4.02 4.02 - 4.02
4 BEL0135*±4EEA 4.07 4.07 4.07 - 4.07
4 BEL0180*±4EEA 4.12 4.12 4.12 - 4.12
4 BEL0220*±4EEA 4.15 4.15 4.15 - 4.15
4 BEL0275*±4EEA 4.15 4.15 4.15 - 4.15

44
DOE Rated AWEF
AWEF DATA
Electric Defrost - Single Speed EC Motors

Electric Defrost/2-Speed EC Motors


Cooler

FPI Model R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F R-407C CO2 DX

AWEF AWEF AWEF AWEF AWEF

6 BEL0040*±6EMA 9.00 9.00 9.00 - 9.00


6 BEL0045*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0065*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0080*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0100*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0130*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0155*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0170*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0205*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0240*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0255*±6EMA 9.00 9.00 9.00 - 9.00
6 BEL0310*±6EMA 9.00 9.00 9.00 - 9.00
4 BEL0045*±4EMA 9.00 9.00 9.00 - 9.00
4 BEL0070*±4EMA 9.00 9.00 9.00 - -
4 BEL0090*±4EMA 9.00 9.00 9.00 - 9.00
4 BEL0135*±4EMA 9.00 9.00 9.00 - 9.00
4 BEL0180*±4EMA 9.00 9.00 9.00 - 9.00
4 BEL0220*±4EMA 9.00 9.00 9.00 - 9.00
4 BEL0275*±4EMA 9.00 9.00 9.00 - 9.00

Freezer

FPI Model R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F R-407C CO2 DX

AWEF AWEF AWEF AWEF AWEF

6 BEL0040*±6EMA 3.96 3.96 3.96 - 3.96


6 BEL0045*±6EMA 3.96 3.96 3.96 - 3.96
6 BEL0065*±6EMA 4.00 4.03 4.02 - 4.00
6 BEL0080*±6EMA 4.00 4.00 4.00 - 4.00
6 BEL0100*±6EMA 4.03 4.03 4.03 - 4.03
6 BEL0130*±6EMA 4.06 4.06 4.06 - 4.06
6 BEL0155*±6EMA 4.09 4.09 4.09 - 4.09
6 BEL0170*±6EMA 4.10 4.10 4.10 - 4.10
6 BEL0205*±6EMA 4.14 4.14 4.14 - 4.14
6 BEL0240*±6EMA 4.15 4.15 4.15 - 4.15
6 BEL0255*±6EMA 4.15 4.15 4.15 - 4.15
6 BEL0310*±6EMA 4.15 4.15 4.15 - 4.15
4 BEL0045*±4EMA 3.96 3.96 3.96 - 3.96
4 BEL0070*±4EMA 3.99 3.99 3.99 - -
4 BEL0090*±4EMA 4.02 4.02 4.02 - 4.02
4 BEL0135*±4EMA 4.07 4.07 4.07 - 4.07
4 BEL0180*±4EMA 4.12 4.12 4.12 - 4.12
4 BEL0220*±4EMA 4.15 4.15 4.15 - 4.15
4 BEL0275*±4EMA 4.15 4.15 4.15 - 4.15

45
LOW PROFILE UNIT COOLERS

DOE Rated AWEF


AWEF DATA
Hot Gas Defrost - Single Speed EC Motors

Hot Gas Defrost/1-Speed EC Motors


Freezer

FPI Model R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F R-407C

AWEF AWEF AWEF AWEF

6 BEL0040*S6HEA 3.96 3.96 3.96 -


6 BEL0045*S6HEA 3.96 3.96 3.96 -
6 BEL0065*S6HEA 4.00 4.03 4.02 -
6 BEL0080*S6HEA 4.03 4.03 4.03 -
6 BEL0100*S6HEA 4.06 4.06 4.06 -
6 BEL0130*S6HEA 4.09 4.09 4.09 -
6 BEL0155*S6HEA 4.10 4.10 4.10 -
6 BEL0170*S6HEA 4.14 4.14 4.14 -
6 BEL0205*S6HEA 4.15 4.15 4.15 -
6 BEL0240*S6HEA 4.15 4.15 4.15 -
6 BEL0255*S6HEA 4.15 4.15 4.15 -
6 BEL0310*S6HEA 4.15 4.15 4.15 -
4 BEL0045*S4HEA 3.96 3.96 3.96 -
4 BEL0070*S4HEA 3.99 3.99 3.99 -
4 BEL0090*S4HEA 4.02 4.02 4.02 -
4 BEL0135*S4HEA 4.07 4.07 4.07 -
4 BEL0180*S4HEA 4.12 4.12 4.12 -
4 BEL0220*S4HEA 4.15 4.15 4.15 -
4 BEL0275*S4HEA 4.15 4.15 4.15 -

46
DOE Rated AWEF
AWEF DATA
Air Defrost - 2-Speed EC Motors

Hot Gas Defrost/2-Speed EC Motors


Cooler

FPI Model R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F R-407C

AWEF AWEF AWEF AWEF

6 BEL0040*S6HMA 9.00 9.00 9.00 -


6 BEL0045*S6HMA 9.00 9.00 9.00 -
6 BEL0065*S6HMA 9.00 9.00 9.00 -
6 BEL0080*S6HMA 9.00 9.00 9.00 -
6 BEL0100*S6HMA 9.00 9.00 9.00 -
6 BEL0130*S6HMA 9.00 9.00 9.00 -
6 BEL0155*S6HMA 9.00 9.00 9.00 -
6 BEL0170*S6HMA 9.00 9.00 9.00 -
6 BEL0205*S6HMA 9.00 9.00 9.00 -
6 BEL0240*S6HMA 9.00 9.00 9.00 -
6 BEL0255*S6HMA 9.00 9.00 9.00 -
6 BEL0310*S6HMA 9.00 9.00 9.00 -
4 BEL0045*S4HMA 9.00 9.00 9.00 -
4 BEL0070*S4HMA 9.00 9.00 9.00 -
4 BEL0090*S4HMA 9.00 9.00 9.00 -
4 BEL0135*S4HMA 9.00 9.00 9.00 -
4 BEL0180*S4HMA 9.00 9.00 9.00 -
4 BEL0220*S4HMA 9.00 9.00 9.00 -
4 BEL0275*S4HMA 9.00 9.00 9.00 -

Freezer

FPI Model R-404A/ R-507A R-448A/ R-449A R-407A/ R-407F R-407C

AWEF AWEF AWEF AWEF

6 BEL0040*S6HMA 3.96 3.96 3.96 -


6 BEL0045*S6HMA 3.96 3.96 3.96 -
6 BEL0065*S6HMA 4.00 4.03 4.02 -
6 BEL0080*S6HMA 4.00 4.00 4.00 -
6 BEL0100*S6HMA 4.03 4.03 4.03 -
6 BEL0130*S6HMA 4.06 4.06 4.06 -
6 BEL0155*S6HMA 4.09 4.09 4.09 -
6 BEL0170*S6HMA 4.10 4.10 4.10 -
6 BEL0205*S6HMA 4.14 4.14 4.14 -
6 BEL0240*S6HMA 4.15 4.15 4.15 -
6 BEL0255*S6HMA 4.15 4.15 4.15 -
6 BEL0310*S6HMA 4.15 4.15 4.15 -
4 BEL0045*S4HMA 3.96 3.96 3.96 -
4 BEL0070*S4HMA 3.99 3.99 3.99 -
4 BEL0090*S4HMA 4.02 4.02 4.02 -
4 BEL0135*S4HMA 4.07 4.07 4.07 -
4 BEL0180*S4HMA 4.12 4.12 4.12 -
4 BEL0220*S4HMA 4.15 4.15 4.15 -
4 BEL0275*S4HMA 4.15 4.15 4.15 -

47
LOW PROFILE UNIT COOLERS

HOT GAS REVERSE CYCLE KITS


Shipped Loose Accessories

TXV Bypass and TXV Liquid Line Piping Kit


Liquid Line Piping Kit (Three Pipe or Rev Cycle Suction/Drain Pan Drain Pan Check
507A (Reverse Cycle) w/o TXV Bypass) Check Valve Piping Kit Valve Piping Kit
(Reverse Cycle) (Three Pipe)
FPI Model For TXV’s SBF/SQE/BBI/EG For TXV’s SBF/SQE/BBI/EG

6 BEL0040*S6H^A 50756301 50756302 50692204 50692302


6 BEL0045*S6H^A 50756301 50756302 50692204 50692302
6 BEL0065*S6H^A 50756301 50756302 50692204 50692302
6 BEL0080*S6H^A 50756301 50756302 50692204 50692302
6 BEL0100*S6H^A 50756301 50756302 5069225 50692302
6 BEL0130*S6H^A 50756301 50756302 5069225 50692302
6 BEL0155*S6H^A 50756301 50756302 50692206 50692302
6 BEL0170*S6H^A 50756301 50756302 50692205 50692302
6 BEL0205*S6H^A 50756301 50756302 50692206 50692302
6 BEL0240*S6H^A 50756301 50756302 50692206 50692302
6 BEL0255*S6H^A 50756301 50756302 50692206 50692302
6 BEL0310*S6H^A 50756301 50756302 50692206 50692302
4 BEL0045*S4H^A 50756301 50756302 50692204 50692302
4 BEL0070*S4H^A 50756301 50756302 50692204 50692302
4 BEL0090*S4H^A 50756301 50756302 50692205 50692302
4 BEL0135*S4H^A 50756301 50756302 50692205 50692302
4 BEL0180*S4H^A 50756301 50756302 50692206 50692302
4 BEL0220*S4H^A 50756301 50756302 50692206 50692302
4 BEL0275*S4H^A 50756301 50756302 50692206 50692302

REVERSE CYCLE PIPING


Reverse cycle defrost unit cooler operation
Reverse cycle defrost is a common method used in systems that include at least four unit coolers connected to a compressor rack. No
more than 25% of the connected unit coolers are typically defrosted at the same time.

During reverse cycle, valving at the compressor rack diverts hot gas through the suction line to the defrosting unit cooler. See piping
view in Figure 1. The suction line check valve directs the hot gas through the pan loop; heating the drain pan and preventing condensate
from freezing during defrost. The hot gas exits the loop at the pan loop outlet header, passes through the drain pan check valve and en-
ters the evaporator coil through the coil suction header. The hot refrigerant gas then flows through the defrosting coil, heating the finned
surface and melting frost. As heat is transferred to the coil fins, hot refrigerant gas condenses to a liquid state. The refrigerant then exits
the coil at the distributor side port, passes around the expansion valve through the bypass check valve and flows into the liquid refrig-
erant line. The liquid refrigerant then feeds other evaporators on the cooling cycle, evaporates, and returns to the compressor through
their suction lines.

In some systems, electric drain pan heaters are used instead of a hot gas pan loop. Hot gas piping is simplified with the suction and
drain pan check valves being eliminated. Electric drain pan heaters are energized during the defrost period, by a defrost control on the
unit cooler or by a compressor rack controller.

48
REVERSE CYCLE DEFROST PIPING KEY COMPONENTS
(FIG. 1)

A. Hot gas drain pan loop


B. Drain pan check valve C
C. Expansion valve
OUT
D. Suction header G

E. Distributor
F. Suction check valve
E
G. Expansion valve bypass check valve

D
IN

REVERSE CYCLE DEFROST PIPING KITS: A


F B
External check valve kit (available factory-installed or for field
installation) includes suction check valve, drain pan check valve
and piping to connect to suction header and hot gas drain pan
loop. This kit is only necessary when the unit cooler is equipped
with a hot gas drain pan loop.

Expansion valve bypass kit (available factory-installed or for


field installation) includes expansion valve bypass check valve and
piping to connect to the distributor side port and liquid line piping.
The factory-installed version includes the expansion valve. DISTRIBUTOR

Use of external liquid/suction line heat exchanger CHECK VALVE


with a reverse cycle system:

To increase the efficiency, higher performance and greater system


protection, a heat exchanger may be beneficial to the system. In
order to use a heat exchanger, the expansion valve bypass piping EXPANSION
VALVE
must be modified. See the piping view in Figure 2. The modifica-
tion includes rerouting the pipe from the expansion valve bypass
check valve to the inlet connection of the liquid line to the heat
exchanger. A pipe needs to be routed from the liquid line outlet TEE R
N GE SUCTION
connection of the heat exchanger to the inlet connection of the LIQUID HA LINE FROM
LINE E XC COIL
thermostatic expansion valve.
AT
HE
SUCTION LINE
Three-pipe defrost unit cooler operation
FIGURE 2. Typical Liquid Line Bypass Kit
Three-pipe defrost systems are connected to either a condensing (Shown assembled and modified for heat exchanger)

unit or a compressor rack. No more than 33% of the connected


unit coolers are typically defrosted at the same time.

During defrost, hot gas is directed through dedicated refrigerant


piping (third pipe) to the defrosting unit cooler. See piping view in
Figure 3. The hot gas enters the drain pan loop; heating the drain
pan and preventing condensate from freezing during defrost.
The hot gas exits the loop at the pan loop outlet header, passes
through the drain pan check valve and enters the evaporator coil
through the distributor side port connection. The hot refrigerant
gas then flows though the defrosting coil, heating the finned
surface and melting frost. As heat is transferred to the coil fins, hot
refrigerant gas condensers to a liquid state. The refrigerant then
exits the coil at the suction header.

49
LOW PROFILE UNIT COOLERS

Three-pipe defrost unit cooler operation (cont.)


In some systems, electric drain pan heaters are used instead of a
hot gas pan loop. Hot gas piping is simplified with the drain pan
check valve being eliminated. Electric drain pan heaters are en-
ergized during the defrost period, by a defrost control on the unit
cooler or by a compressor rack controller.

In order to provide sufficient re-evaporation of the liquid vapor


mixture and sufficient heat for defrost, no more than one-third of
the system should be defrosted at one time. Some means of con-
trol in the 3-pipe hot gas system should be supplied to regulate
the large amount of liquid returning to the compressor, refrigerant
slugging can otherwise damage the compressor.

REVERSE CYCLE THREE-PIPE DEFROST PIPING KEY


COMPONENTS (FIG. 3)
A. Hot gas drain pan loop
C
B. Drain pan check valve
C. Expansion valve
D. Suction header
E. Distributor
E
OUT IN

THREE-PIPE DEFROST PIPING KIT:


D B
A
Three-pipe check valve kit (available factory-installed or for field
installation) includes drain pan check valve and piping to connect the
distributor side port to the hot gas drain pan loop. This kit is only ne-
cessary when the unit cooler is equipped with a hot gas drain pan loop.

Hot gas defrost controls:


Hot gas unit coolers are factory equipped with temperature control(s) that terminate the defrost cycle when the evaporator coil is clear of
frost. After defrost, the control(s) keep the evaporator fans from re-energizing until the coil temperature is close to the freezing point.

STANDARD: OPTIONAL:
The standard control scheme includes an electromechanical defrost The optional control scheme includes an electromechanical defrost
termination / fan delay control. termination control and a separate bimetallic fan delay control. This
For reverse cycle defrost, the control sensing bulb is placed on the scheme provides more options for the placement of the control sensing
expansion valve bypass line, between the distributor side port and the bulb as the defrost termination and fan delay sensing points are no
expansion valve bypass check valve. longer combined.

For three-pipe defrost, the control sensing bulb is placed on the suction The fan delay temperature is sensed on the evaporator coil endplate
header or suction header outlet connection. adjacent to the fins.
For reverse cycle defrost, the control sensing bulb is placed on the ex-
pansion valve bypass line or liquid line piping adjacent to the unit cooler.
For three-pipe defrost, the control sensing bulb is placed on the suction
header or suction header outlet connection.

50
REPLACEMENT PARTS – R-404A/R-507A
Motor/Motor Mounts
Part # Motor Type Voltage Motor Speeds Motor Mount
25312501S / 25329001S EC 115 1-SP / 2-SP 23106301
25312601S / 25329101S EC 208-230 2-SP 23106301
25317701S EC 208-230 1-SP 23106301
25309501S PSC 115 1-SP 23106301
25309801S PSC 208-230 1-SP 23106301
25309701S PSC 460 1-SP 23106401

Fan Blade
Part # Description
5140C Fan Blade 12" Std
5110E Fan Blade 12" Reverse Air Flow

Fan Guard
Part # Description
37001601 Fan Guard Wire Blue
37001701 Fan Guard Molded Blue

Cabinet Components
No. of
Part # Description Defrost Type Cabinet Aluminum Application Notes
Fans
40594101 1 Drain Pan Air/Hot Gas Aluminum Air, Hot Gas Models w/Drain Pan Loop
40595101 1 Drain Pan Air/Hot Gas White Painted Aluminum Air, Hot Gas Models w/Drain Pan Loop
40596101 1 Drain Pan Air/Hot Gas Stainless Steel Air Defrost Only
40594201 2 Drain Pan Air/Hot Gas Aluminum Air, Hot Gas Models w/Drain Pan Loop
40595201 2 Drain Pan Air/Hot Gas White Painted Aluminum Air, Hot Gas Models w/Drain Pan Loop
40596201 2 Drain Pan Air/Hot Gas Stainless Steel Air Defrost Only
40594301 3 Drain Pan Air/Hot Gas Aluminum Air, Hot Gas Models w/Drain Pan Loop
40595301 4 Drain Pan Air/Hot Gas White Painted Aluminum Air, Hot Gas Models w/Drain Pan Loop
40596301 4 Drain Pan Air/Hot Gas Stainless Steel Air Defrost Only
40594401 4 Drain Pan Air/Hot Gas Aluminum Air, Hot Gas Models w/Drain Pan Loop
40595401 4 Drain Pan Air/Hot Gas White Painted Aluminum Air, Hot Gas Models w/Drain Pan Loop
40596401 4 Drain Pan Air/Hot Gas Stainless Steel Air Defrost Only
40594501 5 Drain Pan Air/Hot Gas Aluminum Air, Hot Gas Models w/Drain Pan Loop
40595501 5 Drain Pan Air/Hot Gas White Painted Aluminum Air, Hot Gas Models w/Drain Pan Loop
40596501 5 Drain Pan Air/Hot Gas Stainless Steel Air Defrost Only
40594601 6 Drain Pan Air/Hot Gas Aluminum Air, Hot Gas Models w/Drain Pan Loop
40595601 6 Drain Pan Air/Hot Gas White Painted Aluminum Air, Hot Gas Models w/Drain Pan Loop
40596601 6 Drain Pan Air/Hot Gas Stainless Steel Air Defrost Only

51
LOW PROFILE UNIT COOLERS

REPLACEMENT PARTS
Cabinet Components (cont.)
No. of
Part # Description Defrost Type Cabinet Aluminum Application Notes
Fans
40594102 1 Drain Pan Electric/Hot Gas Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40595102 1 Drain Pan Electric/Hot Gas White Painted Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40594202 2 Drain Pan Electric/Hot Gas Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40595202 2 Drain Pan Electric/Hot Gas White Painted Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40594302 3 Drain Pan Electric/Hot Gas Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40595302 3 Drain Pan Electric/Hot Gas White Painted Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40594402 4 Drain Pan Electric/Hot Gas Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40595402 4 Drain Pan Electric/Hot Gas White Painted Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40594502 5 Drain Pan Electric/Hot Gas Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40595502 5 Drain Pan Electric/Hot Gas White Painted Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40594602 6 Drain Pan Electric/Hot Gas Aluminum Elec, Hot Gas Models w/Drain Pan Heater
40595602 6 Drain Pan Electric/Hot Gas White Painted Aluminum Elec, Hot Gas Models w/Drain Pan Heater
Insulated Outer Drain
40593703 1 All Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593704 1 All White Painted Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593002 1 All Stainless Steel Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593803 2 All Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593804 2 All White Painted Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593102 2 All Stainless Steel Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40591503 3 All Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40591504 3 All White Painted Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593202 3 All Stainless Steel Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40591603 4 All Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40591604 4 All White Painted Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593302 4 All Stainless Steel Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40591703 5 All Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40591704 5 All White Painted Aluminum Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40593402 5 All Stainless Steel Includes Outer Cover and Insulation
Pan Assy
Insulated Outer Drain
40591803 6 All Aluminum Includes Outer Cover and Insulation
Pan Assy

52
REPLACEMENT PARTS
Cabinet Components (cont.)
No. of Defrost
Part # Description Cabinet Aluminum Application Notes
Fans Type

40591804 6 Insulated Outer Drain Pan Assy All White Painted Aluminum Includes Outer Cover and Insulation
40593502 6 Insulated Outer Drain Pan Assy All Stainless Steel Includes Outer Cover and Insulation
41032901 All Access Panel RH (Elect) End All Aluminum/Stainless Steel All w/Unpainted Cabinet
41032902 All Access Panel RH (Elect) End All White Painted Aluminum All w/White Cabinet
41032801 All Access Panel LH (Refrig) End All Aluminum/Stainless Steel Stndard w/Unpainted Cabinet
41032802 All Access Panel LH (Refrig) End All White Painted Aluminum Standard w/White Cabinet
41032803 All Access Panel LH (Refrig) End Air/Electric Aluminum/Stainless Steel IntelliGen/QRC/Beacon II w/Unpainted Cabinet
41032804 All Access Panel LH (Refrig) End Air/Electric White Painted Aluminum IntelliGen/QRC/Beacon II w/White Cabinet
41038401 All Access Panel LH (Refrig) End Air/Electric Aluminum Glycol/CO2 Overfeed Only
41038402 All Access Panel LH (Refrig) End Air/Electric White Painted Aluminum Glycol/CO2 Overfeed Only
41038501 All Access Panel LH (Refrig) End Air/Electric Stainless Steel Glycol/CO2 Overfeed Only
41038701 All Access Panel RH (Elect) End Air/Electric Aluminum Glycol/CO2
41038702 All Access Panel RH (Elect) End Air/Electric White Painted Aluminum Glycol/CO2
41038901 All Access Panel RH (Elect) End Air/Electric Stainless Steel Glycol/CO2

Drain Pan Heaters


No. of
Part # Voltage Wattage Defrost Type Application Notes
Fans

24753101 1 115 150 Hot Gas Hot Gas Models w/Drain Pan Heater
24753102 2 115 300 Hot Gas Hot Gas Models w/Drain Pan Heater
24753103 3 115 450 Hot Gas Hot Gas Models w/Drain Pan Heater
24753104 4 115 600 Hot Gas Hot Gas Models w/Drain Pan Heater
24753105 5 115 750 Hot Gas Hot Gas Models w/Drain Pan Heater
24753106 6 115 900 Hot Gas Hot Gas Models w/Drain Pan Heater
24752501 1 230 150 Electric /Hot Gas Elec, Hot Gas Models w/Drain Pan Heater
24752502 2 230 300 Electric /Hot Gas Elec, Hot Gas Models w/Drain Pan Heater
24752503 3 230 450 Electric /Hot Gas Elec, Hot Gas Models w/Drain Pan Heater
24752504 4 230 600 Electric /Hot Gas Elec, Hot Gas Models w/Drain Pan Heater
24752505 5 230 750 Electric /Hot Gas Elec, Hot Gas Models w/Drain Pan Heater
24752506 6 230 900 Electric /Hot Gas Elec, Hot Gas Models w/Drain Pan Heater
24753201 1 460 150 Hot Gas Hot Gas Models w/Drain Pan Heater
24753202 2 460 300 Hot Gas Hot Gas Models w/Drain Pan Heater
24753203 3 460 450 Hot Gas Hot Gas Models w/Drain Pan Heater
24753204 4 460 600 Hot Gas Hot Gas Models w/Drain Pan Heater
24753205 5 460 750 Hot Gas Hot Gas Models w/Drain Pan Heater
24753206 6 460 900 Hot Gas Hot Gas Models w/Drain Pan Heater

53
LOW PROFILE UNIT COOLERS

REPLACEMENT PARTS
Coil Defrost Heaters
Part # No. of Fans Voltage Wattage Defrost Type

24752001 1 230 300 Electric


24752002 2 230 600 Electric
24752003 3 230 900 Electric
24752004 4 230 1,200 Electric
24752005 5 230 1,500 Electric
24752006 6 230 1,800 Electric
24754101* 1 230 150 Electric
24754102* 2 230 300 Electric
24754103* 3 230 450 Electric
24754104* 4 230 600 Electric
24754105* 5 230 750 Electric
24754106* 6 230 900 Electric

* = One used per 460V unit only, top coil heater position

Electrical Components
Part # Description Defrost Type Application Notes

22597101 Terminal Board Air All


22597701 Terminal Board Electric/Hot Gas All
5709L Defrost Termination/Fan Delay Thermostat Electric Fixed Bi-Metallic Control
5708L Heater Limit Thermostat Electric Fixed Bi-Metallic Control
4267W Defrost Termination/Fan Delay Thermostat Electric/Hot Gas Adjustable Control
28913901 Room Thermostat Air/Electric Room Thermostat Mech
28963201 Room Thermostat Air/Electric Room Thermostat Elec

Drain Fitting
Part # Description Application Notes

26925101 Drain Fitting Kit All

54
STANDARD NOZZLE SELECTION
Air Defrost
Medium Temperature (25°F SST)

No. of Distributor Tube (in.) No. of Nozzle Selections


Model
Fans OD Length Circuits R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
BEL0045*S6A^A 1 3/16 15 1 - - - -
BEL0055*S6A^A 1 3/16 15 2 L-1/3 L-1/2 L-1/3 L-1/3
BEL0060*S6A^A 1 3/16 15 2 L-1/2 L-3/4 L-1/2 L-1/2
BEL0095*S6A^A 2 3/16 15 2 L-1/2 L-3/4 L-1/2 L-1/2
BEL0105*S6A^A 2 3/16 15 3 L-3/4 L-1 L-3/4 L-3/4
BEL0115*S6A^A 2 3/16 15 4 L-1 L-1-1/2 L-1 L-1
BEL0125*S6A^A 2 3/16 15 4 L-1 L-1-1/2 L-1 L-1
BEL0155*S6A^A 3 3/16 15 4 L-1 L-1-1/2 L-1 L-1
BEL0190*S6A^A 3 3/16 15 6 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0250*S6A^A 4 3/16 15 6 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0295*S6A^A 5 3/16 15 6 L-2 L-2-1/2 L-1-1/2 L-1-1/2
BEL0350*S6A^A 6 3/16 15 7 L-2 L-3 L-2 L-2
BEL0380*S6A^A 6 3/16 15 8 L-2-1/2 L-3 L-2-1/2 L-2-1/2

Notes:
Nozzles sized for 90-100°F liquid temperature at expansion valve.
Contact Application Engineering for guidance if:
- Liquid temperature is not 90-100°F
- Evaporator TD is not 10°-15°F (room temperature – saturated suction temperature)
Caution: Refrigeration system will not perform properly without correct nozzle!

55
LOW PROFILE UNIT COOLERS

STANDARD NOZZLE SELECTION


Electric Defrost
Low Temperature (-20°F SST)

No. of Distributor Tube (in.) No. of Nozzle Selections


Model
Fans OD Length Circuits R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
BEL0040*S6E^A 1 3/16 15 2 L-1/2 L-3/4 L-1/2 -
BEL0045*S6E^A 1 3/16 15 2 L-3/4 L-3/4 L-1/2 -
BEL0065*S6E^A 2 3/16 15 3 L-3/4 L-1 L-3/4 -
BEL0080*S6E^A 2 3/16 15 3 L-1 L-1-1/2 L-1 -
BEL0100*S6E^A 2 3/16 15 6 L-1-1/2 L-1-1/2 L-1 -
BEL0130*S6E^A 3 3/16 15 6 L-1-1/2 L-2 L-1-1/2 -
BEL0155*S6E^A 3 3/16 15 8 L-2 L-2-1/2 L-2 -
BEL0170*S6E^A 4 3/16 15 6 L-2 L-2-1/2 L-2 -
BEL0205*S6E^A 4 3/16 15 8 L-2-1/2 L-3 L-2 -
BEL0240*S6E^A 5 3/16 15 8 L-2-1/2 L-4 L-2-1/2 -
BEL0255*S6E^A 6 3/16 15 9 L-3 L-4 L-3 -
BEL0310*S6E^A 6 3/16 15 12 L-4 L-5 L-3 -
BEL0045*S4E^A 1 3/16 15 2 L-1/2 L-3/4 L-1/2 -
BEL0070*S4E^A 2 3/16 15 3 L-3/4 L-1 L-3/4 -
BEL0090*S4E^A 2 3/16 15 6 L-1 L-1-1/2 L-1 -
BEL0135*S4E^A 3 3/16 15 6 L-1-1/2 L-2 L-1-1/2 -
BEL0180*S4E^A 4 3/16 15 8 L-2 L-2-1/2 L-2 -
BEL0220*S4E^A 5 3/16 15 8 L-2 L-3 L-2 -
BEL0275*S4E^A 6 3/16 15 12 L-3 L-4 L-3 -

Medium Temperature (25°F SST)

No. of Distributor Tube (in.) No. of Nozzle Selections


Model
Fans OD Length Circuits R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
BEL0040*S6E^A 1 3/16 15 2 L-1/4 L-1/3 L-1/4 L-1/4
BEL0045*S6E^A 1 3/16 15 2 L-1/3 L-1/2 L-1/3 L-1/3
BEL0065*S6E^A 2 3/16 15 3 L-1/2 L-3/4 L-1/2 L-1/2
BEL0080*S6E^A 2 3/16 15 3 L-3/4 L-3/4 L-1/2 L-1/2
BEL0100*S6E^A 2 3/16 15 6 L-3/4 L-1 L-3/4 L-3/4
BEL0130*S6E^A 3 3/16 15 6 L-1 L-1-1/2 L-1 L-1
BEL0155*S6E^A 3 3/16 15 8 L-1 L-1-1/2 L-1 L-1
BEL0170*S6E^A 4 3/16 15 6 L-1-1/2 L-1-1/2 L-1-1/2 L-1-1/2
BEL0205*S6E^A 4 3/16 15 8 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0240*S6E^A 5 3/16 15 8 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0255*S6E^A 6 3/16 15 9 L-2 L-2-1/2 L-2 L-2
BEL0310*S6E^A 6 3/16 15 12 L-2 L-3 L-2 L-2
BEL0045*S4E^A 1 3/16 15 2 L-1/3 L-1/2 L-1/4 L-1/4
BEL0070*S4E^A 2 3/16 15 3 L-1/2 L-3/4 L-1/2 L-1/2
BEL0090*S4E^A 2 3/16 15 6 L-3/4 L-3/4 L-3/4 L-3/4
BEL0135*S4E^A 3 3/16 15 6 L-3/4 L-1 L-3/4 L-3/4
BEL0180*S4E^A 4 3/16 15 8 L-1 L-1-1/2 L-1 L-1
BEL0220*S4E^A 5 3/16 15 8 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0275*S4E^A 6 3/16 15 12 L-2 L-2-1/2 L-2 L-2

Notes:
Nozzles sized for 90-100°F liquid temperature at expansion valve.
Contact Application Engineering for guidance if:
- Liquid temperature is not 90-100°F
- Evaporator TD is not 10°-15°F (room temperature – saturated suction temperature)
Caution: Refrigeration system will not perform properly without correct nozzle!

56
STANDARD NOZZLE SELECTION
Hot Gas Defrost
Low Temperature (-20°F SST)

No. of Distributor Tube (in.) No. of Nozzle Selections


Model
Fans OD Length Circuits R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
BEL0040*S6H^A 1 3/16 15 2 L-1/2 L-3/4 L-1/2 -
BEL0045*S6H^A 1 3/16 15 2 L-3/4 L-3/4 L-1/2 -
BEL0065*S6H^A 2 3/16 15 3 L-3/4 L-1 L-3/4 -
BEL0080*S6H^A 2 3/16 15 3 L-1 L-1-1/2 L-1 -
BEL0100*S6H^A 2 3/16 15 6 L-1-1/2 L-1-1/2 L-1 -
BEL0130*S6H^A 3 3/16 15 6 L-1-1/2 L-2 L-1-1/2 -
BEL0155*S6H^A 3 3/16 15 8 L-2 L-2-1/2 L-2 -
BEL0170*S6H^A 4 3/16 15 6 L-2 L-2-1/2 L-2 -
BEL0205*S6H^A 4 3/16 15 8 L-2-1/2 L-3 L-2 -
BEL0240*S6H^A 5 3/16 15 8 L-2-1/2 L-4 L-2-1/2 -
BEL0255*S6H^A 6 3/16 15 9 L-3 L-4 L-3 -
BEL0310*S6H^A 6 3/16 15 12 L-4 L-5 L-3 -
BEL0045*S4H^A 1 3/16 15 2 L-1/2 L-3/4 L-1/2 -
BEL0070*S4H^A 2 3/16 15 3 L-3/4 L-1 L-3/4 -
BEL0090*S4H^A 2 3/16 15 6 L-1 L-1-1/2 L-1 -
BEL0135*S4H^A 3 3/16 15 6 L-1-1/2 L-2 L-1-1/2 -
BEL0180*S4H^A 4 3/16 15 8 L-2 L-2-1/2 L-2 -
BEL0220*S4H^A 5 3/16 15 8 L-2 L-3 L-2 -
BEL0275*S4H^A 6 3/16 15 12 L-3 L-4 L-3 -

Medium Temperature (25°F SST)

No. of Distributor Tube (in.) No. of Nozzle Selections


Model
Fans OD Length Circuits R-404A/R-507A R-448A/R-449A R-407A/R-407F R-407C
BEL0040*S6H^A 1 3/16 15 2 L-1/4 L-1/3 L-1/4 L-1/4
BEL0045*S6H^A 1 3/16 15 2 L-1/3 L-1/2 L-1/3 L-1/3
BEL0065*S6H^A 2 3/16 15 3 L-1/2 L-3/4 L-1/2 L-1/2
BEL0080*S6H^A 2 3/16 15 3 L-3/4 L-3/4 L-1/2 L-1/2
BEL0100*S6H^A 2 3/16 15 6 L-3/4 L-1 L-3/4 L-3/4
BEL0130*S6H^A 3 3/16 15 6 L-1 L-1-1/2 L-1 L-1
BEL0155*S6H^A 3 3/16 15 8 L-1 L-1-1/2 L-1 L-1
BEL0170*S6H^A 4 3/16 15 6 L-1-1/2 L-1-1/2 L-1-1/2 L-1-1/2
BEL0205*S6H^A 4 3/16 15 8 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0240*S6H^A 5 3/16 15 8 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0255*S6H^A 6 3/16 15 9 L-2 L-2-1/2 L-2 L-2
BEL0310*S6H^A 6 3/16 15 12 L-2 L-3 L-2 L-2
BEL0045*S4H^A 1 3/16 15 2 L-1/3 L-1/2 L-1/4 L-1/4
BEL0070*S4H^A 2 3/16 15 3 L-1/2 L-3/4 L-1/2 L-1/2
BEL0090*S4H^A 2 3/16 15 6 L-3/4 L-3/4 L-3/4 L-3/4
BEL0135*S4H^A 3 3/16 15 6 L-3/4 L-1 L-3/4 L-3/4
BEL0180*S4H^A 4 3/16 15 8 L-1 L-1-1/2 L-1 L-1
BEL0220*S4H^A 5 3/16 15 8 L-1-1/2 L-2 L-1-1/2 L-1-1/2
BEL0275*S4H^A 6 3/16 15 12 L-2 L-2-1/2 L-2 L-2

Notes:
Nozzles sized for 90-100°F liquid temperature at expansion valve.
Contact Application Engineering for guidance if:
- Liquid temperature is not 90-100°F
- Evaporator TD is not 10°-15°F (room temperature – saturated suction temperature)
Caution: Refrigeration system will not perform properly without correct nozzle!

57
NOTES
NOTES