Froztec Recold MC
Froztec Recold MC
Froztec Recold MC
E VA P O R AT I V E C O N D E N S E R and specifications
www.froztec.com
Recold MC Series Evaporative Condenser — Selection Procedure 2
Suction R-134A 3.6 2.0 6.5 12.0 18.4 26.1 35.0 45.4
Pressure PSIG R-22 10.2 16.5 24.0 32.8 43.0 54.9 68.5 84.0
Capacity Factor 1.32 1.23 1.17 1.11 1.07 1.03 1.00 .97
Recold MC Series Evaporative Condenser — Selection Procedure 3
The MC Series can be furnished with the condenser coil divided Selection:
into individual refrigerant circuits, each sized to meet a specified The adjusted load of 654,840 BTUH should be compared to
capacity. Each circuit is supplied with a hot gas inlet connection “Total Unit BTUH” column in Table 8. The smallest unit that will
and liquid outlet connection tagged for identification. meet the requirement is Model MC50 with a THR of 735,000
The procedure for selecting a multi-circuited condenser coil BTUH.
is described in the “Selection Example” below. For circuit To determine the number of tube circuits required for each
identification purposes it is required that circuits be arranged circuit divide Column 6 by Column 7, and tabulate in Column 8.
in sequence. Connections for the individual circuits, will If the decimal part of the tube circuit requirement is less than
be numbered at the factory, from left to right when facing .3, drop the decimal and enter the whole number in Column 9. If
connection end of unit, with the number 1 circuit being on the the decimal part is equal to or greater than .3, round off to the
extreme left. next higher whole number and enter in Column 9.
The “Tabulation Example” shows 26 tube circuits are required
Selection Example: and Table 8 shows that Model MC50 has 36 tube circuits
Given: available, therefore, it is the proper unit selection.
Condensing Temperature 100°F
Entering Air Wet Bulb Temp. 72°F NOTE:
Ten individual suction cooled hermetic compressor capacities, as If the summation of the number of tube circuits assigned to the
shown in the tabulation below: individual circuits is less than the total number of tube circuits
available in the unit, add enough tubes to effect a balance.
1. Tabulate data in Columns 1, 2 and 3, making sure circuits If the summation of the number of tube circuits assigned to
are in correct numerical sequence. the individual circuits is greater than the total number of tube
2. From Table 6 “Hermetic Compressors”, select Evaporator circuits available in the unit, delete enough tubes to effect a
Temperature Capacity Factor applicable to each Suction balance. However, if such reduction causes more than a 10
Temperature listed in Column 2 and tabulate in Column 4. percent reduction in any of the circuits, go to the next larger
unit size and reassign tube circuits to give adequate capacity to
3. From Table 7, select “Condenser Capacity Conversion
every circuit.
Factor” applicable to the design condensing temperature and
the design entering air wet bulb temperature and tabulate in
Column 5.
4. Multiply figures in Columns 3, 4 and 5 for each circuit, and
tabulate in Column 6.
5. Add all the capacities in Column 6 to arrive at the Total Adj.
BTUH to Nominal required and use the total to select the
proper size condenser.
Tabulation Example
1 2 3 x 4 x 5 = 6 ÷ 7 = 8 9
Evap. Temp. Adj.
Suction Comp. Cond. Cap. Capacity Per Number of
Circuit Cap. BTUH Number of
Temperature Capacity x x Conversion Factor = ÷ Tube Circuit = Circuits
Number Conversion to Circuits Used
°F BTUH Table 7 Table 8 Required
Table 6 Nominal
1 -10 22,500 x 1.69 x 1.03 = 39,165 ÷ 26,008 1.50 2
2 -5 35,200 x 1.65 x 1.03 = 59,822 ÷ 26,008 2.30 2
3 +30 72,800 x 1.36 x 1.03 = 101,978 ÷ 26,008 3.92 4
4 +15 45,400 x 1.48 x 1.03 = 69,208 ÷ 26,008 ÷ 2.66 3
5 -20 41,600 x 1.79 x 1.03 = 76,698 ÷ 26,008 2.95 3
6 +40 70,100 x 1.33 x 1.03 = 96,030 ÷ 26,008 3.69 4
7 -15 29,700 x 1.74 x 1.03 = 53,228 ÷ 26,008 2.05 2
8 -20 45,500 x 1.79 x 1.03 = 78,357 ÷ 26,008 3.01 3
9 -10 19,500 x 1.69 x 1.03 = 33,944 ÷ 26,008 1.30 1
10 +5 28,700 x 1.57 x 1.03 = 46,410 ÷ 26,008 1.789 2
654,840 26
Recold MC Series Evaporative Condenser — Multi-Circuit Selection Procedure 5
Evaporative Temperature
-40 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
°F
Open Compressors 1.75 1.65 1.62 1.59 1.55 1.53 1.50 1.47 1.44 1.40 1.37 1.35 1.32 1.30 1.28 1.26 1.24 1.22
Hermetic Compressors 2.02 1.90 1.852 1.79 1.74 1.69 1.65 1.61 1.57 1.51 1.48 1.45 1.40 1.36 1.34 1.33 1.32 1.31
31/8" Inlet
1087/8"
31/8" Outlet
31/8" Inlet
1087/8"
31/8" Outlet
14" 1441/8"
AVAILABLE OPTIONS
Stainless Pan and Casing For maximum corrosion protection, Control Panel For single point connection, factory wired control
Recold can provide a unit with the pan and casing constructed panels are available. The U.L. panel includes the fan motor starters,
entirely from stainless steel. disconnect switch, and submersible bulb thermostat; all inside a
Sub-Cooling Coil The sub-cooling coil consists of an additional NEMA 12 enclosure.
coil section located below the standard condensing coil. It provides Special Motors A full line of optional motors are available
approximately 10°F of sub-cooling at standard conditions for including: high-efficiency, low-speed, special enclosures and special
halocarbon refrigerants.Specifying a sub-cooling will slightly voltages or frequencies.
increase height and alter certain connection elevations. Please
consult Recold sales representative for certified dimensions. Vibration Isolation The Recold M Series is designed for smooth
and quiet operation. If design conditions require additional vibration
Other Coil Options Additional coil options can be provided isolation, spring type vibration isolator rails can be supplied for field
including: heavy wall tubing, external headers and multiple circuits. installation.
Basin Heaters For freeze protection of the cold water in the Other options are available. Contact your Recold sales
basin, electric immersion heaters are available. Heaters are sized representative for more information.
to maintain a 40°F minimum basin water temperature at a -10°F
ambient temperature.
Recold MC Series Evaporative Condenser / Engineering Data 7
Plan View
31/8" Inlet
115"
31/8" Outlet
GENERAL NOTES
1. S
upporting Steel: Purchaser to design, construct and furnish 6. C
oncrete Slabs: When installed at grade most units are
supporting steel complete with 7⁄8" diameter anchor bolt holes anchored to a flat concrete slab. All applicable piping connections
to suit. All steel must be framed flush and level at top. Maximum are designed to allow adequate clearance for connecting
beam deflection to be 1/360 of span, not to exceed 1⁄2" at purchaser’s piping to the unit when installed on a concrete slab.
anchor bolts.
7. Vibration Isolation: If unit is to be supported on vibration
2. O
perating Weight and Loads: These loads are based upon isolators, the preferred location for the isolators is beneath steel
normal water level in sump pan at shutdown. beams and the unit base rails. If necessary to install isolators
3. Wind Loads: Construction drawings furnished upon request. between the unit base rails and supporting steel beams, contact
Recold sales representative for allowable type and arrangement
4. A
nchor Bolts: All anchor bolts are 3⁄4" inch diameter and are of isolators for a specific model and for dimensional changes on
to be furnished by others. Wind loads at anchorage points are anchor bolt hole locations.
additive to operating loads.
5. S
hipping Weight, Operating Weight, Operating Loads:
These weight and loads do not include optional accessory
weights. Contact Recold sales representative for accessory
weights when applicable.
Recold MC Series Evaporative Condenser — Specifications 8
Furnish _____________ Recold model MC_____________ induced draft evaporative condenser(s). Each unit shall have a condensing
capacity of ______________ MBH total heat rejection when operating with ______________ refrigerant at
___________°F condensing temperature and ______________°F design wet bulb temperature.
Heat Transfer Coil: The heat exchange coil tubes shall be Recirculation Pump: The water recirculation pump shall be
constructed of copper to provide maximum corrosion resistance. close-coupled, centrifugal type with mechanical seal. A minimum
Coil tubes shall be 5/8" OD copper tubing with type L headers. ______ hp open drip proof type pump motor designed for
Tubes shall be supported by stainless steel tube sheets with outdoor service with a 1.15 service factor suitable for service on
floating tube design for long life. The completed coil section ____volts, _____ phase, and ________hertz shall be provided.
shall be leak tested under water at 350 psig.
Drift Eliminators: Shall be of cellular type, thermoformed
Mechanical Equipment: A high-quality bearing assembly, PVC. The eliminator design shall incorporate three changes of
specifically designed for cooling tower service shall be provided. air direction with maximum drift rate less than 0.001% of the
Bearings will be greased at the factory with extended lubelines circulating water rate.
provided. The fan shaft shall be stainless steel. Fans shall
Louvers: Shall be constructed of PVC in a cellular pattern
be low sound, axial propeller type with GRP blades for high-
supported in easily removable subassemblies. Shall provide
efficiency and long life. V-belt drive shall be designed for 150%
directional changes to the entering air to prevent splashout.
of motor horsepower. Belt adjustment shall be accomplished
from the exterior of the unit. Each fan section shall have dividers Pan and Casing: The evaporative condenser shall be
to allow the fans to be cycled individually. constructed of stainless steel sump pan and G-235 galvanized
steel casing panels. Panels shall be flanged outward for greater
Fan Motor: Fan motors (4) shall be minimum 5 hp 1800 RPM
rigidity and to eliminate connecting fasteners from penetrating
open drip-proof type designed for outdoor service with 1.15
inside the tower wet section. The pan bottom shall be sloped
service factor on _____ volts, _____ phase, and _____hertz. All
design to allow for easy draining and cleaning. At least one
motors shall be mounted outside the tower with a protective rain
access door to the top section shall be provided for easy
cover included.
inspection and service. The access doors shall be made from
Water Distribution: System shall be designed to evenly and stainless steel and operate without any gasket of fasteners.
completely distribute the spray water over the coil. Spray nozzles
shall be PVC large orifice, non-clogging design, attached to
PVC headers with stainless steel clamps. Nozzle spray pattern
shall be a full 360° for maximum distribution. Internal piping and Safety: The M Series is designed for routine maintenance
fittings shall be made entirely of schedule 40 PVC for maximum to be performed from the base of the unit’s exterior,
corrosion protection. eliminating the need for permanent access to the top. The
upper horizontal surface is not intended for use as a working
platform. Specific reference to the safety of personnel
performing maintenance and inspection procedures can be
found in the Operation and Maintenance instructions.
Froztec International Inc In the interest of technological progress, all products are subject to design