Fotek
Fotek
Fotek
Temperature Controller
Think Controls
NT series § Intelligence § Easiness
§ Performance § Stability
§ Reliability § Sensitivity
w w w. f o t e k . c o m . t w
陽明電機股份有限公司
FOTEK CONTROLS CO., LTD.
PID + Fuzzy Intelligent Temperature Controller
Ex. NT – 48 R – CT – RS
1 2 3 4 5
1 Series (系列名稱) NT: New generation Temperature controller
Outline (外形) 20: 48*96*60 21: 96*48*60 22: 22.6*75*100
2 (Unit: mm) 48: 48*48*72 72: 72*72*60 96: 96*96*60
3 Output method (輸出方式) R: Relay (3A/250VAC) V: SSR (20mA/12V) L: Linear output (4~20mA)
4 Optioned (附加功能) CT: With Heater break detecting mA: DC current input mV: DC Voltage input
5 Optioned (附加功能) RS: With RS-485 communication (MODBUS protocol) S: PV transmitter
CE, RoHs
1.「Temperature setting status」: Press「SET」key instantaneously to enter into the temperature setting status.
2.「Auto-tuning status」: Press「▲」key 3 sec to set「Auto-tuning」,then press「▲」key 3 sec to reset it.
3.「Manu-output status」: Press「▼」key 3 sec to turn off the output control, then press the「SET」key to set the
「Manu-output volume」If press「▼」key 3 sec may to release「Manu-output status」
4.「Display mode selecting」: Press「SET」key 3 sec to select display mode
4-1.Without CT type: Display「Output volume」(u.xx)→then press「SET」key 3 sec → to display「Temperature set value」
4-2. With CT type: Display「output volume」(u.xx) →then press「SET」key 3 sec → to display「Load current」(xx.xx)
→then press「SET」key 3 sec → to display「Temperature set value」
5.「Parameter setting status」: Press「F」key 3 sec to enter into the parameter setting status.
6.「Alarm setting status」: Press「SET」&「F」key 3 sec to enter into the Alarm setting status.
7.「Communication stetting status」: Press「SET」&「▼」key 3 sec to enter into the Communication stetting status.
8.「Soft start function」: At the final parameter of「setting of alarm」, Press「SET」key 3 sec to set the Soft start
setting value「SV2」.
the fixed output volume is set by the manual output volume.
9. 「Ramping control」: At the「rAP」 parameter in the「setting of alarm」level, if「rAP = 0」, it has not the ramping
control function.
if「rAP≠0」, it will perform the ramping control function.
10. 「Display mode setting」: At the「Sdc」 parameter in the「Setting of parameter」level, if「Sdc = n」, it will be
kept on the selected display mode, if「Sdc = A」, it will be returned to the Temperature
set value mode after 10 seconds.
1. 「溫度值設定狀態」:按「SET」鍵一下就可進入「溫度值設定狀態」
2. 「自動演算狀態」:按「▲」鍵3秒可進入「自動演算狀態」;再按「▲」鍵3秒解除「自動演算狀態」
3. 「手動輸出控溫狀態」: 按「▼」鍵3秒關閉輸出(顯示「OFF」),再按「SET」鍵3秒後可設定「手動輸出量」(顯
示n.xx),完成手動輸出量設定後如果再按「▼」鍵3秒可解除「手動輸出控溫狀態」回複自
動控溫狀態。。
w w w. f o t e k . c o m . t w
4. 「顯示模式選擇」:按「SET」鍵3秒
4-1. 無CT型:「輸出量顯示」(u.xx)→再按「SET」鍵3秒→「溫度設定值顯示」
4-2. CT型:「輸出量顯示」(u.xx) →再按「SET」鍵3秒→「負載電流量顯示」(xx.xx)
→再按「SET」鍵3秒→「溫度設定值顯示」
5. 「參數設定」:按「F」鍵3秒:進入「參數設定」狀態
6. 「警報設定」:按「SET」&「F」鍵3秒:進入「警報設定」狀態
7. 「通訊參數設定」:按「SET」&「▼」鍵3秒:進入「通訊參數設定」狀態
8. 「緩衝起動設定」: 在警報設定的最後一個參數時按「SET」鍵3秒可設定「緩衝起動設定值(SV2)」,固定輸出量由
手動輸出量設定。
9. 「溫升速率控制」: 可設定警報設定層的參數「rAP」;「rAP = 0」時沒有溫升速率控制功能, 「rAP≠0」時執行溫
升速率控制。
10. 「顯示自動切換設定」: 可設定參數設定層的參數「Sdc」;「Sdc = n」時持續顯示「選擇顯示模式」;
「Sdc= A」時10秒後會自動切回「溫度設定值顯示模式」。
01
PID + Fuzzy Intelligent Temperature Controller
NT series
Fixed method Panel type Rail type
Model NT-48 NT-20 NT-21 NT-72E NT-96E NT-22
Outline (U t: mm) 外形尺寸 48*48*72 48*96*60 96*48*60 72*72*60 96*96*60 22.6*75*100
Alarm output 警報輸出 Two alarm Single alarm
Power supply 工作電壓 90~265 VAC/ 50/60 Hz or 24VDC/AC ( Optioned)
Power consumption 消耗電流 5 VA max. or 100mA max.(24VDC/AC)
Input method 輸入方式 PT / K / J / R / S / T/ B / E / N / L(Selectable) or 4~mA or 0~10VDC ( Optioned)
CE, RoHs
Control method 控制方式 Fuzzy + PID or ON / OFF selectable
Control output 控制輸出 Relay or SSR or 4~20mA ( Optioned)
Alarm output 警報輸出 Relay 1a(5A/250VAC SPDT)
Display range 顯示範圍 -999 ~ 9999
Accuracy of display 顯示精度 ± ( 0.1 % OF F.S. + 1 DIGIT)
Setting range 設定範圍 -999 ~ 9999
Memory method 記憶方式 EEPROM
Insulation resistance 絕緣強度 OVER 50MΩ/500VDC
Dielectric strength 耐壓強度 OVER 2.5 KV/ 1 MINUTE
Operating circum. 使用環境 –25℃ ~ 80℃ ; 35%~85% RH
ESD:8 KV Air Discharge(Level3)/ EN-61000-4-2
EMC standard EMC 標準 RF Interference:10V / M / ENV-50140
Burst test:2KV / EN61000-4-4
Controller NO. Id
1 ~ 255 1> Range: 1~255
控制器編號設定 1
Press SET
1>「rs=0」: Modbus-RTU
w w w. f o t e k . c o m . t w
Communication protocol rS
0~1
通訊協定選擇 0 2>「rs=1」: Modbus-ASCII
Press SET
1>「bPS =96」: 9600 bps
Communication speed bPS 2>「bPS =192」: 19200 bps
96 / 192 / 384
通訊速率選擇 192 3>「bPS =384」: 38400 bps
Press SET
Data configuration bIt 8N1 / 8E1 1>「b I t =8N1」: 8 bit non parity
資料結構選擇 8N1 8O1 / 7O1 2>「b I t =8O1」: 8 bit odd parity
3>「b I t =8E1」: 8 bit even parity
Press SET
4>「b I t =8N2」: 8 bit non parity
5>「b I t =7O1」: 7 bit odd parity
6>「b I t =7E1」: 7 bit even parity
02
PID + Fuzzy Intelligent Temperature controller
Auto tuning At
0~1
自動演算 0 2>「At = 1」: Auto tuning status
Press SET
Auto tuning bias tu 0 ~ 99 1> Auto tuning value =「SV - tu」
自動演算偏差值 0
Press SET
Proportion band P 0 ~ 3999 1>「CT = 0」→ 「P」is disappeared
比例帶 36
Press SET
Integral time I
0 ~ 3999 1>「CT = 0」→ 「I」is disappeared
積分時間 120
Press SET
Derivative time d
0 ~ 3999 1>「CT = 0」→ 「d」is disappeared
微分時間 30
Press SET
Hysteresis Hys 1>「CT = 0」→ 「Hys」is appeared only
0 ~ 99 2>「PV>SV)→ Out ON;
動作應差 1
〔PV<(SV-Hys)〕→ Out OFF
Press SET
Gain GAn 0.1~9.9 1> Gain of output control
輸出控制增益 1.0
Press SET
Input selecting Int PT / K / J / R / S 1> 10 input type are selectable
輸入選擇 k T/B/E/N/L
Press SET
Unit selecting Unt ℃/℉
單位選擇 C
Press SET
Decimal point selecting dp
0~1 1> 「d p = 0」:Without decimal point
小數點選擇 0
2> 「d p = 1」:One decimal point
Press SET
Input shift setting Sht
w w w. f o t e k . c o m . t w
03
PID + Fuzzy Intelligent Temperature controller
NT series
Function Range Description
CE, RoHs
AL1 警報設定 50
Press SET
AL2 Limit setting AL2 -999 ~ 9999 1> Refer to the mode of Alarm
AL2 警報設定 50
Press SET
Hysteresis of alarm ALH 0 ~ 9999 Ex. PV≧(SV+AL1)→AL1 ON,
警報應差值設定 1 PV<(SV+AL1-ALH)→AL1 OFF
Press SET
Flick timer t 0 ~ 99 1> Range: 0~99 sec
警報閃爍輸出時間設定 10 2> Cycle time of flick timer
Press SET
Setting limit SLh 0 ~ 9999 1> SV≦SLH
最大設定值限制 400
Press SET
Output limit Out 0 ~ 100% 1> Output volume =
輸出量限制設定 100 Control output volume *「Out」
Press SET
Process output volume Un 0 ~ 99.99 1> Display the output volume
實際輸出量 0.0
Press SET
Max. display value setting dSPH 0 ~ 9999 1> Current or Voltage input type will be appeared only
最大顯示值設定 1000 2> Max. input value will be transmitted into the dSPH
Press SET
Min. display value setting dSPL -999 ~ 9999 1> Current or Voltage input type will be appeared only
最小顯示值設定 0 2> Min. input value will be transmitted into the dSPL
Press SET
Process current of heater Ctu 0 ~ 99.99 1> Range: 0.00 ~ 99.99 A
實際加熱器輸出電流值 0.00
Press SET
Heater break setting Hb 0 ~ 99.99 1> Range: 0.00 ~ 99.99 A
加熱器斷線電流設定值 1.00 2> 「C t u」<「H b」→ AL2 ON
Press SET
CT Low limit setting CtL 0 ~ 99.99 1> Range: -9.99 ~ 99.99
w w w. f o t e k . c o m . t w
NT series
NT - 22-□□ NT – 48-□□
CE, RoHs
NT - 20-□□ NT – 21-□□
NT – 72-□□E NT – 96-□□E
■ Attachment / 附件
w w w. f o t e k . c o m . t w
CT-06: Load current 10 A max CT-09: Load current 30 A max. CT-100: Load current 100 A max.
06
PID + Fuzzy Communication module
NT - 22-□□ NT – 48-□□
CE, RoHs
NT - 20-□□ NT – 21-□□
NT – 72-□□E NT – 96-□□E
陽明電機股份有限公司
FOTEK CONTROLS CO., LTD.