Altivar 18
Altivar 18
Altivar 18
variateurs de vitesse pour moteurs asynchrones, variable speed controllers for asynchronous motors, Frequenzumrichter fr Drehstrom-Asynchronmotoren, variadores de velocidad para motores asncronos.
Merlin Gerin
Modicon
Square D
Telemecanique
Altivar 18
Page 2
F R A N A I S E N G L I S H D E U T S C H E S P A O L
Page 34
Umrichter fr Drehstrom-Asynchronmotoren
Seite 66
Pgina 98
When the speed controller has power on, a number of components are connected to the supply. It is extremely dangerous to touch them. After switching off the supply to the Altivar wait for 1 minute before touching the equipment. This is the time taken for the capacitors to discharge. E N G L I S H During operation the motor can be stopped or started by inhibiting the start command with the speed controller still connected to the supply. For personnel safety during maintenance electronic locking should not be used, the supply should be switched-off.
WARNING
The speed controller incorporates safety devices which can shutdown the speed controller and stop the motor in the event of a fault. These faults may be caused by a mechanical blockage of the motor or alternatively problems with the electrical supply. The removal of the problem may cause the motor to re-start, creating danger for certain machines and installations, especially those which must conform to safety regulations.
In such cases, therefore, the user must take precautions to avoid re-starting of the motor. A device such as a speed detector should be incorporated to remove the supply in the event of an unscheduled stopping of the motor. The equipment has been designed to conform to IEC standards.
In general, power to the speed controller must be switched off before any electrical or mechanical intervention on the installation or machine. The products and materials presented in this document may be changed or modified at any time, either from a technical point of view or in the way they are operated. Their description can in no way be considered contractual.
NOTE
34
Warning
The Altivar 18 must be considered a component. It is neither a machine nor a piece of equipment ready for use in accordance with European directives (machinery directive and electromagnetic compatibility directive). It is the responsibility of the user to ensure that his machine meets these standards. E N G L I S H
This speed controller must be installed and set up in accordance with international and national standards. This compliance is the responsibility of the systems integrator who must respect the European community EMC directive amongst others. The specifications contained in this document must be applied in order to comply with the essential requirements of the EMC directive.
35
E N G L I S H
36
Contents
The "Altivar 18" Preliminary checks Choice of speed controller Available torque Technical characteristics Dimensions - Mounting recommendations Mounting in a wall-fixing or floor standing enclosure Electromagnetic compatibility Accessing terminals - Power terminals Control terminals Connection diagram Functions which do not require adjustment Logic and analog input functions which can be configured Function compatibility table Installation Maintenance - Replacement and repairs Maintenance assistance 34 38 38 39 40 41 42 43 44 and 45 46 47 48 49 to 51 52 53 to 62 63 64 E N G L I S H
37
Preliminary checks
Remove the Altivar 18 from its packaging, and check that it has not been damaged in transit. Check that the reference of the speed controller on the label is the same as that on the delivery note and corresponds to the order form.
200240 4.4 50/60 Hz single phase 7.6 13.9 E N G L I S H 19.4 200230 50/60 Hz 3-phase 16.2 20.4 28.7 38.4 380460 50/60 Hz 3-phase 2.9 5.1 6.8 9.8 12.5 16.9 21.5 31.8 42.9
The Altivar 18 is designed to supply the required power for the appropriate motor.
38
Available torque
Continuous operation
For self-ventilated motors, motor cooling is linked to speed. Derating occurs at speeds of less than half the nominal speed.
Operation in overspeed
Since the voltage can no longer change with the frequency, there is a decrease in motor induction resulting in a loss of torque. Consult the manufacturer to find out whether the machine can operate in overspeed. Torque characteristics :
T/Tn 1,5 1,2 1 0,95
1 2
Continuous usable torque : self-ventilated motor Continuous usable torque : force-ventilated motor Transient overtorque : typical curve at 10 % Value : 1.5 Tn for 60 s E N G L I S H
1 3
0,5
0 1 25 30 50 60
N (Hz)
Note : With a special motor, the nominal frequency and the maximum frequency can be adjusted from 40 to 320 Hz.
39
Technical characteristics
Environment
Degree of protection Vibration and shock resistance in accordance with EN50178 Degree of pollution Relative maximum humidity Ambient air temperature in accordance with EN50178 IP31 IP20 without the blanking cover on the top 0.6 gn from 10 to 50 Hz 2 gn from 50 to 150 Hz Degree 2 according to IEC664. Protect the speed controller from dust, corrosive gases, splashing liquid, etc. 93 % without condensation or dripping water. If there is a risk of condensation, provide a heating system For storage : - 25 C to + 65 C For operation : - 10 C to + 40 C without derating, with the blanking cover - 10 C to + 50 C without derating, without the blanking cover 1000 m without derating. Above this, derate the current by 3 % for each additional 1000 m
Electrical characteristics
Power supply Voltage - single phase : 200 V - 15 % to 240 V + 10 % - 3-phase : 200 V - 15 % to 230 V + 10 % 380 V - 15 % to 460 V + 10 % 50/60 Hz 5 % Maximum voltage equal to mains voltage 0.5 to 320 Hz 150 % of speed controller nominal current for 60 seconds 30 % of the nominal motor torque without brake resistor (typical value). Up to 150 % with brake resistor as an option - Display : 0.1 Hz - Analog inputs : 0.1 Hz for 100 Hz maximum Can be adjusted from 2.2 to 12 kHz - Electrical isolation between power and control circuits (inputs, outputs, supplies) - Protection against short-circuits : . internal supplies available . between output phases U - V - W . between the output phases and earth for ratings 5.5 to 15 kW - Thermal protection from excessive overheating and overcurrents - Under and overvoltage supply - Overvoltage safe on braking Protection integrated in the speed controller by calculating I2t
Frequency Output voltage Output frequency range Maximum transient current Braking torque Frequency resolution Switching frequency Speed controller protection and safety
Motor protection
40
G a
ATV18 U09M2, U18M2 U29M2, U18N4, U29N4 U41M2, U54M2, U72M2, U41N4, U54N4, U72N4 U90M2, D12M2, U90N4, D12N4 D16N4, D23N4
5 5 6 7 10
Mounting recommendations
Mount the unit vertically. Avoid placing close to any heating equipment. Leave enough free space to ensure that sufficient air can circulate for cooling. The unit is ventilated from the bottom upwards. IP2O : remove the blanking cover from the top (self-adhesive film). Ventilation flow rate
100
E N G L I S H
ATV-18U09M2, U18M2, U18N4 : not ventilated. ATV-18U29M2, U29N4 : 0.25 m3/minute. ATV-18U41M2, U54M2, U72M2, U41N4, U54N4, U72N4 : 0.75 m3/minute. ATV-18U90M2, D12M2, U90N4, D12N4, D16N4, D23N4 : 1.3 m3/minute.
50
50
100
41
40 C
40 C
E N G L I S H
Power dissipated by the speed controller : see page 38. Add the power dissipated by the other equipment. Useful heat dissipation surface of the enclosure S (m2) : (sides + top + front, when the controller is wall-mounted) S= K Rth For a metal enclosure : K = 0.12 with an internal fan, K = 0.15 with no fan. Warning : Do not use insulated enclosures, as they have a poor level of conductivity. K = thermal resistance per m2 of the enclosure.
42
Electromagnetic compatibility
Installation : to comply with standards EN55011 class A, EN61800-3, IEC1800-3.
General rules - Grounds between speed controller, motor and cable shielding must have "high frequency" equipotentiality. - Use shielded cables with shielding connected to the ground at 360 at both ends of the motor cable and the control cables. This shielding can be conduit or metal ducting as long as there is no break in continuity. Installation diagram
1 2
ATV 18
E N G L I S H
3 4
6 7
1- Mounting plate, unpainted flat sheet steel, with anti-corrosion treated conductors (machine ground wiring). Painted steel can be used on condition that good electrical contact is ensured between the mounting surfaces with 2 and 5. 2- Altivar 18 fixed directly to the mounting plate (equipotential grounds). 3- Non-shielded supply wires or cable for connecting the line choke, if used. 4- Non-shielded wires for fault relay contact output wires. 5- The shielding for cables 6 and 7 should be fixed and grounded as close to the controller as possible : - strip the shielding, - use the correct size clamps on the stripped parts of the shielding to fix to the backplate, - type of clamps : stainless steel. The shielding must be clamped tightly enough to the backplate for the contacts to be good. 6- Shielded cable for connecting the motor, with shielding connected to ground at both ends. This shielding must be uninterrupted, and any intermediate terminal blocks must be in an EMC shielded metal case. 7- Shielded cable for connecting the control/command system. For uses which may require several conductors, small cross sections should be used (0.5 mm2). The shielding must be connected to ground at both ends. This shielding must be uninterrupted, and any intermediate terminal blocks must be in an EMC shielded metal case. Note : The HF equipotential ground connection between speed controller, motor and cable shielding does not remove the need to connect the protective conductors PE (green-yellow), to the appropriate terminals on each of the units.
43
DATA
ENT
E N G L I S H
Speed controllers are fitted with metal gland plates equipped with rubber blanking plugs which can be perforated to enable cables to be passed through them and also to protect the cables.The gland plates can take EMC metal cable glands.
Power terminals
Terminal characteristics Maximum connection capacity AWG U09M2, U18M2 U29M2, U41M2 U54M2, U72M2 U18N4, U29N4 U41N4, U54N4 U72N4 U90M2, D12M2, U90N4, D12N4 D16N4, D23N4 AWG14 mm2 2.5 Tightening torque in Nm 1
Altivar ATV-18
AWG10
1.2
AWG8 AWG6
10 16
2.4 4
44
Power terminals
Function of terminals For Altivar ATV-18 All ratings 3-phase only All ratings All ratings All ratings
Terminals L1 L2 L3 s
Function
PA PB U V W s
All ratings
All ratings E N G L I S H
s
Terminal connections
L1 L2
PA PB U
L1 L2 L3
PA PB U
PA PB L1 L2 L3 s U V W s
45
Control terminals
Maximum connection capacity : 1.5 mm2, AWG16. Tightening torque : 0.5 mN Factory preset speed controller configuration. Control terminal block electrically isolated from power terminal block. Terminal SA SC SB +10 AI1 AI2 AIC Function Characteristics
C/O contact of the fault relay. Contact switching capacity : Activated when speed controller - minimum 10 mA for 5 Va powered-up, - maximum on inductive load (cos 0.4, L/R 7 ms) no fault 1.5 A for 250 Vc and 1.5 A for 30 Va Power supply for setpoint potentiometer 1 to 10 k Voltage speed reference Voltage setpoint or Current setpoint, summing of AI1 10 V
+15%
+0
10 mA maximum, protected
Analog input 0 + 10 V impedance 30 k Analog input 0 + 10 V impedance 30.55 k or analog input 0 - 20 mA (factory preset) or 4 - 20 mA, impedance 400 AI2 or AIC can be assigned. Do not use them both at the same time.
E N G L I S H
COM
Common for logic and analog inputs and the logic output Run forward command Run reverse command Preset speeds Logic input and output supply Logic output supply Speed reference reached Logic inputs impedance 3.5 k Power supply + 24 V (maximum 30 V) State 0 if < 5 V, state 1 if > 11 V LI2, LI3, LI4 can be assigned + 24 V protected, maximum rate 100 mA To be connected to the internal + 24 V or to the + 24 V (maximum 30 V) of an external supply PLC compatible logic output (open collector) + 24 V maximum 20 mA with internal supply or 200 mA with external supply. LO can be assigned.
46
Connection diagram
Connection diagram with factory preset values
3-phase power supply
Single phase power supply Other connections (external 24 V supply) (1) (2)
LI1 LI2 LI3 LI4 LI2 LI3 +24 LI4 L2 L3 +24 +24 V LO+ LI1 L1 SB SC SA
(4)
(4)
COM
W1
U1
V1
M 3c
KA (3)
0V
COM
LO+
+10
AIC
AI1
AI2
PO PA PB
LO
24 V supply
(1) Line choke if required (1 phase or 3 phases). (2) Fault relay contacts, for remote signalling of the speed controller state. (3) PLC relay or input a 24 V. (4) + 24 V internal. When using a + 24 V external supply, connect the 0 V to the COM terminal, and do not use the + 24 terminal of the speed controller. Note : Suppressors should be fitted to all inductive circuits close to the speed controller or connected on the same circuit (relays, contactors, solenoid valves, etc).
E N G L I S H
Wiring recommendations
Power Follow the cable cross-section recommendations specified in the standards. The speed controller must be earthed, in order to comply with regulations concerning high leakage currents (over 3.5 mA). Upstream protection by differential circuit-breaker is not advised as DC elements may be generated by leakage currents from the speed controller. If the installation has several speed controllers on the same supply, connect each speed controller to earth separately. If necessary, provide a line choke (consult the catalogue). Keep the power cables apart from low-level signal circuits (detectors, PLCs, measuring equipment, video, telephone). Control Keep the control circuits and the power cables apart. For control circuits and speed reference circuits, it is advisable to use a shielded, twisted pair cable at intervals of between 25 and 50 mm by connecting the shielding at each end.
47
48
LI2, LI3, LI4 : can be assigned to the following functions : - reverse direction : rrS assignment When the contact is closed, the frequency setpoint is applied in reverse direction. If LI1 is also closed, the first one to have been closed has priority.
LI2 LI3 LI4 +24
- 2 speeds : PS2 assignment Open contact : reference = LSP + analog reference. Closed contact : reference = HSP.
LI2 LI3 LI4 +24
- 4 speeds : assignment of one input to PS2 and another to PS4 (it is not possible to assign PS4 only) K1 and K2 open : setpoint = L5P + analog setpoint. K1 closed and K2 open : setpoint = SP3 (level 1 adjustment). K1 open and K2 closed : setpoint = SP4 (level 1 adjustment).
LI2 LI3 LI4 (PS4) LI2 LI3 LI4 (PS2) +24
K2 K1
E N G L I S H
49
+24
JOG
Operating direction
Reference
Ref.
JOG
Ref.
JOG
JOG
E N G L I S H
Frequency
Note : 1- During "jog" operation, automatic DC injection braking when the motor is stopped is inhibited. 2- Injection braking on the logic input has priority over JOG operation. Fast stop : FSt assignment Note : Fast stop command is activated when the contact between the input and the + 24 V is open.
LI2 LI3 LI4 +24
Braked stop, with the dEC ramp time divided by 4, but limited to the acceptable minimum without locking on an "excessive braking" fault (self-adaptation if the braking capability is exceeded). Note : During fast stop, braking either by automatic DC injection or on the logic input is inhibited. DC injection braking : dCI assignment Note : Injection braking command is activated when the contact between the input and the + 24 V is closed.
LI2 LI3 LI4 +24
The braking current is equal to the speed controller nominal current during 5 seconds. After 5 seconds, braking current is peak limited to a maximum value of 0.5 ItH motor. Note : 1- Automatic injection braking when stopped remains active if the dCI function is assigned. 2- Fast stop has priority over injection braking.
50
PI regulator feedback : PIF assignment This assignment automatically configures AI1 as a reference for the PI regulator.
P I
Ref.
E N G L I S H
Adjustment parameters rPG, rIG and FbS are in level 1. - AIC parameter setting : 0 - 20 mA or 4 - 20 mA. Note : The PI function is not compatible with certain logic input functions : - preset speeds (2 or 4), - jog operation (JOG).
51
Reverse direction
Forward direction
Summing input
Non-compatible functions Compatible functions not significant Function priority (Functions unable to be used at the same time) :
The function indicated by the arrow has priority over the other one.
The choice of functions is limited by the number of configurable logic inputs (3). Functions using configurable logic inputs : - One input for each function : reverse direction, D.C. braking, fast stop, jog, 2 preset speeds. - Two inputs for the function : 4 preset speeds.
52
E N G L I S H
Preset Speeds
PI regulator
Fast stop
Jog
Installation
The Altivar is factory preset for standard applications : - applications with constant torque.
Preset values
Display : speed controller ready (when stopped), motor frequency (in operation). Supply : 50 Hz. Motor voltage : 230 V or 400 V, depending on the product. Ramps : 3 seconds. Low speed : 0 Hz - High speed : 50 Hz. Frequency loop gain : standard. Thermal motor current = nominal speed controller current. Injection braking current when stopped = 0.7 nominal speed controller current, for 0.5 seconds. Operation at constant torque, with sensorless flux vector control. Logic inputs : . 2 operating directions (LI1, LI2), . 4 preset speeds (LI3, LI4) : 0 Hz, 5 Hz, 25 Hz, 50 Hz. Analog inputs : . AI1 : speed reference 0 + 10 V, . AI2 (0 + 10 V) or AIC (0, 20 mA) summing of AI1. Logic output : . LO : speed reference reached. Automatic adaptation of the deceleration ramp if there is overvoltage on braking. Switching frequency of 4 kHz.
If the above values are compatible with the application, the speed controller can be used without modifying the settings. In power control with line contactor : - avoid frequent operation of contactor KM1 (premature ageing of capacitors), use inputs LI1 to LI4 to control the speed controller, - in the case of cycles < 60 s, these measures are essential, otherwise the load resistor may be destroyed.
E N G L I S H
53
Installation
Integrated display terminal
Functions of keys and display
rdY
Goes to the previous parameter or increases the value displayed Goes to the next parameter or decreases the value displayed
DATA ENT
Saves the parameter or value displayed Switches between the parameter type and its numerical value
E N G L I S H
Normal display (no faults and after installation). - Init : Initialization sequence. - rdY - 40 - dcb : Speed controller ready. : Display of the frequency setpoint. : DC injection braking in progress.
Modifying the value, state or assignment : Pressing or does not memorize the selection.
Memorizing, saving the selection displayed : The display flashes during memorization. Return to parameters :
DATA
ENT
54
Installation
Using the integrated display terminal
Example 1 : ramp adjustment
bFr
(1 flashing)
DATA
{8
ENT
{8
DATA
FLt
(1 flashing)
DATA
no
YES
access to second level
ENT
YES
DATA
LI4
(1 flashing)
LO LO A I C Etc.
DATA
SrA
FtA
ENT
FtA
DATA
55
Installation
Hierarchical access to parameters
UFt
* tUn
UnS FrS tFr brA
ACC dEC LSP HSP FLG ItH JPF IdC tdC UFr FLt L2A = no L 2 A Access to level 2 L2A = YES
YES no
* SLP
tLS LI2
SP3
LI3 LI4 LO AIC CrL SPr SFr StP Atr FCS CPU
Adjustment can be modified when stopped and when running
L2A = YES
Display Configuration can only be modified when stopped
Installation
Adjustment of the speed controller (level 1 parameters)
Factory preset Maximum Minimum value value Resolution (minimum increment)
Function Speed controller ready Frequency setpoint Motor current Frequency of rotation Mains voltage
Choice of parameter displayed during operation (1)
Unit
Type Display
FrH
Hz A Hz V 60 50 Hz
50
The value of bFr presets the nominal motor frequency and voltage to the following values : ATV18M2 : - bFr = 50 : 230 V/50 Hz - bFr = 60 : 230 V/60 Hz ATV18N4 : - bFr = 50 : 400 V/50 Hz - bFr = 60 : 460 V/60 Hz These presets can be modified in level 2 parameters. ACC dEC Linear acceleration ramp 0 3600 1 s Linear deceleration ramp 0 3600 1 s The ramps are defined for the base frequency. Example : ramp 10 s : - if bFr = 50 Hz, 5 s needed for variation of 25 Hz, - if bFr = 60 Hz, 5 s needed for variation of 30 Hz. Low speed High speed : ensure that this setting is suitable for the motor and the application. 0 50 = HSP = tFr (2) 0 = LSP Hz Hz 0.1 or 1 Adjust. 0.1 or 1 Adjust. (0.1 to 999.9 then 1000 to 3600) 0.1 0.1 Adjust. Adjust.
E N G L I S H
LSP HSP
FLG
Frequency loop gain 33 100 0 1 Adjust. Linked to the inertia and resistive torque of the driven mechanism : - machines with high resistive torque or high inertia : gradually reduce to between 33 and 0, - machines with fast cycles, low resistive torque and low inertia : gradually increase the gain to between 33 and 100. Too high a gain may lead to unstable operation 1.15 IN 0.5 IN A 0.1 Adjust. Motor thermal protection (4). IN Adjust ItH to nominal current (3) (3) (3) shown on the motor rating plate. To inhibit thermal protection, increase the value up to its maximum value.
ENT
ItH
the machine stops or goes to the next parameter. (2) tFr is a level 2 parameter which can be adjusted from 40 to 320 Hz, preset at 60 Hz. For HSP > 60 Hz, modify the setting of tFr beforehand (level 2). (3) IN = speed controller permanent output current. (4) Warning : - in the case of motors connected in parallel on a single speed controller, used thermal relay for each motor to offset the risk of the load not being distributed. - if the speed controller is switched off the I2t calculation changes to zero.
57
Installation
Adjustment of speed controller (level 1 parameters)
Factory preset Maximum Minimum value value Resolution (minimum increment)
Code JPF
Function
Unit
Type
Cancellation of a critical speed 0 HSP 0 Hz 0.1 Adjust. which leads to mechanical resonance : it is possible to prevent prolonged operation in a 2 Hz frequency range, which can be adjusted anywhere between LSP and HSP. f 2 Hz JPF Factory preset of 0 deactivates the function.
Setpoint
Idc tdc
0.7 IN (1)
IN (1)
0.25 ItH
0.1
Adjust. Adjust.
Automatic injection braking time 0.5 25.5 0 s 0.1 when stopped. Setting of 0 cancels the injection when stopped, setting to 25.5 makes this permanent (2). Parameter enabling the torque to be optimized at a very low speed 3rd preset speed 4th preset speed Setpoint in "jog" operation 20 S 25 10 100 HSP HSP 10 0 LSP LSP 0 Hz Hz Hz 1 0.1 0.1 0.1
E N G L I S H
UFr
* * * * * * *
Frequency threshold associated with 0 HSP LSP Hz 0.1 the "frequency threshold reached" function of output LO. This threshold comprises an anti-repeat hysteresis of 0.2 Hz. Proportional gain of the PI regulator function Integral gain of the PI regulator function Multiplication coefficient of feedback of PI regulator function, associated with analog input AIC or AI2. Display of the last fault which occurred, by pressing the
DATA
1 1 1
01 01 1 1/s
01 01 1
FLt
Display
key.
When no fault has occurred the display reads : nErr . L2A Access to level 2 parameters. no : no no YES no Configuration
yes : YES the next display will be the first parameter of level 2 if
(1) IN = speed controller permanent output current. (2) Warning, the configuration parameters cannot be modified during braking. Set 25.5 s as the last operation if permanent braking is required. These parameters only appear if the associated functions are selected. Example : SP3 and SP4 only appear as a factory preset.
58
Installation
Extension of functions (level 2 parameters)
Factory preset Maximum Minimum value value Resolution (minimum Type increment) Configuration
Code UFt
Function
Unit
Selection of the type of n nLd L voltage/frequency ratio - L : constant torque for motors connected in parallel or special motors - P : variable torque - n : sensorless flux vector control for applications with a constant torque - nLd : energy saving, for applications with variable torque
tUn
Auto-tune no YES no ConfiguOnly active for V/F ratios : ration n and nLd - no : no (factory parameters of standard IEC motors) - donE (auto-tune has already been performed) : auto-tune parameters already in use - YES : triggers auto-tune. When auto-tune is completed, rdY is displayed. Returning to tUn, donE appears next. If the tnF fault appears, it is because the motor is not adapted : use L or P mode. Nominal motor voltage. ConfiguUse the value shown on the motor ration rating plate. Maximum, minimum and factory preset values depend on the model and the bFr parameter (level 1) ATV18M2. 230 240 200 V 1 ATV18N4 .bFr = 50 400 460 380 V 1 ATV18N4. bFr = 60 460 460 380 V 1 Nominal motor frequency bFr 320 40 Use the value shown on the motor rating plate if it is different from the supply frequency set by bFr Maximum output frequency 60 320 40 Hz 1 Configuration Configuration
UnS
E N G L I S H
FrS
tFr brA
Hz
Automatic adaptation of the YES YES no Configudeceleration ramp time, if the latter ration leads to overvoltage on braking. This function prevents tripping when there is a ObF fault. YES : Active function, no : Inactive function This function may be incompatible with ramp positioning and with the use of a brake resistor. Slip compensation (1) 5 This parameter only appears if the UFt mode is configured for n mode. The value in Hz corresponds to the slip in nominal torque 0 Hz 1 Adjust.
SLP
59
Installation
Extension of functions (level 2 parameters)
Factory preset Maximum Minimum value value Resolution (minimum increment)
Code tLS
Function
Unit
Type
Limiting of operation time at 0 2{5 0 s 1 Adjust. low speed (zero setpoint and start command present). tLS = 0 : function inactive. Automatic restart occurs on the ramp when the reference reappears or after a break when the start command is reestablished. Reassignment of logic input LI2 Ensure that the logic inputs are switched off beforehand. - If a function has already been assigned to another input, it will still appear, but
ENT
LI2
E N G L I S H
to be memorized. - If functions PS2 and PS4 are both assigned, any change to the assignment of the input linked to the function PS2 will only be recognized when the assignment of the input linked to the PS4 function has been changed. When AIC is assigned as a rrS PS4 OFF summing input for AI1 and one of the logic inputs is assigned to PS2 (1) : - OFF : not assigned - rrS : "reverse" rotation direction (2 operating directions) - dCI : fixed DC injection braking (In speed controller for 5 s, then 0.5 Ith) - FSt : fast stop. This function is active when the input is switched off - JOG : jog operation (2) - PS2 : 2 preset speeds - PS4 : 4 preset speeds (2) When AIC is assigned as PI regulator feedback : - OFF See functions - rrS and - dCI comments - FSt above When no logic input is assigned to PS2 : - OFF - rrS See functions - dCI and - FSt comments - JOG above - PS2 rrS FSt OFF Configuration
Configuration
rrS
PS2
OFF
Configuration
(1) This is the case for a factory preset. (2) These functions display the corresponding adjustments in level 1 parameters. Set these parameters (JOG, SP2, SP4).
60
Installation
Extension of functions (level 2 parameters)
Factory preset PS2 PS4 SrA Maximum Minimum value value " " " " Resolution (minimum increment)
Function Reassignment of logic input LI3 : same as LI2 Reassignment of logic input LI4 : same as LI2 Assignment of the logic input 1) SrA : speed reference reached by the motor, with a threshold of 2,5 Hz
Reference
Unit
SrA
FtA
+2,5 Hz
Speed
-2,5 Hz +2,5 Hz
-2,5 Hz
LO
Note : If the reference is less than 0.5 Hz, the output LO is reset to 0. AIC Assignment of the analog input AIC/AI2.
Assigning FtA causes the Fdt setting to appear in level 1 parameters. Set this parameter
E N G L I S H
If the logic inputs are not assigned SAI PIF SAI Configuto the preset speeds (PS2 - PS4) ration or to jog operation (JOG) : - SAI : Summing with AI1 - PIF : PI regulator feedback. This configuration automatically assigns input AI1 as the regulator reference and displays the adjustments in the level 1 parameters : rPG, rIG, FbS. Note : This configuration is only possible if the user has previously been using the following configurations, in the order : 1) LI4 = OFF or FSt 2) LI3 = OFF or dCI 3) LI2 = OFF or rrS If a logic input is assigned SAI to the preset speeds (PS2 - PS4) or to jog operation (JOG) : - SAI : Summing with AI1 CrL Configuration of input AIC/AI2 : - 0 : AIC : 0 - 20 mA / AI2 : 0 + 10 V - 0 : AIC : 4 - 20 mA / AI2 : 2 + 10 V 0 SAI SAI Configuration
mA
Configuration
61
Installation
Extension of functions (level 2 parameters)
Factory preset Maximum Minimum value value Resolution (minimum increment)
Code SPr
Function
Unit
Type
Automatic catching a spinning load no YES no Configuwith speed search. After a short ration power break, the motor restarts on a ramp using its effective speed. The speed search time canreach 3.2 s. The speed reference and operating direction should be maintained on a restart. - no : Function not active - YES : Function active Switching frequency 0 10 2 kHz 1 Adjust. The switching frequency can be adjusted to reduce the noise generated by the motor. Over 4 kHz, derating must be applied to the output current of the speed controller, depending on the model : - ATV-18U09M2, U18M2, U29M2, U41M2, U54M2 : no derating, - other references : . up to 8 kHz : 5 % derating, . over 8 kHz : 10 % derating. Controlled stop on power break : no YES no ConfiguControl of motor stopping during a ration power break, following a ramp which is self adapting as a function of the restored kinetic energy. - no : Function inactive - YES : Function active Automatic restart, after no YES no Configulocking on fault, if the fault is no ration longer present and the other operating conditions allow. To restart, a series of automatic attempts are performed at increasing intervals : 1 s, 5 s, 10 s, then 1 min for subsequent attempts. If the start has not been achieved after 6 min, the procedure is abandoned and the speed controller remains locked until it is switched off and then switched on again. The faults which enable this function are : OHF, OLF, USF, ObF, O5F. The fault relay of the speed controller then remains activated if the function is active. The speed setpoint and the operating direction must be retained. Ensure that an unespected restart does not present any risk to people or equipment. - no : Function inactive - YES : Function active Return to the factory preset no : no YES : yes, the next display will be rdY Software version (information) Display of the software version no YES no Configuration
SFr
E N G L I S H
StP
Atr
FCS
CPU
Display
62
Maintenance
The Altivar 18 does not require any preventive maintenance. However, the user is advised to do the following at regular intervals : - check the state and tightness of connections, - ensure that the temperature in the area around the equipment remains at an acceptable level, and that ventilation is effective (average lifetime of fans : 3 to 5 years depending on the conditions of use), - ensure the speed controller is free from dust.
Maintenance assistance
The first fault detected is memorized and displayed on the display if the voltage is maintained : the speed controller locks itself and the fault relay trips. Clearing the fault Remove the power supply to the speed controller. Find the cause of the fault in order to eliminate it. Reconnect the power supply : this will clear the fault if it has been corrected. In some cases the equipment may automatically restart after the fault has disappeared, if this function has been programmed.
E N G L I S H
63
Maintenance assistance
Faults which can be reset with the automatic restart function, after the cause of the fault has been corrected Fault OHF speed controller overload OLF motor overload OSF overvoltage in steady state or during acceleration USF under voltage ObF overvoltage on deceleration Probable cause - I2t too high or - speed controller temperature too high - I2t motor too high Remedies - Check the motor load, the speed controller ventilation and the environment. Wait for it to cool before restarting. - Check the setting of the motor thermal protection, and check the motor load. Wait for it to cool before restarting. - Check the mains voltage.
- Mains supply voltage too low - Momentary drop in voltage - Weakened load resistance - Braking too abrupt or driving load
- Check the voltage and the voltage parameter. - Reset. - Change the load resistance. - Increase the deceleration time. - Add brake resistor if necessary. - Activate the function brA if it is compatible with the application.
E N G L I S H
Faults which cannot be automatically reset. The cause of the fault must be corrected before resetting by switching the controller off and then on again Fault OCF overcurrent Probable cause - Short-circuit or earthing at speed controller output - Overcurrent in the brake resistor Remedies - Having disconnected the speed controller, check the connection cables, motor isolation and state of the windings. - Check the resistor selected. Having disconnected the speed controller, check the connection cables, insulation of the resistor and its ohmic value. - Check the brake resistor selected. Check the ohmic resistance value. Ensure that the speed controller rating is suitable for the application. - Check the environment (electromagnetic compatibility). - Return the speed controller for servicing/repair. - Use L or P mode.
- Internal fault
- Special motor - Power motor not adapted to the speed controller - Internal fault
64
E N G L I S H
65
75962
1997-07
VVDED396037