CRCC
CRCC
Commercial Refrigeration
Condensed Product Catalog
Technical Bulletin: CRCC_017_051023
Hussmann / Krack will ship DOE / NRCan compliant evaporators and condensing units for covered applications to meet
and adhere with government labeling requirements. Please note that compliance is at the time of manufacture
and responsibility of the OEM.
The DOE / NRCan compliant evaporators will utilize dual speed or variable speed motors. Controls for these options
may be factory installed or field supplied.
Both the dual speed and variable speed motors have default prevention programming. In the event of a control loss
input (0V), the motors will run at full speed.
Table of Contents
Standard Features
Dual Discharge Center Mount – Low Height
At 9-1/4" maximum height, the LH Series is perfect for low clearance walk-in applications in
convenience stores, restaurants, food service or other applications held at -20° F or warmer.
n Center mounted models are flush mounted to the ceiling to not interfere with shelving.
n Two-way air discharge provides smooth air movement keeps product fresh longer with
less product shrink.
n Standard EC motors are two speed 1/15 horsepower and multi-voltage operating on
100-240/1/50-60 power.
n Coil constructed of heavy-wall copper tube and rippled full collar aluminum fins.
n Optimized circuiting for HFC and HFO refrigerants.
n Sealed and pressurized from the factory.
n Factory-wired fans and defrost controls to convenient terminal strips for field connections.
n Plug in motor leads for quick positive connection to wiring harness.
LH D 2 6 E - 129 T D A A
* PSC motors are not allowed in USA or Canada for any evaporator solution.
DOE / NRCan applications will require Dual Speed or Variable Speed fans.
** ‘N’ Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
*** ‘G’ Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
* PSC motors are not allowed in USA or Canada for any evaporator solution.
DOE / NRCan applications will require Dual Speed or Variable Speed fans. Use your QR reader to
** ‘N’ Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing). reference current document
*** ‘G’ Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing). version on www.krack.com.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
AIR DEFROST
COOLER AWEF BY REFRIGERANT and MOTOR AIR DEFROST
[G] STOCK UNIT**, [N] STOCK UNIT***,
COOLER AWEF BY REFRIGERANT and MOTOR
[Q] R-407A, [F] R-407F, [S] R-404A, REFRIGERATION
CAPACITY
[T][G] STOCK
R-448A, UNIT**,
[R] R-449A [N] STOCK UNIT***,
[P] R-507A CONNECTIONS DIMENSIONS (IN)
[Q] R-407A, [F] R-407F, [S] R-404A, (BTU/H) AIR REFRIGERATION REF SHIP
{D}ual {V}ariable {D}ual {V}ariable @CAPACITY
10° F TD FLOW CONNECTIONS CHARGE WGT
[T] R-448A, [R] R-449A [P] R-507A DIMENSIONS (IN)
MODEL Speed Speed Speed Speed (BTU/H)
+25° F EVAP AIR
(CFM) LIQ SUCT (LBS) REF L W H SHIP
(LBS)
{D}ual {V}ariable {D}ual {V}ariable @ 10° F TD FLOW CHARGE WGT
LH*16A-047[
MODEL ]{ } 9.00
Speed 9.00
Speed N/A
Speed 9.00
Speed 4,700
+25° F EVAP 650
(CFM) 1/2" 7/8"
LIQ SUCT (LBS) 2 32.88
L 26.06
W 9.25
H 42
(LBS)
LH*26A-094[ ]{ } 9.00 9.00 N/A 9.00 9,400 1,300 1/2" 7/8" 3 54.88 26.06 9.25 70
LH*16A-047[ ]{ } 9.00 9.00 N/A 9.00 4,700 650 1/2" 7/8" 2 32.88 26.06 9.25 42
LH*36A-140[ ]{ } 9.00 9.00 N/A 9.00 14,000 1,950 1/2" 7/8" 4 76.88 26.06 9.25 123
LH*26A-094[ ]{ } 9.00 9.00 N/A 9.00 9,400 1,300 1/2" 7/8" 3 54.88 26.06 9.25 70
LH*46A-187[ ]{ } 9.00 9.00 N/A 9.00 18,700 2,600 1/2" 1-1/8" 5 98.88 26.06 9.25 164
LH*36A-140[ ]{ } 9.00 9.00 N/A 9.00 14,000 1,950 1/2" 7/8" 4 76.88 26.06 9.25 123
LH*14A-036[
LH*46A-187[ ]{
]{ }} 9.00
9.00 9.00
9.00 N/A
N/A 9.00
9.00 3,600
18,700 680
2,600 1/2"
1/2" 7/8"
1-1/8" 25 32.88
98.88 26.06
26.06 9.25
9.25 38
164
LH*24A-073[ ]{ } 9.00 9.00 N/A 9.00 7,300 1,370 1/2" 7/8" 3 54.88 26.06 9.25 64
LH*14A-036[ ]{ } 9.00 9.00 N/A 9.00 3,600 680 1/2" 7/8" 2 32.88 26.06 9.25 38
LH*34A-109[ ]{ } 9.00 9.00 N/A 9.00 10,900 2,050 1/2" 7/8" 4 76.88 26.06 9.25 105
LH*24A-073[ ]{ } 9.00 9.00 N/A 9.00 7,300 1,370 1/2" 7/8" 3 54.88 26.06 9.25 64
LH*44A-145[ ]{ } 9.00 9.00 N/A 9.00 14,500 2,730 1/2" 1-1/8" 5 98.88 26.06 9.25 146
LH*34A-109[ ]{ } 9.00 9.00 N/A 9.00 10,900 2,050 1/2" 7/8" 4 76.88 26.06 9.25 105
LH*44A-145[ ]{ } 9.00 9.00 N/A 9.00 14,500 2,730 1/2" 1-1/8" 5 98.88 26.06 9.25 146
ELECTRIC DEFROST
ELECTRIC
AWEF BY REFRIGERANT, MOTOR, and APPLICATION DEFROST
[G] STOCK UNIT**, [N] STOCK UNIT***,
AWEF BY REFRIGERANT, MOTOR, and APPLICATION
[Q] R-407A, [F] R-407F, [S] R-404A,
[T][G] STOCK
R-448A, UNIT**,
[R] R-449A [N] STOCK UNIT***,
[P] R-507A
[Q] R-407A, [F] R-407F, [S] R-404A, CAPACITY CAPACITY REFRIGERATION
DIMENSIONS (IN)
[T]{D}ual {V}ariable {D}ual {V}ariable CONNECTIONS
R-448A, [R] R-449A [P] R-507A (BTU/H) (BTU/H) AIR REF SHIP
Speed Speed Speed Speed
CAPACITY CAPACITY REFRIGERATION
{D}ual {V}ariable {D}ual @ 10° F TD
{V}ariable @ 10° F TD FLOW CONNECTIONS CHARGE DIMENSIONS (IN) WGT
MODEL Freezer Cooler Freezer Cooler
(BTU/H)
-20° F EVAP
Freezer Cooler Freezer Cooler
(BTU/H)
+20° F EVAP AIR
(CFM) LIQ SUCT REF
(LBS) L W H SHIP
(LBS)
Speed Speed Speed Speed
@ 10° F TD @ 10° F TD FLOW CHARGE WGT
LH*16E-043[
MODEL ]{ } 4.15 Cooler
Freezer 9.00 Freezer
4.15 9.00 Freezer
Cooler N/A Cooler
N/A Freezer
4.15 Cooler
9.00 -20° 4,300
F EVAP +20°4,700
F EVAP 650
(CFM) 1/2"
LIQ 7/8"
SUCT 2
(LBS) 32.88
L 26.06
W 9.25
H 44
(LBS)
LH*26E-086[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 8,600 9,400 1,300 1/2" 1-1/8" 3 54.88 26.06 9.25 73
LH*16E-043[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 4,300 4,700 650 1/2" 7/8" 2 32.88 26.06 9.25 44
LH*36E-129[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 12,900 14,000 1,950 1/2" 1-1/8" 4 76.88 26.06 9.25 127
LH*26E-086[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 8,600 9,400 1,300 1/2" 1-1/8" 3 54.88 26.06 9.25 73
LH*46E-171[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 17,100 18,700 2,600 1/2" 1-1/8" 5 98.88 26.06 9.25 169
LH*36E-129[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 12,900 14,000 1,950 1/2" 1-1/8" 4 76.88 26.06 9.25 127
LH*14E-033[ ]{
LH*46E-171[ ]{ }} 4.15
4.15 9.00
9.00 4.15
4.15 9.00 9.00 N/A
N/A N/A N/A 4.15 4.15 9.00
9.00 3,300
17,100 3,600
18,700 680
2,600 1/2"
1/2" 7/8"
1-1/8" 52 32.88
98.88 26.06 9.25
26.06 9.25 40
169
LH*24E-067[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 6,700 7,300 1,370 1/2" 1-1/8" 3 54.88 26.06 9.25 67
LH*14E-033[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 3,300 3,600 680 1/2" 7/8" 2 32.88 26.06 9.25 40
LH*34E-100[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 10,000 10,900 2,050 1/2" 1-1/8" 4 76.88 26.06 9.25 109
LH*24E-067[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 6,700 7,300 1,370 1/2" 1-1/8" 3 54.88 26.06 9.25 67
LH*44E-132[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 13,200 14,500 2,730 1/2" 1-1/8" 5 98.88 26.06 9.25 150
LH*34E-100[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 10,000 10,900 2,050 1/2" 1-1/8" 4 76.88 26.06 9.25 109
LH*44E-132[ ]{ } N/A N/A 4.15* For 9.00
motor codeN/A N/A use
and refrigerant, 4.15 9.00AWEF rating
"D" when 13,200
is shown and 14,500 2,730 1/2" 1-1/8" 5 98.88 26.06EXAMPLE
9.25FULL MODEL:
150
"A" for non-regulated applications or where AWEF is NA. [ ] Location for the refrigerant letter code. LHD16A-047QVA is DOE / NRCan with R-407A, Variable Speed EC motor
{ } Include motor code as* For motor
either "D"code and Speed
for Dual refrigerant, for"D"
or "V"use whenSpeed
Variable AWEFECrating
motoris shown and
to be used. and includes the additional letter A for 208 VEXAMPLE FULL
single phase fanMODEL:
power.
"A" for non-regulated applications or where AWEF is NA. [ ] Location for the *refrigerant
motor letter
Forrefrigerant code. AWEF rating isLHD16A-047QVA
refrigerant, use “D” whenLHA36E-129SDAA
codelisting).
and shown and “A”isfor
DOE / NRCan withapplications
non-regulated R-407A, Variable Speed EC motor
** G Stock Units are for glide refrigerants only (consult I/O manual for complete is for non-regulated application with R-404A,orDual
where AWEF
Speed ECismotor
N/A.
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used. and includes the additional[letter A for 208the
] Location V single phaseletter
fan power.
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing). and includes the additional letters AA for 208 V singlefor
phase refrigerant code.
fan and defrost power.
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing). LHA36E-129SDAA
{ } Include motor code as eitheris“D”
for for
non-regulated application
Dual Speed or with R-404A,
“V” for Variable SpeedDual SpeedtoECbemotor
EC motor used.
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing). and includes the additional letters AA for 208 V single phase fan and defrost power.
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Dual Speed fan motors use a voltage input from the incoming fan power to a third connection on the motor to trigger low speed operation. Variable
Speed EC need a 0-10 V signal with 10 V as minimum speed operation. Both motor types operate as a single speed EC motor without a control signal.
AWEF By Refrigerant,
Motor and Application
REFRIGERATION
CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) AIR REF SHIP
@ 10˚ F TD FLOW CHARGE WGT
MODEL {D}ual Speed {V}ariable Speed +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
LH*16A-047C{ } N/A 9.00 4,700 650 1/2" 7/8" 1.6 32.88 26.06 9.25 42
LH*26A-094C{ } N/A 9.00 9,400 1,300 1/2" 7/8" 2.4 54.88 26.06 9.25 70
LH*36A-140C{ } N/A 9.00 14,000 1,950 1/2" 7/8" 3.2 76.88 26.06 9.25 123
LH*46A-187C{ } N/A 9.00 18,700 2,600 1/2" 1-1/8" 4.0 98.88 26.06 9.25 164
LH*14A-036C{ } N/A 9.00 3,600 680 1/2" 7/8" 1.6 32.88 26.06 9.25 38
LH*24A-073C{ } N/A 9.00 7,300 1,370 1/2" 7/8" 2.4 54.88 26.06 9.25 64
LH*34A-109C{ } N/A 9.00 10,900 2,050 1/2" 7/8" 3.2 76.88 26.06 9.25 105
LH*44A-145C{ } N/A 9.00 14,500 2,730 1/2" 1-1/8" 4.0 98.88 26.06 9.25 146
* For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is NA.
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used.
ELECTRIC DEFROST - CO2
EXAMPLE FULL MODEL:
LHD16A-047CVA is DOE / NRCan with CO2, Variable Speed EC motor and includes the additional letter A for 208 V single phase fan power
AWEF By Refrigerant,
Motor and Application
REFRIGERATION
CAPACITY CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) (BTU/H) AIR REF SHIP
{D}ual Speed {V}ariable Speed @ 10˚ F TD @ 10˚ F TD FLOW CHARGE WGT
MODEL Freezer Cooler Freezer Cooler -20˚ F EVAP +20˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
LH*16E-043C{ } 4.15 9.00 4.15 9.00 4,300 4,700 650 1/2" 7/8" 1.6 32.88 26.06 9.25 44
LH*26E-086C{ } 4.15 9.00 4.15 9.00 8,600 9,400 1,300 1/2" 1-1/8" 2.4 54.88 26.06 9.25 73
LH*36E-129C{ } 4.15 9.00 4.15 9.00 12,900 14,000 1,950 1/2" 1-1/8" 3.2 76.88 26.06 9.25 127
LH*46E-171C{ } 4.15 9.00 4.15 9.00 17,100 18,700 2,600 1/2" 1-1/8" 4.0 98.88 26.06 9.25 169
LH*14E-033C{ } 4.15 9.00 4.15 9.00 3,300 3,600 680 1/2" 7/8" 1.6 32.88 26.06 9.25 40
LH*24E-067C{ } 4.15 9.00 4.15 9.00 6,700 7,300 1,370 1/2" 1-1/8" 2.4 54.88 26.06 9.25 67
LH*34E-100C{ } 4.15 9.00 4.15 9.00 10,000 10,900 2,050 1/2" 1-1/8" 3.2 76.88 26.06 9.25 109
LH*44E-132C{ } N/A 9.00 4.15 9.00 13,200 14,500 2,730 1/2" 1-1/8" 4.0 98.88 26.06 9.25 150
* For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is NA.
* For motor code and refrigerant, use “D” when AWEF rating is shown and “A” for non-regulated applications or where AWEF is NA.
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used.
{ } Include motor code as either “D” for Dual Speed or “V” for Variable Speed EC motor to be used.
EXAMPLE FULL MODEL:
EXAMPLE FULL MODEL:
LHA36E-129CDAA is for non-regulated application with CO , Dual Speed EC motor and includes the additional letters AA for 208 V single phase fan and defrost power.
LHD16A-047CVA is DOE / NRCan with CO2, Variable Speed EC2 motor and includes the additional letter A for 208 V single phase fan power.
LHA36E-129CDAA is for non-regulated application with CO2, Dual Speed EC motor and includes the additional letters AA for 208 V single phase fan and defrost power.
Standard Features
Ideal for keeping produce fresh by providing low velocity air distribution to both sides of system.
Quiet operation provides a comfortable environment for employees.
n Low and high silhouette center mounted models will not interfere with shelving.
n Two-way air discharge provides smooth air movement, creating a low velocity “umbrella” style air distribution.
n S
ound levels range from 53 dbA for a one fan to 60 dbA for a six-fan model measured six feet horizontally
from the center of the unit.
n Standard EC motors are two speed 1/15 horsepower and multi-voltage operating on 100-240/1/50-60 power.
n Coil constructed of heavy-wall copper tube and rippled full collar aluminum fins.
n Optimized circuiting for HFC and HFO refrigerants.
n Sealed and pressurized from the factory.
n Factory-wired fans and defrost controls to convenient terminal strips for field connections.
n Plug in motor leads for quick positive connection to wiring harness.
GL D 3 6 D - 135 T D A K
* Available on pan heaters for "H" and "P" defrost options only.
* Available on pan heaters
** PSCfor “H” and
motors are“P”
notdefrost
allowedoptions only.
in USA or Canada for any evaporator solution.
*** ‘N’**Stock
PSC motors arefor
Units are notnon-glide
allowed inorUSA
glideorrefrigerants
Canada for (consult
any evaporator solution.
I/O manual for complete refrigerant listing).
** ‘N’‘G’
**** Stock Units
Stock are for
Units arenon-glide
for glide or glide refrigerants
refrigerants (consultI/OI/Omanual
only (consult manualforforcomplete
completerefrigerant
refrigerant listing).
listing).
*** ‘G’ Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
** All
All air
air defrost
defrost are DOE // NRCan
are DOE NRCan compliant
compliantwhen
whenapplied
appliedwith "D"Dual
with“D” DualSpeed "V" Variable
Speedoror“V” VariableSpeed
SpeedEC
ECmotor
motorcodes
codesand
andrefrigerants
refrigerantsshown
shownabove.
above.
[ ] Location for the refrigerant letter code.
[ ] Location for the refrigerant letter code.
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used.
{ } Include motor code as either “D” for Dual Speed or “V” for Variable Speed EC motor to be used.
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
EXAMPLE FULL MODEL:
EXAMPLE FULL isMODEL:
GHD34A-150TDA DOE / NRCan with R-404A, Dual Speed EC motor and includes the additional letter A for 208 V single phase.
GHD34A-150TDA is DOE / NRCan with R-404A, Dual Speed EC motor and includes the additional letter A for 208 V single phase.
EXAMPLEFULL
EXAMPLE FULLMODEL:
MODEL:
GHD34D-105TDAA is DOE / NRCan
GHD34D-105TDAA is DOEwith R-448A,
/ NRCan with Dual Speed
R-448A, DualECSpeed
motor
ECand includes
motor the additional
and includes letterletter
the additional A forA208 V single
for 208 phase
V single fanfanpower
phase powerand
andKKfor
for208/3/60
208/3/60 defrost.
defrost.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Cooler AWEF By
Refrigerant and Motor
REFRIGERATION
CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) AIR REF SHIP
@ 10˚ F TD FLOW CHARGE WGT
MODEL {D}ual Speed {V}ariable Speed +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
GHD16A-060C{ } 9.00 9.00 6,000 900 1/2" 7/8" 2.4 31.75 28.75 18.25 130
GHD26A-130C{ } 9.00 9.00 13,000 1,800 1/2" 7/8" 3.2 49.75 28.75 18.25 180
GHD36A-198C{ } 9.00 9.00 19,800 2,700 1/2" 1-1/8" 4.8 67.75 28.75 18.25 240
GHD46A-270C{ } 9.00 9.00 27,000 3,600 1/2" 1-1/8" 6.4 85.75 28.75 18.25 320
GHD56A-340C{ } 9.00 9.00 34,000 4,500 1/2" 1-1/8" 7.2 103.75 28.75 18.25 370
GHD66A-410C{ } 9.00 9.00 41,000 5,400 1/2" 1-1/8" 8.8 121.75 28.75 18.25 420
GHD14A-050C{ } 9.00 9.00 5,000 940 1/2" 7/8" 2.4 31.75 28.75 18.25 120
GHD24A-100C{ } 9.00 9.00 10,000 1,880 1/2" 7/8" 3.2 49.75 28.75 18.25 170
GHD34A-150C{ } 9.00 9.00 15,000 2,820 1/2" 1-1/8" 4.8 67.75 28.75 18.25 230
GHD44A-200C{ } 9.00 9.00 20,000 3,760 1/2" 1-1/8" 6.4 85.75 28.75 18.25 310
GHD54A-250C{ } 9.00 9.00 25,000 4,700 1/2" 1-1/8" 7.2 103.75 28.75 18.25 360
GHD64A-300C{ } 9.00 9.00 30,000 5,640 1/2" 1-1/8" 8.8 121.75 28.75 18.25 410
Cooler AWEF By
Refrigerant and Motor
REFRIGERATION
CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) AIR REF SHIP
@ 10˚ F TD FLOW CHARGE WGT
MODEL {D}ual Speed {V}ariable Speed +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
GLD16A-045C{ } 9.00 9.00 4,500 600 1/2" 5/8" 1.6 31.75 28.75 12.25 100
GLD26A-090C{ } 9.00 9.00 9,000 1,200 1/2" 7/8" 2.4 49.75 28.75 12.25 140
GLD36A-135C{ } 9.00 9.00 13,500 1,800 1/2" 1-1/8" 3.2 67.75 28.75 12.25 190
GLD46A-180C{ } 9.00 9.00 18,000 2,400 1/2" 1-1/8" 4.0 85.75 28.75 12.25 250
GLD56A-225C{ } 9.00 9.00 22,500 3,000 1/2" 1-1/8" 4.0 103.75 28.75 12.25 290
GLD66A-268C{ } 9.00 9.00 26,800 3,600 1/2" 1-1/8" 4.8 121.75 28.75 12.25 340
GLD14A-035C{ } 9.00 9.00 3,500 630 1/2" 5/8" 1.6 31.75 28.75 12.25 90
GLD24A-070C{ } 9.00 9.00 7,000 1,260 1/2" 7/8" 2.4 49.75 28.75 12.25 130
GLD34A-105C{ } 9.00 9.00 10,500 1,890 1/2" 1-1/8" 3.2 67.75 28.75 12.25 180
GLD44A-140C{ } 9.00 9.00 14,000 2,520 1/2" 1-1/8" 4.0 85.75 28.75 12.25 240
GLD54A-175C{ } 9.00 9.00 17,500 3,150 1/2" 1-1/8" 4.0 103.75 28.75 12.25 280
GLD64A-210C{ } 9.00 9.00 21,000 3,780 1/2" 1-1/8" 4.8 121.75 28.75 12.25 330
{{}}Include
Includemotor
motor code
code as
as either “D” for
either "D" for Dual
Dual Speed or “V”
Speed or "V" for
for Variable
VariableSpeed
SpeedECECmotor
motortotobebeused.
used.
EXAMPLE FULL MODEL:
GHD34A-150CDA is DOE / NRCan with CO2, Dual Speed EC motor and includes the additional letterEXAMPLE
A for 208 VFULL
singleMODEL:
phase.
GHD34A-150CDA is DOE / NRCan with CO2, Dual Speed EC motor and includes the additional letter A for 208 V single phase.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Cooler AWEF By
Refrigerant and Motor
REFRIGERATION
CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) AIR REF SHIP
@ 10˚ F TD FLOW CHARGE WGT
MODEL {D}ual Speed {V}ariable Speed +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
GHD16D-060C{ } 9.00 9.00 6,000 900 1/2" 7/8" 2.4 31.75 28.75 18.25 130
GHD26D-130C{ } 9.00 9.00 13,000 1,800 1/2" 7/8" 3.2 49.75 28.75 18.25 180
GHD36D-198C{ } 9.00 9.00 19,800 2,700 1/2" 1-1/8" 4.8 67.75 28.75 18.25 240
GHD46D-270C{ } 9.00 9.00 27,000 3,600 1/2" 1-1/8" 6.4 85.75 28.75 18.25 320
GHD56D-340C{ } 9.00 9.00 34,000 4,500 1/2" 1-1/8" 7.2 103.75 28.75 18.25 370
GHD66D-410C{ } 9.00 9.00 41,000 5,400 1/2" 1-1/8" 8.8 121.75 28.75 18.25 420
GHD14D-050C{ } 9.00 9.00 5,000 940 1/2" 7/8" 2.4 31.75 28.75 18.25 120
GHD24D-100C{ } 9.00 9.00 10,000 1,880 1/2" 7/8" 3.2 49.75 28.75 18.25 170
GHD34D-150C{ } 9.00 9.00 15,000 2,820 1/2" 1-1/8" 4.8 67.75 28.75 18.25 230
GHD44D-200C{ } 9.00 9.00 20,000 3,760 1/2" 1-1/8" 6.4 85.75 28.75 18.25 310
GHD54D-250C{ } 9.00 9.00 25,000 4,700 1/2" 1-1/8" 7.2 103.75 28.75 18.25 360
GHD64D-300C{ } 9.00 9.00 30,000 5,640 1/2" 1-1/8" 8.8 121.75 28.75 18.25 410
Cooler AWEF By
Refrigerant and Motor
REFRIGERATION
CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) AIR REF SHIP
@ 10˚ F TD FLOW CHARGE WGT
MODEL {D}ual Speed {V}ariable Speed +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
GLD16D-045C{ } 9.00 9.00 4,500 600 1/2" 5/8" 1.6 31.75 28.75 12.25 100
GLD26D-090C{ } 9.00 9.00 9,000 1,200 1/2" 7/8" 2.4 49.75 28.75 12.25 140
GLD36D-135C{ } 9.00 9.00 13,500 1,800 1/2" 1-1/8" 3.2 67.75 28.75 12.25 190
GLD46D-180C{ } 9.00 9.00 18,000 2,400 1/2" 1-1/8" 4.0 85.75 28.75 12.25 250
GLD56D-225C{ } 9.00 9.00 22,500 3,000 1/2" 1-1/8" 4.0 103.75 28.75 12.25 290
GLD66D-268C{ } 9.00 9.00 26,800 3,600 1/2" 1-1/8" 4.8 121.75 28.75 12.25 340
GLD14D-035C{ } 9.00 9.00 3,500 630 1/2" 5/8" 1.6 31.75 28.75 12.25 90
GLD24D-070C{ } 9.00 9.00 7,000 1,260 1/2" 7/8" 2.4 49.75 28.75 12.25 130
GLD34D-105C{ } 9.00 9.00 10,500 1,890 1/2" 1-1/8" 3.2 67.75 28.75 12.25 180
GLD44D-140C{ } 9.00 9.00 14,000 2,520 1/2" 1-1/8" 4.0 85.75 28.75 12.25 240
GLD54D-175C{ } 9.00 9.00 17,500 3,150 1/2" 1-1/8" 4.0 103.75 28.75 12.25 280
GLD64D-210C{ } 9.00 9.00 21,000 3,780 1/2" 1-1/8" 4.8 121.75 28.75 12.25 330
{{}}Include
Include motor
motor code
code as
as either “D” for
either "D" for Dual Speed oror “V”
Dual Speed "V"for
forVariable
VariableSpeed
SpeedECECmotor
motortotobebeused.
used.
E XAMPLE FULL MODEL:
GHD34D-105DAA
EXAMPLE FULL isMODEL:
DOE / NRCan with CO2, Dual Speed EC motor and includes the additional letter A for 208 V single phase fan power and K for 208/3/60 defrost..
GHD34D-105CDAA is DOE / NRCan with CO2, Dual Speed EC motor and includes the additional letter A for 208 V single phase fan power and K for 208/3/60 defrost.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Standard Features
Specifically designed with a low silhouette that fits flush to the ceiling utilizing less than 15" of headroom
which gives you more usable storage space for every walk-in application.
n Swept
Wing Fan Blade Design for quieter operation. Non-metallic fan guard eliminates possibility for
corrosion.
n F
ront access to refrigeration components and electrical panel with hinged cover for easy access for
service.
n Standard
EC motors are two speed 1/15 horsepower and multi-voltage operating on
100-240/1/50-60 power.
n D
ie-formed patterned aluminum cabinet and drain pan with easy-to-clean radius corners.
n C
oil constructed of heavy-wall copper tube and rippled full collar aluminum fins.
n Optimized
circuiting for HFC and HFO refrigerants.
n Sealed
and pressurized from the factory.
n Factory-wired
fans and defrost controls to convenient terminal strips for field connections.
n P
lug in motor leads for quick positive connection to wiring harness.
KR D 2 6 A - 125 T D A A
Motor Type
Fin Spacing
D - Dual Speed EC
4, 6 FPI V - Variable Speed EC
B - PSC Motors **
Type of Defrost
Refrigerant
A - Air Defrost
E - Electric Defrost with Electric Pan Heat N - Stock Unit *** G - Stock Unit ****
G - 3 Pipe Hot Gas with Gas Pan Heat S - R-404A Q - R-407A T - R-448A
H - 3 Pipe Hot Gas with Electric Pan Heat P - R-507A F - R-407F R - R-449A
K - 2 Pipe Kool Gas with Gas Pan Heat
B - Glycol / Brine C - CO2
P - 2 Pipe Kool Gas with Electric Pan Heat
R - Heat Reclaim
BTU/H in Hundreds (00)
* Available on pan heaters for "H" and "P" defrost options The KR Low Profile Evaporators are certified under NOM-012-ENER-2019 Standard:
only.
** PSC motors are not allowed in USA or Canada forEnergy efficiency ofsolution
any evaporator condenser
andandfew
evaporator
selectedunits for refrigeration
models in Mexicoapplication in Mexico.
(check with your sales representative fo
*** ‘N’ Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
* Available
**** ‘G’ Stock Units are for glide on pan
refrigerants heaters
only for I/O
(consult “H”manual
and “P”fordefrost options
complete only. listing).
refrigerant
** PSC motors are not allowed in USA or Canada for any evaporator solution and few selected models in Mexico
(check with your sales representative for the models).
** ‘N’ Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
*** ‘G’ Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
AIR DEFROST
COOLER AWEF BY REFRIGERANT and MOTOR
[G] STOCK UNIT**, [N] STOCK UNIT***,
[Q] R-407A, [F] R-407F, [S] R-404A, REFRIGERATION
CAPACITY
HANGERS
[T] R-448A, [R] R-449A [P] R-507A CONNECTIONS DIMENSIONS (IN)
(BTU/H) AIR REF SHIP
{D}ual {V}ariable {D}ual {V}ariable @ 10˚ F TD FLOW CHARGE WGT
MODEL Speed Speed Speed Speed +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
KR*16A-040[ ]{ } 9.00 9.00 9.00 9.00 4,000 845 1/2" 5/8" 4 1 29.13 15.32 15.90 55
KR*16A-060[ ]{ } 9.00 9.00 9.00 9.00 6,000 845 1/2" 5/8" 4 1 29.13 15.32 15.90 60
KR*26A-089[ ]{ } 9.00 9.00 9.00 9.00 8,900 1,690 1/2" 7/8" 4 2 47.13 15.32 15.90 100
KR*26A-125[ ]{ } 9.00 9.00 9.00 9.00 12,500 1,690 1/2" 7/8" 4 2 47.13 15.32 15.90 100
KR*36A-134[ ]{ } 9.00 9.00 9.00 9.00 13,400 2,535 1/2" 7/8" 4 3 65.13 15.32 15.90 120
KR*36A-170[ ]{ } 9.00 9.00 9.00 9.00 17,000 2,535 1/2" 1-1/8" 4 3 65.13 15.32 15.90 140
KR*46A-216[ ]{ } 9.00 9.00 9.00 9.00 21,600 3,380 1/2" 1-1/8" 6 3 83.13 15.32 15.90 180
KR*56A-242[ ]{ } 9.00 9.00 9.00 9.00 24,200 4,225 1/2" 1-1/8" 6 4 101.13 15.32 15.90 220
KR*66A-340[ ]{ } 9.00 9.00 9.00 9.00 34,000 5,070 1/2" 1-3/8" 6 5 119.13 15.32 15.90 265
KR*14A-058[ ]{ } 9.00 9.00 9.00 9.00 5,800 855 1/2" 5/8" 4 1 29.13 15.32 15.90 60
KR*24A-096[ ]{ } 9.00 9.00 9.00 9.00 9,600 1,750 1/2" 5/8" 4 2 47.13 15.32 15.90 90
KR*24A-117[ ]{ } 9.00 9.00 9.00 9.00 11,700 1,710 1/2" 5/8" 4 2 47.13 15.32 15.90 100
KR*34A-143[ ]{ } 9.00 9.00 9.00 9.00 14,300 2,625 1/2" 5/8" 4 3 65.13 15.32 15.90 125
KR*34A-173[ ]{ } 9.00 9.00 9.00 9.00 17,300 2,565 1/2" 5/8" 4 3 65.13 15.32 15.90 140
KR*44A-191[ ]{ } 9.00 9.00 9.00 9.00 19,100 3,500 1/2" 5/8" 6 3 83.13 15.32 15.90 165
KR*44A-232[ ]{ } 9.00 9.00 9.00 9.00 23,200 3,420 1/2" 5/8" 6 3 83.13 15.32 15.90 180
KR*54A-290[ ]{ } 9.00 9.00 9.00 9.00 29,000 4,275 1/2" 5/8" 6 4 101.13 15.32 15.90 225
KR*64A-348[ ]{ } 9.00 9.00 9.00 9.00 34,800 5,130 1/2" 5/8" 6 5 119.13 15.32 15.90 265
* All air defrost are DOE / NRCan compliant when applied with “D” for*Dual
All air defrost
Speed are DOE
or “V” / NRCan
for Variable compliant
Speed when
EC motor applied
codes and any "D"/ for
withHFC HFODual Speed or[ ]"V"
refrigerant. for Variable
Location for theSpeed EC motor
refrigerant lettercodes
code.and any HFC / HFO refrigerant.
[ ] Location for the refrigerant letter code. { } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used.
{ } Include motor code as either “D” for Dual Speed or “V” for Variable Speed EC motor to be used..
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing). ** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing). *** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
HANGERS
{D}ual {V}ariable {D}ual {V}ariable CONNECTIONS DIMENSIONS (IN) SHIP
(BTU/H) (BTU/H) AIR REF
Speed Speed Speed Speed @ 10° F TD @ 10° F TD FLOW CHARGE WGT
MODEL Freezer Cooler Freezer Cooler Freezer Cooler Freezer Cooler -20° F EVAP +20° F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
KR*14E-037[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 3,700 5,000 875 1/2" 5/8" 4 1 29.13 15.32 15.90 55
KR*24E-074[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 7,400 9,990 1,750 1/2" 7/8" 4 2 47.13 15.32 15.90 90
KR*34E-111[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 11,100 14,990 2,625 1/2" 7/8" 4 3 65.13 15.32 15.90 125
KR*44E-148[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 14,800 19,850 3,500 1/2" 1-1/8" 6 3 83.13 15.32 15.90 165
KR*54E-185[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 18,500 24,980 4,375 1/2" 1-1/8" 6 4 101.10 15.32 15.90 200
KR*64E-220[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 22,000 29,700 5,250 1/2" 1-1/8" 6 5 119.10 15.32 15.90 240
KR*16E-035[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 3,500 4,730 845 1/2" 5/8" 4 1 29.13 15.32 15.90 55
KR*16E-045[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 4,500 6,080 845 1/2" 5/8" 4 1 29.13 15.32 15.90 60
KR*26E-090[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 9,000 12,150 1,690 1/2" 7/8" 4 2 47.13 15.32 15.90 100
KR*36E-135[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 13,500 18,230 2,535 1/2" 7/8" 4 3 65.13 15.32 15.90 140
KR*46E-180[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 18,000 24,300 3,380 1/2" 1-1/8" 6 4 83.13 15.32 15.90 180
KR*56E-192[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 19,200 25,920 4,225 1/2" 1-1/8" 6 4 101.10 15.32 15.90 220
KR*66E-270[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 27,000 36,450 5,070 1/2" 1-1/8" 6 5 119.10 15.32 15.90 265
* For motor code and refrigerant, use "D" when
EXAMPLE FULLAWEF rating is shown and "A" for non-regulated
MODEL: * For motor applications
code andorrefrigerant,
where AWEF use
is N/A. EXAMPLE
‘D’ when AWEF rating is shownFULLand
MODEL:
‘A’ for non-regulated applications or where AWEF is N/A.
De-rate capacity 12% for 50 Hertz operation with 3 phase motors only. [ ] Location for the refrigerant letter code. KRD16E-035QDAA is DOE / NRCan with R-407A, Dual Speed EC motor and includes
KRD16E-035QDAA is DOE / NRCan with R-407A, De-rate capacity 12% for 50 Hertz operation with 3 phase motors only. [ ] Location for the refrigerant letter code.
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used. the additional letters AA for 208 V single phase power.
Dual Speed EC motor and includes t he additional { } Include motor code as either ‘D’ for Dual Speed or ‘V’ for Variable Speed EC motor to be used.
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
letters AA for 208 V single phase power.
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing). ** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
HANGERS
{D}ual {V}ariable {D}ual {V}ariable (BTU/H) @ (BTU/H) @ AIR CONNECTIONS DIMENSIONS (IN) SHIP
Speed Speed Speed Speed REF
10° TD 10° TD FLOW HOT CHARGE WGT
MODEL Freezer Cooler Freezer Cooler Freezer Cooler Freezer Cooler -20°F EVAP +20°F EVAP (CFM) LIQ SUCT GAS LBS L W H (LBS)
KR*14( )-037[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 3,700 5,000 875 1/2" 5/8" 1/2" 4 1 29.13 15.32 15.90 55
KR*24( )-074[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 7,400 9,990 1,750 1/2" 7/8" 1/2" 4 2 47.13 15.32 15.90 90
KR*34( )-111[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 11,100 14,990 2,625 1/2" 7/8" 1/2" 4 3 65.13 15.32 15.90 125
KR*44( )-148[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 14,800 19,850 3,500 1/2" 1-1/8" 1/2" 6 3 83.13 15.32 15.90 165
KR*54( )-185[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 18,500 24,980 4,375 1/2" 1-1/8" 1/2" 6 4 101.1 15.32 15.90 200
KR*64( )-220[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 22,000 29,700 5,250 1/2" 1-1/8" 1/2" 6 5 119.1 15.32 15.90 240
KR*16( )-035[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 3,500 4,730 845 1/2" 5/8" 1/2" 4 1 29.13 15.32 15.90 55
KR*16( )-045[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 4,500 6,080 845 1/2" 5/8" 1/2" 4 1 29.13 15.32 15.90 60
KR*26( )-090[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 9,000 12,150 1,690 1/2" 7/8" 1/2" 4 2 47.13 15.32 15.90 100
KR*36( )-135[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 13,500 18,230 2,535 1/2" 7/8" 1/2" 4 3 65.13 15.32 15.90 140
KR*46( )-180[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 18,000 24,300 3,380 1/2" 1-1/8" 1/2" 6 4 83.13 15.32 15.90 180
KR*56( )-192[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 19,200 25,920 4,225 1/2" 1-1/8" 1/2" 6 4 101.1 15.32 15.90 220
KR*66( )-270[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 27,000 36,450 5,070 1/2" 1-1/8" 1/2" 6 5 119.1 15.32 15.90 265
* For motor code and refrigerant,
Available "D" when
GasuseDefrost AWEF rating is shown and "A" for non-regulated
Types applications
* For motor code andor where N/A.‘D’ when AWEF rating isAvailable
AWEF isuse
refrigerant, shown and Gas‘A’
Defrost Types
for non-regulated applications or where AWEF is N/A.
( ) Gas defrost type K, H, G, or P. See definition to the right. [ ] Location for the refrigerant letter code. (K) - definition
2 Pipe Kool to
Gasthe
withright.
Gas Pan
(K) - 2 Pipe Kool Gas with Gas Pan ( ) Gas defrost type K, H, G, or P. See [ ] Location for the refrigerant letter code.
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used. (P) -“D”
2 Pipe
{ } Include motor code as either forKool
DualGasSpeed
with Electric
or “V” Pan
for Heat
Variable Speed EC motor to be used.
**(P)G -Stock
2 Pipe KoolareGas
Units withrefrigerants
for glide Electric Pan
onlyHeat
(consult I/O manual for complete refrigerant listing). (G) - 3 Pipe Hot Gas with Hot Gas Pan
(G) - 3 Pipe Hot Gas with Hot Gas Pan
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing). ** G Stock Units are for glide refrigerants
(H) - 3 Pipe Hotonly
Gas(consult I/O Pan
with Electric manual
Heat for complete refrigerant listing).
(H) - 3 Pipe Hot Gas with Electric Pan Heat
EXAMPLE FULL MODEL: *** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
KRD24K-035PVA is DOE / NRCan with R-507A, Variable Speed EC motor and includes the additional letter A for 208 V single phase fan power.
EXAMPLE FULL MODEL:
KRD24K-035PVA is DOE / NRCan with R-507A, Variable Speed EC motor and includes the additional letter A for 208V single phase fan power.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Cooler AWEF By
Refrigerant and Motor
REFRIGERATION
CAPACITY
HANGERS
C - CO2 CONNECTIONS DIMENSIONS (IN)
(BTU/H) AIR REF SHIP
@ 10˚ F TD FLOW CHARGE WGT
MODEL {D}ual Speed {V}ariable Speed +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
KRD16A-040C{ } 9.00 9.00 4,000 845 1/2" 5/8" 4 0.8 29.13 15.32 15.90 55
KRD16A-060C{ } 9.00 9.00 6,000 845 1/2" 5/8" 4 0.8 29.13 15.32 15.90 60
KRD26A-089C{ } 9.00 9.00 8,900 1,690 1/2" 7/8" 4 1.6 47.13 15.32 15.90 100
KRD26A-125C{ } 9.00 9.00 12,500 1,690 1/2" 7/8" 4 1.6 47.13 15.32 15.90 100
KRD36A-134C{ } 9.00 9.00 13,400 2,535 1/2" 7/8" 4 2.4 65.13 15.32 15.90 120
KRD36A-170C{ } 9.00 9.00 17,000 2,535 1/2" 1-1/8" 4 2.4 65.13 15.32 15.90 140
KRD46A-216C{ } 9.00 9.00 21,600 3,380 1/2" 1-1/8" 6 2.4 83.13 15.32 15.90 180
KRD56A-242C{ } 9.00 9.00 24,200 4,225 1/2" 1-1/8" 6 3.2 101.13 15.32 15.90 220
KRD66A-340C{ } 9.00 9.00 34,000 5,070 1/2" 1-1/8" 6 4.0 119.13 15.32 15.90 265
KRD14A-058C{ } 9.00 9.00 5,800 855 1/2" 5/8" 4 0.8 29.13 15.32 15.90 60
KRD24A-096C{ } 9.00 9.00 9,600 1,750 1/2" 5/8" 4 1.6 47.13 15.32 15.90 90
KRD24A-117C{ } 9.00 9.00 11,700 1,710 1/2" 5/8" 4 1.6 47.13 15.32 15.90 100
KRD34A-143C{ } 9.00 9.00 14,300 2,625 1/2" 5/8" 4 2.4 65.13 15.32 15.90 125
KRD34A-173C{ } 9.00 9.00 17,300 2,565 1/2" 5/8" 4 2.4 65.13 15.32 15.90 140
KRD44A-191C{ } 9.00 9.00 19,100 3,500 1/2" 5/8" 6 2.4 83.13 15.32 15.90 165
KRD44A-232C{ } 9.00 9.00 23,200 3,420 1/2" 5/8" 6 2.4 83.13 15.32 15.90 180
KRD54A-290C{ } 9.00 9.00 29,000 4,275 1/2" 5/8" 6 3.2 101.13 15.32 15.90 225
KRD64A-348C{ } 9.00 9.00 34,800 5,130 1/2" 5/8" 6 4.0 119.13 15.32 15.90 265
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used.
EXAMPLE FULL MODEL:
KRD16A-040CDA is DOE / NRCan with CO2, Dual Speed EC motor and includes the additional letter A for 208 V single phase fan power.
AWEF By Refrigerant,
Motor and Application
REFRIGERATION
CAPACITY CAPACITY
HANGERS
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
MK/MV Series Unit Coolers
Standard Features
MK Medium Profile Unit Coolers are designed with a wide capacity range and air
movement for WICF 12' to 20' high required to meet DOE / NRCan regulation.
MV Models are available for non-regulated applications requiring a longer air throw.
n uggedly constructed cabinets are installed level and flush to the ceiling
R
or with hanger rods.
n Wide capacity range with coils with 4, 6, or 8 fins per inch.
n Swept Wing Fan Blade Design for quieter operation standard on air defrost.
n Aluminum cabinet and drain pan.
n Coated, corrosion-proof wire fan guards.
n C fan motor is a nominal 1/3 horsepower, dual voltage 115/1/60 or 208-230/1/60,
E
and will accept a 0-10 V signal to vary the fan speed.
n Plug in motor leads for quick positive connection to wiring harness.
n actory-wired fans and defrost controls to convenient terminal strips for field
F
connections.
n Coil constructed of heavy-wall copper tube and rippled full collar aluminum fins.
n Optimized circuiting for HFC and HFO refrigerants.
n Sealed and pressurized from the factory.
MK D 2 6 E - 152 T V A A
* Single phase motors wired for 3 phase operation. Not available on single fan units.
* Single phase motors wired for 3 phase operation. Not available on single fan units.
** 460 V motors are Motor Type PSC only and not available for any evaporator solution in the USA or Canada.
** 460 V***
motors are Motor
EC motor Typefor
required PSCDOE
onlywith
andVariable
not available
Speedfororany
Dualevaporator solution
Speed control in the
option areUSA
A, BororCanada.
K motor voltage only.
*** EC motor
**** required for on
Available DOEpan
withheaters
Variable for
Speed
"H"or Dual
and Speed control option
"P" defrost optionsareonly.
A, B or K motor voltage only.
**** Available on pan
***** PSC heaters
motors arefornot
“H”allowed
and “P” in defrost
USA oroptions only.for any evaporator solution.
Canada
******
***** PSC ‘N’are
motors Stock Units are
not allowed in for
USAnon-glide
or Canadaorforglide
anyrefrigerants (consult I/O manual for complete refrigerant listing).
evaporator solution. Use your QR reader to
‘N’ Stock‘G’
****** ******* Stock
Units Units
are for are foror glide
non-glide glide refrigerants only (consult
refrigerants (consult I/O manual
I/O manual for complete
for complete refrigerant
refrigerant listing). listing) reference current document
******* ‘G’ Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing) version on www.krack.com.
* For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is N/A.
* For motor code and refrigerant, use “D” when AWEF rating is shown and “A” for non-regulated applications or where AWEF is N/A. [ ] Location for the refrigerant letter code.
[ ] Location for the refrigerant letter code. { } Variable Speed EC motor is standard, include "V" for Variable Speed EC control
{ } Variable Speed EC motor is standard, include “V” for Variable Speed EC control or “D” when Dual Speed control from 10 V signal will be applied. or "D" when Dual Speed control from 10 V signal will be applied.
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
EXAMPLE FULL MODEL:
EXAMPLE FULL MODEL: MKD16A-118TVA is DOE / NRCan with R-448A, Variable Speed EC motor and includes the additional letter A for 208 V single phase fan power.
MKD16A-118TVA is DOE / NRCan with R-448A, Variable Speed EC motor and includes the additional letter A for 208 V single phase fan power.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
GAS DEFROST
AWEF BY REFRIGERANT, MOTOR, and APPLICATION
[G] STOCK UNIT**, [N] STOCK UNIT***,
[Q] R-407A, [F] R-407F, [S] R-404A,
[T] R-448A, [R] R-449A [P] R-507A REFRIGERATION
CAPACITY CAPACITY
{D}ual {V}ariable {D}ual {V}ariable CONNECTIONS DIMENSIONS (IN)
(BTU/H) (BTU/H) AIR REF SHIP
Speed Speed Speed Speed @ 10° F TD @ 10° F TD FLOW CHARGE WGT
MODEL Freezer Cooler Freezer Cooler Freezer Cooler Freezer Cooler -20° F EVAP +20° F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
MK*16( )-103[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 10,300 11,800 2,815 1/2" 1-1/8" 3 38.00 19.00 26.75 125
MK*16( )-127[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 12,700 14,500 2,725 1/2" 1-1/8" 4 38.00 19.00 26.75 130
MK*26( )-206[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 20,600 23,600 5,630 5/8" 1-5/8" 5 63.00 19.00 26.75 225
MK*26( )-254[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 25,400 29,000 5,450 5/8" 1-5/8" 6 63.00 19.00 26.75 240
MK*36( )-309[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 30,900 35,400 8,445 7/8" 1-5/8" 7 92.00 19.00 26.75 330
MK*36( )-381[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 38,100 43,500 8,175 7/8" 2-1/8" 8 92.00 19.00 26.75 350
MK*46( )-508[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 50,800 58,000 10,900 7/8" 2-1/8" 11 119.00 19.00 26.75 470
MK*14( )-082[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 8,200 9,400 3,060 1/2" 1-1/8" 3 38.00 19.00 26.75 125
MK*14( )-105[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 10,500 12,100 2,960 1/2" 1-1/8" 4 38.00 19.00 26.75 130
MK*24( )-164[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 16,400 18,800 6,120 5/8" 1-5/8" 5 63.00 19.00 26.75 225
MK*24( )-210[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 21,000 24,200 5,920 5/8" 1-5/8" 6 63.00 19.00 26.75 240
MK*34( )-246[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 24,600 28,200 9,180 7/8" 1-5/8" 7 92.00 19.00 26.75 330
MK*34( )-315[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 31,500 36,300 8,880 7/8" 2-1/8" 8 92.00 19.00 26.75 350
MK*44( )-420[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 42,000 48,400 11,840 7/8" 2-1/8" 11 119.00 19.00 26.75 470
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
AWEF By Refrigerant,
Motor and Application
REFRIGERATION
CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) AIR REF SHIP
{D}ual Speed {V}ariable Speed @ 10˚ F TD FLOW CHARGE WGT
MODEL Cooler Cooler +25˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
MKD18A-133C{ } 9.00 9.00 13,300 2,710 1/2" 7/8" 2.4 38.00 19.00 26.75 125
MKD18A-160C{ } 9.00 9.00 16,000 2,625 1/2" 1-1/8" 3.2 38.00 19.00 26.75 130
MKD28A-266C{ } 9.00 9.00 26,600 5,420 1/2" 1-1/8" 4.0 63.00 19.00 26.75 225
MKD28A-320C{ } 9.00 9.00 32,000 5,250 5/8" 1-1/8" 4.8 63.00 19.00 26.75 240
MKD38A-393C{ } 9.00 9.00 39,300 8,130 5/8" 1-1/8" 5.6 92.00 19.00 26.75 330
MKD38A-480C{ } 9.00 9.00 48,000 7,875 5/8" 1-1/8" 6.4 92.00 19.00 26.75 350
MKD48A-640C{ } 9.00 9.00 64,000 10,500 5/8" 1-1/8" 8.8 119.00 19.00 26.75 470
MKD16A-118C{ } 9.00 9.00 11,800 2,815 1/2" 7/8" 2.4 38.00 19.00 26.75 125
MKD16A-145C{ } 9.00 9.00 14,500 2,725 1/2" 1-1/8" 3.2 38.00 19.00 26.75 130
MKD26A-236C{ } 9.00 9.00 23,600 5,630 1/2" 1-1/8" 4.0 63.00 19.00 26.75 225
MKD26A-290C{ } 9.00 9.00 29,000 5,450 1/2" 1-1/8" 4.8 63.00 19.00 26.75 240
MKD36A-354C{ } 9.00 9.00 35,400 8,445 5/8" 1-1/8" 5.6 92.00 19.00 26.75 330
MKD36A-435C{ } 9.00 9.00 43,500 8,175 5/8" 1-1/8" 6.4 92.00 19.00 26.75 350
MKD46A-580C{ } 9.00 9.00 58,000 10,900 5/8" 1-1/8" 8.8 119.00 19.00 26.75 470
MKD14A-094C{ } 9.00 9.00 9,400 3,060 1/2" 7/8" 2.4 38.00 19.00 26.75 125
MKD14A-121C{ } 9.00 9.00 12,100 2,960 1/2" 7/8" 3.2 38.00 19.00 26.75 130
MKD24A-188C{ } 9.00 9.00 18,800 6,120 1/2" 1-1/8" 4.0 63.00 19.00 26.75 225
MKD24A-242C{ } 9.00 9.00 24,200 5,920 1/2" 1-1/8" 4.8 63.00 19.00 26.75 240
MKD34A-363C{ } 9.00 9.00 36,300 8,880 5/8" 1-1/8" 6.4 92.00 19.00 26.75 350
MKD44A-484C{ } 9.00 9.00 48,400 11,840 5/8" 1-1/8" 8.8 119.00 19.00 26.75 470
{ } Variable Speed EC motor is standard, include "V" for Variable Speed EC control or "D" when Dual Speed control from 10 V signal will be applied.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
AWEF By Refrigerant,
Motor and Application
REFRIGERATION
CAPACITY CAPACITY CONNECTIONS DIMENSIONS (IN)
C - CO2
(BTU/H) (BTU/H) AIR REF SHIP
{D}ual Speed {V}ariable Speed @ 10˚ F TD @ 10˚ F TD FLOW CHARGE WGT
MODEL Freezer Cooler Freezer Cooler -20˚ F EVAP +20˚ F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
MKD16E-103C{ } 4.15 9.00 4.15 9.00 10,300 11,800 2,815 1/2" 1-1/8" 2.4 38.00 19.00 26.75 125
MKD16E-127C{ } 4.15 9.00 4.15 9.00 12,700 14,500 2,725 1/2" 1-1/8" 3.2 38.00 19.00 26.75 130
MKD26E-206C{ } 4.15 9.00 4.15 9.00 20,600 23,600 5,630 5/8" 1-1/8" 4.0 63.00 19.00 26.75 225
MKD26E-254C{ } 4.15 9.00 4.15 9.00 25,400 29,000 5,450 5/8" 1-1/8" 4.8 63.00 19.00 26.75 240
MKD36E-309C{ } 4.15 9.00 4.15 9.00 30,900 35,400 8,445 7/8" 1-1/8" 5.6 92.00 19.00 26.75 330
MKD36E-381C{ } 4.15 9.00 4.15 9.00 38,100 43,500 8,175 7/8" 1-1/8" 6.4 92.00 19.00 26.75 350
MKD46E-508C{ } 4.15 9.00 4.15 9.00 50,800 58,000 10,900 7/8" 1-1/8" 8.8 119.00 19.00 26.75 470
MKD14E-082C{ } 4.15 9.00 4.15 9.00 8,200 9,400 3,060 1/2" 1-1/8" 2.4 38.00 19.00 26.75 125
MKD14E-105C{ } 4.15 9.00 4.15 9.00 10,500 12,100 2,960 1/2" 1-1/8" 3.2 38.00 19.00 26.75 130
MKD24E-164C{ } 4.15 9.00 4.15 9.00 16,400 18,800 6,120 5/8" 1-1/8" 4.0 63.00 19.00 26.75 225
MKD24E-210C{ } 4.15 9.00 4.15 9.00 21,000 24,200 5,920 5/8" 1-1/8" 4.8 63.00 19.00 26.75 240
MKD34E-246C{ } 4.15 9.00 4.15 9.00 24,600 28,200 9,180 7/8" 1-1/8" 5.6 92.00 19.00 26.75 330
MKD34E-315C{ } 4.15 9.00 4.15 9.00 31,500 36,300 8,880 7/8" 1-1/8" 6.4 92.00 19.00 26.75 350
MKD44E-420C{ } 4.15 9.00 4.15 9.00 42,000 48,400 11,840 7/8" 1-1/8" 8.8 119.00 19.00 26.75 470
{ } Include motor code as either "D" for Dual Speed or "V" for Variable Speed EC motor to be used.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
Standard Features
Medium Profile Units for Medium Size Walk-In Coolers and Freezers
The MS Series Unit Coolers have a medium profile to provide increased air flow for warehouse
refrigeration applications. The MS Series is built for performance with increased BTU/H capacities
and heavy-duty construction to meet your refrigeration requirements.
n Ruggedly
constructed cabinets are installed pulled against the ceiling or with hanger rods
sloped towards the drain connection on the end of the unit.
n Efficient
draw-thru design with 20" diameter fan blades provide air throw of 60 feet.
n High
efficiency 1/2 horsepower motors operate fans at 1140 RPM.
n Wide
capacity range with coils with 4, 5, 6, or 7 fins per inch.
n Air
defrost models for rooms operating above 34° F.
n Electric
and hot gas defrost models for colder rooms and freezers.
n Mill
galvanized drain pan and fan cabinet.
n Coated,
corrosion-resistant wire fan guards.
n Drain
pan and fan cabinet end panels are hinged for easy access and cleaning.
n Factory-wired
fans and defrost controls to convenient terminal strips for field connections.
n Adjustable
defrost termination and fan delay thermostat installed with electric defrost.
n Coil
constructed of heavy-wall copper tube and rippled full collar aluminum fins.
n Optimized
circuiting for HFC and HFO refrigerants.
n Sealed
and pressurized from the factory.
MS A 2 6 E - 0390 T C K K
AIR DEFROST
COOLER AWEF BY REFRIGERANT and MOTOR
* For motor code and refrigerant, use “D” when AWEF rating is shown and “A” for non-regulated * For motor code andor
applications refrigerant,
where AWEFuse "D" whenDe-rate
is N/A. AWEF rating
capacity 12%andfor"A"50forHertz
is shown non-regulated
operationapplications
with 3 phaseor where AWEF
motors is NA.
only.
De-rate capacity 12% for 50 Hertz operation with 3 phase motors only. [ ] Location for the refrigerant letter code.
[ ] Location for the refrigerant letter code. { } 3 phase motor C is standard for non-regulated applications, include “V” for Variable Speed EC control or “D” when Dual Speed control of the variable speed
{ } 3 phase motor C is standard for non-regulated applications, include "V" for Variable Speed EC control
motor will be from a fixed 10 V signal. or "D" when Dual Speed control of the variable speed motor will be from a fixed 10 V signal.
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing). ** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
EXAMPLE FULL MODEL: EXAMPLE FULL MODEL:
MSD36A-0712TVK is DOE / NRCan application with R-448A, Variable Speed EC motor and 208/3/60 power.
MSD36A-0712TVK is DOE / NRCan application with R-448A, Variable Speed EC motor and 208/3/60 power.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
* For motor code and refrigerant, * For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is N/A.
HOT
De-rate capacity 12% for 50 Hertz operation with 3 phase motors only. [ ] GAS DEFROST
Location for - MEDIUM
the refrigerant letter / LOW
code. { } 3 phase motor TEMPERATURE
C is standard for non-regulated applications, include "V" for Variable Speed EC control
use “D” when AWEF rating is or "D" when Dual Speed control of the
AWEF BYvariable speed motor willMOTOR,
REFRIGERANT, be from a fixed
and10 V signal.
APPLICATION
shown and “A” for non-regulated
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
applications or where AWEF is N/A. [G] STOCK UNIT**, [N] STOCK UNIT***,
De-rate capacity 12% for 50 Hertz *** N Stock Units are for non-glide or glide refrigerants
[Q] R-407A, [F] R-407F,(consult I/O manual[S]
for R-404A,
complete refrigerant listing).
[T] R-448A, [R] R-449A [P] R-507A
operation with 3 phase motors only. EXAMPLE FULL MODEL: CAPACITY CAPACITY REFRIGERATION
{D}ual CONNECTIONS DIMENSIONS (IN) SHIP
( ) Gas defrost type K, H, G, or P. MSD36E-0532QDKK is DOE / NRCan with R-407A,{V}ariable {D}ual
Variable Speed EC motor {V}ariable
with Dual Speed (BTU/H)
control and 208/3/60 (BTU/H)
power for fans and defrost. AIR REF
See definition below. [ ] Location for Speed Speed Speed Speed @ 10° F TD @ 10° F TD FLOW CHARGE WGT
the refrigerant letter code. MODEL Freezer Cooler Freezer Cooler Freezer Cooler Freezer Cooler -20° F EVAP +20° F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
{ } Variable Speed EC motor is MS*14( )-0162[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 16,180 19,030 4,120 5/8" 1-1/8" 7 57.00 26.63 26.25 174
standard, include “V” for Variable MS*14( )-0212[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 21,170 24,910 3,920 7/8" 1-1/8" 10 57.00 26.63 26.25 208
Speed control or “D” when Dual MS*15( )-0178[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 17,790 20,930 4,060 5/8" 1-1/8" 7 57.00 26.63 26.25 186
Speed control from 10 V signal will MS*15( )-0223[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 22,260 26,190 3,890 7/8" 1-1/8" 10 57.00 26.63 26.25 221
be applied. MS*16( )-0195[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 19,500 22,940 4,040 5/8" 1-1/8" 7 57.00 26.63 26.25 198
MS*16( )-0239[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 23,890 28,100 3,850 7/8" 1-1/8" 10 57.00 26.63 26.25 236
** G Stock Units are for glide MS*24( )-0323[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 32,340 38,050 8,240 7/8" 1-3/8" 13 102.00 26.63 26.25 297
refrigerants only (consult I/O MS*24( )-0424[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 42,350 49,820 7,840 7/8" 1-3/8" 18 102.00 26.63 26.25 357
manual for complete refrigerant MS*25( )-0356[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 35,580 41,860 8,120 7/8" 1-3/8" 13 102.00 26.63 26.25 317
listing). MS*25( )-0444[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 44,450 52,290 7,780 7/8" 1-3/8" 18 102.00 26.63 26.25 381
MS*26( )-0390[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 39,000 45,880 8,080 7/8" 1-3/8" 13 102.00 26.63 26.25 337
*** N Stock Units are for non-
MS*26( )-0478[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 47,760 56,190 7,700 7/8" 1-3/8" 18 102.00 26.63 26.25 406
glide or glide refrigerants (consult
MS*34( )-0445[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 44,540 52,400 12,135 7/8" 1-5/8" 16 129.00 26.63 26.25 398
I/O manual for complete refrigerant MS*34( )-0602[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 60,200 70,820 11,325 1-3/8" 1-5/8" 23 129.00 26.63 26.25 470
listing). MS*35( )-0502[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 50,180 59,030 12,015 7/8" 1-5/8" 16 129.00 26.63 26.25 425
. MS*35( )-0643[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 64,330 75,680 11,205 1-3/8" 1-5/8" 23 129.00 26.63 26.25 502
MS*36( )-0532[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 53,220 62,610 11,895 7/8" 1-5/8" 16 129.00 26.63 26.25 452
EXAMPLE FULL MODEL: MS*36( )-0685[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 68,530 80,620 10,995 1-3/8" 1-5/8" 23 129.00 26.63 26.25 534
MSD36P-0685QDAA is for MS*44( )-0594[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 59,390 69,870 16,180 1-3/8" 2-1/8" 21 168.00 26.63 26.25 541
DOE / NRCan application with MS*44( )-0803[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 80,270 94,430 15,100 1-3/8" 2-1/8" 31 168.00 26.63 26.25 616
R-407A, Variable Speed EC motor MS*45( )-0669[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 66,900 78,710 16,020 1-3/8" 2-1/8" 21 168.00 26.63 26.25 578
with 2 speed control and includes MS*45( )-0858[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 85,770 100,910 14,940 1-3/8" 2-1/8" 31 168.00 26.63 26.25 658
the additional letters A for 208 V MS*46( )-0710[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 70,960 83,480 15,860 1-3/8" 2-1/8" 21 168.00 26.63 26.25 615
single phase power. MS*46( )-0914[ ]{ } N/A N/A 4.15 9.00 N/A N/A 4.15 9.00 91,370 107,490 14,660 1-3/8" 2-1/8" 31 168.00 26.63 26.25 700
Available Gas Defrost Types * For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is N/A.
De-rate capacity 12% for 50 Hertz operation with 3 phase motors only. ( ) Gas defrost type K, H, G, or P. See definition below. [ ] Location for the refrigerant letter code.
(H) - HGE 3 Pipe Hot Gas with Electric Pan Heat. No defrost termination or fan delay. (P)motor
{ } Variable Speed EC - KGEis2standard,
Pipe Kool Gas "V"
include withforElectric
VariablePan Heat.
Speed control or "D" when Dual Speed control from 10 V signal will be applied.
(G) - HGG 3 Pipe Hot Gas with Gas Pan Heat. No defrost termination or fan delay. (K) - KGG 2 Pipe Kool**Gas with Gas
G Stock Pan
Units areHeat.
for glide refrigerants only (consult I/O manual for complete refrigerant listing).
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
Standard Features
SM SERIES –
Ideal for Warehouse Coolers or Freezers with a Wide Range of Capacities.
n
Ruggedly constructed cabinets are installed pulled against the ceiling or with hanger rods
sloped towards the drain connection on the end of the unit.
n Efficient draw-thru design with 30" diameter aluminum fan blades provide air throw of 60 feet.
n High efficiency 1 horsepower 3 phase motors operate fans at 850 RPM.
n Wide capacity range with coils with 4, 5, 6, or 7 fins per inch.
n Air defrost models for rooms operating above 34° F.
n Electric and hot gas defrost models for colder rooms and freezers.
n Mill galvanized drain pan and fan cabinet.
n Coated, corrosion-resistant wire fan guards.
n Insulated drain pan on electric and gas defrost models.
n Drain pan and fan cabinet end panels are hinged for easy access and cleaning.
n Factory-wired fans and defrost controls to convenient terminal strips for field connections.
n Adjustable defrost termination and fan delay thermostat installed with electric defrost.
n Coil constructed of heavy-wall copper tube and rippled full collar aluminum fins.
n Optimized circuiting for HFC and HFO refrigerants.
n Sealed and pressurized from the factory.
SV SERIES –
Designed to Deliver Low Temperature Air at High Velocity in Freezers.
n
Ruggedly constructed cabinets are installed pulled against the ceiling or with hanger rods
sloped towards the drain connection on the end of the unit.
n Efficient draw-thru design with 30" diameter aluminum fan blades provide air throw of 80 feet.
n High efficiency 1-1/2 horsepower 3 phase motors operating fans at 1140 RPM.
n Wide capacity range with coils with 4, 5, or 6 fins per inch.
n Electric and hot gas defrost models for low temperature rooms.
n Mill galvanized drain pan and fan cabinet.
n Coated, corrosion-resistant wire fan guards.
n Insulated drain pan on electric and gas defrost models.
n Drain pan and fan cabinet end panels are hinged for easy access and cleaning.
n Factory-wired fans and defrost controls to convenient terminal strips for field connections.
n Adjustable defrost termination and fan delay thermostat installed with electric defrost.
n Coil constructed of heavy-wall copper tube and rippled full collar aluminum fins.
n Optimized circuiting for HFC and HFO refrigerants.
n Sealed and pressurized from the factory.
Model Key
SM A 2 5 E - 0842 T C K K
AIR DEFROST
COOLER AWEF BY REFRIGERANT and MOTOR*
[G] STOCK UNIT**, [N] STOCK UNIT***,
[Q] R-407A, [F] R-407F, [S] R-404A, REFRIGERATION
CAPACITY
[T] R-448A, [R] R-449A [P] R-507A CONNECTIONS DIMENSIONS (IN)
(BTU/H) AIR REF SHIP
{D}ual {V}ariable {D}ual {V}ariable @ 10° F TD FLOW CHARGE WGT
MODEL Speed Speed Speed Speed +25° F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
SM*14A-0314[ ]{ } N/A 9.00 N/A 9.00 31,400 9,860 N/A 1-3/8" 10 77.0 38.5 40.5 410
SM*16A-0378[ ]{ } 9.00 9.00 N/A 9.00 37,800 8,980 N/A 1-3/8" 10 77.0 38.5 40.5 445
SM*17A-0410[ ]{ } 9.00 9.00 N/A 9.00 41,000 8,550 N/A 1-3/8" 10 77.0 38.5 40.5 465
SM*14A-0403[ ]{ } N/A 9.00 N/A 9.00 40,300 9,690 N/A 1-5/8" 13 77.0 38.5 40.5 430
SM*16A-0463[ ]{ } 9.00 9.00 N/A 9.00 46,300 8,810 N/A 1-5/8" 13 77.0 38.5 40.5 470
SM*17A-0503[ ]{ } 9.00 9.00 N/A 9.00 50,300 8,390 N/A 1-5/8" 13 77.0 38.5 40.5 490
SM*14A-0469[ ]{ } 9.00 9.00 N/A 9.00 46,900 9,510 N/A 1-5/8" 16 77.0 38.5 40.5 450
SM*16A-0538[ ]{ } 9.00 9.00 9.00 9.00 53,800 8,480 N/A 1-5/8" 16 77.0 38.5 40.5 495
SM*17A-0585[ ]{ } 9.00 9.00 9.00 9.00 58,500 8,100 N/A 1-5/8" 16 77.0 38.5 40.5 515
SM*14A-0526[ ]{ } 9.00 9.00 N/A 9.00 52,600 9,330 N/A 2-1/8" 19 77.0 38.5 40.5 484
SM*16A-0604[ ]{ } 9.00 9.00 9.00 9.00 60,400 8,400 N/A 2-1/8" 19 77.0 38.5 40.5 530
SM*17A-0657[ ]{ } 9.00 9.00 9.00 9.00 65,700 8,000 N/A 2-1/8" 19 77.0 38.5 40.5 550
SM*24A-0619[ ]{ } N/A 9.00 N/A 9.00 61,900 19,700 N/A 2-1/8" 18 134.3 38.5 40.5 830
SM*26A-0746[ ]{ } N/A 9.00 N/A 9.00 74,600 17,900 N/A 2-1/8" 18 134.3 38.5 40.5 885
SM*27A-0811[ ]{ } N/A 9.00 N/A 9.00 81,100 17,100 N/A 2-1/8" 18 134.3 38.5 40.5 940
SM*24A-0797[ ]{ } N/A 9.00 N/A 9.00 79,700 19,380 N/A 2-5/8" 24 134.3 38.5 40.5 836
SM*26A-0915[ ]{ } 9.00 9.00 N/A 9.00 91,500 17,600 N/A 2-5/8" 24 134.3 38.5 40.5 895
SM*27A-0995[ ]{ } 9.00 9.00 N/A 9.00 99,500 16,800 N/A 2-5/8" 24 134.3 38.5 40.5 950
SM*24A-0882[ ]{ } N/A 9.00 N/A 9.00 88,200 18,890 N/A 2-5/8" 30 134.3 38.5 40.5 845
SM*26A-1063[ ]{ } 9.00 9.00 N/A 9.00 106,300 16,900 N/A 2-5/8" 30 134.3 38.5 40.5 905
SM*27A-1155[ ]{ } 9.00 9.00 N/A 9.00 115,500 16,100 N/A 2-5/8" 30 134.3 38.5 40.5 960
SM*24A-1038[ ]{ } 9.00 9.00 N/A 9.00 103,800 18,400 N/A 2-5/8" 36 134.3 38.5 40.5 858
SM*26A-1192[ ]{ } 9.00 9.00 N/A 9.00 119,200 16,800 N/A 2-5/8" 36 134.3 38.5 40.5 915
SM*27A-1296[ ]{ } 9.00 9.00 9.00 9.00 129,600 15,900 N/A 2-5/8" 36 134.3 38.5 40.5 975
SM*34A-1123[ ]{ } N/A 9.00 N/A 9.00 112,300 28,600 N/A 2-5/8" 33 134.3 38.5 51.0 960
SM*36A-1289[ ]{ } N/A 9.00 N/A 9.00 128,900 24,900 N/A 2-5/8" 33 134.3 38.5 51.0 1,070
SM*37A-1402[ ]{ } N/A 9.00 N/A 9.00 140,200 24,700 N/A 2-5/8" 33 134.3 38.5 51.0 1,090
SM*34A-1243[ ]{ } N/A 9.00 N/A 9.00 124,300 28,000 N/A 2-5/8" 40 134.3 38.5 51.0 1,034
SM*36A-1498[ ]{ } 9.00 9.00 N/A 9.00 149,800 24,600 N/A 2-5/8" 40 134.3 38.5 51.0 1,156
SM*37A-1628[ ]{ } 9.00 9.00 N/A 9.00 162,800 23,700 N/A 2-5/8" 40 134.3 38.5 51.0 1,175
SM*34A-1463[ ]{ } 9.00 9.00 N/A 9.00 146,300 27,400 N/A 2-5/8" 48 134.3 38.5 51.0 1,100
SM*36A-1678[ ]{ } 9.00 9.00 N/A 9.00 167,800 24,400 N/A 2-5/8" 48 134.3 38.5 51.0 1,235
SM*37A-1824[ ]{ } 9.00 9.00 N/A 9.00 182,400 23,500 N/A 2-5/8" 48 134.3 38.5 51.0 1,255
SM*44A-1532[ ]{ } N/A 9.00 N/A 9.00 153,200 33,900 N/A 2-5/8" 42 173.0 38.5 52.5 1,280
SM*46A-1846[ ]{ } N/A 9.00 N/A 9.00 184,600 33,200 N/A 2-5/8" 42 173.0 38.5 52.5 1,430
SM*47A-1920[ ]{ } 9.00 9.00 N/A 9.00 192,000 32,930 N/A 2-5/8" 42 173.0 38.5 52.5 1,455
SM*44A-1829[ ]{ } N/A 9.00 N/A 9.00 182,900 33,400 N/A 2-5/8" 52 173.0 38.5 52.5 1,380
SM*46A-2204[ ]{ } 9.00 9.00 N/A 9.00 220,400 32,800 N/A 2-5/8" 52 173.0 38.5 52.5 1,540
SM*47A-2281[ ]{ } 9.00 9.00 N/A 9.00 228,100 31,600 N/A 2-5/8" 52 173.0 38.5 52.5 1,565
SM*44A-2015[ ]{ } 9.00 9.00 N/A 9.00 201,500 33,000 N/A 2-5/8" 62 173.0 38.5 52.5 1,470
SM*46A-2428[ ]{ } 9.00 9.00 N/A 9.00 242,800 32,530 N/A 2-5/8" 62 173.0 38.5 52.5 1,645
SM*47A-2581[ ]{ } 9.00 9.00 9.00 9.00 258,100 31,330 N/A 2-5/8" 62 173.0 38.5 52.5 1,670
* For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is N/A.
* For motor code and refrigerant, use “D” when AWEF rating is shown and “A” for non-regulated applications or where AWEF is N/A.Include fan motor heat of 4000 BTU/H per fan for SM and 6600 BTU/H
Include fan motor heat of 4000 BTU/H per fan for SM and 6600 BTU/H per fan for SV models in room load calculations. De-rate capacity 12% for 50 Hertz operation with 3 phase motors only.
per fan for SV models in room load calculations.[ De-rate
] Location for the refrigerant letter code. { } 3 phasewith
capacity 12% for 50 Hertz operation 3 phase
motor motorsforonly.
C is standard [ ] Location
non-regulated for the refrigerant
applications, include "V"letter code.Speed
for Variable { } 3 EC
phase motor
control C iswhen
or "D" standard for control
Dual Speed
non-regulated applications, include “V” for Variable Speed EC control or “D” when Dual Speed control o f the variable speed motor will be from a fixed 10ofVthesignal. variable speed motor will be from a fixed 10 V signal.
** Consult I/O manual for complete refrigerant listing. ** Connsult I/O manual for complete refrigerant listing.
Key Point -
Prices, product availability, and specifications
Krack evaporator capacities
are subject to change shown are with midpoint evaporating temperature to offer a consistent capacity
without notice. Page 1 of 1
for selection when using different refrigerants and match other Krack and Hussmann equipment.
applications or where AWEF is N/A. [G] STOCK UNIT**, [N] STOCK UNIT***,
Include fan motor heat of 4000 BTU/H [Q] R-407A, [F] R-407F, [S] R-404A,
per fan in room load calculations. [T] R-448A, [R] R-449A [P] R-507A
CAPACITY CAPACITY REFRIGERATION
De-rate capacity 12% for 50 Hertz {D}ual {V}ariable {D}ual {V}ariable CONNECTIONS DIMENSIONS (IN)
(BTU/H) (BTU/H) AIR REF SHIP
operation with 3 phase motors Speed Speed Speed Speed
@ 10° F TD @ 10° F TD FLOW CHARGE WGT
only. Four fan SM/SV models for SM MODEL Freezer Cooler Freezer Cooler Freezer Cooler Freezer Cooler -20° F EVAP +20° F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
low temperature requires two SM*14E-0384[ ]{ } 4.15 N/A 4.15 9.00 N/A N/A 4.15 9.00 38,400 40,300 9,690 N/A 1-5/8" 13 77.00 38.50 40.50 440
expansion valves. SM*15E-0426[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 42,600 44,700 6,250 N/A 1-5/8" 13 77.00 38.50 40.50 450
[ ] Location for the refrigerant letter SM*16E-0440[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 44,400 46,300 8,810 N/A 1-5/8" 13 77.00 38.50 40.50 470
code. { } 3 phase motor C is standard SM*14E-0501[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 50,100 52,600 9,330 N/A 2-1/8" 19 77.00 38.50 40.50 495
for non-regulated applications, SM*15E-0556[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 55,600 58,400 8,900 N/A 2-1/8" 19 77.00 38.50 40.50 505
include “V” for Variable Speed EC SM*16E-0574[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 57,400 60,400 8,400 N/A 2-1/8" 19 77.00 38.50 40.50 530
control or “D” when Dual Speed SM*24E-0759[ ]{ } 4.15 N/A 4.15 9.00 N/A N/A 4.15 9.00 75,900 79,700 19,380 N/A 2-1/8" 24 134.30 38.50 40.50 836
control of the variable speed motor SM*25E-0842[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 84,200 88,400 18,500 N/A 2-1/8" 24 134.30 38.50 40.50 874
will be from a fixed 10 V signal. SM*26E-0869[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 86,900 91,500 17,600 N/A 2-1/8" 24 134.30 38.50 40.50 912
SM*24E-0989[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 98,900 103,800 18,400 N/A 2-5/8" 36 134.30 38.50 40.50 860
** G Stock Units are for glide SM*25E-1097[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 109,700 115,200 17,600 N/A 2-5/8" 36 134.30 38.50 40.50 900
refrigerants only (consult I/O manual SM*26E-1132[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 113,200 119,200 16,800 N/A 2-5/8" 36 134.30 38.50 40.50 920
for complete refrigerant listing). SM*34E-1070[ ]{ } 4.15 N/A 4.15 9.00 N/A N/A 4.15 9.00 107,000 112,300 28,600 N/A 2-5/8" 33 134.30 38.50 51.00 1,030
SM*35E-1186[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 118,600 124,500 27,300 N/A 2-5/8" 33 134.30 38.50 51.00 1,050
*** N Stock Units are for non-glide
SM*36E-1225[ ]{ } 4.15 N/A 4.15 9.00 N/A N/A 4.15 9.00 122,500 128,900 24,900 N/A 2-5/8" 33 134.30 38.50 51.00 1,060
or glide refrigerants (consult
SM*34E-1393[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 139,300 146,300 27,400 N/A 2-5/8" 48 134.30 38.50 51.00 1,195
I/O manual for complete
SM*35E-1544[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 154,400 162,100 26,100 N/A 2-5/8" 48 134.30 38.50 51.00 1,215
refrigerant listing). N/A 159,400 25,800 N/A 2-5/8" 48 134.30 38.50
SM*36E-1594[ ]{ } 4.15 9.00 4.15 9.00 N/A 4.15 9.00 167,800 51.00 1,240
¥ Unit requires two (2) expansion SM*44E-1465[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 146,500 167,000 38,130 N/A (2) 2-1/8" 47 173.00 38.50 52.50 1,370
valves. Face split is included in the SM*45E-1523[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 152,300 173,600 36,400 N/A (2) 2-1/8" 47 173.00 38.50 52.50 1,340
base model price. Face split is only SM*46E-1754[ ]{ } 4.15 N/A 4.15 9.00 N/A N/A 4.15 9.00 175,400 184,600 33,200 N/A (2) 2-1/8" 47 173.00 38.50 52.50 1,400
required for 4- fan, 6-row low temp ¥ SM*44E-1769[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 176,900 201,800 36,530 N/A (2) 2-1/8" 67 173.00 38.50 52.50 1,469
¥ SM*45E-1985[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 198,500 226,300 34,800 N/A (2) 2-1/8" 67 173.00 38.50 52.50 1,540
applications.
¥ SM*46E-2307[ ]{ } 4.15 9.00 4.15 9.00 N/A N/A 4.15 9.00 230,700 242,800 32,530 N/A (2) 2-1/8" 67 173.00 38.50 52.50 1,600
EXAMPLE FULL MODEL:
SMD36E-1225SVK is DOE / NRCan * For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is N/A. Include fan motor heat of 4000 BTU/H per fan in room load calculations. De-rate capacity 12% for 50 Hertz operation
with R-404A, variable speed motors with 3 phase motors only. Four fan SM/SV models for low temperature requires two expansion valves. LOW TEMPERATURE
[ ] Location for the refrigerant letter code. { } 3 phase motor C is standard for non-regulated applications, include "V" for
Variable Speed EC control or "D" when Dual Speed control of the variable speed motor will be from a fixed 10 V signal.
and 208/3/60 power. FREEZER AWEF BY REFRIGERANT and MOTOR
** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
[G] STOCK UNIT**, [N] STOCK UNIT***,
*** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
[Q] R-407A, [F] R-407F, [S] R-404A, REFRIGERATION
* For motor code and refrigerant, use CAPACITY CAPACITY
¥ Unit requires two (2) expansion[T]
valves. Face split[R]
R-448A, is included
R-449Ain the base model[P]
price.R-507A
Face split is only required for 4-fan, 6-row low temp applications. CONNECTIONS DIMENSIONS (IN)
“D” when AWEF rating is shown and (BTU/H) (BTU/H) AIR REF SHIP
{D}ual {V}ariable {D}ual {V}ariable @ 10° F TD @ 10° F TD FLOW CHARGE WGT
“A” for non-regulated applications or EXAMPLE
SV MODELFULL MODELS: Speed Speed Speed Speed -20° F EVAP +20° F EVAP (CFM) LIQ SUCT (LBS) L W H (LBS)
where AWEF is N/A. SV models are SMD36E-1225SVK is DOE / NRCan with R-404A, variable speed motors and 208/3/60 power.
SV*14E-0422[ ]C N/A 4.15 N/A 4.15 42,200 - 11,250 N/A 2-1/8" 13 77.00 38.50 40.50 440
available for use in non-regulated
SV*15E-0468[ ]C N/A 4.15 N/A 4.15 46,800 - 11,125 N/A 2-1/8" 13 77.00 38.50 40.50 450
applications. 3 phase motors can
SV*16E-0664[ ]C N/A 4.15 N/A 4.15 66,400 - 11,000 N/A 2-1/8" 13 77.00 38.50 40.50 530
be upgraded to Variable Speed EC
SV*14E-0550[ ]C N/A 4.15 N/A 4.15 55,000 - 11,250 N/A 2-1/8" 19 77.00 38.50 40.50 495
motors for energy savings. - 19 77.00 38.50 40.50 505
SV*15E-0611[ ]C N/A 4.15 N/A 4.15 61,100 11,125 N/A 2-1/8"
Include fan motor heat of 6600 BTU/H SV*16E-0684[ ]C N/A 4.15 N/A 4.15 68,400 - 11,000 N/A 2-1/8" 19 77.00 38.50 40.50 540
per fan in room load calculations. SV*24E-0834[ ]C N/A 4.15 N/A 4.15 83,400 - 24,225 N/A 2-1/8" 24 134.30 38.50 40.50 836
De-rate capacity 12% for 50 Hertz SV*25E-0926[ ]C N/A 4.15 N/A 4.15 92,600 - 23,125 N/A 2-1/8" 24 134.30 38.50 40.50 874
operation with 3 phase motors only. SV*26E-1005[ ]C N/A 4.15 N/A 4.15 100,500 - 22,800 N/A 2-1/8" 24 134.30 38.50 40.50 912
Four fan SM/SV models for SV*24E-1088[ ]C N/A 4.15 N/A 4.15 108,800 - 23,000 N/A 2-1/8" 36 134.30 38.50 40.50 860
low temperature requires two SV*25E-1206[ ]C N/A 4.15 N/A 4.15 120,600 - 22,000 N/A 2-1/8" 36 134.30 38.50 40.50 900
expansion valves. [ ] Location for SV*26E-1311[ ]C N/A 4.15 N/A 4.15 131,100 - 21,550 N/A 2-1/8" 36 134.30 38.50 40.50 920
the refrigerant letter code. SV*34E-1177[ ]C N/A 4.15 N/A 4.15 117,700 - 35,750 N/A 2-5/8" 33 134.30 38.50 51.00 1,030
{ } 3 phase motor C is standard for SV*35E-1304[ ]C N/A 4.15 N/A 4.15 130,400 - 34,125 N/A 2-5/8" 33 134.30 38.50 51.00 1,050
non-regulated applications, include SV*36E-1418[ ]C N/A 4.15 N/A 4.15 141,800 - 33,400 N/A 2-5/8" 33 134.30 38.50 51.00 1,060
“V” for Variable Speed EC controller SV*34E-1530[ ]C N/A 4.15 N/A 4.15 153,000 - 34,250 N/A 2-5/8" 48 134.30 38.50 51.00 1,195
“D” when Dual Speed control of the SV*35E-1698[ ]C N/A 4.15 N/A 4.15 169,800 - 32,625 N/A 2-5/8" 48 134.30 38.50 51.00 1,215
variable speed motor will be from a SV*36E-1843[ ]C N/A 4.15 N/A 4.15 184,300 - 32,000 N/A 2-5/8" 48 134.30 38.50 51.00 1,240
fixed 10 V signal. SV*44E-1699[ ]C N/A 4.15 N/A 4.15 169,900 - 47,650 N/A (2) 2-1/8" 47 173.00 38.50 52.50 1,370
SV*45E-1883[ ]C N/A 4.15 N/A 4.15 188,300 - 45,500 N/A (2) 2-1/8" 47 173.00 38.50 52.50 1,340
** G Stock Units are for glide SV*46E-2047[ ]C N/A 4.15 N/A 4.15 204,700 - 44,500 N/A (2) 2-1/8" 47 173.00 38.50 52.50 1,400
refrigerants only (consult I/O manual ¥ SV*44E-2052[ ]C N/A 4.15 N/A 4.15 205,200 - 45,650 N/A (2) 2-1/8" 67 173.00 38.50 52.50 1,469
for complete refrigerant listing). ¥ SV*45E-2274[ ]C N/A 4.15 N/A 4.15 227,400 - 43,600 N/A (2) 2-1/8" 67 173.00 38.50 52.50 1,540
¥ SV*46E-2472[ ]C N/A 4.15 N/A 4.15 247,200 - 42,700 N/A (2) 2-1/8" 67 173.00 38.50 52.50 1,600
*** N Stock Units are for non-glide
or glide refrigerants (consult I/O * For motor code and refrigerant, use "D" when AWEF rating is shown and "A" for non-regulated applications or where AWEF is N/A.
manual for complete refrigerant SV models are available for use in non-regulated applications. 3 phase motors can be upgraded to Variable Speed EC motors for energy savings.
listing). Include fan motor heat of 6600 BTU/H per fan in room load calculations. De-rate capacity 12% for 50 Hertz operation with 3 phase motors only.
Key Point -
Four fan SM/SV models for low temperature requires two expansion valves.
¥ Unit requires two (2) expansion [ ] Location
Krack evaporator capacities shown areforwith
the refrigerant letter code. {evaporating
midpoint } 3 phase motor C is standard for non-regulatedto
temperature applications,
offerinclude "V" for Variable Speed
a consistent EC control
capacity
valves. Face split is included in the or "D" when Dual Speed control of the variable speed motor will be from a fixed 10 V signal.
for selection when using different refrigerants and match other Krack and Hussmann equipment.
base model price. Face split is only ** G Stock Units are for glide refrigerants only (consult I/O manual for complete refrigerant listing).
required for 4- fan, 6-row low temp *** N Stock Units are for non-glide or glide refrigerants (consult I/O manual for complete refrigerant listing).
applications. ¥ Unit requires two (2) expansion valves. Face split is included in the base model price. Face split is only required for 4-fan, 6-row low temp applications.
EXAMPLE FULL MODEL: COMMERCIAL CONDENSED PRODUCT CATALOG 27
EXAMPLE FULL MODELS:
SMD36E-1225SVK is DOE / NRCan
Specifications subject
SVA36E-1418QCK to change
is for non-regulated without
applications notice.
with R-407A, 3 phase motors and 208/3/60 power.
with R-404A, variable speed motors
and 208/3/60 power.
SM/SV Series Unit Coolers
** FFor
or motor
motorcode
codeandandrefrigerant,
refrigerant, “D” AWEF
use when
use "D" whenrating
AWEFisrating
shown isandshown
"A" forand “A” for non-regulated
non-regulated applications orapplications where AWEF is N/A. Available
where AWEF isorN/A. Gas Defrost
( ) Gas defrost type K,Types
H, G, or P. See definition to the right.
[( ]) Gas defrostfor
Location type
theK, refrigerant
H, G, or P. See definition
letter code.to{ the right. [ ]Speed
} Variable LocationECformotor
the refrigerant letterinclude
is standard, code. “V” for Variable Speed EC control or “D”(H)when- HGEDual Speed
3 Pipe control
Hot Gas from 10PanV signal
with Electric Heat. Nowill be applied.
defrost termination or fan delay.
{ } Variable Speed EC motor is standard, include "V" for Variable Speed EC control or "D" when Dual Speed control from 10 V signal will be applied. (G) - HGG 3 Pipe Hot Gas with Gas Pan Heat. No defrost termination or fan delay.
**
** GG Stock
StockUnits
Unitsareare
for for
glideglide refrigerants
refrigerants only (consult
only (consult I/Ofor
I/O manual manual forrefrigerant
complete completelisting).
refrigerant listing). (P) - KGE 2 Pipe Kool Gas with Electric Pan Heat.
*** NNStock (K) - KGG 2 Pipe Kool Gas with Gas Pan Heat.
*** StockUnits
Unitsareare
for non-glide or glide
for non-glide or refrigerants (consult (consult
glide refrigerants I/O manualI/Oformanual
completeforrefrigerant
completelisting).
refrigerant listing).
¥ Unit requires two (2) expansion valves. Face split is included in the base model price. Face split is only required for
¥ Unit requires
4-fan, twotemp
6-row low (2) applications.
expansion valves. Face split is included in the base model price. Face split is only required for 4- fan, 6-row low temp applications.
Example Full Model:
EXAMPLE FULL MODEL:
MKD36P-309QDAA is for DOE / NRCan application with R-407A, Dual Speed EC motor and includes the additional letters AA for 208 V single phase power.
MKD36P-309QDAA is for DOE / NRCan application with R-407A,
Dual Speed EC motor and includes the additional letters AA for 208 V single phase power.
Available Gas Defrost Types
(H) - HGE 3 Pipe Hot Gas with Electric Pan Heat No defrost termination or fan delay.
(G) - HGG 3 Pipe Hot Gas with Gas Pan Heat. No defrost termination or fan delay.
(P) - KGE 2 Pipe Kool Gas with Electric Pan Heat.
(K) - KGG 2 Pipe Kool Gas with Gas Pan Heat.
Key Point -
Krack evaporator capacities shown are with midpoint evaporating temperature to offer a consistent capacity
for selection when using different refrigerants and match other Krack and Hussmann equipment.
KR LH GH / GL
DUAL SPEED VARIABLE SPEED DUAL SPEED VARIABLE SPEED DUAL SPEED VARIABLE SPEED
MOTORS MOTORS MOTORS MOTORS MOTORS MOTORS
* Glide refrigerants
DEFROST TYPE
(R-407A, R-407F, R-448A, R-449A, Air
refer to I/O Manual for others). X X X X X X
Glide Refrigerants*
Models in tables with ‘*’ are not
Non-Glide Refrigerants** X X - X X (Except GL*56A and GL*14A) X
tied to this note.
CO2
** Non-Glide refrigerants X X - X X X
Coolers
(R-404A, R-507A, refer to
Freezers - - - - - -
I/O Manual for others)
Electric
*** Room T-Stat needs to be Glide Refrigerants*
separate from T-Stat
Coolers X X X (Except LH*44E) X X X
controlling motors
Freezers X X X (Except LH*44E) X - -
**** Includes 10 V power supply Non-Glide Refrigerants**
for driving fans to low speed
Coolers - X - X X (Except GL*56D and GL*14D) X
***** Amplifier works with a Freezers - X - X - -
maximum of six motors CO2
1
Only one control may Coolers X X - X X X
be selected Freezers X X X (Except LH*44E-132) X X X
Hot Gas
Glide Refrigerants*
Coolers X X - - X X
Freezers X X - - - -
Non-Glide Refrigerants**
Coolers - X - - X (Except GL*56( ) and GL*14( )) X
Freezers - X - - - -
VOLTAGES / PHASE (All 60 HZ)
115/1 X X X X X X
208-230/1 X X X X X X
208-230/3 X X X X X X
460/1 - - - - - -
460/3 - - - - - -
575/3 - - - - - -
FAN CONTROLS
RT-3*** - T-Stat 1 - 1 - 1 -
X X X
RT-4*** - T-Stat with 0 to 10 V Power Supply - - - - - -
R24V - Relay if Remote Board 1 - 1 - 1 -
X X X
R24P**** - Relay If Remote Board - - - - - -
VC4P - JC450 plus Amplifier - 1 - 1 - 1
X X X
AMP1***** - Amplifier for
- 1 - 1 - 1
Remote Controller X X X
VC4 - JC450 Loose - - - - - -
VC4A, VC4B - JC450 Mounted
- - - - - -
with Transformer
KE2 Therm - - - - - -
Expansion Valves
TEV - - - - - -
Sporlan Stepper Valve - - - - - -
Control Boards
KE2 OEM Board - - - - - -
Sensors
Air Defrost - 3 Temp Sensors
- - - - - -
(1 Room, 2 Coils)
Positive Defrost - 3 Temp Sensors
- - - - - -
(1 Room, 2 Coils)
Options
Remote Display
- - - - - -
(Stays within Six Feet of Board)
Edge Manager
- - - - - -
(for Remote Wifi Access and Data Logging)
8 or 16 Port Switch
- - - - - -
(Inter-Connecting Multiple Boards)
* Glide Refrigerants (R-407A, R-407F, R-448A, R-449A, refer to I/O Manual for others). Models in tables with '*' are not tied to this note.
** Non-Glide Refrigerants (R-404A, R-507A, refer to I/O Manual for others)
*** Room T-Stat needs to be separate from T-Stat Controlling Motors
**** Includes 10 V Power Supply for Driving Fans to Low Speed
COMMERCIAL CONDENSED PRODUCT CATALOG 29
***** Amplifier Works with a Maximum of Six Motors
1
Specifications subject to change without notice.
Only One Control may be selected
Commercial Condensed Product Catalog
MK / MV MS SM / SV
DUAL SPEED VARIABLE SPEED DUAL SPEED VARIABLE SPEED DUAL SPEED VARIABLE SPEED
MOTORS MOTORS MOTORS MOTORS MOTORS MOTORS
DEFROST TYPE
Air * G lide refrigerants
X (Except SM*14A, SM*24A, (R-407A, R-407F, R-448A, R-449A,
SM*26A-0746, SM*27A-0811,
Glide Refrigerants* X X - X SM*34A-1123 and 1243, SM*36A- X
refer to I/O Manual for others).
1289, SM*37A-1402, SM*44A-1532 Models in tables with ‘*’ are not
and 1829, SM*46A-1846) tied to this note.
X (Except MK*18A-133, MK*28A- X (Units Available:
266, MK*16A-118, MK*26A-236 SM*16A-0538 and 604, SM*17A- ** N on-Glide refrigerants
Non-Glide Refrigerants** X - X X
and 290, MK*14A-94 and 121, 0585 and 0657, SM*27A-1296, (R-404A, R-507A, refer to
MK*24A-188 and 242) and SM*47A-2581)
I/O Manual for others)
CO2
Coolers X X N/A N/A N/A N/A *** R oom T-Stat needs to be
Freezers - - N/A N/A N/A N/A separate from T-Stat
Electric
controlling motors
Glide Refrigerants*
**** Includes 10 V power
X (Except SM*14E-0384, SM*24E- supply for driving fans
Coolers X X (Except ALL MV Models) - X 0759, SM*34E-1070, SM*36E- X
1225, SM*46E-1754) to low speed
Freezers X (Except ALL MV Models) X (Except All MV Models) - X X (Except ALL SV Models) X
***** A mplifier works with a
Non-Glide Refrigerants** maximum of six motors
Coolers - X (Except All MV Models) - X - X
Freezers - X (Except All MV Models) - X - X
1
O nly one control may
be selected
CO2
Coolers X X N/A N/A N/A N/A
2
O nly on multiple fan units wired
Freezers X X N/A N/A N/A N/A for 3 phase operation
Hot Gas 3
C hoose only one type of
Glide Refrigerants* expansion valve
X (Except SM*14( )-0384,
Coolers X (Except ALL MV Models) X (Except ALL MV Models) - X SM*24( )-0759, SM*34( )-1070, X
4
C hoose only one based upon
SM*36( )-1225, SM*46( )-1754) either air or positive defrost
Freezers X (Except ALL MV Models) X (Except ALL MV Models) - X X X requirements
Non-Glide Refrigerants** 5
ore than one option can
M
Coolers - X (Except ALL MV Models) - X - X be chosen
Freezers - X (Except ALL MV Models) - X - X
VOLTAGES / PHASE (All 60 HZ)
115/1 X X X X - -
208-230/1 X X X X - -
208-230/3 2 2 2 2 X X
X X X X
460/1 - - - - - -
460/3 - - - - X X
575/3 - - - - - -
FAN CONTROLS
RT-3*** - T-Stat - - - - - -
RT-4*** - T-Stat with 0 to 10 V Power Supply 1 - 1 - 1 -
X X X
R24V - Relay if Remote Board - - - - - -
R24P**** - Relay If Remote Board 1 - 1 - 1 -
X X X
VC4P - JC450 plus Amplifier - - - - - -
AMP1***** - Amplifier for
- - - - - -
Remote Controller
KE2 Therm - 1 - 1 - 1
X X X
Expansion Valves
TEV - 3 - 3 - 3
X X X
Sporlan Stepper Valve - 3 - 3 - 3
X X X
Control Boards
KE2 OEM Board - X - X - X
Sensors
Air Defrost - 3 Temp Sensors
- 4 - 4 - 4
(1 Room, 2 Coils) X X X
Edge Manager
- 5 - 5 - 5
(for Remote Wifi Access and Data Logging) X X X
8 or 16 Port Switch
- 5 - 5 - 5
(Inter-Connecting Multiple Boards) X X X
The LEVITOR system addresses refrigerant coil wear and leaks due to vibration and thermal stress.
LEVITOR Coil Design Eliminates Refrigerant Tube Wear
Environmental concerns and spiraling cost of refrigerants have led to the development of direct drive
remote air-cooled condensers with the LEVITOR coil support system. This innovative design uses dedicated
stainless steel tubes and a unique coil support system to isolate refrigerant tubes from the unit. Coil support
is transferred from the fins to the stainless tubes and truncated tube plates which ride freely in “C” channels.
Tubes expand and contract without interference. The result, contact and friction wear are eliminated.
Quiet by Design
LEVITOR coil design does more than just eliminate tube wear. Sound reduction is an added benefit.
Unlike traditional air-cooled condensers, fan and coil vibration are isolated from the cabinet, so it is not
transmitted to the unit frame and building supports.
Vspeed Variable Speed Condenser Fan Solutions Direct Driven Propeller Fans
n rack’s latest fan motor technology is now offered with
K n Quiet
multi-bladed propeller fans provide uniform air
a variable speed fan motor solution called Vspeed under distribution through the coil. Venturi fan orifices optimize
the LAVK configuration that utilizes a Brushless Permanent efficiency.
Motor (BPM) and panel mounted electronic drive (per
motor). The electronic drive will vary the fan speeds High Efficiency Coil
(1140 RPM at 0 volts / 0 RPM at 10 volts) to match the n Copper
tubes are mechanically expanded into corrugated
loads saving more energy versus single speed fans. full collared aluminum fins spaced 8, 10, or 12 per inch.
Fan blade configurations, mounting, and capacities are Coils are helium leak and pressure tested with 400 psig
equivalent to the standard 1140 RPM motor options. dry air, shipped pressurized with dry nitrogen.
Low Sound Quietor Fan n Optional
fin materials are copper or polyester coated
aluminum.
n The
“swept-wing” blade design offers lower noise levels at
the same fan speed. For example, the QUIETOR fan blade n Optional
Electrofin or Heresite coil coatings.
on a 575 RPM motor will be much quieter (8 dBA) than the n Multi-circuiting
available.
old 575 RPM fan.
n ower noise condensers can translate into savings for your
L Fan Motors and Electrical Rating
customer by minimizing the need of costly noise barriers. n Outdoor
condenser motors designed with ball bearings
n Q
uietor fan not available on 24" models. inherent overheat protection in each phase; shaft slingers;
enclosure, hardware, and lubrication for all weather
Computerized Circuiting conditions. Each motor lead is wired to terminals in an
electrical enclosure.
n ur computerized coil circuiting program is designed to
O
minimize the condenser refrigerant charge and maximize n Inverter duty motors are standard for 230/3 ,460/3
sub-cooling. Every condenser will be custom circuited to and some 575/3 (F = 1140 RPM and A = 850 RPM 1 HP)
precisely meet your application needs. condensers.
n All
models employ mill galvanized steel fan sections n Temperature
fan cycling
and coil side baffles. Legs are heavy gauge mill n Pressure
fan cycling
galvanized steel. n Temperature
and pressure fan cycling
n Electronic
relay boards
Use your QR reader to
reference current document n Variable
speed header end fans
version on www.krack.com. US n E
nergy-saving variable speed options for all fans
Model Key
L A V A 1 2 4 10 M
* K Vspeed Variable Speed BPM (brushless permanent magnet motors) and panel mounted electronic drive are 208-240/3/60, 380/3/50, 380/3/60,and 460/3/60.
Gravity dampers should not be used with K motor applications.
** LAVB only.
Levitor Application
Locate Condensers no closer than their width from wall or other
condensers. Avoid locations near exhaust fans, plumbing vents, flues
or chimneys. Reference the IOM for other considerations for locating
condensers.
Gravity Liquid Drain Lines should drop from each outlet as low as possible
before headering or running horizontally. Pitch downhill to receiver.
See Installation and Operating instructions for piping, holdback and fan cycling details.
Notes
See NOTES on 50 HZ operation and TEMPERATURE DIFFERENCE on page 23. See Correction Factor Table for refrigerant charge on page 22.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the entering air temp. to the condenser.
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
See NOTES on 50 HZ operation and TEMPERATURE DIFFERENCE on page 23. See Correction Factor Table for refrigerant charge on page 22.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
See NOTES on 50 HZ operation and TEMPERATURE DIFFERENCE on page 23. See Correction Factor Table for refrigerant charge on page 22.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the entering air temp. to the condenser.
See NOTES on 50 HZ operation and TEMPERATURE DIFFERENCE on page 23. See Correction Factor Table for refrigerant charge on page 22.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
See NOTES on 50 HZ operation and TEMPERATURE DIFFERENCE on page 23. See Correction Factor Table for refrigerant charge on page 22.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
NOTE: Ratings are based on 85°F-115°F entering air temperature. The temperature difference is between the saturated condensing temp. and the entering air temp. to the condenser.
See NOTES on 50 HZ operation and TEMPERATURE DIFFERENCE on page 23. See Correction Factor Table for refrigerant charge on page 22.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
See NOTES on 50 HZ operation and TEMPERATURE DIFFERENCE on page 23. See Correction Factor Table for refrigerant charge on page 22.
CEC TITLE 24 COMPLIANT indicates condenser meets the 65 BTU/H / watt efficiency requirement. To complete the Title 24 compliance, fan speed must vary requiring
an additional VFD and controller on fixed speed motors (F, A, C, E, and B).
Krack recommends the K motor option which has variable speed capability and need only a controller to provide the 0-10 V control signal to meet the regulation.
Model Key
F F 4
FIN MATERIAL:
UNIT TYPE:
TUBE DIAMETER:
" VOLTAGE:
" *
**
FAN DISCHARGE DIRECTIONS: ***
**
****
**
FIN SPACING:
*
ROWS DEEP:
FANS WIDE:
* FAVB only.
** Invertor suitable motor.
* FAVB only. *** Contact Application Engineering for quoting.
** Inverter suitable motor. **** Invertor suitable motor on F and A models
*** Contact Application Engineering for quoting. ***** BPM motors are 208-230/3/60 or 460/3/60 only.
**** Inverter suitable motor on ‘F’ and ‘A’ models.
***** BPM motors are 208-230/3/60 or 460/3/60 only. Gravity dampers should not be used with K motor applications.
Standard Features
Krack’s Microchannel Remote Air-Cooled Condenser incorporates
a patented modular assembly.
n Smaller size and less weight reduces cost in the building construction.
n
The new coil has less internal volume resulting in a significant reduction
in refrigerant charge. Less refrigerant is environmentally friendly.
n Coil slabs are easily replaced from the rear of the unit.
Model Key
MX K - 10 M
UNIT TYPE:
MX - Microchannel MOTOR VOLTAGE:
K - 208-230/3/60
M - 460/3/60
FAN/MOTOR P - 575/3/60
COMBINATION: U - 380/3/50**
A - 850 RPM, 1.0 HP, 30"
NUMBER OF FANS:
C - 850 RPM, 1.5 HP, 30"
2 10
E - 575 RPM, 0.5 HP, 30"
4 12
F - 1140 RPM, 1.5 HP, 30" 6 14
K - 1140 RPM, 1.5 HP, 30"* 8
Applications
n ocate Condensers no closer than their width from wall or other condensers. Avoid locations near exhaust fans,
L
plumbing vents, flues or chimneys. Reference the IOM for other considerations for locating condensers.
n Parallel Condensers should be the same model resulting in the same refrigerant side pressure drops.
Compressor discharge lines should have equal pressure drops to each condenser.
n ondenser Refrigerant Charge for Summer conditions are listed on the Performance Data Table. The additional
C
Winter Flooding charge required is difficult to predict with fan cycling and is maximized with holdback; however, the
maximum additional refrigerant charge is also listed on the Performance Data Table for Winter conditions at -20˚ F.
The Summer operating and Winter maximum flooding charge is substantially less than that required for traditional
tube and fin condensers due to the reduced internal volume of the Microchannel coils. Further reduction in flooding
charge can be obtained with the “Modular Winter Reduction” option, by “shutting down” the associated refrigerant
circuit in combination with fan cycling.
n Compressor Discharge lines should be sized to minimize pressure drops and maintain oil return gas velocities. Each
connection should be looped to the top of the condenser.
n ravity Liquid Drain Lines should drop from each outlet as low as possible before headering or running horizontally.
G
Pitch downhill to receiver.
n ff-Line Coil Sections will have refrigerant pressures corresponding to the ambient. Check valves or isolating valves
O
should be installed in the liquid line drains to prevent refrigerant migration and receiver pressure loss.
Performance Data
PERFORMANCE DATA
TOTAL HEAT OF REJECTION (MBH)
R-404A / R-507A R-407A, R-448A / R-449A
AIR SOUND SUMMER WINTER SHIP
MX TEMP DIFFERENCE TEMP DIFFERENCE FLOW dBA EST CHARGE CHARGE WEIGHT
MODEL 10° F 15° F 20° F 10° F 15° F 20° F (CFM) @10 FT (LBS R-404A) (LBS R-404A) (LBS)
MX( )-02 180.6 270.9 361.2 177.8 266.6 355.5 25,600 75 4 17 560
MX( )-04 361.2 541.9 722.5 355.5 533.3 711.0 51,200 78 8 34 1,170
MXF / MXK
MX( )-06 541.9 812.8 1083.7 533.3 799.9 1066.6 76,800 80 11 50 1,705
1.5 HP MX( )-08 722.5 1083.7 1445.0 711.0 1066.6 1422.1 102,400 81 15 67 2,280
1140 RPM MX( )-10 903.1 1354.7 1806.2 888.8 1333.2 1777.6 128,000 82 19 84 2,850
MX( )-12 1083.7 1625.6 2167.4 1066.6 1599.8 2133.1 153,600 83 23 101 3,385
MX( )-14 1264.3 1896.5 2528.7 1244.3 1866.5 2488.6 179,200 84 26 117 3,920
MXC-02 168.9 253.3 337.7 164.9 247.4 329.8 22,830 68 4 17 560
MXC-04 337.7 506.6 675.4 329.8 494.7 659.6 45,660 71 8 34 1,170
MXC
MXC-06 506.6 759.9 1013.1 494.7 742.1 989.3 68,490 73 11 50 1,705
1.5 HP MXC-08 675.4 1013.1 1350.8 659.6 989.3 1319.1 91,320 74 15 67 2,280
850 RPM MXC-10 844.3 1266.4 1688.5 824.5 1236.7 1648.9 114,150 75 19 84 2,850
MXC-12 1013.1 1519.7 2026.2 989.3 1484.0 1978.7 136,980 76 23 101 3,385
MXC-14 1182.0 1773.0 2363.9 1154.2 1731.4 2308.5 159,810 77 26 117 3,920
MXA-02 160.8 241.2 321.6 155.3 233.0 310.6 20,800 66 4 17 560
MXA-04 321.6 482.5 643.3 310.6 466.0 621.3 41,600 69 8 34 1,170
MXA MXA-06 482.5 723.7 964.9 466.0 698.9 931.9 62,400 71 11 50 1,705
1.0 HP MXA-08 643.3 964.9 1286.6 621.3 931.9 1242.6 83,200 72 15 67 2,280
850 RPM MXA-10 804.1 1206.2 1608.2 776.6 1164.9 1553.2 104,000 73 19 84 2,850
MXA-12 964.9 1447.4 1929.8 931.9 1397.9 1863.8 124,800 74 23 101 3,385
MXA-14 1125.7 1688.6 2251.5 1087.2 1630.9 2174.5 145,600 75 26 117 3,920
MXE-02 115.0 172.5 229.9 112.0 168.0 224.0 12,600 55 4 17 560
MXE-04 229.9 344.9 459.8 224.0 335.9 447.9 25,200 58 8 34 1,170
MXE
MXE-06 344.9 517.3 689.7 335.9 503.9 671.9 37,800 60 11 50 1,705
0.5 HP MXE-08 459.8 689.7 919.6 447.9 671.9 895.8 50,400 61 15 67 2,280
575 RPM MXE-10 574.8 862.2 1149.5 559.9 839.9 1119.8 63,000 62 19 84 2,850
MXE-12 689.7 1034.6 1379.4 671.9 1007.8 1343.8 75,600 63 23 101 3,385
MXE-14 804.7 1207.0 1609.3 783.9 1175.8 1567.7 88,200 64 26 117 3,920
CPC NC B 4 1 5 N
RELAY BOARD:
AMBIENT AIR SENSOR:
N - None T - Ambient Air Sensor
CPC - CPC 8RO N - Sensor Not Required
CPC1 - Multiflex 88
CPC2 - Multiflex 88AO
TYPE OF APPLICATION:
AKC - Danfoss 88 with AK2-XM205B (TP78-Old)*
1 - Standard
AKS - Danfoss 88 with AK2-XM205B (RS485)*
4 - No Control Operation (Terminal Blocks Only)
DAN - Danfoss
5 - Modular Winter Reduction (Four Fans or More)
MTH - Microthermo 508
MTH1 - Microthermo 722F and 784A
NOV - Novar FUSES AND BREAKERS:
HSM - Hussmann Controller 1 - Individual Fuses and Contactors
2 - Individual Circuit Breakers and Contactors
RELAY BOARD CONTROLS: 3 - Fuses and Contactors per Pair of Fans
NC - No Controls 4 - Terminal Blocks Only
PT - Pressure Fan Cycling Controls 5 - Circuit Breaker and Contactor per Pair of Fans
TF - Temp. Fan Cycling Controls 6 - Fuses per Motor
TP - Temp. and Pressure Fan Cycling Control 7 - Individual Circuit Breaker per Fan
*PV - Pressure Control w/Variable Speed
*TV - Temp. Control w/Variable Speed CONTROL TYPE:
*VN - No Controls w/Variable Speed 3 - Johnson Electronic
KB - KB Drive 4 - No Controls
CONTROL VOLTAGE:
A - 208/230 V
B - 115 V
C - No Control Voltage
D - 24 V
E - 208/230 V without Transformer
F - 115 V with Transformer
H - 24 V without Transformer
Note:
1
Contact Application Engineering for quoting.
H-Series Legacy Condensing Units provide a robust design for a long service life with
Copeland (Scroll, Discus or Semi-Hermetic) or Bitzer Ecoline compressors with nominal
horsepower ranging from ½ to 12 HP for medium temperature and 15 hp low temperature.
Outdoor units with typical options can be quoted with typical options using the
Technical Bulletin and Price List.
Additional options are available for indoor, stackable, water-cooled, 575/3/60 voltages.
For detailed information on Performance Data and Electrical Specifications, please reference
the H-Series Legacy Condensing Units Technical Bulletin found at www.krack.com.
Model Key
H T S D - 100 0 L S K F F
SERIES
RECEIVER SIZE:
UNIT TYPE: A - 6" x 12"
N - Indoor B - 6" x 18"
T - Outdoor C - 6" x 23"
R - Remote D - 6" x 30"
S - Satellite E - 8.625" x 30"
F - 10.75" x 30"
BASE: G - 10.75" x 38"
S - Standard H - 12.75" x 30"
H - Heavy-Duty X - No Receiver
NOTE: Units are ordered refrigerant specific (i.e. “S” for R-404A)
but will include other refrigerants that can also be used on the data plate.
208-230/1/60
380/3/50
Unit Power 208-230/3/60
575/3/60
460/3/60
Condenser Fan Motor(s) PSC (Permanent Split Capacitor Type) ECM (Under Development)
Frame/Receiver Type Standard Base (Vertical Receiver) Heavy-Duty Base (Horizontal Receiver)
Electronic
Defrost Method Time Clock Contactors and Fuses for Electric Defrost
Sealed
Suction Filter None Steel Replaceable Core
Brass Replaceable Core
Replaceable Core
Liquid Drier Sealed with Sight Glass
with Sight Glass
Accumulator
Suction Accumulator None Accumulator with Boil-Out
Available with either Scroll or Reciprocating compressors. Nominal compressor capacities up to 16 HP.
These refrigeration systems are not intended for use in Walk-In Coolers or Freezers where US Department of Energy (DOE) or Natural Resources Canada (NRCan) efficiency requirements apply.
Model Key
H D S D - 100 0 L S K F F - D
SERIES DOE:
D - DOE / NRCan
UNIT TYPE: A - Non-Regulated
E - Indoor,
High Efficiency RECEIVER SIZE:
D - Outdoor, A = 6" x 12"
High Efficiency B - 6" x 18"
C - 6" x 23"
BASE: D - 6" x 30"
S - Standard E - 8.625" x 30"
H - Heavy-Duty F - 10.75" x 30"
G - 10.75" x 38"
COMPRESSOR TYPE: H - 12.75" x 30"
D - Copeland Discus X - No Receiver
Z - Copeland Scroll
B - Bitzer Ecoline, Motor 2 CONDENSER SIZE:
E - Bitzer Ecoline, Motor 1 A - Small, 3 Row, 1 Fan
S - Copeland Semi-Hermetic B - Medium, 3 Row, 1 Fan
D - Medium, 4 Row, 2 Fan
COMPRESSOR HORSEPOWER: F - Large, 4 Row, 4 Fan
005 - 0.5 HP J - XLarge, 4 Row, 6 Fan
030 - 3.0 HP
100 - 10.0 HP VOLTAGE:
150 - 15.0 HP D - 208-230 V/1 PH/60 HZ
K - 208-230 V/3 PH/60 HZ
ALTERNATIVE: M - 460 V/3 PH/60 HZ
0 - Basic P - 575 V/3 PH/60 HZ
1 - First Alternative U - 380 V/3 PH/50 HZ
2 - Second Alternative
REFRIGERANT:
TEMPERATURE RANGE: S - R-404A
M - Medium (Max. Evap. Temp. = +35˚ F) P - R-507A
L - Low (Max. Evap. Temp. = +0˚ F) Q - R-407A
F - R-407F
T - R-448A
R - R-449A
NOTE: Units are ordered refrigerant specific (i.e. “S” for R-404A)
but will include other refrigerants that can also be used on the data plate.
208-230/1/60
380/3/50
Unit Power 208-230/3/60
575/3/60
460/3/60
Condenser Fan Motor(s) PSC (Permanent Split Capacitor Type) ECM (Under Development)
Frame/Receiver Type Standard Base (Vertical Receiver) Heavy-Duty Base (Horizontal Receiver)
Electronic
Defrost Method Time Clock Contactors and Fuses for Electric Defrost
Sealed
Suction Filter None Steel Replaceable Core
Brass Replaceable Core
Replaceable Core
Liquid Drier Sealed with Sight Glass
with Sight Glass
Accumulator
Suction Accumulator None Accumulator with Boil-Out
Available with either Scroll or Reciprocating compressors. Nominal compressor capacities up to 16 HP.
Condensing units with a single refrigeration circuit have AWEF values for application on walk-in coolers
and freezers covered by the DOE and NRCan regulations. Dual refrigeration circuit models are exempt
from both regulations. Unit capacity for different refrigerants are shown in the Technical Bulletin
and all standard options are selectable in the Price List.
For detailed information on DOE regulations, Performance Data, and Electrical Specifications,
please reference the Large Air-Cooled Condensing Units Technical Bulletin found at www.krack.com.
CS B - 0300 - L Q M
APPLICATION TEMPERATURE:
M - Medium
L - Low
* Low and medium temperatures
** Medium and high temperatures
Models
n CS Series Units are new, more efficiently sized units that have a reduced footprint,
more standard features and provide increased options for sizing large jobs.
n CP Series Parallel Units are two compressors piped together to provide one refrigeration circuit.
n CD Series Dual Units are two compressors piped independently for a separate circuit operation.
Note
n Additional information will be given per model on
their respective pages.
Model Features
Hussmann pioneered the development of integrated refrigeration systems and now offers a complete
selection of advanced parallel racks which are available under the Krack brand.
n F
lexible:
Custom designed, engineered, and manufactured under the supervision of the experienced
applications and design engineers in the Non Traditional Request (NTR) group for each application
and to meet specific customer requirement.
n R
eliablePerformance: High-quality components, advanced manufacturing techniques, and extensive
quality testing ensures reliable performance and the lowest warranty cost in the industry.
n E
nergy Efficiency and Reliability: Multiple compressor options, sub-cooling techniques, and
proprietary technologies are used to maximize efficiency and provide long service life.
Model Features
Indoor Protocols: Available in vertical and horizontal configurations with 2 to 8 Scroll compressors.
Outdoor Proto-Aire and OLP (Outdoor Low Profile): Available with up to 6 Scroll compressors.
n Refrigeration systems close to the refrigeration loads with loop piping
significantly reduce refrigerants charge of HFC/HFO in the system.
n Pre-bent tubing on the Protocol and loop piping also
have significantly lower refrigerant leak rates.
n Applications of the variety of systems options is available
through the experienced engineers in the NTR group.
Model Features
Notes
Notes