NRB Model Data Sheet
NRB Model Data Sheet
NRB Model Data Sheet
0800/3000
Chillers.
Air/Water for outdoor installation.
Scroll compressors, plate heat exchangers.
Axial fans.
Cooling capacity 57.77 - 240.8 ton
60Hz
R410A
• OUTDOOR INSTALLATION
• MICROCHANNEL COIL
• NIGHT MODE
CHARACTERISTICS
NRB is a dual-circuit chiller charged with R410a gas. It Range of operation: Work up to 122°F of outdoor different static pressures available.
has axial fans to ensure the quietest possible machine air temperature at full load, depending on size and - Microprocessor adjustment, complete with a 7”
operation, scroll compressors with a high yield and low version. For further details refer to the selection touch screen keyboard, which allows to navigate
electricity absorption, a plate heat exchanger and “V software/technical documentation. intuitively among the various screens, allowing
block” micro-channel coils. The unit with two • Unit with 2 refrigerant circuits designed to to modify the operating parameters and
refrigerant circuits is designed to provide the maximum provide maximum efficiency at full load, also graphically view the progress of some variables
yield when fully charged, but also guaranteeing high ensuring high efficiency at partial loads and in real time.
efficiency even with partial charging and ensuring ensuring continuity in case one of the circuits - The presence of a programmable timer allows
continuity if one of the two circuits stops operating. The stops. setting time bands of operation and a possible
machine cools water to supply the distribution system • The full range uses aluminium microchannel second set-point.
that is usually connected to fan coil type terminals. In coils, ensuring very high levels of efficiency. This - The temperature control takes place with the
addition, NRB can also produce domestic hot water if it allows the use less refrigerant compared to integral proportional logic, based on the leaving
is fitted with a desuperheater or total recovery system. traditional copper coils. water temperature.
It is ideal for residential, commercial and industrial • The possibility of using the electronic thermostatic - Floating HP: is supplied as standard on all
contexts. There are different versions available in order valve brings significant benefits, particular in when models. Night Mode: it is possible to set a
to meet market requirements - standard, silenced the refrigerant is working at partial loads to the silenced operation profile.
standard, high efficiency, silenced high efficiency, extra benefit of energy efficiency of the unit. It is Perfect for night operation, since it guarantees
high efficiency and silenced extra high efficiency. supplied as standard from size 1800/3000, and is greater acoustic comfort in the evenings, and a
optional for all other sizes. high efficiency in the time of greater load.
Versions • Electrical heater for plate heat exchanger. Night Mode is standard on all low noise versions.
NRB_A High efficiency • Possibility of integrated hydronic kit enclosed in
NRB_E High efficiency low noise
the frame of the unit; it is available in different
NRB_U Very high efficiency
NRB_N Very high efficiency low noise configurations with one or two pumps, with
ACCESSORIES
ACCESSORIES MULTICHILLER_EVO RIFNRB
AER485P1 Control, switch-on and switch-off system of the Current rephaser. Connected in parallel to the
RS-485 interface for supervising systems with individual chillers when multiple units are installed motor, it allows a reduction of the input current
MODBUS protocol. in parallel, always ensuring constant flow rate to (approx. 10%).
the evaporators.
AERNET GP
The device allows the control, the management FL Anti-intrusion grid.
and the remote monitoring of a Chiller with a PC, Flow switch. ATTENTION: the flow switch and the
smartphone or tablet using Cloud connection. water filter must be mounted; failure to do so COMPATIBILITY WITH VMF SYSTEM
AERNET works as Master while every unit will void the warranty. For further information on system, refer to specific
connected is configured as Slave (max. 6 unit); also, documentation.
with a simple click is possible to save a log file with AVX
all the connected unit datas in the personal Spring anti-vibration mounts.
terminal for post analysis.
ACCESSORIES FACTORY FITTED ONLY
PGD1 DRENRB
Allows you to control the chiller at a distance. Plate peak current reduction electronic device.
COMPATIBILITY OF ACCESSORIES
NRB 0800 0900 1000 1100 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
AER485P1 • • • • • • • • • • • • • •
AERNET • • • • • • • • • • • • • •
PGD1 • • • • • • • • • • • • • •
MULTICHILLER_EVO • • • • • • • • • • • • • •
A AVX1099 AVX1099 AVX1080 AVX1080 AVX1080 AVX1080 AVX1081 AVX1081 AVX1083 AVX1100 AVX1089 AVX1087 AVX1087 AVX1087
E AVX1080 AVX1080 AVX1080 AVX1081 AVX1081 AVX1081 AVX1083 AVX1084 AVX1084 AVX1087 AVX1087 AVX1091 AVX1091 AVX1092
AVX (1)
U AVX1080 AVX1080 AVX1080 AVX1081 AVX1081 AVX1081 AVX1083 AVX1084 AVX1084 AVX1087 AVX1087 AVX1091 AVX1091 AVX1092
N AVX1081 AVX1081 AVX1081 AVX1083 AVX1083 AVX1083 AVX1084 AVX1085 AVX1085 AVX1101 AVX1090 AVX1092 AVX1092 AVX1093
FL • • • • • • • • • • • • • •
ACCESSORIES MOUNTED IN THE FACTORY
DRENRB (*) • • • • • • • • • • • • • •
RIFNRB (*) • • • • • • • • • • • • • •
A 2VN 2VN 3VN 3VN 3VN 3VN 4VN 4VN 5VN 5VN 6V 7V 7V 7V
E 3VN 3VN 3VN 4VN 4VN 4VN 5VN 6V 6V 7V 7V 8V 8V 9VN
GP
U 3VN 3VN 3VN 4VN 4VN 4VN 5VN 6V 6V 7V 7V 8V 8V 9VN
N 4VN 4VN 4VN 5VN 5VN 5VN 6V 7V 7V 8V 8V 9VN 9VN 10V
(1) The accessory refers to the version “00” without hydronic kit.
(*) Accessory to be defined for compatibility. Contact the head office.
UNIT CONFIGURATOR
UNIT NRB INTEGRATED HYDRONIC KIT
0800 - 0900 - 1000 - 1100 - 1200 - 1400 - 1600 - 1800 - 2000 - 00 Without hydronic kit
SIZES (1)
2200 - 2400 - 2600 - 2800 - 3000 WITH 1 PUMP
OPERATIONAL LIMITS
PA Pump A
Mechanical thermostatic valve (outlet water temperature above
° (2) PB Pump B
+4°C/+39.2°F)
Mechanical thermostatic valve (outlet water temperature below PC Pump C
Y (2)
+4°C/+39.2°F) PD Pump D
Electronic thermostatic valve (outlet water temperature above PE Pump E
X
+4°C/+39.2°F)
Electronic thermostatic valve (outlet water temperature below PF Pump F
Z PG Pump G
+4°C/+39.2°F)
MODEL PH Pump H
° Cooling Only WITH 2 PUMP
C (3) Moto-Condensing Unit - unit requires remote evaporator DA Pump A and Stand-by pump
HEAT RECOVERY DB Pump B and Stand-by pump
° Without Heat Recovery DC Pump C and Stand-by pump
D (4) With Desuperheater DD Pump D and Stand-by pump
T (4)(5) With Total Recovery DE Pump E and Stand-by pump
VERSION (6) DF Pump F and Stand-by pump
A High Efficiency DG Pump G and Stand-by pump
E Low Noise High Efficency DH Pump H and Stand-by pump
U Very High Efficiency WITH 1 PUMP AND BUFFER TANK
N Low noise very high efficiency AA Pump A and buffer tank
COILS AB Pump B and buffer tank
° Aluminium microchannel AC Pump C and buffer tank
O Painted Aluminium Microchannel AD Pump D and buffer tank
R Copper - copper AE Pump E and buffer tank
S Copper - Tinned AF Pump F and buffer tank
FANS AG Pump G and buffer tank
° (7) Standard AH Pump H and buffer tank
J Inverter WITH 2 PUMPS AND BUFFER TANK
POWER SUPPLY BA Pump A with Stand-by pump and buffer tank
6 (8) 230V/3/60Hz BB Pump B with Stand-by pump and buffer tank
7 460V/3/60Hz BC Pump C with Stand-by pump and buffer tank
8 575V/3/60Hz BD Pump D with Stand-by pump and buffer tank
9 (8) 208V/3/60Hz BE Pump E with Stand-by pump and buffer tank
BF Pump F with Stand-by pump and buffer tank
BG Pump G with Stand-by pump and buffer tank
BH Pump H with Stand-by pump and buffer tank
(1) The availability of the models must be agreed with the technical/sales office
(2) For sizes from 2000 to 3000 the electronic expansion valve comes as standard
(3) The motocondensing units are not configurable with option X/Y/Z
Heat recovery D and T are not compatible with the Y and Z range of use (NOT = YD - YT - ZD - ZT). Warning: on the recovery side (D), a minimum input temperature of
(4)
95.0°F must always be guaranteed on the heat exchanger.
(5) Hydronic kit with storage tank Ax and Bx not compatible with heat recovery T
(6) In versions A-E-U-N it is possible to product cooling water down to 14°F (contact us for more information)
(7) Not available for silenced versions (E, N)
(8) Available only with J inverter and for sizes 0800 - 1200
TECHNICAL DATA
NRB 0800 0900 1000 1100 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
A 58.80 66.44 77.70 87.01 95.12 107.7 124.3 138.5 155.7 169.6 186.9 205.7 218.5 233.1
Cooling capacity (1) ton
U 61.94 69.82 78.59 89.78 99.18 112.1 129.3 145.7 161.0 178.7 192.3 208.9 222.2 240.8
A 57.77 65.30 76.33 85.49 93.47 108.3 122.2 138.2 156.8 166.1 179.5 197.5 209.9 226.0
E 58.14 65.19 72.97 83.99 92.41 103.7 120.3 136.0 149.4 162.4 174.3 189.8 201.2 218.4
Cooling capacity J (1) ton
U 60.83 68.58 77.20 88.18 97.41 110.1 127.0 143.1 158.1 171.5 184.7 200.5 213.4 231.1
N 59.82 67.43 75.87 86.16 95.12 107.4 123.4 138.7 152.9 165.5 178.0 193.1 205.0 222.0
A 64.83 75.79 84.44 95.90 107.6 125.7 139.7 160.3 177.5 195.7 209.7 228.0 247.5 267.9
Total power input kw
U 65.29 74.86 84.64 96.07 106.9 123.0 139.1 158.0 176.9 193.3 208.8 227.4 246.2 265.3
A 65.08 75.98 84.87 96.29 108.0 125.9 140.2 160.7 178.0 196.1 210.4 228.9 248.3 268.6
E 60.15 70.81 81.73 89.99 102.3 120.8 134.2 150.3 171.2 185.7 203.9 219.5 240.6 256.7
Total power input J kw
U 65.80 75.33 85.09 96.72 107.5 123.5 139.9 159.0 177.8 194.3 209.7 228.5 247.3 266.6
N 58.73 68.47 78.43 87.85 99.16 116.0 130.4 147.2 167.1 181.9 198.9 215.3 235.5 252.2
A 10.88 10.52 11.04 10.89 10.61 10.28 10.68 10.37 10.53 10.40 10.70 10.83 10.60 10.44
EER BTU/W
U 11.38 11.19 11.14 11.21 11.13 10.93 11.16 11.06 10.92 11.09 11.06 11.02 10.83 10.89
A 10.65 10.31 10.79 10.65 10.39 10.32 10.46 10.32 10.56 10.16 10.24 10.35 10.14 10.10
E 11.60 11.05 10.71 11.20 10.84 10.31 10.76 10.86 10.47 10.49 10.25 10.38 10.03 10.21
EER J BTU/W
U 11.09 10.92 10.89 10.94 10.88 10.69 10.90 10.80 10.67 10.59 10.57 10.53 10.35 10.40
N 12.22 11.82 11.61 11.77 11.51 11.10 11.36 11.31 10.98 10.92 10.74 10.76 10.45 10.56
A 14.81 14.30 15.01 14.81 14.43 14.06 14.50 14.09 14.43 14.09 14.13 14.26 14.23 14.06
IPLV BTU/W
U 15.49 15.22 15.15 15.25 15.15 14.88 15.15 15.05 15.25 15.15 14.81 14.77 14.81 14.88
A 16.96 16.45 17.20 16.99 16.55 16.14 16.65 16.21 16.41 16.28 16.34 16.55 16.21 15.97
E 18.56 17.61 17.06 17.85 17.27 16.41 17.16 17.37 16.75 17.13 16.31 16.58 16.04 16.31
IPLV J BTU/W
U 17.67 17.40 17.33 17.44 17.33 17.03 17.37 17.23 16.99 17.30 16.86 16.82 16.51 16.62
N 19.48 18.90 18.49 18.77 18.36 17.67 18.08 18.02 17.50 17.85 17.13 17.20 16.69 16.86
A 141 159 186 208 228 258 298 332 372 406 447 492 523 558
Water flow rate gpm
U 148 167 188 215 237 268 309 347 385 427 460 500 532 576
A 138 156 183 204 224 259 292 331 375 397 429 472 502 541
E 139 156 175 201 221 248 288 325 357 388 417 454 481 522
Water flow rate J gpm
U 145 164 185 211 233 263 304 342 378 410 442 480 510 553
N 143 161 181 206 228 257 295 331 366 396 426 462 490 531
A 5.99 5.21 7.15 5.98 7.15 6.21 8.66 7.74 9.60 10.1 12.7 8.13 9.19 8.59
Pressure drop ft H2O
U 4.53 5.76 4.88 6.37 5.53 7.04 6.97 8.83 9.02 6.13 7.10 8.39 9.49 9.35
A 5.78 5.04 6.90 5.77 6.91 6.28 8.37 7.71 9.73 9.69 11.7 7.49 8.47 8.08
E 3.98 5.01 4.21 5.57 4.80 6.04 6.04 7.69 7.78 5.07 5.84 6.93 7.79 7.69
Pressure drop J ft H2O
U 4.37 5.56 4.71 6.14 5.33 6.80 6.72 8.52 8.71 5.65 6.54 7.73 8.75 8.61
N 4.22 5.37 4.55 5.86 5.09 6.46 6.35 8.01 8.14 5.27 6.10 7.18 8.09 7.95
ELECTRICAL DATA (Power supply 460V/3/60Hz) Fans °
Total input current in cooling A A 96 107 110 126 143 168 184 212 232 258 275 297 324 352
mode U A 93 102 110 123 138 160 179 201 227 247 270 292 318 340
A A 291 341 357 413 431 484 521 632 665 698 654 773 799 825
[LRA]
U A 298 348 357 420 439 491 528 647 673 713 662 780 806 840
A A 129 138 154 180 204 232 265 306 351 369 389 438 475 513
[MCA]
U A 137 146 154 188 211 240 272 322 359 384 397 446 483 528
A A 155 169 185 222 246 287 319 379 424 442 443 511 548 586
[MOP]
U A 163 176 185 230 253 294 327 395 432 457 451 519 556 601
A A 150 150 175 200 225 250 300 350 400 400 400 500 500 500
Recomm. Fuse
U A 150 150 175 225 225 250 300 350 400 400 400 500 500 600
ELECTRICAL DATA (Power supply 460V/3/60Hz) Fans J
A A 108 118 127 143 160 185 206 235 260 287 309 336 363 391
Total input current in cooling E A 99 110 120 132 149 175 194 217 246 268 295 317 346 369
mode U A 110 119 128 145 161 183 207 235 261 287 310 337 363 391
N A 98 107 116 130 146 169 190 213 241 263 289 312 340 364
A A 291 341 357 413 432 484 521 632 666 699 655 774 800 826
E A 299 349 357 421 440 492 529 648 674 715 663 782 808 842
[LRA]
U A 299 349 357 421 440 492 529 648 674 715 663 782 808 842
N A 307 357 365 429 448 500 537 656 682 723 671 790 816 849
A A 129 139 155 181 204 233 266 307 352 370 390 440 477 514
E A 137 147 155 189 212 240 273 323 360 385 398 447 485 529
[MCA]
U A 137 147 155 189 212 240 273 323 360 385 398 447 485 529
N A 145 154 163 196 220 248 281 331 368 393 406 455 492 537
A A 156 169 185 223 246 287 320 380 425 443 445 513 550 587
E A 164 177 185 231 254 295 328 396 433 458 452 520 558 602
[MOP]
U A 164 177 185 231 254 295 328 396 433 458 452 520 558 602
N A 171 185 193 238 262 303 336 404 441 466 460 528 565 610
A A 150 150 175 200 225 250 300 350 400 400 400 500 500 500
E A 150 150 175 225 225 250 300 350 400 450 400 500 500 500
Recomm. Fuse
U A 150 150 175 225 225 250 300 350 400 450 400 500 500 500
N A 150 175 175 225 250 250 300 350 400 450 450 500 500 600
Sound power calculated on the basis of measurements made in accordance with UNI EN ISO 9614-2, as required for Eurovent certification.
NRB hydronic kit 0800 0900 1000 1100 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
A 00 in 97 97 97 97 97 97 97 97 97 97 97 97 97 97
A 110 110 156 156 156 156 203 203 250 250 297 344 344 344
E 156 156 156 203 203 203 250 297 297 344 344 391 391 438
B 00 in
U 156 156 156 203 203 203 250 297 297 344 344 391 391 438
N 203 203 203 250 250 250 297 344 344 391 391 438 438 469
C 00 in 87 87 87 87 87 87 87 87 87 87 87 87 87 87
A 4,806 5,225 6,504 6,658 6,746 7,011 8,157 8,356 9,304 10,362 11,288 12,787 12,853 13,095
NRB_Y_NA60_03
E 5,842 6,173 6,592 7,738 7,981 8,069 9,171 10,031 10,207 12,147 12,699 13,713 13,779 14,859
Empty weight 00 lbs
U 5,842 6,173 6,592 7,738 7,981 8,069 9,171 10,031 10,207 12,147 12,699 13,713 13,779 14,859
N 7,540 7,871 8,289 9,259 9,524 9,612 10,670 11,729 11,949 13,779 14,352 15,454 15,521 16,513