Slope Calculation of Line Diff Relay P543
Slope Calculation of Line Diff Relay P543
Slope Calculation of Line Diff Relay P543
Relay Setting
0.3
0.2 Slope 1 30
2 IDiff 0.8
0.8 Ibais 2
Relay Setting
0.3
80
0.7 Slope 2 69.09722
800 Idiff 3960
6000 Ibais
3980
page no. 540
Slope 1 SLOPE CALCULA
The tripping criteria formula is: -
For I diff > Is1 and I bias < Is2 (I bias < Is1/k1)
Idiff = k1 * I bias
Slope 2
The tripping criteria formula is:-
For I diff ≥ Is2 and I bias > Is2
Idiff = K1 * Is2 + K2 (I bias - Is2)
SLOPE CALCULATION OF LINE DIFF RELAY P543