Numerical Distance Protection Relay Terminal-CSC 101
Numerical Distance Protection Relay Terminal-CSC 101
Application
Type
Functions and arrangement
CSC-101A CSC-101B
Distance pilot selectable selectable
1
EHV Line Protection Equipment
Features
• Take full advantages of current fault component phase selection, lower voltage phase
selection, negative- and zero-sequence current phase selection, to achieve selective trip
whenever fault occurs at power swing system, weak source system or complex fault
circumstance.
• Schemes of power swing blocking detection: Comparing zero- and
negative-sequence current and taking ∆R/∆T as criterion to detect all kinds of faults
selectively during power swing. According to various systems operating conditions or
different frequency of power swing, adjusting their operation thresholds adaptively to
ensure the primary protection works normally.
• Incorporates the latest high-powered fourth generation hardware system with 32 bit
DSP-MCU combined chip technology, which gives computational intensity and system
control efficiency in a single chip.
• All setting parameters can be input via either the integrated operator and display panel
or a personal computer. The parameters are written into non-volatile memory so that
the setting values remain secure even during interruption of the DC power supply.
• All-important hardware and software components are continuously monitored;
irregularities in hardware and program sequence are detected and alarmed. This
improves the security and availability of the protection system significantly.
• Current, voltage etc can be monitored conveniently through large LCD (Liquid crystal
display).
• The equipment is equipped with 1 serial interface in the front. The serial interface is
suitable for connecting a PC. The PC based software CSPC can be used for convenient
and transparent setting, recording disturbance and evaluation as well as commissioning.
• 2 RS485 and 2 Ethernet interfaces (or 2 electric or fiber Ethernet interfaces, selectable)
are equipped on the rear board. It is convenient to connect to a substation automation
system or to a protection data master unit. These ports support IEC 61850 & IEC
60870-5-103 communication protocols.
• 6 shortcut keys on the front panel, 4 keys for printing all kinds of messages, 2 keys for
switching the setting storage zone.
• The equipment supplies detailed data for the analysis of disturbances as well as for
checking of states during operation. Disturbance event and operation indications
memories are safeguarded against DC power supply failure.
• Outputs, display of indication. Indication (alarm) relays & LEDs meets user
2
EHV Transmission Line Protection Equipment
requirements. The storable LED displays are secured against DC power supply failure.
Functions
Mechanical structure
● The enclosure for equipment is 19 inches width and 4U height according to IEC
60297-3.
● The front panel door of the equipment is hinged at the bottom to open vertically downwards.
LCD, LEDs and keys are mounted on the panel. There is a serial interface on the panel.
● The modules can be combined through the bus on the rear board. Both the equipment
and the other system can be combined through the rear interfaces.
3
EHV Line Protection Equipment
Distance protection with communication is the primary protection for EHV line. It is
applicable to three kinds of channel pattern: blocking mode, permissive under reach mode
and permissive over reach mode.
● blocking mode
Relay A Relay B
Zone 1
Zone 2
2 Instantaneous trip if
a) Zone 1 Operation
b) Zone 2 + No blocking Signal from Remote end WITHIN the Permissive Trip
Time
Relay A Relay B
Zone 2
4
EHV Transmission Line Protection Equipment
1 Operation of Zone 1 sends signal to remote end
2 Instantaneous trip if
a) Zone 1 Operation
Relay A Relay B
Zone 1
2 Instantaneous trip if
c) Zone 1 Operation
● Distance element
As shown in fig. 2.1, the characteristic is polygonal. RDZ is set R1, R2, R3 (For Zone 1, 2
5
EHV Line Protection Equipment
The polygon is shaped to meet the requirement of (a) Resistive tolerance to high path
fault resistance for short time (b) Improve the ability of avoiding load impedence for long
lines (c) To enhance the ability to prevent the relay from over-reaching at forward faults.
For faults after reclose or manual close, based on the characteristic shown in fig. 2.2, Z3
impedance operating characteristic is added with a small rectangle to ensure that faults near
Special directional elements are set to resolve dead zone for distance protection when
fault occurs near the bus. For symmetric fault, the memory voltage that is the pre-fault
voltage is used to compare phasor with post-fault current to detect direction. For
asymmetric fault near the bus, negative-sequence directional element is taken as directional
element of distance relay. The operating conditions for distance relay are as below: The
forward directional element operates, and measuring impedance lies within the setting
polygon area.
Fig.2-1 Fig.2-2
Within time τ , if
∆R < K ⋅ ∆R min£¨180°£¬TZMAX £¬τ )
is satisfied, it is determined that
Within time τ , if
∆R ≥ K ⋅ ∆R min£¨180°£¬TZMAX £¬τ )
is satisfied, it is determined that
Zero-current protection
This protection function is a backup protection for the transmission line and the power
system. The protection comprises 4 stages 3I0>. The zero-current protection Function can
be applied via binary settings.
lm
forward
81 81
18
3U0
reverse
7
EHV Line Protection Equipment
setting.
lm
Forward
81 81
18
3U2
Reverse
T _ factor
T= + T_INV
3I 0
( )N −1
3I 0 _ INV
3I0 - fault current.
T_factor - time coefficient of inverse time zero current.
N - exponent setting of inverse time zero current.
3I0_INV - current setting of inverse time zero current.
T_INV - delay time setting of inverse time zero current which can meet the requirement
that inverse time zero current co-operates with different protection.
Inverse curves can be obtained according to the following setting
T_factor =0.02 and N =0.14 Standard inverse (IEC Standard)
T_factor =1 and N =13.5 Very inverse
8
EHV Transmission Line Protection Equipment
T_factor =2 and N =80 Extremity inverse.
Autoreclose
CSC-101B protection system is provided with autoreclose whose performance is only to
close the circuit breaker but not to select faulted phase and trip.
Four types of autoreclose mode are provided:
Single-phase autoclose The faulted phase is tripped and then reclosed when
single-phase fault occurs, in the case of a multi-phase fault, three phases are tripped, but
reclosure is not performed.
Three-phase autoclose Three phases are tripped, and then reclosed regardless of
the fault types, whether single-phase fault or multi-phase fault.
Single- and three-phase autoclose Single-phase tripping and reclosure are
performed if a single-phase fault occurs, while three-phase tripping and reclosure are
performed if a multi-phase fault occurs.
Inoperative mode Autoreclose function is out of service, three phases are tripped
regardless of the fault types, but reclosure is disabled. This mode must be set when
autoreclose is not used for a long time.
9
EHV Line Protection Equipment
A transfer switch connected to the rear terminals of the device can be used to realize switching
among four types of autoreclose mode.
. . .
1) Summation of three phase voltages is not zero and U A + U B+ U C > 7V. It
2) Voltages of all three phase are smaller than 8V and current of any phase >0.04In or breaker
closes (test TWJ). It is considered as loss of three phase.
When any one of the above are met, distance relay will be blocked & alarm will be intiated.
On-load measurement
The on-load measured values generated in the unit such as current, voltage, phase
angle, etc. can be displayed at the LCD or by means of a PC.
10
EHV Transmission Line Protection Equipment
Technical data
Input circuits Rated current IN 1 or 5A
Rated voltage UN 63.5V or 110V AC
Rated frequency fN 50Hz
Thermal overload capability
In voltage circuit, continuous 1.2×UN AC
In current circuit, continuous 2×IN
≤ 4s 40×IN
≤ 10s 10×IN
1s 70×IN
Power consumption less than 0.5VA
In voltage circuit at UN=110V less than 1VA
In current circuit at IN = 1A less than 0.5VA
at IN = 5A
DC voltage supply Rated auxiliary voltage Uaux 220V DC; 110V DC
Permissible tolerance at rated -30% to +14%
auxiliary voltage
Power consumption
at energized state max. 50W
at quiescent state max. 30W
Pick-up tolerances Current values Less than 3% of set value
Under rated Voltage values Less than 3% of set value
Conditions distance values Less than 3% of set value
Time values Less than 20ms
Binary inputs Binary inputs for 24VDC voltage 7, can be expanded 12;
Current consumption for each 2mA 5mA
input
Binary inputs for 220V(110V)DC 10, can be expanded 12;
voltage
Current consumption for each 1mA 3mA
input
11
EHV Line Protection Equipment
12
EHV Transmission Line Protection Equipment
Voltage Upe> 1 to 120V
Time delay T 0 to 60s
PU & DO Times
Pickup time Upe> approx. 20ms
Drop-off time Upe> approx. 40ms
Tolerance
Current pickup Upe> ±5% of set value or ±0.1V
Time delays not more than 40ms
Undervoltage Setting ranges
protection Voltage Upe< 1 to 60V
Time delay T 0 to 60s
PU & DO Times
Pickup time Upe< approx. 20ms
Drop-off time Upe< approx. 40ms
Tolerance
Current pickup Upe> ±5% of set value or ±0.1V
Time delays not more than 40ms
Breaker failure Setting ranges
Protection Current I> 0.1×IN to 20×IN
Time delay T 0.1 to 5s
PU & DO Times
At 1.2 times of set value Less than 40ms
Drop-off time I> approx. 40ms
Tolerance
Current pickup I> ±3% of set value or ±0.02IN
Time delays not more than 40ms
Drop-off ratio
I> approx. 0.9
On-load Display of values
Measurement for current IA, IB, IC, 3I0, IN
for voltage UA, UB, UC, Ux
P Q etc
for power supply DC+,DC-
Fault recording Instantaneous values IA,IB,Ic,3I0,IAR,IBR,ICR,3I0R,UA,UB,UC,3U0,U
(approx. every 0.833ms at 50Hz) x
2 records of max. 5 secs duration
(adjustable pre & post fault
duration)
13
EHV Line Protection Equipment
Rated current
1A
5A 1
5
Documentation
English Catalog D******: CSC-101 Digital EHV line XXXXXXX
protection equipment (V1.00E)
Manual:CSC-101 Digital EHV line protection XXXXXXX
equipment(V1.00E)
14
EHV Transmission Line Protection Equipment
Connection diagram
Figure 5 illustrates the recommended standard connection for line. The permissible
cable length and the TA design (permissible load) are mutually dependent. Recalculation is
advisable as for lengths of more than 100m.
Typical connection
*
c
UA
*
b UB
*
a UC
*
c
*
b
*
a X1 AC
b a
IA’ 1 IA
IB’ 2 IB
*
*
IC’ 3 IC
IN’ 4 IN
5
6
UX’ 7 UX
8
UC 9 UB
UN 10 UA
11
*
15
EHV Line Protection Equipment
Dimension drawings in mm
Dimension drawings for CSC-101 used 19 inch (4U) enclosure for panel flush-mounting
and cabinet mounting.
16