D.C. FEEDER MANAGER RELAY
32, 45, 49, 64, 76, 79, 80
The relay measures the Line current and voltage through Besides the normal Watchdog and Powerfail functions,
one current transducer and one voltage transducer. a comprehensive program of self-test and self diagnostic
provides:
The transducers (type MHCO) are galvanically insulated
• Diagnostic and functional test with checking of program
via fiber optic and have the following measuring ranges:
routines and memory contents, running every time the
• Line voltage : (0 ÷ 2)Vn
auxiliary power supply is switched on.
• Line current : (0 ÷ 10)In
• Dynamic functional test running during normal operation.
• Insulation voltage 20kVac 1min.
• Complete Test activated by the keyboard or via the
Real time measurements of primary input values can communication bus.
be read continuously both from the display and via serial
Any internal fault detected is indicated by a fault message on
communication. Relay programmation can be done both
the display and by de-energization of associated I.R.F. output relay.
via the frontal keyboard and via serial communication.
The associated Circuit Breaker can be controlled both The relay is available in three different executions:
via the frontal keyboard and via serial communication. • Flush mounting
M13-ING-Rev.06
U-MLEs
Accessories
• High-Voltage Current/Voltage measuring Transducer with Fiber Optic output : Type MHCO-T/V-I
• High-Voltage Current measuring Transducer with Fiber Optic output : Type MHCO-T-I.
• High-Voltage Voltage measuring Transducer with Fiber Optic output : Type MHCO-T-V
• Voltage measuring reciver with fiber optic input and 3 Analogic outputs : Type MHCO-R-V
• Current measuring reciver with fiber optic input and 3 Analogic outputs : Type MHCO-R-I
• Input/Output Expansion Module: UX10-4 - 10 Digital Inputs + 4 Outputs Relay
UX14DI - 14 Digital Inputs
UX14DO - 14 Outputs Relay
• Cable monitoring device A-MSG-1 (Cable Screen-to-Ground or Conductor-to-Screen monitoring)
with current output directly supplyed to the U-MLEs relay
M13-ING-Rev.06
U-MLEs
U-MLEs
U-MLEs
U-MLEs
Typical Characteristics
Accuracy at reference value of influencing factors 2% In - 0.2% On for measurements
2% +/- 10ms for times
Input 0 ÷ 20 mA
Average power supply consumption <10 VA
Output relays rating 5 A; Vn = 380 V
A.C. resistive switching = 1100W (380V max)
make = 30 A (peak) 0.5 sec.
break = 0.3 A, 110 Vcc,
L/R = 40 ms (100.000 op.)