Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

RP-2002 (E) -TT xả khí

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DN-60240:B

RP-2002(E)
Agent Release Control Panel

Conventional Releasing Panels

General
The RP-2002 is a six-zone FACP for single and dual hazard
agent releasing applications. The RP-2002 provides reliable
fire detection, signaling and protection for commercial, indus-
trial and institutional buildings requiring agent-based releasing.
The RP-2002 is compatible with System Sensor’s i3 detectors
which are conventional smoke detectors that can transmit a
maintenance trouble signal to the FACP indicating the need for
cleaning and a supervisory ‘freeze’ signal when the ambient
temperature falls below the detector rating of approximately
45°F (7.22°C). In addition, the control panel is compatible with
conventional input devices such as two-wire smoke detectors,
four-wire smoke detectors, pull stations, waterflow devices,
tamper switches and other normally-open contact devices.
Refer to the Notifier Device Compatibility Document for a com-
plete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appli-
ance Circuits) or releasing circuits. Three programmable
Form-C relays (factory programmed for Alarm, Trouble and

RP2002.jpg
Supervisory) and 24 VDC special application resettable and
non-resettable power outputs are also included on the main
circuit board. The RP-2002 supervises all wiring, AC voltage,
battery charger and battery level.
Activation of a compatible smoke detector or any normally-
– Amseco
open fire alarm initiating device will activate audible and visual
signaling devices, illuminate an indicator, display alarm infor- • Three programmable Form-C relays.
mation on the panel’s LCD, sound the piezo sounder at the • 7.0 amps total 24 VDC output current.
FACP, activate the FACP alarm relay and operate an optional • Resettable and non-resettable output power.
module used to notify a remote station or initiate an auxiliary
• Built-in Programmer.
control function.
• ANN-BUS for connection to optional devices (up to 8 total of
The RP-2002E offers the same features as the RP-2002 but any of the following):
allows connection to 220/240 VAC. Unless otherwise speci-
fied, the information in this data sheet applies to both the 110/ – N-ANN-80 Remote LCD Annunciator
120 VAC and 220/240 VAC versions of the panels. – N-ANN-I/O LED Driver
– N-ANN-S/PG Printer Module
Features – N-ANN-RLY Relay Module
• Listed to UL Standard 864, 9th edition. – N-ANN-LED Annunciator Module
• FM Approved. • 80-character LCD display (backlit).
• Designed for agent releasing standards NFPA 12, 12A, • Real-time clock/calendar with daylight savings time control.
12B, and 2001. • History log with 256 event storage.
• Disable/Enable control per input zone and output zone. • Piezo sounder for alarm, trouble and supervisory.
• Extensive transient protection. • 24 volt operation.
• Dual hazard operation. • Low AC voltage sense.
• Adjustable pre-discharge, discharge and waterflow delay • Outputs Programmable for:
timers. – Releasing Circuits or NACS
• Cross-zone (double-interlock) capability. • NACs programmable for:
• Six programmable Style B (Class B) IDCs (Initiating Device – Silence Inhibit
Circuit).
– Auto-Silence
• System Sensor i3 series detector compatible.
– Strobe Synchronization
• Four programmable Style Y (Class B) output circuits - (spe-
cial application power). – Selective Silence (horn-strobe mute)
• Strobe synchronization: – Temporal or Steady Signal
– System Sensor – Silenceable or Non-silenceable
– Wheelock – Release Stage Sounder
– Gentex • Automatic battery charger with charger supervision.
– Faraday • Optional Dress Panel DP-51050 (red).

DN-60240:B • 03/12/2009 — Page 1 of 4


• Optional Trim Ring TR-CE (red) for semi-flush mounting the • Supervised and power-limited circuitry.
cabinet. • Style B (Class B) wiring with Style D (Class A) option.
• Optional N-CAC-5X Class A Converter Module for Outputs • Normal Operating Voltage: Nominal 20 VDC.
and IDCs.
• Alarm Current: 15 mA minimum.
• Optional 4XTM Municipal Box Transmitter Module.
• Short Circuit Current: 40 mA max.
• Optional Digital Alarm Communicators (411, 411UD,
• Maximum Loop Resistance: 100 Ohms.
411UDAC).
• End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
PROGRAMMING AND SOFTWARE: • Standby Current: 4 mA.
• Custom English labels (per point) may be manually entered Refer to the Notifier Device Compatibility Document for listed
or selected from an internal library file. compatible devices.
• Programmable Abort operation. Notification Appliance and Releasing Circuit(s) - TB5 and
• Three programmable Form-C relay outputs. TB7
• Pre-programmed and custom application templates. • Four Output Circuits.
• Continuous fire protection during online programming at the • Style Y (Class B) or Style Z (Class A) with optional con-
front panel. verter module.
• Program Check automatically catches common errors not • Special Application power.
linked to any zone or input point.
• Supervised and power-limited circuitry.
USER INTERFACE: • Normal Operating Voltage: Nominal 24 VDC.
• Integral 80-character LCD display with backlighting. • Maximum Signaling Current: 7.0 amps (3.0 amps maximum
• Real-time clock/calendar with automatic daylight savings per NAC).
adjustments. • End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
• ANN-Bus for connection to remote annunciators. • Max. Wiring Voltage Drop: 2 VDC.
• Audible or silent walk test capabilities. Refer to the Notifier Device Compatibility Document for com-
• Piezo sounder for alarm, trouble, and supervisory. patible listed devices.
Form-C Relays - Programmable - TB8
Controls and Indicators • Relay 1 (factory default programmed as Alarm Relay)
LED INDICATORS • Relay 2 (factory default programmed as fail-safe Trouble
Relay)
• FIRE ALARM (red).
• Relay 3 (factory default programmed as Supervisory Relay)
• SUPERVISORY (yellow).
• Relay Contact Ratings:
• TROUBLE (yellow).
– 2 amps @ 30 VDC (resistive)
• AC POWER (green).
– 0.5 amps @ 30 VAC (resistive)
• ALARM SILENCED (yellow).
Auxiliary Trouble Input – J6
• DISCHARGED (red).
• PRE-DISCHARGE (red indicator). The Auxiliary Trouble Input is an open collector circuit which
can be used to monitor external devices for trouble conditions.
• ABORT (yellow indicator). It can be connected to the trouble bus of a peripheral, such as
CONTROL BUTTONS a power supply, which is compatible with open collector cir-
cuits.
• ACKNOWLEDGE.
Special Application Resettable Power - TB9
• ALARM SILENCE.
• SYSTEM RESET (lamp test). • Operating Voltage: Nominal 24 VDC.
• DRILL. • Maximum Available Current: 500 mA - appropriate for
powering 4-wire smoke detectors (see note).
AC Power – TB1
• Power-limited Circuitry.
• RP-2002: 120 VAC, 60 Hz, 3.66 amps.
Refer to the Notifier Device Compatibility Document for com-
• RP-2002E: 240 VAC, 50 Hz, 2.085 amps. patible listed devices.
• Wire size: minimum #14 AWG (2.0 mm2) with 600V insula- NOTE: Total current for resettable power, nonresettable power and
tion. Output Circuits must not exceed 7.0 amps.
• Supervised, nonpower-limited. Special Application Resettable or Nonresettable Power -
Battery (sealed lead acid only) – J12: TB9
• Maximum Charging Circuit - Normal Flat Charge: 27.6 • Operating Voltage: Nominal 24 VDC.
VDC @ 1.4 amp. Supervised, nonpower-limited. • Maximum Available Current: 500 mA (see note 1).
• Maximum Charger Capacity: 26 Amp Hour battery (two • Power-limited Circuitry.
18 Amp Hour batteries can be housed in the FACP cabinet.
Larger batteries require separate battery box such as the • Jumper selectable by JP31 for resettable or nonresettable
BB-26 or NFS-LBBR). power.
• Minimum Battery Size: 7 Amp Hour. Refer to the Notifier Device Compatibility Document for com-
patible listed devices.
Initiating Device Circuits - TB4 and TB6
• Zones 1 - 5 on TB4.
• Zone 6 on TB6.

Page 2 of 4 — DN-60240:B • 03/12/2009


Product Line Information
RP-2002: Six-zone, 24 volt Agent Release Control Panel
(includes backbox, power supply, technical manual, and a
frame & post operating instruction sheet) for single and dual
hazard agent releasing applications.
RP-2002E: Same as above but allows connection to 220/240
VAC.
N-CAC-5X: Class A Converter Module can be used to convert
the Style B (Class B) Initiating Device Circuits to Style D
(Class A) and Style Y (Class B) Output Circuits to Style Z
(Class A).
NOTE: Two Class A Converter modules are required to convert all
four Output Circuits and six Initiating Device Circuits.
4XTM: Transmitter Module provides a supervised output for
local energy municipal box transmitter and alarm and trouble
reverse polarity. It includes a disable switch and disable trouble
LED.
N-ANN-80(-W): LCD Annunciator is a remote LCD annuncia-
tor that mimics the information displayed on the FACP LCD
display. Recommended wire type is un-shielded. (Basic model
is black; order -W version for white; see DN-7114.)
N-ANN-LED: Annunciator Module provides three LEDs for
each zone: Alarm, Trouble and Supervisory. Ships with red or
black enclosure (see DN-60242).
N-ANN-RLED: Provides alarm (red) indicators for up to 30
input zones or addressable points. (See DN-60242).
N-ANN-RLY: Relay Module, which can be mounted inside or
outside the cabinet, provides 10 programmable Form-C relays.
(See DN-7107.)
N-ANN-S/PG: Serial/Parallel Printer Gateway module pro-
vides a connection for a serial or parallel printer. (See DN-
7103.)
N-ANN-I/O: LED Driver Module provides connections to a
user supplied graphic annunciator. (See DN-7105.)
DP-51050: Dress panel (red) is available as an option. The
dress panel restricts access to the system wiring while allow-
ing access to the membrane switch panel.
TR-CE: Trim-ring (red) is available as an option. The trim-ring
allows semi-flushing mounting of the cabinet.
BB-26: Battery box, holds up to two 26 Amp Hour batteries
and CHG-75.
NFS-LBBR: Battery box, houses two 55 Amp Hour batteries,
red.
BAT Series Batteries: Refer to DN-6933.
PRN-6: UL-listed compatible event printer. Dot-matrix, tractor-
fed paper, 120 VAC.
PRT-PK-CABLE: Programming cable. Used to update the
FACP’s flash firmware. (Also requires an RS485 to RS232
converter).

DN-60240:B • 03/12/2009 — Page 3 of 4


SYSTEM SPECIFICATIONS

System Capacity ture ranges and humidity. Therefore, it is recommended that


this system and its peripherals be installed in an environment
• Annunciators ..................................................... .................8 with a normal room temperature of 15 – 27°C/60 – 80°F.

Electrical Specifications NFPA Standards


• RP-2002 (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66 The RP-2002(E) complies with the following NFPA 72 Fire
amps Alarm Systems requirements:
• RP-2002E (FLPS-7 Power Supply): 240 VAC, 50 Hz, 2.085
– NFPA 12 CO2 Extinguishing Systems
amps
– NFPA 12A Halon 1301 Extinguishing Systems
• Wire size: minimum 14 AWG (2.0 mm²) with 600 V insula-
tion, supervised, nonpower-limited – NFPA 12B Halon 1211 Extinguishing Systems
– NFPA 72 National Fire Alarm Code for Local Fire Alarm
Cabinet Specifications Systems and Remote Station Fire Alarm Systems
(requires an optional Remote Station Output Module)
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x
– NFPA 2001 Clean Agent Fire Extinguishing Systems
0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x
16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring
(TR- CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. Agency Listings and Approvals
The listings and approvals below apply to the basic RP-
Shipping Specifications 2002(E) and RP-2002(E)E control panels. In some cases, cer-
tain modules may not be listed by certain approval agencies,
Dimensions:
or listing may be in process. Consult factory for latest listing
– Height 20.00" (50.80cm) status.
– Width 22.50" (57.15cm) • UL: S635
– Depth 8.50" (21.59cm) • FM approved
• CSFM: 7165-0028:245
Temperature and Humidity Ranges • MEA: 333-07-E
This system meets NFPA requirements for operation at 0 – NOTE: For ULC-listed model, see DN-60444.
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-

NOTIFIER® and System Sensor® are registered trademarks of Honeywell


International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com

Page 4 of 4 — DN-60240:B • 03/12/2009

You might also like