Fire Alarm Systems - W ST Wall Mount Multi Candela Strobes

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Fire Alarm Systems | W‑ST Wall‑mount Multi‑candela Strobes

W‑ST Wall‑mount Multi‑candela Strobes


www.boschsecurity.com

u Sleek modern aesthetics

u Multiple voltages (12 VDC or 24 VDC)

u Voltage test points

u Eight strobe candela options

u Universal mounting base

The Cooper Wheelock Exceder Series Strobes feature Region Certification


a sleek modern design that incorporates high reliability
and high-efficiency optics to minimize current draw. USA UL UUKC: Signaling Appliances and Equip-
ment for the Hearing Impaired (ANSI/UL
The reduced current draw allows for a greater number 1971), UVAV: Visual-signal Appliances
of devices on the two‑wire notification appliance for Fire-protective Signaling Systems
circuit. This, in combination with eight candela options (ANSI/UL 1638)
in one appliance, no tools needed for changing FM see the FM Approval Guide
settings, voltage test points, 12 V or 24 V DC
operation, the universal mounting base, and multiple CSFM see our website
mounting options results in a reduced cost of
ownership. Installation/configuration notes
These strobes provide eight candela settings. All the Compatibility
switches to change these settings can be set without a Strobe:
tool and are located behind the appliance to prevent These strobes provide a non-synchronized strobe
tampering. appliance when connected directly to a Fire Alarm
The separate universal mounting base can be easily Control Panel (FACP), or provide a synchronized
mounted to five industry‑standard back box types. strobe appliance when used in conjunction with an
They can also be pre‑wired to allow full testing of the FACP that incorporates the Cooper Notification sync
circuit wiring before the appliance is installed and the protocol, a Cooper Notification Sync Module, or the
surface finished. These wall‑mounting strobes also Cooper Notification Power Supply. They are designed
feature voltage test points for taking readings with a to flash at 1 flash per second minimum over their
volt meter for troubleshooting or AHJ inspection. Regulated Voltage Range.
Certifications and approvals

Cooper Wheelock holds these Listings and Approvals:


2 | W‑ST Wall‑mount Multi‑candela Strobes

Wiring Considerations
Notice The wiring terminals on the Universal Mounting Base
Strobes are not designed to be used on coded accept two appliance wires with diameters between
systems in which the applied voltage is cycled on 12 AWG and 18 AWG (ISO 4 mm2 and 0.75 mm2) at
and off. each terminal.
Compatible Products Parts included
The following Bosch Security Systems, Inc. products
are compatible with the Cooper Wheelock Exceder Quant. Component
Series Strobes:
1 Strobe appliance
Category Product ID Product Description
1 Universal mounting base
Control Panels FPA-10001 Analog Addressable Fire
1 Contact cover
Panels
1 Hardware pack
FPD-70241 Conventional or
• Two pan head mounting screws
Addressable2 FACP
• One securing screw
D10024A3 Analog FACP
1 Literature – Installation Instructions
D80243 Analog FACP
Technical specifications
D91243 Addressable FACP
Electrical
D7024 3 Conventional or
Addressable2 FACP Strobe Current Draw
D70223 Conventional FACP 24 V nominal (16.0 V to 33.0 V range)
Modules SM‑12/24‑R Synchronization module
Voltage Type Current Draw
(red)
DC/FWR: 15 cd: 57 mA, 15/75 cd: 70 mA,
DSM‑12/24‑R Dual synchronization
30 cd: 85 mA, 75 cd: 135 mA,
module (red)
95 cd: 163 mA, 110 cd: 182 mA,
Power Supplies FPP-RNAC-8A-4C1 Remote Notification 135 cd: 205 mA, 185 cd: 253 mA
Appliance Circuit (RNAC)
12 V nominal (8.0 V to 17.5 V range)
Power Supply

PS‑24‑8MC1 Power supply with built-in Voltage Type Current Draw


synchronization protocol DC: 15 cd: 110 mA, 15/75 cd: 140 mA
1
These products have built‑in Cooper Notification
Voltage (input)
synch protocol.
2
When used with a D7039 Multiplex Expansion Regulated Range
Module, the FPD‑7024 and D7024 become
addressable FACPs. 12 VDC 8.0 V to 17.5 V
3
For synchronization, use the SM or DSM modules 24 VDC or Vrms 16.0 V to 33.0 V
with these control panels.
Mounting Considerations Environmental
The Universal Mounting Base supplied with each
Environment: Indoor, dry
strobe can be pre-wired. With the supplied Contact
Cover in place, the pre‑wired circuit can be checked Relative Humidity: 93±2% maximum, non‑condensing
for continuity before the strobes are mounted. The
strobes snap onto the pre-installed Universal Mounting Temperature +32°F to +120°F (0°C to +49°C)
Bases with the Contact Covers removed and can be (operating):
secured to the base with an optional securing screw.
The Universal Mounting Base flush mounts on single-
gang, double-gang, 4 in. square, 4 in. octal, 3.5 in.
octal and 100 mm European-type back boxes.
3 | W‑ST Wall‑mount Multi‑candela Strobes

Mechanical

Candela Ratings1: 15 cd, 15/75 cd2, 30 cd, 75 cd, 95 cd,


110 cd, 135 cd, or 185 cd

Dimensions: 5.24 in. x 4.58 in. x 2.19 in.


(133.1 mm x 116.4 mm x 55.7 mm)

Material: Molded plastic enclosure incorporating a


Xenon flashtube and Lexan lens.
1
When set for 12 V operation strobe devices are only
approved by UL to be set at 15 cd or 15/75 cd and
only to be powered by DC not FWR.
2
Although this product is UL Listed at 15 cd, it
provides 75 cd on axis.
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.

Ordering information

W‑STR Wall‑mount Multi‑candela Strobe (two‑wire,


12/24 V, red)
Rectangular red two‑wire strobe that is field‑selectable
for eight candela options.
Order number W-STR

W‑STW Wall‑mount Multi‑candela Strobe (two‑wire,


12/24 V, white)
Rectangular white two‑wire strobe that is
field‑selectable for eight candela options.
Order number W-STW
Accessories
DSM‑12/24‑R Dual Synchronization Module (red)
A 12/24 VDC Cooper Wheelock module that
synchronizes notification appliances on a single Class
A or two Class B circuits.
Order number DSM-12/24-R

SM‑12/24‑R Single Synchronization Module (red)


A 12/24 VDC Cooper Wheelock module that
synchronizes notification appliances on Class B alarm
circuits.
Not Available.
Order number SM‑12/24‑R

Represented by:

Europe, Middle East, Africa: Germany: North America: Asia-Pacific:


Bosch Security Systems B.V. Bosch Sicherheitssysteme GmbH Bosch Security Systems, Inc. Robert Bosch (SEA) Pte Ltd, Security Systems
P.O. Box 80002 Robert-Bosch-Ring 5 130 Perinton Parkway 11 Bishan Street 21
5600 JB Eindhoven, The Netherlands 85630 Grasbrunn Fairport, New York, 14450, USA Singapore 573943
Phone: + 31 40 2577 284 Germany Phone: +1 800 289 0096 Phone: +65 6571 2808
emea.securitysystems@bosch.com www.boschsecurity.com Fax: +1 585 223 9180 Fax: +65 6571 2699
emea.boschsecurity.com onlinehelp@us.bosch.com apr.securitysystems@bosch.com
www.boschsecurity.us www.boschsecurity.asia

© Bosch Security Systems 2016 | Data subject to change without notice


2713864203 | en, V6, 11. Aug 2016

You might also like