Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

FN-642 842 1042-ULADA DataSheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

FN-642-ULADA, FN-842-ULADA, FN-1042-ULADA

STANDARD FEATURES
 Two (2) Class A or (2) Class B FACP inputs
 Two (2) NC dry contact trigger inputs
 Four (4) Class A or Four (4) Class B indicating
circuits
 Two (2) Class B outputs may be paralleled for more
power on an indicating circuit
 One (1) Aux. Power Output @ 1 amp supply current
(with or without battery backup)
 Signal Circuit Trouble Memory - Facilitates quickly
locating intermittent system trouble and eliminates
costly and unnecessary service calls. LED's indicate
a prior fault (short, open, ground) has occurred on
one or more signaling circuit outputs.
DESCRIPTION  2 wire Horn/Strobe Sync mode allows audible notifi-
cation appliances (Horns) to be silenced while visual
The FN-642-ULADA, FN-842-ULADA, and FN-1042- notification appliances (Strobes) continue to operate
ULADA are extremely cost effective voltage regulated  Horn/Strobe sync protocols include: Gentex, System
remote NAC Power Extenders. They may be connected Sensor, Faraday, Wheelock and Amseco.
to any 12 or 24VDC Fire Alarm Control Panel (FACP).  Temporal Code 3 Mode
Primary applications include Notification Appliance  Steady Mode
Circuit (NAC) expansion (supports ADA requirements)  Input to Output Follower Mode (maintains synchroni-
and will provide auxiliary power to support system zation of notification appliance circuits)
accessories.  March Time
 Compatible with 24VDC or 12VDC fire panels
SPECIFICATIONS  Input 115VAC
 AC fail, battery presence & low battery monitoring
FN-642-ULADA:  Accommodates up to two (2) 12VDC/12AH batteries
 24VDC OR 12VDC rated @ 6.5 amps max  Power supply, logic board, red enclosure, cam lock,
 Four (4) Class A or Four (4) Class B outputs transformer & battery leads
 Enclosure size of 18"H x 14.5"W x 4.625"D

FN-842-ULADA:
 24VDC OR 12VDC rated @ 8 amps max
 Four (4) Class A or Four (4) Class B outputs
 Enclosure size of 18"H x 14.5"W x 4.625"D
PRODUCT LISTINGS
FN-1042-ULADA:
 24VDC OR 12VDC rated @ 10 amps max MEA California State
Fire Marshal
 Four (4) Class A or Four (4) Class B outputs NYC Department
of Building 7315-0410:171
 Enclosure size of 18"H x 14.5"W x 4.625"D 3022852
S5694 220-95E Vol. 18

Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800-845-6692 or technicalsupport@hochiki.com F0105 01/2016