FN-642 842 1042-ULADA DataSheet
FN-642 842 1042-ULADA DataSheet
FN-642 842 1042-ULADA DataSheet
STANDARD FEATURES
Two (2) Class A or (2) Class B FACP inputs
Two (2) NC dry contact trigger inputs
Four (4) Class A or Four (4) Class B indicating
circuits
Two (2) Class B outputs may be paralleled for more
power on an indicating circuit
One (1) Aux. Power Output @ 1 amp supply current
(with or without battery backup)
Signal Circuit Trouble Memory - Facilitates quickly
locating intermittent system trouble and eliminates
costly and unnecessary service calls. LED's indicate
a prior fault (short, open, ground) has occurred on
one or more signaling circuit outputs.
DESCRIPTION 2 wire Horn/Strobe Sync mode allows audible notifi-
cation appliances (Horns) to be silenced while visual
The FN-642-ULADA, FN-842-ULADA, and FN-1042- notification appliances (Strobes) continue to operate
ULADA are extremely cost effective voltage regulated Horn/Strobe sync protocols include: Gentex, System
remote NAC Power Extenders. They may be connected Sensor, Faraday, Wheelock and Amseco.
to any 12 or 24VDC Fire Alarm Control Panel (FACP). Temporal Code 3 Mode
Primary applications include Notification Appliance Steady Mode
Circuit (NAC) expansion (supports ADA requirements) Input to Output Follower Mode (maintains synchroni-
and will provide auxiliary power to support system zation of notification appliance circuits)
accessories. March Time
Compatible with 24VDC or 12VDC fire panels
SPECIFICATIONS Input 115VAC
AC fail, battery presence & low battery monitoring
FN-642-ULADA: Accommodates up to two (2) 12VDC/12AH batteries
24VDC OR 12VDC rated @ 6.5 amps max Power supply, logic board, red enclosure, cam lock,
Four (4) Class A or Four (4) Class B outputs transformer & battery leads
Enclosure size of 18"H x 14.5"W x 4.625"D
FN-842-ULADA:
24VDC OR 12VDC rated @ 8 amps max
Four (4) Class A or Four (4) Class B outputs
Enclosure size of 18"H x 14.5"W x 4.625"D
PRODUCT LISTINGS
FN-1042-ULADA:
24VDC OR 12VDC rated @ 10 amps max MEA California State
Fire Marshal
Four (4) Class A or Four (4) Class B outputs NYC Department
of Building 7315-0410:171
Enclosure size of 18"H x 14.5"W x 4.625"D 3022852
S5694 220-95E Vol. 18