DCP-SOM-A/-AI - CLASS A SUPERVISED OUTPUT MODULE

SPECIFICATIONS
Supply Voltage (S-SC) 25.3 ~ 39 VDC
Auxiliary Supply Voltage 24 VDC
Average Current Consumption
SOM-AI - 420μA (Typical), SOM-A - 220μA (Typical)
(on S-SC Line) Maximum 6mA: Red Alarm LED On
Current Consumption on
Auxiliary Power Lines Typical 50μA
SCI On Resistance
40m ohm Max. (Normal Condition)
SCI Fault Detection Threshold 12 volts (Typical)
SCI Isolation Current
(Short Circuit Condition) 10mA (Typical)
Maximum Quantity Per Loop 127
STANDARD FEATURES Dimensions 4.2"W x 4.7"H x 1.4"D
Ambient Temperature 32°F (0°C) ~ 120°F (49° C)
• Built-in SCI circuitry (SOM-AI only)
• Flexible application Mounting 4" square electrical box
• Quick response to emergency conditions Maximum Output Current 2A@24VDC power limited
• Operation parameters are maintained by the Relative Humidity 90% RH Non-condensing
module, and individual communication with the
control system during emergency conditions
is not required DESCRIPTION
• Contacts are rated 2.0 Amps @ 24VDC The Class A Supervised Output Modules (DCP-SOM-A &
• Programming is highly flexible providing 16 SOM-AI) have been designed to provide application
priority states plus zoning capability flexibility and quick response to emergency conditions.
• Programmed device output is turned off, silenced, Flexibility is provided by a wide range of operating
or programmed to output the selected pattern modes, including supporting multi-zone operations, and/
• UL 864 Listed or functions, up to 16 different modulation patterns and
multi-state programming. The operating parameters for
the DCP-SOM-A & -AI are maintained by the module
and do not require individual communication with the
control system during emergency conditions to operate.
PRODUCT LISTINGS The control panel simply broadcasts system conditions
on the Signaling Line Circuit (SLC) and the DCP-SOM-A
California & -AI modules do the rest based upon the custom
State Fire configuration. Each DCP-SOM-A & -AI provides a single
Marshal 3036830 Class B or Class A circuit rated for 2.0 Amps @ 24
7300-0410:150 VDC. Each DCP-SOM-A & -AI also requires a 24 VDC
S5694
power source in addition to the SLC.

Specifications subject to change without notice.


Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0091 05/2010
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable Class A Supervised Output Modules
(DCP-SOM-A & -AI). The modules shall be UL listed and compatible with the fire alarm control panel. The device
address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall flash to indicate normal
system communication .
The DCP-SOM-A & -AI shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or
double gang electrical back box. The DCP-SOM-A & -AI shall provide a monitor LED that is visible from outside the
cover plate.

Back side of a SOM-AI Back side of a SOM-A


WIRING DIAGRAM
OUT TO NEXT
U.L. LISTED 1481 24VDC INTERFACE MODULE
REGULATED, POWER
S+ SC-
LIMITED SUPPLY FOR FIRE
PROTECTION SIGNALING
SERVICE FOR AUDIBLE Hochiki America Corporation
DEVICES. REFER TO TB1 DCP-SOM-A HOCHIKI
CLASS A SUPERVISED OUTPUT MODULE
CONTROL PANEL 24V +
MANUFACTURER'S 24V+ SER. NO. 910300001

INSTALLATION 24V - U.L. LISTED


24V- IN S+ S+
INSTRUCTIONS. COMPATIBLE
FIRE CONTROL
OUT+ IN SC- SC-
PANEL
For Dry Indoor Use Only
OUT-

IN+
For Proper Installation CIRCUIT OUT+, OUT-, IN+, IN- SHOWN IS
See HA-06-138 Rev 06/09
TB3 SUPERVISED AND INHERENTLY POWER
IN- LIMITED. CONNECT POWER LIMITED
CLASS-B CLASS-A
SUPPLY TO 24V+ & 24V-.

CLASS-B CLASS-A
!
U.L. LISTED SIGNALING DEVICES SELECT CLASS-A WIRING
BY SETTING THIS JUMPER
+ +
- -

CLASS-A OUTPUT WIRING

U.L. LISTED 1481 24VDC OUT TO NEXT


REGULATED, POWER INTERFACE MODULE
LIMITED SUPPLY FOR FIRE
PROTECTION SIGNALING S+ SC-
SERVICE FOR AUDIBLE
Hochiki America Corporation
DEVICES. REFER TO TB1 DCP-SOM-AI HOCHIKI
CONTROL PANEL CLASS A SUPERVISED OUTPUT MODULE

MANUFACTURER'S 24V + 24V+ SER. NO. 910300001

INSTALLATION 24V - U.L. LISTED


INSTRUCTIONS. 24V- IN S+ S+
COMPATIBLE
OUT+ FIRE CONTROL
IN SC- SC-
For Proper Installation PANEL
See HA-06-138 Rev 06/09
OUT- OUT S+

LEAVE TERMINALS "IN+"


IN+ OUT SC-
AND "IN-" UNCONNECTED
For Dry Indoor Use Only TB3
IN-
CLASS-B CLASS-A

CIRCUIT OUT+, OUT-, IN+, IN- SHOWN IS


SUPERVISED AND INHERENTLY POWER
LIMITED. CONNECT POWER LIMITED
SUPPLY TO 24V+ & 24V-.

CLASS-B CLASS-A
!
U.L. LISTED SIGNALING DEVICES SELECT CLASS-B WIRING
BY SETTING THIS JUMPER
+ E.O.L. DEVICE

- PART NUMBER
0400-01046

CLASS-B OUTPUT WIRING E.O.L. DEVICE


PART NUMBER
0400-01046

Hochiki America Corporation SOM-A & -AI Specifications subject to change without notice.