DCP-CZM CONVENTIONAL ZONE MODULE

DESCRIPTION
The Hochiki Conventional Zone Module (DCP-CZM) is
designed for use on an analog addressable Fire Alarm
system. Up to 127 devices can be placed on a single
SLC loop. The device address is uniquely stored on an
onboard EEPROM. The module allows the panel to
interface and monitor two-wire conventional detectors
or pull stations. Each DCP-CZM transmits the status on
one zone of devices (25 maximum per zone) back to
the panel. It supervises the power supply as well as the
entire zone of devices. Status conditions are reported
as normal, open or alarm. All 2-wire smoke detectors
must be UL listed as compatible to be interfaced with
the DCP-CZM. The interrupt driven Digital Communica-
tion Protocol (DCP) combines maximum communica-
tion reliability and fast response to emergency condi-
tions. The module has a single bicolored LED to indi-
STANDARD FEATURES cate device status. It fits into a standard 4" square or
 UL 864 9th Edition Listed double gang electrical back box.
 Provides an address point for a zone of up to 25
conventional smoke detectors
 Blinks green when polled. Latched on red (controlled SPECIFICATIONS
by panel) when activated
Supply Voltage (S-SC) 25.3 ~ 39 VDC
 Device address can be programmed with a handheld Auxiliary Supply Voltage 18.8 ~ 27.2 VDC
programmer. Device address- ranges from 1 to 127 Average Current Consumption 670µA
 Compatible with Class B and Class A wiring
2-Wire Detector Loop Current 1mA Max.
 Auxiliary power source provides power for the zone
of detectors From Auxiliary Supply 60mA Max.
EOL Device 4.7 ohms Resistor
 Compatible with conventional detectors, SOC-24V,
Max. Quantity Per Loop 127
SOC-24VN, SLR, SIJ, SLK, SLV, DCD, DFE and SIH
Alarm Threshold Level <1.5K ohms
series
Wiring Threshold Level >2.5K ohms & <6K ohms
 Compatible with TH series linear heat cables from Open Circuit Threshold Level >10K ohms
Max. 2-Wire Conventional 50 ohms (total wire length)

Dimensions 4.2”W x 4.7”H x 1.4”D


Operating Temperature 32°F (0°C) ~ 120°F (49°C)
PRODUCT LISTINGS Mounting 4” square electrical box
Relative Humidity 90% RH Non-Condensing
California State
Fire Marshal
7300-0410:150

S5694 3033215

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax: 714-522-2268
Technical Support: 800-845-6692 or technicalsupport@hochiki.com F0004 12/2018
DCP-CZM CONVENTIONAL ZONE MODULE

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install
where indicated on the plans, Conventional
Zone Module (DCP-CZM). The modules
shall be UL Listed and compatible with the
Hochiki America Control Panel Protocol.
The device address shall be electrically
programmed and stored in EEPROM. A
bi-colored LED shall indicate device status.
The DCP-CZM shall be supplied with a
plastic cover and shall be suitable for
mounting to a 4” square or double gang
electrical back box. The DCP-CZM shall
provide a monitor LED that is visible from
outside the cover plate.

Compatible Two Wire Detectors for use with the CZM with zone identifier A:
Detector Max
Detector Model Detector Type Base Model Base Identifier
Identifier Detectors
NS4 and NS6 series -100, -220, -221, -224, HB-3, HB-4, HB-5,
SOC-24V, SOC-24VN HD-3 Photoelectric 25
HSC-220R, HSC-224R HB-55, HB-72, HB-73
SLK24F HD-3 Photoelectric HSB-224 HB-53 25
SLK24F HD-3 Photoelectric HSB-220 HB-56 25
SIH-24F HD-3 Ionization HSB-224 HB-53 25
SIH-24F HD-3 Ionization HSB-220 HB-56 25
SLR-24H HD-3 Photoelectric w/heat NS4-224 , NS6-224 HB-5 25
SLR-24H HD-3 Photoelectric w/heat NS4-220, NS6-220 HB-3 25
SLR-24V HD-3 Photoelectric NS4-224, NS6-224 HB-5 25
SLR-24V HD-3 Photoelectric NS4-220, NS6-220 HB-3 25
SLR-835 /-835W HD-3 Photoelectric (8-35V) NS4-224, NS6-224, NS4-224W, NS6-224W HB-5 18
SLR-835 /-835W HD-3 Photoelectric (8-35V) NS4-220, NS6-220, NS4-220W, NS6-220W HB-5 18
SLR-835H /-835HW HD-5 Photoelectric (8-35V) w/thermal NS4-224, NS6-224, NS4-224W, NS6-224W HB-5 18
SLR-835H /-835HW HD-5 Photoelectric (8-35V) w/thermal NS4-220, NS6-220, NS4-220W, NS6-220W HB-3 18
SLR-835B-2 /-2W HD-6 Photoelectric (8-35V) (baseless) N/A N/A 18
SLR-835BH-2 /-2W HD-6 Photoelectric (8-35V) w/thermal (baseless) N/A N/A 18
DCD-135/ -190 HD-3 Heat Fixed Temp / Rate of Rise NS4-224, NS6-224 HB-5 25
DCD-135/ -190 HD-3 Heat Fixed Temp / Rate of Rise NS4-220, NS6-220 HB-3 25
DFE-135/ -190 N/A Heat Fixed Temp HSC-224L HB-62 25
DFE-135/ -190 N/A Heat Fixed Temp HSC-220L HB-64 25
SLV-24/ -24N/ -24V HD-3 Photoelectric NS4-224, NS6-224, NS4-224W, NS6-224W HB-5 25
SLV-24/ -24N/ -24V HD-3 Photoelectric NS4-220, NS6-220, NS4-220W, NS6-220W HB-3 25

Compatible Linear Heat Detection Cable for use with the CZM:
Manufacturer Model Description Maximum Length
Proline Protection Systems TH 68 Fixed Temp. line type heat detector cable 115°F (68° C) 8,000ft. (2,438m)
Proline Protection Systems TH 88 Fixed Temp. line type heat detector cable 190°F (88° C) 8,000ft. (2,438m)
Proline Protection Systems TH 105 Fixed Temp. line type heat detector cable 221°F (105° C) 8,000ft. (2,438m)

Hochiki America Corporation CZM Specifications subject to change without notice.