DN 60955
DN 60955
DN 60955
General
The FireWarden-50X (NFW-50X) and FireWarden-50XI (NFW-50XI)
are the latest intelligent addressable fire alarm control panels (FACPs)
within the FireWarden Series and are direct replacements for the Fire-
Warden-50 (NFW-50). The NFW-50X Series supports up to 50
addressable devices in any combination of detectors or modules. With
an extensive list of powerful features, the NFW-50X Series programs
just like FireWarden-100 products, yet fits into applications previously
served only by conventional panels.
The NFW-50X features a pre-installed IPOTS-COM, a dual technology
(POTS and IP) communicator. The POTS transmits system status
(alarms, troubles, AC loss, etc.) to a Central Station via the public
switched telephone network. The IP communicator’s internet monitor-
ing capability sends alarm signals over the Internet saving the monthly
cost of two dedicated business telephone lines. Although not required,
the secondary telephone line may be retained providing backup com-
munication over the public switched telephone line. Optional cellular
reporting is available using an HW-TG7F Series Communicators or
the CLSS Pathway.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can be
• Waterflow selection per module point
uploaded/downloaded via the panel’s USB port (and USB cable) or via
an ethernet connection using the IPOTS-COM communicator(NFW- • Alarm verification selection per detector point
50X only). The USB port also allows for the download or upload of the • Maintenance alert warns when smoke detector dust accumulation
entire program, history file, walk-test data, current status and system is excessive
voltages by means of a USB flash drive. • One-person audible or silent walktest with walktest log & printout
The power supply and all electronics are contained on a circuit board • System alarm verification selection per detector point
supported on a new quick install chassis and housed in a metal cabi- • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72
net. Available accessories include local and remote upload/download compliant)
software, remote annunciators, and reverse polarity/city box transmit- • Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
ter (4XTM). • Remote Acknowledge, Alarm Silence, Reset and Drill via address-
able modules or remote annunciator
Features • Upload/Download of program and data via USB with optional
FS-Tools Programming Utility
• Listed to UL Standard 864, 10th edition
• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- SLC COMMUNICATION LOOP
phone Service) Central Station Communicator (NFW-50X only) • Supports FlashScan® and CLIP protocols
• Optional Cellular Central Station Communicators over AlarmNet® • SLC operates up to 10,000 ft. (3,000 m) in FlashScan mode with
(NFW-50X only) twisted, unshielded wire
• Compatible with SWIFT® wireless devices • Single addressable SLC loop which meets NFPA Class B and
• Auto-programming (learn mode) reduces installation time. Reports Class A requirements
two devices set to the same address • 50 addressable device capacity (any combination of addressable
• Certified for seismic applications when used with the appropriate detectors and modules)
seismic mounting kit • Compatible with NOTIFIER FireWarden & ONYX Series address-
• Two independently programmable, built-in, Class A or Class B NAC able devices (refer to the FireWarden SLC Wiring Manual)
circuits
NOTIFICATION APPLIANCE CIRCUITS (NACS)
• Selectable strobe synchronization for System Sensor, Wheelock,
and Gentex devices • Two independently programmable output circuits. Circuits can be
• Notification Appliance Circuit End of Line resistor matching configured for Class A or Class B wiring.
• Four programmable function keys for ease of maintenance – Class B
• Two programmable relays and one fixed trouble relay – Class A
• Built-in Programmer • Silence Inhibit and Autosilence timer options
• Integral 80-character LCD display with backlighting • Continuous, March Time, Temporal, or California code for main cir-
cuit board NACs with two-stage capability
• Real-time clock/calendar with automatic daylight savings control
• Selectable strobe synchronization per NAC
• History file with 1,000 event capacity
• 2.5 A special application, 250mA regulated, total power for NACs
• Addressable sounder base
NOTE: Maximum or total 24VDC system power shared between all NAC
• Control module delay timer circuits and the ANN-BUS is 2.7 A
• Automatic detector sensitivity testing (NFPA 72 compliant)
• Automatic device type-code verification PROGRAMMING AND SOFTWARE
• Point trouble identification • Autoprogramming (learn mode) reduces installation time