NFS2-640 Intelligent Addressable Fire Alarm Control Panel

General
The NFS2-640 intelligent Fire Alarm Control Panel is part of the
ONYX® Series of Fire Alarm Controls from NOTIFIER.
In stand-alone or network configurations, ONYX Series products
meet virtually every application requirement.
The NFS2-640’s modular design makes system planning easier. The
panel can be configured with just a few devices for small building
applications, or networked with many devices to protect a large cam-
pus or a high-rise office block. Simply add additional peripheral
equipment to suit the application.
A host of other options are available, including single- or multichan-
nel voice; firefighter’s telephone; LED, LCD, or PC-based graphic
annunciators; networking; advanced detection products for challeng-
ing environments; wireless fire protection; and many additional
options.
NOTE: Unless called out with a version-specific “E” at the end of the part
number, “NFS2-640” refers to models NFS2-640 and NFS2-640E; simi-
larly, “CPU2-640” refers to models CPU2-640 and CPU2-640E.

Features
• Certified for seismic applications when used with the appropriate
seismic mounting kit.
• Approved for Marine applications when used with listed compati-
ble equipment. See DN-60688.
• One, expandable to two, isolated intelligent Signaling Line Circuit
(SLC) Class A, B, or X.
• Wireless fire protection using SWIFT Smart Wireless Integrated • 80-character remote annunciators (up to 32).
Fire Technology. See DN-60820.
• EIA-485 annunciators, including custom graphics.
• Up to 159 detectors and 159 modules per SLC; 318 devices per
• Printer interface (80-column and 40-column printers).
loop/636 per FACP or network node.
• History file with 800-event capacity in nonvolatile memory, plus
– Detectors can be any mix of ion, photo, thermal, or multi-sen-
separate 200-event alarm-only file.
sor; wireless detectors are available for use with the FWSG.
• Alarm Verification selection per point, with automatic counter.
– Modules include addressable pull stations, normally open con-
tact devices, two-wire smoke detectors, notification, or relay; • Presignal/Positive Alarm Sequence (PAS).
wireless modules are available for use with the FWSG. • Silence inhibit and Auto Silence timer options.
• Standard 80-character display, 640-character large display • March time/temporal/California two-stage coding/strobe synchro-
(NCA-2), or display-less (a node on a network). nization.
• Network options: • Full QWERTY keypad.
– High-speed network for up to 200 nodes (NFS2-3030, NFS2- • Battery charger supports 18 – 200 AH batteries.
640, NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM, • Non-alarm points for lower priority functions.
ONYXWorks, NFS-3030, NFS-640, and NCA). • Remote ACK/Signal Silence/System Reset/Drill using monitor
– Standard network for up to 103 nodes (NFS2-3030, NFS2-640, modules.
NFS-320(C), NFS-320SYS, NCD, NCA-2, DVC-EM,
• Automatic time control functions, with holiday exceptions.
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-
300/400, AFP-1010, and AM2020). Up to 54 nodes when DVC- • Surface Mount Technology (SMT) electronics.
EM is used in network paging. • Extensive, built-in transient protection.
• 6.0 A switch mode power supply with four Class A/B built-in Noti- • Powerful Boolean logic equations.
fication Appliance Circuits (NAC). Selectable System Sensor, • Support for SCS Series smoke control system in HVAC mode.
Wheelock, or Gentex strobe synchronization.
• Built-in Alarm, Trouble, Security, and Supervisory relays. NCA-2 AS PRIMARY DISPLAY
• Field-programmable on panel or on PC. • Backlit, 640-character display.
• VeriFire® Tools online or offline programming utility. Upload/ • Supports SCS Series smoke control system in FSCS mode when
Download, save, store, check, compare, and simulate panel data- SCS is connected to the NCA-2 used as primary display.
bases. Upgrade panel firmware. • Supports DVC digital audio loop.
• Autoprogramming and Walk Test reports. • Printer and CRT EIA-232 ports.
• Multiple central station communication options: • EIA-485 annunciator and terminal mode ports.
– Standard UDACT • Alarm, Trouble, Supervisory, and Security relays.
– Internet
– Internet/GSM
DN-7111:N • 12/20/2020 — Page 1 of 9
SWIFT WIRELESS FLASHSCAN® INTELLIGENT FEATURES
• Self-healing mesh wireless protocol. • Polls up to 318 devices in less than two seconds.
• Each SWIFT Gateway supports up to 50 devices: 1 wireless gate- • Activates up to 159 outputs in less than five seconds.
way and up to 49 SWIFT devices. • Multicolor LEDs blink device address during Walk Test.
• Up to 4 wireless gateways can be installed with overlapping net- • Fully digital, high-precision protocol (U.S. Patent 5,539,389).
work coverage. • Manual sensitivity adjustment — up to nine levels.
RELEASING FEATURES • Pre-alarm ONYX intelligent sensing — up to nine levels.
• Ten independent hazards. • Day/Night automatic sensitivity adjustment.
• Sophisticated cross-zone (three options). • Sensitivity windows:
• Delay timer and Discharge timers (adjustable). – Photo – 0.5 to 2.35%/foot obscuration.
• Abort (four options). – High-Sensitivity Photoelectric (VIEW®) – Open Air Protection
• Low-pressure CO2 listed. (0.5% - 2.0%/ft. obscuration), Special Applications (0.02%-
0.5%/ft. obscuration)
DIGITAL VOICE AND TELEPHONE FEATURES – Multi-Criteria Detector – Open Air Protection (2.52-3.89%/ft.
• Up to eight channels of digital audio. obscuration), Special Applications (1.13-2.52%/ft. obscuration)
• 35, 50, 75, and 100/125 watt digital amplifiers (DAA2/DAX series • Drift compensation (U.S. Patent 5,764,142).
and DS series; NCA-2 required as primary display). • Degraded mode: In the unlikely event that the CPU2-640 micro-
• Solid-state digital message generation. processor fails, FlashScan detectors revert to degraded operation
• Firefighter telephone option. and can activate the CPU2-640 NAC circuits and alarm relay.
Each of the four built-in panel circuits includes a Disable/Enable
• 30- to 120-watt high-efficiency amplifiers (AA Series).
switch for this feature.
• Backup tone generator and amplifier option.
• Multi-detector algorithm involves nearby detectors in alarm deci-
• NFS2-640 can also integrate with the FirstCommand® Emer- sion (U.S. Patent 5,627,515).
gency Communications System. See DN-60772.
• Automatic detector sensitivity testing (NFPA-72 compliant).
HIGH-EFFICIENCY OFFLINE SWITCHING • Maintenance alert (two levels).
3.0 A POWER SUPPLY (6.0 A IN ALARM) • Self-optimizing pre-alarm.
• 120 VAC (NFS2-640); 240 VAC (NFS2-640E).
• Displays battery current/voltage on panel (with display).

SLC Intelligent Loop 1


Up to 32 remote displays
DEVICES
FWSG
FPTI-951 NBG-12LX XP6/10
FSP-951
FST-951 FMM-1 FCM-1
FCO-951 IDC NAC
FDU-80 …etc. FRM-1
LCD2-80 Relay Contact
SLC Intelligent Loop 2
EIA-485

KDM-R2 display EIA-485 2048 annunciator/control points


OR

NCA-2
OR ACM-8R LDM-32
ACM/AEM-24AT
with no display Relay Control Custom Graphics
LED Annunciator

Dual phone
lines to
Optional 636-point UDACT Central
EIA-232
Station

Sample NFS2-640
System “C” cabinet size shown 7111blok-2014.wmf
PRN Series Printer
Options

Page 2 of 9 — DN-7111:N • 12/20/2020


FSV-951 SERIES VIEW® (VERY INTELLIGENT EARLY WARNING) allows the NFS2-640 to have the largest device per loop capacity in
HIGH-SENSITIVITY SMOKE DETECTOR the industry — 318 points — yet every input and output device is
sampled in less than two seconds. The microprocessor-based
• Advanced ONYX intelligent sensing algorithms differentiate
FlashScan detectors have bicolor LEDs that can be coded to provide
between smoke and non-smoke signals.
diagnostic information, such as device address during Walk Test.
• Addressable operation pinpoints the fire location.
• Ivory models (-IV) support CLIP mode as well as FlashScan. ONYX Intelligent Sensing
• ULC listed models available; “A” models are ULC Listed. Intelligent sensing is a set of software algorithms that provides the
• -R is retrofit, backwards compatible for use with older panels. NFS2-640 with industry-leading smoke detection capability. These
complex algorithms require many calculations on each reading of
FCO-951/-IV ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR each detector, and are made possible by the high-speed microcom-
• Detects all four major elements of a fire (smoke, heat, CO, and puter used by the NFS2-640.
flame).
Drift Compensation and Smoothing: Drift compensation allows
• 135°F (57.2°C) fixed-temperature heat detector. the detector to retain its original ability to detect actual smoke, and
• Transmits an alarm signal due to heat. resist false alarms, even as dirt accumulates. It reduces mainte-
• Separate signal for life-safety CO detection. nance requirements by allowing the system to automatically perform
• Optional addressable sounder base for Temp-3 (fire) or Temp-4 the periodic sensitivity measurements required by NFPA 72.
(CO) tone. Smoothing filters are also provided by software to remove transient
noise signals, such as those caused by electrical interference.
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance-alarm immunity. Maintenance Warnings: When the drift compensation performed
for a detector reaches a certain level, the performance of the detec-
• ULC listed models available; -A models are ULC Listed. tor may be compromised, and special warnings are given. There are
FPTI-951(A) INTELLIGENT MULTI-CRITERIA DETECTOR three warning levels: (1) Low Chamber value; (2) Maintenance Alert,
indicative of dust accumulation that is near but below the allowed
• Combined Photoelectric Thermal and Infrared Sensor limit; (3) Maintenance Urgent, indicative of dust accumulation above
• UL 268 7th Edition and UL 521 Listed; Canadian models CAN/ the allowed limit.
ULC S529 and CAN/ULC S530
Sensitivity Adjust: Nine sensitivity levels are provided for alarm
• Microprocessor-based technology; combination photo, thermal, detection. These levels can be set manually, or can change automat-
and infrared technology. ically between day and night. Nine levels of pre-alarm sensitivity can
also be selected, based on predetermined levels of alarm. Pre-alarm
FPC-951(A) PHOTOELECTRIC/CO SENSOR
operation can be latching or self-restoring, and can be used to acti-
• Combined photoelectric and carbon monoxide sensor vate special control functions.
FSCO-95(A) INTELLIGENT CO SENSOR Self-Optimizing Pre-Alarm: Each detector may be set for “Self-
• Carbon monoxide sensor Optimizing” pre-alarm. In this special mode, the detector “learns” its
normal environment, measuring the peak analog readings over a
FS-OSI-RI(A) ADDRESSABLE INTELLIGENT SINGLE-ENDED BEAM long period of time, and setting the pre-alarm level just above these
SMOKE DETECTOR
normal peaks.
• Intelligent addressable reflector-type linear optical beam smoke Cooperating Multi-Detector Sensing: A patented feature of ONYX
detector intelligent sensing is the ability of a smoke sensor to consider read-
ings from nearby sensors in making alarm or pre-alarm decisions.
• Fast, easy, and intuitive beam alignment indicated by directional
Without statistical sacrifice in the ability to resist false alarms, it
LED arrows
allows a sensor to increase its sensitivity to actual smoke by a factor
• Long range coverage of 16-328 ft (5-100 m) is standard; no sepa- of almost two to one.
rate long-range kit required
FMM-4-20 GAS DETECTION MODULE Field Programming Options
• Interface to industry-standard linear scale 4-20 mA sensors. Autoprogram is a timesaving feature. The FACP “learns” what
• Five programmable thresholds. devices are physically connected and automatically loads them in
the program with default values for all parameters. Requiring less
• FM Approved, Class 6320 (Stationary Gas Sensors/Detectors). than one minute to run, this routine allows the user to have almost
INTELLIGENT VESDA DETECTORS immediate fire protection in a new installation, even if only a portion
of the detectors are installed.
• Intelligent aspiration smoke detectors connect directly to the SLC
loop of compatible ONYX® Series panels: Keypad Program Edit (with KDM-R2) The NFS2-640, like all NOTI-
– VEA-040-A00-NTF, VEA-040-A10-NTF FIER intelligent panels, has the exclusive feature of program cre-
ation and editing capability from the front panel keypad, while
– VEP-A00-P-NTF, VEP-A10-P-NTF, VEP-A00-1P-NTF continuing to provide fire protection. The architecture of the NFS2-
– VEU-A00-NTF, VEU-A10-NTF 640 software is such that each point entry carries its own program,
• Models offer LED display, LCD display, or both including control-by-event links to other points. This allows the pro-
• Coverage options for spaces up to 69,965 square feet gram to be entered with independent per-point segments, while the
NFS2-640 simultaneously monitors other (already installed) points
FlashScan, Exclusive for alarm conditions.
World-Leading Detector Protocol VeriFire® Tools is an offline programming and test utility that can
greatly reduce installation programming time, and increase confi-
At the heart of the NFS2-640 is a set of detection devices and device dence in the site-specific software. It is Windows®-based and pro-
protocol — FlashScan (U.S. Patent 5,539,389). FlashScan is an all- vides technologically advanced capabilities to aid the installer. The
digital protocol that gives superior precision and high noise immunity. installer may create the entire program for the NFS2-640 in the com-
In addition to providing quick identification of an active input device, fort of the office, test it, store a backup file, then bring it to the site
this protocol can also activate many output devices in a fraction of and download from a laptop into the panel.
the time required by competitive protocols. This high speed also

DN-7111:N • 12/20/2020 — Page 3 of 9


Placement of Equipment CONFIGURATION GUIDELINES
in Chassis and Cabinet Stand-alone and network systems require a main display. On sys-
tems with one FACP (one CPU2-640/-640E), display options are the
The following guidelines outline the NFS2-640’s flexible system KDM-R2 or the NCA-2. On network systems (two or more networked
design. fire panel nodes), at least one NCD, NCA-2, NCS, or ONYXWorks
Rows: The first row of equipment in the cabinet mounts in the chas- annunciation device is required. Other options listed as follows.
sis shipped with the FACP. Mount the second, third, or fourth rows of
equipment in a CHS-4 series chassis or, for Digital Voice Command MAIN SYSTEM COMPONENTS
products, in CA-1 or CA-2. (For DVC-EM and DAA2/DAX compo- CPU2-640: Central processing unit (CPU) with integral 3.0 A (6.0 A
nents see DVC Manual; for DS series components see DS-AMP in alarm) power supply for an NFS2-640 system. Includes control
Manual; for DVC-AO applications, see AA Series Installation Man- panel factory-mounted on a chassis; one Signaling Line Circuit
ual). Other options are available; see your panel’s installation man- expandable to two; documentation kit. Order one per system or as
ual. necessary (up to 103 network nodes) on a network system. (Non-
English versions also available: CPU2-640-FR, CPU2-640-PO,
Wiring: When designing the cabinet layout, consider separation of
CPU2-640-SP.)
power-limited and non-power-limited wiring as discussed in the
NFS2-640 Installation Manual. CPU2-640E: Same as CPU2-640 but requires 240 VAC, 1.5 A, (3.0
A in alarm). (Non-English versions also available: CPU2-640E-PO,
Positions: A chassis offers four basic side-by-side positions for
CPU2-640E-SP.)
components; the number of modules that can be mounted in each
position depends on the chassis model and the size of the individual KDM-R2: 80-character backlit LCD display with QWERTY program-
module. There are a variety of standoffs and hardware items avail- ming and control keypad. Order two BMP-1 blank modules and DP-
able for different combinations and configurations of components. DISP2 mounting plate separately. Requires top row of a cabinet.
Required for each stand-alone 80-character display system. The
It is critical that all mounting holes of the NFS2-640 are secured with
a screw or standoff to ensure continuity of Earth Ground. KDM-R2 may mount in network nodes to display “local” node infor-
mation as long as at least one NCA-2 or NCS/ONYXWorks network
Layers: The control panel’s chassis accepts four layers of equip- display is on the system to display network information. (Non-English
ment, including the control panel. The CPU2-640 fills three positions versions also available: KDM-R2C for ULC application, KDM-R2-FR,
(left to right) in the first-installed layer (the back of the chassis); its KDM-R2-PO, KDM-R2-SP.)
integral power supply occupies the center two positions in the next
NCA-2: Network Control Annunciator, 640 characters. On single
two layers; the optional display occupies (the left) two positions at
the front, flush with the door. Some equipment, such as the NCA-2, CPU2-640/-640E systems, the optional NCA-2 can be used as the
Primary Display for the panel and connects directly to the CPU2-
may be mounted in the dress panel directly in front of the control
640/-640E. On network systems (two or more networked fire panel
panel. The NCA-2 can be used as a primary display for the NFS2-
640 (use NCA/640-2-KIT) by directly connecting their network ports nodes), one network display (either NCA-2 or NCS/ONYXWorks) is
required for every system. On network systems, the NCA-2 connects
(required in Canadian stand-alone applications); see NCA-2 data
to (and requires) a standard Network Communication Module or
sheet for mounting options (DN-7047).
High-Speed Network Communication Module. Mounts in a row of
Expansion: Installing an LEM-320 Loop Expander Module adds a FACP node or in two annunciator positions. Mounting options
second SLC loop to the control panel. The LEM-320 is mounted onto include the DP-DISP2, ADP-4B, or in an annunciator box, such as
the CPU2-640, occupying the middle-right, second (back) slot on the the ABS-2D. In CAB-4 top-row applications, a DP-DISP2 and two
chassis. BMP-1 blank modules are required for mounting. Required for
Networking: If networking two or more control panels, each unit NFS2-640 applications employing the DVC-EM with DAL devices.
requires a Network Communication Module or High-Speed Network Non-English versions are available. NCA-2 are available for ULC
Communication Module. (HS-NCM can support two nodes; see applications. For marine applications, order NCA-2-M; for non-
“Networking Options” on page 4). These modules can be installed in English Marine applications, order NCA-2-M and the appropriate
any option board position (see manual), and additional option boards KP-KIT-XX. See DN-7047.
can be mounted in front of the network communication modules. NCD: As part of a standalone NFS2-640 system, the NCD can serve
as Primary Display for the panel, to provide control and status capa-
KDM-R2 Controls and Indicators bilities on displayless nodes. On network systems, the NCD con-
Program Keypad: QWERTY type (keyboard layout, see figure). nects to (and requires) a standard Network Communication Module
or High-Speed Network Communication Module. Mounting options
12 LED indicators: Power; Fire Alarm; Pre-Alarm; Security; Super-
include the ABS-TD for standalone applications. In the CAB-4 series
visory; System Trouble; Signals Silenced; Points Disabled; Control
the NCD can be mounted in the top row with a DP-GDIS1 or lower
Active; Abort; Pre-Discharge; Discharge.
rows using a DP-GDIS2. See DN-60974.
Keypad Switch Controls: Acknowledge/Scroll Display; Signal
NCA/640-2-KIT: Bracket installation kit required to mount NCA-2 to
Silence; Drill; System Reset; Lamp Test.
the CPU2-640/-640E’s standard chassis.
LCD Display: 80 characters (2 x 40) with long-life LED backlight.
DP-DISP2: Dress panel for top row in cabinet with CPU2-640/640E
installed.
Product Line Information
ADP2-640: Dress panel for middle rows with CPU2-640/640E.
• “Configuration Guidelines” on page 4
BMP-1: Blank module for unused module positions.
• “Main System Components” on page 4
BP2-4: Battery plate, required.(Existing JADT-XLS-BP2-4 may be
• “Networking Options” on page 4
used in retrofits.)
• “Auxiliary Power Supplies and Batteries” on page 5
LEM-320: Loop Expander Module. Expands each NFS2-640 to two
• “Audio Options” on page 5
Signaling Line Circuits. See DN-6881.
• “Compatible Devices, EIA-232 Ports” on page 5
• “Compatible Devices, EIA-485 Ports” on page 5 NETWORKING OPTIONS
• “Compatible Intelligent Devices” on page 6 NCM-W, NCM-F: Standard Network Communications Modules. Wire
• “Enclosures, Chassis, and Dress Plates” on page 7 and multi-mode fiber versions available. See DN-6861.
• “Other Options” on page 8

Page 4 of 9 — DN-7111:N • 12/20/2020


HS-NCM-W(-2), HS-NCM-MF, HS-NCM-SF, HS-NCM-WMF(-2), DAA2-7525(E): 75W, 25 Vrms digital audio amplifier assembly with
HS-NCM-WSF(-2), HS-NCM-MFSF: High-speed Network Commu- power supply; includes chassis. See DN-60556.
nications Modules that can connect to two nodes. Wire, single-mode DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly with
fiber, multi-mode fiber, and media conversion models are available. power supply, includes chassis. See DN-60561.
See DN-60454.
DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assembly with
RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire power supply, includes chassis. See DN-60561.
connection (RPT-W), multi-mode fiber connection (RPT-F), or allow-
ing a change in media type between wire and fiber (RPT-WF). Not DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with
used with high-speed networks. See DN-6971. power supply, includes chassis. See DN-60561.
ONYXWorks: UL-listed graphics PC workstation, software, and DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with
computer hardware. See DN-7048 for specific part numbers. power supply, includes chassis. See DN-60561.
NFN-GW-EM-3: NFN Gateway, embedded. (Replaces NFN-GW- TELH-1: Firefighter’s Telephone Handset for use with the DVC-EM
EM.) See DN-60499. when mounted in the CA-2 chassis. See DN-7045.
NWS-3: NOTI•FIRE•NET™ Web Server. See DN-6928. CMIC-1: Optional microphone and microphone well assembly used
with the CA-1 chassis.
CAP-GW: Common Alerting Protocol Gateway. See DN-60756.
RM-1/RM-1SA: Remote microphone assemblies, mount on ADP-4
VESDA-HLI-GW: VESDAnet high-level interface gateway. See DN- (RM-1) dress panel or CAB-RM/-RMR (RM-1SA) stand-alone cabi-
60753. nets. See DN-6728.
LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic and AA-30: Audio Amplifier, 30 watts, 25 Vrms. Includes amplifier and
high-speed NOTI•FIRE•NET networks through the NFN Gateway. audio input supervision, backup input, and automatic switchover,
See DN-60679. power supply, cables. See DN-3224.
OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See DN- AA-120/AA-100: Audio Amplifier provides up to 120 watts of 25
60679. VRMS audio power for the NFS-640. The amplifier contains an inte-
AUXILIARY POWER SUPPLIES AND BATTERIES gral chassis for mounting to a CAB-B4, -C4, or -D4 backbox (con-
sumes one row). Switch-mode power. Includes audio input and
ACPS-610: 6.0 A or 10.0 A addressable charging power supply. See amplified output supervision, backup input, and automatic switcho-
DN-60244. ver to backup tone. Order the AA-100 for 70.7 VRMS systems and
APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of 100 watts of power. See DN-3224.
power for peripheral devices. Includes battery input and transfer DAA Series Digital Audio Amplifiers: Legacy DAA Series amplifi-
relay, and overcurrent protection. Mounts on two of four positions on ers are compatible with DVC-EM systems running SR4.0. For spe-
a CHS-4L or CHS-4 chassis. See DN-5952. cific information on DAA-50 series amplifiers, refer to DN-7046. For
FCPS-24S6/S8: Remote 6 A and 8 A power supplies with battery information on DAA-7525 Series, refer to DN-60257.
charger. See DN-6927. NFC-25/50: 25 watt, 25 VRMS, emergency Voice Evacuation Con-
BAT Series: Batteries. NFS2-640 uses two 12 volt, 18 to 200 AH trol Panel (VECP) with integral commercial microphone, digital mes-
batteries. See DN-6933. sage generator, and single-/dual-channel Class A or Class B
speaker circuits. See DN-60772.
AUDIO OPTIONS
NOTE: For mounting hardware, see “Enclosures, Chassis, and Dress COMPATIBLE DEVICES, EIA-232 PORTS
Plates” on page 7 and peripheral data sheets. PRN-7: 80-column printer. See DN-60897.
DVC-EM: Digital Voice Command, digital audio processor with mes- VS4095/5: Printer, 40-column, 24V. Mounted in external backbox.
sage storage for up to 32 minutes of standard quality (4 minutes at See DN-3260.
high quality) digital audio. Capable of playing up to eight simultane- DPI-232: Direct Panel Interface, specialized modem for extending
ous messages when used with Digital Audio Loop (DAL) devices. serial data links to remotely located FACPs and/or peripherals. See
See DN-7045. DN-6870.
DVC-RPU: Digital Voice Command Remote Paging Unit for use with
DVC-EM. Includes the keypad/display. See DN-60726. COMPATIBLE DEVICES, EIA-485 PORTS
DS-DB: Digital Series Distribution Board, provides bulk amplification ACM-24AT: ONYX Series ACS annunciator – up to 96 points of
capabilities to the DVC-EM while retaining digital audio distribution annunciation with Alarm or Active LED, Trouble LED, and switch per
capabilities. Can be configured with up to four DS-AMPs, supplying circuit. Active/Alarm LEDs can be programmed (by powered-up
high-level risers spread throughout an installation. See DN-60565. switch selection) by point to be red, green, or yellow; the Trouble
LED is always yellow. See DN-6862.
DVC-KD: DVC-EM keypad for local annunciation and controls; sta-
tus LEDs and 24 user-programmable buttons. See DN-7045. AEM-24AT: Same LED and switch capabilities as ACM-24AT,
expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
DS-AMP/E: 125W, 25 VRMS, or 100W, 70VRMS. 70VRMS requires
DS-XF70V step-up transformer. Digital Series Amplifier, part of the ACM-48A: ONYX Series ACS annunciator – up to 96 points of
DS-DB system. See DN-60663. annunciation with Alarm or Active LED per circuit. Active/Alarm
LEDs can be programmed (by powered-up switch selection) in
DS-RFM, DS-FM, DS-SFM: Fiber conversion modules for DVC-EM, groups of 24 to be red, green, or yellow. Expandable to 96 points
DS-DB distribution board, and DAX and DAA2 Series amplifiers. See with one AEM-48A. See DN-6862.
DN-60633.
AEM-48A: Same LED capabilities as ACM-48A, expands the ACM-
DVC-AO: DVC Analog Output board provides four analog output cir- 48A to 96 points. See DN-6862.
cuits for use with AA Series amplifiers. Four-channel operation sup-
ported. See DN-7045. ACM-8R: Remote Relay Module with eight Form-C contacts. Can be
located up to 6,000 ft. (1828.8 m) from panel on four wires. See DN-
DAA2-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with 3558.
power supply; includes chassis. See DN-60556.
FDU-80: Terminal mode. 80-character, backlit LCD display. Mounts
DAA2-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See DN-
with power supply; includes chassis. See DN-60556. 6820.

DN-7111:N • 12/20/2020 — Page 5 of 9


LCD2-80: Terminal and ACS mode. 80-character, backlit LCD dis- FST-951H: White, low-profile intelligent 190°F fixed thermal sensor,
play. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FlashScan only. Must be mounted to one of the bases listed below.
FACP. See DN-60548. ULC: FST-951HA.
LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM-R32; FST-951H-IV: Ivory, low-profile intelligent 190°F thermal sensor,
remote custom graphic driver modules. See DN-0551. FlashScan and CLIP. Must be mounted to one of the bases listed
SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers SCS- below. ULC: FST-951HA-IV.
8L, SCE-8L; eight (expandable to 16) circuits (HVAC only). See DN- FSV-951, FSV-951R:White, intelligent high-sensitivity photoelectric
4818. smoke detector. ULC: FSV-951A, FSV-951RA
TM-4: Transmitter Module. Includes three reverse-polarity circuits FSV-951-IV, FSV-951R-IVIvory, intelligent high-sensitivity photoelec-
and one municipal box circuit. Mounts in panel module position (sin- tric smoke detector. ULC: FSV-951A-IV, FSV-951RA-IV.
gle-address-style) or in CHS2-M2 position. See DN-6860. VEP-A00-P-NTF: Intelligent aspiration smoke detector with LED dis-
UDACT-2: Universal Digital Alarm Communicator Transmitter, 636 play, 4 pipes, covers up to 21,520 square feet. See DN-61029. UL/
channel. See DN-60686. ULC Listed.
UZC-256: Programmable Universal Zone Coder provides positive VEP-A10-P-NTF: Intelligent aspiration smoke detector with LED and
non-interfering successive zone coding. Microprocessor-controlled, LCD display, 4 pipes, covers up to 21,520 square feet. See DN-
field-programmable from IBM®-compatible PCs (requires optional 61029. UL/ULC Listed.
programming kit). Up to 256 programmable codes. Mounts in BB- VEP-A00-1P-NTF: Intelligent aspiration smoke detector with LED
UZC or other compatible chassis (purchased separately). See DN- display, single pipe, covers up to 10,760 square feet. See DN-61029.
3404. UL/ULC Listed.
COMPATIBLE INTELLIGENT DEVICES VEU-A00-NTF: Intelligent aspiration smoke detector with LED dis-
NOTE: “A” suffix indicates ULC-Listed model. play, 4 pipes, covers up to 69,965 square feet. See DN-61034. UL/
ULC Listed.
FWSG Wireless SWIFT Gateway: Addressable gateway supports
wireless SLC devices. Not appropriate for ULC applications. See VEU-A10-NTF: Intelligent aspiration smoke detector with LED and
DN-60820. LCD display, 4 pipes, covers up to 69,965 square feet. See DN-
61034. UL/ULC Listed.
FCO-951/-IV FlashScan, Addressable intelligent multi-criteria smoke
sensors, photo, carbon monoxide, fixed temperature heat detector VEA-040-A00-NTF: Intelligent aspiration with LED display, 40 point-
and infra-red (IR). ULC: FCO-951A/-IV addressable detection points. Covers 36,000 square feet. See DN-
61036. UL/ULC Listed.
FPC-951. FlashScan, Combined photoelectric and carbon monoxide
sensor. ULC: FPC-951A. VEA-040-A10-NTF: Intelligent aspiration with LED and LCD display,
40 point-addressable detection points. Covers 36,000 square feet.
FSCO-951. FlashScan, Addressable carbon monoxide sensor. See DN-61036. UL/ULC Listed.
ULC: FSCO-951A.
DNR: InnovairFlex low-flow non-relay duct-detector housing. ULC:
FPTI-951, FPTI-951-IV: Addressable intelligent multi-criteria photo- DNRA. (Order FSP-951R(A) separately.) See DN-60429.
electric, thermal and IR sensors. ULC: FPTI-951A, FPTI-951A-IV.
DNRW: Same as above with NEMA-4 rating, watertight. See DN-
FS-OSI-RIAddressable intelligent single-ended beam smoke detec- 60429.
tor. ULC: FS-OSI-RIA.
B224RB-WH: White, low-profile relay base. See DN-60054. ULC:
FSP-951: White, low-profile intelligent photoelectric sensor, B224RBA-WH.
FlashScan only. ULC: FSP-951A.
B224RB-IV: Ivory, plug-in System Sensor relay base. ULC:
FSP-951-IV: Ivory, low-profile intelligent photoelectric sensor. B224RBA-IV.
ULC: FSP-951A-IV
B224BI-WH: White, isolator base for low-profile detectors. See DN-
FSP-951T: White, same as FSP-951 but includes a built-in 135°F 60054. ULC: B224BIA-WH.
(57°C) fixed-temperature thermal device. FlashScan only.
ULC: FSP-951TA. B224BI-IV: Ivory isolator detector base. ULC: B224BIA-IV.
FSP-951T-IV: Ivory, same as FSP-951T but includes a built-in 135°F B300-6: White, standard flanged low-profile mounting base. (For 10-
(57°C) fixed-temperature thermal device. ULC: FSP-951TA-IV. pack order B300-6-BP.) ULC: B300A-6.
FSP-951R: White, low-profile intelligent photoelectric sensor, remote B300-6-IV: Ivory, standard flanged low-profile mounting base. ULC:
test capable. For use with DNR/DNRW. FlashScan only. ULC: FSP- B300A-6-IV.
95RA B501-WHITE: European-style, 4" (10.16 cm) base. See DN-60054.
FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, (For 10-pack order B501-WHITE-BP.) UL/ULC listed.
remote test capable. FlashScan only. ULC: FSP-95RA-IV, for use B501-BL: Black, 4” standard European flangeless mounting base.
with DNRA. UL/ULC listed.
FST-951: White, low-profile intelligent 135°F fixed thermal sensor, B501-IV: Ivory color, 4” standard European flangeless mounting
FlashScan only. Must be mounted to one of the bases listed below. base. UL/ULC listed.
ULC: FST-951A. See DN-60975. B200S-WH: White, intelligent programmable sounder base, capable
FST-951-IV: Ivory, low-profile intelligent 135°F fixed thermal sensor, of producing a variety of tone patterns including ANSI Temporal 3.
FlashScan and CLIP. Must be mounted to one of the bases listed Compatible with synchronization protocol. See DN-60054. ULC:
below. ULC: FST-951A-IV. B200SA-WH.
FST-951R: White, low-profile intelligent rate-of-rise thermal sensor, B200S-IV: Ivory intelligent, programmable sounder base. ULC:
FlashScan only. Must be mounted to one of the bases listed below. B200SA-IV.
ULC: FST-951A B200SCOA-WH: White intelligent, programmable sounder base in
FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, English/French (required in Canada for ULC applications with CO
remote test capable. FlashScan only. ULC: FSP-95RA-IV, for use detectors. Based on B200SA. ULC listed.
with DNRA.

Page 6 of 9 — DN-7111:N • 12/20/2020


B200SCOA-IV: Ivory intelligent, programmable sounder base in CHS-BH1: Battery chassis; holds two 12.0 AH batteries. Mounts
English/French (required in Canada for ULC applications with CO one the left side of DAA2 chassis. See DN-7046.
detectors. Based on B200SA. ULC listed. CA-1: Chassis, occupies one tier of a CAB-4 Series enclosure. The
B200S-LF-WH: White, low-frequency version of B200S. See DN- left side accommodates one DVC-EM and a DVC-KD (optional); and
60054. the right side houses a CMIC-1 microphone and its well (optional).
B200S-LF-IV: Ivory, low-frequency version of B200S. See DN-7045.
B200SR-WH: White intelligent programmable sounder base, Tem- CA-2: Chassis assembly, occupies two tiers of a CAB-4 Series
poral 3 or Continuous tone. For retrofit installations replacing enclosure. The left side accommodates one DVC-EM mounted on a
B501BH series bases. See DN-60054. ULC: B200SRA-WH. half-chassis and one NCA-2 mounted on a half-chassis. The right
side houses a microphone/handset well. The CA-2 assembly
B200SR-IV: Ivory intelligent programmable sounder base, Temporal includes CMIC-1 microphone. ADDR Series doors with two-tier visi-
3 or Continuous tone. For retrofit installations replacing B501BH bility are available for use with the CA-2 configuration: ADDR-B4,
series bases. ULC: B200SRA-IV. ADDR-C4, ADDR-D4 (below).
B200SR-LF-WH: White, low-frequency version of B200SR. See DN- CFFT-1: Chassis to mount firefighter’s telephone and one ACS
60054. annunciator in a CAB-4 row. Includes TELH-1 firefighter’s handset
B200SR-LF-IV: Ivory, low-frequency version of B200SR. for the DVC-EM, chassis, phone well and mounting hardware. Order
FMM-1(A): FlashScan monitor module. See DN-6720. DP-CFFT dress panel separately.
FDM-1(A): FlashScan dual monitor module. See DN-6720. DP-CFFT: CFFT-1 dress panel. Requires BMP-1 if no ACS annunci-
ator is installed.
FZM-1(A): FlashScan two-wire detector monitor module. See DN-
6720. ADDR-B4*: Two-tier-sized door designed for use with the CA-2
chassis configuration. ADDR Series doors are similar to CAB-4
FMM-101(A): FlashScan miniature monitor module. See DN-6720.
Series “DR” doors, but a clear window space exposes the top two
FTM-1(A): Firephone Telephone Module connects a remote fire- tiers of the CAB-4 enclosure. Use an SBB-B4 backbox with the
fighter telephone to a centralized telephone console. Reports status ADDR-B4. See DN-7045, DN-6857.
to panel. Wiring to jacks and handsets is supervised. See DN-6989.
ADDR-C4*: Three-tier-sized door, designed for use with the CA-2
FCM-1(A): FlashScan control module. See DN-6720. chassis configuration. ADDR Series doors are similar to CAB-4
FCM-1-REL(A): FlashScan releasing control module. See DN- Series “DR” doors, but a clear window space exposes the top two
60390. tiers of the CAB-4 enclosure. Use an SBB-C4 backbox with the
ADDR-C4. See DN-7045, DN-6857.
FRM-1(A): FlashScan relay module. See DN-6720.
ADDR-D4*: Four-tier-sized door designed for use with the CA-2
FDRM-1(A): FlashScan dual monitor/dual relay module. See DN-
chassis configuration. ADDR Series doors are similar to CAB-4
60709.
Series “DR” doors, but a clear window space exposes the top two
NBG-12LX: Manual pull station, addressable. See DN-6726. tiers of the CAB-4 enclosure. Use an SBB-D4 backbox with the
N-MPS series: Manual pull stations, addressable and conventional. ADDR-D4. See DN-7045, DN-6857.
For use in Canada only. See DN-5497 and DN-60629. * Note: Use ADDR-B4/C4/D4 when CA-2 chassis is installed in top
ISO-X(A): Isolator module. See DN-2243. two rows with NCA-2 or BP-CA2. Use standard door when CA-2 is
ISO-6(A): Six fault isolator module. See DN-60844. not installed in top two rows. For additional configuration information,
see the DVC application guide on http://esd.notifier.com.
XP6-C(A): FlashScan six-circuit supervised control module. See
DN-6924. DPA-1: Dress panel, used with the CA-1 chassis when configured
with a DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
XP6-MA(A): FlashScan six-zone interface module; connects intelli-
gent alarm system to two-wire conventional detection zone. See DN- DPA-2B: Dress panel used with CA-2 chassis assembly.
6925. VP-2B: Dress panel, required when CA-2 chassis is installed in the
XP6-R(A): FlashScan six-relay (Form-C) control module. See DN- top two cabinet rows.
6926. DPA-1A4: Dress panel, used with the CA-1 chassis when the CMIC-
XP10-M(A): FlashScan ten-input monitor module. See DN-6923. 1 is not used. Provides mounting options on right two bays for two
ACS annunciators, or for blank plates. See DN-7045.
ENCLOSURES, CHASSIS, AND DRESS PLATES BP-CA2: Blank plate for CA-2 chassis.
CAB-4 Series Enclosure: NFS2-640 mounts in a standard CAB-4 SEISKIT-CAB: Seismic mounting kit. Required for seismic-certified
Series enclosure (available in four sizes, “A” through “D”). Backbox applications with NFS2-640 and other equipment mounted in CAB-4
and door ordered seperately; requires BP2-4 battery plate. A trim Series Enclosures. Includes battery bracket for two 26 AH batteries.
ring option is available for semi-flush mounting. See DN-6857.
SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery bracket
EQ Series Cabinets: EQ series cabinets will house amplifiers, for two 55 AH batteries.
power supplies, battery chargers and control modules. EQ cabinets
are available in three sizes, “B” through “D”. See DN-60229. . BACKBOXES
CAB-BM Marine System: Protects equipment in shipboard and NOTE: “C” suffix indicates ULC-Listed model.
waterfront applications. Also order BB-MB for systems using 100 AH ABF-1B(C) Annunciator Flush Box.
batteries. For a full list of required and optional equipment, see DN-
ABF-1DB(C) Annunciator Flush Box with Door.
60688.
ABF-2B Annunciator Flush Box
CHS-4: Chassis for mounting up to four APS-6Rs.
ABF-2DB/C Annunciator Flush Box with Door
CHS-4L: Low-profile four-position Chassis. Mounts two AA-30
amplifiers or one AMG-E and one AA-30. ABF-4B Annunciator Flush Box
DP-1B: Blank dress panel. Provides dead-front panel for unused ABS-1TB(C) Annunciator Surface Box
tiers; covers DAA2/DAX series or AA-series amplifier. ABS-1B(C) Annunciator Surface Box
NFS-LBB: Battery Box (required for batteries larger than 26 AH). ABS-2B Annunciator Surface Box
NFS-LBBR: Same as above but red.

DN-7111:N • 12/20/2020 — Page 7 of 9


ABS-2D(C) Annunciator Surface Box
ABS-4D(C) Annunciator Surface Box
BB-UZC: Backbox for housing the UZC-256 in applications where
the UZC-256 will not fit in panel enclosure. Black; for red, order BB-
UZC-R.
OTHER OPTIONS
411: Slave digital alarm communicator. See DN-6619.
411UDAC: Digital alarm communicator. See DN-6746.
IPDACT-2/2UD, IPDACT Internet Monitoring Module: Connects to
primary and secondary DACT telephone output ports for internet
communications over customer-provided Ethernet connection.
Requires compatible Teldat VisorALARM Central Station Receiver.
Can use DHCP or static IP. See DN-60408.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For mounting
an IPDACT-2/2UD onto the panel chassis or CHS-4 series chassis.
Use IPENC for external mounting applications.
IPSPLT: Y-adapter option allow connection of both panel dialer out-
puts to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT mounting
bracket; Red. For Black order IPENC-B.
HWF2V-COM: LTE Digital Cellular Fire Alarm Communicator and
Internet Panel, Verizon LTE / IP. Provides selectable configurable
paths: cellular only, IP only, or IP primary with cellular backup. Con-
nects to the primary and secondary ports of a DACT. See DH-62010.
(For Canadian applications order IPGSM-4GC. See DH-60771.)
HWF2A-COM: LTE Digital Cellular Fire Alarm Communicator and
Internet Panel, AT&T LTE / IP. Provides selectable configurable
paths: cellular only, IP only, or IP primary with cellular backup. Con-
nects to the primary and secondary ports of a DACT. (For Canadian
applications order IPGSM-4GC. See DH-60771.)
NOTE: For other options including compatibility with retrofit equipment,
refer to the panel's installation manual, the SLC manual, and the Device
Compatibility Document.

Page 8 of 9 — DN-7111:N • 12/20/2020


SPECIFICATIONS

SYSTEM CAPACITY is recommended that this system and its peripherals be installed in
• Intelligent Signaling Line Circuits .....................1 expandable to 2 an environment with a normal room temperature of 15 – 27°C/60 –
• Intelligent detectors ................................................. 159 per loop 80°F.
• Addressable monitor/control modules ...................... 159 per loop AGENCY LISTINGS AND APPROVALS
• Programmable software zones ................................................. 99 The listings and approvals below apply to the basic NFS2-640 con-
• Special programming zones ..................................................... 14 trol panel. In some cases, certain modules may not be listed by cer-
• LCD annunciators per CPU2-640/-640E tain approval agencies, or listing may be in process. Consult factory
and NCA-2 (observe power) ..................................................... 32 for latest listing status.
• ACS annunciators per
• UL/ULC Listed: S635.
CPU2-640/-640E .................................. 32 addresses x 64 points
• ULC Listed: S527-11
• ACS annunciators per NCA-2...... 32 addresses x 64 or 96 points
• FM Approved.
NOTE: The NCA-2 supports up to 96 annunciator address points per
ACM-24AT/-48A. • MEA: 128-07-E.
• Fire Dept. of New York: #6212.
ELECTRICAL SPECIFICATIONS • CSFM: 7165-0028:0243.
• Primary input power: • City of Chicago.
– CPU2-640 board: 120 VAC, 50/60 Hz, 5.0 A. • City and County of Denver.
– CPU2-640E board: 220/240 VAC, 50/60 Hz, 2.5 A. • CCCF listed.
• Current draw (standby/alarm): Marine Applications: Marine approved systems must be configured
– CPU2-640(E) board: 0.250 A. Add 0.035 A for each NAC in using components itemized in this document. (See Main System
use. Components, in “Product Line Information.) Specific connections
– KDM-R2: 0.100 A. and requirements for those components are described in the instal-
lation document, PN 54756. When these requirements are followed,
– LEM-320: 0.100 A. systems are approved by the following agencies:
• Total output 24 V power: 6.0 A in alarm.
• US Coast Guard 161.002/50/0, 161.002/55/0 (Standard 46 CFR
NOTE: The power supply has a total of 6.0 A. of available power. This is and 161.002).
shared by all internal circuits. See Installation Manual for a complete cur-
rent draw calculation sheet. • Lloyd's Register 11/600013 (ENV 3 category).
• American Bureau of Shipping (ABS) Type Approval.
• Standard notification circuits (4): 1.5 A each.
NOTE: For information on marine applications, see DN-60688.
• Resettable regulated 24V power: 1.25 A.
• Two non-resettable regulated 24V power outputs: STANDARDS
– 1.25 A. The NFS2-640 complies with the following UL Standards and NFPA
– 0.50 A. 72, International Building Code (IBC), and California Building Code
• Non-resettable 5V power: 0.15 A. (CBC) Fire Alarm Systems requirements:
• Battery charger range: 18 AH – 200 AH. Use separate cabinet for • UL 864, 9th Edition (Fire).
batteries over 26 AH. • UL 1076 (Burglary).
• Float rate: 27.6 V. • UL 2572 (Mass Notification Systems). (NFS2-640 version 20 or
higher.)
CABINET SPECIFICATIONS
• ULC-S527-11 Standard for the Installation of Fire Alarm Sys-
• Systems can be installed in CAB-4 Series cabinets (four sizes tems.
with various door options, see DN-6857). Requires BP2-4 Battery
• LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi-
Plate.
sory).
SHIPPING WEIGHT • AUXILIARY (Automatic, Manual and Waterflow) (requires TM-4).
• CPU2-640/-640: 14.3 lb (6.49 kg). • REMOTE STATION (Automatic, Manual, Waterflow and Sprinkler
• CPU2-640/-640E: 14.55 lb (6.60 kg). Supervisory) (requires TM-4).
• PROPRIETARY (Automatic, Manual and Waterflow).
TEMPERATURE AND HUMIDITY RANGES Not applicable for FM.
This system meets NFPA requirements for operation at 0 – 49°C/32 • EMERGENCY VOICE/ALARM.
– 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at
• OT, PSDN (Other Technologies, Packet-switched Data Network).
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's
standby batteries and the electronic components may be adversely • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
affected by extreme temperature ranges and humidity. Therefore, it • CBC 2007 (Seismic).

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

NOTI•FIRE•NET™, ONYXWorks™, and SWIFT™ are all trademarks of and FlashS-


NOTIFIER can®, NOTIFIER®, ONYX®, VeriFire® Tools, and VIEW® are all registered trademarks of
Honeywell International Inc.
12 Clintonville Road ©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this docu-
Northford, CT 06472 ment is strictly prohibited.

203.484.7161
www.notifier.com Country of Origin: USA

You might also like