NFS2 3030 Data Sheet DN - 7070
NFS2 3030 Data Sheet DN - 7070
NFS2 3030 Data Sheet DN - 7070
NFS2-3030
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels
General
The NFS2-3030 is an intelligent Fire Alarm Control Panel
designed for medium- to large-scale facilities. Fire emergency
detection and evacuation are extremely critical to life safety,
and the NFS2-3030 is ideally suited for these applications. The
NFS2-3030 is part of the ONYX Series of products from
NOTIFIER. The NFS2-3030 is ideal for virtually any application
because it features a modular design that is configured per
project requirements. With one to ten Signaling Line Circuits
(SLCs), the NFS2-3030 supports up to 3,180 intelligent
addressable devices.
Information is critical to fire evacuation personnel, and the
NFS2-3030s large 640-character Liquid Crystal Display (LCD)
presents vital information to operators concerning a fire situation, fire progression, and evacuation details.
A host of other options are available, including single- or multichannel voice; firefighters telephone; LED, LCD, or PC-based
graphic annunciators; fire or integration networking; advanced
detection products for challenging environments, and many
additional options.
7070covg.jpg
Features
Certified for seismic applications when used with the appropriate seismic mounting kit.
One to ten isolated intelligent Signaling Line Circuits (SLC)
Style 4, 6 or 7.
Up to 159 detectors and 159 modules per SLC, 318 devices
per loop/3,180 per FACP or network node. Detectors can be
any mix of ion, photo, laser photo, thermal, or multi-sensor
detectors; modules can be addressable pull stations, normally open contact devices, two-wire smoke, notification, or
relay modules.
Large 640-character LCD backlit display (16 lines x 40 characters) or display-less (a node on a network).
Network options:
High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC,
ONYXWorks, NFS-3030, NFS-640, and NCA).
Standard network for up to 103 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC,
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200,
AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes
when DVC is used in network paging.
Built-in Alarm, Trouble, Security, and Supervisory relays.
VeriFire Tools online/offline program option.
Application code is saved in Flash memory.
With built-in Degraded Mode operation, the system is capable of general alarm if a fire alarm condition is present even
if the CPU fails.
Weekly Occupancy Schedules allow changing sensitivity by
time of day and day of week.
EIA-485 annunciators, including custom graphics.
History file with 4000-event capacity in nonvolatile memory,
plus separate 1000-event alarm-only file.
Advanced history filters allow sorting by event, time, date,
or address.
Alarm Verification selection per point, with tally.
FAPT-851
ACCLIMATE
PLUS
INTELLIGENT MULTI-SENSOR
LOW-PROFILE
FSC-851 INTELLIQUAD
ADVANCED MULTI-CRITERIA DETECTOR
Detects all four major elements of a fire (smoke, heat, CO,
and flame).
Automatic drift compensation of smoke sensor and CO cell.
High nuisance-alarm immunity.
Six sensitivity levels.
FAPT-851
FSL-751
FSP-851
...etc.
XP6/10 I/O
Modules
7070blok.wmf
CPU2-3030D
display or
CPU2-3030ND
NFS2-3030
Shown in CAB-C4 with display
DVC audio in CA-1 in second tier
PRN Series
Printer
NOTE: CPU2-3030 firmware version 14.0 (and higher) can support LCD-160 on the RDP port, or LCD2-80/LCD-80 in terminal mode,
but not both at the same time.
RELEASING FEATURES
FlashScan Exclusive
World-Leading Detector Protocol
At the heart of the NFS2-3030 is a set of detection devices and
device protocol FlashScan (U.S. Patent 5,539,389). FlashScan is an all-digital protocol that gives superior precision and
high noise immunity.
As well as giving quick identification of an active input device,
this new protocol can also activate many output devices in a
fraction of the time required by competitive protocols. This high
speed also allows the NFS2-3030 to have the largest device
per loop capacity in the industry 318 points yet every
input and output device is sampled in less than two seconds.
The microprocessor-based FlashScan detectors have bicolor
LEDs that can be coded to provide diagnostic information,
such as device address during Walk Test.
Maintenance Warnings. When the drift compensation performed for a detector reaches a certain level, the performance
of the detector may be compromised, and special warnings
are given. There are three warning levels: (1) Low Chamber
value; (2) Maintenance Alert, indicative of dust accumulation
that is near but below the allowed limit; (3) Maintenance
Urgent, indicative of dust accumulation above the allowed limit.
Sensitivity Adjust. Nine sensitivity levels are provided for
alarm detection. These levels can be set manually, or can
change automatically between day and night. Nine levels of
pre-alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre-alarm operation can be latching or
self-restoring, and can be used to activate special control functions.
Self-Optimizing Pre-Alarm. Each detector may be set for
Self-Optimizing pre-alarm. In this special mode, the detector
learns its normal environment, measuring the peak analog
readings over a long period of time, and setting the pre-alarm
level just above these normal peaks.
Cooperating Multi-Detector Sensing. A patented feature of
ONYX Intelligent Sensing is the ability of a smoke sensor to
consider readings from nearby sensors in making alarm or
pre-alarm decisions. Without statistical sacrifice in the ability to
resist false alarms, it allows a sensor to increase its sensitivity
to actual smoke by a factor of almost two to one.
Ordering Information
CONFIGURATION GUIDELINES
Stand-alone and network systems require a main display. On
single-CPU systems (one NFS2-3030D), the display option is
the CPU2-3030D. On network systems (two or more networked fire panel nodes), at least one NCA-2, NCS, or ONYXWorks annunciation device is required. Options listed as
follows.
CPU2-3030D: NFS2-3030 Primary Display. CPU2-3030D
ships with keypad/display installed; includes 640-character
backlit LCD display, QWERTY programming and control keypad. CPU2-3030 is a central processing unit and requires an
AMPS-24(E) power supply.
CPU2-3030ND: CPU2-3030 without display.
VeriFire-TCD: VeriFire Tools programming software for
ONYX series products and DVC. Includes local panel connection cable. Programming PC requires a serial port connection.
See DN-6871.
LCM-320: Loop Control Module. Adds SLCs to 3030; 3030
supports up to 5 LCM-320s and 5 LEM-320s. See DN-6881.
LEM-320: Loop Expander Module. Expands each LCM used
on the 3030. See DN-6881.
AUDIO OPTIONS
NOTE: See Enclosures, Chassis, and Dress Plates on page 5 for
mounting harware.
NETWORKING OPTIONS
DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
UZC-256: Programmable Universal Zone Coder provides positive non-interfering successive zone coding. Microprocessorcontrolled, field-programmable from IBM-compatible PCs
(requires optional programming kit). Mounts on a CHS-4
series chassis within NFS2-3030.
FSB-200S: Intelligent beam smoke detector with integral sensitivity test. See DN-6985.
BB-100: Backbox for batteries and power supplies. The BB100 is used to mount up to two 100-AH batteries and power
supply, if needed. 30" (76.20 cm) wide x 25" (63.50 cm) high x
7.5" (19.05 cm) deep; depth includes door.
SEISKIT-CAB: Seismic mounting kit. Required for seismiccertified applications with NFS2-3030, NFS2-640, and BB-26.
Includes battery bracket for two 26 AH batteries.
OTHER OPTIONS
411: Slave digital alarm communicator. See DN-6619.
411UDAC: Digital alarm communicator. See DN-6746.
IPDACT-2, IPDACT Internet Monitoring Module: Connects
to primary and secondary DACT telephone output ports for
internet communications over customer-provided ethernet
connection. Requires compatible Teldat VisorALARM Central
Station Receiver. Can use DHCP or static IP. See DN-60408.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For
mounting an IPDACT-2/2UD onto the panel chassis or CHS-4
series chassis. Use IPENC for external mounting applications.
IPSPLT: Y-adaptor option allow connection of both panel dialer
outputs to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT
mounting bracket; Red; for black, order IPENC-B.
IPGSM-COM: Internet and Digital Cellular Fire Communicator
Panel. Uses internet as primary with dual GSM technology as
backup. Connects to the primary and secondary ports of a
DACT. See DN-60656.
NOTE: For other options including compatibility with retrofit equipment, refer to the panel's installation manual, the SLC manual, and
the Device Compatibility Document.
SYSTEM SPECIFICATIONS
System Capacity
Specifications
Primary input power:
AMPS-24: 110-120 VAC, 50/60 Hz, 4.5 A maximum.
AMPS-24E: 240 VAC, 50/60 Hz, 2.25 A maximum.
DC output:
Main 24 VDC: Up to 5.0 A
Aux 24 VDC: Up to 5.0 A
5 VDC: Up to 0.15 A.
NOTE: For details of DC output values, see manual 51907.
Battery charger range: 7 AH 200 AH. Use separate cabinet for batteries over 26 AH.
Float Rate: 27.6 V.
Shipping Weight
CPU2-3030D: 5.95 lb (2.70 kg).
CPU2-3030ND: 2.90 lb (1.32 kg).
UL Listed: S635
ULC Listed: S635
MEA: 232-06-E
FDNY: COA#6065
CSFM: 7165-0028:0224 (Commercial)
FM Approved
FM6320 Approved. Class 6320 for Gas Detection
City of Chicago
City of Denver
PSB Corporation
CCCF listed
Fire Services Department (Hong Kong)
Standards
The NFS2-3030 complies with the following UL Standards and
NFPA 72, IBC, and CBC Fire Alarm Systems requirements:
UL 864 (Fire).
UL 1076 (Burglary).
LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
AUXILIARY (Automatic, Manual and Waterflow) (requires
TM-4).
REMOTE STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires TM-4).
PROPRIETARY (Automatic, Manual, Waterflow and Sprinkler Supervisory). Not applicable for FM.
EMERGENCY VOICE/ALARM.
OT, PSDN (Other Technologies, Packet-switched Data Network).
IBC 2000, IBC 2003, IBC 2006, IBC2009 (Seismic).
CBC 2007 (Seismic).
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 8 of 8 DN-7070:G1 9/7/2011