ES 1000X FACP Datasheet
ES 1000X FACP Datasheet
ES 1000X FACP Datasheet
ES-1000X Series
Intelligent Addressable FACP
with 954 Point Capacity
Addressable Fire Alarm Control Panels
General
The Fire•Lite ES-1000X, ES-1000XC, and ES-1000XI are intelligent
addressable Fire Alarm Control Panels (FACP) with a pre-installed
loop card. The ES-1000X control panels support up to 318 address-
able devices per Signaling Line Circuit (SLC) (Digital Communication
Loop) (DCL) loop (159 detectors and 159 modules) with a maximum of
three loops. With an extensive list of powerful features, the ES-1000X
programs just like Fire•Lite’s other addressable products while offering
expanded support for up to 954 devices for larger and more complex
installations.
The ES-1000X and ES-1000XC feature a pre-installed IPOTS-COM
communicator which transmits system status (alarms, troubles, AC
loss, etc.) to a Central Station via the public switched telephone net-
work. The communicator’s internet monitoring capability sends alarm
signals over the Internet saving the monthly cost of two dedicated
business telephone lines. Although not required, the secondary tele-
phone line may be retained providing backup communication over the
public switched telephone line. Optional cellular reporting is available
using the CLSS Pathway or GSM Communicators.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can be
uploaded/downloaded via the panel’s USB port and thumb drive. This
allows download of the entire program or upload of the entire program,
• Alarm verification selection per detector point
history file, walk-test data, current status and system voltages.
• Maintenance alert warns when smoke detector dust accumulation
The power supply and all electronics are contained on a circuit board is excessive
supported on a new quick install chassis and housed in a metal cabi-
net. Available accessories include local and remote upload/download • One-person audible or silent walk test with walk-test log and print-
software, remote annunciators, and reverse polarity/city box transmit- out
ter (4XTMF). • System alarm verification selection per detector point
• PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72
Features compliant)
• Listed to UL Standard 864, 10th edition • Up to 16 ANN-Bus annunciators- 8 per each ANN-Bus
• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- • Remote Acknowledge, Alarm Silence, Reset and Drill via address-
phone Service) Central Station Communicator (ES-1000X/C) able modules or remote annunciator
• Optional CLSS or GSM Central Station Communicators • Upload/Download of program and data via USB with optional
FS-Tools Programming Utility
• Compatible with SWIFT® wireless devices
• Four independently programmable, built-in, Class A or Class B SLC(DCL) COMMUNICATION LOOP
NAC circuits • LiteSpeed™ polling protocol for faster SLC (DCL) response time
• Selectable strobe synchronization for System Sensor®, Whee- • SLC (DCL) operates up to 10,000 ft. (3,000 m) in LiteSpeed mode
lock®, and Gentex® devices with twisted, unshielded wire
• Four programmable function keys for ease of maintenance • Single addressable SLC (DCL) loop, expandable up to three, which
• Two programmable relays and one fixed trouble relay meets NFPA Class B, Class A, and Class X requirements
• Built-in Programmer • Two additional SLC (DCL) loops available using the SLC-3LS Loop
Expander Cards
• Integral 80-character LCD display with backlighting
• 318 addressable device capacity (159 addressable detectors and
• Real-time clock/calendar with automatic daylight savings control
modules) per SLC (DCL) loop.
• History file with 1,000 event capacity
• Compatible with Fire•Lite’s addressable devices (refer to the SLC
• Auto-programming (learn mode) reduces installation time. Reports Wiring Manual)
two devices set to the same address
NOTIFICATION APPLIANCE CIRCUITS (NACS)
• Addressable sounder base
• Four independently programmable output circuits. Circuits can be
• Multi-criteria detector (smoke, heat, CO) with programmable
configured for Class A and Class B outputs
response
• Silence Inhibit and Autosilence timer options
• Control module delay timer
• Continuous, March Time, Temporal, or California code for main cir-
• Automatic detector sensitivity testing (NFPA 72 compliant)
cuit board NACs with two-stage capability
• Automatic device type-code verification
• Selectable strobe synchronization per NAC
• Point trouble identification
• 3 A special application, 300mA regulated, total power for NACs
• Waterflow selection per module point
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: USA
www.firelite.com