ES 1000X FACP Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DF-60961:A

ES-1000X Series
Intelligent Addressable FACP
with 954 Point Capacity
Addressable Fire Alarm Control Panels

General
The Fire•Lite ES-1000X, ES-1000XC, and ES-1000XI are intelligent
addressable Fire Alarm Control Panels (FACP) with a pre-installed
loop card. The ES-1000X control panels support up to 318 address-
able devices per Signaling Line Circuit (SLC) (Digital Communication
Loop) (DCL) loop (159 detectors and 159 modules) with a maximum of
three loops. With an extensive list of powerful features, the ES-1000X
programs just like Fire•Lite’s other addressable products while offering
expanded support for up to 954 devices for larger and more complex
installations.
The ES-1000X and ES-1000XC feature a pre-installed IPOTS-COM
communicator which transmits system status (alarms, troubles, AC
loss, etc.) to a Central Station via the public switched telephone net-
work. The communicator’s internet monitoring capability sends alarm
signals over the Internet saving the monthly cost of two dedicated
business telephone lines. Although not required, the secondary tele-
phone line may be retained providing backup communication over the
public switched telephone line. Optional cellular reporting is available
using the CLSS Pathway or GSM Communicators.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can be
uploaded/downloaded via the panel’s USB port and thumb drive. This
allows download of the entire program or upload of the entire program,
• Alarm verification selection per detector point
history file, walk-test data, current status and system voltages.
• Maintenance alert warns when smoke detector dust accumulation
The power supply and all electronics are contained on a circuit board is excessive
supported on a new quick install chassis and housed in a metal cabi-
net. Available accessories include local and remote upload/download • One-person audible or silent walk test with walk-test log and print-
software, remote annunciators, and reverse polarity/city box transmit- out
ter (4XTMF). • System alarm verification selection per detector point
• PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72
Features compliant)
• Listed to UL Standard 864, 10th edition • Up to 16 ANN-Bus annunciators- 8 per each ANN-Bus
• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- • Remote Acknowledge, Alarm Silence, Reset and Drill via address-
phone Service) Central Station Communicator (ES-1000X/C) able modules or remote annunciator
• Optional CLSS or GSM Central Station Communicators • Upload/Download of program and data via USB with optional
FS-Tools Programming Utility
• Compatible with SWIFT® wireless devices
• Four independently programmable, built-in, Class A or Class B SLC(DCL) COMMUNICATION LOOP
NAC circuits • LiteSpeed™ polling protocol for faster SLC (DCL) response time
• Selectable strobe synchronization for System Sensor®, Whee- • SLC (DCL) operates up to 10,000 ft. (3,000 m) in LiteSpeed mode
lock®, and Gentex® devices with twisted, unshielded wire
• Four programmable function keys for ease of maintenance • Single addressable SLC (DCL) loop, expandable up to three, which
• Two programmable relays and one fixed trouble relay meets NFPA Class B, Class A, and Class X requirements
• Built-in Programmer • Two additional SLC (DCL) loops available using the SLC-3LS Loop
Expander Cards
• Integral 80-character LCD display with backlighting
• 318 addressable device capacity (159 addressable detectors and
• Real-time clock/calendar with automatic daylight savings control
modules) per SLC (DCL) loop.
• History file with 1,000 event capacity
• Compatible with Fire•Lite’s addressable devices (refer to the SLC
• Auto-programming (learn mode) reduces installation time. Reports Wiring Manual)
two devices set to the same address
NOTIFICATION APPLIANCE CIRCUITS (NACS)
• Addressable sounder base
• Four independently programmable output circuits. Circuits can be
• Multi-criteria detector (smoke, heat, CO) with programmable
configured for Class A and Class B outputs
response
• Silence Inhibit and Autosilence timer options
• Control module delay timer
• Continuous, March Time, Temporal, or California code for main cir-
• Automatic detector sensitivity testing (NFPA 72 compliant)
cuit board NACs with two-stage capability
• Automatic device type-code verification
• Selectable strobe synchronization per NAC
• Point trouble identification
• 3 A special application, 300mA regulated, total power for NACs
• Waterflow selection per module point

DF-60961:A • 7/18/2023 — Page 1 of 4


NOTE: Maximum or total 24VDC system power shared between all NAC FS-Tools: Programming software for Windows-based PC computer.
circuits and Auxiliary Power circuits is 8.0 A Available for download at www.firelite.com.
PROGRAMMING AND SOFTWARE BB-2F: Optional cabinet for one or two modules.
• Auto-programming (learn mode) reduces installation time BB-6F: Optional cabinet for up to six modules mounted on CHS-6
• Custom English labels (per point) may be manually entered or chassis.
selected from an internal library file BB-26: Battery backbox, holds up to two 25 AH batteries and
• Two programmable Form-C relay outputs CHG-75.
• 256 software zones BB-55F: Battery box, houses two 55 AH batteries
• Continuous fire protection during online programming CHS-6: Chassis, mounts up to six multi-modules in a BB-6F cabinet.
• Program Check automatically catches common errors not linked to
CHG-75: Battery charger for lead-acid batteries with a rating of 25 to
any zone or input point
75 AH.
• OFFLINE PROGRAMMING: Create the entire program in your
office using FS-Tools, a Windows®-based software package, and CHG-120F: Remote battery charging system for lead-acid batteries
upload/download system programming locally. Offline programming with a rating of 55 to 120 AH. Requires additional BB-55F for mount-
requires an ethernet connection. FS-Tools is available on www.fire- ing.
lite.com. BAT Series: Batteries, see data sheet DF-52397.
PRN Series: UL listed compatible event printer. Uses tractor-fed
User interface paper.
LED INDICATORS OPTIONAL EQUIPMENT
• Fire Alarm (red) 4XTMF Reverse Polarity Transmitter Module: Provides a super-
• CO Alarm (yellow) vised output for local energy municipal box transmitter, alarm and trou-
• AC Power (green) ble. Includes a disable switch and disable trouble LED.
• Supervisory (yellow) FL-PS / HPF-PS Series Power Supplies: Optional NAC Expander
power supply with either 6 amps or 10 amps power.
• Trouble (yellow)
• Ground fault (yellow) COMPATIBLE ANNUNCIATORS
• Battery fault (yellow) ANN-80: Remote, red LCD annunciator mimics the information dis-
played on the FACP LCD display. Recommended wire type is un-
• Disabled (yellow)
shielded.
• Maintenance (yellow)
ANN-100: Remote LCD annunciator mimics the information displayed
• Communication (yellow)
on the FACP LCD display. Recommended wire type is un-shielded.
• Alarm Silenced (yellow) For use in FM applications only.
• F1-F4 Function Keys (yellow) ANN-I/O: LED Driver Module provides connections to a user supplied
KEYPAD graphic annunciator. (See DF-52430.)
• 16 key alpha-numeric pad ANN-LED: Annunciator Module provides three LEDs for each zone:
• Acknowledge Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF-
60241.)
• Alarm Silence
ANN-RLED: Provides alarm (red) indicators for up to 30 input zones
• Drill (Manual Evacuate)
or addressable points. (See DF-60241.)
• Reset (lamp test)
ANN-RLY: Relay Module provides 10 programmable Form-C relays.
• Four (4) programmable function keys Can be mounted inside the cabinet. (See DF-52431.)
ANN-S/PG: Serial/Parallel Printer Gateway module provides a con-
Product Line Information nection for a serial or parallel printer. (See DF-52429.)
ES-1000X: Addressable Fire Alarm Control Panel with one SLC loop.
Includes main circuit board with display, pre-installed communicator, ADDRESSABLE DEVICES
chassis with transformer, backbox with dress panel and door, plastic All feature a polling LED and rotary switches for addressing.
bag containing screws, cables, key, etc. SD365(A): Addressable low-profile photoelectric smoke detector. Lite-
ES-1000XC: Addressable Fire Alarm Control Panel with one DCL loop Speed only.
for Canadian applications. Includes main circuit board with display, SD365(A)-IV: Addressable low-profile photoelectric smoke detector.
pre-installed communicator, chassis with transformer, backbox with Ivory. LiteSpeed and CLIP mode.
dress panel and door, plastic bag containing screws, cables, key, etc. SD365T(A): Addressable low-profile photoelectric smoke detector
ES-1000XI: Addressable Fire Alarm Control Panel with one SLC loop. with thermal sensor. LiteSpeed only.
Includes main circuit board with display, chassis with transformer, SD365T(A)-IV: Addressable low-profile photoelectric smoke detector
backbox with dress panel and door, plastic bag containing screws, with thermal sensor. Ivory. LiteSpeed and CLIP mode.
cables, key, etc., manual.
SD365R(A): Remote test capable addressable photoelectric smoke
SLC-3LS: Optional loop expander card. Maximum 2 per panel. detector for use with DNR(W) duct detector housing. LiteSpeed only.
HW-AV-LTE-M: CLSS Dual-Path LTE Communicator with Dial Capture SD365R(A)-IV: Remote test capable addressable photoelectric smoke
Interface detector for use with DNR(W) duct detector housing. Ivory. LiteSpeed
and CLIP mode.
HW-TG7FS-A / HW-TG7S-V: CLSS-Enabled 5G /LTE-M Commercial
Fire Alarm Communicators for AT&T® and Verizon® SD365CO: Addressable, low-profile device that provides fire, heat,
and carbon monoxide (CO) detection, LiteSpeed only.
HW-TG7FE-A / HW-TG7FE-V: CLSS-Enabled 5G/LTE-M Dual Path
Commercial Fire Alarm Communicators for AT&T and Verizon SD365CO-IV: Addressable, low-profile device that provides fire, heat,
and carbon monoxide (CO) detection. Ivory. LiteSpeed and CLIP
HW-TG7FP-A / HW-TG7FP-V: CLSS-Enabled 5G/LTE-M Sole Path mode.
Commercial Fire Alarm Communicators for AT&T and Verizon H365(A): Low-profile 135°F fixed thermal sensor. LiteSpeed only.

Page 2 of 4 — DF-60961:A • 7/18/2023


H365(A)-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed MMF-300: Addressable Monitor Module for one zone of normally-open
and CLIP mode. dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box.
H365R(A): Low-profile, intelligent, rate-of-rise thermal sensor. Lite- Includes plastic cover plate and end-of-line resistor. Module may be
Speed only. configured for either a Class B or Class A IDC.
H365R(A)-IV: Low-profile, intelligent, rate-of-rise thermal sensor. MMF-300-10: Ten-input monitor module. Mount one or two modules in
Ivory. LiteSpeed and CLIP mode. a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chas-
H365HT(A): Low-profile intelligent 190°F/88°C fixed thermal sensor. sis in a BB-6F cabinet.
LiteSpeed only. MMF-301: Miniature version of MMF-300. Excludes LED and Class A
H365HT(A)-IV: Low-profile intelligent 190°F/88°C fixed thermal sen- wiring option. Connects with wire pigtails. May mount in device back-
sor. Ivory. LiteSpeed and CLIP mode. box.
D365PL: Low-flow non-relay duct-detector housing; includes SD365R. MMF-302: Similar to MMF-300. Addressable Monitor Module for one
Legacy Devices zone of conventional two-wire detectors. Requires resettable 24 VDC
power. Refer to the Device Compatibility Document for listed compati-
CP355(A): Addressable low-profile ionization smoke detector. ble devices and quantity limitation.
SD355(A): Addressable low-profile photoelectric smoke detector.
MMF-302-6: Six-zone interface module. Mount one or two modules in
SD355T(A): Addressable low-profile photoelectric smoke detector a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chas-
with thermal sensor. sis in a BB-6F cabinet.
SD355R(A): Remote test capable addressable photoelectric smoke SMB500: Used to mount all modules except the MMF-301 and M301.
detector for use with DNR(W) duct detector housing.
SD355CO: Addressable, low-profile device that provides fire, heat, SWIFT Wireless Devices
and carbon monoxide (CO) detection. W-GATE(A): LiteSpeed Wireless Gateway
H355(A): Fast-response, low-profile heat detector. W-SD355(A): LiteSpeed intelligent, wireless photo detector.
H355R(A): Fast-response, low-profile heat detector with rate-of-rise W-H355R(A): LiteSpeed intelligent wireless rate of rise (135°) heat
option. detector.
H355HT(A): Fast-response, low-profile heat detector that activates at W-SD355T(A): intelligent wireless photo/heat detector.
190°F/88°C. W-H355(A): LiteSpeed intelligent wireless fixed-temperature (135°)
AD355(A): Low-profile, intelligent, “Adapt” multi-sensor detector heat detector.
(B350LP base included). W-MMF(A): LiteSpeed Intelligent wireless monitor module.
B200S(A)(-WH)(-IV): Programmable, addressable sounder base. W-CRF(A): LiteSpeed Intelligent wireless relay module.
B200SR(A)(-WH)(-IV): Addressable sounder base. W-BG12LX(A): LiteSpeed Intelligent wireless pull station.
B200S-LF(-WH)(-IV): Programmable, addressable sounder base, low- WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: LiteSpeed Intelligent AV
frequency. bases.
B200SR-LF(-WH)(-IV): Addressable sounder base, low-frequency. W-USB: Wireless USB radio/antenna dongle that plugs into the USB
port of a PC running SWIFT Tools.
BEAM355: Intelligent beam smoke detector.
SWIFT Tools: Programming and diagnostic utility for the Wireless
BEAM355S: Intelligent beam smoke detector with integral sensitivity Gateway and devices. Available for download from firelite.com.
test.
NOTE: For more information on Compatible Addressable Devices for use
D355PL(A): InnovairFlex low-flow non-relay duct-detector housing; with the ES-1000X, see the following data sheets (document numbers):
includes SD355R. AD355(A) (DF-52386), AD365(A) (DF-62007), BG-12LX (DF-52013),
DNR(A): InnovairFlex low-flow non-relay duct-detector housing. CMF-300-6(A) (DF-52365), CRF-300-6(A) (DF-52374), CMF(A)/CRF(A)
(Order SD355R(A)/SD365R(A) separately.) Series (DF-52130), CP355(A) (DF-52383), H355(A) Series (DF-52385),
H365(A) Series (DF-61011), I300(A) (DF-52389), ISO-6(A) (DF-60485),
DNRW: InnovairFlex low-flow non-relay duct-detector housing, with MMF-300(A) Series/MDF-300(A) (DF-52121), MMF-300-10(A) (DF-
NEMA-4 rating. Watertight. (Order SD355R(A)/SD365R(A) sepa- 52347), MMF-302-6(A) (DF-52356), SD355(A)/SD355T(A) (DF-52384),
rately.) SD365(A) Series (DF-61010), SD355CO (DF-60963) SD365CO (DF-
Addressable Modules 62000).
CMF-300: Addressable Control Module for one Class B or A zone of ADDRESSABLE DEVICE ACCESSORIES
supervised polarized Notification Appliances. Mounts directly to a 4.0" End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm
(10.16 cm.) electrical box. Notification Appliance Circuit option assembly supervises the MMF-300(A), MDF-300(A), MMF-301(A),
requires external 24 VDC to power notification appliances. and CMF-300(A) module circuits. The 3.9k ohm assembly supervises
CMF-300-6: Six-circuit supervised control module. Mount one or two the MMF-302(A) module circuit. These resistors are included with
modules in a BB-2F cabinet (optional). Mount up to six modules on a each module.
CHS-6 chassis in a BB-6F cabinet. Power Supervision Relay: Supervises the power to 4-wire smoke
CRF-300: Addressable relay module containing two isolated sets of detectors and notification appliances.
Form-C contacts, which operate as a DPDT switch. Mounts directly to
a 4.0" (10.16 cm.) box, surface mount using the SMB500. Wiring Requirements
CRF-300-6: Six-relay control module (Form-C relays). Mount one or While shielded wire is not required, it is recommended that all SLC
two modules in a BB-2F cabinet (optional). Mount up to six modules (DLC) wiring be twisted-pair to minimize the effects of electrical inter-
on a CHS-6 chassis in a BB-6F cabinet. ference. Refer to the panel manual for wiring details.
I300: This module isolates the SLC (DCL) loop from short circuit con-
ditions (required for Class A or Class X operation).
ISO-6: Six-fault isolator module. Mount one or two modules in a BB-2F
cabinet (optional). Mount up to six modules on a CHS-6 chassis in a
BB-6F cabinet.
MDF-300: Dual Monitor Module. Same as MMF-300 except it provides
two Class B-only IDCs.

DF-60961:A • 7/18/2023— Page 3 of 4


SYSTEM SPECIFICATIONS
System Capacity Temperature and Humidity Ranges
• Maximum Intelligent Signaling Line Circuits ...............................3 This system meets NFPA requirements for operation at 0 – 49°C/32
• Addressable device capacity per loop ....................................318 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's
• Programmable software zones ...............................................256
standby batteries and the electronic components may be adversely
• Annunciators.............................................................................16 affected by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and its peripherals be installed in
Electrical Specifications an environment with a normal room temperature of 15 – 27°C/60 –
80°F.
AC Power: 120/240 VAC, 50/60 Hz, 2.4 A. Wire size: minimum 14
AWG (2.00 mm2) with 600 V insulation. Non-power-limited, super-
vised. NFPA Standards
Battery: Minimum System Battery Size: 18 Amp Hour, Maximum The ES-1000X complies with the following NFPA 72 Fire Alarm Sys-
Battery Charger Capacity: 55 Amp Hour, FACP cabinet holds maxi- tems requirements:
mum of two 26 Amp Hour batteries. – LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi-
Communication Loop: Supervised and power-limited. sory)
Notification Appliance Circuits: Terminal Block provides connec- – AUXILIARY (Automatic, Manual and Waterflow) (requires
tions for four NACs, Class B or Class A. Special Application power. 4XTMF)
Power-limited, supervised circuitry. Maximum signaling current per – REMOTE STATION (Automatic, Manual and Waterflow) (Where
circuit: 3.0 amps special application, 300mA regulated. End-of-Line a DACT is not accepted, the alarm, trouble and supervisory
Resistor: 4.7k ohm, ½ watt (P/N 71252 UL listed) for Class B NAC; relays may be connected to UL 864 listed transmitters. For
system capable of 1.9 kΩ - 22 kΩ ELR range. Refer to the Fire•Lite reverse polarity signaling of alarm and trouble, 4XTMF is
Device Compatibility Document for listed compatible devices. required.)
Two Programmable Relays and One Fixed Trouble Relay: Con- – PROPRIETARY (Automatic, Manual and Waterflow)
tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). – CENTRAL STATION (Automatic, Manual and Waterflow, and
Form-C relays, non-power-limited, non-supervised. Sprinkler Supervised)
– DAC, PSDN (Digital Alarm Communicator, Packet-switched
Cabinet Specifications Data Network)
Door: 20.30" (51.56 cm.) high x 20.57" (52.25 cm.) wide x 0.72"
(1.82 cm.) deep. Backbox: 20.00" (50.8 cm.) high x 20.50" (52.07 Agency Listings
cm.) wide x 6.755" (13.34 cm.) deep. The listings and approvals below apply to the basic ES-1000X con-
trol panel. In some cases, certain modules may not be listed by cer-
Shipping Specifications tain approval agencies, or listing may be in process. Consult factory
for latest listing status.
Weight: 41.0 lbs. (18.6 kg.) Dimensions: 22.0625” (53.088 cm.)
high x 23.875” (60.643 cm.) wide x 7.75” (19.69 cm.) deep. • UL: S624
• CSFM: 7165-0075:0500

LiteSpeed™ is a trademark and Fire-Lite® Alarms, SWIFT®, and System Sensor®


are registered trademarks of Honeywell International Inc. AT&T® is a registered
trademark of the AT&T Properties, L.P. Gentex® is a registered trademark of the
Gentex Corporation. Microsoft® and Windows® are registered trademarks of the Mi-
crosoft Corporation. Verizon® is a registered trademark of Verizon Trademark Ser-
vices LLC. Wheelock® is a registered trademark of Cooper Technologies Co.
©2023 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: USA
www.firelite.com

Page 4 of 4 — DF-60961:A • 7/18/2023