DS 9189

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SRP-4x4 Fire Alarm/Releasing

Control Panel
F eatures
• Four zone fire alarm control and release panel
• Initiating circuits capable of Class A
(Style D) or Class B (Style B) Service
• 10,000 ft. (3,048m) of Protectowire and 5 smoke
detectors per zone
• Field selectable input and output configurations
• Ground fault detection
• Four Class B (Style Y) output circuits
• Protectowire Alarm Point Location Meter available

Description
The Model SRP-4x4 is a UL listed and FM approved, Fire
Alarm/Releasing Control Panel. Primarily designed for use as
a releasing panel for Pre-action and Deluge water-based extin-
guishing systems, it may also be used as a stand alone Fire Alarm
Control Panel and is ideally suited for many commercial and
light industrial applications.
The unit consists of a single multifunction control board for
flexibility in adapting to individual job requirements. Field selec-
table input and output configurations, detection circuits capable
of Class A (Style D) or Class B (Style B) service, battery charg-
er/monitor, and ground fault detection are standard features of
the control panel. The versatile single board configuration
eliminates custom assembly of multiple modules thus ensuring
a streamlined system.
System Design F eatures
The SRP-4x4 is a four zone control panel designed for use with
Protectowire Linear Heat Detector, two wire smoke and heat
detectors, flame detectors and direct shorting devices such as
manual pull stations and water flow switches. The panel is UL
listed and FM approved for automatic release service.
The unit comes completely assembled in a surface mounted
enclosure. The traditional red textured finish resists scratches
and the durable, heavy-gauge steel cabinet has a piano hinged
door allowing for greater rigidity to prevent sagging.

APPROVED An ISO 9001:2008 Registered Company


Configuration: The control panel provides four Class A or B (Style will convert two output circuits.
D or B) Initiating Circuits, one dedicated Class B (Style B) Zone Alarm Relays: A zone operated Alarm Relay Board, Model
Supervisory Circuit, and four Class B (Style Y) Output Circuits. RB-4, is available that provides four SPDT relays, rated at 1 amp,
An optional Class A (Style Z) Output Module is available. 24 VDC. The RB-4 is designed for quick, easy field installation
Programming: The four input circuits and four output circuits can and provides zone activated contacts for auxiliary alarm control and
be configured into 16 standard operating programs that are field annunciation functions.
selectable by utilizing a set of simple to operate dip switches.
Specifications
Output 1 is reserved for use as a general alarm notification appliance
Enclosure:
circuit, while Outputs 2, 3, and 4 can be configured in various
• 16 gauge steel with piano hinged door.
combinations as solenoid release circuits, or notification appliance
• Size: 20.5 in. (H) x 14.5 in. (W) x 4.7 in. (D) (52 cm x 37 cm x 12 cm)
circuits suitable for fire alarm, water flow, or supervisory signaling.
Initiating Device Circuits:
For ease of servicing, Outputs 2, 3, and 4 have a disconnect switch
• Four Class A or B (Style D or B) Alarm Circuits and one
to prevent accidental operation. When activated, the disconnect
dedicated Class B (Style B) Supervisory Circuit.
switch causes an off-normal supervisory indication at the control
• Maximum length of Protectowire Linear Heat Detector per
panel. Cross-zoning configurations are limited to the following input
circuit: 10,000 feet (3,048 m).
groupings: Inputs 1 and 2; Inputs 3 and 4.
• Two Wire Smoke Detector capacity per circuit: 5 - 0.045 mA
Visual Indicators: Seven system status indicators are mounted on
type as supplied by The Protectowire Company.
the main control board. A green Power On LED, a red Common
Output Circuits:
Alarm LED, and five yellow LED’s indicating Ground Fault,
Alarm Indicating, Trouble Indicating, Supervisory, or Releasing.
Battery Trouble, System Trouble, Output Disconnect Supervisory
and System Silence. Additional red and yellow LED’s are provided • Four Class B (Style Y) Output Circuits, reverse polarity on alarm.
for each of the four input and four output circuits to indicate indi- • Optional Class A (Style Z) AM-91-2 Module available.
vidual zone Alarm and Trouble. The dedicated supervisory circuit • Output 1, dedicated to Common (General) Alarm signaling,
is provided with two yellow LED’s to indicate zone alarm and trouble. rated 24 V FWR, 1 amp continuous. Outputs 2, 3, and 4 are
System Controls: The system controls consist of two momentary rated at 1 amp each, 2.1 amp combined.
push button switches that provide the following functions: System • Outputs 2, 3, and 4 are provided with a common disconnect
Silence, and System Reset. The switches are located on the main switch.
control board and are accessible only by unlocking the enclosure door. • UL listed compatible Solenoids (see manual) and FM Solenoid
Groups A, B, D, E, F, G & H.
Options Outputs:
Protectowire Alarm Point Location Meter: The SRP-4x4 • Remote Signaling SPDT Relays rated 3 amp, 30 VDC for Alarm,
Control Panel is available with the PDM-1000-4 Alarm Point Trouble, and Supervisory.
Location Meter. This unique feature is designed to locate a heat- • Auxiliary Power - Regulated 24 VDC, rated 100 mA max. (Power
actuated point on the Protectowire Linear Heat Detector. The high Limited).
intensity LCD meter will display the distance in feet or meters from Input Power:
the start of the Detector portion of the zone to the heat actuated • 120 VAC +10 –15% - 100 VA max. (240 VAC available).
point on the Protectowire Linear Heat Detector. Approvals:
Class A (Style Z) Output Circuits: A conversion Module, Model • UL listed (9th Edition) • Factory Mutual
AM-91-2, is available to convert the standard Class B (Style Y) out- • California State Fire Marshal #7165-0854:0104
put circuits to Class A (Style Z) operation. Each AM-91-2 Module

Ordering Information
Model Description Approx. Shipping Weight
Lbs. Kg
SRP-4x4 Four Zone Fire Alarm/Releasing Control Panel with 21 9.5
one dedicated Supervisory Circuit and four Output Circuits.
SRP-4x4M Four Zone Fire Alarm/Releasing Control Panel with one dedicated 22 10
Supervisory Circuit, four Output Circuits and Digital Protectowire
Alarm Point Location Meter.
RB-4 Alarm Relay Board with four SPDT relays, rated 1 amp, 24 VDC. (Field Installed) 1 .45
AM-91-2 Class A (Style Z) Conversion Module. Converts two Class B (Style Y) 1 .45
Output Circuits to Class A operation. (Field Installed)
Refer to Operating & Maintenance Manual for battery size selection and programming information and limitations.

© 2016 The Protectowire Co., Inc. SPECIAL HAZARD FIRE DETECTION SYSTEMS DS 9189E-1116 (1C)