KCGG
KCGG
KCGG
CTA
CTB
Protected
unit
Z MA
Z MB
R CTA
R CTB
RL
RL
R RELAY CIRCUIT
RL
RL
(1)
(2)
= maximum lead
resistance from the
current transformer to
the relaying point
If
= maximum secondary
external fault current
= a constant affected by
the dynamic response
of the relay
12
Typical
operating
time (ms)
30
40
50
60
(3)
Vs
Ir
Rr
(4)
Ir
(5)
Use of Metrosil
Non-linear Resistors
When the maximum through fault
current is limited by the protected
circuit impedance, such as in the
case of generator differential and
power transformer restricted earth
fault protection, it is generally found
unnecessary to use non-linear
voltage limiting resistors (Metrosils).
However, when the maximum
through fault current is high, such as
in busbar protection, it is more
common to use a non-linear resistor
(Metrosil) across the relay circuit
(relay and stabilising resistor).
Metrosils are used to limit the peak
voltage developed by the current
transformers, under internal fault
conditions, to a value below the
insulation level of the current
transformers, relay and
interconnecting leads, which are
able to withstand 3000V peak.
The following formulae should be
used to estimate the peak transient
voltage that could be produced for
an internal fault. This voltage is a
function of the current transformer
kneepoint voltage and the
prospective voltage that would be
produced for an internal fault if
current transformer saturation did
not occur. Note, the internal fault
level, I'f , can be significantly higher
than the external fault level, If , on
generators where current can be fed
from the supply system and the
generator.
Vp = 2 2VK (Vf VK)
(6)
V = CI
(8)
I = instantaneous current
through the non-linear
resistor (Metrosil)
With a sinusoidal voltage applied
across the Metrosil, the RMS current
would be approximately 0.52x the
peak current. This current value can
be calculated as follows:
I(rms) = 0.52
Vs(rms) x 2 4
(9)
C
Stability voltage
Vs (V) rms
Single pole
Triple pole
Up to 125V
600A/S1/S256
C = 450
600A/S3/I/S802
C = 450
125-300V
600A/S1/S1088
C = 900
600A/S3/I/S1195
C = 900
internal fault
Current
(A) rms
50A
Up to 200V
250V
275V
300V
600A/S1/S1213
C = 540/640
600A/S1/S1214
C = 670/800
600A/S1/S1214
C = 670/800
600A/S1/S1223
C = 740/870
100A
150A
The KCGG
The KCGG142 is a numerical 3
phase overcurrent and earth fault
relay with 3 stages of phase and
earth fault protection, I>/Io>, I>>/
Io>> and I>>>/Io>>> which can
be used for 3 phase differential
protection or restricted earth fault
(REF) protection. The KCGG122 is a
numerical single phase overcurrent
and earth fault relay with the same
3 stages of phase and earth fault
protection, which can be used for
REF protection only. It is
recommended that the I> element is
used as the main protection element
for 3 phase differential protection
and the Io> element for restricted
earth fault applications. This is
because the I>/Io> elements have
increased through fault stability
compared to the I>>/Io>> and
I>>>/Io>>> elements. The I>/Io>
elements operate when the Fourier
value exceeds the threshold setting
and the positive and negative peak
values exceed 90% of the threshold
setting. The I>>/Io>> and I>>>/
Io>>> elements operate when the
Fourier derived values exceeds the
threshold setting or where the peak
of any half cycle exceeds twice the
set threshold. Since the differential
spill current is likely to contain a dc
offset level, the positive and
negative peaks will have different
amplitudes and so the I>/Io>
element is more stable. The time
delay characteristic should be
selected to be definite time and with
a setting of zero seconds.
The output relay that is to trip the
circuit breakers must be allocated in
the relay masks for t>A, t>B and
t>C. Any relay allocated in these
relay masks will dwell in the closed
state for a minimum of 100
milliseconds, even if fleeting
operation of the protection should
occur, ensuring positive operation of
the circuit breaker, or trip relay. It is
not advised that the start outputs
from I> are used because they do
not have this in-built minimum
contact dwell.
Separate output relays may be
allocated to each phase trip if it is
required to have phase segregated
outputs. However, the three relay
1000 x 103
3 x 415
= 1391A
Maximum through fault level
(ignoring source impedance)
Vs = 40 + 0.05RST +
0.04If(RCT + 2RL)
(10)
Ir = 40 + 0.05RST +
0.04If(RCT+ 2RL)
(11)
(12)
Ie <
where
Current transformer
requirements
Is Ir
n
5
30
x 1391 x
1500
100
= 1.4A
100
=
x 1391
5
= 1A
n = number of current
transformers in parallel
with the relay
= 27820A
= 4
Ir
= 17.6
1
= 17.6 ohms
5A rated KCGG relays can be
supplied, on request, with stabilising
resistors that are continuously
adjustable between 0 and 47.
Thus, a stabilising resistance of
17.6 can be set using the
standard supplied resistor.
Ie @ 17.6V <
1.4 1
4
< 0.1A
The time delay setting of the to>
element should be set to 0s.
The Io>>/Io>>>/I>>/I>>>
elements not used should be
disabled by setting the phase and
earth fault function links PF1, PF2,
EF1 and EF2 to 0. Note, the phase
overcurrent elements not used for
restricted earth fault protection could
be used to provide normal
overcurrent protection.
Metrosil non-linear resistor
requirements
5
= 27820 x
x
1500
(0.3 + 0.08 + 17.6)
= 92.7 x 17.98
= 1667V
Therefore substituting these values
for VK and Vf into the main formula,
it can be seen that the peak voltage
developed by the current
transformer is:
Vp = 2 2VK (Vf VK)
= 2 2 x 88 x (1667 88)
= 1054V
This value is well below the
maximum of 3000V peak and
therefore no Metrosils are required
with the relay. If, on the other hand,
the peak voltage VP given by the
formula had been greater than
3000V peak, a non-linear resistor
(Metrosil) would have to be
connected across the relay and the
stabilising resistor.
The recommended non-linear
resistor type would have to be
chosen in accordance with the
maximum secondary internal fault
current and the voltage setting.
Busbar Protection
A typical 132kV double bus
generating station is made up of
two 100MVA generators and
associated step-up transformers,
providing power to the high voltage
system, by means of four overhead
transmission lines, shown in
Figure 2. The main and reserve
busbars are sectionalised with bus
section circuit breakers.
The application for a high
impedance circulating current
scheme having 4 zones and an
overall check feature, is as follows:
The switchgear rating is 3500MVA,
the system voltage is 132kV solidly
earthed and the maximum loop lead
resistance is 4 ohms. The current
transformers are of ratio 500/1
amp and have a secondary
resistance of 0.7 ohms.
Stability voltage
3500 x 10
= 15300A
3 x 132 x 103
If (RCT + 2RL)
Current setting
Discriminating zone
Vs
Ir
72
0.8
= 90
=
Current transformer
requirements
= 360V
1
x (0.7 + 4 + 90)
500
= 30.6 x 94.7
= 2898V
Therefore substituting these values
for VK and Vf into the main formula,
it can be seen that the peak voltage
developed by the current
transformer is:
Vp = 2 2VK (Vf VK)
= 2 2 x 360 x (2898 360)
= 2704V
This value is below the maximum of
3000V peak and therefore no
Metrosils are required with the
relay. If, on the other hand, the peak
voltage VP given by the formula had
been greater than 3000V peak, a
non-linear resistor (Metrosil) would
have to be connected across the
Busbar supervision
Ir RST
Ir = 0.8In
RST = 61
Vs = 0.8 x 61 = 48.8V
Steady state stability limit
(RCT + 2RL) < (VK + Vs)/IF.
Assuming VK = 5 Vs
(0.7 + 4) <
(6 x 48.8)
(15300/500)
100MVA 15kV
100MVA 132/15kV
132kV
Main
reserve
A
B
P1
P2
P1
P2
S1
S2
S1
S2
Protected
plant
Figure 3:
A
B
C
21 R A
Protective
relays 22
v
R ST
23 R B
v
R ST
24
P1
P2
S1
S2
25 R C
26
v
R ST
A
B
C
28
27
Figure 4:
P2
S2
R
v
P1
S1
R ST
P1
P2
S1
S2
A
B
C
Figure 5:
28
27
R R ST
P2
P2
S2
S2
A
B
C
Figure 6:
P2
P2
S2
S2
27
28
R R ST
v
P2
P1
S2
S1
A
B
C
P2
P1
S2
Figure 7:
S1
28
27
P2
S2
P1
S1
R R ST
v
10
P1
P2
S1
S2
A
B
P1
P2
S1
S2
P2
P1
S2
S1
A
B
Figure 8:
21 R A
Protective
relays 22
v
R ST
23 R B
24
P1
S1
P2
S2
v
R ST
25 R C
26
R ST
A
B
C
Figure 9:
P2
S2
P2
S2
P1
S1
P1
S1
A
B
C
21 R
A
Contacts from
buswire
supervision
auxiliary relay
11kV
Protective
relays 22
23
R ST
25 R
C
RB
v
24
R ST
27
RN
28
26
v
R ST
Buswire
supervision
1500/5A
415V
A
R CT
B
C
RL
RL
Figure 10: Restricted earth fault protection on a
power transformer LV winding.
R CT
Data
Protection:
R L = 0.04
R LC = 0.3
Transformer: X
= 5%
11
RL
Restricted
earth fault
protection
RL
ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: enquiries@pcs.alstom.co.uk Internet: www.gecalsthomgpc.co.o.uk
1998 ALSTOM T&D Protection & Control Ltd
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
Publication R6142A
Printed in England.