Busbar Protection
Busbar Protection
Bus Protection
Introduction
Incoming Source
Busbars in power systems are the location where transmission lines,
generation sources, and distribution loads converge. Because of
this convergence, short circuits located on or near the busbar tend
to have very high magnitude currents. The high magnitude fault
currents require high-speed operation of the busbar protection to 51 51N Inverse Time Overcurrent
Bus Protection
or Reverse Interlocked
limit equipment damage. However, this high-speed clearing must 50 50N Overcurrent
be balanced against the need for security. Tripping incorrectly for 52
an external fault may cause large outages, and jeopardize power
system stability. The high fault magnitudes increase the possibility
of CT saturation during external faults close to the busbar, and CT
51 51 51 51
saturation increases the possibility of an incorrect operation of the
busbar protection. 51N 51N 51N 51N
the topology of the bus. Many busbars connect all circuits to one
common segment of busbar. The complication for these buses is
simply the number of connected circuits. However, a specific busbar
Radial Feeders
may have multiple bus segments, with individual circuits that
connect to different bus segments depending on operating needs. Overcurrent based interlocking schemes for simple Bus protection
252 www.GEMultilin.com
Bus Protection
Bus Protection
impedance differential is the ability to handle routine bus switching,
such as removing a circuit breaker for maintenance. Typical, the
differential relay must be blocked during such switching operations.
While this type of switching is uncommon with the typical single
segment busbar, it is a routine occurrence with multiple segment
busbars, making high-impedance differential schemes difficult to Differential characteristic region
apply on such multiple segment busbars.
Percentage differential relays, also known as low-impedance
differential relays, provide similar operating speed, and can provide
a similar level of security, as high-impedance differential relays. In
addition, low-impedance relays are simple to apply, as there are
no special requirements for CT performance class, turns ratio, or
secondary lead burden other than good performance practice. A
microprocessor-based low-impedance differential relay measures
input currents from each set of CT, and therefore can provide
auxiliary functions such as breaker failure for every circuit, and
measure and record all currents during a fault event. In addition,
switching events can be routinely handled in the relay, and low-
impedance differential relays can be specifically designed for
multiple segment busbars. Adaptive Trip logic
www.GEMultilin.com 253
Bus Protection
Dynamic bus
ZONE 1
replica knows
breaker status,
isolator status
ZONE 2
Bus side CT:
bus protection
must detect this
fault when CB is
open T
End-zone fault:
bus protection
must detect this
fault when CB is
open
Re-configurable busbar with zone boundaries
254 www.GEMultilin.com
Bus Protection
Bus Protection
End Zone Fault - Bus side CTs
www.GEMultilin.com 255