Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

FaultCal Adv

Download as pdf or txt
Download as pdf or txt
You are on page 1of 43

Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Lecture 2
Fault Calculations

05/09/2005 Hong Kong Polytechnic University 1

Symmetrical and Unsymmetrical Fault


Calculations
Per unit representation
Symmetrical fault calculations
Sequence components
Connection of sequence networks under
various unsymmetrical fault conditions
Transformer zero sequence network
representation

Hong Kong Polytechnic University 05/09/2005 2

Hong Kong Polytechnic University 1


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Symmetrical Fault Analysis


Per Unit Values
The per unit values of any quantity is defined
as the ratio of the quantity expressed as a
decimal to its base value.

V I
V pu= I pu =
Vb Ib
MVA
MVA pu = MVA b = 3Vb ph I b ph
MVAb

Hong Kong Polytechnic University 05/09/2005 3

Z Vb
Z pu = where Z b =
Zb Ib
IbZ
=
Vb
3Vb I b Z MVA SC = 3Vb I f
=
3Vb2 MVAb
=
MVAb Z Z T pu
=
(Vb line )2

Hong Kong Polytechnic University 05/09/2005 4

Hong Kong Polytechnic University 2


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Change of MVA base


MVAb new Z
Z pu new =
(Vb line ) 2
MVAb old Z
Z pu old =
(Vb line ) 2
Z pu new MVAb new
=
Z pu old MVAb old

Hong Kong Polytechnic University 05/09/2005 5

Change of Voltage base


MVAb Z
Z pu new =
(Vb l new ) 2
MVAb Z
Z pu old =
(Vb l old ) 2
Z pu new (Vb l old ) 2
=
Z pu old (Vb l new ) 2

Hong Kong Polytechnic University 05/09/2005 6

Hong Kong Polytechnic University 3


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Change of both MVA base and Voltage


base

Z pu new MVAb new (Vb l old ) 2


=
Z pu old MVAb old (Vb l new ) 2

Hong Kong Polytechnic University 05/09/2005 7

Symmetrical Components
V a= Zs Ia + Zm Ib + Zm Ic
V b= Zm Ia + Zs Ib+ Zm Ic
V c= Zm Ia+ Zm Ib+ Zs Ic
[V ] = [Z ][I ]
⎡ ⎤ ⎡V a ⎤ ⎡ ⎤ ⎡I a⎤ ⎡ ⎤ ⎡ Z s Z m Z m⎤
⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥
⎢V ⎥ = ⎢V b ⎥ ⎢ I ⎥ = ⎢ I b⎥ ⎢Z ⎥ = ⎢ Z m Z s Z m ⎥
⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥ ⎢ ⎥
⎣ ⎦ ⎢⎣V c ⎥⎦ ⎣ ⎦ ⎢⎣ I c ⎥⎦ ⎣ ⎦ ⎢⎣ Z m Z m Z s ⎥⎦

Hong Kong Polytechnic University 05/09/2005 8

Hong Kong Polytechnic University 4


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

⎡ ⎤ ⎡1 1 1⎤ ⎡1 1 1⎤
-1
⎡ ⎤
⎢ ⎥ ⎢ ⎥ ⎢ ⎥ 1⎢ ⎥
⎢ ⎥
A = ⎢1 a
2
a ⎥ ⎢ ⎥
A = ⎢ 1 a a
2

⎢ ⎥ ⎢ ⎥ ⎢ ⎥ 3 ⎢ ⎥
⎣ ⎦ ⎢⎣1 a a 2 ⎥⎦ ⎣ ⎦ ⎢⎣1 a 2 a ⎥⎦
a = 1∠120° 1+ a + a2 = 0
[V ] = [Z ][A][A]-1 [I ]
[A]−1 [V ] = [A]-1 [Z ][A]× [A]-1 [I ]
-1
⎡ ⎤ ⎡ ⎤ ⎡1 1 1⎤ ⎡V a ⎤ ⎡V o ⎤ ⎡ ⎤
⎢ ⎥ ⎢ ⎥ 1⎢ ⎥⎢ ⎥ ⎢ ⎥ ⎢ ⎥
⎢ A ⎥ ⎢V ⎥ = 3 ⎢1 a a ⎥ ⎢V b ⎥ = ⎢V 1⎥ = ⎢ V s ⎥
2

⎢ ⎥ ⎢ ⎥ ⎢ ⎥⎢ ⎥ ⎢ ⎥ ⎢ ⎥
⎣ ⎦ ⎣ ⎦ ⎣⎢1 a
2
a ⎥⎦ ⎢⎣V c ⎦⎥ ⎣⎢V 2 ⎦⎥ ⎣⎢ _ ⎦⎥

Hong Kong Polytechnic University 05/09/2005 9

V0 = 1 (Va + Vb + Vc )
3
(
V1 = 1 Va + aVb + a 2Vc
3
)
(
V2 = 1 Va + a 2Vb + aVc
3
)
-1
⎡ ⎤ ⎡ ⎤ ⎡1 1 1⎤ ⎡ I a ⎤ ⎡ I o ⎤ ⎡ ⎤
⎢ ⎥ ⎢ ⎥ 1⎢ ⎥⎢ ⎥ ⎢ ⎥ ⎢ ⎥
⎢ ⎥ ⎢ ⎥ 3
A I = ⎢ 1 a a
2
⎥ ⎢ I b ⎥ = ⎢ I 1⎥ = ⎢ Is ⎥
⎢ ⎥ ⎢ ⎥ ⎢ ⎥⎢ ⎥ ⎢ ⎥ ⎢ ⎥
⎣ ⎦ ⎣ ⎦ ⎣⎢1 a
2
a ⎦⎥ ⎣⎢ I c ⎦⎥ ⎣⎢ I 2 ⎦⎥ ⎣⎢ _ ⎦⎥
I 0 = 1 (I a + I b + I c )
3
I 1 = 1 (I a + aI b + a 2 I c )
3
I 2 = 1 (I a + a 2 I b + aI c )
3

Hong Kong Polytechnic University 05/09/2005 10

Hong Kong Polytechnic University 5


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

[A]−1 [Z ][A] = [Z ]
⎡1 1 1⎤ ⎡ Z s Z m Z m ⎤ ⎡1 1 1⎤
1⎢ ⎥⎢ ⎥⎢ ⎥
⎢1 a a 2 ⎥ ⎢ Z m Z s Z m ⎥ ⎢1 a 2 a ⎥
3⎢ ⎥⎢ ⎥⎢ ⎥
⎢⎣1 a 2 a ⎥⎦ ⎢⎣ Z m Z m Z s ⎥⎦ ⎢⎣1 a a 2 ⎥⎦

⎡Z s + 2 Z m 0 0⎤ ⎡Z o 0 0⎤
⎢ ⎥ ⎢ ⎥
=⎢ 0 Zs - Zm 0⎥ = ⎢ 0 Z 1 0⎥
⎢ ⎥ ⎢ ⎥
⎣⎢ 0 0 Z s - Z m ⎦⎥ ⎣⎢ 0 0 Z 2 ⎦⎥
⎡V o ⎤ ⎡ Z o 0 0 ⎤ ⎡ I o ⎤
⎢ ⎥ ⎢ ⎥⎢ ⎥
⎢V 1⎥ = ⎢ 0 Z 1 0 ⎥ ⎢ I 1⎥
⎢ ⎥ ⎢ ⎥⎢ ⎥
⎢⎣V 2 ⎥⎦ ⎢⎣ 0 0 Z 2 ⎥⎦ ⎢⎣ I 2 ⎥⎦
Hong Kong Polytechnic University 05/09/2005 11

[ I ] = [ A ] [ Is ]

⎡ I a ⎤ ⎡1 1 1⎤ ⎡ I o ⎤
⎢ ⎥ ⎢ ⎥⎢ ⎥
⎢ I b⎥ ⎢ a
= 1 2
a ⎥ ⎢ I 1⎥
⎢ ⎥ ⎢ ⎥⎢ ⎥
⎣⎢ I c ⎦⎥ ⎣⎢1 a a ⎦⎥ ⎣⎢ I 2 ⎦⎥
2

⎡V a ⎤ ⎡1 1 1⎤ ⎡V o ⎤
⎢ ⎥ ⎢ ⎥⎢ ⎥
⎢V b ⎥ = ⎢1 a 2 a ⎥ ⎢V 1⎥
⎢ ⎥ ⎢ ⎥⎢ ⎥
⎣⎢V c ⎦⎥ ⎣⎢1 a a ⎦⎥ ⎣⎢V 2 ⎦⎥
2

Hong Kong Polytechnic University 05/09/2005 12

Hong Kong Polytechnic University 6


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Single phase to earth (L-E) fault

Ia

Ib

Ic

Hong Kong Polytechnic University 05/09/2005 13

Va = 0 ∴, V1 + V2 + V0 = 0
I a = I f = I1 + I 2 + I 0
Ib = Ic = 0
1
I1 = I 2 = I 0 = I f
3

The +ve, -ve, 0 sequence networks are


therefore connected in series

Hong Kong Polytechnic University 05/09/2005 14

Hong Kong Polytechnic University 7


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Z1T
+ve G E1

Z2T
-ve

Z0T
0

Hong Kong Polytechnic University 05/09/2005 15

Example 1 – For a L-E fault in the system


shown below, calculate
The fault current
The phase–earth voltage of all 3 phases at R
Z1=j0.1 pu
Z2=j0.15 pu
Z0=j0.2 pu
R
G •
Z1=Z2=j0.2 pu
E=1.0 pu
Z0=j0.4 pu

Hong Kong Polytechnic University 05/09/2005 16

Hong Kong Polytechnic University 8


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

1 1
I1 = I 2 = I 0 = = = − j 0.8
Z 1T + Z 2T + Z 0T j1.25
I F = 3I 0 = − j 2.4
V1 = E − I 1 Z 1S = 1 − (− j 0.8)( j 0.1) = 0.92
V2 = − I 2 Z 2 S = −(− j 0.8)( j 0.15) = −0.12
V0 = − I 0 Z 0 S = −(− j 0.8)( j 0.2 ) = −0.16
V A = V1 + V2 + V0 = 0.64
V B = a 2V1 + aV2 + V0 = 0.92∠240° − 0.12∠120° − 0.16
= −0.56 − j 0.9007 = 1.06∠ − 122°
V B = aV1 + a 2V2 + V0 = 0.92∠120° − 0.12∠240° − 0.16
= −0.56 + j 0.9007 = 1.06∠122°
Hong Kong Polytechnic University 05/09/2005 17

Single phase to earth (L-E) fault with fault


resistance
Ia

Ib

Ic

Rf

Hong Kong Polytechnic University 05/09/2005 18

Hong Kong Polytechnic University 9


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Va = I f Zf ∴, V1 + V2 + V0 = I f R f
I a = I f = I1 + I 2 + I 0
Ib = Ic = 0
1
I1 = I 2 = I 0 = I f
3
V1 + V2 + V0 = 3I 0 R f

Hong Kong Polytechnic University 05/09/2005 19

Z1T
+ve G E1

-ve Z2T

Z0T
0
3Rf

Hong Kong Polytechnic University 05/09/2005 20

Hong Kong Polytechnic University 10


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Example 2 – Calculate
The value of the neutral earthing resistance in
pu to limit the magnitude of the fault current
of a L-E fault to 1.2 pu

Z1=j0.1 pu
Z2=j0.15 pu
Z0=j0.2 pu
R
G •
Z1=Z2=j0.2 pu
E=1.0 pu
Z0=j0.4 pu

Hong Kong Polytechnic University 05/09/2005 21

3 3
I F = 3I 0 = =
Z 1T + Z 2T + Z 0T + 3R N 3R N + j1.25
3
IF = = 1.2
3R N + j1.25
32
= 1.2 2
(3R N ) 2
+ 1.25 2

R N = 0.72

Hong Kong Polytechnic University 05/09/2005 22

Hong Kong Polytechnic University 11


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Phase to phase (L-L) fault

Ia

Ib

Ic

Hong Kong Polytechnic University 05/09/2005 23

Ia = 0 ∴, I b = − I c = I f
I1 + I 2 = 0
Vb = Vc = V f
V1 = V2

The +ve, and -ve sequence networks are


therefore connected in parallel

Hong Kong Polytechnic University 05/09/2005 24

Hong Kong Polytechnic University 12


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Z1T
+ve G E1

-ve Z2T

Z0T
0

Hong Kong Polytechnic University 05/09/2005 25

Example 3 – a B-C fault occurs in the


system below, calculate
The fault current
Z1=j0.1 pu
Z2=j0.15 pu
Z0=j0.2 pu
R
G •
Z1=Z2=j0.2 pu
E=1.0 pu
Z0=j0.4 pu

Hong Kong Polytechnic University 05/09/2005 26

Hong Kong Polytechnic University 13


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

1 1
I1 = I 2 = = = − j1.538
Z1T + Z 2T j 0.65
I F = I B = a 2 I 1 + aI 2 = a 2 − a I 1( )
= j 3I 1 = 2.66∠180°

Hong Kong Polytechnic University 05/09/2005 27

Phase to phase to earth (L-L-E) fault


with fault resistance
Ia

Ib

Ic

Rf

Hong Kong Polytechnic University 05/09/2005 28

Hong Kong Polytechnic University 14


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Ia = 0 I1 + I 2 + I 0 = 0
I f = Ib + Ic I b + I c = 3I 0
Vb = Vc = I f R f

V1 =
1
3
( 1
3
)
V a + aV b + a 2 V c = (V a − V b )

1
3
( 1
3
)
V 2 = V a + a 2 V b + aV c = (V a − V b )

V 0 = (V a + V b + V c ) = (V a + 2V b )
1 1
3 3
= V1 + V b = V1 + 3 I 0 R f
V1 = V 2 = V 0 − 3 I 0 R f

Hong Kong Polytechnic University 05/09/2005 29

Z1T
+ve G E1

-ve Z2T

Z0T
0
3Rf

Hong Kong Polytechnic University 05/09/2005 30

Hong Kong Polytechnic University 15


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Effect of Fault Impedance


Assume pre-fault load current = 0
EA, EB are in phase and have same magnitude.
EA = EB = E

Hong Kong Polytechnic University 05/09/2005 31

Single phase to earth (L-E) fault with fault


resistance
I1’, I2’, I0’
Ia Ia ’

Ib

Ic

Rf

Hong Kong Polytechnic University 05/09/2005 32

Hong Kong Polytechnic University 16


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Z1T
+ve G E1

-ve Z2T

Z0T
0
3Rf

Hong Kong Polytechnic University 05/09/2005 33

I A = I 1' + I 2' + I 0' = C1 I 1 + C 2 I 2 + C 0 I 0


Z B1T
C1 =
Z A1T + Z B1T
where Z A1T = Z SA1 + Z LA1
Z B1T = Z SB1 + Z LB1
Normally the + ve and - ve sequence
networks are identical
∴, I A = 2C1 I 1 + C 0 I 0

Hong Kong Polytechnic University 05/09/2005 34

Hong Kong Polytechnic University 17


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

V A1 = C1 I 1 Z LA1 + V1
V A 2 = C 2 I 2 Z LA 2 + V2 = C1 I 1 Z LA1 + V2
V A0 = C 0 I 0 Z LA0 + V0
V1 + V2 + V0 = 3I 0 R f
V A = 2C1 I 1 Z LA1 + C 0 I 0 Z LA0 + 3I 0 R f

Hong Kong Polytechnic University 05/09/2005 35

Transformer Sequence Impedance


+ve and –ve sequence impedance

Hong Kong Polytechnic University 05/09/2005 36

Hong Kong Polytechnic University 18


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Zero sequence impedance of a two


winding transformer
The exciting branch is now the exciting
impedance to zero sequence voltages or currents
which are identical in all three phases. The core
design of transformer will affect the zero
sequence impedance.
Account must be taken of the method of
interconnection of the windings and the presence
or absence of a neutral connection.

Hong Kong Polytechnic University 05/09/2005 37

Hong Kong Polytechnic University 05/09/2005 38

Hong Kong Polytechnic University 19


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Does a physical circuit exist by means of which


zero sequence currents can be passed into the
winding in question from the external circuit on
that side (i.e. is there a neutral point on the
transformer or elsewhere which is connected to
earth or to a neutral wire, possibly through an
impedance). If so, the link 'a' is closed; if not it is
left open. This is done for each side of the
transformer in turn.
Can zero sequence currents circulate in the
winding in question, without flowing in the
external circuit (i.e. does a delta connection
exist). If so, the appropriate link 'b' is closed.

Hong Kong Polytechnic University 05/09/2005 39

Hong Kong Polytechnic University 05/09/2005 40

Hong Kong Polytechnic University 20


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Hong Kong Polytechnic University 05/09/2005 41

Hong Kong Polytechnic University 05/09/2005 42

Hong Kong Polytechnic University 21


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Hong Kong Polytechnic University 05/09/2005 43

+ve and –ve sequence network of three


winding transformers

Hong Kong Polytechnic University 05/09/2005 44

Hong Kong Polytechnic University 22


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Zero sequence network of three winding


transformers

Hong Kong Polytechnic University 05/09/2005 45

Hong Kong Polytechnic University 05/09/2005 46

Hong Kong Polytechnic University 23


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Earthing Methods
Solidly earthed
Resistance earthed
Reactance earthed
Resonant or Peterson Coil earthed
Insulated earthed
Earthing transformer

Hong Kong Polytechnic University 05/09/2005 47

Solidly earthed
The zero sequence impedance is a minimum. The
earth fault current is highest. However, overvoltage
in unfaulted phases is a minimum. Earth fault
protection is simple as the fault current is usually
high. Overvoltage during earth faults is usually less
than 0.8 times phase to phase voltage.
Resistance earthed
Earthing the system by resistor reduces both the fault
current and transient overvoltages. However, high
value of earthing resistance will produce overvoltage
in unfaulted phases during earth faults approaching
to phase to phase voltage.
Hong Kong Polytechnic University 05/09/2005 48

Hong Kong Polytechnic University 24


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Reactance earthed
Reactors are usually smaller and less expensive than
resistors, it can reduce fault current but this is
associated with a increase in transient overvoltages
during earth faults. Transient overvoltages are a
maximum when the value of earthing reactance is
approximately one third of the value required for
resonant earthing. In order to reduce the transient
overvoltages to an admissible level the earthing
reactance has to be reduced so that the earth fault
current approaches that for a solidly earthed system.
Overvoltages during earth faults will be between 0.8
times and full phase to phase voltage.
Hong Kong Polytechnic University 05/09/2005 49

Resonant or Peterson Coil earthed


When the earthing reactance is equal to the
total system capacitive reactance to earth,
arcing earth faults will be self extinguishing.
The system capacitance must however
remain fairly constant, otherwise the
efficiency of this earthing method is greatly
diminished. The steady state voltages in the
sound phases during a phase to earth fault is
the full phase to phase voltage.

Hong Kong Polytechnic University 05/09/2005 50

Hong Kong Polytechnic University 25


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Insulated earthed
The earth fault current is capacitive and if
small may be self extinguished. Automatic
segregation of faulty zones is extremely
difficult. The system can be run with an
earth fault for long periods. Overvoltages
during earth faults may be greater than phase
to phase voltage. Arcing earth faults are very
likely and these can result in high transient
overvoltages.

Hong Kong Polytechnic University 05/09/2005 51

Earthing transformer
In some cases where the neutral of the power
transformer is not available, the system is earthed
via a earthing transformer of zig-zag type. A
minimum impedance is offered to the flow of zero
sequence currents. Under normal operating
conditions the currents flowing through the
windings are the magnetising currents of the
earthing transformer. The earthing transformer is
designed to carry the maximum fault current for 30
seconds.

Hong Kong Polytechnic University 05/09/2005 52

Hong Kong Polytechnic University 26


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Use of earthing transformer

Hong Kong Polytechnic University 05/09/2005 53

Variation of Healthy Phase Voltages -


Single Phase to Earth Fault
2
a + aK 2 + K 0
Vb = a 2V1 + aV2 + V0 = Eb − Ea
(1 + K 2 + K 0 )
a + a2 K2 + K0
Vc = aV1 + a V2 + V0 = Ec −
2
E
(1 + K 2 + K 0 ) a
K0 −1
Vb = Eb − E
(2 + K 0 ) a
K0 −1
Vc = E c − E
(2 + K 0 ) a
Hong Kong Polytechnic University 05/09/2005 54

Hong Kong Polytechnic University 27


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Effectively
earthed system

Non-effectively
earthed system

A-E Fault

Hong Kong Polytechnic University 05/09/2005 55

Phase to Phase to Earth Fault

3K 2 K 0
Va = Ea
(K 2 + K 0 + K 2 K 0 )
3K 0
= Ea if K 2 = 1
(1 + 2K 0 )

Hong Kong Polytechnic University 05/09/2005 56

Hong Kong Polytechnic University 28


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

B-C-E Fault

Hong Kong Polytechnic University 05/09/2005 57

For solidly earthed system and with a earth fault close to


generation, K0 may be approaching to 0.5. In this case,
the voltage in the sound phase is below rated phase to
neutral voltage.
For solidly earthed system and with a earth fault more
distant from generation, K0 may be approaching to 1.0.
In this case, the voltage in the sound phase equals the
rated phase to neutral voltage.
Even on a solidly earthed system a earth fault far away
from the source of generation, can result in a value of K0
approaching to 2.5 to 4.5. The voltage in the sound phase
will increase above the normal rated phase to neutral
voltage.
Hong Kong Polytechnic University 05/09/2005 58

Hong Kong Polytechnic University 29


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

What is effective earthed system?


During phase to earth faults, the voltage to
earth voltage of the sound phases does not
exceed 80 % of the voltage between lines
of the system.

Hong Kong Polytechnic University 05/09/2005 59

Effective earthing includes


Direct earthing
Low reactance earthing.
Non effective earthing is characterised
by a high Z0 / Z1 ratio (large K0) and
includes
Resistance earthing
Distribution transformer earthing
Resonant earthing
Insulated systems.
Hong Kong Polytechnic University 05/09/2005 60

Hong Kong Polytechnic University 30


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Neutral Displacement and Residual


Voltages

3V AN
VNG = − I F Z E = − ZE
Z1 (1 + K 2 + K 0 ) + 3Z E
ZE
=− V AN if K 2 = K 0 = 1
Z1 + Z E

Hong Kong Polytechnic University 05/09/2005 61

Hong Kong Polytechnic University 05/09/2005 62

Hong Kong Polytechnic University 31


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Residual voltage measurement can be used


to detect earth faults on a system and to
provide a polarising quantity for directional
earth fault relays.
The residual voltage Vres depends mainly
on the value of K0 and ZE.
On systems with high earthing impedance
or insulated neutral, the value of Vres will
approach 3 times rated phase to neutral
voltage.
Hong Kong Polytechnic University 05/09/2005 63

On solidly earthed systems the value of K0 may


be small and there may be insufficient neutral
displacement to provide the necessary polarising
quantities. For this reason, where directional earth
fault relays are used at generating stations where
the system is solidly earthed, current polarisation
is preferred to voltage polarisation.
As the voltage between the neutral of power
transformers and earth is small during earth faults
on solidly earthed systems, graded insulation can
be used with considerable reduction in cost.

Hong Kong Polytechnic University 05/09/2005 64

Hong Kong Polytechnic University 32


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Calculate the value of the neutral


earthing resistor to limit the earth fault
current to 2 times full load current of the
transformer and the voltage of unfaulted
phases
15 kV at the busbar.
125 MW
Z= j0.125 pu
Z1=j0.08pu
150 MVA
Z2=j0.12pu
15/132 kV
Z0=j0.2pu
132 kV
G
Z1=Z2= j5Ω
Z0= j10Ω

Hong Kong Polytechnic University 05/09/2005 65

3
=2
ZT1 + ZT 2 + Z T 0 + 3RN
3
=2
3RN + j 0.787
[(3R N ) 2 + 0.787 2 = 2.25 ]
RN = 0.4256 = 49.4Ω

Hong Kong Polytechnic University 05/09/2005 66

Hong Kong Polytechnic University 33


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

1
I1 = I 2 = I 0 =
3 × 0.4256 + j 0.787
= 0.5675 − j 0.35 = 0.667∠ − 31.6°
V B / B1 = E − I 1 ( Z S 1 + Z Tx1 )
= 1 − (0.5675 − j 0.35)( j 0.221) = 0.923 − j 0.125
V B / B 2 = − I 2 ( Z S 2 + Z Tx 2 )
= −(0.5675 − j 0.35)( j 0.264) = −0.0923 − j 0.1498
VB / B0 = − I 0 ( Z Tx 0 + 3 R N )
= −(0.5675 − j 0.35)(1.277 + j 0.125) = −0.768 + j 0.376

Hong Kong Polytechnic University 05/09/2005 67

VB / B A = VB / B1 + VB / B 2 + VB / B 0
= 0.06 + j 0.1 = 9.1kV
VB / B B = a 2VB / B1 + aVB / B 2 + VB / B 0
= (−0.5 − j 0.866)(0.923 − j 0.125) +
(−0.5 + j 0.866)(−0.0923 − j 0.1498) + (−0.768 + j 0.376)
= −1.162 − j 0.366 = 1.22∠ − 162.5° = 93kV
VB / B C = aVB / B1 + a 2VB / B 2 + VB / B 0
= (−0.5 + j 0.866)(0.923 − j 0.125) +
(−0.5 − j 0.866)(−0.0923 − j 0.1498) + (−0.768 + j 0.376)
= −1.21 + j1.393 = 1.84∠131° = 140kV

Hong Kong Polytechnic University 05/09/2005 68

Hong Kong Polytechnic University 34


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Advance Fault Calculation


How a 3 phase auto transformer is
represented in unsymmetrical fault
calculation?
More unsymmetrical fault calculation
Open circuit fault
Simultaneous fault – OC and 1 Ph/E fault
simultaneously

Hong Kong Polytechnic University 05/09/2005 69

Sequence circuit of 3 phase auto transformer

Positive and negative sequence network of a 3 phase auto transformer

Zero sequence network of a 3 phase auto transformer

Hong Kong Polytechnic University 05/09/2005 70

Hong Kong Polytechnic University 35


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

I L 0 n C = I H 0 (n S + n C )
With the tertiary winding open circuited
nC
I H 0= I L 0
n S + nC
1
= I L0
1+ N
nS
where N =
nC
EH n + nC
= S =1+ N
EL nC
⎡ 1 ⎤
I L 0 − I H 0 = I L 0 ⎢1 −
⎣ 1 + N ⎥⎦
N
= I L0
1+ N
Hong Kong Polytechnic University 05/09/2005 71

In the zero sequence network, Z X seems to be :


I L 0 Z X = I L 0 Z L + 3(I L 0 − I H 0 )Z n
N
= ZL + 3 Zn
1+ N
Similarly,on the HV side, Z Y' seems to be :
I H 0 Z Y = Z H − 3(I L 0 − I H 0 )Z n
I L0 I N
Z Y = L0 Z H − 3 I L0 Z n
1+ N 1+ N 1+ N
Z Y = Z H − 3NZ n referring to HV side
N
Z Y' = Z H' − 3Z n referring to LV side
(1 + N )2
Hong Kong Polytechnic University 05/09/2005 72

Hong Kong Polytechnic University 36


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Now consider the HV side open circuited but with the


tertiary winding closed

I T 0 (Z X + Z Z ) = I L 0 (Z L + Z T + 3 Z n )
Z X + Z Z = Z L + Z T + 3Z n by using p.u. values
N
As Z X = Z L + 3Z n
1+ N
1
∴, Z Z = Z T + 3Z n
1+ N
Hong Kong Polytechnic University 05/09/2005 73

Open circuit fault – open circuit of phase


conductor

E xa = E ya + I a Z a and E x0=
1
3
[
(E ya + I a Z a ) + E yb + E yc ]
E xb = E yb
[
= (E ya + E yb + E yc ) + I a Z a
1
3
]
E xc = E yc
1
E x0= E y0+ I a Z a
3
1
and similarly E x1 = E y1 + I a Z a
3
1
E x2= E y2+ I a Z a
3
Hong Kong Polytechnic University 05/09/2005 74

Hong Kong Polytechnic University 37


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

IaZa = Za (I1 + I2 + I0 )
1 1
3 3

Hong Kong Polytechnic University 05/09/2005 75

Simultaneous fault –one phase open circuit


on one side and phase to earth fault on the
other side in the same phase
Ia P Q Ia ’

Ib I b’

Ic Ic’

G
Hong Kong Polytechnic University 05/09/2005 76

Hong Kong Polytechnic University 38


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Hong Kong Polytechnic University 05/09/2005 77

For the open circuit fault at P side,


I a= 0
∴, I a1= −( I a 2 + I a 0 )
V b−Vb' = 0
( ) ( ) (
∴, a 2 V a1−Va'1 + a V a 2−Va' 2 + V a 0−Va' 0 = 0 )
V c−Vc' = 0
( ) ( ) (
∴, a V a1−Va'1 + a 2 V a 2−Va' 2 + V a 0−Va' 0 = 0 )
For this to be true,
(V a1 ) (
−Va'1 = V a 2−Va' 2 = V a 0−Va' 0) ( )
Hong Kong Polytechnic University 05/09/2005 78

Hong Kong Polytechnic University 39


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

For the 1 phase to earth fault at Q side,


Va' = 0
∴, Va'1 + Va' 2 + Va' 0 = 0
I b+ I b' = 0
( ) ( ) (
∴, a 2 I a1+ I a' 1 + a I a 2+ I a' 2 + I a 0+ I a' 0 = 0 )
I c+ I c' = 0
( ) ( ) (
∴, a I a1+ I a' 1 + a 2 I a 2+ I a' 2 + I a 0+ I a' 0 = 0 )
For this to be true,
(I ) ( ) (
+ I a' 1 = I a 2+ I a' 2 = I a 0+ I a' 0
a1 )
Hong Kong Polytechnic University 05/09/2005 79

Hong Kong Polytechnic University 05/09/2005 80

Hong Kong Polytechnic University 40


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Fault Transients in Power System

400 kV system, line length 125 km


Fault point is 100 km away from local end
Remote end source fault level 35 GVA
Local end source fault level changes from 35 GVA
(strong source) to 5 GVA (weak source)
Fault inception is at voltage zero to produce
maximum transient but has negligible offsets
Hong Kong Polytechnic University 05/09/2005 81

Strong source

Voltage and current at relaying point


Hong Kong Polytechnic University 05/09/2005 82

Hong Kong Polytechnic University 41


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Weak Source

Voltage and current at relaying point


Hong Kong Polytechnic University 05/09/2005 83

Further Study
Paul M. Anderson, “Analysis of Faulted
Power Systems”, IEEE Press, 1995.

Hong Kong Polytechnic University 05/09/2005 84

Hong Kong Polytechnic University 42


Modern Protection Methods - Lect 2 Fault Calculations 05/09/2005

Self Evaluation
Do you understand the physical meaning of positive
and negative sequence components?
What is the relationship between mutual coupling
impedance and sequence impedance in the power
system?
How do you transform between the actual system
voltages and currents into their corresponding sequence
components?
Do you understand why the actual system network can
be transformed into sequence networks?
How the sequence networks are connected under
various unsymmetrical faults?
Hong Kong Polytechnic University 05/09/2005 85

Self Evaluation
Do you know how to form the zero sequence network
of a power transformer? Now do you understand how to
form the zero sequence network of the power system?
Do you know how to solve tutorial questions from 1 to
10?
How do you connect the sequence networks for an open
circuited fault?
How to represent the simultaneous fault by sequence
networks?
Are you able to solve the open circuit and simultaneous
fault problems from Q11 to Q15?

Hong Kong Polytechnic University 05/09/2005 86

Hong Kong Polytechnic University 43

You might also like