Power System Protection Lab
Power System Protection Lab
Power System Protection Lab
SIKAR
Lab File
(6EE4-23)
Semester: 6th
1. To determine fault type, fault impedance and fault location during single line to
ground fault.
2. To determine fault type, fault impedance and fault location during single line-to-
line fault.
3. To determine fault type, fault impedance and fault location during double line to
ground fault.
4. To study the operation of micro-controller based over current relay in DMT type
and IDMT type.
10. To study the operation of micro-controller un-based biased three phase differential
relay.
11. To study the operation of micro-controller based biased three phase differential
relay.
EE Department i
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 1
OBJECT: - To determine fault type, fault impedance and fault location during single line to
ground fault.
APPARATUS REQUIRED: -
For a single line to ground fault phase a is connected to ground at the fault point F. The fault
impedance is Zf. The fault current is Ia.
F
a
Ia
c
Va Vb
Vc
Zf
Ib Ic
Ib = 0
EE Department 1
BIET PSP Lab Manual EE6th Sem
Ic = 0
Va = IaZf
Va
Fault impedance Zf=
Ia
Sequence Network:
EE Department 2
BIET PSP Lab Manual EE6th Sem
OBSERVATION TABLE: -
RESULT: -
The fault impedance and fault current of a single line to ground fault are …………. ohm and
……….. amp. respectively.
EE Department 3
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 2
OBJECT: - To determine fault type, fault impedance and fault location during single line to line
fault.
APPARATUS REQUIRED: -
A line to line fault occur when two conductors are short circuited. A three phase system with a
line to line fault between phases b and c. the fault impedance is Zf. The L-L fault is placed
between lines b and c. The fault current is I b.
c
Va Vb
Vc
Ia = 0 Zf
Ib Ic
Ia= 0
Ib = -Ic
EE Department 4
BIET PSP Lab Manual EE6th Sem
Vb – Vc = IbZf
Fault current If = Ib
Ia0 = 0
1
I a1 ( 2 ) I b
3
1
I a 2 ( 2 ) I b
3
I a1 I a 2
Vbc= Vb- Vc
Vbc
Fault impedance Zf=
Ib
Sequence Network:
EE Department 5
BIET PSP Lab Manual EE6th Sem
OBSERVATION TABLE: -
RESULT: -
The fault impedance and fault current of a line to line fault are …………. ohm and ………..
amp. respectively.
EE Department 6
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 3
OBJECT: - To determine fault type, fault impedance and fault location during single line to line
fault.
APPARATUS REQUIRED: -
The double line to ground fault occur when two conductors are short circuited with the ground.
A three phase system with a phases b and c are faulted. the fault impedance is Z f. The D-L-L
fault is placed between lines b and c. The common line to ground fault impedance is Z g.
c
Va Vb
Vc
Ia = 0 Zf
Ib Ic
Ib + Ic Zg
Ia= 0
EE Department 7
BIET PSP Lab Manual EE6th Sem
Vbc
Fault impedance Zf=
Ib Ic
Sequence Network:
OBSERVATION TABLE: -
RESULT: -
The fault impedance and fault current of a double line to ground fault are …………. ohm and
……….. amp. respectively.
EE Department 8
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 4
OBJECT: - To study the operation of micro-controller based over current relay in DMT type
and IDMT type.
APPARATUS REQUIRED:-
THEORY:-
The overcurrent relay is defined as the relay, which operates only when the value of the current
is greater than the relay setting time. It protects the equipment of the power system from the
fault current. In an over current relay or o/c relay the actuating quantity is only current. There
is only one current operated element in the relay, no voltage coil etc. are required to construct
this protective relay.
Depending upon the time of operation, overcurrent relays may be categorized as:
The relay pick up in certain shortest time without any intentional time delay. The operating time
is less than 0.2 seconds.
EE Department 9
BIET PSP Lab Manual EE6th Sem
CONNECTION DIAGRAM:-
CONNECTION PROCEDURE:
EE Department 10
BIET PSP Lab Manual EE6th Sem
4. Connect ‘NC’ contact (4) of over current relay to current coil input (L1) of the over
current relay.
5. Connect the power chords at the back side of unit of variable AC current source and
microcontroller based over current relay.
6. Keep the current source variac at zero position.
7. Now switch on the power supply of variable AC current source and over current relay.
2. By using button 1and 2 of VPL-01 module you change the set current.
3. Adjust actual current above the set current using the variac of VPL-01 ACC.
4. Now press the button 4 of VPL-01 module.
DMT TYPE
IDMT TYPE
5. Now select DMT and IDMT type.
6. For DMT Mode select DMT press the button 1 of VPL-01.
7. Select setup time up to 50 seconds.
SET TIME ………………… SEC.
(1-50.00 SEC)
8. Press the button 4 of VPL-01 module.
9. The display of VPL-01 module show,
SET CURRENT (S. C.) ……………….. A
ACTUAL CURRENT (A. C.) ………………..A
EE Department 11
BIET PSP Lab Manual EE6th Sem
OBSERVATION TABLE:-
S. Set Current Fault Current Set Time Actual relay Tripping Time
No. (A) (A) (Sec.) (sec.)
RESULT: -We have successfully studied the operation of micro-controller based over current
relay in DMT type and IDMT type.
EE Department 12
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 5
OBJECT: - To study the operation of micro-controller based directional over current relay in
DMT type and IDMT type.
APPARATUS REQUIRED: -
THEORY: -Directional overcurrent protection is used when it is necessary to protect the system
against fault currents that could circulate in both directions through a system element, and when
bi-directional overcurrent protection could produce unnecessary disconnection of circuits. This
can happen in ring or mesh-type systems and in systems with a number of infeed points.
Directional overcurrent relay determine the direction of the fault current by measuring the
voltage with a voltage transformer as well as the current with a current transformer, and
establishing the phase difference.
EE Department 13
BIET PSP Lab Manual EE6th Sem
CONNECTION DIAGRAM: -
EE Department 14
BIET PSP Lab Manual EE6th Sem
OBSERVATION TABLE: -
S. Set Current Fault Current Set Time Actual relay Tripping Time
No. (A) (A) (Sec.) (Sec.)
S. Set Current Fault Current Calculated relay tripping Actual relay tripping
No. (A) (A) time (Sec.) time (Sec.)
EE Department 15
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 6
APPARATUS REQUIRED: -
THEORY: -Undervoltage occurs when the average voltage of a power system drops below
intended levels, and is sometimes referred to as a brown-out. Electromechanical devices,
including three phase motors and pumps, are designed to be operated at very specific voltage
levels. If these devices are allowed to operate at reduced voltage levelsthey will draw higher
currents. The increase in current causes increased heat in the winding and coils of the equipment
damaging the critical insulation protecting them. Operating in under-voltage conditions can
drastically reduce the life of the electromechanical equipment and lead to premature failure.
Undervoltage conditions are usually be caused by undersized or overloaded utility and facility
transformers. During peak demand periods and/or when the utility is experiencing problems, the
demand for power exceeds the capability of the transformer and as a result the voltage drops.
These conditions can occur without warning and provide no obvious indications. To protect
motors and equipment, use an undervoltage protection.
CONNECTION PROCEDURE: -
EE Department 16
BIET PSP Lab Manual EE6th Sem
CONNECTION DIAGRAM: -
OBSERVATION TABLE: -
S. Set voltage Fault Voltage Set Time Actual relay Tripping Time
No. (V) (V) (Sec.) (Sec.)
S. Set Voltage Fault Voltage Calculated relay tripping Actual relay tripping
No. (V) (V) time (Sec.) time (Sec.)
RESULT: - We have successfully studied the operation of micro-controller based under voltage
relay in DMT type and IDMT type.
EE Department 17
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 7
APPARATUS REQUIRED:-
THEORY:-An over-voltage relay operates when the current produced by a load, or device
connected to the output of a circuit, exceeds a predetermined value.The over-voltage relay
connects to a transformer, or device that transfers electrical energy from one circuit to
another. The relay is calibrated to operate at or over a preset voltage level. When the relay is
switched on, one or multiple contacts trip, or open a circuit breaker.
Overvoltage relay serves primarily the same purpose as an overcurrent relay except that it is
connected in the line by a potential transformer which measures the voltage across the line.
When an overvoltage exists, the relay operates and opens the circuit breaker.
EE Department 18
BIET PSP Lab Manual EE6th Sem
CONNECTION DIAGRAM:-
OBSERVATION TABLE: -
S. Set voltage Fault Voltage Set Time Actual relay Tripping Time
No. (V) (V) (Sec.) (Sec.)
S. Set Voltage Fault Voltage Calculated relay tripping Actual relay tripping
No. (V) (V) time (Sec.) time (Sec.)
RESULT: - We have successfully studied the operation of micro-controller based over voltage
relay in DMT type and IDMT type.
EE Department 19
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 8
OBJECT: - To study the operation of micro-controller based un-biased single phase differential
relay.
APPARATUS REQUIRED: -
CONNECTION DIAGRAM: -
EE Department 20
BIET PSP Lab Manual EE6th Sem
CONNECTION PROCEDURE: -
OBSERVATION TABLE: -
RESULT: - We have successfully studied the micro-controller based single phase unbiased
differential relay.
EE Department 21
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 9
APPARATUS REQUIRED: -
CONNECTION DIAGRAM: -
EE Department 22
BIET PSP Lab Manual EE6th Sem
CONNECTION PROCEDURE: -
OBSERVATION TABLE: -
RESULT: - We have successfully studied the micro-controller based single phase unbiased
differential relay.
EE Department 23
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 10
OBJECT: To study the operation of micro-controller based un-biased three phase differential
relay.
APPARATUS REQUIRED: -
1. Micro controller based 3phase differential relay.
2. Transformer MP1
3. Transformer MP2
4. Rheostat 100Ω/ 2 A
5. Power Chords
6. Patch Chords
THEORY: -A differential relay is a suitably connected overcurrent relay which operate when
the phasor difference of currents at the two ends of protected elements exceeds a predetermine
value. The three phase differential protection of three phase circuits. Under normal conditions
the three secondary currents of CTs are balanced and their phasor sum is zero. Therefore, no
current flows the operating coil of the relay. If the differential current is more than the pick-up
value, the relay operates.
CONNECTION DIAGRAM: -
Fig. connection diagram of micro controller based 3 phase unbiased differential relay
EE Department 24
BIET PSP Lab Manual EE6th Sem
CONNECTION PROCEDURE: -
OBSERVATION TABLE: -
RESULT: - We have successfully studied the micro-controller based un-biased three phase
differential relay.
EE Department 25
BIET PSP Lab Manual EE6th Sem
EXPERIMENT NO. 11
OBJECT: - To study the operation of micro-controller based biased three phase differential
relay.
APPARATUS REQUIRED: -
Biased differential relay provides high sensitivity to light internal faults and make differential
protection schemes more stable. In biased three phase differential relay have three operating coil
and three restraining connected in each phase respectively. The operating coil is connected to the
midpoint of the restraining coil.
The relay operates if the operating torque produced by the operating coil is more than the
restraining torque produced by the restraining coil.
Id >KIr
Id = I1 – I2
EE Department 26
BIET PSP Lab Manual EE6th Sem
CONNECTION DIAGRAM: -
Fig. connection diagram of micro controller based 3 phase biased differential relay
CONNECTION PROCEDURE: -
EE Department 27
BIET PSP Lab Manual EE6th Sem
OBSERVATION TABLE: -
RESULT: - We have successfully studied the micro-controller based biased three phase
differential relay.
EE Department 28