Power Transmission and Distribution Rev.: 7UM62.Inst.20Hz_1-3Hz_en.002.01 NM 7UM62x Installation Instructions for 100% SEF (20Hz) and rotor earth fault (1-3Hz & R,fn)
7UM62x - Installation Instructions for 100% SEF (20Hz) and Rotor EF (1-3Hz & R,fn)
100% Stator Earth Fault (20 Hz principle)
Example 1: 20Hz Equipment installed close to neutral transformer
20 Hz Band pass
20 Hz Generator
Protection cubicle
7XT34 3)
1B1 1B4
7XT33
4A1
U NG / 3 500V
400/5A 4) 1FS5 5) 15 VA P2 P1 S2 S1
RL
4A3
20Hz
1) 2) 3PP1336
Burden < 0.5 6 250 3 500 5
500
7UM62.
R13 R14 UE
J8 J7
IEE1
1) 2) 3) 4) 5)
The (separate) Voltage divider is only necessary in case of secondary voltages higher than 200Va.c. Voltage divider to be installed close to 7UM62 device to minimize interference in these leads. Cross section according to the maximum (short time-) current. The transformation ratio of the miniature CT 400A/5 A can be halved to 200A/5A by passing the primary conductor twice through the transformer window. Principally also a class P core could be used.
SIEMENS
Page 2 of 6
Date: Sept.-21-2007
Power Transmission and Distribution Rev.: 7UM62.Inst.20Hz_1-3Hz_en.002.01 NM 7UM62x Installation Instructions for 100% SEF (20Hz) and rotor earth fault (1-3Hz & R,fn)
Protection cubicle
20 Hz Band pass 20 Hz Generator
7XT34 3)
max. 3A (20Hz) .. mA 1B1 1A4
660
7XT33
1B4 4A1
U NG / 3 500V
RL
2)
1A1
660 330
1)
20Hz
1A2 1A3
4A3
7UM62.
Burden < 0.5 R13 R14 J8 J7 UE IEE1
1) 2)
Voltage divider is only necessary in case of secondary voltages higher than 200Va.c. The voltage divider must be connected via two separate leads directly to the load resistor RL. If not, the measured (20Hz) voltage is too high. (and the calculated resistance as well) Example: RL shall be 1 and the loop resistance between band pass/20 Hz generator and load resistor shall be 1 as well measured 20Hz voltage and calculated resistance are approximately twice than real. Cross section according to the maximum (short time-) current. The transformation ratio of the miniature CT 400A/5 A can be halved to 200A/5A by passing the primary conductor twice through the transformer window. Principally also a class P core could be used.
3) 4) 5)
SIEMENS
Page 3 of 6
Date: Sept.-21-2007
Power Transmission and Distribution Rev.: 7UM62.Inst.20Hz_1-3Hz_en.002.01 NM 7UM62x Installation Instructions for 100% SEF (20Hz) and rotor earth fault (1-3Hz & R,fn)
7XT71
27 19 21 15 17
7UM62.
K13+ control K14 K15+
meas. K16 TD1
A6
G 3~
Excit.
A11 B11
2)
20 k
TD2
20 k 20 k
B14
25
1)
Example: LiYCY 4x1.5
generator shaft
B18
3PP1326
1
500 500
7UM62.
2 K17+
TD3
9 k
10F 250V
K18
1)
The distance between controller unit 7XT71 and protection device 7UM62x should be as short as possible (to be installed in the same cubicle). The connections in between shall be laid closely together and twisted or a screened cable should be used. connection example for excitation voltages < 850V d.c. (an other connection example for excitation voltages < 1200V d.c. can be found in the Quick reference 7XR6004) : http://siemens.siprotec.de/download_neu/html_nav/ind_acc_e.htm
2)
SIEMENS
Page 4 of 6
Date: Sept.-21-2007
Power Transmission and Distribution Rev.: 7UM62.Inst.20Hz_1-3Hz_en.002.01 NM 7UM62x Installation Instructions for 100% SEF (20Hz) and rotor earth fault (1-3Hz & R,fn)
7XT71
27 19 21 15 17 25
7UM62.
K13+ control K14 K15+ meas. K16
TD1
A6
G 3~
Excit.
2)
A11 20 k B11 20 k B14
TD2
1)
Example: LiYCY 4x1.5
generator shaft
B18 20 k
3PP1326
1
500 500
7UM62.
2 K17+
TD3
9 k
10F 250V
K18
1)
The distance between controller unit 7XT71 and protection device 7UM62x should be as short as possible (to be installed in the same cubicle). The connections in between shall be laid closely together and twisted or a screened cable should be used. connection example for excitation voltages < 850V d.c. (an other connection example for excitation voltages < 1200V d.c. can be found in the Quick reference 7XR6004): http://siemens.siprotec.de/download_neu/html_nav/ind_acc_e.htm
2)
SIEMENS
Page 5 of 6
Date: Sept.-21-2007
Power Transmission and Distribution Rev.: 7UM62.Inst.20Hz_1-3Hz_en.002.01 NM 7UM62x Installation Instructions for 100% SEF (20Hz) and rotor earth fault (1-3Hz & R,fn)
3A1
7UM62.
4A1
4 F 333/50W
G 3~
Excit.
3
105
IR
4 4B1
4 F 333/50W 0.75 H
J8 J7
IEE1
R13
UE
1A1
R14
generator shaft
3PP1326
1 500 4
500 9 k
2)
2 3
7UM62.
TD3
K17+
10F 250V
The internal resistors can not be used in case of higher currents (IR). In the event of large harmonics content in the rotor voltage an external series resistor, type 3PP1336-0DZ-K2Y is recommended for the protection of the coupling capacitors. In this case the internal resistors should be shorted like in the Figure above. Refer also to Directions for use 7XR61 (Connection Examples): http://siemens.siprotec.de/download_neu/html_nav/ind_acc_e.htm 1) 2) In the absolutely most cases there is no need to connect the 0.75 H Inductor. The decision has to be made during hot commissioning. Can be also located inside excitation cubicle
SIEMENS
Page 6 of 6
Date: Sept.-21-2007
Power Transmission and Distribution Rev.: 7UM62.Inst.20Hz_1-3Hz_en.002.01 NM 7UM62x Installation Instructions for 100% SEF (20Hz) and rotor earth fault (1-3Hz & R,fn)
Protection cubicle
7XR61
4A1
4 F 333/50W
3A1
7UM62.
G 3~
Excit.
IR
4B1
4 F 333/50W
J8 J7
IEE1
0 V 1B1
R14
generator shaft
1
3PP1326
500 500
7UM62.
2 K17 +
TD3
9 k
10F 250V
Refer also to Directions for use 7XR61 (Connection Examples): http://siemens.siprotec.de/download_neu/html_nav/ind_acc_e.htm 1) In the absolutely most cases there is no need to connect the 0.75 H Inductor. The decision has to be made during hot commissioning.