Commissioning Service Department

Commissioning Standard Test Formats


Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 1 of 20
1. GENERAL DATA AND INFORMATION:

Bay Name : R02.2 (GT-2) Rated Voltage (Vn) : 100-120 V

Serial No. : MBHC16000089 Rated Current (In) : 1 /5 A

Manufacturer : GE Rated Aux. Voltage (Vx) : 110-250 VDC

Rly designation. : 87T-2 Frequency : 60 HZ

Model No. : T60 No. Of B/I & B/O : 16 I/P & 16 O/P

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED


1 Inspect for physical damage or defects.
2 Verify connections as per approved drawings.
3 Check tightness of all connections.
4 Check Ferrules
5 Check apparatus lists

3- ELECTRICAL TESTS
a) FUNCTION TEST:

ITEM DESCRIPTION CHECKED


1 Test switch / plug checked for correct function.
2 Alarm / Trip contacts checked.
3 All output contacts resistance measured <0.2Ω
4 Battery Fail Alarm Check
5 Date and Time Check

b) TRANSFORMER DATA:

Manufacturer : HYUNDAI
Rated Power: 50/67 MVA Vector Group: YNyn0+d
HV Rated Voltage 132 KV LV Rated Voltage 13.8 KV
HV Rated Current 218.7 A LV Rated Current 2092 A

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 2 of 20
c) GLOBAL PROTECTION SETTINGS:
Transformer rating 50MVA
winding “HV” Voltage 132 kV
winding “LV”Voltage 13.8 kV
CT Ratio winding “HV”: 600/1
CT Ratio winding “LV” : 3600/1
Neutral CT Ratio winding “HV”: 600/1 (HV REF)
Neutral CT Ratio winding “LV”: 3600/1 (LV REF)
Neutral CT Ratio winding “LV”: 800/1 (LV SBEF)
VT Nominal secondary : 115 V
% Impedance 22

d) BURDEN TEST:

Relay status Supply Voltage (VDC) Measured Current (mA) Calculated Burden (VA)
Not operated 125 0.195 24.375
Operated 125 0.205 25.625

e) SECONDARY INJECTION TESTS:

1.1- Current Measurement Check:


Injection Measured Value
Winding Phase Expected Value (A)
Value (A)
L1 1.0 A 600 599.1A
HV Side L2 1.0 A 600 599.5A
L3 1.0 A 600 599.7A
L1 1.0 A 3600 3.59kA
LV Side L2 1.0 A 3600 3.59kA
L3 1.0 A 3600 3.59kA
HV Neutral LN1 1.0 A 600 599.7A
LV Neutral LN2 1.0 A 3600 3.59kA
LV SBEF LN3 1.0 A 800 798.9A

1.2- Voltage Measurement Check:


Injection Expected Value Measured Value
Winding Phase
Value in Volts (kV) (kV)
R-N 66.4 76.21 76.22
Y-N 66.4 76.21 76.20
B-N 66.4 76.21 76.12
HV Side
R-Y 115 132.0 131.81
Y-B 115 132.0 131.82
B-R 115 132.0 132.01

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 3 of 20
2- INPUTS, OUTPUTS & LEDS CHECKS:

OUTPUT RELAY CHECKS


Output
Terminal No. Type Function Assigned sheet Result
No.
O/P-1 H1 NO SPARE --

O/P-2 H2 NO SPARE --

O/P-3 H3 NO SPARE --

O/P-4 H4 NO 87T + 64NP + 64NS 30

O/P-5 P1 NO 87T + 64NP + 64NS 30

O/P-6 P2 NO 51S + 51NS + LV SBEF 30

O/P-7 P3 NO 50/51P 30

O/P-8 P4 NO HV CBF Trip 33

O/P-9 U1 NO HV CBF Trip 33

O/P-10 U2 NO CBF INITIATION TO LV 33

O/P-11 U3 NO SPARE --

O/P-12 U4 NC CBF INITIATION TO LV 33

O/P-13 U5 NO SPARE --

O/P-14 U6 NO SPARE --

O/P-15 U7 NO SPARE --

O/P-16 U8 NO SPARE --

BINARY INPUT CHECKS


Input No. Terminal No. Function Assigned Sheet No. Result

Input-1 H5a – H5b HV CBF Initiation 27

Input-2 H5c – H5b LV CBF Initiation 27

Input-3 H6a – H5b Protn. OUT 27

Input-4 H6c – H5b VT MCB Trip 27


Mechanical Protn. Trip to CBF
Input-5 H7a – H7b 27
Initiation
Input-6 H7c – H7b 94T-2 Optd. 27

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 4 of 20

Input-7 H8a – H7b 86T-2 Optd. 27

Input-8 H8c – H7b SPARE 27

Input-9 P5a – P5b Relay DC Fail 28

Input-10 P5c – P5b Indication DC Fail 28

Input-11 P6a – P5b AC supply Fail 28

Input-12 P6c – P5b 132 kV BB Protn. Optd. 28

Input-13 P7a – P7b CBF Protn. Optd. 28

Input-14 P7c – P7b SPARE 28

Input-15 P8a – P7b SPARE 28

Input-16 P8c – P7b SPARE 28

LED CHECK
LED No. Allocation (Function Assigned) Result
LED 1 XFMR PCNT DIFF OP
LED 2 XFMR PCNT DIFF OP A
LED 3 XFMR PCNT DIFF OP B
LED 4 XFMR PCNT DIFF OP C
LED 5 XFMR INST DIFF OP
LED 6 XFMR INST DIFF OP A
LED 7 XFMR INST DIFF OP B
LED 8 XFMR INST DIFF OP C
LED 9 XFMR PCNT DIFF 2ND A
LED 10 XFMR PCNT DIFF 2ND B
LED 11 XFMR PCNT DIFF 2ND C
LED 12 XFMR PCNT DIFF 5TH A
LED 13 XFMR PCNT DIFF 5TH B
LED 14 XFMR PCNT DIFF 5TH C
LED 15 RESTD GND FT1 OP
LED 16 RESTD GND FT2 OP
LED 17 PHASE TOC1 OP
LED 18 PHASE TOC1 OP A

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 5 of 20

LED No. Allocation (Function Assigned) Result


LED 19 PHASE TOC1 OP B
LED 20 PHASE TOC1 OP C
LED 21 NEUTRAL TOC1 OP
LED 22 NEUTRAL TOC2OP
LED 23 GROUND TOC1 OP
LED 24 GROUND IOC1 OP
LED 25 HV CBF INIT On(H5a)
LED 26 BKR FAIL 1 T1 OP
LED 27 LV CBF INIT On(H5c)
LED 28 BKR FAIL 2 T1 OP
LED 29 TCS-2 FAIL On (VO6)
LED 30 PHASE TOC2 OP
LED 31 PHASE TOC2 OP A
LED 32 PHASE TOC2 OP B
LED 33 PHASE TOC2 OP C

3- DIFFERENTIAL PROTECTION

HV CT Matching Factor = (HV rated volt * HV CT ratio)


(LV rated volt * LV CT ratio)
= (132000 * 600) / (13800 * 3600)
M1 = 1.59

LV CT Matching Factor = (LV rated volt * LV CT ratio)


(LV rated volt * LV CT ratio)
= (13800 * 3600) / (13800 * 3600)
M2 = 1.00

Differential Protection Settings:


Winding “HV” CT matching factor – M1 1.59
Winding “LV” CT matching factor – M2 1.00
Vector group reference HV-LV 0
Zero sequence filter on winding “HV” Not within Zone ( Off )
Zero sequence filter on winding “LV” Not within Zone ( Off )
Pick Up 0.3 PU
Slope-1 30 %
Slope-2 80 %
Break point-1 2 PU
Break point-2 3 PU
Instantaneous Pick up 5 PU
Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 6 of 20

2nd Harmonic Inrush Current 10%


5th harmonic Over fluxing 20%
HV CT Terminals* Source-1
LV CT Terminals* Source-2

3.1 Checking the first section of tripping characteristics: (Zero Sequence Filter Off for All Windings)
Test method: (Zero sequence filtering disabled during this test for all windings, Vec. Group HV, LV=0).
Expected Operating Current = 0.3/M1 = 0.3/1.59 = 0.188A @HV side
=0.3/M2 =0.3/1 = 0.3A @LV side
Pick Up Drop off
Test Winding Expected operating current
current current
1-phase (L1 phase) HV 0.188 0.189 0.176
1-phase (L1 phase) LV 0.300 0.301 0.281
1-phase (L2 phase) HV 0.188 0.190 0.176
1-phase (L2 phase) LV 0.300 0.301 0.281
1-phase (L3 phase) HV 0.188 0.189 0.176
1-phase (L3 phase) LV 0.300 0.301 0.281
* Pick-up: formula ±0.5% of reading or ±1% of rated
* Drop-off: 97% to 98% of pick up (GE-T60 instruction manual page no: 56 of 788)

3.2) Checking the first section of tripping characteristics: (Zero Sequence Filter On for All Windings)
Test method:
(Zero sequence filtering enable during this test for all windings, Vec. Group HV, LV=0).
Expected Operating Current = (0.3/M1) / (2/3) = (0.3/1.59) / 0.67 = 0.281A @HV side
= (0.3/M2) / (2/3) = (0.3/1) / 0.67= 0.447A @LV side

(Factor of 0.67 for zero seq. filtering for single phase injection)

Test Winding Expected operating current Pick Up current Drop of current


1-phase (L1 phase) HV 0.281 0.283 0.265
1-phase (L1 phase) LV 0.447 0.451 0.422
1-phase (L2 phase) HV 0.281 0.283 0.265
1-phase (L2 phase) LV 0.447 0.451 0.422
1-phase (L3 phase) HV 0.281 0.283 0.265
1-phase (L3 phase) LV 0.447 0.451 0.422
* Pick-up: formula ±0.5% of reading or ±1% of rated
* Drop-off: 97% to 98% of pick up (GE-T60 instruction manual page no: 56 of 788)

3.3) Checking of second/third section of tripping characteristic:


Test method: (Zero sequence filtering disabled during test for both sides, Vec. Group =0).

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 7 of 20

Calculations:
Ib measured = Ib= (I1*M1+I2*M2)/2.
Id measured= (I1*M1)-(I2*M2)
First section of characteristics: Id calculated = K1*Ib
Third Section of characteristics: Id calculated = K2*Ib
A- First section of characteristics:

Id calculated = K1*Ib
Ib = 1.5 P.U
at unstable case: Id = 0.3 * 1.5 = 0.45 P.U
at stable case: Id = 0
I1 = (Id-+I2)/M1 I2 = Ib = 1.5A
I1 = (0.0+1.5)/1.59 = 0.943A

B- Second Section of characteristics:


I restraint between break point1 &2
Ib = 2.5 P.U
at stable case: Id = 0
I1 = (Id-+I2)/M1 I2 = Ib = 2.5A
I1 = (0.0+2.5)/1.59 = 1.572A

C- Third Section of characteristics:

Id calculated = K2*Ib
Ib = 3.5 P.U
at unstable case: Id = 0.8 * 3.5 = 2.8 P.U
at stable case: Id = 0
I1 = (Id-+I2)/M1 I2 = Ib = 3.5A
I1 = (0.0+3.5)/1.59 = 2.201A

Note: varied the phase angle of HV or LV current. Keep current magnitude constant for fix the bias constant.

L1-Phase

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 8 of 20

Winding Winding
Section of Restrain current Differential current
“HV” “LV” Measured
tripping ( with respect to Iref) ( with respect to Iref)
Injected Injected %Slope
char. Under
Current Current (Id/Ib)
test Calculated Measured Calculated Measured
A A
min pickup 0.314 0.500 0.5 0.499 0.30 0.301 Min. pick up
First (30%) 0.943 1.500 1.5 1.499 0.45 0.450 30.02 %
Second
1.572 2.500 2.5 2.500 1.430 57.20 %
(30%-80%) 1.5(approx.)
Third (80%) 2.201 3.500 3.5 3.500 2.80 2.807 80.20 %

L2-Phase

Winding Winding
Section of Restrain current Differential current
“HV” “LV” Measured
tripping ( with respect to Iref) ( with respect to Iref)
Injected Injected %Slope
char. Under
Current Current (Id/Ib)
test Calculated Measured Calculated Measured
A A
min pickup 0.314 0.500 0.5 0.499 0.30 0.301 Min. pick up
First (30%) 0.943 1.500 1.5 1.499 0.45 0.449 29.95 %
Second
1.572 2.500 2.5 2.500 1.430 57.2 %
(30%-80%) 1.5(approx.)
Third (80%) 2.201 3.500 3.5 3.501 2.80 2.806 80.14 %

L3-Phase
Winding Winding
Section of Restrain current Differential current
“HV” “LV” Measured
tripping ( with respect to Iref) ( with respect to Iref)
Injected Injected %Slope
char. Under
Current Current (Id/Ib)
test Calculated Measured Calculated Measured
A A
min pickup 0.314 0.500 0.5 0.499 0.30 0.300 Min. pick up
First (30%) 0.943 1.500 1.5 1.499 0.45 0.450 30.02 %
Second
1.572 2.500 2.5 2.500 1.427 57.08 %
(30%-80%) 1.5(approx.)
Third (80%) 2.201 3.500 3.5 3.502 2.80 2.805 80.09 %
* Pick-up: formula ±0.5% of reading or ±1% of rated
* Drop-off: 97% to 98% of pick up (GE-T60 instruction manual page no: 56 of 788)

3.4) checking of tripping Time: Expected Op Time: < 40 msec

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 9 of 20

Injected current = 1 Amps Operating time(msec) LED

L1 HV 20
L2 HV 19
L3 HV 21
L1 LV 20
L2 LV 19
L3 LV 20

3.5) Magnetizing Inrush Restraint (2nd Harmonic)

HV Side: I2h setting=10%


Injected 2nd
Applied Phase Injected (I1) Current 2nd Harmonic %
Harmonic Current
L1-Phase 1.0 0.100 10 %
L2-Phase 1.0 0.100 10 %
L3-Phase 1.0 0.100 10 %

LV Side: I2h setting=10%


Injected 2nd
Applied Phase Injected (I1) Current 2nd Harmonic %
Harmonic Current
L1-Phase 1.0 0.100 10 %
L2-Phase 1.0 0.100 10 %
L3-Phase 1.0 0.100 10 %
Note: Cross blocking verified: OK

3.6 Over fluxing 5th Harmonic Blocking:

HV Side: 20%
Injected 5th
Applied Phase Injected (I1) Current 5th Harmonic %
Harmonic Current
L1-Phase 1.0 0.199 19.9 %
L2-Phase 1.0 0.199 19.9 %
L3-Phase 1.0 0.199 19.9 %

LV Side: 20%
Injected 5th
Applied Phase Injected (I1) Current 5th Harmonic %
Harmonic Current
L1-Phase 1.0 0.199 19.9 %
L2-Phase 1.0 0.199 19.9 %
L3-Phase 1.0 0.199 19.9 %

3.7) INST. Differential: (Expected time less than 25 msec)


Expected Operating Current = (IS/M1) = 5/1.59 = 3.14A @HV side

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 10 of 20
= (IS/M2) = 5/1 = 5 A @LV side

Expected operating Time(msec) at 3*


Phase Pickup (Amps) LED
current I set
L1-HV 3.14 3.139 18
L2-HV 3.14 3.139 17
L3-HV 3.14 3.139 18
L1-LV 5.0 4.999 17
L2-LV 5.0 4.999 17
L3-LV 5.0 5.001 16
* Pick-up: formula ±0.5% of reading or ±1% of rated
* Drop-off: 97% to 98% of pick up
* operating time ≤ 20 ms @ 3 * pick up at 60Hz (GE-T60 instruction manual page no: 56 of 788)

4. Restricted Earth Fault 64NP & 64NS:

4.1) HV REF:

Pick up 0.08 A
Slope 40 %
Op.time 0.8 A
Source HV

4.1.1) Pick Up And Drop Off Tests:


Pick up Value Drop off Value
Injected Current at
Calculated Measured Measured
R 0.080 0.081 0.078
Y 0.080 0.081 0.078
B 0.080 0.080 0.078
N 0.080 0.080 0.078
* Pick-up: formula ±0.5% of reading or ±1% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

4.1.2) Trip Time Test:


REF Relay ( A )
Injected Current at Expected time Measured time at 2 X IREF
(m Sec) (m Sec)
R 0 20
Y 0 20
B 0 21
N 0 19
* operating time ≤ 1 power system cycle (GE-T60 instruction manual page no: 57 of 788)
4.1.3) Slope Test:

Slope= Id/Ib
Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 11 of 20
Note: varied the phase angle of Phase or Neutral current. Keep current magnitude constant for fix the bias constant.

Injected Current in A Calculated values in A Measured Values in A


Phase
IPH IN I diff REF I diff REF I Bias REF Slope reg.
0.1 0.1 48.0 47.88 109.6 min. pick up
R
0.5 0.5 222.1 222.2 555.3 40.0 %
0.1 0.1 48.0 47.9 109.6 min. pick up
Y
0.5 0.5 222.7 221.2 556.8 39.73 %
0.1 0.1 48.0 47.9 109.7 min. pick up
B
0.5 0.5 222.5 221.8 556.1 39.88 %
* Pick-up: formula ±0.5% of reading or ±1% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

4.2). LV REF:

Pick up 0.08 A
Slope 40 %
Op.time 0.8 A
Source LV

4.2.1) Pick Up And Drop Off Tests:


Pick up Value Drop off Value
Injected Current at
Calculated Measured Measured
R 0.08 0.08 0.078
Y 0.08 0.08 0.078
B 0.08 0.08 0.078
N 0.08 0.08 0.078
* Pick-up: formula ±0.5% of reading or ±1% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

4.2.2) Trip Time Test:


Injected Current at REF Relay ( A )
Expected time Measured time at 2 X IREF
Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 12 of 20

(m Sec) (m Sec)
R 0 20
Y 0 19
B 0 19
N 0 18
* operating time ≤ 1 power system cycle (GE-T60 instruction manual page no: 57 of 788)

4.2.3) Slope Test:

Slope= Id/Ib
Note: varied the phase angle of Phase or Neutral current. Keep current magnitude constant for fix the bias
constant.

Injected Current in A Calculated values in A Measured Values in A


Phase
IPH IN I diff REF I diff REF I Bias REF Slope reg.
0.1 0.1 288.0 287.5 657.10 min. pick up
R
0.5 0.5 1334.8 1330.1 3336.6 39.86 %
0.1 0.1 288.0 284.9 657.80 min. pick up
Y
0.5 0.5 1334.4 1327.4 3335.8 39.79 %
0.1 0.1 288.0 287.7 657.90 min. pick up
B
0.5 0.5 1334.1 1332.1 3335.1 39.97 %
* Pick-up: formula ±0.5% of reading or ±1% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

5. HV OVERCURRENT & EARTH FAULT

5.1) Winding-1 OVERCURRENT (51)


- Pick-Up: ±5% of 1.05 I set or ± 20 mA.
- Drop-Off: ±5% of 0.95 I set or ± 20 mA.

Pick-Up and Drop-Off Test:


Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A B C A B C
0.5 P.U 0.501 0.501 0.501 0.487To 0.502 0.486 0.486 0.486 0.485-0.490
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)
Timing Test:
Current Time meas. in sec.
IEC TMS/TIME Time cal. in sec.
multiple Rph Yph Bph 3ph

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 13 of 20

2 2.507 2.548 2.533 2.536 2.532


INV.A 5 0.25 1.069 1.092 1.091 1.090 1.085
8 0.824 0.844 0.839 0.848 0.845
2 3.375 3.414 3.408 3.410 3.412
INV.B 5 0.25 0.843 0.865 0.860 0.866 0.864
8 0.482 0.499 0.503 0.503 0.499
2 6.666 6.730 6.724 6.733 6.720
INV.C 5 0.25 0.833 0.857 0.855 0.856 0.851
8 0.317 0.337 0.333 0.337 0.336
2 0.444 0.469 0.467 0.468 0.464
ST.INV. 5 0.25 0.188 0.209 0.207 0.204 0.201
8 0.144 0.159 0.161 0.166 0.159
2 1.000 1.022 1.016 1.024 1.016
DFT 5 1.0 1.000 1.014 1.015 1.015 1.009
8 1.000 1.019 1.013 1.021 1.021
* operating time ±3.5% of operating time or ± 1/2 power system cycle (GE-T60 instruction manual page no: 57 of 788)
T = (K*Tm) / ((I/I s) ^ α – 1)) sec.
For Inv.A: K=0.14, α=0.02 For Inv.B: K=13.5, α=1 For Inv.C: K=80, α=2 For STI: K=0.05, α=0.04
(GE-T60 instruction manual page no: 365 of 788)

5.2) Winding-1 OVERCURRENT (50)


Pick-Up and Drop-Off Test:
Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A B C A B C
2.0 2.002 2.002 2.002 1.99 - 2.01 1.942 1.942 1.942 1.94 - 1.96
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing Test:
Current Time meas. in sec.
IEC TIME Time cal. in sec.
multiple Rph Yph Bph 3ph
DT 2 0.0 0.00 0.016 0.019 0.019 0.015
* operating time ±3% of operating time or ± 1/4 power system cycle (GE-T60 instruction manual page no: 57 of 788)

5.3 Winding-1 Earth fault (51N)


Pick-Up and Drop-Off Test:
Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
N N
0.25A 0.251 0.249 – 0.251 0.244 0.242 – 0.245
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing Test

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 14 of 20

Current
IEC TMS/TIME Time cal. in sec. Time meas. in sec.
multiple

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 15 of 20

2.507 2.579
2 1.069 1.106
INV.A 0.25
5 0.824 0.857
8 3.375 3.490
2 0.843 0.882
INV.B 0.25
5 0.482 0.510
8 6.666 6.905
2 0.833 0.868
INV.C 0.25
5 0.317 0.345
8 0.444 0.484
2 0.188 0.215
ST.INV. 0.25
5 0.144 0.172
8 1.000 1.026
2 1.000 1.024
DFT 1.0
5 1.000 1.019
* operating time ±3.5% of operating time or ± 1/2 power system cycle (GE-T60 instruction manual page no: 57 of 788)
T = (K*Tm) / ((I/I s) ^ α – 1)) sec.
For Inv.A: K=0.14, α=0.02 For Inv.B: K=13.5, α=1 For Inv.C: K=80, α=2 For STI: K=0.05, α=0.04
(GE-T60 instruction manual page no: 365 of 788)

5.4) Winding-1 Earth fault (50N)

Pick-Up and Drop-Off Test:


Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A A
2.0A 2.137 1.99 – 2.01 2.073 1.94 – 1.96
* For single phase injection Pick-up: 0.9375 *I injected (GE-T60 instruction manual page no: 376 of 788)
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing test
Current
IEC TIME Time cal. in sec. Time meas. in sec.
multiple
DT 2 0.00 0.00 0.021
* operating time ±3% of operating time or ± 1/4 power system cycle (GE-T60 instruction manual page no: 57 of 788)

6: LV OVERCURRENT & EARTH FAULT

6.1) Winding-2 OVERCURRENT (51)

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 16 of 20

Pick-Up and Drop-Off Test:


Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A B C A B C
0.5A 0.501 0.502 0.502 0.498 – 0.502 0.486 0.486 0.486 0.485 – 0.490
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing Test :

Current Time meas. in sec.


IEC TMS/TIME Time cal. in sec.
multiple Rph Yph Bph 3ph
2 2.530 2.536 2.535 2.539 2.536
INV.A 5 0.25 1.091 1.089 1.089 1.089 1.086
8 0.843 0.845 0.843 0.846 0.845
2 3.397 3.414 3.408 3.415 3.413
INV.B 5 0.25 0.864 0.864 0.859 0.861 0.866
8 0.501 0.507 0.505 0.502 0.500
2 6.678 6.740 6.736 6.726 6.719
INV.C 5 0.25 0.850 0.851 0.855 0.855 0.851
8 0.335 0.336 0.337 0.343 0.335
2 0.444 0.472 0.470 0.475 0.468
ST.INV. 5 0.25 0.188 0.209 0.200 0.203 0.204
8 0.144 0.162 0.158 0.162 0.158
2 1.000 1.018 1.021 1.020 1.021
DFT 5 1.000 1.000 1.020 1.010 1.022 1.011
8 1.000 1.010 1.021 1.010 1.014
* operating time ±3.5% of operating time or ± 1/2 power system cycle (GE-T60 instruction manual page no: 57 of 788)
T = (K*Tm) / ((I/I s) ^ α – 1)) sec.
For Inv.A: K=0.14, α=0.02 For Inv.B: K=13.5, α=1 For Inv.C: K=80, α=2 For STI: K=0.05, α=0.04
(GE-T60 instruction manual page no: 365 of 788)

6.2) Winding-2 OVERCURRENT (50)

Pick-Up and Drop-Off Test:


Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A B C A B C
2.0 2.002 2.002 2.002 1.997 – 2.030 1.944 1.944 1.944 1.994 – 1.996
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing test
Current Time meas. in sec.
IEC TIME Time cal. in sec.
multiple R ph Y ph B ph 3ph

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 17 of 20

DT 2 0.00 0.00 0.017 0.014 0.018 0.016


* operating time ±3% of operating time or ± 1/4 power system cycle (GE-T60 instruction manual page no: 57 of 788)

6.3) Winding-2 Earth fault (51N)

Pick-Up and Drop-Off Test:


Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
N N
0.25A 0.251 0.249 - 0251 0.243 0.242 – 0.245
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing test
Current
IEC TMS/TIME Time cal. in sec. Time meas. in sec.
multiple
2 2.530 2.580
5 0.25 1.091 1.109
INV.A
8 0.843 0.852
2 3.397 3.475
5 0.25 0.864 0.880
INV.B
8 0.501 0.510
2 6.678 6.891
5 0.25 0.850 0.875
INV.C
8 0.335 0.344
2 0.444 0.484
5 0.25 0.188 0.215
ST.INV.
8 0.144 0.172
2 1.000 1.027
5 1.0 1.000 1.020
DFT
8 1.000 1.020
* operating time ±3.5% of operating time or ± 1/2 power system cycle (GE-T60 instruction manual page no: 57 of 788)
T = (K*Tm) / ((I/I s) ^ α – 1)) sec.
For Inv.A: K=0.14, α=0.02 For Inv.B: K=13.5, α=1 For Inv.C: K=80, α=2 For STI: K=0.05, α=0.04
(GE-T60 instruction manual page no: 365 of 788)

6.4) Winding-2 Earth fault (50N)


Pick-Up and Drop-Off Test:
Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A A
2.0 2.136 1.99 – 2.01 2.073 1.94 – 1.96
* For single phase injection Pick-up: 0.9375 *I injected (GE-T60 instruction manual page no: 376 of 788)

* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated


* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 18 of 20
Timing test
Current
IEC TIME Time cal. in sec. Time meas. in sec.
multiple
DT 2 0.00 0.00 0.020
* operating time ±3% of operating time or ± 1/4 power system cycle (GE-T60 instruction manual page no: 57 of 788)

7. LV Stand By Earth Fault (51NS):

Pick-Up and Drop-Off Test:


Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A A
0.1 0.101 0.099 – 0.101 0.098 0.097 – 0.098
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing test
Current
IEC TIME Time cal. in sec. Time meas. in sec.
multiple
DT 2 1.0 1.0 1.029
* operating time ±3.5% of operating time or ± 1/2 power system cycle (GE-T60 instruction manual page no: 57 of 788)

7.2) LV Stand By Earth Fault (50NS):

Pick-Up and Drop-Off Test:


Pick-Up (Amps) Drop-Off (Amps)
I Setting Limit Limit
A A
1.0 1.001 1.97 – 2.03 0.972 1.94 – 1.96
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing test
Current
IEC TIME Time cal. in sec. Time meas. in sec.
multiple
DT 2 0.00 0.00 0.016
* operating time ±3% of operating time or ± 1/4 power system cycle (GE-T60 instruction manual page no: 57 of 788)

8. Neutral Current Alarm :

Pick-Up and Drop-Off Test:


Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 19 of 20

Pick-Up (Amps) Drop-Off (Amps)


I Setting Limit Limit
A A
0.1 0.101 0.1 0.098 0.097 – 0.098
* Pick-up: formula ±0.5% of reading or ±0.4% of rated @ I < 2*CT rated
* Pick-up: formula ±1.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 57 of 788)

Timing test
Current
IEC TIME Time cal. in sec. Time meas. in sec.
multiple
DT 2 5.0 5.0 5.05
* operating time ±3.5% of operating time or ± 1/2 power system cycle (GE-T60 instruction manual page no: 57 of 788)

9. HV CBF Protection 50BF:

I > 0.10 Time-2 = 150 msec.

PICK UP AND DROP OFF TEST


PICK-UP CURRENT DROP-OFF CURRENT
SETTING PHASE PHASE
VALUE
R Y B R Y B
0.10 0.101 0.101 0.101 0.098 0.098 0.098
* Pick-up: formula ±0.75% of reading or ±2% of rated @ I < 2*CT rated
* Pick-up: formula ±2.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 59 of 788)

TIMING TEST:

I set Stage-1 Set Time Operating Time at 2 I set (msec)


AMPS (msec) R Y B
0.10 150 169 170 169

10. LV CBF Protection 50BF:

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017
Commissioning Service Department
Commissioning Standard Test Formats
Description : Pre check – 87T Relay Test Record No. :
Equip. No. : 87T-2 (R02.2) Contract no : GOSI-A-16-1
Contractor : CAPITAL LIGHTS CO. Drawing Ref: CD-814828
Substation No: 8340 Sheet No : Page 20 of 20

I > 0.10 Time-2 = 150 msec.

PICK UP AND DROP OFF TEST


PICK-UP CURRENT DROP-OFF CURRENT
I SETTING PHASE PHASE
VALUE
R Y B R Y B
0.10 A 0.101 0.101 0.101 0.098 0.098 0.098
* Pick-up: formula ±0.75% of reading or ±2% of rated @ I < 2*CT rated
* Pick-up: formula ±2.5% of reading @ I > 2*CT rated (GE-T60 instruction manual page no: 59 of 788)

TIMING TEST:

I set Stage-1 Set Time Operating Time at 2 I set (msec)


AMPS (msec) R Y B
0.10 150 170 169 168

TEST EQUIPMENT USED

EQUIPMENT SERIAL NO DUE DATE


FREJA 300 1102381 Nov 2017 21
FLUKE METER 23210213 Oct 2017 05

Tested by Reviewed by
Name: P Ranjitkumar (PFL-017)
Signature:
Date: 02/08/2017