REV615 - Capacitor
REV615 - Capacitor
REV615 - Capacitor
1MRS757952 A
Contents
1. Description.....................................................................3
2. Standard configurations.................................................3
3. Protection functions........................................................7
4. Application.....................................................................7
6. Control.........................................................................11
7. Measurements.............................................................12
8. Disturbance recorder....................................................12
9. Event log......................................................................12
25. Tools...........................................................................45
28. Certificates..................................................................49
13. Self-supervision...........................................................13
29. References..................................................................49
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
Copyright 2014 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
ABB
1. Description
REV615 is a dedicated capacitor bank IED (intelligent
electronic device) designed for the protection, control,
measurement and supervision of capacitor banks used for
compensation of reactive power in utility substations and
industrial power systems. REV615 can also be used for
protection of harmonic filter circuits, if the highest significant
harmonic component is the 11th. REV615 is a member of
ABBs Relion product family and part of its 615 protection
and control product series. The 615 series IEDs are
characterized by their compactness and withdrawable-unit
design.
Re-engineered from the ground up, the 615 series has been
designed to unleash the full potential of the IEC 61850
standard for communication and interoperability between
substation automation devices.
The IED provides main protection for single Y, double Y, and
H-bridge connected capacitor banks and harmonic filters in
distribution networks.
Depending on the chosen standard configuration, the IED is
adapted for the protection of H-bridge connected or double
star connected shunt capacitor banks. Once the standard
configuration IED has been given the application-specific
settings, it can directly be put into service.
ABB
1MRS757952 A
Issued: 2014-01-24
Revision: A
The 615 series IEDs support a range of communication
protocols including IEC 61850 with GOOSE messaging, IEC
61850-9-2 LE (except in RED615), IEC 60870-5-103,
Modbus and DNP3. Profibus DPV1 communication protocol
is supported by using the protocol converter SPA-ZC 302.
2. Standard configurations
REV615 is available in two alternative standard
configurations. The standard signal configuration can be
altered by means of the signal matrix or the graphical
application functionality of the Protection and Control IED
Manager PCM600. Further, the application configuration
functionality of PCM600 supports the creation of multi-layer
logic functions using various logical elements, including timers
and flip-flops. By combining protection functions with logic
function blocks, the IED configuration can be adapted to userspecific application requirements.
The IED is delivered from the factory with default connections
described in the functional diagrams for binary inputs, binary
outputs, function-to-function connections and alarm LEDs.
The positive measuring direction of directional protection
functions is towards the outgoing feeder.
REV615
1MRS757952 A
PROTECTION
LOCAL HMI
ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization
Master Trip
Lockout relay
94/86
ESC
Clear
R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
3
I2>
46
3Ith>T
49T
3I>>>
50P/51P
STANDARD
CONFIGURATION
ESC
Clear
AND
R
L
OR
3
ARC
50L/50NL
3I>3I<
51C
2
dI>C
51NC-1
3I>/Io>BF
51BF/51NBF
3dI>C
51NC-2
3I>
51P-1
MCS 3I
MCS 3I
CBCM
CBCM
2
TD>
55TD
3I>>
51P-2
CONDITION MONITORING
AND SUPERVISION
Io
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus
IEC 60870-5-103
DNP3
1 0 1 0 0
1 0 1 1 0
1 1 0 0 1
1 0 1 1 0
1 0 1 0 0
1 0 1 1 0
1 1 0 0 1
1 0FX1(LC)
1 0
(RJ45),
OPTS
OPTM
Interfaces:
Ethernet: TX
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP
TCS
TCM
Io
Io
Io>>>
50N/51N
Io>
51N-1
Io>>
51N-2
Ctrl 2)
Ind 3)
DC
ES
2)
3)
1
1
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
1
0
1
1
1
0
1
1
MEASUREMENT
CB
1)
0
0
1
1
0
0
1
1
- I, Io
- Limit value supervision
- Load prole record
- RTD/mA measurement (optional)
- Symmetrical components
1)
Current transformer
Voltage transformer
1)
PQM3I
PQM3I
REMARKS
18
MAP
MAP
6xRTD
2xmA
Optional
function
3 No. of
instances
Calculated
value
Io/Uo
OR Alternative
function to be
dened when
ordering
3Iunb
GUID-DFC320F5-AD45-4D28-8632-C3FB2CFDCB06 V2 EN
Figure 1.
ABB
0
0
0
0
0
0
0
0
0
1 0
0
0 1 0 1 0 0
1 0
0
UL1UL2UL3
Uo
REV615
1MRS757952 A
PROTECTION
LOCAL HMI
ALSO AVAILABLE
Conguration
System
HMI
Time
Authorization
Master Trip
Lockout relay
94/86
ESC
Clear
R
L
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
3
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
1
0
1
1
1
0
1
1
0
0
0
0
0
0
0
0
I2>
46
3Ith>T
49T
3I>>>
50P/51P
STANDARD
CONFIGURATION
ESC
Clear
AND
R
L
OR
3
ARC
50L/50NL
0
1 0
3I>3I<
51C
0
0 1 0 1 0 0 0 1 1 0 0 1 1 0 0
1 0
dI>C
51NC-1
3I>/Io>BF
51BF/51NBF
3dI>C
51NC-2
TD>
55TD
3I>>
51P-2
3I
CONDITION MONITORING
AND SUPERVISION
CBCM
CBCM
FUSEF
60
3I>
51P-1
OPTS
OPTM
Io
COMMUNICATION
Protocols:
IEC 61850-8-1/-9-2LE
1 0
Modbus
1 0
IEC 60870-5-103 1 1
1 0
DNP3
MCS 3I
MCS 3I
1
1
Io>>
51N-2
Io>
67N-1
Io>>
67N-2
TCS
TCM
Uo
Ctrl 2)
Ind 3)
DC
ES
UL1UL2UL3
2)
3U<
27
3U>
59
U2>
47O3
U1<
47U+
Uo>
59G
UL1UL2UL3
3)
PQM3U
PQM3V
1
0
0
0
1
0
0
0
0
1
1
1
0
1
1
1
0
1
1
1
0
1
1
1
1
1
0
0
1
1
0
0
PQM3I
PQM3I
1
1
1
1
1
1
1
1
MEASUREMENT
CB
1)
0
0
1
1
0
0
1
1
Interfaces:
1
1
Ethernet: TX (RJ45),
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
D-sub 9, IRIG-B
Redundant protocols:
HSR
PRP
RSTP
Io
Io
1 0 0
1 1 0
0 0 1
1 1 0
0 1 0 0
0 1 1 0
1 0 0 1
0 1(LC)
1 0
FX
1)
Current transformer
Voltage transformer
1)
PQMU
PQMV
REMARKS
18
MAP
MAP
2xRTD
1xmA
Optional
function
3 No. of
instances
Calculated
value
Io/Uo
OR Alternative
function to be
dened when
ordering
Iunb
GUID-393D9B25-06C8-42AE-A7D0-642BBCB89DBE V1 EN
Figure 2.
Std. conf.
Capacitor bank overload and unbalance protection, non-directional overcurrent and non-directional earth-fault protection, CB
control and condition monitoring
Capacitor bank overload and unbalance protection, non-directional overcurrent and directional earth-fault protection, voltage
based protection, CB control and condition monitoring
ABB
1
0
1
1
1
0
1
1
0
0
0
0
0
0
0
0
0
1 0
0
0 1 0 1
1 0
0
1MRS757952 A
IEC 61850
PHLPTOC
PHHPTOC
PHIPTOC
EFLPTOC
2 2)
EFHPTOC
1 2)
Protection1)
1 2)
2)
EFIPTOC
DEFLPDEF
DEFHPDEF
NSPTOC
ROVPTOV
PHPTUV
PHPTOV
PSPTUV
NSPTOV
Three-phase thermal overload protection for power transformers, two time constants
T2PTTR
CCBRBRF
Master trip 6)
TRPPTRC
2 (5)
2 (5)
Arc protection
ARCSARC
(3)
(3)
MAPGAPC
18
18
COLPTOC
8)
CUBPTOC
2 2)3)
1 2)3)
2
2
3 3)4)5)
4)
HCUBPTOC
1 4)
SRCPTOC
(1) 9)
(1) 10)
Power quality
Current total demand distortion
CMHAI
VMHAI
(1) 10)
Voltage variation
PHQVVR
(1) 10)
Control
Circuit-breaker control
CBXCBR
Disconnector control 4)
DCXSWI
4)
ESXSWI
DCSXSWI
ESSXSWI
SSCBR
TCSSCBR
CCRDIF
SEQRFUF
MDSOPT
Disturbance recorder
RDRE
LDPMSTA
CMMXU
CSMSQI
RESCMMXU
VMMXU
RESVMMXU
VSMSQI
PEMMXU
RTD/mA measurement
XRGGIO130
Condition monitoring
Measurement
1
2
1 4)
1
(1)
(1)
ABB
1MRS757952 A
IEC 61850
Frequency measurement
FMMXU
SMVSENDER
B
1
(1)
The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
Io selectable by parameter, "Io measured" as default
Uo selectable by parameter, "Uo measured" as default
Must be added with Application Configuration to be available in Signal Matrix and in IED
"Uob measured" is always used for unbalance protection with unearthed single Y-connected capacitor bank.
Master trip included and connected to the corresponding HSO in the configuration only when the BIO0007 module is used. If the ARC option is selected additionally, ARCSARC is
connected to the corresponding master trip input in the configuration.
7)
Multi-purpose protection is used, for example, for RTD/mA-based protection or analog GOOSE.
8)
The Iunb measurement values are taken from this block and put in the Measurement view.
9)
Power quality option includes only current total demand distortion.
10) Power quality option includes current total demand distortion, voltage total harmonic distortion and voltage variation.
11) Unbalance voltage measurement for capacitor bank
12) Only available with COM0031-COM0034
3. Protection functions
The IED offers three phase overload protection with
undercurrent and reconnection inhibit functionality for
capacitors, single or three phase current based unbalance
protection for capacitors including compensation for natural
unbalance and a current based switching resonance
protection.
The IED features non-directional overcurrent and thermal
overload protection as well and non-directional earth-fault
protection.
Additionally, the standard configuration B includes directional
earth-fault protection, residual voltage protection, overvoltage
and undervoltage protection functions.
Enhanced with optional hardware and software, the IED also
features three light detection channels for arc fault protection
of the circuit breaker, busbar and cable compartment of
metal-enclosed indoor switchgear.
The arc-fault protection sensor interface is available on the
optional communication module. Fast tripping increases staff
safety and security and limits material damage in an arc fault
situation. A binary input and output module can be selected
as an option - having three high speed binary outputs (HSO) it
further decreases the total operate time with typically 4...6 ms
compared to the normal power outputs.
4. Application
REV615 is intended for protection of capacitor banks used for
reactive power compensation in utility substations and
industrial power systems. REV615 offers protection
functionality especially for H-bridge, double Y and single Y
connected capacitor banks and the feeder cable.
ABB
1MRS757952 A
REV615
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I
ESC
Clear
Std. conf.
R
L
Io
ANSI
IEC
50L/50NL
ARC
50P/51P
3I>>>
51C
3I> 3I<
51NC-2
3dI>C
51P/51N
3I>/Io>
55TD
TD>
3Iunb
GUID-B7F0755C-006A-4806-91D3-8C290EE3ECA0 V1 EN
Figure 3.
capacitor bank. O/C and E/F are used for protection of the
feeder cable and capacitor bank combination.
3U
Uo
3I
A
REV615
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
Io
ESC
Clear
R
L
Std. conf.
ANSI
IEC
27/59/59G 3U</3U>/Uo>
50L/50NL
ARC
50P/51P
3I>>>
51C
3I> 3I<
51NC-1
dI>C
51P/51N
3I>/Io>
55TD
TD>
67N
Io>
Iunb
GUID-5F33A1B7-2B6F-4CFA-9DD6-71E633C46846 V1 EN
Figure 4.
Protection of a double star connected capacitor bank in a distribution network with a compensated or isolated neutral
the capacitor bank. O/C and directional E/F are used for
protection of the feeder cable and capacitor bank
combination.
ABB
1MRS757952 A
3U
Uo
3I
A
REV615
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
ESC
Clear
Io
R
L
Std. conf.
ANSI
IEC
27/59/59G 3U</3U>/Uo>
49T
3Ith>T
50L/50NL
ARC
50P/51P
3I>>>
51C
3I> 3I<
51NC-2
3dI>C
51P/51N
3I>/Io>
55TD
TD>
3Iunb
GUID-30461537-C53B-460B-BA27-9667D6977F77 V1 EN
Figure 5.
3U
Uo
3I
A
REV615
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
Io
ESC
Clear
R
L
Std. conf.
ANSI
IEC
27/59/59G 3U</3U>/Uo>
50L/50NL
ARC
50P/51P
3I>>>
51C
3I> 3I<
51P
3I>
55TD
TD>
67N
Io>
Uob
GUID-9C6F9938-FB13-4615-842A-9606411B47FC V1 EN
Figure 6.
ABB
1MRS757952 A
Version
System 800xA
5.1 or later
10
ABB
1MRS757952 A
ABB
MicroSCADA Pro/
System 800xA
COM600
Web HMI
Ethernet switch
PCM600
IEC 61850
COM600
Web HMI
Ethernet switch
PCM600
IEC 61850
GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V1 EN
Figure 7.
ABB power system example using Relion IEDs, Grid Automation controller COM600 and MicroSCADA Pro/System 800xA
6. Control
REV615 integrates functionality for the control of a circuit
breaker via the front panel HMI or by means of remote
controls. In addition to the circuit breaker control the IED
features two control blocks intended for motor-operated
control of disconnectors or circuit breaker truck and their
position indications.
The IED has one control block intended for motor-operated
control of one earthing switch control and its position
indication. Two physical binary inputs and two physical binary
outputs are needed in the IED for each controllable primary
device taken into use. The number of unused binary inputs
and binary outputs varies, depending on the chosen standard
configuration of the IED. Further, some standard
configurations offer optional hardware modules that increase
the number of available binary inputs and outputs.
If the amount of available binary inputs and / or outputs of the
chosen standard configuration is not sufficient, the following
alternatives are recommended:
ABB
12
1MRS757952 A
9. Event log
To collect sequence-of-events information, the IED has a nonvolatile memory with a capacity of storing 1024 events with
associated time stamps. The non-volatile memory retains its
data also in case the IED temporarily loses its auxiliary supply.
The event log facilitates detailed pre- and post-fault analyses
of feeder faults and disturbances. The increased capacity to
process and store data and events in the IED offers
prerequisites to support the growing information demand of
future network configurations.
The sequence-of-events information can be accessed either
locally via the user interface on the IED front panel, or
remotely via the communication interface of the IED. The
information can also be accessed using the Web browserbased user interface, either locally or remotely.
10. Recorded data
The IED has the capacity to store the records of the 128
latest fault events. The records enable the user to analyze the
power system events. Each record includes current, voltage
and angle values, time stamp and so on. The fault recording
can be triggered by the start signal or the trip signal of a
protection block, or by both. The available measurement
modes include DFT, RMS and peak-to-peak. Fault records
store IED measurement values at the moment when any
protection function starts. In addition, the maximum demand
current with time stamp is separately recorded. By default,
the records are stored in the nonvolatile memory.
11. Condition monitoring
The condition monitoring functions of the IED constantly
monitors the performance and the condition of the circuit
breaker. The monitoring comprises the spring charging time,
SF6 gas pressure, the travel time and the inactivity time of the
circuit breaker.
The monitoring functions provide operational circuit breaker
history data, which can be used for scheduling preventive
circuit breaker maintenance.
In addition, the IED includes a runtime counter for monitoring
of how many hours a protected device has been in operation
thus enabling scheduling of time-based preventive
maintenance of the device.
12. Trip-circuit supervision
The trip-circuit supervision continuously monitors the
availability and operability of the trip circuit. It provides opencircuit monitoring both when the circuit breaker is in its
closed and in its open position. It also detects loss of circuitbreaker control voltage.
ABB
13. Self-supervision
The IEDs built-in self-supervision system continuously
monitors the state of the IED hardware and the operation of
the IED software. Any fault or malfunction detected is used
for alerting the operator.
A permanent IED fault blocks the protection functions to
prevent incorrect operation.
14. Fuse failure supervision
In the standard configuration B, the IED includes fuse failure
supervision functionality. The fuse failure supervision detects
failures between the voltage measurement circuit and the IED.
The failures are detected either by the negative sequencebased algorithm or by the delta voltage and delta current
algorithm. Upon the detection of a failure, the fuse failure
supervision function activates an alarm and blocks voltagedependent protection functions from unintended operation.
15. Current circuit supervision
The IED includes current circuit supervision. Current circuit
supervision is used for detecting faults in the current
transformer secondary circuits. On detecting of a fault the
current circuit supervision function activates an alarm LED
and blocks certain protection functions to avoid unintended
operation. The current circuit supervision function calculates
the sum of the phase currents from the protection cores and
compares the sum with the measured single reference current
from a core balance current transformer or from separate
cores in the phase current transformers.
16. Access control
To protect the IED from unauthorized access and to maintain
information integrity, the IED is provided with a four-level, role-
ABB
1MRS757952 A
based authentication system with administratorprogrammable individual passwords for the viewer, operator,
engineer and administrator level. The access control applies
to the front-panel user interface, the Web browser-based
user interface and PCM600.
17. Inputs and outputs
The IED is equipped with three phase-current inputs, three
unbalance-current inputs and one residual-current input for
non-directional earth-fault protection.
In the standard configuration B, the IED is additionally
equipped with three phase-voltage inputs, one residual
voltage input for directional earth-fault protection and one
voltage input (Uob) that can be used for voltage based
unbalance protection.
The rated level of the current inputs is 1/5 A and selectable in
the IED software. The three phase-voltage inputs and the
residual-voltage inputs cover the rated voltages 60-210 V.
Both phase-to-phase voltages and phase-to-earth voltages
can be connected. The binary input thresholds 16176 V DC
are selected by adjusting the IEDs parameter settings.
All binary inputs and outputs contacts are freely configurable
with the signal matrix or application configuration functionality
of PCM600.
Please refer to the Input/output overview table and the
terminal diagrams for more detailed information about the
inputs and outputs.
Optionally, a binary input and output module can be selected.
It has three high speed binary outputs (HSO) and it decreases
the total operate time with typically 4...6 ms compared to the
normal power outputs.
13
1MRS757952 A
Analog channels
Binary channels
5-6
7-8
CT
VT
BI
BO
RTD
mA
BA
4 PO + 6 SO
BB
14
4 PO + 9 SO
FD
4 PO + 2 SO
+ 3 HSO
FF
14
4 PO + 5 SO
+ 3 HSO
BA
4 PO + 6 SO
FD
4 PO + 2 SO
+ 3 HSO
AD
12
4 PO + 6 SO
FE
12
4 PO + 2 SO
+ 3 HSO
BA
4 PO + 6 SO
FD
4 PO + 2 SO
+ 3 HSO
BA
A
BG
BC
B
BE
The IED also supports IEC 61850 process bus with sampled
values of analog phase voltages. With this functionality the
galvanic interpanel wiring can be replaced with Ethernet
communication. The measured values are transferred as
sampled values using IEC 61850-9-2 LE protocol. The
intended application for sampled values shares the phase
voltages to other 615 series IEDs, having phase voltage
based functions and 9-2 support. 615 IEDs with process bus
based applications use IEEE 1588 for high accuracy time
synchronization.
For redundant Ethernet communication, the IED offers either
two optical or two galvanic Ethernet network interfaces. A
third port with galvanic Ethernet network interface is also
available. The third Ethernet interface provides connectivity
for any other Ethernet device to an IEC 61850 station bus
inside a switchgear bay, for example connection of a Remote
I/O. The high accuracy time synchronization method IEEE
ABB
1MRS757952 A
COM600
Ethernet switch
REF615
REF620
SCADA
RET620
Ethernet switch
REM620
REF615
GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V1 EN
Figure 8.
ABB
the sender node discards the frame to avoid loops. The HSR
ring with 615 series IEDs supports the connection of up to
thirty IEDs. If more than 30 IEDs are to be connected, it is
recommended to split the network into several rings to
guarantee the performance for real-time applications.
15
COM600
1MRS757952 A
SCADA
Ethernet switch
Redundancy
Box
Redundancy
Box
Redundancy
Box
REF615
REF620
RET620
REM620
REF615
GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN
Figure 9.
16
ABB
1MRS757952 A
Client A
Client B
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
Figure 10.
17
1MRS757952 A
Ethernet
Serial
100BASE-TX RJ-45
100BASE-FX LC
RS-232/RS-485
Fibre-optic ST
IEC 61850-8-1
IEC 61850-9-2 LE
MODBUS RTU/ASCII
MODBUS TCP/IP
DNP3 (serial)
DNP3 TCP/IP
IEC 60870-5-103
= Supported
18
ABB
1MRS757952 A
Value
Width
frame
177 mm
case
164 mm
frame
177 mm (4U)
case
160 mm
Height
Depth
Weight
4.1 kg
2.1 kg
Type 1
Type 2
50 ms at Un
Fuse type
T4A/250 V
Value
Operating range
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
ABB
19
1MRS757952 A
Value
Rated voltage
250 V AC/DC
5A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
Value
Rated voltage
250 V AC/DC
5A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20
ABB
1MRS757952 A
Value
Rated voltage
250 V AC/DC
6A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Start
1 ms
Reset
Protocol
Cable
Front
TCP/IP protocol
10 MBits/s
Value
B004, B0051)
Isolation
500V 1 min
Modulation
Unmodulated
Logic level
5 V TTL
Current consumption
<4 mA
Power consumption
<20 mW
1)
Value
Front side
IP 54
IP 20
Value
-25...+55C (continuous)
-40...+85C (<16h)1)2)
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
-40...+85C
1)
2)
ABB
Degradation in MTBF and HMI performance outside the temperature range of -25...+55 C
For IEDs with an LC communication interface the maximum operating temperature is +70 C
21
1MRS757952 A
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
Common mode
2.5 kV
Differential mode
2.5 kV
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
2.5 kV
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
Contact discharge
8 kV
Air discharge
15 kV
IEC 61000-4-6
IEC 60255-22-6, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f = 80...1000 MHz
IEEE C37.90.2-2004
All ports
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
4 kV
IEC 61000-4-5
IEC 60255-22-5
Communication
1 kV, line-to-earth
Other ports
4 kV, line-to-earth
2 kV, line-to-line
IEC 61000-4-8
Continuous
1...3 s
300 A/m
1000 A/m
1000 A/m
6.4/16 s
IEC 61000-4-10
2s
100 A/m
1 MHz
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
22
IEC 61000-4-9
IEC 61000-4-11
ABB
1MRS757952 A
Reference
IEC 61000-4-16
IEC 60255-22-7, class A
Common mode
300 V rms
Differential mode
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
Emission tests
IEC 61000-4-16
EN 55011, class A
IEC 60255-25
Conducted
0.15...0.50 MHz
0.5...30 MHz
Radiated
30...230 MHz
230...1000 MHz
Reference
Dielectric tests
>100 M, 500 V DC
<0.1 , 4 A, 60 s
IEC 60255-27
Description
Reference
Requirement
Class 2
Class 2
Seismic test
IEC 60255-21-3
Class 2
ABB
23
1MRS757952 A
Reference
96 h at +55C
IEC 60068-2-2
96 h at -25C
16 h at -40C
IEC 60068-2-1
IEC 60068-2-30
5 cycles (3 h + 3 h)
at -25C...+55C
IEC60068-2-14
Storage test
96 h at -40C
96 h at +85C
IEC 60068-2-1
IEC 60068-2-2
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
EN 60255-1 (2009)
Reference
EMC directive
2004/108/EC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
24
ABB
1MRS757952 A
Protection functions
Table 25. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
PHHPTOC
and
PHIPTOC
Typical
Maximum
16 ms
19 ms
23 ms
11 ms
12 ms
14 ms
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
2)
3)
4)
ABB
Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Includes the delay of the heavy-duty output contact
Valid for FPHLPTOC
25
1MRS757952 A
Function
Value (Range)
Step
Start Value
PHLPTOC
0.05...5.00 In
0.01
PHHPTOC
0.10...40.00 In
0.01
PHIPTOC
1.00...40.00 In
0.01
PHLPTOC
0.05...15.00
0.01
PHHPTOC
0.05...15.00
0.01
PHLPTOC
40...200000 ms
10
PHHPTOC
40...200000 ms
10
PHIPTOC
20...200000 ms
10
PHLPTOC
PHHPTOC
PHIPTOC
Definite time
Time multiplier
1)
Value
Operation accuracy
EFHPTOC
and
EFIPTOC
Typical
Maximum
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1)
2)
3)
26
Measurement mode = default (depends on stage), current before fault = 0.0 I n, f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 I n , Start value multiples in range of 1.5...20
ABB
1MRS757952 A
Function
Value (Range)
Step
Start value
EFLPTOC
0.010...5.000 In
0.005
EFHPTOC
0.10...40.00 In
0.01
EFIPTOC
1.00...40.00 In
0.01
EFLPTOC
0.05...15.00
0.01
EFHPTOC
0.05...15.00
0.01
EFLPTOC
40...200000 ms
10
EFHPTOC
40...200000 ms
10
EFIPTOC
20...200000 ms
10
EFLPTOC
EFHPTOC
EFIPTOC
Definite time
Time multiplier
1)
ABB
27
1MRS757952 A
Value
Operation accuracy
Current:
1.5% of the set value or 0.002 In
Voltage
1.5% of the set value or 0.002 Un
Phase angle:
2
DEFHPDEF
Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle:
2
Minimum
Typical
Maximum
42 ms
46 ms
49 ms
58 ms
62 ms
66 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1)
Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 I n , f n = 50 Hz, earth-fault current
2)
3)
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 I n , Start value multiples in range of 1.5...20
28
ABB
1MRS757952 A
Function
Value (Range)
Step
Start Value
DEFLPDEF
0.010...5.000 In
0.005
DEFHPDEF
0.10...40.00 In
0.01
Directional mode
1 = Non-directional
2 = Forward
3 = Reverse
Time multiplier
DEFLPDEF
0.05...15.00
0.01
DEFHPDEF
0.05...15.00
0.01
DEFLPDEF
60...200000 ms
10
DEFHPDEF
40...200000 ms
10
DEFLPDEF
DEFHPDEF
1 = Phase angle
2 = IoSin
3 = IoCos
4 = Phase angle 80
5 = Phase angle 88
Operation mode
1)
Value
Operation accuracy
Minimum
Typical
Maximum
23 ms
15 ms
26 ms
18 ms
28 ms
20ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
Negative sequence current before fault = 0.0, f n = 50 Hz, results based on statistical distribution of 1000 measurements
2)
3)
ABB
29
1MRS757952 A
Function
Value (Range)
Step
Start value
NSPTOC
0.01...5.00 In
0.01
Time multiplier
NSPTOC
0.05...15.00
0.01
NSPTOC
40...200000 ms
10
NSPTOC
1)
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
Minimum
Typical
Maximum
48 ms
51 ms
54 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
Residual voltage before fault = 0.0 U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
2)
measurements
Includes the delay of the signal output contact
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 Un
0.001
ROVPTOV
40...300000 ms
30
ABB
1MRS757952 A
Value
Operation accuracy
Start time1)2)
UFault = 0.9 set Start value
Minimum
Typical
Maximum
62 ms
66 ms
70 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
Start value = 1.0 Un, Voltage before fault = 1.1 U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 Un
0.01
Time multiplier
PHPTUV
0.05...15.00
0.01
PHPTUV
60...300000 ms
10
PHPTUV
1)
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
Minimum
Typical
Maximum
23 ms
27 ms
31 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
ABB
Start value = 1.0 Un, Voltage before fault = 0.9 U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 1.20 U n, Start value multiples in range of 1.10... 2.00
31
1MRS757952 A
Function
Value (Range)
Step
Start value
PHPTOV
0.05...1.60 Un
0.01
Time multiplier
PHPTOV
0.05...15.00
0.01
PHPTOV
40...300000 ms
10
PHPTOV
1)
Value
Operation accuracy
Start time1)2)
UFault = 0.99 set Start value
UFault = 0.9 set Start value
Minimum
Typical
Maximum
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
Start value = 1.0 Un, Positive sequence voltage before fault = 1.1 U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Function
Value (Range)
Step
Start value
PSPTUV
0.010...1.200 Un
0.001
PSPTUV
40...120000 ms
10
PSPTUV
0.01...1.0 Un
0.01
32
ABB
1MRS757952 A
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
UFault = 2.0 set Start value
Minimum
Typical
Maximum
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
Negative-sequence voltage before fault = 0.0 U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
2)
Function
Value (Range)
Step
Start value
NSPTOV
0.010...1.000 Un
0.001
NSPTOV
40...120000 ms
Value
Operation accuracy
Retardation time
<20 ms
Function
Value (Range)
Step
CCBRBRF
0.05...1.00 In
0.05
CCBRBRF
0.05...1.00 In
0.05
CCBRBRF
1 = Current
2 = Breaker status
3 = Both
CCBRBRF
1 = Off
2 = Without check
3 = Current check
Retrip time
CCBRBRF
0...60000 ms
10
CB failure delay
CCBRBRF
0...60000 ms
10
CB fault delay
CCBRBRF
0...60000 ms
10
ABB
33
1MRS757952 A
Value
Operation accuracy
Operate time
Minimum
Typical
Maximum
9 ms
10 ms
12 ms
Typically 40 ms
Reset time
Reset ratio
Typically 0.96
Function
Value (Range)
Step
ARCSARC
0.50...40.00 x In
0.01
ARCSARC
0.05...8.00 x In
0.01
Operation mode
ARCSARC
2=Light only
3=BI controlled
Value
Operation accuracy
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
Over
Under
Value
Operation accuracy
Typically 75 ms
Typically 26 ms
Typically 60 ms
Reset ratio
Typically 0.96
1)
Harmonics current before fault = 0.5 I n, harmonics fault current 1.5 Start value , results based on statistical distribution of 1000 measurements
2)
3)
34
ABB
1MRS757952 A
Table 50. Three phase overload protection for shunt capacitor banks (COLPTOC) main settings
Parameter
Function
Value (Range)
Step
COLPTOC
0.30...1.50 In
0.01
COLPTOC
80...120%
COLPTOC
0.10...0.70 In
0.01
Time multiplier
COLPTOC
0.05...2.00
0.01
COLPTOC
500...6000000
100
COLPTOC
100...120000
100
Value
Operation accuracy
Start time1)2)
Typically 26 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Suppression of harmonics
1)
Fundamental frequency current = 1.0 I n, current before fault = 0.0 I n, fault current = 2.0 Start value , results based on statistical distribution of 1000 measurements
2)
Table 52. Current unbalance protection for SCB (CUBPTOC) main settings
Parameter
Function
Value (Range)
Step
Alarm mode
CUBPTOC
1=Normal
2=Element counter
Start value
CUBPTOC
0.01...1.00 In
0.01
CUBPTOC
0.01...1.00 In
0.01
Time multiplier
CUBPTOC
0.05...15.00
0.01
CUBPTOC
CUBPTOC
50...200000 ms
10
CUBPTOC
50...200000 ms
10
1)
ABB
35
1MRS757952 A
Table 53. Three-phase current unbalance protection for capacitor banks (HCUBPTOC)
Characteristic
Value
Operation accuracy
Start time1)2)
Typically 26 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Suppression of harmonics
1)
Fundamental frequency current = 1.0 I n, current before fault = 0.0 I n, fault current = 2.0 Start value , results based on statistical distribution of 1000 measurements
2)
Table 54. Three-phase current unbalance protection for Hbridge SCB (HCUBPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
HCUBPTOC
0.01...1.00 In
0.01
HCUBPTOC
0.01...1.00 In
0.01
Time multiplier
HCUBPTOC
0.05...15.00
0.01
HCUBPTOC
HCUBPTOC
40...200000 ms
10
HCUBPTOC
40...200000 ms
10
1)
Value
Operation accuracy
Reset time
Typically 45 ms or maximum 50 ms
Retardation time
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
-50 dB at f = fn
36
ABB
1MRS757952 A
Table 56. Capacitor bank switching resonance protection, current based (SRCPTOC) main settings
Parameter
Function
Range (Value)
Step
SRCPTOC
0.03...0.50 In
0.01
Start value
SRCPTOC
0.03...0.50 In
0.01
SRCPTOC
1...11
SRCPTOC
120...360000 ms
SRCPTOC
120...360000 ms
Value (Range)
ABB
37
1MRS757952 A
Value
Operation accuracy
Reset ratio
38
ABB
1MRS757952 A
Supervision functions
Table 59. Current circuit supervision (CCRDIF)
Characteristic
Value
Operate time1)
<30 ms
1)
Function
Value (Range)
Step
Start value
CCRDIF
0.05...0.20 x In
0.01
CCRDIF
1.00...5.00 x In
0.01
Value
NPS function
Delta function
1)
<33 ms
<18 ms
<30 ms
<24 ms
Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Value
0.5%
1)
ABB
39
1MRS757952 A
Measurement functions
Table 63. Three-phase current measurement (CMMXU)
Characteristic
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
40
ABB
1MRS757952 A
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
10 mHz
(in measurement range 35...75 Hz)
ABB
41
1MRS757952 A
IECA070904 V3 EN
Figure 11.
apart from the default single line diagram. The SLD view can
also be accessed using the Web browser-based user
interface. The default SLD can be modified according to user
requirements by using the Graphical Display Editor in
PCM600. The user can create up to 10 SLD pages.
The local HMI includes a push button (L/R) for local/remote
operation of the IED. When the IED is in the local mode, the
IED can be operated only by using the local front panel user
interface. When the IED is in the remote mode, the IED can
execute commands sent from a remote location. The IED
supports the remote selection of local/remote mode via a
binary input. This feature facilitates, for example, the use of
an external switch at the substation to ensure that all IEDs are
in the local mode during maintenance work and that the
circuit breakers cannot be operated remotely from the
network control center.
IECA070901 V3 EN
Small display
Figure 12.
Large display
20
8 or more
1)
10
20
8 or more
1)
42
ABB
1MRS757952 A
Mounting methods:
Flush mounting
Semi-flush mounting
Semi-flush mounting in a 25 tilt
Rack mounting
Wall mounting
Mounting to a 19" equipment frame
Mounting with a RTXP 18 test switch to a 19" rack
190
6
18
164
177
230
177
177
160
160
25
1 53
48
IECA070900 V4 EN
Figure 13.
98
IECA070903 V4 EN
Flush mounting
Figure 14.
133
IECA070902 V4 EN
Semi-flush mounting
ABB
107
103
Figure 15.
measuring IED unit and vice versa, i.e. the IED cases are
assigned to a certain type of IED plug-in unit.
23. Selection and ordering data
Use the ABB Library to access the selection and ordering
information and to generate the order number.
43
1MRS757952 A
Order number
1MRS050696
1MRS050697
1MRS050831
1MRS050694
1MRS050695
Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19 variant C)
2RCA022642P0001
2RCA022643P0001
19 rack mounting kit for one IED and one RTXP18 test switch (the test switch is not included in the delivery)
2RCA021952A0003
19 rack mounting kit for one IED and one RTXP24 test switch (the test switch is not included in the delivery)
2RCA022561A0003
Replacement kit for a Strmberg SP_J40 series relay (cut-out in the center of the installation plate)
2RCA027871A0001
Replacement kit for a Strmberg SP_J40 series relay (cut-out on the left or the right of the installation plate)
2RCA027874A0001
2RCA027880A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (one cut-out)
2RCA027894A0001
19 rack replacement kit for Strmberg SP_J3/J6 series relays (two cut-outs)
2RCA027897A0001
2RCA027881A0001
2RCA027882A0001
2RCA027885A0001
44
ABB
25. Tools
The IED is delivered as a pre-configured unit. The default
parameter setting values can be changed from the front-panel
user interface, the Web browser-based user interface (Web
HMI) or the PCM600 tool in combination with the IED-specific
connectivity package.
The Protection and Control IED Manager PCM600 offers
extensive IED configuration functions such as IED signal
configuration, application configuration, graphical display
configuration including single line diagram configuration, and
IEC 61850 communication configuration including horizontal
GOOSE communication.
When the Web browser-based user interface is used, the IED
can be accessed either locally or remotely, using a Web
browser (Internet Explorer). For security reasons, the Web
1MRS757952 A
Version
PCM600
2.6 or later
5.0
ABB
45
1MRS757952 A
Web HMI
PCM600
Signal monitoring
Application configuration
Event viewing
Online monitoring
= Supported
46
download and Web HMI uses TLS encryption with 128 bit
key length protecting data in transit according FTPS and
HTTPS standards.
ABB
1MRS757952 A
REV615
X120
1
1/5A
2
3
1/5A
4
5
N
1/5A
6
7
N
1/5A
8
9
N
1/5A
10
11
N
1/5A
12
13
N
1/5A
14
X100
+
IL1unb 2)
U aux
-
IL2unb
IRF
IL3unb
1
2
3
4
5
PO1
IL1
6
7
IL2
PO2
IL3
8
9
10
Io
SO1
11
12
13
SO2
PO3
X110
1
2
3
4
5
6
7
8
9
10
11
12
13
BI 1
3)
TCS1
BI 2
PO4
2
3
4
5
6
7
8
9
17
15
19
18
20
22
21
23
BI 3
TCS2
BI 4
24
X110
3)
BI 5
14
SO1
16
15
17
BI 6
SO2
BI 7
19
18
20
BI 8
SO3
22
21
23
X130
1
14
16
SO4
BI 1
24
4)
X130
BI 2
4)
10
SO1
BI 3
12
11
13
BI 4
SO2
15
14
16
BI 5
SO3
BI 6
X13
Light sensor input 1
X14
Light sensor input 2
X15
Light sensor input 3
18
17
1)
1)
1)
1) Optional
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
3) BIO0005 Module (8BI+4BO)
Alternative Module BIO0007 (8BI+3HSO)
4) BIO0006 Module (6BI+3BO)
Alternative Module RTD0001 (6RTD+2mA)
GUID-E075C9E1-5D32-4556-ADD7-8B64EF861FA8 V1 EN
Figure 16.
ABB
47
1MRS757952 A
REV615
X130
1
BI 1
BI 2
4
5
7
12
13
14
15
16
60 210V
N
60 210V
N
60 210V
N
60 210V
17
N
60 210V
18
1/5A
N
1/5A
4
5
N
1/5A
6
7
N
1/5A
8
9
N
1/5A
10
11
N
1/5A
12
13
N
1/5A
14
3
4
5
PO2
U1
8
9
10
U2
SO1
11
12
13
U3
SO2
Uo
PO3
2
3
6
7
UoB
X120
1
PO1
BI 4
11
IRF
BI 3
U aux
-
10
X100
+
4)
IL1unb 2)
TCS1
IL2unb
PO4
IL3unb
14
16
17
15
19
18
20
22
21
23
TCS2
IL1
24
IL2
IL3
Io
X110
1
2
3
4
5
6
7
8
9
10
11
12
13
BI 1
3)
BI 2
BI 3
X110
3)
BI 4
14
SO1
16
15
17
BI 5
SO2
19
18
20
BI 6
SO3
BI 7
22
21
23
BI 8
SO4
24
X13
Light sensor input 1
X14
Light sensor input 2
X15
Light sensor input 3
1)
1)
1)
1) Optional
2) The IED features an automatic short-circuit
mechanism in the CT connector when plug-in
unit is detached
3) BIO0005 Module (8BI+4BO)
Alternative Module BIO0007 (8BI+3HSO)
4) AIM0006 Module (5U+4BI)
Alternative Module AIM0003 (5U+2RTD+1mA)
GUID-71A7F7FA-9605-46FE-A7EF-B53142C4EE9F V1 EN
Figure 17.
48
ABB
28. Certificates
KEMA has issued an IEC 61850 Certificate Level A1 for
Relion 615 series. Certificate number: 74102147-MOC/INC
13-4263.
29. References
The www.abb.com/substationautomation portal provides
information on the entire range of distribution automation
products and services.
ABB
1MRS757952 A
49
1MRS757952 A
IEC 61850
IEC 60617
IEC-ANSI
PHLPTOC1
3I> (1)
51P-1 (1)
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
PHIPTOC1
3I>>> (1)
50P/51P (1)
EFLPTOC1
Io> (1)
51N-1 (1)
EFLPTOC2
Io> (2)
51N-1 (2)
EFHPTOC1
Io>> (1)
51N-2 (1)
EFIPTOC1
Io>>> (1)
50N/51N (1)
DEFLPDEF1
67N-1 (1)
DEFLPDEF2
67N-1 (2)
DEFHPDEF1
67N-2 (1)
NSPTOC1
I2> (1)
46 (1)
NSPTOC2
I2> (2)
46 (2)
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
ROVPTOV3
Uo> (3)
59G (3)
PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
PSPTUV1
U1< (1)
47U+ (1)
NSPTOV1
U2> (1)
47O- (1)
T2PTTR1
3Ith>T (1)
49T (1)
CCBRBRF1
3I>/Io>BF (1)
51BF/51NBF (1)
Master trip
TRPPTRC1
94/86 (1)
TRPPTRC2
94/86 (2)
TRPPTRC3
94/86 (3)
TRPPTRC4
94/86 (4)
TRPPTRC5
94/86 (5)
ARCSARC1
ARC (1)
50L/50NL (1)
ARCSARC2
ARC (2)
50L/50NL (2)
ARCSARC3
ARC (3)
50L/50NL (3)
Protection
Arc protection
50
ABB
1MRS757952 A
IEC 61850
IEC 60617
IEC-ANSI
Multi-purpose protection1)
MAPGAPC1
MAP (1)
MAP (1)
MAPGAPC2
MAP (2)
MAP (2)
MAPGAPC3
MAP (3)
MAP (3)
MAPGAPC4
MAP (4)
MAP (4)
MAPGAPC5
MAP (5)
MAP (5)
MAPGAPC6
MAP (6)
MAP (6)
MAPGAPC7
MAP (7)
MAP (7)
MAPGAPC8
MAP (8)
MAP (8)
MAPGAPC9
MAP (9)
MAP (9)
MAPGAPC10
MAP (10)
MAP (10)
MAPGAPC11
MAP (11)
MAP (11)
MAPGAPC12
MAP (12)
MAP (12)
MAPGAPC13
MAP (13)
MAP (13)
MAPGAPC14
MAP (14)
MAP (14)
MAPGAPC15
MAP (15)
MAP (15)
MAPGAPC16
MAP (16)
MAP (16)
MAPGAPC17
MAP (17)
MAP (17)
MAPGAPC18
MAP (18)
MAP (18)
COLPTOC1
51C/37 (1)
CUBPTOC1
dI>C (1)
51NC-1 (1)
HCUBPTOC1
3dI>C (1)
51NC-2 (1)
SRCPTOC1
TD> (1)
55TD (1)
CMHAI1
PQM3I (1)
PQM3I (1)
VMHAI1
PQM3U (1)
PQM3V (1)
Voltage variation
PHQVVR1
PQMU (1)
PQMV (1)
Circuit-breaker control
CBXCBR1
I <-> O CB (1)
I <-> O CB (1)
Disconnector control
DCXSWI1
DCXSWI2
ESXSWI1
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
DCSXSWI3
I <-> O DC (3)
I <-> O DC (3)
ESSXSWI1
I <-> O ES (1)
I <-> O ES (1)
ESSXSWI2
I <-> O ES (2)
I <-> O ES (2)
SSCBR1
CBCM (1)
CBCM (1)
Power quality
Control
Condition monitoring
Circuit-breaker condition monitoring
ABB
51
1MRS757952 A
IEC 61850
IEC 60617
IEC-ANSI
TCSSCBR1
TCS (1)
TCM (1)
TCSSCBR2
TCS (2)
TCM (2)
CCRDIF1
MCS 3I (1)
MCS 3I (1)
SEQRFUF1
FUSEF (1)
60 (1)
MDSOPT1
OPTS (1)
OPTM (1)
Disturbance recorder
RDRE1
DR (1)
DFR (1)
LDPMSTA1
LOADPROF (1)
LOADPROF (1)
CMMXU1
3I (1)
3I (1)
CSMSQI1
RESCMMXU1
Io (1)
In (1)
VMMXU1
3U (1)
3V (1)
RESVMMXU1
Uo (1)
Vn (1)
RESVMMXU2
Uo (2)
Vn (2)
VSMSQI1
PEMMXU1
P, E (1)
P, E (1)
RTD/mA measurement
XRGGIO130
Frequency measurement
FMMXU1
f (1)
f (1)
SMVSENDER
SMVSENDER
SMVSENDER
Measurement
1)
2)
Product version
History
A/2014-01-24
5.0
First release
52
ABB
53
ABB Oy
Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
ABB Limited
Distribution Automation
Maneja
Vadodara 390013, India
Phone
+91 265 2604032
Fax
+91 265 2638922
www.abb.com/substationautomation
Contact us