Totally Integrated 7SL87 - LINEA A VILLA HAYES

Automation Portal

Settings
Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 172.16.60.60 (Integrated Ethernet interface)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Hide all settings
Hide SIPROTEC extensions in IEC 61850 structure Hide all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.

General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.115 Set. format residu. comp. All: Kr, Kx
91.138 Block monitoring dir. All: off

General \Setting change


Number Settings Value
91.163 Reserv.time for com.prot. All: 120 s

General \Chatter blocking


Number Settings Value
91.123 No. permis.state changes All: 0
91.127 Initial test time All: 1 s
91.124 No. of chatter tests All: 0
91.125 Chatter idle time All: 1 min
91.137 Subsequent test time All: 2 s

General \Measurements
Number Settings Value
91.162 Blk setting change All: false
91.163 Reserv.time for com.prot. All: 120 s
91.111 Energy restore interval Settings group 1: 10 min
91.112 Energy restore time Settings group 1: none

General \Control
Number Settings Value
91.120 Energy restore Settings group 1: latest value
91.121 Energy restore by A.time All: false
91.118 Enable sw.auth. station All: false

1 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

General \Spontan.indic.
Number Settings Value
91.119 Multiple sw.auth. levels All: false

General \CFC
Number Settings Value
91.152 Specific sw. authorities All: false

General \Test support


Number Settings Value
91.139 Fault-display All: with pickup
91.161 CFC chart quality handling All: automatic

Localization
Number Settings Value
6211.139 Unit system All: SI

Time settings
General
Settings Value
Date format All: DD.MM.YYYY

Time source
Settings Value
Fault indication after All: 600 s
Time source 1 none
Time source 2 none
Time zone time source 1 All: local
Time zone time source 2 All: local
Sync. latency time src.1 All: 0 μs
Sync. latency time src.2 All: 0 μs

Time zone and daylight saving time


Settings Value
Time zone offset to UTC All: 60 min
Offset daylight sav. time All: 60 min
Switch daylight sav. time true
Start of daylight sav. time Last Sunday in March at 2:00 AM
End of daylight sav. time Last Sunday in October at 3:00 AM

Power system \General


General
Number Settings Value
11.2311.101 Phase sequence All: ABC

2 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Power system \Tensión derv.AB


VT 3-phase
Number Settings Value
11.941.8911.101 Rated primary voltage All: 500.000 kV
11.941.8911.102 Rated secondary voltage All: 115 V
11.941.8911.104 VT connection All: 3 ph-to-gnd voltages
11.941.8911.106 Inverted phases All: none
11.941.8911.111 Tracking All: active
11.941.8911.130 Measuring-point ID All: 1

VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A

VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B

VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
11.941.3813.108 Phase All: V C

Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: on
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: on
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s

3 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s

Power system \Barra


General
Number Settings Value
11.961.2311.101 Rated primary voltage All: 500.000 kV
11.961.2311.102 Rated secondary voltage All: 111 V
11.961.2311.103 Tracking All: inactive
11.961.2311.130 Measuring-point ID All: 2

VT 1
Number Settings Value
11.961.3811.103 Magnitude correction All: 1
11.961.3811.108 Phase All: V B

VT miniatureCB
Number Settings Value
11.961.2641.101 Response time Settings group 1: 0 s

Power system \Meas.point I-3ph 1


CT 3-phase \General
Number Settings Value
11.931.8881.115 CT connection All: 3-phase + IN
11.931.8881.127 Tracking All: active
11.931.8881.130 Measuring-point ID All: 4

CT 3-phase \CT phases


Number Settings Value
11.931.8881.101 Rated primary current All: 2000 A
11.931.8881.102 Rated secondary current All: 1 A
11.931.8881.117 Current range All: 100 x IR
11.931.8881.118 Internal CT type All: CT protection
11.931.8881.116 Neutr.point in dir.of ref.obj All: yes
11.931.8881.114 Inverted phases All: none
11.931.8881.107 CT error changeover All: 1.5
11.931.8881.108 CT error A All: 3 %
11.931.8881.109 CT error B All: 10 %

CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A

4 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B

CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C

CT 4
Number Settings Value
11.931.3844.103 Magnitude correction All: 1
11.931.3844.117 Phase All: IN

Brk.wire det.
Number Settings Value
11.931.5581.1 Mode Settings group 1: off
11.931.5581.101 Mode of blocking Settings group 1: blocking
11.931.5581.102 Delta value for autoblock Settings group 1: 1

Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 1000 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: on
11.931.2431.102 Threshold Settings group 1: 200 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s

Supv.ADC sum I
Number Settings Value
11.931.2401.1 Mode Settings group 1: on

5 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Saturat. det.
Number Settings Value
11.931.17731.101 CT saturation threshold Settings group 1: 16000 A

Recording \Fault recorder


Control
Number Settings Value
51.791.2761.130 Fault recording All: with pickup & AR cyc.
51.791.2761.131 Storage All: always
51.791.2761.111 Maximum record time All: 5 s
51.791.2761.112 Pre-trigger time All: 0.5 s
51.791.2761.113 Post-trigger time All: 0.5 s
51.791.2761.116 Manual record time All: 0.5 s
51.791.2761.140 Sampling frequency All: 2 kHz
51.791.2761.141 Sampl. freq. IEC61850 rec. All: 1 kHz
51.791.2761.128 Scaling COMTRADE All: Secondary values

Line 1 \General
General \Rated values
Number Settings Value
21.9001.101 Rated current All: 1923 A
21.9001.102 Rated voltage All: 500 kV
21.9001.103 Rated apparent power All: 1665.4 MVA

General \Line data


Number Settings Value
21.9001.149 Neutral point Settings group 1: grounded
21.9001.112 C1 per length unit Settings group 1: 0.014 μF/km
21.9001.148 C0 per length unit Settings group 1: 0.008 μF/km
21.9001.113 X per length unit Settings group 1: 0.267 Ω/km
21.9001.114 Line length Settings group 1: 333 km
21.9001.108 Line angle Settings group 1: 84.43 °
21.9001.104 Kr Settings group 1: 3.45
21.9001.105 Kx Settings group 1: 0.74
21.9001.119 CT saturation detection All: no
21.9001.111 Series compensation Settings group 1: no
21.9001.110 Series capacit. reactance Settings group 1: 0 Ω

General \Measurements
Number Settings Value
21.9001.158 P, Q sign Settings group 1: not reversed

Line 1 \Process monitor


Closure detec.
Number Settings Value
21.1131.4681.101 Operating mode Settings group 1: Manual close only
21.1131.4681.102 Action time after closure Settings group 1: 0.05 s
21.1131.4681.103 Min. time feeder open Settings group 1: 0.25 s

6 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

1pol.open det.
Number Settings Value
21.1131.4711.101 Operating mode Settings group 1: with measurement

Volt.criterion
Number Settings Value
21.1131.4801.101 Threshold U open Settings group 1: 120.00 kV

Line 1 \68 P.swing blk


68 P.swing blk
Number Settings Value
21.5311.1 Mode Settings group 1: on
21.5311.103 Max. blocking time Settings group 1: oo s

68 P.swing blk \Zones to be blocked


Number Settings Value
21.5311.102 21 Distance prot. 1.Z 1 true
21.5311.102 21 Distance prot. 1.Z 2 true
21.5311.102 21 Distance prot. 1.Z 3 true
21.5311.102 21 Distance prot. 1.Z 4 true
21.5311.102 21 Distance prot. 1.Z 1B true

Line 1 \Fault locator


Fault locator
Number Settings Value
21.8671.1 Mode Settings group 1: on
21.8671.101 Start Settings group 1: with going pickup
21.8671.103 Load compensation Settings group 1: no

Line 1 \Mes.v.fail.det
Mes.v.fail.det
Number Settings Value
21.2671.1 Mode Settings group 1: on
21.2671.115 Asym.fail.-DO on netw.flt. Settings group 1: no
21.2671.113 Asym.fail. - time delay Settings group 1: 10 s
21.2671.102 3ph.fail. - phs.curr.release Settings group 1: 100 A
21.2671.103 3ph.fail. - phs.curr. jump Settings group 1: 100 A
21.2671.101 3ph.fail. - VA,VB,VC < Settings group 1: 20 kV
21.2671.107 Switch-on 3ph. failure All: on
21.2671.106 SO 3ph.fail. - time delay Settings group 1: 3 s

Line 1 \85-21Perm.overr.
85-21Perm.over
Number Settings Value
21.1291.5701.1 Mode Settings group 1: on

7 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


21.1291.5701.101 Send prolongation Settings group 1: 0.05 s
21.1291.5701.102 Send delay Settings group 1: 0 s
21.1291.5701.105 Trans. blk. pickup delay Settings group 1: 0.03 s
21.1291.5701.106 Trans. blk. dropout delay Settings group 1: 0.07 s
21.1291.5701.11 1-pole operate allowed Settings group 1: yes
21.1291.5701.103 Operate delay (1-phase) Settings group 1: 0 s
21.1291.5701.104 Operate delay (multi-ph.) Settings group 1: 0 s

85-21Perm.over \Send with


Number Settings Value
21.1291.5701.140 21 Distance prot. 1.pickup forward false
21.1291.5701.140 21 Distance prot. 1.Z 1 false
21.1291.5701.140 21 Distance prot. 1.Z 2 false
21.1291.5701.140 21 Distance prot. 1.Z 3 false
21.1291.5701.140 21 Distance prot. 1.Z 4 false
21.1291.5701.140 21 Distance prot. 1.Z 1B true

85-21Perm.over \Operate with


Number Settings Value
21.1291.5701.141 21 Distance prot. 1.pickup forward false
21.1291.5701.141 21 Distance prot. 1.Z 1 false
21.1291.5701.141 21 Distance prot. 1.Z 2 false
21.1291.5701.141 21 Distance prot. 1.Z 3 false
21.1291.5701.141 21 Distance prot. 1.Z 4 false
21.1291.5701.141 21 Distance prot. 1.Z 1B true

85-21Perm.over \Trans. block. with


Number Settings Value
21.1291.5701.142 85-67N Dir. comp..85-67N Dir.com true

Line 1 \85-67N Dir. comp.


85-67N Dir.com
Number Settings Value
21.1301.5761.1 Mode Settings group 1: on
21.1301.5761.101 Send prolongation Settings group 1: 0.05 s
21.1301.5761.102 Send delay Settings group 1: 0 s
21.1301.5761.105 Trans. blk. pickup delay Settings group 1: 0.03 s
21.1301.5761.106 Trans. blk. dropout delay Settings group 1: 0.07 s
21.1301.5761.104 3I0 threshold rev./forw. Settings group 1: 75 %
21.1301.5761.11 1-pole operate allowed Settings group 1: yes
21.1301.5761.103 Operate delay (1-phase) Settings group 1: 0 s

85-67N Dir.com \Send with


Number Settings Value
21.1301.5761.140 67N GFP gnd.sys.1.Definite-T 1 false
21.1301.5761.140 67N GFP gnd.sys.1.Definite-T 2 false
21.1301.5761.140 67N GFP gnd.sys.1.Inverse-T 1 true

8 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

85-67N Dir.com \Operate with


Number Settings Value
21.1301.5761.141 67N GFP gnd.sys.1.Definite-T 1 false
21.1301.5761.141 67N GFP gnd.sys.1.Definite-T 2 false
21.1301.5761.141 67N GFP gnd.sys.1.Inverse-T 1 true

85-67N Dir.com \Trans. block. with


Number Settings Value
21.1301.5761.142 85-21Perm.overr..85-21Perm.over true

Line 1 \Switch onto fault 1


Stage 1
Number Settings Value
21.1341.5941.1 Mode Settings group 1: on
21.1341.5941.2 Operate & flt.rec. blocked Settings group 1: no
21.1341.5941.6 Operate delay Settings group 1: 0 s

Stage 1 \Configuration
Number Settings Value
21.1341.5941.102 50/51 OC-3ph 1p 1.Definite-T 1 false
21.1341.5941.102 50N/51N OC-gnd-A1.Definite-T 1 false
21.1341.5941.102 50 high-speed 1pol 1.Standard 1 true
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 1 false
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 2 false
21.1341.5941.102 67N GFP gnd.sys.1.Inverse-T 1 true
21.1341.5941.102 21 Distance prot. 1.Z 1 false
21.1341.5941.102 21 Distance prot. 1.Z 2 false
21.1341.5941.102 21 Distance prot. 1.Z 3 false
21.1341.5941.102 21 Distance prot. 1.Z 4 false
21.1341.5941.102 21 Distance prot. 1.Z 1B true

Line 1 \50/51 OC-3ph 1p 1


General
Number Settings Value
21.221.2311.101 Emergency mode Settings group 1: no

Definite-T 1 \General
Number Settings Value
21.221.841.1 Mode Settings group 1: on
21.221.841.2 Operate & flt.rec. blocked Settings group 1: no
21.221.841.11 1-pole operate allowed Settings group 1: no
21.221.841.26 Dynamic settings All: no
21.221.841.8 Method of measurement Settings group 1: fundamental comp.
21.221.841.3 Threshold Settings group 1: 2400 A
21.221.841.4 Dropout ratio Settings group 1: 0.95
21.221.841.102 Pickup delay Settings group 1: 0 s
21.221.841.101 Dropout delay Settings group 1: 0 s
21.221.841.6 Operate delay Settings group 1: 60 s

9 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Line 1 \50N/51N OC-gnd-A1


General
Number Settings Value
21.211.2311.101 Emergency mode Settings group 1: no
21.211.2311.9 Measured value Settings group 1: IN measured

Definite-T 1 \General
Number Settings Value
21.211.751.1 Mode Settings group 1: off
21.211.751.2 Operate & flt.rec. blocked Settings group 1: no
21.211.751.26 Dynamic settings All: no
21.211.751.8 Method of measurement Settings group 1: fundamental comp.
21.211.751.3 Threshold Settings group 1: 1200 A
21.211.751.4 Dropout ratio Settings group 1: 0.95
21.211.751.101 Dropout delay Settings group 1: 0 s
21.211.751.6 Operate delay Settings group 1: 0.3 s

Line 1 \50 high-speed 1pol 1


Standard 1
Number Settings Value
21.981.3961.1 Mode Settings group 1: on
21.981.3961.102 1-pole operate allowed Settings group 1: no
21.981.3961.101 Activation Settings group 1: on CB closure
21.981.3961.3 Threshold Settings group 1: 1203 A
21.981.3961.4 Dropout ratio Settings group 1: 0.9

Line 1 \67N GFP gnd.sys.1


General
Number Settings Value
21.1111.2311.114 Polarization with All: V0 + IY or V2 + I2
21.1111.2311.101 Angle forward α Settings group 1: 338 °
21.1111.2311.102 Angle forward β Settings group 1: 122 °
21.1111.2311.103 Min. zero-seq. voltage V0 Settings group 1: 2.61 kV
21.1111.2311.115 Dir.reslt=forw.at V0<min Settings group 1: no
21.1111.2311.104 Min.3I0 f.increas.dir.sens. Settings group 1: 100 A
21.1111.2311.107 Min. neg.-seq. voltage V2 Settings group 1: 2.61 kV
21.1111.2311.106 Min. neg.-seq. current I2 Settings group 1: 100 A
21.1111.2311.116 Dir.corr.at ser.comp.lines Settings group 1: no

Definite-T 1 \General
Number Settings Value
21.1111.4861.1 Mode Settings group 1: on
21.1111.4861.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4861.114 Directional mode Settings group 1: forward
21.1111.4861.11 1-pole operate allowed Settings group 1: no
21.1111.4861.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4861.130 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4861.129 Op.mode at 1p dead time Settings group 1: blocked

10 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


21.1111.4861.112 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4861.115 Dynamic settings All: no
21.1111.4861.111 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4861.3 Threshold Settings group 1: 3638 A
21.1111.4861.6 Operate delay Settings group 1: 0.25 s

Definite-T 1 \Blocking by
Number Settings Value
21.1111.4861.140 87 Line diff. prot..Group indicat. true
21.1111.4861.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4861.140 21 Distance prot. 1.Z 1 false
21.1111.4861.140 21 Distance prot. 1.Z 2 false
21.1111.4861.140 21 Distance prot. 1.Z 3 false
21.1111.4861.140 21 Distance prot. 1.Z 4 false
21.1111.4861.140 21 Distance prot. 1.Z 1B false

Definite-T 2 \General
Number Settings Value
21.1111.4862.1 Mode Settings group 1: off
21.1111.4862.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4862.114 Directional mode Settings group 1: non-directional
21.1111.4862.11 1-pole operate allowed Settings group 1: no
21.1111.4862.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4862.129 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4862.112 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4862.115 Dynamic settings All: no
21.1111.4862.111 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4862.3 Threshold Settings group 1: 3638 A
21.1111.4862.6 Operate delay Settings group 1: 0.25 s

Definite-T 2 \Blocking by
Number Settings Value
21.1111.4862.140 87 Line diff. prot..Group indicat. false
21.1111.4862.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4862.140 21 Distance prot. 1.Z 1 false
21.1111.4862.140 21 Distance prot. 1.Z 2 false
21.1111.4862.140 21 Distance prot. 1.Z 3 false
21.1111.4862.140 21 Distance prot. 1.Z 4 false
21.1111.4862.140 21 Distance prot. 1.Z 1B false

Inverse-T 1 \General
Number Settings Value
21.1111.4891.1 Mode Settings group 1: on
21.1111.4891.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4891.115 Directional mode Settings group 1: forward
21.1111.4891.11 1-pole operate allowed Settings group 1: no
21.1111.4891.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4891.131 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4891.130 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4891.113 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4891.116 Dynamic settings All: no

11 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


21.1111.4891.112 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4891.3 Threshold Settings group 1: 300 A
21.1111.4891.133 Type of character. curve Settings group 1: IEC normal inverse
21.1111.4891.106 Time dial Settings group 1: 0.13
21.1111.4891.132 Additional time delay Settings group 1: 0 s
21.1111.4891.134 Reset Settings group 1: instantaneous

Inverse-T 1 \Blocking by
Number Settings Value
21.1111.4891.140 87 Line diff. prot..Group indicat. true
21.1111.4891.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4891.140 21 Distance prot. 1.Z 1 false
21.1111.4891.140 21 Distance prot. 1.Z 2 false
21.1111.4891.140 21 Distance prot. 1.Z 3 false
21.1111.4891.140 21 Distance prot. 1.Z 4 false
21.1111.4891.140 21 Distance prot. 1.Z 1B false

Line 1 \59 Overvolt.-3ph 1


Definite-T 1
Number Settings Value
21.51.181.1 Mode Settings group 1: on
21.51.181.2 Operate & flt.rec. blocked Settings group 1: no
21.51.181.9 Measured value Settings group 1: phase-to-phase
21.51.181.8 Method of measurement Settings group 1: fundamental comp.
21.51.181.101 Pickup mode Settings group 1: 3 out of 3
21.51.181.3 Threshold Settings group 1: 575 kV
21.51.181.4 Dropout ratio Settings group 1: 0.95
21.51.181.6 Operate delay Settings group 1: 5 s

Definite-T 2
Number Settings Value
21.51.182.1 Mode Settings group 1: on
21.51.182.2 Operate & flt.rec. blocked Settings group 1: no
21.51.182.9 Measured value Settings group 1: phase-to-phase
21.51.182.8 Method of measurement Settings group 1: fundamental comp.
21.51.182.101 Pickup mode Settings group 1: 1 out of 3
21.51.182.3 Threshold Settings group 1: 600 kV
21.51.182.4 Dropout ratio Settings group 1: 0.95
21.51.182.6 Operate delay Settings group 1: 1 s

Line 1 \21 Distance prot. 1


General
Number Settings Value
21.901.2311.110 Zone timer start Settings group 1: on dist. pickup
21.901.2311.107 Dist. characteristic angle Settings group 1: 72 °
21.901.2311.105 Ground-fault detection Settings group 1: 3I0 or V0
21.901.2311.103 3I0> threshold value Settings group 1: 200 A
21.901.2311.102 V0> threshold value Settings group 1: 21.74 kV
21.901.2311.104 3I0 pickup stabilization Settings group 1: 0.1
21.901.2311.108 Loop select. with ph-ph-g Settings group 1: block leading phase

12 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Pickup Z<
Number Settings Value
21.901.3661.101 Min. phase-current thresh Settings group 1: 200 A
21.901.3661.102 Use ph-g load cutout All: no
21.901.3661.105 Use ph-ph load cutout All: no

Z1
Number Settings Value
21.901.3571.1 Mode Settings group 1: on
21.901.3571.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3571.121 Blocked if diff.prot.active Settings group 1: yes
21.901.3571.11 1-pole operate allowed Settings group 1: yes
21.901.3571.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3571.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3571.109 Directional mode Settings group 1: forward
21.901.3571.102 X reach Settings group 1: 75.57 Ω
21.901.3571.103 R (ph-g) Settings group 1: 42 Ω
21.901.3571.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3571.113 Zone-inclination angle Settings group 1: 0 °
21.901.3571.110 Operate delay (1-phase) Settings group 1: 0 s
21.901.3571.112 Operate delay (multi-ph.) Settings group 1: 0 s

Z2
Number Settings Value
21.901.3572.1 Mode Settings group 1: on
21.901.3572.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3572.121 Blocked if diff.prot.active Settings group 1: no
21.901.3572.11 1-pole operate allowed Settings group 1: no
21.901.3572.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3572.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3572.109 Directional mode Settings group 1: forward
21.901.3572.102 X reach Settings group 1: 106.69 Ω
21.901.3572.103 R (ph-g) Settings group 1: 42 Ω
21.901.3572.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3572.113 Zone-inclination angle Settings group 1: 0 °
21.901.3572.110 Operate delay (1-phase) Settings group 1: 0.3 s
21.901.3572.112 Operate delay (multi-ph.) Settings group 1: 0.3 s

Z3
Number Settings Value
21.901.3573.1 Mode Settings group 1: on
21.901.3573.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3573.121 Blocked if diff.prot.active Settings group 1: no
21.901.3573.11 1-pole operate allowed Settings group 1: no
21.901.3573.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3573.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3573.109 Directional mode Settings group 1: forward
21.901.3573.102 X reach Settings group 1: 209.17 Ω
21.901.3573.103 R (ph-g) Settings group 1: 42 Ω
21.901.3573.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3573.113 Zone-inclination angle Settings group 1: 0 °
21.901.3573.110 Operate delay (1-phase) Settings group 1: 1.3 s

13 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


21.901.3573.112 Operate delay (multi-ph.) Settings group 1: 1.3 s

Z4
Number Settings Value
21.901.3574.1 Mode Settings group 1: on
21.901.3574.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3574.121 Blocked if diff.prot.active Settings group 1: no
21.901.3574.11 1-pole operate allowed Settings group 1: no
21.901.3574.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3574.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3574.109 Directional mode Settings group 1: reverse
21.901.3574.102 X reach Settings group 1: 21.34 Ω
21.901.3574.103 R (ph-g) Settings group 1: 42 Ω
21.901.3574.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3574.113 Zone-inclination angle Settings group 1: 0 °
21.901.3574.110 Operate delay (1-phase) Settings group 1: 1.8 s
21.901.3574.112 Operate delay (multi-ph.) Settings group 1: 1.8 s

Z 1B
Number Settings Value
21.901.3575.1 Mode Settings group 1: on
21.901.3575.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3575.121 Blocked if diff.prot.active Settings group 1: no
21.901.3575.11 1-pole operate allowed Settings group 1: yes
21.901.3575.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3575.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3575.109 Directional mode Settings group 1: forward
21.901.3575.102 X reach Settings group 1: 106.69 Ω
21.901.3575.103 R (ph-g) Settings group 1: 42 Ω
21.901.3575.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3575.113 Zone-inclination angle Settings group 1: 0 °
21.901.3575.110 Operate delay (1-phase) Settings group 1: oo s
21.901.3575.112 Operate delay (multi-ph.) Settings group 1: oo s

Line 1 \Weak infeed


Weak infeed
Number Settings Value
21.1331.5821.101 Echo block time after Tx Settings group 1: 0.05 s
21.1331.5821.102 Echo and operate delay Settings group 1: 0.04 s
21.1331.5821.103 Echo pulse Settings group 1: 0.05 s
21.1331.5821.104 Weak infeed action Settings group 1: only echo
21.1331.5821.105 85-21/67N common chan. Settings group 1: no
21.1331.5821.106 Undervoltage threshold Settings group 1: 108.70 kV

Line 1 \87 Line diff. prot.


General
Number Settings Value
21.831.2311.1 Mode Settings group 1: on
21.831.2311.11 1-pole operate allowed Settings group 1: yes
21.831.2311.102 Min. current for release Settings group 1: 0 A

14 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


21.831.2311.104 Supervision Idiff All: yes: block diff. prot.

I-DIFF
Number Settings Value
21.831.3451.1 Mode Settings group 1: on
21.831.3451.2 Operate & flt.rec. blocked Settings group 1: no
21.831.3451.3 Threshold Settings group 1: 416 A
21.831.3451.101 Thresh. switch onto fault Settings group 1: 416 A
21.831.3451.6 Operate delay Settings group 1: 0 s

I-DIFF fast 2
Number Settings Value
21.831.18211.1 Mode Settings group 1: on
21.831.18211.2 Operate & flt.rec. blocked Settings group 1: no
21.831.18211.3 Threshold Settings group 1: 2000 A
21.831.18211.101 Thresh. switch onto fault Settings group 1: 2000 A

Ic-compensat.
Number Settings Value
21.831.3511.1 Mode Settings group 1: on
21.831.3511.101 Ic-stabilization/Ic-rated Settings group 1: 1.5
21.831.3511.102 Total line length Settings group 1: 333 km
21.831.3511.110 Rated charging current Settings group 1: 415 A

Line 1 \87 Stub diff. prot. 1


General
Number Settings Value
21.1431.2311.1 Mode Settings group 1: on

S-DIFF
Number Settings Value
21.1431.8401.1 Mode Settings group 1: on
21.1431.8401.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.8401.3 Threshold Settings group 1: 400 A
21.1431.8401.6 Operate delay Settings group 1: 0 s

S-DIFF fast 2
Number Settings Value
21.1431.18241.1 Mode Settings group 1: on
21.1431.18241.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.18241.3 Threshold Settings group 1: 2000 A

Line 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Line 1\ 85-21Perm.overr.\ 85-21Perm.over Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip

15 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Protection group Circuit-breaker group(s)


Line 1\ 85-67N Dir. comp.\ 85-67N Dir.com Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ Switch onto fault 1\ Stage 1 Circuit breaker 1:Blk. auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Blk. auto.recl., Circuit breaker 2:Trip
Line 1\ 50/51 OC-3ph 1p 1\ Definite-T 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 50N/51N OC-gnd-A1\ Definite-T 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 67N GFP gnd.sys.1\ Definite-T 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 67N GFP gnd.sys.1\ Definite-T 2 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 67N GFP gnd.sys.1\ Inverse-T 1 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 59 Overvolt.-3ph 1\ Definite-T 2 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 87 Line diff. prot.\ General Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 87 Stub diff. prot. 1\ General Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 1 Circuit breaker 1:Start auto.recl., Circuit breaker 1:Trip, Circuit
breaker 2:Start auto.recl., Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 2 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 3 Circuit breaker 1:Trip, Circuit breaker 2:Trip
Line 1\ 21 Distance prot. 1\ Z 4 Circuit breaker 1:Trip, Circuit breaker 2:Trip

Circuit breaker 1 \General


General \Ref. for %-values
Number Settings Value
301.2311.101 Rated normal current All: 2000.00 A
301.2311.102 Rated voltage All: 500.00 kV

General \Breaker settings


Number Settings Value
301.2311.112 Current thresh. CB open All: 100 A
301.2311.113 1-pole operate allowed All: yes

Circuit breaker 1 \Trip logic


Trip logic
Number Settings Value
301.5341.101 Trip at 2ph short circuit All: 3-pole
301.5341.102 3-pole coupling All: with trip
301.5341.103 Reset of trip command All: with I<

Circuit breaker 1 \Circuit break.


Circuit break.
Number Settings Value
301.4261.101 Output time All: 0.1 s
301.4261.105 Indicat. of breaking values All: always

16 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Circuit breaker 1 \Manual close


Manual close
Number Settings Value
301.6541.101 Action time Settings group 1: 0.3 s
301.6541.102 CB open dropout delay Settings group 1: 0 s

Circuit breaker 1 \Control


Control
Number Settings Value
301.4201.101 Control model All: SBO w. enh. security
301.4201.102 SBO time-out All: 30 s
301.4201.103 Feedback monitoring time All: 1 s
301.4201.104 Check switching authority All: yes
301.4201.105 Check if pos. is reached All: yes
301.4201.106 Check double activat. blk. All: yes
301.4201.107 Check blk. by protection All: yes

Circuit breaker 1 \CB test


CB test
Number Settings Value
301.6151.101 Dead time All: 0.1 s
301.6151.102 Trip only All: false
301.6151.103 Consider current criterion All: false

Circuit breaker 1 \79 Auto. reclosing


General
Number Settings Value
301.1361.6601.1 Mode Settings group 1: off
301.1361.6601.101 79 operating mode All: with op., with act. time
301.1361.6601.102 CB ready check bef. start Settings group 1: no
301.1361.6601.103 Reclai. time aft.succ.cyc. Settings group 1: 3 s
301.1361.6601.104 Block. time aft. man.close Settings group 1: 1 s
301.1361.6601.105 Start signal supervis.time Settings group 1: 0.13 s
301.1361.6601.106 CB ready superv. time Settings group 1: 3 s
301.1361.6601.107 3-pole operate by 79 Settings group 1: yes
301.1361.6601.108 Evolving-fault detection Settings group 1: with trip
301.1361.6601.109 Response to evolv. faults Settings group 1: blocks 79
301.1361.6601.110 Max. dead-time delay Settings group 1: 0.5 s
301.1361.6601.111 Max. dead-time extension Settings group 1: 1.2 s
301.1361.6601.112 Send delay f. remot. close Settings group 1: 0.05 s

General \DLC, RDT


Number Settings Value
301.1361.6601.113 Dead-line check/reduc.d.t All: without

Cycle 1
Number Settings Value
301.1361.6571.102 Start from idle state allow. Settings group 1: yes

17 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


301.1361.6571.103 Action time Settings group 1: 0.2 s
301.1361.6571.108 Dead time aft. 3-pole trip Settings group 1: 0.5 s
301.1361.6571.107 Dead time aft. 1-pole trip Settings group 1: 1.2 s
301.1361.6571.109 Dead time aft. evolv. fault Settings group 1: 1.2 s
301.1361.6571.111 CB ready check bef.close Settings group 1: no
301.1361.6571.110 Synchroch. aft. 3-pole d.t. Settings group 1: none

Cycle 1 \Intern. synchrocheck with


Number Settings Value
301.1361.6571.112 Intern. synchrocheck with

Circuit breaker 1 \25 Synchronization


General
Number Settings Value
301.1151.2311.127 Angle adjust. (transform.) Settings group 1: 0 °

Synchrocheck 1 \General
Number Settings Value
301.1151.5071.1 Mode Settings group 1: off
301.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
301.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
301.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
301.1151.5071.108 Direct close command Settings group 1: no
301.1151.5071.126 Voltage adjustment Settings group 1: 1

Synchrocheck 1 \De-en.gized switch.


Number Settings Value
301.1151.5071.105 Close cmd. at V1< & V2> Settings group 1: no
301.1151.5071.106 Close cmd. at V1> & V2< Settings group 1: no
301.1151.5071.107 Close cmd. at V1< & V2< Settings group 1: no
301.1151.5071.103 V1, V2 without voltage Settings group 1: 20 kV
301.1151.5071.104 V1, V2 with voltage Settings group 1: 320 kV
301.1151.5071.109 Supervision time Settings group 1: 0.1 s

Synchrocheck 1 \Synchr. conditions


Number Settings Value
301.1151.5071.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
301.1151.5071.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
301.1151.5071.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
301.1151.5071.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz
301.1151.5071.124 Max. angle diff. α2>α1 Settings group 1: 10 °
301.1151.5071.125 Max. angle diff. α2<α1 Settings group 1: 10 °

Sychr./Asycr.1 \General
Number Settings Value
301.1151.5041.1 Mode Settings group 1: on
301.1151.5041.101 Min. operating limit Vmin Settings group 1: 450 kV
301.1151.5041.102 Max. operat. limit Vmax Settings group 1: 550 kV

18 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


301.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
301.1151.5041.108 Direct close command Settings group 1: no
301.1151.5041.126 Voltage adjustment Settings group 1: 1

Sychr./Asycr.1 \De-en.gized switch.


Number Settings Value
301.1151.5041.105 Close cmd. at V1< & V2> Settings group 1: yes
301.1151.5041.106 Close cmd. at V1> & V2< Settings group 1: yes
301.1151.5041.107 Close cmd. at V1< & V2< Settings group 1: no
301.1151.5041.103 V1, V2 without voltage Settings group 1: 50 kV
301.1151.5041.104 V1, V2 with voltage Settings group 1: 400 kV
301.1151.5041.109 Supervision time Settings group 1: 0.1 s

Sychr./Asycr.1 \Asynchr. op.mode


Number Settings Value
301.1151.5041.114 Async. operating mode Settings group 1: on
301.1151.5041.113 CB make time Settings group 1: 0.06 s
301.1151.5041.115 Max. voltage diff. V2>V1 Settings group 1: 50 kV
301.1151.5041.116 Max. voltage diff. V2<V1 Settings group 1: 50 kV
301.1151.5041.117 Max. frequency diff. f2>f1 Settings group 1: 0.08 Hz
301.1151.5041.118 Max. frequency diff. f2<f1 Settings group 1: 0.08 Hz

Sychr./Asycr.1 \Synchr. op.mode


Number Settings Value
301.1151.5041.119 Sync. operating mode Settings group 1: off
301.1151.5041.120 f-threshold ASYN<->SYN Settings group 1: 0.01 Hz
301.1151.5041.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
301.1151.5041.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
301.1151.5041.124 Max. angle diff. α2>α1 Settings group 1: 10 °
301.1151.5041.125 Max. angle diff. α2<α1 Settings group 1: 10 °
301.1151.5041.121 Delay close command Settings group 1: 0 s

Circuit breaker 2 \General


General \Ref. for %-values
Number Settings Value
302.2311.101 Rated normal current All: 2000.00 A
302.2311.102 Rated voltage All: 500.00 kV

General \Breaker settings


Number Settings Value
302.2311.112 Current thresh. CB open All: 100 A
302.2311.113 1-pole operate allowed All: yes

Circuit breaker 2 \Trip logic


Trip logic
Number Settings Value
302.5341.101 Trip at 2ph short circuit All: 3-pole

19 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


302.5341.102 3-pole coupling All: with trip
302.5341.103 Reset of trip command All: with I<

Circuit breaker 2 \Circuit break.


Circuit break.
Number Settings Value
302.4261.101 Output time All: 0.1 s
302.4261.105 Indicat. of breaking values All: always

Circuit breaker 2 \Manual close


Manual close
Number Settings Value
302.6541.101 Action time Settings group 1: 0.3 s
302.6541.102 CB open dropout delay Settings group 1: 0 s

Circuit breaker 2 \Control


Control
Number Settings Value
302.4201.101 Control model All: SBO w. enh. security
302.4201.102 SBO time-out All: 30 s
302.4201.103 Feedback monitoring time All: 1 s
302.4201.104 Check switching authority All: yes
302.4201.105 Check if pos. is reached All: yes
302.4201.106 Check double activat. blk. All: yes
302.4201.107 Check blk. by protection All: yes

Circuit breaker 2 \CB test


CB test
Number Settings Value
302.6151.101 Dead time All: 0.1 s
302.6151.102 Trip only All: false
302.6151.103 Consider current criterion All: false

Circuit breaker 2 \79 Auto. reclosing


General
Number Settings Value
302.1361.6601.1 Mode Settings group 1: off
302.1361.6601.101 79 operating mode All: with op., with act. time
302.1361.6601.102 CB ready check bef. start Settings group 1: no
302.1361.6601.103 Reclai. time aft.succ.cyc. Settings group 1: 3 s
302.1361.6601.104 Block. time aft. man.close Settings group 1: 1 s
302.1361.6601.105 Start signal supervis.time Settings group 1: 0.13 s
302.1361.6601.106 CB ready superv. time Settings group 1: 3 s
302.1361.6601.107 3-pole operate by 79 Settings group 1: yes
302.1361.6601.108 Evolving-fault detection Settings group 1: with trip
302.1361.6601.109 Response to evolv. faults Settings group 1: blocks 79

20 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


302.1361.6601.110 Max. dead-time delay Settings group 1: 0.5 s
302.1361.6601.111 Max. dead-time extension Settings group 1: 1.2 s
302.1361.6601.112 Send delay f. remot. close Settings group 1: 0.05 s

General \DLC, RDT


Number Settings Value
302.1361.6601.113 Dead-line check/reduc.d.t All: without

Cycle 1
Number Settings Value
302.1361.6571.102 Start from idle state allow. Settings group 1: yes
302.1361.6571.103 Action time Settings group 1: 0.2 s
302.1361.6571.108 Dead time aft. 3-pole trip Settings group 1: 0.5 s
302.1361.6571.107 Dead time aft. 1-pole trip Settings group 1: 1.2 s
302.1361.6571.109 Dead time aft. evolv. fault Settings group 1: 1.2 s
302.1361.6571.111 CB ready check bef.close Settings group 1: no
302.1361.6571.110 Synchroch. aft. 3-pole d.t. Settings group 1: none

Cycle 1 \Intern. synchrocheck with


Number Settings Value
302.1361.6571.112 Intern. synchrocheck with

Circuit breaker 2 \25 Synchronization


General
Number Settings Value
302.1151.2311.127 Angle adjust. (transform.) Settings group 1: 0 °

Synchrocheck 1 \General
Number Settings Value
302.1151.5071.1 Mode Settings group 1: on
302.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5071.108 Direct close command Settings group 1: no
302.1151.5071.126 Voltage adjustment Settings group 1: 1

Synchrocheck 1 \De-en.gized switch.


Number Settings Value
302.1151.5071.105 Close cmd. at V1< & V2> Settings group 1: no
302.1151.5071.106 Close cmd. at V1> & V2< Settings group 1: no
302.1151.5071.107 Close cmd. at V1< & V2< Settings group 1: no
302.1151.5071.103 V1, V2 without voltage Settings group 1: 20 kV
302.1151.5071.104 V1, V2 with voltage Settings group 1: 320 kV
302.1151.5071.109 Supervision time Settings group 1: 0.1 s

21 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Synchrocheck 1 \Synchr. conditions


Number Settings Value
302.1151.5071.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
302.1151.5071.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
302.1151.5071.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
302.1151.5071.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz
302.1151.5071.124 Max. angle diff. α2>α1 Settings group 1: 10 °
302.1151.5071.125 Max. angle diff. α2<α1 Settings group 1: 10 °

Sychr./Asycr.1 \General
Number Settings Value
302.1151.5041.1 Mode Settings group 1: off
302.1151.5041.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5041.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5041.108 Direct close command Settings group 1: no
302.1151.5041.126 Voltage adjustment Settings group 1: 1

Sychr./Asycr.1 \De-en.gized switch.


Number Settings Value
302.1151.5041.105 Close cmd. at V1< & V2> Settings group 1: no
302.1151.5041.106 Close cmd. at V1> & V2< Settings group 1: no
302.1151.5041.107 Close cmd. at V1< & V2< Settings group 1: no
302.1151.5041.103 V1, V2 without voltage Settings group 1: 20 kV
302.1151.5041.104 V1, V2 with voltage Settings group 1: 320 kV
302.1151.5041.109 Supervision time Settings group 1: 0.1 s

Sychr./Asycr.1 \Asynchr. op.mode


Number Settings Value
302.1151.5041.114 Async. operating mode Settings group 1: on
302.1151.5041.113 CB make time Settings group 1: 0.06 s
302.1151.5041.115 Max. voltage diff. V2>V1 Settings group 1: 20 kV
302.1151.5041.116 Max. voltage diff. V2<V1 Settings group 1: 20 kV
302.1151.5041.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
302.1151.5041.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz

Sychr./Asycr.1 \Synchr. op.mode


Number Settings Value
302.1151.5041.119 Sync. operating mode Settings group 1: on
302.1151.5041.120 f-threshold ASYN<->SYN Settings group 1: 0.01 Hz
302.1151.5041.122 Max. voltage diff. V2>V1 Settings group 1: 20 kV
302.1151.5041.123 Max. voltage diff. V2<V1 Settings group 1: 20 kV
302.1151.5041.124 Max. angle diff. α2>α1 Settings group 1: 10 °
302.1151.5041.125 Max. angle diff. α2<α1 Settings group 1: 10 °
302.1151.5041.121 Delay close command Settings group 1: 0 s

Disconnector 1 \Control
Control
Number Settings Value
601.4201.101 Control model All: SBO w. enh. security

22 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal

Number Settings Value


601.4201.102 SBO time-out All: 30 s
601.4201.103 Feedback monitoring time All: 10 s
601.4201.104 Check switching authority All: yes
601.4201.105 Check if pos. is reached All: yes
601.4201.106 Check double activat. blk. All: yes

Disconnector 1 \Disconnector
Disconnector
Number Settings Value
601.5401.101 Maximum output time All: 10 s
601.5401.102 Seal-in time All: 0 s
601.5401.103 Switching-device type All: disconnector

23 of 23
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Settings
Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 192.168.60.60 (Integrated Ethernet interface)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Show all settings
Hide SIPROTEC extensions in IEC 61850 structure Show all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.

General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.138 Block monitoring dir. All: off

General \Chatter blocking


Number Settings Value
91.123 No. permis.state changes All: 0
91.127 Initial test time All: 1 s
91.124 No. of chatter tests All: 0
91.125 Chatter idle time All: 1 min
91.137 Subsequent test time All: 2 s

General \Control
Number Settings Value
91.162 Blk setting change All: false
91.118 Enable sw.auth. station All: false
91.119 Multiple sw.auth. levels All: false

General \Spontan.indic.
Number Settings Value
91.152 Specific sw. authorities All: false

General \CFC
Number Settings Value
91.139 Fault-display All: with pickup

1 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

General \Test support


Number Settings Value
91.161 CFC chart quality handling All: automatic
91.150 Activate device test mode All: false

Localization
Number Settings Value
6211.139 Unit system All: SI

Time settings
General
Settings Value
Date format All: DD.MM.YYYY

Time source
Settings Value
Fault indication after All: 600 s
Time source 1 Ch1:port E:SNTP
Time source 2 none
Time zone time source 1 All: UTC
Time zone time source 2 All: local
Sync. latency time src.1 All: 0.1 μs
Sync. latency time src.2 All: 0 μs

Time zone and daylight saving time


Settings Value
Time zone offset to UTC All: -240 min
Offset daylight sav. time All: 60 min
Switch daylight sav. time true
Start of daylight sav. time Last Sunday in October at 12:00 AM
End of daylight sav. time Third Sunday in March at 12:00 AM

Power system \General


General
Number Settings Value
11.2311.101 Phase sequence All: ABC

Power system \Meas.point I-3ph 1


CT 3-phase \General
Number Settings Value
11.931.8881.115 CT connection All: 3-phase
11.931.8881.127 Tracking All: active
11.931.8881.130 Measuring-point ID All: 1

2 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

CT 3-phase \CT phases


Number Settings Value
11.931.8881.101 Rated primary current All: 100 A
11.931.8881.102 Rated secondary current All: 1 A
11.931.8881.117 Current range All: 100 x IR
11.931.8881.118 Internal CT type All: CT protection
11.931.8881.116 Neutr.point in dir.of ref.obj All: yes
11.931.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A

CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B

CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C

Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 50 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: off
11.931.2431.102 Threshold Settings group 1: 10 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s

Power system \Meas.point I-3ph 2


CT 3-phase \General
Number Settings Value
11.932.8881.115 CT connection All: 3-phase

3 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Number Settings Value


11.932.8881.127 Tracking All: active
11.932.8881.130 Measuring-point ID All: 2

CT 3-phase \CT phases


Number Settings Value
11.932.8881.101 Rated primary current All: 100 A
11.932.8881.102 Rated secondary current All: 1 A
11.932.8881.117 Current range All: 100 x IR
11.932.8881.118 Internal CT type All: CT protection
11.932.8881.116 Neutr.point in dir.of ref.obj All: yes
11.932.8881.114 Inverted phases All: none

CT 1
Number Settings Value
11.932.3841.103 Magnitude correction All: 1
11.932.3841.117 Phase All: I A

CT 2
Number Settings Value
11.932.3842.103 Magnitude correction All: 1
11.932.3842.117 Phase All: I B

CT 3
Number Settings Value
11.932.3843.103 Magnitude correction All: 1
11.932.3843.117 Phase All: I C

Supv. balan. I
Number Settings Value
11.932.2491.1 Mode Settings group 1: on
11.932.2491.101 Release threshold Settings group 1: 50 A
11.932.2491.102 Threshold min/max Settings group 1: 0.5
11.932.2491.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.I
Number Settings Value
11.932.2551.1 Mode Settings group 1: on
11.932.2551.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum I
Number Settings Value
11.932.2431.1 Mode Settings group 1: off
11.932.2431.102 Threshold Settings group 1: 10 A
11.932.2431.101 Slope factor Settings group 1: 0.1
11.932.2431.6 Delay supervision alarm Settings group 1: 5 s

4 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Power system \Meas.point I-1ph 1


General
Number Settings Value
11.951.2311.101 Rated primary current All: 100 A
11.951.2311.102 Rated secondary current All: 1 A
11.951.2311.103 Current range All: 100 x IR
11.951.2311.104 Internal CT type All: CT protection
11.951.2311.116 Term. 1,3,5,7 in dir. of obj. All: yes
11.951.2311.105 Tracking All: inactive
11.951.2311.130 Measuring-point ID All: 3

CT 1
Number Settings Value
11.951.3841.103 Magnitude correction All: 1
11.951.3841.117 Phase All: Ix

Power system \Meas.point V-3ph 1


VT 3-phase
Number Settings Value
11.941.8911.101 Rated primary voltage All: 500 kV
11.941.8911.102 Rated secondary voltage All: 115 V
11.941.8911.104 VT connection All: 3 ph-to-gnd voltages
11.941.8911.106 Inverted phases All: none
11.941.8911.111 Tracking All: active
11.941.8911.130 Measuring-point ID All: 4

VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A

VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B

VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
11.941.3813.108 Phase All: V C

Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: off
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s

5 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: off
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s

VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s

Power system \Meas.point V-1ph 1


General
Number Settings Value
11.961.2311.101 Rated primary voltage All: 500 kV
11.961.2311.102 Rated secondary voltage All: 111 V
11.961.2311.103 Tracking All: inactive
11.961.2311.130 Measuring-point ID All: 5

VT 1
Number Settings Value
11.961.3811.103 Magnitude correction All: 1
11.961.3811.108 Phase All: V B

VT miniatureCB
Number Settings Value
11.961.2641.101 Response time Settings group 1: 0 s

Recording \Fault recorder


Control
Number Settings Value
51.791.2761.130 Fault recording All: with pickup
51.791.2761.131 Storage All: always
51.791.2761.111 Maximum record time All: 5 s
51.791.2761.112 Pre-trigger time All: 0.5 s
51.791.2761.113 Post-trigger time All: 0.5 s
51.791.2761.116 Manual record time All: 0.5 s
51.791.2761.140 Sampling frequency All: 2 kHz

6 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Transformer side 1 \General


General \Rated values
Number Settings Value
911.91.103 Rated apparent power All: 80 MVA
911.91.102 Rated voltage All: 500 kV
911.91.101 Rated current All: 92 A

General \Side data


Number Settings Value
911.91.149 Neutral point Settings group 1: isolated
911.91.104 Winding configuration Settings group 1: Y (Wye)
911.91.163 Vector group numeral All: 0
911.91.130 Side number All: Side 1
911.91.210 MI3ph1 usesMeasP with ID All: 1
911.91.214 M I-1ph uses MeasP with ID All: 3
911.91.215 CT mismatch M I-3ph 1 All: 1.083
911.91.223 CT mismatch M I-1ph All: 1.083

General \Measurements
Number Settings Value
911.91.158 P, Q sign Settings group 1: not reversed

Transformer side 1 \Process monitor


Transformer side 1 \49 Th.overl.-A 1
49 Th.overl. 1
Number Settings Value
911.191.601.1 Mode Settings group 1: off
911.191.601.2 Operate & flt.rec. blocked Settings group 1: yes
911.191.601.101 Threshold current warning Settings group 1: 86.6 A
911.191.601.104 Threshold thermal warn. Settings group 1: 90 %
911.191.601.105 Dropout threshold operate Settings group 1: 90 %
911.191.601.112 Emerg. start T overtravel Settings group 1: 300 s
911.191.601.106 K-factor Settings group 1: 1.1
911.191.601.110 Thermal time constant Settings group 1: 900 s
911.191.601.111 Cooling time constant Settings group 1: 3600 s
911.191.601.107 Imax thermal Settings group 1: 216.5 A
911.191.601.108 Imin cooling Settings group 1: 43.3 A
911.191.601.109 Temperature rise at Irated Settings group 1: 70 K
911.191.601.113 Storage of thermal replica Settings group 1: no
911.191.601.114 Behav. at I> Imax therm. Settings group 1: current limiting
911.191.601.118 Default temperature Settings group 1: 40 °C
911.191.601.117 Minimal temperature Settings group 1: -20 °C

Transformer side 1 \50/51 OC-3ph-B1


Definite-T 1
Number Settings Value
911.1941.661.1 Mode Settings group 1: on
911.1941.661.2 Operate & flt.rec. blocked Settings group 1: no
911.1941.661.27 Blk. w. inrush curr. detect. Settings group 1: yes

7 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Number Settings Value


911.1941.661.8 Method of measurement Settings group 1: fundamental comp.
911.1941.661.3 Threshold Settings group 1: 370 A
911.1941.661.6 Operate delay Settings group 1: 0.1 s

Inverse-T 1
Number Settings Value
911.1941.691.1 Mode Settings group 1: on
911.1941.691.2 Operate & flt.rec. blocked Settings group 1: no
911.1941.691.27 Blk. w. inrush curr. detect. Settings group 1: yes
911.1941.691.8 Method of measurement Settings group 1: fundamental comp.
911.1941.691.3 Threshold Settings group 1: 111 A
911.1941.691.130 Type of character. curve Settings group 1: IEC normal inverse
911.1941.691.131 Reset Settings group 1: instantaneous
911.1941.691.101 Time dial Settings group 1: 0.14

Transformer side 1 \50N/51N OC-gnd-B1


Definite-T 1
Number Settings Value
911.1731.751.1 Mode Settings group 1: on
911.1731.751.2 Operate & flt.rec. blocked Settings group 1: no
911.1731.751.27 Blk. w. inrush curr. detect. Settings group 1: yes
911.1731.751.8 Method of measurement Settings group 1: fundamental comp.
911.1731.751.3 Threshold Settings group 1: 185 A
911.1731.751.6 Operate delay Settings group 1: 0.1 s

Inverse-T 1
Number Settings Value
911.1731.781.1 Mode Settings group 1: on
911.1731.781.2 Operate & flt.rec. blocked Settings group 1: no
911.1731.781.27 Blk. w. inrush curr. detect. Settings group 1: yes
911.1731.781.8 Method of measurement Settings group 1: fundamental comp.
911.1731.781.3 Threshold Settings group 1: 20 A
911.1731.781.108 Type of character. curve Settings group 1: IEC normal inverse
911.1731.781.109 Reset Settings group 1: instantaneous
911.1731.781.101 Time dial Settings group 1: 0.29

Transformer side 1 \87N REF 1


87N REF 1
Number Settings Value
911.10081.1 Mode Settings group 1: on
911.10081.2 Operate & flt.rec. blocked Settings group 1: no
911.10081.103 Threshold Settings group 1: 0.06 I/IrObj
911.10081.105 Slope Settings group 1: 0.05
911.10081.109 Operate delay Settings group 1: 0 s

8 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Transformer side 1 \Inrush detect.


Inrush detect.
Number Settings Value
911.4141.1 Mode All: on
911.4141.106 Operat.-range limit Imax Settings group 1: 649.5 A
911.4141.111 Blocking with CWA Settings group 1: yes
911.4141.110 Blocking with 2. harmonic Settings group 1: yes
911.4141.102 2nd harmonic content Settings group 1: 15 %
911.4141.112 Crossblocking Settings group 1: no
911.4141.109 Crossblocking time Settings group 1: 0.06 s
911.4141.114 Start flt.rec Settings group 1: yes

Transformer side 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer side 1\ 87N REF 1 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure
Transformer side 1\ 49 Th.overl.-A 1\ 49 Th.overl. 1 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure
Transformer side 1\ 50/51 OC-3ph-B1\ Definite-T 1 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure
Transformer side 1\ 50/51 OC-3ph-B1\ Inverse-T 1 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure
Transformer side 1\ 50N/51N OC-gnd-B1\ Definite-T 1 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure
Transformer side 1\ 50N/51N OC-gnd-B1\ Inverse-T 1 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure

Transformer side 2 \General


General \Rated values
Number Settings Value
912.91.103 Rated apparent power All: 80 MVA
912.91.102 Rated voltage All: 500 kV
912.91.101 Rated current All: 92 A

General \Side data


Number Settings Value
912.91.149 Neutral point Settings group 1: isolated
912.91.104 Winding configuration Settings group 1: Y (Wye)
912.91.163 Vector group numeral All: 0
912.91.130 Side number All: Side 2
912.91.210 MI3ph1 usesMeasP with ID All: 2
912.91.215 CT mismatch M I-3ph 1 All: 1.083

Transformer side 2 \Process monitor


Transformer diff. 1 \87T diff. prot. 1
General
Number Settings Value
901.1691.2311.105 CT mismatch side 1 M3ph 1 All: 1.083
901.1691.2311.109 CT mismatch side 1 M1ph All: 1.083
901.1691.2311.110 CT mismatch side 2 M3ph 1 All: 1.083
901.1691.2311.191 Reference side is All: Side 1
901.1691.2311.151 MU-ID Side 1 Mp3ph 1 All: 1
901.1691.2311.155 MU-ID Side 1 Mp1ph All: 3
901.1691.2311.156 MU-ID Side 2 Mp3ph 1 All: 2

9 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

I-DIFF \General
Number Settings Value
901.1691.11041.1 Mode Settings group 1: on
901.1691.11041.2 Operate & flt.rec. blocked Settings group 1: no
901.1691.11041.6 Operate delay Settings group 1: 0 s

I-DIFF \Operate curve


Number Settings Value
901.1691.11041.3 Threshold Settings group 1: 0.1 I/IrObj
901.1691.11041.100 Slope 1 Settings group 1: 0.2
901.1691.11041.101 Intersection 1 Irest Settings group 1: 1.11 I/IrObj
901.1691.11041.102 Slope 2 Settings group 1: 0.5
901.1691.11041.103 Intersection 2 Irest Settings group 1: 5 I/IrObj

I-DIFF \Starting detection


Number Settings Value
901.1691.11041.106 Starting detection Settings group 1: no
901.1691.11041.107 Thresh. startup detection Settings group 1: 0.1 I/IrObj
901.1691.11041.108 Factor increasing char. Settings group 1: 2
901.1691.11041.109 Max. perm. Start. time Settings group 1: 5 s

I-DIFF \DC offset detection


Number Settings Value
901.1691.11041.110 Factor increasing char. DC Settings group 1: 2.3

I-DIFF \Inrush blocking


Number Settings Value
901.1691.11041.115 Blocking with 2. harmonic Settings group 1: yes
901.1691.11041.116 2nd harmonic content Settings group 1: 15 %
901.1691.11041.117 Crossblock. time 2nd har. Settings group 1: 0 s
901.1691.11041.118 Blocking with CWA Settings group 1: no

I-DIFF \Overexcit. blocking


Number Settings Value
901.1691.11041.121 Blocking with 3rd harm. Settings group 1: no
901.1691.11041.122 3rd harmonics content Settings group 1: 30 %
901.1691.11041.123 Crossblock. time 3rd har. Settings group 1: 0 s
901.1691.11041.124 Blocking with 5th harm. Settings group 1: yes
901.1691.11041.125 5th harmonics content Settings group 1: 30 %
901.1691.11041.126 Crossblock. time 5th har. Settings group 1: 0 s
901.1691.11041.127 Limit Idiff 3., 5. harmonics Settings group 1: 1.5 I/IrObj

I-DIFF \Ext. fault detection


Number Settings Value
901.1691.11041.128 Threshold add-on stabiliz. Settings group 1: 2 I/IrObj
901.1691.11041.129 Time of add-on stabiliz. Settings group 1: 0.3 s
901.1691.11041.130 Crossblk. time add-on st. Settings group 1: 0.3 s

10 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

I-DIFF fast
Number Settings Value
901.1691.11071.1 Mode Settings group 1: on
901.1691.11071.3 Threshold Settings group 1: 2 I/IrObj
901.1691.11071.6 Operate delay Settings group 1: 0 s
901.1691.11071.100 Operate & flt.rec. blocked Settings group 1: no

Transformer diff. 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transformer diff. 1\ 87T diff. prot. 1\ I-DIFF Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure
Transformer diff. 1\ 87T diff. prot. 1\ I-DIFF fast Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure

Transform. neut.p 1 \General


General \Rated values
Number Settings Value
921.9421.104 Rated current All: 92 A

General \Power-system data


Number Settings Value
921.9421.214 M I-1ph uses MeasP with ID All: 3
921.9421.223 CT mismatch M I-1ph All: 1.08

Transform. neut.p 1 \50N/51N OC-1ph-A1


Definite-T 1
Number Settings Value
921.211.12661.1 Mode Settings group 1: on
921.211.12661.2 Operate & flt.rec. blocked Settings group 1: no
921.211.12661.27 Blk. w. inrush curr. detect. Settings group 1: no
921.211.12661.8 Method of measurement Settings group 1: fundamental comp.
921.211.12661.3 Threshold Settings group 1: 15 A
921.211.12661.6 Operate delay Settings group 1: 60 s

Definite-T 2
Number Settings Value
921.211.12662.1 Mode Settings group 1: on
921.211.12662.2 Operate & flt.rec. blocked Settings group 1: no
921.211.12662.27 Blk. w. inrush curr. detect. Settings group 1: no
921.211.12662.8 Method of measurement Settings group 1: fundamental comp.
921.211.12662.3 Threshold Settings group 1: 25 A
921.211.12662.6 Operate delay Settings group 1: 2 s

Transform. neut.p 1\Ciruit-breaker interaction


Protection group Circuit-breaker group(s)
Transform. neut.p 1\ 50N/51N OC-1ph-A1\ Definite-T 1 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure
Transform. neut.p 1\ 50N/51N OC-1ph-A1\ Definite-T 2 Circuit breaker 1:Trip, Circuit breaker 1:Start CB failure

11 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Circuit breaker 1 \General


General \Ref. for %-values
Number Settings Value
201.2311.101 Rated normal current All: 100.00 A
201.2311.102 Rated voltage All: 500 kV

General \Breaker settings


Number Settings Value
201.2311.112 Current thresh. CB open All: 10 A

Circuit breaker 1 \Trip logic


Trip logic
Number Settings Value
201.5341.103 Reset of trip command All: with I<

Circuit breaker 1 \Circuit break.


Circuit break.
Number Settings Value
201.4261.101 Output time All: 0.1 s

Circuit breaker 1 \Manual close


Manual close
Number Settings Value
201.6541.101 Action time Settings group 1: 0.3 s

Circuit breaker 1 \Control


Control
Number Settings Value
201.4201.101 Control model All: SBO w. enh. security
201.4201.102 SBO time-out All: 30 s
201.4201.103 Feedback monitoring time All: 1 s
201.4201.104 Check switching authority All: yes
201.4201.105 Check if pos. is reached All: yes
201.4201.106 Check double activat. blk. All: yes
201.4201.107 Check blk. by protection All: yes

Circuit breaker 1 \CB test


CB test
Number Settings Value
201.6151.101 Dead time All: 0.1 s

12 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Circuit breaker 1 \50BF CB fail.1


50BF CB fail.1
Number Settings Value
201.4381.1 Mode Settings group 1: on
201.4381.105 Holding int. start signal Settings group 1: yes
201.4381.107 Start via binary input All: 2 channel
201.4381.106 Holding ext. start signal Settings group 1: no
201.4381.111 Sup.time for release signl Settings group 1: 0.06 s
201.4381.103 CB aux.cont. crit. allowed Settings group 1: no
201.4381.104 Dropout Settings group 1: with effective criterion
201.4381.108 Retrip after T1 Settings group 1: parallel start T2, T1
201.4381.102 Threshold phase current Settings group 1: 25 A
201.4381.101 Threshold sensitive Settings group 1: 20 A
201.4381.109 Delay T1 for 3-pole retrip Settings group 1: 0.1 s
201.4381.110 Delay T2 for 3-pole trip Settings group 1: 0.2 s
201.4381.112 Minimum operate time Settings group 1: 0.1 s
201.4381.120 3I0 criterion All: Plausibility check
201.4381.121 I2 criterion All: Plausibility check
201.4381.122 Threshold 3I0 dir. release Settings group 1: 25 A
201.4381.123 Threshold I2 dir. release Settings group 1: 25 A
201.4381.124 Monit. time for BI ">Start" Settings group 1: 15 s
201.4381.125 Monit.tm. f.BI ">Release" Settings group 1: 15 s

Circuit breaker 1 \25 Synchronization


General
Number Settings Value
201.1151.2311.127 Angle adjust. (transform.) Settings group 1: 0 °

Synchrocheck 1 \General
Number Settings Value
201.1151.5071.1 Mode Settings group 1: off
201.1151.5071.101 Min. operating limit Vmin Settings group 1: 391.30 kV
201.1151.5071.102 Max. operat. limit Vmax Settings group 1: 478.26 kV
201.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
201.1151.5071.108 Direct close command Settings group 1: no
201.1151.5071.126 Voltage adjustment Settings group 1: 1

Synchrocheck 1 \De-en.gized switch.


Number Settings Value
201.1151.5071.105 Close cmd. at V1< & V2> Settings group 1: no
201.1151.5071.106 Close cmd. at V1> & V2< Settings group 1: no
201.1151.5071.107 Close cmd. at V1< & V2< Settings group 1: no
201.1151.5071.103 V1, V2 without voltage Settings group 1: 21.74 kV
201.1151.5071.104 V1, V2 with voltage Settings group 1: 347.83 kV
201.1151.5071.109 Supervision time Settings group 1: 0.1 s

Synchrocheck 1 \Synchr. conditions


Number Settings Value
201.1151.5071.122 Max. voltage diff. V2>V1 Settings group 1: 21.74 kV
201.1151.5071.123 Max. voltage diff. V2<V1 Settings group 1: 21.74 kV
201.1151.5071.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz

13 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

Number Settings Value


201.1151.5071.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz
201.1151.5071.124 Max. angle diff. α2>α1 Settings group 1: 10 °
201.1151.5071.125 Max. angle diff. α2<α1 Settings group 1: 10 °

Sychr./Asycr.1 \General
Number Settings Value
201.1151.5041.1 Mode Settings group 1: off
201.1151.5041.101 Min. operating limit Vmin Settings group 1: 391.30 kV
201.1151.5041.102 Max. operat. limit Vmax Settings group 1: 478.26 kV
201.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
201.1151.5041.108 Direct close command Settings group 1: no
201.1151.5041.126 Voltage adjustment Settings group 1: 1

Sychr./Asycr.1 \De-en.gized switch.


Number Settings Value
201.1151.5041.105 Close cmd. at V1< & V2> Settings group 1: no
201.1151.5041.106 Close cmd. at V1> & V2< Settings group 1: no
201.1151.5041.107 Close cmd. at V1< & V2< Settings group 1: no
201.1151.5041.103 V1, V2 without voltage Settings group 1: 21.74 kV
201.1151.5041.104 V1, V2 with voltage Settings group 1: 347.83 kV
201.1151.5041.109 Supervision time Settings group 1: 0.1 s

Sychr./Asycr.1 \Asynchr. op.mode


Number Settings Value
201.1151.5041.114 Async. operating mode Settings group 1: on
201.1151.5041.113 CB make time Settings group 1: 0.06 s
201.1151.5041.115 Max. voltage diff. V2>V1 Settings group 1: 21.74 kV
201.1151.5041.116 Max. voltage diff. V2<V1 Settings group 1: 21.74 kV
201.1151.5041.117 Max. frequency diff. f2>f1 Settings group 1: 0.1 Hz
201.1151.5041.118 Max. frequency diff. f2<f1 Settings group 1: 0.1 Hz

Sychr./Asycr.1 \Synchr. op.mode


Number Settings Value
201.1151.5041.119 Sync. operating mode Settings group 1: on
201.1151.5041.120 f-threshold ASYN<->SYN Settings group 1: 0.01 Hz
201.1151.5041.122 Max. voltage diff. V2>V1 Settings group 1: 21.74 kV
201.1151.5041.123 Max. voltage diff. V2<V1 Settings group 1: 21.74 kV
201.1151.5041.124 Max. angle diff. α2>α1 Settings group 1: 10 °
201.1151.5041.125 Max. angle diff. α2<α1 Settings group 1: 10 °
201.1151.5041.121 Delay close command Settings group 1: 0 s

Analog units \MT module 1


MT in 1
Number Settings Value
826.1832.5491.101 Meas. transduc. I/O type All: Current input
826.1832.5491.103 Unit All: m
826.1832.5491.108 Resolution All: 0.1
826.1832.5491.107 Range active All: false
826.1832.5491.104 Conversion factor All: 100

14 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal

MT in 2
Number Settings Value
826.1832.5492.101 Meas. transduc. I/O type All: Current input
826.1832.5492.103 Unit All: m
826.1832.5492.108 Resolution All: 0.1
826.1832.5492.107 Range active All: false
826.1832.5492.104 Conversion factor All: 100

MT in 3
Number Settings Value
826.1832.5493.101 Meas. transduc. I/O type All: Current input
826.1832.5493.103 Unit All: m
826.1832.5493.108 Resolution All: 0.1
826.1832.5493.107 Range active All: false
826.1832.5493.104 Conversion factor All: 100

MT in 4
Number Settings Value
826.1832.5494.101 Meas. transduc. I/O type All: Current input
826.1832.5494.103 Unit All: m
826.1832.5494.108 Resolution All: 0.1
826.1832.5494.107 Range active All: false
826.1832.5494.104 Conversion factor All: 100

15 of 15
B00_R00_F006_prn_16_42_04

AYOLAS / 500/220kV / 87B 500kV /


SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

AYOLAS / 500/220kV / 87B 500kV / B00_R00_F006

MLFB: 7SS5220**B921!A0
Parameter-set version: V04.72.01
Device path: C:\PRESEL\AYOLAS DIGSI 4 V4.88
\AYOLAS ECP 87B 500KV\P7DI\GV\SD\00000009
Author: A. Cangrejo
Creation date: 02.05.13 09:26:28
Last modified: 28.04.18 15:05:06
Operating mode: Offline
Comment:
Setting values in: Secondary value description

PRINT - CONTENTS
1 Substation Data ....................................................................................................................................................… 3
1.1 Group Power System Data 1; Group Power System ...........................................................................................… 3
2 Settings groups ....................................................................................................................................................… 4
2.1 Group Protection general; Group Power System ..................................................................................................... 4
2.2 Group Bus Bar Protection; Group Bus Zone ............................................................................................................ 4
2.3 Group Bus Bar Protection; Group Check Zone ........................................................................................................ 4
2.4 Group Breaker Failure Protection; Group Breaker Failure ....................................................................................... 4
2.5 Group Monitoring; Group General ........................................................................................................................… 5
2.6 Group Monitoring; Group Idiff Superv ..................................................................................................................… 5
2.7 Group Monitoring; Group 0-Cross Superv ............................................................................................................… 5
2.8 Group Monitoring; Group CB/DCO Superv ..........................................................................................................… 5
2.9 Group Monitoring; Group CB Test ........................................................................................................................… 6
3 Bay unit allocation ................................................................................................................................................… 7
3.1 Bay unit allocation ................................................................................................................................................… 7
4 Bay units ...............................................................................................................................................................… 8
4.1 Function blocks ....................................................................................................................................................… 8
4.1.1 Group Bay Unit @01; Group General ..................................................................................................................… 8
4.1.2 Group Bay Unit @01; Group Breaker Failure .......................................................................................................… 8
4.1.3 Group Bay Unit @01; Group End fault stage .......................................................................................................… 9
4.1.4 Group Bay Unit @01; Group Breaker ...................................................................................................................… 9
4.2 Function blocks ....................................................................................................................................................… 9
4.2.1 Group Bay Unit @02; Group General ..................................................................................................................… 9
4.2.2 Group Bay Unit @02; Group Breaker Failure .......................................................................................................… 9
4.2.3 Group Bay Unit @02; Group End fault stage .....................................................................................................… 10
4.2.4 Group Bay Unit @02; Group Breaker .................................................................................................................… 10
4.3 Function blocks ..................................................................................................................................................… 10
4.3.1 Group Bay Unit @03; Group General ................................................................................................................… 10
4.3.2 Group Bay Unit @03; Group Breaker Failure .....................................................................................................… 11
4.3.3 Group Bay Unit @03; Group End fault stage .....................................................................................................… 11
4.3.4 Group Bay Unit @03; Group Breaker .................................................................................................................… 11
4.4 Function blocks ..................................................................................................................................................… 12
4.4.1 Group Bay Unit @04; Group General ................................................................................................................… 12
4.4.2 Group Bay Unit @04; Group Breaker Failure .....................................................................................................… 12
4.4.3 Group Bay Unit @04; Group End fault stage .....................................................................................................… 13
4.4.4 Group Bay Unit @04; Group Breaker .................................................................................................................… 13
4.5 Function blocks ..................................................................................................................................................… 13
4.5.1 Group Bay Unit @05; Group General ................................................................................................................… 13

Page 1 of 15
B00_R00_F006_prn_16_42_04

AYOLAS / 500/220kV / 87B 500kV /


SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

4.5.2 Group Bay Unit @05; Group Breaker Failure .....................................................................................................… 13


4.5.3 Group Bay Unit @05; Group End fault stage .....................................................................................................… 14
4.5.4 Group Bay Unit @05; Group Breaker .................................................................................................................… 14
4.6 Function blocks ..................................................................................................................................................… 14
4.6.1 Group Bay Unit @06; Group General ................................................................................................................… 14
4.6.2 Group Bay Unit @06; Group Breaker Failure .....................................................................................................… 15
4.6.3 Group Bay Unit @06; Group End fault stage .....................................................................................................… 15
4.6.4 Group Bay Unit @06; Group Breaker .................................................................................................................… 15

Page 2 of 15
B00_R00_F006_prn_16_42_04
Substation Data
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

1 Substation Data

1.1 Group Power System Data 1; Group Power System


Group Power System Data 1; Group Power System
No. Settings Value Group

5104 Nominal frequency 50 Hz All

Page 3 of 15
B00_R00_F006_prn_16_42_04
Settings groups
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

2 Settings groups

2.1 Group Protection general; Group Power System


Group Protection general; Group Power System
No. Settings Value Group

6106 Minimum duration of TRIP command 0.15 sec All


6320A Sensitive characteristic switchover blocked All
6318 Control release for bay units released All
5401 Selective protection for transfer busbar YES All
5112A Bay unit output enable during test mode NO All
5108A Test mode for module SK OFF All
5111 Language of bay units English All
6120A Additional criterion for tripping nonexistent All

2.2 Group Bus Bar Protection; Group Bus Zone


Group Bus Bar Protection; Group Bus Zone
No. Settings Value Group

6101 Stabilizing factor - BZ 0.65 All


6102 Diff-current threshold - BZ 1.00 I / Ino All

2.3 Group Bus Bar Protection; Group Check Zone


Group Bus Bar Protection; Group Check Zone
No. Settings Value Group

6103 Stabilizing factor - CZ 0.50 All


6104 Diff-current threshold - CZ 1.00 I / Ino All

2.4 Group Breaker Failure Protection; Group Breaker Failure


Group Breaker Failure Protection; Group Breaker Failure
No. Settings Value Group

6201 Stabilizing factor BF protection 0.25 All

Page 4 of 15
B00_R00_F006_prn_16_42_04

AYOLAS / 500/220kV / 87B 500kV /


SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

2.5 Group Monitoring; Group General


Group Monitoring; Group General
No. Settings Value Group

6317 Supervision bin. input TRIP-Release 0.06 sec All

2.6 Group Monitoring; Group Idiff Superv


Group Monitoring; Group Idiff Superv
No. Settings Value Group

6306 Differential current supervision OFF All


6307 Time delay for diff-current supervision 2.00 sec All
6308 Limit value diff-current supervision -BZ 0.25 I / Ino All
6309 Limit value diff-current supervision -CZ 0.20 I / Ino All
6310 Diff-current supervision mode -BZ blocking during the fault All
6311 Diff-current supervision mode -CZ alarm without blocking All

2.7 Group Monitoring; Group 0-Cross Superv


Group Monitoring; Group 0-Cross Superv
No. Settings Value Group

6312A Zero crossing supervision ON All


6313A Threshold for zero crossing supervision 0.50 I / Ino All

2.8 Group Monitoring; Group CB/DCO Superv


Group Monitoring; Group CB/DCO Superv
No. Settings Value Group

6315 CB supervision time 7.00 sec All


6301 Limit value disconnector time 15.00 sec All
6302 Reaction on disconnector malfunction alarm without blocking All
6303 Treatment disconnector status on DC fail old disconnector status All
6304 Treatment disconn. status not plausible old disconnector status All

Page 5 of 15
B00_R00_F006_prn_16_42_04
Group Monitoring; Group CB Test
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

2.9 Group Monitoring; Group CB Test


Group Monitoring; Group CB Test
No. Settings Value Group

6316 Limit value for circuit breaker test 0.05 I / In All

Page 6 of 15
B00_R00_F006_prn_16_42_04
Bay unit allocation
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

3 Bay unit allocation

3.1 Bay unit allocation


Bay unit allocation
No. bay unit SIPROTEC device

1 BU@ 1 B01_R11_F016
2 BU@ 2 B02_R12_F016
3 BU@ 3 B01_R21_F016
4 BU@ 4 B02_R22_F016
5 BU@ 5 B03_R13_F016
6 BU@ 6 B03_R23_F016

Page 7 of 15
B00_R00_F006_prn_16_42_04
Bay units
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

4 Bay units

4.1 Function blocks

4.1.1 Group Bay Unit @01; Group General


Group Bay Unit @01; Group General
No. Settings Value Group

0112 Bay status in service All


0106A Combi-Coupler NO All
0151A Maintenance for disconnector 1 YES All
0152A Maintenance for disconnector 2 YES All
0153A Maintenance for disconnector 3 YES All
0154A Maintenance for disconnector 4 YES All
0155A Maintenance for disconnector 5 YES All
0156A Maintenance for CB YES All

4.1.2 Group Bay Unit @01; Group Breaker Failure


Group Bay Unit @01; Group Breaker Failure
No. Settings Value Group

0114 Binary input mode / supervision BF Initiation and release with supervision All
0115 Operation mode BF TRIP repetition with current query All
0116 Low-current mode BF OFF All
0117 TRIP repeat mode 3pole All
0118 Current threshold for BF 0.25 I / In All
0119A Current threshold for BF - EF 0.20 I / In All
0120 Time delay for BF with 1-pole faults 0.13 sec All
0121 Time delay for BF with multi-pole faults 0.20 sec All
0122 Time delay for BF low current mode 0.20 sec All
0123A Time delay for BF pulse mode 0.20 sec All
0124 Time delay BF after CB fault 0.10 sec All
0125 Time delay for TRIP repeat 0.10 sec All
0126 Time delay for CB open 0.05 sec All
0127 Supervision bin. input BF-release 15.00 sec All
0128 Supervision time BF start / release 0.06 sec All

Page 8 of 15
B00_R00_F006_prn_16_42_04
Group Bay Unit @01; Group End fault stage
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

4.1.3 Group Bay Unit @01; Group End fault stage


Group Bay Unit @01; Group End fault stage
No. Settings Value Group

0129 End fault protection ON All

4.1.4 Group Bay Unit @01; Group Breaker


Group Bay Unit @01; Group Breaker
No. Settings Value Group

0113 Current threshold for TRIP release 0.05 I / In All

4.2 Function blocks

4.2.1 Group Bay Unit @02; Group General


Group Bay Unit @02; Group General
No. Settings Value Group

0212 Bay status in service All


0206A Combi-Coupler NO All
0251A Maintenance for disconnector 1 YES All
0252A Maintenance for disconnector 2 YES All
0253A Maintenance for disconnector 3 YES All
0254A Maintenance for disconnector 4 YES All
0255A Maintenance for disconnector 5 YES All
0256A Maintenance for CB YES All

4.2.2 Group Bay Unit @02; Group Breaker Failure


Group Bay Unit @02; Group Breaker Failure
No. Settings Value Group

0214 Binary input mode / supervision BF Initiation and release with supervision All
0215 Operation mode BF TRIP repetition with current query All
0216 Low-current mode BF OFF All
0217 TRIP repeat mode 3pole All
0218 Current threshold for BF 0.25 I / In All
0219A Current threshold for BF - EF 0.20 I / In All
0220 Time delay for BF with 1-pole faults 0.20 sec All

Page 9 of 15
B00_R00_F006_prn_16_42_04

AYOLAS / 500/220kV / 87B 500kV /


SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

Group Bay Unit @02; Group Breaker Failure(2)


No. Settings Value Group

0221 Time delay for BF with multi-pole faults 0.20 sec All
0222 Time delay for BF low current mode 0.20 sec All
0223A Time delay for BF pulse mode 0.20 sec All
0224 Time delay BF after CB fault 0.10 sec All
0225 Time delay for TRIP repeat 0.10 sec All
0226 Time delay for CB open 0.05 sec All
0227 Supervision bin. input BF-release 15.00 sec All
0228 Supervision time BF start / release 0.06 sec All

4.2.3 Group Bay Unit @02; Group End fault stage


Group Bay Unit @02; Group End fault stage
No. Settings Value Group

0229 End fault protection ON All

4.2.4 Group Bay Unit @02; Group Breaker


Group Bay Unit @02; Group Breaker
No. Settings Value Group

0213 Current threshold for TRIP release 0.05 I / In All

4.3 Function blocks

4.3.1 Group Bay Unit @03; Group General


Group Bay Unit @03; Group General
No. Settings Value Group

0312 Bay status in service All


0306A Combi-Coupler NO All
0351A Maintenance for disconnector 1 YES All
0352A Maintenance for disconnector 2 YES All
0353A Maintenance for disconnector 3 YES All
0354A Maintenance for disconnector 4 YES All
0355A Maintenance for disconnector 5 YES All
0356A Maintenance for CB YES All

Page 10 of 15
B00_R00_F006_prn_16_42_04

AYOLAS / 500/220kV / 87B 500kV /


SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

4.3.2 Group Bay Unit @03; Group Breaker Failure


Group Bay Unit @03; Group Breaker Failure
No. Settings Value Group

0314 Binary input mode / supervision BF Initiation and release with supervision All
0315 Operation mode BF TRIP repetition with current query All
0316 Low-current mode BF OFF All
0317 TRIP repeat mode 3pole All
0318 Current threshold for BF 0.25 I / In All
0319A Current threshold for BF - EF 0.20 I / In All
0320 Time delay for BF with 1-pole faults 0.20 sec All
0321 Time delay for BF with multi-pole faults 0.20 sec All
0322 Time delay for BF low current mode 0.20 sec All
0323A Time delay for BF pulse mode 0.20 sec All
0324 Time delay BF after CB fault 0.10 sec All
0325 Time delay for TRIP repeat 0.10 sec All
0326 Time delay for CB open 0.05 sec All
0327 Supervision bin. input BF-release 15.00 sec All
0328 Supervision time BF start / release 0.06 sec All

4.3.3 Group Bay Unit @03; Group End fault stage


Group Bay Unit @03; Group End fault stage
No. Settings Value Group

0329 End fault protection ON All

4.3.4 Group Bay Unit @03; Group Breaker


Group Bay Unit @03; Group Breaker
No. Settings Value Group

0313 Current threshold for TRIP release 0.05 I / In All

Page 11 of 15
B00_R00_F006_prn_16_42_04
Function blocks
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

4.4 Function blocks

4.4.1 Group Bay Unit @04; Group General


Group Bay Unit @04; Group General
No. Settings Value Group

0412 Bay status in service All


0406A Combi-Coupler NO All
0451A Maintenance for disconnector 1 YES All
0452A Maintenance for disconnector 2 YES All
0453A Maintenance for disconnector 3 YES All
0454A Maintenance for disconnector 4 YES All
0455A Maintenance for disconnector 5 YES All
0456A Maintenance for CB YES All

4.4.2 Group Bay Unit @04; Group Breaker Failure


Group Bay Unit @04; Group Breaker Failure
No. Settings Value Group

0414 Binary input mode / supervision BF Initiation and release with supervision All
0415 Operation mode BF TRIP repetition with current query All
0416 Low-current mode BF OFF All
0417 TRIP repeat mode 3pole All
0418 Current threshold for BF 0.25 I / In All
0419A Current threshold for BF - EF 0.20 I / In All
0420 Time delay for BF with 1-pole faults 0.20 sec All
0421 Time delay for BF with multi-pole faults 0.20 sec All
0422 Time delay for BF low current mode 0.20 sec All
0423A Time delay for BF pulse mode 0.20 sec All
0424 Time delay BF after CB fault 0.10 sec All
0425 Time delay for TRIP repeat 0.10 sec All
0426 Time delay for CB open 0.05 sec All
0427 Supervision bin. input BF-release 15.00 sec All
0428 Supervision time BF start / release 0.06 sec All

Page 12 of 15
B00_R00_F006_prn_16_42_04
Group Bay Unit @04; Group End fault stage
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

4.4.3 Group Bay Unit @04; Group End fault stage


Group Bay Unit @04; Group End fault stage
No. Settings Value Group

0429 End fault protection ON All

4.4.4 Group Bay Unit @04; Group Breaker


Group Bay Unit @04; Group Breaker
No. Settings Value Group

0413 Current threshold for TRIP release 0.05 I / In All

4.5 Function blocks

4.5.1 Group Bay Unit @05; Group General


Group Bay Unit @05; Group General
No. Settings Value Group

0512 Bay status in service All


0506A Combi-Coupler NO All
0551A Maintenance for disconnector 1 YES All
0552A Maintenance for disconnector 2 YES All
0553A Maintenance for disconnector 3 YES All
0554A Maintenance for disconnector 4 YES All
0555A Maintenance for disconnector 5 YES All
0556A Maintenance for CB YES All

4.5.2 Group Bay Unit @05; Group Breaker Failure


Group Bay Unit @05; Group Breaker Failure
No. Settings Value Group

0514 Binary input mode / supervision BF Initiation and release with supervision All
0515 Operation mode BF TRIP repetition with current query All
0516 Low-current mode BF OFF All
0517 TRIP repeat mode 3pole All
0518 Current threshold for BF 0.25 I / In All
0519A Current threshold for BF - EF 0.20 I / In All
0520 Time delay for BF with 1-pole faults 0.20 sec All

Page 13 of 15
B00_R00_F006_prn_16_42_04

AYOLAS / 500/220kV / 87B 500kV /


SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

Group Bay Unit @05; Group Breaker Failure(2)


No. Settings Value Group

0521 Time delay for BF with multi-pole faults 0.20 sec All
0522 Time delay for BF low current mode 0.20 sec All
0523A Time delay for BF pulse mode 0.20 sec All
0524 Time delay BF after CB fault 0.10 sec All
0525 Time delay for TRIP repeat 0.10 sec All
0526 Time delay for CB open 0.05 sec All
0527 Supervision bin. input BF-release 15.00 sec All
0528 Supervision time BF start / release 0.06 sec All

4.5.3 Group Bay Unit @05; Group End fault stage


Group Bay Unit @05; Group End fault stage
No. Settings Value Group

0529 End fault protection ON All

4.5.4 Group Bay Unit @05; Group Breaker


Group Bay Unit @05; Group Breaker
No. Settings Value Group

0513 Current threshold for TRIP release 0.00 I / In All

4.6 Function blocks

4.6.1 Group Bay Unit @06; Group General


Group Bay Unit @06; Group General
No. Settings Value Group

0612 Bay status in service All


0606A Combi-Coupler NO All
0651A Maintenance for disconnector 1 YES All
0652A Maintenance for disconnector 2 YES All
0653A Maintenance for disconnector 3 YES All
0654A Maintenance for disconnector 4 YES All
0655A Maintenance for disconnector 5 YES All
0656A Maintenance for CB YES All

Page 14 of 15
B00_R00_F006_prn_16_42_04

AYOLAS / 500/220kV / 87B 500kV /


SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06

4.6.2 Group Bay Unit @06; Group Breaker Failure


Group Bay Unit @06; Group Breaker Failure
No. Settings Value Group

0614 Binary input mode / supervision BF Initiation and release with supervision All
0615 Operation mode BF TRIP repetition with current query All
0616 Low-current mode BF OFF All
0617 TRIP repeat mode 3pole All
0618 Current threshold for BF 0.25 I / In All
0619A Current threshold for BF - EF 0.20 I / In All
0620 Time delay for BF with 1-pole faults 0.20 sec All
0621 Time delay for BF with multi-pole faults 0.20 sec All
0622 Time delay for BF low current mode 0.20 sec All
0623A Time delay for BF pulse mode 0.20 sec All
0624 Time delay BF after CB fault 0.10 sec All
0625 Time delay for TRIP repeat 0.10 sec All
0626 Time delay for CB open 0.05 sec All
0627 Supervision bin. input BF-release 15.00 sec All
0628 Supervision time BF start / release 0.06 sec All

4.6.3 Group Bay Unit @06; Group End fault stage


Group Bay Unit @06; Group End fault stage
No. Settings Value Group

0629 End fault protection ON All

4.6.4 Group Bay Unit @06; Group Breaker


Group Bay Unit @06; Group Breaker
No. Settings Value Group

0613 Current threshold for TRIP release 0.00 I / In All

Page 15 of 15
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

Settings
Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 10.200.4.34 (Port E)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Show all settings
Hide SIPROTEC extensions in IEC 61850 structure Show all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.

General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.115 Set. format residu. comp. All: Kr, Kx
91.138 Block monitoring dir. All: off

General \Chatter blocking


Number Settings Value
91.123 No. permis.state changes All: 0
91.127 Initial test time All: 1 s
91.124 No. of chatter tests All: 0
91.125 Chatter idle time All: 1 min
91.137 Subsequent test time All: 2 s

General \Measurements
Number Settings Value
91.162 Blk setting change All: false
91.111 Energy restore interval Settings group 1: 10 min
91.112 Energy restore time Settings group 1: none
91.120 Energy restore Settings group 1: latest value

General \Control
Number Settings Value
91.121 Energy restore by A.time All: false
91.118 Enable sw.auth. station All: false
91.119 Multiple sw.auth. levels All: false

General \Spontan.indic.
Number Settings Value
91.152 Specific sw. authorities All: false

1 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

General \CFC
Number Settings Value
91.139 Fault-display All: with pickup

General \Test support


Number Settings Value
91.161 CFC chart quality handling All: automatic
91.150 Activate device test mode All: false

Localization
Number Settings Value
6211.139 Unit system All: SI

Time settings
General
Settings Value
Date format All: DD.MM.YYYY

Time source
Settings Value
Fault indication after All: 600 s
Time source 1 Ch1:port E:SNTP
Time source 2 none
Time zone time source 1 All: UTC
Time zone time source 2 All: local
Sync. latency time src.1 All: 0.10 μs
Sync. latency time src.2 All: 0 μs

Time zone and daylight saving time


Settings Value
Time zone offset to UTC All: -240 min
Offset daylight sav. time All: 60 min
Switch daylight sav. time true
Start of daylight sav. time First Sunday in October at 12:00 AM
End of daylight sav. time Third Sunday in March at 12:00 AM

Power system \General


General
Number Settings Value
11.2311.101 Phase sequence All: ABC

2 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

Power system \Corriente Corte


CT 3-phase \General
Number Settings Value
11.931.8881.115 CT connection All: 3-phase + IN
11.931.8881.127 Tracking All: active
11.931.8881.130 Measuring-point ID All: 1

CT 3-phase \CT phases


Number Settings Value
11.931.8881.101 Rated primary current All: 1200 A
11.931.8881.102 Rated secondary current All: 1 A
11.931.8881.117 Current range All: 100 x IR
11.931.8881.118 Internal CT type All: CT protection
11.931.8881.116 Neutr.point in dir.of ref.obj All: yes
11.931.8881.114 Inverted phases All: none
11.931.8881.107 CT error changeover All: 1
11.931.8881.108 CT error A All: 5 %
11.931.8881.109 CT error B All: 15 %

CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A

CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B

CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C

CT 4
Number Settings Value
11.931.3844.103 Magnitude correction All: 1
11.931.3844.117 Phase All: IN

Brk.wire det.
Number Settings Value
11.931.5581.1 Mode Settings group 1: on
11.931.5581.101 Mode of blocking Settings group 1: not blocking
11.931.5581.102 Delta value for autoblock Settings group 1: 1

3 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 600 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 100 s

Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 100 s

Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: on
11.931.2431.102 Threshold Settings group 1: 120 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s

Supv.ADC sum I
Number Settings Value
11.931.2401.1 Mode Settings group 1: on

Power system \Tension


VT 3-phase
Number Settings Value
11.941.8911.101 Rated primary voltage All: 500.00 kV
11.941.8911.102 Rated secondary voltage All: 111 V
11.941.8911.103 Matching ratio Vph / VN All: 1.73
11.941.8911.104 VT connection All: 3 ph-to-gnd volt. + VN
11.941.8911.106 Inverted phases All: none
11.941.8911.111 Tracking All: active
11.941.8911.130 Measuring-point ID All: 3

VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A

VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B

VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1

4 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

Number Settings Value


11.941.3813.108 Phase All: V C

VT 4
Number Settings Value
11.941.3814.103 Magnitude correction All: 1
11.941.3814.108 Phase All: VN

Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: on
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s

Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: on
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s

Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s

VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s

Recording \Fault recorder


Control
Number Settings Value
51.791.2761.130 Fault recording All: with pickup
51.791.2761.131 Storage All: with trip
51.791.2761.111 Maximum record time All: 5 s
51.791.2761.112 Pre-trigger time All: 0.5 s
51.791.2761.113 Post-trigger time All: 0.5 s
51.791.2761.116 Manual record time All: 0.5 s
51.791.2761.140 Sampling frequency All: 2 kHz

Line 1 \General
General \Rated values
Number Settings Value
21.9001.101 Rated current All: 1200 A
21.9001.102 Rated voltage All: 500 kV

5 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

Number Settings Value


21.9001.103 Rated apparent power All: 1039.2 MVA

General \Line data


Number Settings Value
21.9001.149 Neutral point Settings group 1: grounded
21.9001.112 C1 per length unit Settings group 1: 0.014 μF/km
21.9001.148 C0 per length unit Settings group 1: 0.009 μF/km
21.9001.113 X per length unit Settings group 1: 0.2793 Ω/km
21.9001.114 Line length Settings group 1: 16 km
21.9001.108 Line angle Settings group 1: 86.8 °
21.9001.104 Kr Settings group 1: 1.41
21.9001.105 Kx Settings group 1: 0.36
21.9001.119 CT saturation detection All: yes
21.9001.120 CT saturation threshold Settings group 1: 12000 A
21.9001.111 Series compensation All: no

General \Measurements
Number Settings Value
21.9001.158 P, Q sign Settings group 1: not reversed

Line 1 \Process monitor


Closure detec.
Number Settings Value
21.1131.4681.101 Operating mode Settings group 1: Manual close only
21.1131.4681.102 Action time after closure Settings group 1: 0.05 s
21.1131.4681.103 Min. time feeder open Settings group 1: 0.25 s

1pol.open det.
Number Settings Value
21.1131.4711.101 Operating mode Settings group 1: with measurement

Volt.criterion
Number Settings Value
21.1131.4801.101 Threshold U open Settings group 1: 135.14 kV

Line 1 \50BF E0
Standard 1
Number Settings Value
21.971.3901.1 Mode Settings group 1: on
21.971.3901.101 Activation Settings group 1: always active
21.971.3901.3 Threshold Settings group 1: 300 A
21.971.3901.4 Dropout ratio Settings group 1: 0.9

6 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

Circuit breaker 1 \General


General \Ref. for %-values
Number Settings Value
301.2311.101 Rated normal current All: 1200 A

General \Breaker settings


Number Settings Value
301.2311.112 Current thresh. CB open All: 60 A
301.2311.113 1-pole operate allowed All: no

Circuit breaker 1 \Trip logic


Trip logic
Number Settings Value
301.5341.101 Trip at 2ph short circuit All: 3-pole
301.5341.102 3-pole coupling All: with trip
301.5341.103 Reset of trip command All: with dropout

Circuit breaker 1 \Circuit break.


Circuit break.
Number Settings Value
301.4261.101 Output time All: 0.1 s

Circuit breaker 1 \Manual close


Manual close
Number Settings Value
301.6541.101 Action time Settings group 1: 0.3 s

Circuit breaker 1 \Control


Control
Number Settings Value
301.4201.101 Control model All: SBO w. enh. security
301.4201.102 SBO time-out All: 30 s
301.4201.103 Feedback monitoring time All: 1 s
301.4201.104 Check switching authority All: yes
301.4201.105 Check if pos. is reached All: yes
301.4201.106 Check double activat. blk. All: yes
301.4201.107 Check blk. by protection All: yes

Circuit breaker 1 \CB test


CB test
Number Settings Value
301.6151.101 Dead time All: 0.1 s

7 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal

Circuit breaker 1 \50BF CB fail.1


50BF CB fail.1
Number Settings Value
301.4381.1 Mode Settings group 1: on
301.4381.105 Holding int. start signal Settings group 1: yes
301.4381.107 Start via binary input All: 2 channel
301.4381.106 Holding ext. start signal Settings group 1: no
301.4381.108 Sup.time for release signl Settings group 1: 0.06 s
301.4381.103 CB aux.cont. crit. allowed Settings group 1: no
301.4381.104 Dropout Settings group 1: with effective criterion
301.4381.110 Retrip after T1 All: parallel start T2, T1
301.4381.102 Threshold phase current Settings group 1: 300 A
301.4381.101 Threshold sensitive Settings group 1: 240 A
301.4381.111 Delay T1 for 3-pole retrip Settings group 1: 0.1 s
301.4381.112 Delay T2 for 3-pole trip Settings group 1: 0.2 s
301.4381.115 Minimum operate time Settings group 1: 0.1 s
301.4381.120 3I0 criterion All: Plausibility check
301.4381.121 I2 criterion All: Plausibility check
301.4381.122 Threshold 3I0 dir. release Settings group 1: 250 A
301.4381.123 Threshold I2 dir. release Settings group 1: 250 A
301.4381.124 Monit. time for BI ">Start" Settings group 1: 15 s
301.4381.125 Monit.tm. f.BI ">Release" Settings group 1: 15 s