Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 172.16.60.60 (Integrated Ethernet interface)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Hide all settings
Hide SIPROTEC extensions in IEC 61850 structure Hide all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.
General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.115 Set. format residu. comp. All: Kr, Kx
91.138 Block monitoring dir. All: off
General \Measurements
Number Settings Value
91.162 Blk setting change All: false
91.163 Reserv.time for com.prot. All: 120 s
91.111 Energy restore interval Settings group 1: 10 min
91.112 Energy restore time Settings group 1: none
General \Control
Number Settings Value
91.120 Energy restore Settings group 1: latest value
91.121 Energy restore by A.time All: false
91.118 Enable sw.auth. station All: false
1 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
General \Spontan.indic.
Number Settings Value
91.119 Multiple sw.auth. levels All: false
General \CFC
Number Settings Value
91.152 Specific sw. authorities All: false
Localization
Number Settings Value
6211.139 Unit system All: SI
Time settings
General
Settings Value
Date format All: DD.MM.YYYY
Time source
Settings Value
Fault indication after All: 600 s
Time source 1 none
Time source 2 none
Time zone time source 1 All: local
Time zone time source 2 All: local
Sync. latency time src.1 All: 0 μs
Sync. latency time src.2 All: 0 μs
2 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A
VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B
VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
11.941.3813.108 Phase All: V C
Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: on
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s
Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: on
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s
3 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s
VT 1
Number Settings Value
11.961.3811.103 Magnitude correction All: 1
11.961.3811.108 Phase All: V B
VT miniatureCB
Number Settings Value
11.961.2641.101 Response time Settings group 1: 0 s
CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A
4 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B
CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C
CT 4
Number Settings Value
11.931.3844.103 Magnitude correction All: 1
11.931.3844.117 Phase All: IN
Brk.wire det.
Number Settings Value
11.931.5581.1 Mode Settings group 1: off
11.931.5581.101 Mode of blocking Settings group 1: blocking
11.931.5581.102 Delta value for autoblock Settings group 1: 1
Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 1000 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 5 s
Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: on
11.931.2431.102 Threshold Settings group 1: 200 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s
Supv.ADC sum I
Number Settings Value
11.931.2401.1 Mode Settings group 1: on
5 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Saturat. det.
Number Settings Value
11.931.17731.101 CT saturation threshold Settings group 1: 16000 A
Line 1 \General
General \Rated values
Number Settings Value
21.9001.101 Rated current All: 1923 A
21.9001.102 Rated voltage All: 500 kV
21.9001.103 Rated apparent power All: 1665.4 MVA
General \Measurements
Number Settings Value
21.9001.158 P, Q sign Settings group 1: not reversed
6 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
1pol.open det.
Number Settings Value
21.1131.4711.101 Operating mode Settings group 1: with measurement
Volt.criterion
Number Settings Value
21.1131.4801.101 Threshold U open Settings group 1: 120.00 kV
Line 1 \Mes.v.fail.det
Mes.v.fail.det
Number Settings Value
21.2671.1 Mode Settings group 1: on
21.2671.115 Asym.fail.-DO on netw.flt. Settings group 1: no
21.2671.113 Asym.fail. - time delay Settings group 1: 10 s
21.2671.102 3ph.fail. - phs.curr.release Settings group 1: 100 A
21.2671.103 3ph.fail. - phs.curr. jump Settings group 1: 100 A
21.2671.101 3ph.fail. - VA,VB,VC < Settings group 1: 20 kV
21.2671.107 Switch-on 3ph. failure All: on
21.2671.106 SO 3ph.fail. - time delay Settings group 1: 3 s
Line 1 \85-21Perm.overr.
85-21Perm.over
Number Settings Value
21.1291.5701.1 Mode Settings group 1: on
7 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
8 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Stage 1 \Configuration
Number Settings Value
21.1341.5941.102 50/51 OC-3ph 1p 1.Definite-T 1 false
21.1341.5941.102 50N/51N OC-gnd-A1.Definite-T 1 false
21.1341.5941.102 50 high-speed 1pol 1.Standard 1 true
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 1 false
21.1341.5941.102 67N GFP gnd.sys.1.Definite-T 2 false
21.1341.5941.102 67N GFP gnd.sys.1.Inverse-T 1 true
21.1341.5941.102 21 Distance prot. 1.Z 1 false
21.1341.5941.102 21 Distance prot. 1.Z 2 false
21.1341.5941.102 21 Distance prot. 1.Z 3 false
21.1341.5941.102 21 Distance prot. 1.Z 4 false
21.1341.5941.102 21 Distance prot. 1.Z 1B true
Definite-T 1 \General
Number Settings Value
21.221.841.1 Mode Settings group 1: on
21.221.841.2 Operate & flt.rec. blocked Settings group 1: no
21.221.841.11 1-pole operate allowed Settings group 1: no
21.221.841.26 Dynamic settings All: no
21.221.841.8 Method of measurement Settings group 1: fundamental comp.
21.221.841.3 Threshold Settings group 1: 2400 A
21.221.841.4 Dropout ratio Settings group 1: 0.95
21.221.841.102 Pickup delay Settings group 1: 0 s
21.221.841.101 Dropout delay Settings group 1: 0 s
21.221.841.6 Operate delay Settings group 1: 60 s
9 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Definite-T 1 \General
Number Settings Value
21.211.751.1 Mode Settings group 1: off
21.211.751.2 Operate & flt.rec. blocked Settings group 1: no
21.211.751.26 Dynamic settings All: no
21.211.751.8 Method of measurement Settings group 1: fundamental comp.
21.211.751.3 Threshold Settings group 1: 1200 A
21.211.751.4 Dropout ratio Settings group 1: 0.95
21.211.751.101 Dropout delay Settings group 1: 0 s
21.211.751.6 Operate delay Settings group 1: 0.3 s
Definite-T 1 \General
Number Settings Value
21.1111.4861.1 Mode Settings group 1: on
21.1111.4861.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4861.114 Directional mode Settings group 1: forward
21.1111.4861.11 1-pole operate allowed Settings group 1: no
21.1111.4861.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4861.130 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4861.129 Op.mode at 1p dead time Settings group 1: blocked
10 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Definite-T 1 \Blocking by
Number Settings Value
21.1111.4861.140 87 Line diff. prot..Group indicat. true
21.1111.4861.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4861.140 21 Distance prot. 1.Z 1 false
21.1111.4861.140 21 Distance prot. 1.Z 2 false
21.1111.4861.140 21 Distance prot. 1.Z 3 false
21.1111.4861.140 21 Distance prot. 1.Z 4 false
21.1111.4861.140 21 Distance prot. 1.Z 1B false
Definite-T 2 \General
Number Settings Value
21.1111.4862.1 Mode Settings group 1: off
21.1111.4862.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4862.114 Directional mode Settings group 1: non-directional
21.1111.4862.11 1-pole operate allowed Settings group 1: no
21.1111.4862.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4862.129 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4862.112 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4862.115 Dynamic settings All: no
21.1111.4862.111 Stabiliz. w. phase current Settings group 1: 10 %
21.1111.4862.3 Threshold Settings group 1: 3638 A
21.1111.4862.6 Operate delay Settings group 1: 0.25 s
Definite-T 2 \Blocking by
Number Settings Value
21.1111.4862.140 87 Line diff. prot..Group indicat. false
21.1111.4862.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4862.140 21 Distance prot. 1.Z 1 false
21.1111.4862.140 21 Distance prot. 1.Z 2 false
21.1111.4862.140 21 Distance prot. 1.Z 3 false
21.1111.4862.140 21 Distance prot. 1.Z 4 false
21.1111.4862.140 21 Distance prot. 1.Z 1B false
Inverse-T 1 \General
Number Settings Value
21.1111.4891.1 Mode Settings group 1: on
21.1111.4891.2 Operate & flt.rec. blocked Settings group 1: no
21.1111.4891.115 Directional mode Settings group 1: forward
21.1111.4891.11 1-pole operate allowed Settings group 1: no
21.1111.4891.8 Method of measurement Settings group 1: 1-cycle filter
21.1111.4891.131 Blocking by prot. pickup Settings group 1: every pickup
21.1111.4891.130 Op.mode at 1p dead time Settings group 1: blocked
21.1111.4891.113 Hold mode 1p dead time Settings group 1: 0.04 s
21.1111.4891.116 Dynamic settings All: no
11 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Inverse-T 1 \Blocking by
Number Settings Value
21.1111.4891.140 87 Line diff. prot..Group indicat. true
21.1111.4891.140 87 Stub diff. prot. 1.Group indicat. false
21.1111.4891.140 21 Distance prot. 1.Z 1 false
21.1111.4891.140 21 Distance prot. 1.Z 2 false
21.1111.4891.140 21 Distance prot. 1.Z 3 false
21.1111.4891.140 21 Distance prot. 1.Z 4 false
21.1111.4891.140 21 Distance prot. 1.Z 1B false
Definite-T 2
Number Settings Value
21.51.182.1 Mode Settings group 1: on
21.51.182.2 Operate & flt.rec. blocked Settings group 1: no
21.51.182.9 Measured value Settings group 1: phase-to-phase
21.51.182.8 Method of measurement Settings group 1: fundamental comp.
21.51.182.101 Pickup mode Settings group 1: 1 out of 3
21.51.182.3 Threshold Settings group 1: 600 kV
21.51.182.4 Dropout ratio Settings group 1: 0.95
21.51.182.6 Operate delay Settings group 1: 1 s
12 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Pickup Z<
Number Settings Value
21.901.3661.101 Min. phase-current thresh Settings group 1: 200 A
21.901.3661.102 Use ph-g load cutout All: no
21.901.3661.105 Use ph-ph load cutout All: no
Z1
Number Settings Value
21.901.3571.1 Mode Settings group 1: on
21.901.3571.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3571.121 Blocked if diff.prot.active Settings group 1: yes
21.901.3571.11 1-pole operate allowed Settings group 1: yes
21.901.3571.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3571.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3571.109 Directional mode Settings group 1: forward
21.901.3571.102 X reach Settings group 1: 75.57 Ω
21.901.3571.103 R (ph-g) Settings group 1: 42 Ω
21.901.3571.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3571.113 Zone-inclination angle Settings group 1: 0 °
21.901.3571.110 Operate delay (1-phase) Settings group 1: 0 s
21.901.3571.112 Operate delay (multi-ph.) Settings group 1: 0 s
Z2
Number Settings Value
21.901.3572.1 Mode Settings group 1: on
21.901.3572.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3572.121 Blocked if diff.prot.active Settings group 1: no
21.901.3572.11 1-pole operate allowed Settings group 1: no
21.901.3572.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3572.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3572.109 Directional mode Settings group 1: forward
21.901.3572.102 X reach Settings group 1: 106.69 Ω
21.901.3572.103 R (ph-g) Settings group 1: 42 Ω
21.901.3572.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3572.113 Zone-inclination angle Settings group 1: 0 °
21.901.3572.110 Operate delay (1-phase) Settings group 1: 0.3 s
21.901.3572.112 Operate delay (multi-ph.) Settings group 1: 0.3 s
Z3
Number Settings Value
21.901.3573.1 Mode Settings group 1: on
21.901.3573.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3573.121 Blocked if diff.prot.active Settings group 1: no
21.901.3573.11 1-pole operate allowed Settings group 1: no
21.901.3573.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3573.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3573.109 Directional mode Settings group 1: forward
21.901.3573.102 X reach Settings group 1: 209.17 Ω
21.901.3573.103 R (ph-g) Settings group 1: 42 Ω
21.901.3573.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3573.113 Zone-inclination angle Settings group 1: 0 °
21.901.3573.110 Operate delay (1-phase) Settings group 1: 1.3 s
13 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Z4
Number Settings Value
21.901.3574.1 Mode Settings group 1: on
21.901.3574.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3574.121 Blocked if diff.prot.active Settings group 1: no
21.901.3574.11 1-pole operate allowed Settings group 1: no
21.901.3574.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3574.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3574.109 Directional mode Settings group 1: reverse
21.901.3574.102 X reach Settings group 1: 21.34 Ω
21.901.3574.103 R (ph-g) Settings group 1: 42 Ω
21.901.3574.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3574.113 Zone-inclination angle Settings group 1: 0 °
21.901.3574.110 Operate delay (1-phase) Settings group 1: 1.8 s
21.901.3574.112 Operate delay (multi-ph.) Settings group 1: 1.8 s
Z 1B
Number Settings Value
21.901.3575.1 Mode Settings group 1: on
21.901.3575.2 Operate & flt.rec. blocked Settings group 1: no
21.901.3575.121 Blocked if diff.prot.active Settings group 1: no
21.901.3575.11 1-pole operate allowed Settings group 1: yes
21.901.3575.101 Function mode Settings group 1: ph-gnd and ph-ph
21.901.3575.114 Zone-spec. residu. comp. Settings group 1: no
21.901.3575.109 Directional mode Settings group 1: forward
21.901.3575.102 X reach Settings group 1: 106.69 Ω
21.901.3575.103 R (ph-g) Settings group 1: 42 Ω
21.901.3575.104 R (ph-ph) Settings group 1: 42 Ω
21.901.3575.113 Zone-inclination angle Settings group 1: 0 °
21.901.3575.110 Operate delay (1-phase) Settings group 1: oo s
21.901.3575.112 Operate delay (multi-ph.) Settings group 1: oo s
14 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
I-DIFF
Number Settings Value
21.831.3451.1 Mode Settings group 1: on
21.831.3451.2 Operate & flt.rec. blocked Settings group 1: no
21.831.3451.3 Threshold Settings group 1: 416 A
21.831.3451.101 Thresh. switch onto fault Settings group 1: 416 A
21.831.3451.6 Operate delay Settings group 1: 0 s
I-DIFF fast 2
Number Settings Value
21.831.18211.1 Mode Settings group 1: on
21.831.18211.2 Operate & flt.rec. blocked Settings group 1: no
21.831.18211.3 Threshold Settings group 1: 2000 A
21.831.18211.101 Thresh. switch onto fault Settings group 1: 2000 A
Ic-compensat.
Number Settings Value
21.831.3511.1 Mode Settings group 1: on
21.831.3511.101 Ic-stabilization/Ic-rated Settings group 1: 1.5
21.831.3511.102 Total line length Settings group 1: 333 km
21.831.3511.110 Rated charging current Settings group 1: 415 A
S-DIFF
Number Settings Value
21.1431.8401.1 Mode Settings group 1: on
21.1431.8401.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.8401.3 Threshold Settings group 1: 400 A
21.1431.8401.6 Operate delay Settings group 1: 0 s
S-DIFF fast 2
Number Settings Value
21.1431.18241.1 Mode Settings group 1: on
21.1431.18241.2 Operate & flt.rec. blocked Settings group 1: no
21.1431.18241.3 Threshold Settings group 1: 2000 A
15 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
16 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Cycle 1
Number Settings Value
301.1361.6571.102 Start from idle state allow. Settings group 1: yes
17 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Synchrocheck 1 \General
Number Settings Value
301.1151.5071.1 Mode Settings group 1: off
301.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
301.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
301.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
301.1151.5071.108 Direct close command Settings group 1: no
301.1151.5071.126 Voltage adjustment Settings group 1: 1
Sychr./Asycr.1 \General
Number Settings Value
301.1151.5041.1 Mode Settings group 1: on
301.1151.5041.101 Min. operating limit Vmin Settings group 1: 450 kV
301.1151.5041.102 Max. operat. limit Vmax Settings group 1: 550 kV
18 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
19 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
20 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Cycle 1
Number Settings Value
302.1361.6571.102 Start from idle state allow. Settings group 1: yes
302.1361.6571.103 Action time Settings group 1: 0.2 s
302.1361.6571.108 Dead time aft. 3-pole trip Settings group 1: 0.5 s
302.1361.6571.107 Dead time aft. 1-pole trip Settings group 1: 1.2 s
302.1361.6571.109 Dead time aft. evolv. fault Settings group 1: 1.2 s
302.1361.6571.111 CB ready check bef.close Settings group 1: no
302.1361.6571.110 Synchroch. aft. 3-pole d.t. Settings group 1: none
Synchrocheck 1 \General
Number Settings Value
302.1151.5071.1 Mode Settings group 1: on
302.1151.5071.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5071.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5071.108 Direct close command Settings group 1: no
302.1151.5071.126 Voltage adjustment Settings group 1: 1
21 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Sychr./Asycr.1 \General
Number Settings Value
302.1151.5041.1 Mode Settings group 1: off
302.1151.5041.101 Min. operating limit Vmin Settings group 1: 360 kV
302.1151.5041.102 Max. operat. limit Vmax Settings group 1: 440 kV
302.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
302.1151.5041.108 Direct close command Settings group 1: no
302.1151.5041.126 Voltage adjustment Settings group 1: 1
Disconnector 1 \Control
Control
Number Settings Value
601.4201.101 Control model All: SBO w. enh. security
22 of 23
Totally Integrated 7SL87 - LINEA A VILLA HAYES
Automation Portal
Disconnector 1 \Disconnector
Disconnector
Number Settings Value
601.5401.101 Maximum output time All: 10 s
601.5401.102 Seal-in time All: 0 s
601.5401.103 Switching-device type All: disconnector
23 of 23
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
Settings
Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 192.168.60.60 (Integrated Ethernet interface)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Show all settings
Hide SIPROTEC extensions in IEC 61850 structure Show all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.
General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.138 Block monitoring dir. All: off
General \Control
Number Settings Value
91.162 Blk setting change All: false
91.118 Enable sw.auth. station All: false
91.119 Multiple sw.auth. levels All: false
General \Spontan.indic.
Number Settings Value
91.152 Specific sw. authorities All: false
General \CFC
Number Settings Value
91.139 Fault-display All: with pickup
1 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
Localization
Number Settings Value
6211.139 Unit system All: SI
Time settings
General
Settings Value
Date format All: DD.MM.YYYY
Time source
Settings Value
Fault indication after All: 600 s
Time source 1 Ch1:port E:SNTP
Time source 2 none
Time zone time source 1 All: UTC
Time zone time source 2 All: local
Sync. latency time src.1 All: 0.1 μs
Sync. latency time src.2 All: 0 μs
2 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A
CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B
CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C
Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 50 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 5 s
Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: off
11.931.2431.102 Threshold Settings group 1: 10 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s
3 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
CT 1
Number Settings Value
11.932.3841.103 Magnitude correction All: 1
11.932.3841.117 Phase All: I A
CT 2
Number Settings Value
11.932.3842.103 Magnitude correction All: 1
11.932.3842.117 Phase All: I B
CT 3
Number Settings Value
11.932.3843.103 Magnitude correction All: 1
11.932.3843.117 Phase All: I C
Supv. balan. I
Number Settings Value
11.932.2491.1 Mode Settings group 1: on
11.932.2491.101 Release threshold Settings group 1: 50 A
11.932.2491.102 Threshold min/max Settings group 1: 0.5
11.932.2491.6 Delay supervision alarm Settings group 1: 5 s
Supv. ph.seq.I
Number Settings Value
11.932.2551.1 Mode Settings group 1: on
11.932.2551.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum I
Number Settings Value
11.932.2431.1 Mode Settings group 1: off
11.932.2431.102 Threshold Settings group 1: 10 A
11.932.2431.101 Slope factor Settings group 1: 0.1
11.932.2431.6 Delay supervision alarm Settings group 1: 5 s
4 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
CT 1
Number Settings Value
11.951.3841.103 Magnitude correction All: 1
11.951.3841.117 Phase All: Ix
VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A
VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B
VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
11.941.3813.108 Phase All: V C
Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: off
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s
5 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: off
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s
VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s
VT 1
Number Settings Value
11.961.3811.103 Magnitude correction All: 1
11.961.3811.108 Phase All: V B
VT miniatureCB
Number Settings Value
11.961.2641.101 Response time Settings group 1: 0 s
6 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
General \Measurements
Number Settings Value
911.91.158 P, Q sign Settings group 1: not reversed
7 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
Inverse-T 1
Number Settings Value
911.1941.691.1 Mode Settings group 1: on
911.1941.691.2 Operate & flt.rec. blocked Settings group 1: no
911.1941.691.27 Blk. w. inrush curr. detect. Settings group 1: yes
911.1941.691.8 Method of measurement Settings group 1: fundamental comp.
911.1941.691.3 Threshold Settings group 1: 111 A
911.1941.691.130 Type of character. curve Settings group 1: IEC normal inverse
911.1941.691.131 Reset Settings group 1: instantaneous
911.1941.691.101 Time dial Settings group 1: 0.14
Inverse-T 1
Number Settings Value
911.1731.781.1 Mode Settings group 1: on
911.1731.781.2 Operate & flt.rec. blocked Settings group 1: no
911.1731.781.27 Blk. w. inrush curr. detect. Settings group 1: yes
911.1731.781.8 Method of measurement Settings group 1: fundamental comp.
911.1731.781.3 Threshold Settings group 1: 20 A
911.1731.781.108 Type of character. curve Settings group 1: IEC normal inverse
911.1731.781.109 Reset Settings group 1: instantaneous
911.1731.781.101 Time dial Settings group 1: 0.29
8 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
9 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
I-DIFF \General
Number Settings Value
901.1691.11041.1 Mode Settings group 1: on
901.1691.11041.2 Operate & flt.rec. blocked Settings group 1: no
901.1691.11041.6 Operate delay Settings group 1: 0 s
10 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
I-DIFF fast
Number Settings Value
901.1691.11071.1 Mode Settings group 1: on
901.1691.11071.3 Threshold Settings group 1: 2 I/IrObj
901.1691.11071.6 Operate delay Settings group 1: 0 s
901.1691.11071.100 Operate & flt.rec. blocked Settings group 1: no
Definite-T 2
Number Settings Value
921.211.12662.1 Mode Settings group 1: on
921.211.12662.2 Operate & flt.rec. blocked Settings group 1: no
921.211.12662.27 Blk. w. inrush curr. detect. Settings group 1: no
921.211.12662.8 Method of measurement Settings group 1: fundamental comp.
921.211.12662.3 Threshold Settings group 1: 25 A
921.211.12662.6 Operate delay Settings group 1: 2 s
11 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
12 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
Synchrocheck 1 \General
Number Settings Value
201.1151.5071.1 Mode Settings group 1: off
201.1151.5071.101 Min. operating limit Vmin Settings group 1: 391.30 kV
201.1151.5071.102 Max. operat. limit Vmax Settings group 1: 478.26 kV
201.1151.5071.110 Max.durat. sync.process Settings group 1: 30 s
201.1151.5071.108 Direct close command Settings group 1: no
201.1151.5071.126 Voltage adjustment Settings group 1: 1
13 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
Sychr./Asycr.1 \General
Number Settings Value
201.1151.5041.1 Mode Settings group 1: off
201.1151.5041.101 Min. operating limit Vmin Settings group 1: 391.30 kV
201.1151.5041.102 Max. operat. limit Vmax Settings group 1: 478.26 kV
201.1151.5041.110 Max.durat. sync.process Settings group 1: 30 s
201.1151.5041.108 Direct close command Settings group 1: no
201.1151.5041.126 Voltage adjustment Settings group 1: 1
14 of 15
Totally Integrated 7UT85 - REACTOR DE LÍNEA AYOLAS
Automation Portal
MT in 2
Number Settings Value
826.1832.5492.101 Meas. transduc. I/O type All: Current input
826.1832.5492.103 Unit All: m
826.1832.5492.108 Resolution All: 0.1
826.1832.5492.107 Range active All: false
826.1832.5492.104 Conversion factor All: 100
MT in 3
Number Settings Value
826.1832.5493.101 Meas. transduc. I/O type All: Current input
826.1832.5493.103 Unit All: m
826.1832.5493.108 Resolution All: 0.1
826.1832.5493.107 Range active All: false
826.1832.5493.104 Conversion factor All: 100
MT in 4
Number Settings Value
826.1832.5494.101 Meas. transduc. I/O type All: Current input
826.1832.5494.103 Unit All: m
826.1832.5494.108 Resolution All: 0.1
826.1832.5494.107 Range active All: false
826.1832.5494.104 Conversion factor All: 100
15 of 15
B00_R00_F006_prn_16_42_04
MLFB: 7SS5220**B921!A0
Parameter-set version: V04.72.01
Device path: C:\PRESEL\AYOLAS DIGSI 4 V4.88
\AYOLAS ECP 87B 500KV\P7DI\GV\SD\00000009
Author: A. Cangrejo
Creation date: 02.05.13 09:26:28
Last modified: 28.04.18 15:05:06
Operating mode: Offline
Comment:
Setting values in: Secondary value description
PRINT - CONTENTS
1 Substation Data ....................................................................................................................................................… 3
1.1 Group Power System Data 1; Group Power System ...........................................................................................… 3
2 Settings groups ....................................................................................................................................................… 4
2.1 Group Protection general; Group Power System ..................................................................................................... 4
2.2 Group Bus Bar Protection; Group Bus Zone ............................................................................................................ 4
2.3 Group Bus Bar Protection; Group Check Zone ........................................................................................................ 4
2.4 Group Breaker Failure Protection; Group Breaker Failure ....................................................................................... 4
2.5 Group Monitoring; Group General ........................................................................................................................… 5
2.6 Group Monitoring; Group Idiff Superv ..................................................................................................................… 5
2.7 Group Monitoring; Group 0-Cross Superv ............................................................................................................… 5
2.8 Group Monitoring; Group CB/DCO Superv ..........................................................................................................… 5
2.9 Group Monitoring; Group CB Test ........................................................................................................................… 6
3 Bay unit allocation ................................................................................................................................................… 7
3.1 Bay unit allocation ................................................................................................................................................… 7
4 Bay units ...............................................................................................................................................................… 8
4.1 Function blocks ....................................................................................................................................................… 8
4.1.1 Group Bay Unit @01; Group General ..................................................................................................................… 8
4.1.2 Group Bay Unit @01; Group Breaker Failure .......................................................................................................… 8
4.1.3 Group Bay Unit @01; Group End fault stage .......................................................................................................… 9
4.1.4 Group Bay Unit @01; Group Breaker ...................................................................................................................… 9
4.2 Function blocks ....................................................................................................................................................… 9
4.2.1 Group Bay Unit @02; Group General ..................................................................................................................… 9
4.2.2 Group Bay Unit @02; Group Breaker Failure .......................................................................................................… 9
4.2.3 Group Bay Unit @02; Group End fault stage .....................................................................................................… 10
4.2.4 Group Bay Unit @02; Group Breaker .................................................................................................................… 10
4.3 Function blocks ..................................................................................................................................................… 10
4.3.1 Group Bay Unit @03; Group General ................................................................................................................… 10
4.3.2 Group Bay Unit @03; Group Breaker Failure .....................................................................................................… 11
4.3.3 Group Bay Unit @03; Group End fault stage .....................................................................................................… 11
4.3.4 Group Bay Unit @03; Group Breaker .................................................................................................................… 11
4.4 Function blocks ..................................................................................................................................................… 12
4.4.1 Group Bay Unit @04; Group General ................................................................................................................… 12
4.4.2 Group Bay Unit @04; Group Breaker Failure .....................................................................................................… 12
4.4.3 Group Bay Unit @04; Group End fault stage .....................................................................................................… 13
4.4.4 Group Bay Unit @04; Group Breaker .................................................................................................................… 13
4.5 Function blocks ..................................................................................................................................................… 13
4.5.1 Group Bay Unit @05; Group General ................................................................................................................… 13
Page 1 of 15
B00_R00_F006_prn_16_42_04
Page 2 of 15
B00_R00_F006_prn_16_42_04
Substation Data
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
1 Substation Data
Page 3 of 15
B00_R00_F006_prn_16_42_04
Settings groups
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
2 Settings groups
Page 4 of 15
B00_R00_F006_prn_16_42_04
Page 5 of 15
B00_R00_F006_prn_16_42_04
Group Monitoring; Group CB Test
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
Page 6 of 15
B00_R00_F006_prn_16_42_04
Bay unit allocation
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
1 BU@ 1 B01_R11_F016
2 BU@ 2 B02_R12_F016
3 BU@ 3 B01_R21_F016
4 BU@ 4 B02_R22_F016
5 BU@ 5 B03_R13_F016
6 BU@ 6 B03_R23_F016
Page 7 of 15
B00_R00_F006_prn_16_42_04
Bay units
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
4 Bay units
0114 Binary input mode / supervision BF Initiation and release with supervision All
0115 Operation mode BF TRIP repetition with current query All
0116 Low-current mode BF OFF All
0117 TRIP repeat mode 3pole All
0118 Current threshold for BF 0.25 I / In All
0119A Current threshold for BF - EF 0.20 I / In All
0120 Time delay for BF with 1-pole faults 0.13 sec All
0121 Time delay for BF with multi-pole faults 0.20 sec All
0122 Time delay for BF low current mode 0.20 sec All
0123A Time delay for BF pulse mode 0.20 sec All
0124 Time delay BF after CB fault 0.10 sec All
0125 Time delay for TRIP repeat 0.10 sec All
0126 Time delay for CB open 0.05 sec All
0127 Supervision bin. input BF-release 15.00 sec All
0128 Supervision time BF start / release 0.06 sec All
Page 8 of 15
B00_R00_F006_prn_16_42_04
Group Bay Unit @01; Group End fault stage
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
0214 Binary input mode / supervision BF Initiation and release with supervision All
0215 Operation mode BF TRIP repetition with current query All
0216 Low-current mode BF OFF All
0217 TRIP repeat mode 3pole All
0218 Current threshold for BF 0.25 I / In All
0219A Current threshold for BF - EF 0.20 I / In All
0220 Time delay for BF with 1-pole faults 0.20 sec All
Page 9 of 15
B00_R00_F006_prn_16_42_04
0221 Time delay for BF with multi-pole faults 0.20 sec All
0222 Time delay for BF low current mode 0.20 sec All
0223A Time delay for BF pulse mode 0.20 sec All
0224 Time delay BF after CB fault 0.10 sec All
0225 Time delay for TRIP repeat 0.10 sec All
0226 Time delay for CB open 0.05 sec All
0227 Supervision bin. input BF-release 15.00 sec All
0228 Supervision time BF start / release 0.06 sec All
Page 10 of 15
B00_R00_F006_prn_16_42_04
0314 Binary input mode / supervision BF Initiation and release with supervision All
0315 Operation mode BF TRIP repetition with current query All
0316 Low-current mode BF OFF All
0317 TRIP repeat mode 3pole All
0318 Current threshold for BF 0.25 I / In All
0319A Current threshold for BF - EF 0.20 I / In All
0320 Time delay for BF with 1-pole faults 0.20 sec All
0321 Time delay for BF with multi-pole faults 0.20 sec All
0322 Time delay for BF low current mode 0.20 sec All
0323A Time delay for BF pulse mode 0.20 sec All
0324 Time delay BF after CB fault 0.10 sec All
0325 Time delay for TRIP repeat 0.10 sec All
0326 Time delay for CB open 0.05 sec All
0327 Supervision bin. input BF-release 15.00 sec All
0328 Supervision time BF start / release 0.06 sec All
Page 11 of 15
B00_R00_F006_prn_16_42_04
Function blocks
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
0414 Binary input mode / supervision BF Initiation and release with supervision All
0415 Operation mode BF TRIP repetition with current query All
0416 Low-current mode BF OFF All
0417 TRIP repeat mode 3pole All
0418 Current threshold for BF 0.25 I / In All
0419A Current threshold for BF - EF 0.20 I / In All
0420 Time delay for BF with 1-pole faults 0.20 sec All
0421 Time delay for BF with multi-pole faults 0.20 sec All
0422 Time delay for BF low current mode 0.20 sec All
0423A Time delay for BF pulse mode 0.20 sec All
0424 Time delay BF after CB fault 0.10 sec All
0425 Time delay for TRIP repeat 0.10 sec All
0426 Time delay for CB open 0.05 sec All
0427 Supervision bin. input BF-release 15.00 sec All
0428 Supervision time BF start / release 0.06 sec All
Page 12 of 15
B00_R00_F006_prn_16_42_04
Group Bay Unit @04; Group End fault stage
AYOLAS / 500/220kV / 87B 500kV /
SIMATIC B00_R00_F006/7SS522 28.04.18 16:42:06
0514 Binary input mode / supervision BF Initiation and release with supervision All
0515 Operation mode BF TRIP repetition with current query All
0516 Low-current mode BF OFF All
0517 TRIP repeat mode 3pole All
0518 Current threshold for BF 0.25 I / In All
0519A Current threshold for BF - EF 0.20 I / In All
0520 Time delay for BF with 1-pole faults 0.20 sec All
Page 13 of 15
B00_R00_F006_prn_16_42_04
0521 Time delay for BF with multi-pole faults 0.20 sec All
0522 Time delay for BF low current mode 0.20 sec All
0523A Time delay for BF pulse mode 0.20 sec All
0524 Time delay BF after CB fault 0.10 sec All
0525 Time delay for TRIP repeat 0.10 sec All
0526 Time delay for CB open 0.05 sec All
0527 Supervision bin. input BF-release 15.00 sec All
0528 Supervision time BF start / release 0.06 sec All
Page 14 of 15
B00_R00_F006_prn_16_42_04
0614 Binary input mode / supervision BF Initiation and release with supervision All
0615 Operation mode BF TRIP repetition with current query All
0616 Low-current mode BF OFF All
0617 TRIP repeat mode 3pole All
0618 Current threshold for BF 0.25 I / In All
0619A Current threshold for BF - EF 0.20 I / In All
0620 Time delay for BF with 1-pole faults 0.20 sec All
0621 Time delay for BF with multi-pole faults 0.20 sec All
0622 Time delay for BF low current mode 0.20 sec All
0623A Time delay for BF pulse mode 0.20 sec All
0624 Time delay BF after CB fault 0.10 sec All
0625 Time delay for TRIP repeat 0.10 sec All
0626 Time delay for CB open 0.05 sec All
0627 Supervision bin. input BF-release 15.00 sec All
0628 Supervision time BF start / release 0.06 sec All
Page 15 of 15
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
Settings
Device settings
Settings Value
Edit mode primary
Number settings groups 1
Activat. of settings group settings group 1
DIGSI 5 uses following IP address 10.200.4.34 (Port E)
Operation-panel language English (United States)
Binary input channel threshold Low: 44 V, High: 88 V
Used time stamp in GOOSE subscriptions On message reception
Hide settings in IEC 61850 structure Show all settings
Hide SIPROTEC extensions in IEC 61850 structure Show all SIPROTEC extensions
Use dynamic reporting True
Block IEC 61850 settings changes False
Access point used in Edition1 No access point is specified for the SCD import.
General \Device
Number Settings Value
91.101 Rated frequency All: 50 Hz
91.102 Minimum operate time All: 0 s
91.115 Set. format residu. comp. All: Kr, Kx
91.138 Block monitoring dir. All: off
General \Measurements
Number Settings Value
91.162 Blk setting change All: false
91.111 Energy restore interval Settings group 1: 10 min
91.112 Energy restore time Settings group 1: none
91.120 Energy restore Settings group 1: latest value
General \Control
Number Settings Value
91.121 Energy restore by A.time All: false
91.118 Enable sw.auth. station All: false
91.119 Multiple sw.auth. levels All: false
General \Spontan.indic.
Number Settings Value
91.152 Specific sw. authorities All: false
1 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
General \CFC
Number Settings Value
91.139 Fault-display All: with pickup
Localization
Number Settings Value
6211.139 Unit system All: SI
Time settings
General
Settings Value
Date format All: DD.MM.YYYY
Time source
Settings Value
Fault indication after All: 600 s
Time source 1 Ch1:port E:SNTP
Time source 2 none
Time zone time source 1 All: UTC
Time zone time source 2 All: local
Sync. latency time src.1 All: 0.10 μs
Sync. latency time src.2 All: 0 μs
2 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
CT 1
Number Settings Value
11.931.3841.103 Magnitude correction All: 1
11.931.3841.117 Phase All: I A
CT 2
Number Settings Value
11.931.3842.103 Magnitude correction All: 1
11.931.3842.117 Phase All: I B
CT 3
Number Settings Value
11.931.3843.103 Magnitude correction All: 1
11.931.3843.117 Phase All: I C
CT 4
Number Settings Value
11.931.3844.103 Magnitude correction All: 1
11.931.3844.117 Phase All: IN
Brk.wire det.
Number Settings Value
11.931.5581.1 Mode Settings group 1: on
11.931.5581.101 Mode of blocking Settings group 1: not blocking
11.931.5581.102 Delta value for autoblock Settings group 1: 1
3 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
Supv. balan. I
Number Settings Value
11.931.2491.1 Mode Settings group 1: on
11.931.2491.101 Release threshold Settings group 1: 600 A
11.931.2491.102 Threshold min/max Settings group 1: 0.5
11.931.2491.6 Delay supervision alarm Settings group 1: 100 s
Supv. ph.seq.I
Number Settings Value
11.931.2551.1 Mode Settings group 1: on
11.931.2551.6 Delay supervision alarm Settings group 1: 100 s
Supv. sum I
Number Settings Value
11.931.2431.1 Mode Settings group 1: on
11.931.2431.102 Threshold Settings group 1: 120 A
11.931.2431.101 Slope factor Settings group 1: 0.1
11.931.2431.6 Delay supervision alarm Settings group 1: 5 s
Supv.ADC sum I
Number Settings Value
11.931.2401.1 Mode Settings group 1: on
VT 1
Number Settings Value
11.941.3811.103 Magnitude correction All: 1
11.941.3811.108 Phase All: V A
VT 2
Number Settings Value
11.941.3812.103 Magnitude correction All: 1
11.941.3812.108 Phase All: V B
VT 3
Number Settings Value
11.941.3813.103 Magnitude correction All: 1
4 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
VT 4
Number Settings Value
11.941.3814.103 Magnitude correction All: 1
11.941.3814.108 Phase All: VN
Supv. balan. V
Number Settings Value
11.941.2521.1 Mode Settings group 1: on
11.941.2521.101 Release threshold Settings group 1: 250 kV
11.941.2521.102 Threshold min/max Settings group 1: 0.75
11.941.2521.6 Delay supervision alarm Settings group 1: 5 s
Supv. ph.seq.V
Number Settings Value
11.941.2581.1 Mode Settings group 1: on
11.941.2581.6 Delay supervision alarm Settings group 1: 5 s
Supv. sum V
Number Settings Value
11.941.2461.1 Mode Settings group 1: off
11.941.2461.3 Threshold Settings group 1: 125 kV
11.941.2461.6 Delay supervision alarm Settings group 1: 5 s
VT miniatureCB
Number Settings Value
11.941.2641.101 Response time Settings group 1: 0 s
Line 1 \General
General \Rated values
Number Settings Value
21.9001.101 Rated current All: 1200 A
21.9001.102 Rated voltage All: 500 kV
5 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
General \Measurements
Number Settings Value
21.9001.158 P, Q sign Settings group 1: not reversed
1pol.open det.
Number Settings Value
21.1131.4711.101 Operating mode Settings group 1: with measurement
Volt.criterion
Number Settings Value
21.1131.4801.101 Threshold U open Settings group 1: 135.14 kV
Line 1 \50BF E0
Standard 1
Number Settings Value
21.971.3901.1 Mode Settings group 1: on
21.971.3901.101 Activation Settings group 1: always active
21.971.3901.3 Threshold Settings group 1: 300 A
21.971.3901.4 Dropout ratio Settings group 1: 0.9
6 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
7 of 8
Totally Integrated 7VK87 - 50BF CORTE B AYOLAS
Automation Portal
8 of 8