TB 03700001 e
TB 03700001 e
TB 03700001 e
February 2007
37-1
Lighting Contactors
Contents
Description Open Control CN35 Electrically Held . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C30CN Mechanically Held . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A202 Magnetically Latched . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . UL Rated AC Enclosed Product Family Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C30CN Electrically and Mechanically Held. . . . . . . . . . . . . . . . . . . . . . . . . CN35 Electrically Held . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A202 Magnetically Latched . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 37-2 37-8 37-17 37-20 37-23 37-24 37-26 37-28 37-29
37
CA08102001E
37-2
Contents
Description Electrically Held Product Description . . . . . . . Application Description. . . . Features . . . . . . . . . . . . . . . . Instructional Leaets . . . . . . Standards and Certications . . . . . . . . . . . Accessories . . . . . . . . . . . . . Renewal Parts . . . . . . . . . . . Dimensions . . . . . . . . . . . . . Product Selection . . . . . . . . 37-2 37-2 37-2 37-2 37-2 37-2 37-5 37-6 37-7 Page
Features
Instructional Leaets
19225 19227 24829 24840 19227 19229 19874 20218 20171 20172 20172 CN35AN (2-, 3-, 4-Pole) CN35BN (2-, 3-Pole) CN35BN (4-, 5-Pole) CN35BN (6-, 9-, 12-Pole) CN35DN (2-, 3-Pole) CN35GN (2-, 3-Pole) CN35GN (4-, 5-Pole) CN35KN (2-, 3-Pole) CN35NN (2-, 3-Pole) CN35SN (2-, 3-Pole) CN35TN (2-, 3-Pole)
37
Designed and tested specically for lighting and resistive loads Easy to install and maintain Full line of Freedom snap-on Accessories Standard with 1NO auxiliary contact (the 10A two- and three-pole ship standard with the auxiliary in the fourth power pole position with no increase in width) Top and side mounted auxiliary contacts available for 10 60A devices; side mounted auxiliaries only available on 100A and greater Straight-through wiring
Accessories
Transient Suppressor Kits
20A Cat. No. CN35BN3AB
10 60A Contactors
Product Description
Cutler-Hammer Type CN35 Electrically Held Lighting Contactors from Eatons electrical business are designed to handle the switching of tungsten (incandescent) or ballast (uorescent and mercury arc) lamp loads as well as other non-motor (resistive) loads.
Application Description
Ideal applications include industrial plants, stadiums, parks and any new construction requiring lighting control. Ballast Lamps equate to Fluorescent, Mercury Vapor, Sodium Vapor and Quartz loads and will operate at a maximum of 600V. Filament Lamps equate to Incandescent, Infrared, Sodium Iodine and Heating loads and will operate at a maximum of 480V. Resistance Heating equates to radiant and convection heating, furnace and oven loads.
These kits limit high voltage transients produced in the control circuit when power is removed from the contactor or starter coil. There are three separate suppressors for use on 24 120V, 240V or 480V coils respectively. These devices mount directly to the coil terminals of lighting contactors 10 60A. Table 37-1. Kits for 10 60A
Description Transient Suppressor Coil Voltage Catalog Number Price U.S. $
This device mounts on top of any side mounted auxiliary contact on lighting contactors 100 300A. It connects across coil terminals on any 120V contactor magnet coil. Limits high voltage transients produced in the circuit when power is removed from the coil. Table 37-2. Kits for 100 300A
Description Transient Suppressor Coil Voltage 120V Catalog Number C320AS1 Price U.S. $
37-3
Auxiliary Contacts
CN35 Lighting Contactors include a 1NO maintaining auxiliary contact mounted on right hand side (on 10A, 2- and 3-pole devices, auxiliary contact occupies 4th power pole position no increase in width). The 10 60A devices will accept additional auxiliary contacts on the top and/or sides. Auxiliary contact blocks are designed for snap-on installation fast, easy installation (no tools required up to 60A). All auxiliary contacts are of the bifurcated design with parallel circuit paths. This redundant path provides very high reliability. Auxiliary contacts can be snapped on the side (up to 2 circuits per auxiliary contact) and on the top (up to 4 circuits). Auxiliary contacts for larger contactors, 100 400A sizes, will accept side mounted auxiliaries only and easily attach to the side of the contactor with 2 screws.
Side Mounted
1NO 1NC 1NO-1NC 2NO 2NC C320KGS1 C320KGS2 C320KGS3 C320KGS4 C320KGS5 C320KGT1 C320KGT2 C320KGT3 C320KGT4 C320KGT5 C320KGT9 C320KGT10 C320KGT11 C320KGT12 C320KGT13 C320KGT14 C320KGT15 C320KGT16 C320KGT17
Top Mounted
1NO 1NC 1NO-1NC 2NO 2NC 3NO 2NO-1NC 1NO-2NC 3NC 4NO 3NO-1NC 2NO-2NC 1NO-3NC 4NC
37
For Reference Only not part of Catalog Number. See below left. Cannot be added to contactors or starters mounted in Box 1 (NEMA Type 1).
Side Mounted
Top Mounted
For Reference Only not part of Catalog Number. See below left. NO-NC occupies two positions L2 & L3 or R2 & R3. See Page 37-4.
NEMA A600
Make & Interrupting Break Continuous 60.0 6.0 10.0
NEMA P300
Base Auxiliary Contact Cat. No. C320KGS42 Auxiliary Contact Cat. No. C320KGS22 Continuous Thermal Rating: 5 Amperes DC Volts 125 250 Make/Break Amperes 1.10 0.55
37-4
Pneumatic Timer
NEMA 3R, 4X, 12 L1, T1 L1, T1 L1, T1 L1, T1 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3
NEMA 1 L1 L1 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3
37
24 23 4 5 23 23 23 23
T1, L1, R1 T1, L1 T1, L1 T1, L1 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3 R2, R3, L1, L2, L3
Attachment mounts on top of 10 60A lighting contactors (top mounted auxiliary contacts can not be installed on device when timer is used). Timer unit has DPST timed contacts circuits in each pole must be the same polarity. Units are convertible from OFF to ON Delay or vice-versa. Table 37-7. Pneumatic Timers
Timing Range .1 to 30 Seconds 10 to 180 Seconds Catalog Number C320TP1 C320TP2 Price U.S. $
Available positions on contactors or starters other than what is factory installed. When a pneumatic timer is mounted on contactor, only side mounted auxiliary contact positions are available. The solid-state timer, when added, takes up side mounted auxiliary contact position. For 100 400A contactors, a base auxiliary contact must be added in position L1 before additional contacts can be mounted.
L1
T1
R1
L1 Rear
L2
L3
R3
R2
R1 Rear
Base Aux. Aux. Aux. Cont. Cont. Cont. Left Side of Contactor Front of Contactor 100 400A Contactors
Aux. Aux. Base Cont. Cont. Aux. Cont. Right Side of Contactor
37-5
Solid-State Timers
Solid-State ON DELAY Timer Side Mounted on CN35 Freedom Series Lighting Contactors through 60A
This timer is designed to be wired in SERIES with the load (typically a coil). When the START button is pushed (power applied to timer), the ON DELAY timing function starts. At the completion of the set timing period, timer and series wired load will both be energized.
Price U.S. $
Add operating voltage Sufx to Catalog Number. A = 120V, B = 240V, E = 208V Rated .5 ampere pilot duty not to be used on larger contactors. Terminal connections are quick connects only. Two per side.
Renewal Parts
Table 37-10. Renewal Parts for CN35 Lighting Contactors
Description 10A Price 20A, 30A Price 60A Price Series C1 U.S. $ Series C1 U.S. $ Series B1 U.S. $ Part No. Part No.
37
100A Part No. 6-43-5 6-43-6 Price U.S. $ 200A Part No. 6-44 6-44-2 Price U.S. $ 300A Price Series B1 U.S. $ Part No. 6-45 6-45-2 Part No. 6-65-7 6-65-8 6-65-15 6-65-16
Contact Kits
2-Pole 3-Pole 4-Pole 5-Pole .................... .................... .................... ....................
Magnet Coils
120V 60 Hz or 110V 50 Hz . . 240V 60 Hz or 220V 50 Hz . . 480V 60 Hz or 440V 50 Hz . . 600V 60 Hz or 550V 50 Hz . . 208V 60 Hz . . . . . . . . . . . . . . 277V 60 Hz . . . . . . . . . . . . . . 208/240V 60Hz . . . . . . . . . . 240V 50Hz. . . . . . . . . . . . . . . 380 415V 50 Hz . . . . . . . . .
Coil Sufx
A B C D E H J K L 9-2875-1 9-2875-2 9-2875-3 9-2875-4 9-2875-5 9-2875-12 9-2875-37 9-2875-11 9-2875-6 9-2875-36 9-2875-36 9-2875-16 9-2875-8 9-2875-9 9-2876-1 9-2876-2 9-2876-3 9-2876-4 9-2876-5 9-2876-12 9-2876-37 9-2876-11 9-2876-6 9-2876-36 9-2876-13 9-2876-16 9-2876-8 9-2876-9 9-2703-1 9-2703-2 9-2703-3 9-2703-4 9-2703-9 9-2703-7 9-2703-14 9-2703-8 9-2703-6 9-2703-12 9-2703-10 9-2703-11 9-2703-13 9-2756-1 9-2756-2 9-2756-3 9-2756-4 9-2756-5 9-2756-9 9-2756-13 9-2756-12 9-2756-8 9-2756-14 9-2756-6 9-2756-11 9-2756-10 9-2756-15 9-2756-7 9-1891-1 9-1891-2 9-1891-3 9-1891-4 9-1891-13 9-1891-26 9-1891-20 9-1891-14 9-1891-21 9-1891-8 9-1891-15 9-1891-16 9-1891-18 9-1891-1 9-1891-2 9-1891-3 9-1891-4 9-1891-13 9-1891-26 9-1891-20 9-1891-14 9-1891-21 9-1891-8 9-1891-15 9-1891-16 9-1891-18
380V 50 Hz . . . . . . . . . . . . . . L 415V 50 Hz . . . . . . . . . . . . . . M 550V 50 Hz . . . . . . . . . . . . . . N 24V 60 Hz 24V 50 Hz . . . . . 24V 60 Hz . . . . . . . . . . . . . . . 24V 50 Hz . . . . . . . . . . . . . . . 32V 50 Hz . . . . . . . . . . . . . . . 48V 60 Hz . . . . . . . . . . . . . . . 48V 50 Hz . . . . . . . . . . . . . . .
T T U V W Y
37-6
Dimensions
Table 37-11. Approximate Dimensions and Shipping Weights
Ampere Rating Number of Poles Dimensions in Inches (mm) Wide A High B Deep C Mounting D 1.50 (38.1) 1.50 (38.1) 3.50 (88.9) 4.50 (114.3) 4.50 (114.3) 2.00 (50.8) 2.00 (50.8) 2.00 (50.8) 3.00 (76.2) 6.00 (152.4) 6.00 (152.4) E 3.38 (85.9) 3.38 (85.9) 3.86 (98.0) 5.00 (127.0) 5.00 (127.0) 4.50 (114.3) 4.50 (114.3) 4.50 (114.3) 6.63 (168.4) 8.50 (215.9) 12.50 (317.5) 4.90 (124.5) 4.90 (124.5) 4.90 (124.5) 5.80 (147.3) 5.80 (147.3) 5.80 (147.3) .54 (13.7) .54 (13.7) .54 (13.7) .54 (13.7) .54 (13.7) .54 (13.7) .54 (13.7) 1.4 (.6) 1.5 (.7) 2.9 (1.3) 4.4 (2.0) 5.8 (2.6) 3.5 (1.6) 3.5 (1.6) 3.5 (1.6) 9.0 (4.1) 20.0 (9.1) 23.0 (10.4) F G Ship. Wt. Lbs. (kg)
Open Type
10 20 30 20 30 20 30 20 30 60 60 60 100 200 300
24 23 46 9 12 23 4 5 23 23 23
2.00 (50.8) 2.00 (50.8) 4.20 (106.7) 10.50 (266.7) 10.50 (266.7) 2.56 (65.0) 3.46 (87.9) 4.36 (110.7) 3.54 (89.9) 7.05 (179.1) 7.05 (179.1)
3.88 (98.6) 3.88 (98.6) 4.35 (110.5) 5.75 (146.1) 5.75 (146.1) 5.05 (128.3) 5.05 (128.3) 5.05 (128.3) 7.17 (182.1) 9.11 (231.4) 13.12 (333.2)
3.49 (88.6) 3.49 (88.6) 3.52 (89.4) 4.52 (114.8) 4.52 (114.8) 4.44 (112.8) 4.44 (112.8) 4.44 (112.8) 5.94 (150.9) 7.25 (184.2) 7.78 (197.6)
37
A U X
A U E X
A U X E
Auxiliary Contacts Mtg. Holes for #10-32 Screws Open Type 20 30A Sizes, 9- to 12-Pole G
Auxiliary Contacts Mtg. Holes for (3) #10-32 Screws Open Type
A U E X
100A, 2- to 3-Pole G
A U X
A U E X
B B E
A U X
B E
G C
A U X
A U E X
A U X
A U E X
37-7
Product Selection
10
20
30
37
Catalog Number including the Coil Sufx Code from the Magnet Coil Selection Table. Any required Accessories.
60
The listed ampere ratings are based on a maximum load voltage of 480V for tungsten lamp applications and 600V for ballast or mercury vapor type applications. Additional power poles mounted on side(s) of contactor. Underscore (_) indicates missing Code Letter for Magnet Coil see Magnet Coil Selection table below. UL ballast and resistive ratings only.
Code Sufx A B C D
Code Sufx E H J K
Coil Voltage and Hertz 380 415/60 550/50 24/60, 24/50 24/50
Code Sufx L N T U
For 10, 20 and 30A sizes only. For 10, 20 and 30A sizes only. Sizes 60 400A are 24V/60 Hz only. For DC Magnet Coils, see NEMA Contactors & Starters, Pages 33-98 33-99.
Dimensions. . . . . . . . . . . . . . . . . . . . . . Page 37-6 Special Modications . . . . . . . . . . . . Page 33-100 Discount Symbol . . . . . . . . . . . . . . . . 1CD-1C CA08102001E For more information visit: www.eaton.com
37-8
Contents
Description Open Control Product Description . . . . . . Application Description . . . Features . . . . . . . . . . . . . . . . Operation . . . . . . . . . . . . . . Instructional Leaets . . . . . Standards and Certications . . . . . . . . . . Technical Data and Specications . . . . . . . . . . Components . . . . . . . . . . . . Replacement Parts . . . . . . . Wiring Diagrams . . . . . . . . . Dimensions . . . . . . . . . . . . . Catalog Number Selection . . . . . . . . . . . . . . Product Selection . . . . . . . . Page 37-8 37-8 37-8 37-9 37-9 37-9 37-9 37-10 37-11 37-12 37-14 37-14 37-15
Application Description
The mechanically held lighting contactor provides effective control in applications such as ofce buildings, industrial plants, hospitals, stadiums, airports, etc. They are ideal for applications that require quiet, energy-efcient operation. Designed to handle different load types:
Features
See Figure 37-3.
37
Tungsten (incandescent lament) Ballast (uorescent and mercury arc) High intensity discharge (HID) Non-motor AC resistive Single- and Three-Phase Motor Ratings
30 amp power pole rating Up to 12 poles maximum Power poles latch easily onto the base, and designating them as NO or NC is a simple matter of left or right positioning. Additional poles, either NO or NC, may be easily added at any time. Low magnetic noise results in quiet operation Low input VA permits long wire runs Come in a wide range of input voltages and with coils from 24V to 277V AC and 12V to 24V DC.
Enclosed contacts resist contaminants for greater reliability Common easily-installed power poles change from NO to NC (or vise versa) simply by unlatching and rotating 180 Power poles rated for a range of tasks: 30A rated contacts 15A motor rated Pilot duty rated Auxiliary contacts, rated A600, are suitable for use on low level circuits down to 12V, 5 mA
Power poles are available as single or double poles, creating 74 different circuit combinations Convenient side access for eld power wiring
C30CNM
Contact conguration indicator Robust pole terminals accept up to two 8 AWG wires
Product Description
The Cutler-Hammer C30CNM 30A Mechanically Held Lighting Contactors from Eatons electrical business are designed for industrial, commercial and outdoor lighting applications where efficient control is required. The mechanically held operation ensures that the contactor will not switch to OFF during control power failure. It also ensures the removal of coil from the circuit for noise-free operation and the elimination of all coil losses after the contactor is latched. The control module microprocessor validates the control signal before operation, so it will not respond to momentary voltage spikes of noise. The operation command has a built-in .4 sec delay to avoid multiple short-term commands that can cause contact fatigue or failure. Also, the feedback loop prevents the contactor from getting out of sequence with switches, even after power failures.
Plug-in auxiliary contacts are NC when installed on the right side of the base, NO on the left
CA08102001E
37-9
Operation
3-wire control is the choice for use with momentary devices allowing operation from multiple locations. A momentary pulse of energy operates the contactor while a second pulse on an alternate leg returns the contactor to its original state. 2-wire control is the choice for single output automatic operation or for operation from single-pole devices. When voltage is applied to the input terminals the contactor is latched into position (coil is removed from the circuit while control voltage is continuously supplied). When control voltage is removed, the latch is disengaged and the contactor is returned to its original state.
Ballast Tungsten
37
200 277V AC
Instructional Leaets
50765 50766 50767 50768 C30CN Lighting Contactor Series Coil Kit for C30CN Lighting Contactors Power Pole Kit for C30CN Lighting Contactors Control Module Kit for C30CN Lighting Contactors
Ambient Temperature:
-13 to 104F (-25 to 40C)
Mounting Position:
Vertical 3-point mounting only.
Wire Size
Table 37-19. Wire Specications
Component Power Poles Coil Control Module Auxiliary Contacts
Number of Cables 1 2 1 or 2 1 1 or 2
CA08102001E
37-10
Components
Electrically Held Base Contactor
The C30CNE20_0 Electrically Held Base Contactor contains a 2NO power pole as standard and will allow the addition of power poles to build an Electrically Held Contactor up to 12 poles maximum. A Mechanically Held Module Kit can also be added to convert the Electrically Held Contactor into a Mechanically Held Contactor in the eld.
Catalog Number C30CNE20_0
37
2-Wire
24 277V AC 110 120V AC 200 277V AC 24V AC 12 24V DC 110 120V AC 200 277V AC 24V AC 12 24V DC
When ordering, select required contactor by Catalog Number and replace the magnet coil alpha designation in the Catalog Number (_) with the proper Code Sufx from Table 37-21.
3-Wire
24 277V AC
Power Poles
Power Poles
The C30CNM contactor accepts up to a maximum 6 single- or double-pole (or combinations) power poles. These can be used to form up to: 12 NO poles max. when 6 double-poles are used in NO positions (1 6) or 8 NC poles max. with 4 double-poles in the NC position (1 4) and 4 NO poles with 2 double-poles in the 2 NO positions (5 6)
Table 37-22. Power Poles
Power Poles Single-Pole Double-Pole Catalog Number C320PRP1 C320PRP2 Price U.S. $
37-11
Auxiliary Contacts
A Mechanically Held Contactor with a 2-wire control module uses 1NC auxiliary contact as standard for the control wiring circuit. The Mechanically Held Contactor with a 3-wire control module uses 1NO-1NC auxiliary contacts as standard for the control wiring circuit. See Table 37-24 for possible additional auxiliary contact congurations. Table 37-24. Auxiliary Contact Congurations
2-Wire None 1NO (single-pole) 2NO (double-pole) 1NC (double-pole) 1NO-1NC (NO single pole, NC double-pole) 2NO-1NC (double-pole) 3-Wire 1NC (double-pole) 1NO (double-pole) 1NO-1NC (double-pole)
Replacement Parts
Magnet Coils for the Base Contactor
Magnetic Coils
37
Catalog Number 9-3242-1 9-3242-2 9-3242-3 9-3242-4 9-3242-5 9-3242-6 9-3242-7 9-3242-8 9-3242-9 Price U.S. $
Auxiliary Contacts
37-12
Wiring Diagrams
C30CNE Electrically Held Line 1 2 3 4 Remote OFF Auxiliary Contact Remote Auxiliary Contact ON Load OFF Pushbutton L1 * Fuse ON Pushbutton ON * L2 View B Optional Pilot Devices for Electrically Held Contactor * If Used
A2
Coil
A1
Fuse
37
5 6
OFF
View A A1 Optional Auxiliary Contacts Coil A2 Optional Auxiliary Contacts L1 * Fuse Remote Device OFF SS AUTO
ON * L2
Coil Voltage
A2 Auxiliary Contact
Coil
A1
Fuse
OFF
ON L1 * * L2
Fuse
Coil
A1
Fuse
OFF
CA08102001E
37-13
C30CNM Mechanically Held Refer to View A for 2-/3-Wire Control Options Load Line 1 2 3 4 Control Voltage OFF ON
Fuse
Electronic-Module P1 P2 P3 P4 P5
OFF
5 6 View A Electronic-Module P1 P2 P3 P4 P5 C Not Used A1 Coil A2 Optional NC Aux. Contact Control Voltage OFF ON
Remote ON
Fuse
* Coil Voltage *
AUTO
Remote Device
Fuse
37
View C Optional Pilot Devices for 3-Wire Control NO Remote Auxiliary OFF Electronic-Module P1 P2 P3 P4 P5 OFF
ON
Fuse
Coil Voltage
NC Auxiliary
A2
Coil
A1
Fuse
* Coil Voltage *
Control Voltage
ON OFF ON
NC Auxiliary
A2
Coil
A1
Fuse
CA08102001E
37-14
Dimensions
.35 (9.0) SIDE VIEW Power Pole TOP VIEW 2 NO Aux Contacts 1 NO Aux Contact 6.50 (165.1) 7.39 (187.6) NOTE: 1 Mounting dimensions remain the same for 1 to 12 poles. 2 Line and Load terminals are interchangeable. 3 Up to 2NO and 2NC auxiliary contacts can be added onto the base product. 4 Same power pole can be configured as NO type or NC type in pole positions 1 4; NO type only in positions 5 6. END VIEW
P1 P2 P3 P4 P5
ON ON ON ON ON ON
37
Optional NO Aux Contacts Mounting Holes Accept #10 Screws .22 (5.5)
P1 P2 P3 P4 P5
A1
A2
.59 (14.9)
C30CN M 2 2 A A 2 A0
Product C30CN = Open 30A Lighting Contactor Class E = Electrically Held M = Mechanically Held No. of Normally Open Poles 0 12 Auxiliary Contact Installed No. of Normally Closed Poles 08 Base Coil Voltage A = 115 120V 60 Hz/110V 50 Hz B = 230 240V 60 Hz/220V 50 Hz C = 460 480V 60 Hz/440V 50 Hz D = 575 600V 60 Hz/550V 50 Hz E = 200 208V 60 Hz H = 265 277V 60 Hz/240V 50 Hz T = 24V 60 Hz/20V 50 Hz V = 28V 60 Hz/24V 50 Hz X = 347V 60 Hz 2-Wire Control Module 0 = None A = 1NO B = 2NO C = 1NC D = 1NO-1NC E = 2NO-1NC 3-Wire Control Module 0 = None C = 1NC F = 1NO G = 1NO-1NC Mechanically Held Control Module Voltage A0 = 110 120V AC H0 = 200 277V AC T0 = 24V AC T1 = 24V DC Control Module Operation 2 = 2-wire 3 = 3-wire
C 1
3 2
0 3
C 4
N 5
M 6
2 7
2 8
A 9
A 10
2 11
12 13
CA08102001E
37-15
Product Selection
2-Wire Mechanically Held Lighting Contactors Standard Assembled Forms
The Standard Assembled Forms in Table 37-28 are 2-wire open mechanically held 30 amp lighting contactors with 120V 60 Hz/ 110V 50 Hz base coil voltage, 120V control module voltage, and no additional auxiliary contacts. To change the base coil voltage, auxiliary contact options or control module voltage, refer to Tables 37-29, 37-30 and 37-31 respectively. Table 37-28. 2-Wire Mechanically Held Lighting Contactors Standard Assembled Forms Product Selection
No. of Poles 2 NO 0 1 2 0 1 2 3 0 1 2 3 4 0 1 2 3 4 5 0 1 2 3 4 5 6 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 NC 2 1 0 3 2 1 0 4 3 2 1 0 5 4 3 2 1 0 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 8 7 6 5 4 3 2 1 0 8 7 6 5 4 3 2 1 0 8 7 6 5 4 3 2 1 0 Catalog Number C30CNM02A02A0 C30CNM11A02A0 C30CNM20A02A0 C30CNM03A02A0 C30CNM12A02A0 C30CNM21A02A0 C30CNM30A02A0 C30CNM04A02A0 C30CNM13A02A0 C30CNM22A02A0 C30CNM31A02A0 C30CNM40A02A0 C30CNM05A02A0 C30CNM14A02A0 C30CNM23A02A0 C30CNM32A02A0 C30CNM41A02A0 C30CNM50A02A0 C30CNM06A02A0 C30CNM15A02A0 C30CNM24A02A0 C30CNM33A02A0 C30CNM42A02A0 C30CNM51A02A0 C30CNM60A02A0 C30CNM07A02A0 C30CNM16A02A0 C30CNM25A02A0 C30CNM34A02A0 C30CNM43A02A0 C30CNM52A02A0 C30CNM61A02A0 C30CNM70A02A0 C30CNM08A02A0 C30CNM17A02A0 C30CNM26A02A0 C30CNM35A02A0 C30CNM44A02A0 C30CNM53A02A0 C30CNM62A02A0 C30CNM71A02A0 C30CNM80A02A0 C30CNM18A02A0 C30CNM27A02A0 C30CNM36A02A0 C30CNM45A02A0 C30CNM54A02A0 C30CNM63A02A0 C30CNM72A02A0 C30CNM81A02A0 C30CNM90A02A0 C30CNM28A02A0 C30CNM37A02A0 C30CNM46A02A0 C30CNM55A02A0 C30CNM64A02A0 C30CNM73A02A0 C30CNM82A02A0 C30CNM91A02A0 C30CNM100A02A0 Price U.S. $ No. of Poles 11 NO 3 4 5 6 7 8 9 10 11 12 4 6 8 10 12
NC 8 7 6 5 4 3 2 1 0 8 6 4 2 0
Catalog Number C30CNM38A02A0 C30CNM47A02A0 C30CNM56A02A0 C30CNM65A02A0 C30CNM74A02A0 C30CNM83A02A0 C30CNM92A02A0 C30CNM101A02A0 C30CNM110A02A0 C30CNM48A02A0 C30CNM66A02A0 C30CNM84A02A0 C30CNM102A02A0 C30CNM120A02A0
Price U.S. $
37
To change the base coil voltage, replace the content of Position 9 with the appropriate Code Sufx from Table 37-29. To change auxiliary contact options, replace the content of Position 10 with the appropriate Code Sufx from Table 37-30. To change the control module voltage, replace the content of Positions 12-13 with the appropriate Code Sufx from Table 37-31.
37-16
NC 8 7 6 5 4 3 2 1 0 8 6 4 2 0
Catalog Number C30CNM38A03A0 C30CNM47A03A0 C30CNM56A03A0 C30CNM65A03A0 C30CNM74A03A0 C30CNM83A03A0 C30CNM92A03A0 C30CNM101A03A0 C30CNM110A03A0 C30CNM48A03A0 C30CNM66A03A0 C30CNM84A03A0 C30CNM102A03A0 C30CNM120A03A0
Price U.S. $
37
4
To change the base coil voltage, replace the content of Position 9 with the appropriate Code Sufx from Table 37-33. To change auxiliary contact options, replace the content of Position 10 with the appropriate Code Sufx from Table 37-34. To change the control module voltage, replace the content of Positions 12-13 with the appropriate Code Sufx from Table 37-35.
37-17
The Magnetically Latched Lighting Contactor provides effective control in applications such as ofce buildings, industrial plants, hospitals, stadiums, airports, etc.
Instructional Leaets
IL16965 30A (2, 3, 4, 5 Poles) IL16966 60 200A (2, 3, 4, 5 Poles)
Features
60A Size
Product Description
The Cutler-Hammer A202 Lighting Contactor from Eatons electrical business provides a safe and convenient means for local or remote switching of relatively large tungsten, uorescent or mercury arc lamp loads.
Designed and tested specically for lighting and resistive loads Easy to install and maintain No control power necessary to maintain contact closure
UL Listed File # E44424, Guide NRNT CSA Certied File # LR39402, Class 3231-01
Operation
A permanent magnet is built into the contactor structure that will maintain the contactor in its energized state indenitely without using control power. When energized, a DC current is applied to the latch coil, producing a magnetic eld that reinforces the polarity of the permanent magnet, pulling in the contactor. The coil clearing interlock disconnects the current to the coil. In order to drop out the contactor, it is necessary to apply a eld through the STOP coil in the reverse direction to the permanent magnet. This momentarily cancels the magnetic attraction and the contactor drops out.
37
Application Description
The Magnetically Latched Lighting Contactors are designed to withstand the large initial inrush currents of tungsten lamp loads without contact welding. The A202 Contactors are fully rated devices that do not require de-rating similar to standard motor control contactors.
Ballast load: 600 AC, breaking all lines Tungsten lamp loads, maximum volts Line-to-line: 480V AC Line-to-neutral: 277V AC
Accessories
See A200 NEMA Contactor Accessories, Page 33-194 33-196.
Wiring Diagrams
The standard wiring of an A202 contactor can be controlled by a separate customer supplied single-pole doublethrow controlling station.
Control Line
L2 (+)
Line
ON
OFF
Black
Close
White
Open
Red
Figure 37-8. Standard Wiring Two-wire control can be accomplished with a customer supplied relay with 1NO/1NC auxiliary contacts, wire as shown.
Switch Line or Neutral Line
L2 (+)
ON
OFF
Line
Black
CM
CM Control
CM 2 CM
White
Red
37-18
Renewal Parts
Table 37-36. AC Coil Renewal Parts for A202 Magnetically Latched
Voltage Hz 2-, 3-, 4-Pole Part Number 7874A93G01 7874A93G02 7874A93G03 7874A93G04 7874A93G05 2-, 3-Pole 7874A93G01 7874A93G02 7874A93G03 7874A93G04 7874A93G05 7874A85G01 7874A85G02 7874A85G03 7874A85G04 7874A85G05 Price U.S. $ 5-Pole Part Number 7874A89G01 7874A89G02 7874A89G03 7874A89G04 7874A89G05 4-, 5-Pole 7874A87G01 7874A87G02 7874A87G03 7874A87G04 7874A87G05 7874A83G01 7874A83G02 7874A83G03 7874A83G04 7874A83G05 Price U.S. $
30 Ampere
110/120 208/240 277 440/480 575 50/60
60 Ampere
37
110/120 208/240 277 440/480 575 110/120 208/240 277 440/480 550/575
50/60
30 Ampere
N/A
60 Ampere
179C755G17
100 Ampere
179C755G19 179C755G18
179C755G19
179C755G28
179C755G30
179C755G31
Order quantity of two for 4-pole design. Group members for the 5-pole terminal represent the combination of the 2- and 3-pole number.
Arc boxes, upper base assemblies and cross bars are equivalent to the A201 series. See Page 33-194. Contact kits are equivalent to the A201 Model J series, with the exception of the magnetically latched 200 ampere unit. It uses Catalog Number 672B788G07 for the 3-pole device. For other poles, consult factory.
37-19
Dimensions
Table 37-39. Approximate Dimensions for Non-combination Open Lighting Contactors 2- to 12-Pole
Continuous Amperes Number of Poles Pole Dimensions in Inches (mm) Conguration Open Type Wide A High B 3.31 (84.1) 4.19 (106.4) 7.13 (181.1) 7.13 (181.1) 10.63 (270.0) 12.38 (314.5) 3.31 (84.1) 4.19 (106.4) 7.13 (181.1) 10.63 (270.0) 10.63 (270.0) 15.00 (381.0) 4.63 (117.6) 7.25 (184.2) 9.75 (247.7) 12.38 (314.5) 15.00 (381.0) 34.13 (866.9) 4.63 (117.6) 7.25 (184.2) 9.75 (247.7) 12.38 (314.5) 15.00 (381.0) 34.13 (866.9) 4.38 (111.3) 4.38 (111.3) 4.46 (113.3) 4.46 (113.3) 4.46 (113.3) 6.88 (174.8) 4.38 (111.3) 4.38 (111.3) 4.46 (113.3) 4.46 (113.3) 4.46 (113.3) 6.88 (174.8) 6.63 (168.4) 6.63 (168.4) 6.88 (174.8) 6.88 (174.8) 6.88 (174.8) 27.50 (698.5) 6.63 (168.4) 6.63 (168.4) 6.88 (174.8) 6.88 (174.8) 6.88 (174.8) 27.50 (698.5)
Product Selection
When Ordering Specify
Catalog Number with Coil Sufx Code from the Magnet Coil Selection Table. Any required Accessories. Table 37-40. Latched AC Lighting Contactors
Holding Circuit Auxiliary Contact or Pushbutton Station Not Included Continuous Amperes (Enclosed) 30 Number of Poles Open Type Catalog Number A202K1B_M A202K1C_M A202K1D_M A202K1E_M A202K1F_M A202K1G_M A202K1H_M A202K1K_M A202K2B_M A202K2C_M A202K2D_M A202K2E_M A202K2F_M A202K2G_M A202K2H_M A202K2K_M A202K3B_M A202K3C_M A202K3D_M A202K3E_M A202K3F_M A202K3G_M A202K3H_M A202K3K_M A202K4B_M A202K4C_M A202K4D_M A202K4E_M A202K4F_M A202K4G_M A202K4H_M A202K4K_M A202K5B_M A202K5C_M A202K6B_M A202K6C_M Price U.S. $
30
60
100
200
24 5 6 8 10 12 2, 3 4, 5 6 8 10 12 2, 3 4, 5 6 8 10 12 2, 3 4, 5 6 8 10 12
2 3 4 5 6 8 10 12
37
60
2 3 4 5 6 8 10 12
100
2 3 4 5 6 8 10 12
B 200
2 3 4 5 6 8 10 12
A Open Type
300 400
2 3 2 3
Lighting contactors are not available with DC coils. Contactors rated 300A and 400A are mechanically latched. Underscore (_) indicates missing Code letter for Magnet Coil Selection see Magnet Coil Selection Table.
Available on 2- to 5-pole, 30 and 60A devices and on 2- to 3-pole 100 and 200A devices.
37-20
Contents
Description Product Family Overview . . . . Cover Control . . . . . . . . . . . Catalog Number Selection . . . . . . . . . . . . . . C30CN Electrically and Mechanically Held . . . . . CN35 Electrically Held . . . . . . . A202 Magnetically Latched . . . . . . . . . . . . . . . . . Combination . . . . . . . . . . . . . . . Wiring Diagrams . . . . . . . . . . . . Page 37-20 37-21 37-22 37-23 37-24 37-26 37-28 37-29
Accessories
Auxiliary Contacts
C30CN Electrically Held Contactors The base C30CN product line can accept up to four auxiliary contacts (2NO/2NC), which are mounted on the top of the unit. The auxiliary contacts, rated A600, are also suitable for use on low-level circuits down to 12V, 5 mA. CN35 Electrically Held Contactors Include a NO maintaining auxiliary contact mounted on the right side of the contactor. The 10 60A devices will accept additional auxiliary contacts on the top (front) and/or sides. The 100 400A sizes will accept side mounted auxiliaries only. Mechanically Held and Magnetically Latched Holding circuit auxiliary contact, if needed, is not included and should be added separately as an option.
37
Product Description
Cutler-Hammer Lighting Contactors from Eatons electrical business are designed to provide a safe, convenient means for local or remote switching of tungsten (incandescent lament) or ballast (uorescent and mercury arc) lamp loads. They are also suitable for other loads such as low pressure and high pressure sodium lamp loads and other non-motor (resistive) loads. They are not recommended for most sign ashing loads. These lighting contactors are designed to withstand the large initial inrush currents of tungsten lamp loads without contact welding. They are fully rated and do not require derating.
Type 3R Price U.S. $ Catalog Number ECLC202A ECLC202E ECLC202B ECLC202H ECLC202C Price U.S. $
Application Description
Loads: Ballast Lamps Fluorescent, Mercury Vapor, Metal Halide Sodium Vapor, Quartz 600V maximum. Filament Lamps Incandescent, Infrared, Heating 480V maximum, line to line; 277V maximum line to neutral. Resistance Heating Radiant and convection heating, furnaces and ovens.
37-21
Cover Control
Table 37-43. Cover Mounted Pilot Devices
Description For use with Lighting Contactor Factory Installed Cover Control Type 1, 3R, 4X & 12 Type 7/9 Field Installation Kits Type 1 Type 3R, 4X, 12 Combination & Non-combination Catalog Price Number U.S. $
Modication Adder Code Sufx U.S. $ ON/OFF Pushbuttons Electrical P8 with Red RUN Pilot Light 3-wire C30CN; P8P23 with red RUN/GREEN off lights CN35; A202 P8P23P25 ON/OFF Pushbuttons Mechanical P8 with Red RUN Pilot Light 3-wire C30CN P8P23 with red RUN/GREEN off lights P8P23P25 ON/OFF Pushbuttons Elec. & Mech. P8 with Red RUN Pilot Light 2-wire C30CN; P8P23 with red RUN/GREEN off lights CN35; A202 P8P23P25 Start/Stop Pushbuttons Mechanical P7 with Red RUN Pilot Light 3-wire C30CN P7P23 with red RUN/GREEN off lights P7P23P25 Start/Stop Pushbuttons Elec. & Mech. P7 with Red RUN Pilot Light 2-wire C30CN P7P23 with red RUN/GREEN off lights P7P23P25 HAND/OFF/AUTO Cover Control Elec. & Mech. S3 with Red RUN Pilot Light 2-wire C30CN; S3P23 with red RUN/GREEN off lights CN35; A202 S3P23P25 Red RUN Pilot Light All P23 Green OFF Pilot Light P25 Red RUN/Green OFF Pilot Light P23P25 For use with Non-combination units (Box sizes 1 4). For use with Type 1 Combination units as well. Selector Switch. With 3-position selector switch, Mod C20 (2-wire control relay) must be used with magnetically latched contactor (ECL04, ECL13, ECL15).
Catalog Number
Price U.S. $
P8 C400GK18 C400T2 P8P23 C400GK19_ P8P23P25 C400GK1A_ P8 C400GK4 C400T201 P8P23 C400GK48_ P8P23P25 C400GK49_ P8 C400GK5 C400T14 P8P23 C400GK52_ P8P23P25 C400GK55_ P7 C400GK7 C400T200 P7P23 C400GK72_ P7P23P25 C400GK75_ P7 C400GK6 C400T13 P7P23 C400GK62_ P7P23P25 C400GK65_ C400GK3 C400T12 S3 S3P23 C400GK32_ S3P23P25 C400GK35_ P23 C400GK42_ C400T9_ P25 C400GK41_ C400T10_ P23P25 C400GK46_ C400T11_ Add Code Letter from table below to Catalog Number for Voltage in place of _. Rating Code Rating Code Letter Letter 24V 60 Hz 120V 60 Hz 208V 60 Hz 240V 60 Hz T A E B 277V 60 Hz 380V 60 Hz 480V 60 Hz 600V 60 Hz H L C D
37
37-22
EC L 12 D 1 A 3 E - X
Design L = CN35 or A202 Lighting Contactor C = C30CN Lighting Contactor Class Non-combination Contactors Page Modification Codes (See Enclosed Control Product Guide) Disconnect Fuse Clip Ratings A= B= C= D= E= F= G= H= None 30A/250V R 30A/600V R 60A/250V R 30A/600V R 100A/250V R 100A/600V R 200A/250V R J = 200A/600V R K = 400A/250V R L = 400A/600V R M = 600A/250V R N = 600A/600V R P = 800A/600V R T = By Description
37
03 = Electrically Held 37-23 & 37-24 04 = Mechanically/Magnetically Latched 37-23 & 37-26 Combination Fusible 12 = Electrically Held 37-28 13 = Mechanically/Magnetically Latched 37-28 Combination Thermal-Magnetic Circuit Breaker 14 = Electrically Held 37-28 15 = Mechanically/Magnetically Latched 37-28 Ampere Size A= B= C= D= E= 10A 20A 30A 60A 100A F= G= H= J= 200A 300A 400A 600A
Thermal-Magnetic Breaker Ratings A = None D = 20A E = 30A F = 60A G = 100A H = 200A J = 300A K = 400A L = 600A M = 800A T = By Description
Number of Poles 1, 2, 3, 4, 5, 6, 7, 8, 9 = Poles Required A = 10 Poles B = 12 Poles C = 20 Poles Combination Devices = 3-Pole Only Coil Voltage A= B= C= D= E= G= H= J= 120/60 110/50 240/60 220/50 480/60 440/50 600/60 550/50 208/60 550/50 277/60 208 240/60 K = 240/50 L = 380/50 M = 415/50 P = 12V DC Q = 24V DC R = 48V DC S = 125V DC T = 24/60 U = 24/50 V = 32/50 W = 48/60 X = 104 120/60 Y = 48/50 Z = By Description
Enclosure Types 1 = Type 1 General Purpose 2 = Type 3R Rainproof 3 = Type 4 Watertight (Painted) 4 = Type 4X Watertight (304-Grade Stainless Steel) 6 = Type 7/9 Explosion Proof 8 = Type 12 Dust-Tight 9 = Type 4X Watertight (316-Grade Stainless Steel)
For normally closed poles see Modication Codes. C30CN available in 30A only.
Enclosures
Lighting contactors are available open or mounted in Type 1, 3R, 4, 4X, 12 or 7/9 enclosures. Type 1 is for indoor, general purpose for personal protection. Knock-outs are provided in the top and bottom for conduit entry. Type 3R is for outdoor applications and rated for rain, sleet and external ice buildup. Type 3R enclosures have knockouts in the bottom and provisions for a hub in the top. Type 4 and 4X are for mounting indoor or outdoor and provides protection from splashing water, hose-directed water and wind-blown dust. Watertight conduit hubs are provided in the top and bottom of Type 4X enclosures. The standard Type 4X enclosures are made of 304-Grade stainless steel, providing corrosion protection. 316-Grade stainless steel construction is available as an upgrade option. Type 12 enclosures are for indoor mounting and protect from dripping liquids, falling dirt and dust. No knockouts or hubs are provided with Type 12 enclosures. Type 1, 3R, 4 and 12 enclosures are painted with a polyester urethane powder coat paint meeting UL requirements and the color is ANSI 61 gray. Type1 enclosures have knockouts for cover controls. All the other Types have holes plugged, ready for cover controls. Type 7/9 is also available for explosion proof applications. Please contact the factory for additional details.
Note: Modication codes can be found on Pages 5-16 through 5-30 of the Enclosed Control Product Guide (PG03300001E).
CA08102001E
37-23
Product Selection
2-Wire and 3-Wire Control Wiring Options 2-Wire Control Standard
Table 37-45. Class ECC03 Non-combination Electrically Held 2-Wire or 3-Wire Control C30CN
Number of Poles Type 1 Catalog Number Type 3R Catalog Number ECC03C2_2A ECC03C2_3A ECC03C2_4A ECC03C2_5A ECC03C2_6A ECC03C2_7A ECC03C2_8A ECC03C2_9A ECC03C2_AA ECC03C2_BA Type 4X Catalog Number ECC03C4_2A ECC03C4_3A ECC03C4_4A ECC03C4_5A ECC03C4_6A ECC03C4_7A ECC03C4_8A ECC03C4_9A ECC03C4_AA ECC03C4_BA Type 7/9 Catalog Number ECC03C6_2A ECC03C6_3A ECC03C6_4A ECC03C6_5A ECC03C6_6A ECC03C6_7A ECC03C6_8A ECC03C6_9A ECC03C6_AA ECC03C6_BA Type 12 Catalog Number ECC03C8_2A ECC03C8_3A ECC03C8_4A ECC03C8_5A ECC03C8_6A ECC03C8_7A ECC03C8_8A ECC03C8_9A ECC03C8_AA ECC03C8_BA Component Contactor (Open) Catalog Number C30CNE20_0 C30CNE30_0 C30CNE40_0 C30CNE50_0 C30CNE60_0 C30CNE70_0 C30CNE80_0 C30CNE90_0 C30CNE100_0 C30CNE120_0
37
Continuous Amps 30
2 3 4 5 6 7 8 9 10 12
ECC03C1_2A ECC03C1_3A ECC03C1_4A ECC03C1_5A ECC03C1_6A ECC03C1_7A ECC03C1_8A ECC03C1_9A ECC03C1_AA ECC03C1_BA
These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECC03C4A2A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. For rst open position (Coil Voltage), use the table below. Sufx A B C Coil Voltage 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 Sufx D E H Coil Voltage 600/60 or 550/50 208/60 277/60 or 240/50 Sufx T V X Coil Voltage 24/60 28/60 or 24/50 347/60
Table 37-46. Class ECC04 Non-combination Mechanically Held 2-Wire Control C30CN
Number of Poles Type 1 Catalog Number Type 3R Catalog Number ECC04C2_2A ECC04C2_3A ECC04C2_4A ECC04C2_5A ECC04C2_6A ECC04C2_7A ECC04C2_8A ECC04C2_9A ECC04C2_AA ECC04C2_BA Type 4X Catalog Number ECC04C4_2A ECC04C4_3A ECC04C4_4A ECC04C4_5A ECC04C4_6A ECC04C4_7A ECC04C4_8A ECC04C4_9A ECC04C4_AA ECC04C4_BA Type 7/9 Catalog Number ECC04C6_2A ECC04C6_3A ECC04C6_4A ECC04C6_5A ECC04C6_6A ECC04C6_7A ECC04C6_8A ECC04C6_9A ECC04C6_AA ECC04C6_BA Type 12 Catalog Number ECC04C8_2A ECC04C8_3A ECC04C8_4A ECC04C8_5A ECC04C8_6A ECC04C8_7A ECC04C8_8A ECC04C8_9A ECC04C8_AA ECC04C8_BA Component Contactor (Open) Catalog Number C30CNM20_ C30CNM30_ C30CNM40_ C30CNM50_ C30CNM60_ C30CNM70_ C30CNM80_ C30CNM90_ C30CNM100_ C30CNM120_
Continuous Amps 30
2 3 4 5 6 7 8 9 10 12
ECC04C1_2A ECC04C1_3A ECC04C1_4A ECC04C1_5A ECC04C1_6A ECC04C1_7A ECC04C1_8A ECC04C1_9A ECC04C1_AA ECC04C1_BA
Add C18 Modication Code for 3-wire control. These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECC04C4A2A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5. For rst open position (Coil Voltage), use the table below. Sufx A B C Coil Voltage 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 Sufx D E H Coil Voltage 600/60 or 550/50 208/60 277/60 or 240/50 Sufx T V X Coil Voltage 24/60 28/60 or 24/50 347/60
Note: To get the C30CN Lighting Contactor with normally closed power poles, see Modication Codes.
Accessories . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.eaton.com
37-24
Product Selection
Table 37-47. Class ECL03 Electrically Held CN35
No. of Poles Frame Size Type 1 General Purpose Catalog Number Type 3R Rainproof Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number ECL03A4_2A ECL03A4_3A ECL03A4_4A ECL03A4_5A ECL03A4_6A ECL03A4_9A ECL03A4_AA ECL03A4_BA ECL03A4_CA ECL03B4_2A ECL03B4_3A ECL03B4_4A ECL03B4_5A ECL03B4_6A ECL03B4_9A ECL03B4_AA ECL03B4_BA ECL03B4_CA ECL03C4_2A ECL03C4_3A ECL03C4_4A ECL03C4_5A ECL03C4_6A ECL03C4_9A ECL03C4_AA ECL03C4_BA ECL03C4_CA ECL03D4_2A ECL03D4_3A ECL03D4_4A ECL03D4_5A ECL03D4_6A ECL03D4_9A ECL03D4_AA ECL03D4_BA Type 7/9 Hazardous Location Catalog Number ECL03A6_2A ECL03A6_3A ECL03A6_4A ECL03A6_5A ECL03A6_6A ECL03A6_9A ECL03A6_AA ECL03A6_BA ECL03A6_CA ECL03B6_2A ECL03B6_3A ECL03B6_4A ECL03B6_5A ECL03B6_6A ECL03B6_9A ECL03B6_AA ECL03B6_BA ECL03B6_CA ECL03C6_2A ECL03C6_3A ECL03C6_4A ECL03C6_5A ECL03C6_6A ECL03C6_9A ECL03C6_AA ECL03C6_BA ECL03C6_CA ECL03D6_2A ECL03D6_3A ECL03D6_4A ECL03D6_5A ECL03D6_6A ECL03D6_9A ECL03D6_AA ECL03D6_BA
Type 12 Dust-Tight Industrial Catalog Number ECL03A8_2A ECL03A8_3A ECL03A8_4A ECL03A8_5A ECL03A8_6A ECL03A8_9A ECL03A8_AA ECL03A8_BA ECL03A8_CA ECL03B8_2A ECL03B8_3A ECL03B8_4A ECL03B8_5A ECL03B8_6A ECL03B8_9A ECL03B8_AA ECL03B8_BA ECL03B8_CA ECL03C8_2A ECL03C8_3A ECL03C8_4A ECL03C8_5A ECL03C8_6A ECL03C8_9A ECL03C8_AA ECL03C8_BA ECL03C8_CA ECL03D8_2A ECL03D8_3A ECL03D8_4A ECL03D8_5A ECL03D8_6A ECL03D8_9A ECL03D8_AA ECL03D8_BA
Component Contactor (Open) Catalog Number CN35AN2_B CN35AN3_B CN35AN4_B CN35BN2_B CN35BN3_B CN35BN4_B CN35BN6_B CN35BN9_B CN35BN12_B CN35DN2_B CN35DN3_B CN35DN4_B CN35DN5_B CN35DN6_B CN35DN9_B CN35DN12_B CN35GN2_B CN35GN3_B CN35GN4_B CN35GN5_B
Catalog Number ECL03A2_2A ECL03A2_3A ECL03A2_4A ECL03A2_5A ECL03A2_6A ECL03A2_9A ECL03A2_AA ECL03A2_BA ECL03A2_CA ECL03B2_2A ECL03B2_3A ECL03B2_4A ECL03B2_5A ECL03B2_6A ECL03B2_9A ECL03B2_AA ECL03B2_BA ECL03B2_CA ECL03C2_2A ECL03C2_3A ECL03C2_4A ECL03C2_5A ECL03C2_6A ECL03C2_9A ECL03C2_AA ECL03C2_BA ECL03C2_CA ECL03D2_2A ECL03D2_3A ECL03D2_4A ECL03D2_5A ECL03D2_6A ECL03D2_9A ECL03D2_AA ECL03D2_BA
45 mm
37
45 mm
ECL03A1_2A ECL03A1_3A ECL03A1_4A ECL03A1_5A ECL03A1_6A ECL03A1_9A ECL03A1_AA ECL03A1_BA ECL03A1_CA ECL03B1_2A ECL03B1_3A ECL03B1_4A ECL03B1_5A ECL03B1_6A ECL03B1_9A ECL03B1_AA ECL03B1_BA ECL03B1_CA ECL03C1_2A ECL03C1_3A ECL03C1_4A ECL03C1_5A ECL03C1_6A ECL03C1_9A ECL03C1_AA ECL03C1_BA ECL03C1_CA ECL03D1_2A ECL03D1_3A ECL03D1_4A ECL03D1_5A ECL03D1_6A ECL03D1_9A ECL03D1_AA ECL03D1_BA
45 mm
45 mm
65 mm
Ampere ratings are based on a maximum load voltage of 480V for tungsten lamp applications and 600V for ballast or mercury vapor type applications.
These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECL03B4A2A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
For open position (Coil Voltage), use the table below: Sufx A B C D E H Coil Voltage 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 or 550/50 208/60 277/60
Accessories . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . For more information visit: www.eaton.com
37-25
Type 12 Dust-Tight Industrial Catalog Number ECL03E8_2A ECL03E8_3A ECL03E8_4A ECL03E8_5A ECL03E8_6A ECL03E8_9A ECL03F8_2A ECL03F8_3A ECL03F8_4A ECL03F8_5A ECL03F8_6A ECL03G8_2A ECL03G8_3A ECL03G8_4A ECL03G8_5A ECL03G8_6A ECL03H8_2A ECL03H8_3A
Component Contactor (Open) Catalog Number CN35KN2_ CN35KN3_ CN35NN2_ CN35NN3_ CN35SN2_ CN35SN3_ CN35TN2_ CN35TN3_
Catalog Number ECL03E2_2A ECL03E2_3A ECL03E2_4A ECL03E2_5A ECL03E2_6A ECL03E2_9A ECL03F2_2A ECL03F2_3A ECL03F2_4A ECL03F2_5A ECL03F2_6A ECL03G2_2A ECL03G2_3A ECL03G2_4A ECL03G2_5A ECL03G2_6A ECL03H2_2A ECL03H2_3A
90 mm
ECL03E1_2A ECL03E1_3A ECL03E1_4A ECL03E1_5A ECL03E1_6A ECL03E1_9A ECL03F1_2A ECL03F1_3A ECL03F1_4A ECL03F1_5A ECL03F1_6A ECL03G1_2A ECL03G1_3A ECL03G1_4A ECL03G1_5A ECL03G1_6A ECL03H1_2A ECL03H1_3A
90 mm
37
180 mm
180 mm
Ampere ratings are based on a maximum load voltage of 480V for tungsten lamp applications and 600V for ballast or mercury vapor type applications. UL ballast and resistive ratings only.
These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECL03B4A2A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
For open position (Coil Voltage), use the table below: Sufx A B C D E H Coil Voltage 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 or 550/50 208/60 277/60
Accessories . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . CA08102001E For more information visit: www.eaton.com
37-26
Operation
A permanent magnet is built into the contactor structure that will maintain the contactor in its energized state indenitely without using control power. When energized, a DC current is applied to the latch coil, producing a magnetic eld that reinforces the polarity of the permanent magnet, pulling in the contactor. The current to the coil is disconnected by the coil clearing interlock. In order to drop out the contactor, it is necessary to apply a eld through the STOP coil in the reverse direction to the permanent magnet. This momentarily cancels the magnetic attraction and the contactor drops out.
Product Selection
Table 37-48. Class ECL04 Magnetically Latched A202
No. of Poles Type 1 General Purpose Catalog Number Type 3R Rainproof Type 4X Watertight & Dust-Tight Stainless Steel Catalog Number ECL04C4_2A ECL04C4_3A ECL04C4_4A ECL04C4_5A ECL04C4_6A ECL04C4_8A ECL04C4_9A ECL04C4_AA ECL04C4_BA ECL04C4_CA ECL04D4_2A ECL04D4_3A ECL04D4_4A ECL04D4_5A ECL04D4_6A ECL04D4_8A ECL04D4_9A ECL04D4_AA ECL04D4_BA ECL04D4_CA ECL04E4_2A ECL04E4_3A ECL04E4_4A ECL04E4_5A ECL04E4_6A ECL04E4_8A ECL04E4_9A ECL04E4_AA ECL04E4_BA ECL04E4_CA
37
2 3 4 5 6 8 9 10 12 20 2 3 4 5 6 8 9 10 12 20 2 3 4 5 6 8 9 10 12 20
Type 7/9 Hazardous Location Catalog Number ECL04C6_2A ECL04C6_3A ECL04C6_4A ECL04C6_5A ECL04C6_6A ECL04C6_8A ECL04C6_9A ECL04C6_AA ECL04C6_BA ECL04C6_CA ECL04D6_2A ECL04D6_3A ECL04D6_4A ECL04D6_5A ECL04D6_6A ECL04D6_8A ECL04D6_9A ECL04D6_AA ECL04D6_BA ECL04D6_CA ECL04E6_2A ECL04E6_3A ECL04E6_4A ECL04E6_5A ECL04E6_6A ECL04E6_8A ECL04E6_9A ECL04E6_AA ECL04E6_BA ECL04E6_CA
Type 12 Dust-Tight Industrial Catalog Number ECL04C8_2A ECL04C8_3A ECL04C8_4A ECL04C8_5A ECL04C8_6A ECL04C8_8A ECL04C8_9A ECL04C8_AA ECL04C8_BA ECL04C8_CA ECL04D8_2A ECL04D8_3A ECL04D8_4A ECL04D8_5A ECL04D8_6A ECL04D8_8A ECL04D8_9A ECL04D8_AA ECL04D8_BA ECL04D8_CA ECL04E8_2A ECL04E8_3A ECL04E8_4A ECL04E8_5A ECL04E8_6A ECL04E8_8A ECL04E8_9A ECL04E8_AA ECL04E8_BA ECL04E8_CA
Component Contactor (Open) Catalog Number A202K1B_M A202K1C_M A202K1D_M A202K1E_M A202K1F_M A202K1G_M A202K1H_M A202K1K_M A202K2B_M A202K2C_M A202K2D_M A202K2E_M A202K2F_M A202K2G_M A202K2H_M A202K2K_M A202K3B_M A202K3C_M A202K3D_M A202K3E_M A202K3F_M A202K3G_M A202K3H_M A202K3K_M
Catalog Number ECL04C2_2A ECL04C2_3A ECL04C2_4A ECL04C2_5A ECL04C2_6A ECL04C2_8A ECL04C2_9A ECL04C2_AA ECL04C2_BA ECL04C2_CA ECL04D2_2A ECL04D2_3A ECL04D2_4A ECL04D2_5A ECL04D2_6A ECL04D2_8A ECL04D2_9A ECL04D2_AA ECL04D2_BA ECL04D2_CA ECL04E2_2A ECL04E2_3A ECL04E2_4A ECL04E2_5A ECL04E2_6A ECL04E2_8A ECL04E2_9A ECL04E2_AA ECL04E2_BA ECL04E2_CA
Ampere ratings are based on a maximum load voltage of 480V for tungsten lamp applications and 600V for ballast or mercury vapor type applications.
These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECL04B4A2A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
For open position (Coil Voltage), use the table below: Enclosed Sufx A B C D E H Open Sufx A W X E B Z Coil Voltage 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 208/60 277/60
Accessories . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . For more information visit: www.eaton.com
37-27
Type 7/9 Hazardous Location Catalog Number ECL04F6_2A ECL04F6_3A ECL04F6_4A ECL04F6_5A ECL04F6_6A ECL04F6_8A ECL04F6_9A ECL04F6_AA ECL04F6_BA ECL04F6_CA ECL04G6_2A ECL04G6_3A ECL04G6_4A ECL04G6_5A ECL04G6_6A ECL04H6_2A ECL04H6_3A ECL04H6_4A ECL04H6_5A ECL04H6_6A
Type 12 Dust-Tight Industrial Catalog Number ECL04F8_2A ECL04F8_3A ECL04F8_4A ECL04F8_5A ECL04F8_6A ECL04F8_8A ECL04F8_9A ECL04F8_AA ECL04F8_BA ECL04F8_CA ECL04G8_2A ECL04G8_3A ECL04G8_4A ECL04G8_5A ECL04G8_6A ECL04H8_2A ECL04H8_3A ECL04H8_4A ECL04H8_5A ECL04H8_6A
Component Contactor (Open) Catalog Number A202K4B_M A202K4C_M A202K4D_M A202K4E_M A202K4F_M A202K4G_M A202K4H_M A202K4K_M A202K5B_M A202K5C_M A202K6B_M A202K6C_M
Catalog Number ECL04F2_2A ECL04F2_3A ECL04F2_4A ECL04F2_5A ECL04F2_6A ECL04F2_8A ECL04F2_9A ECL04F2_AA ECL04F2_BA ECL04F2_CA ECL04G2_2A ECL04G2_3A ECL04G2_4A ECL04G2_5A ECL04G2_6A ECL04H2_2A ECL04H2_3A ECL04H2_4A ECL04H2_5A ECL04H2_6A
ECL04F1_2A ECL04F1_3A ECL04F1_4A ECL04F1_5A ECL04F1_6A ECL04F1_8A ECL04F1_9A ECL04F1_AA ECL04F1_BA ECL04F1_CA ECL04G1_2A ECL04G1_3A ECL04G1_4A ECL04G1_5A ECL04G1_6A ECL04H1_2A ECL04H1_3A ECL04H1_4A ECL04H1_5A ECL04H1_6A
37
Ampere ratings are based on a maximum load voltage of 480V for tungsten lamp applications and 600V for ballast or mercury vapor type applications.
These are the Catalog Numbers for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECL04B4A2A. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
For open position (Coil Voltage), use the table below: Enclosed Sufx A B C D E H Open Sufx A W X E B Z Coil Voltage 120/60 or 110/50 240/60 or 220/50 480/60 or 440/50 600/60 208/60 277/60
Accessories . . . . . . . . . . . . . . . . . . . . Cover Control . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . . . . . . CA08102001E For more information visit: www.eaton.com
37-28
Combination
Product Selection
Table 37-49. Combination Fusible
Max. Amp Rating No. of Poles Fuse Clips Amps/Volts Type 1 General Purpose Catalog Number Type 3R Rainproof Catalog Number ECL12C2_3B ECL12C2_3C ECL12D2_3D ECL12D2_3E ECL12E2_3F ECL12E2_3G ECL12F2_3H ECL12F2_3J ECL12G2_3K ECL12G2_3L ECL12H2_3K ECL12H2_3L ECL13C2_3B ECL13C2_3C ECL13D2_3D ECL13D2_3E ECL13E2_3F ECL13E2_3G ECL13F2_3H ECL13F2_3J Type 4X Watertight & Dust-Tight SS Catalog Number ECL12C4_3B ECL12C4_3C ECL12D4_3D ECL12D4_3E ECL12E4_3F ECL12E4_3G ECL12F4_3H ECL12F4_3J ECL12G4_3K ECL12G4_3L ECL12H4_3K ECL12H4_3L ECL13C4_3B ECL13C4_3C ECL13D4_3D ECL13D4_3E ECL13E4_3F ECL13E4_3G ECL13F4_3H ECL13F4_3J
Type 7/9 Hazardous Location Catalog Number ECL12C6_3B ECL12C6_3C ECL12D6_3D ECL12D6_3E ECL12E6_3F ECL12E6_3G ECL12F6_3H ECL12F6_3J ECL12G6_3K ECL12G6_3L ECL12H6_3K ECL12H6_3L ECL13C6_3B ECL13C6_3C ECL13D6_3D ECL13D6_3E ECL13E6_3F ECL13E6_3G ECL13F6_3H ECL13F6_3J
Type 12 Dust-Tight Industrial Catalog Number ECL12C8_3B ECL12C8_3C ECL12D8_3D ECL12D8_3E ECL12E8_3F ECL12E8_3G ECL12F8_3H ECL12F8_3J ECL12G8_3K ECL12G8_3L ECL12H8_3K ECL12H8_3L ECL13C8_3B ECL13C8_3C ECL13D8_3D ECL13D8_3E ECL13E8_3F ECL13E8_3G ECL13F8_3H ECL13F8_3J
Component Contactor (Open) Catalog Number CN35DN3_B CN35GN3_B CN35KN3_ CN35NN3_ CN35SN3_ CN35TN3_
37
3 3 3 3
The listed ampere ratings are based on a maximum load voltage of 480V for tungsten lamp applications and 600V for ballasts or mercury vapor type applications.
The underscore (_) indicates missing Code letter for Coil Selection see Table 37-51. Example: Magnet coils with 120/110V coils change 8th character to A. ECL12C1A3B. Power fuses are not included. Type 7/9 Hazardous Location Catalog Number ECL14C6_3E ECL14D6_3F ECL14E6_3G ECL14F6_3H ECL14G6_3J ECL14H6_3K ECL15C6_3E ECL15D6_3F ECL15E6_3G ECL15F6_3H Type 12 Dust-Tight Industrial Catalog Number ECL14C8_3E ECL14D8_3F ECL14E8_3G ECL14F8_3H ECL14G8_3J ECL14H8_3K ECL15C8_3E ECL15D8_3F ECL15E8_3G ECL15F8_3H Component Contactor (Open) Catalog Number CN35DN3_B CN35GN3_B CN35KN3_ CN35NN3_ CN35SN3_ CN35TN3_ A202K1C_M A202K2C_M A202K3C_M A202K4C_M
The listed ampere ratings are based on a maximum load voltage of 480V for tungsten lamp applications and 600V for ballasts or mercury vapor type applications.
The underscore (_) indicates missing Code letter for Coil Selection see Table 37-51. Example: Magnet coils with 120/110V coils change 8th character to A. ECL12C1A3B.
Note: The Catalog Numbers listed in the Type 4X column are for Type 4X 304-Grade Stainless Steel, as indicated by the seventh digit 4. Example: ECL12C4A3B. To order Type 4X 316-Grade Stainless Steel, change that digit to 9. To order Type 4 Painted Steel, change that digit to 3. To order Nonmetallic, change that digit to 5.
Additional Common Modications are available for outside lighting for ballelds, parks, etc.: E7 Service Entrance E5 Enclosure with pole mounting brackets P70 Photocell T1 T25 Timers See Enclosed Control Product Guide for details on Modication Codes.
For more information visit: www.eaton.com
Accessories Electrically Held . . . . . . . . . . . Mechanically Held . . . . . . . . . Cover Control . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . Modications . . . . . . . . . . . . . . . Discount Symbol . . . . . . . . . . . .
Pages 37-2 37-5 Page 37-20 Page 37-21 PG03300001E PG03300001E 1CD-1C CA08102001E
37-29
Wiring Diagrams
Wiring Diagrams
COMBINATION MOTOR CONTROLLER Connections for Control Stations Local Control Figure A START/STOP Pushbuttons Yel 2/13 Start (On) Blk 3/14 3 4 Stop (Off) Red 1 1 2 Figure B START/STOP Selector Switch Blk 3/14 1 Start (On) 1 Red 2 Figure C 3 Position Selector Switch Yel 3/14 Hand Blk 3 Auto 4 Red 1 Remote Switch To Coil Terminal A1 Remote Control 2 Wire Control 3/14 L2 L3 L4 3 Wire Control Start Stop 3/14 2/13 1 L6 L7 L8 L9 L10 L11 L12 L5 C30CN WIRING DIAGRAM C30CNE Electrically Held Line L1 1 2 3 4 5 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 Load
3 4
37
Figure E Pilot Light (Motor Run) X1 X2 Blk/Wht Connect to Coil Terminals Blk/Wht A1 & A2
When more than one pushbutton station is used, omit connector A and connect per sketch below. Start Stop A Combined Remote and Local (For Figures 1 & 2) Remote Local Start (On) 3/14 2/13 Start 4 3 Stop Stop (Off) 1 2 1 Start Stop 3/14 2/13 1
3 4
T11 6 T12
Figure D 2 Position Selector Switch Yel 3/14 Hand 1 2 Blk 3 Auto 4 Red 1
Figure F STARTSTOP with Pilot Light X1 X2 Start (On) 4 3 Stop (Off) 2 1 Blk/Wht Connect to Coil Terminals Blk/Wht A1 & A2 2/13 3/14 1
Aux. Contacts
Optional Pilot Devices for Electrically Held Contactor *Separate Source 1 Red Off On C Yellow C On R 3 (A1) Black 7 Off G C (A2) X2
Omit Connector
Connections for Starters Figure 2 Fusible Control Transformer Remove wire C (Figure 1) if used and connect as shown below. (All other starter wires remain as shown in Figure 1.) H4 H1 Fuse Fuse CPT 1 Secondary Connections 5 1 3 L3 L1 L2 A1 A2 OL M Primary Connections
D.S. or C.B. Disconnecting Means CPT Fusible Control 1 Transformer L1 (If Used) See Figure 2 1 Omit this connector if Figure 2 Is Used M
X1 XF
Fuse
H2 3 L2 5 L3 C H3 1
ON/OFF Pushbuttons (Momentary) *Separate Source 1 Red 96 Reset 95 Off On On R 3 (A1) Yellow C 7 Off G C (A2) X2
X2 G
A1 A2
OL 2 T1 T1 2
4 T2 T2 4
6 T3 T3 6
2/13
1 L1
ON/OFF Pushbuttons (Maintained) *Separate Source 1 Off Hand Auto Black On R C (A2) Off G X2
T1 T2 T3
Motor
OL 2 T1 T1 T1
Red 4 T2 6 T3 T2 T2
Motor
3 (A1) Yellow C 7
HAND/OFF/AUTO Selector Switch * If common control 1 to L1/X2 to L2. See Pub. 50774 if CPT is required.
SEPARATE CONTROL Remove wire C when it is supplied. Connect separate control lines to #1 terminal on the remote pilot device, and to the #96 terminal on the overload relay.
37-30
Wiring Diagrams
30-200 Amp L04 Contactor 2 12 Pole 1 4 CR If Used CR CR 3 2 K1 K1 OFF Black K1 (+) Red Red AC K1 ON AC White () *A 2 K1 K1 Red K1 OFF Black (+) Red AC K1 ON AC White () Red X2 CPT L1 Fuse L2 (2) L11 X1
37
Red
L12 X2 X2 Ground HOA Selector Switch HAND 4 OFF 1 4 AUTO ON/OFF PB with C20 Mod (10250T Device) OFF ON 1A 1 4 CR 1 Fuse ON/OFF PB with C20 Mod (GK Kit) OFF ON 1A 1 4 ON/OFF PB without C20 Mod OFF ON 3 2 1 Lights OFF K1 G 1 X2 ON K1 1 X2 R No TB with 1 Contactor No C20 X2 2 3 If C20 X2 1 4
*B 2 3 *NOTE: A 1 Contactor B 2 Contactors C 3 Contactors K1 K1 Red Red K1 OFF Black (+) Red AC K1 ON AC White ()
*C
Suitable for use on POWER TERMINATIONS a circuit capable of Use 60/75 C AI/Cu Conductors Only producing not more Torque than 5,000 (33 100A) Contactor Wire Range Size (AWG) (lb - in) or 10,000 (200A) RMS 18 - 20 symmetrical amperes, 30 Amp 14 8 60 Amp 14 4 45 - 50 600 volts maximum. 100 Amp 6 1/0 110 - 130 200 Amp 6 300MCM 275 - 375
CA08102001E
37-31
Wiring Diagrams
L1 CPT Fusible Control Transformer (If Used) See Figure 2 Omit This Connector If Figure 2 Is Used
L2
L3
Primary Connections
H4 4
H1 X1
CPT
Fuse
H2 Fuse
C
XF 1
Secondary Connections
H3
Fuse
1 L1
3 L2
5 L3
1
A1 A2 2/13 3/14 Local Control (Flange-Mounting If Used) See Figures A,B,C, D, E and F
X2
37
1 L1 3 L2 A1 A2 5 L3
G
M
T1 2
T2 4
T3 6
Remove wire C (Figure 1) if used and connect as shown above. (All other starter wires remain as shown in Figure 1).
Fusible Control Transformer Figure 2 Yellow 3/14 Remote Switch
Start (ON)
Hand
4 Red
Black Auto
To Coil Terminal A1
4 1 2
4 1 3-Position Selector Switch Figure C Yellow Hand 3/14 Connect to A1 and A2 Coil Terminals X1 X2 Red Black/White Red
Black Auto
STOP/START with Pilot Light Figure F Remote 2/13 4 Omit Connector 3 Local Start (ON) 3/14
3/14 1 Not for use with auto reset OL relays. 2-Wire Control
When more than one pushbutton station is used, omit connector A and connect per sketch below. Start Start 3/14 2/13 Stop A Stop 1
Start
Stop (OFF) 1 2 1
Stop
Remote Control
37-32
Wiring Diagrams
L1
L2
Remove wire C (Figure 1) if used and connect as shown below. (All other starter wires remain as shown in Figure 1). Primary Connections
H4 4
H1 X1
CPT
Fuse
H2
L2
XF 1 Secondary Connections X2
+ 1 L1 3 L2 5 L3
H3
Local Control (FlangeMounting If Used) See Figures A,B,C, D and E
37
3 2 1
NC 3
NO 2 L2 Control Module M
Fuse
Fuse
L2 Control Module
Black
ON
OFF
White M Red L1 Lines L2 L3 Auxiliary Contact (When Used) Poles to Load Front View Diagram Figure 1 Red 1 Black 3 Start (ON) Connect to Terminals 2 and L2 2 Black/White Auxiliary Contact (When Used) D.S. or C.B. L1 M L2 M L3 Load
1 OFF 1 ON Top 3 NC
X1 X2
Momentary Pushbutton
1 2
3 4
1 START/STOP Selector Switch Figure B X1 Black/White Connect to Terminals 3 and L2 X2 L2 Black/White Pilot Light (ON) Figure C Local Control 3
Black/White Start (ON) Start 4 3 3 Stop 2 2 1 3-Wire Control Remote Control 260887 D4 3
Stop (OFF) 4 3
NOTICE
These les are the same as the last printed version of the catalog dated February 2007. For the most up-to-date information, install the Automatic Tab Updater (ATU) by visiting www.gathermydata.com/install or visit our web site at www.eaton.com/electrical.
Click HERE to Continue