Transformer Stability Test: Differential Relay As Well As REF Relay Stability
Transformer Stability Test: Differential Relay As Well As REF Relay Stability
Transformer Stability Test: Differential Relay As Well As REF Relay Stability
Transformer Details
Rated Power 30 Mva % Impedance 30 mVA base
Vector Group Dyn1 At Tap-1 14.50 %
At Tap-9 14.00 %
Rated Voltage HV 115 Kv At Tap-21 13.80 %
Rated Current HV 150.61 Amp.
CT Ratio HV 400/5 HV Voltage
At Tap-1 126.5 Kv
Rated Voltage LV 13.8 kV At Tap-9 115 kV
Rated Current LV 1255.1 Amp. At Tap-21 97.75 kV
CT Ratio LV 2000/5
Tap-9 is nominal tap of the transformer.
Procedure for Transfer Stability
Differential Relay as well as REF Relay Stability
Apply 3-ph 380 Volts at the Primary side of the Transformer and SHORT all the THREE PHASE LV after
Differential CTs.
Applied Voltage in Primary Side 380 V
Expected HV Side Current = Applied Voltage x HV Current (At Tap-9)
% Impedance x Voltage of the Tap
= 380 x 150.61
0.14 x 115000
= 3.554 Amps.
Expected Secondary Current of High side CT
= 3.554 x 5
400
= 0.044 Amps.
Expected LV sided Current = Applied Voltage x LV Current (At Tap-9)
% Impedence x Voltage of the Tap
= 380 x 1255.1
0.14 x 115000
= 29.62 Amps.
Expected Secondary Current of Low side CT
= 29.62 x 5
2000
= 0.0740 Amps.
Now, for checking of Transformer STABILITY, you have to create a fault on outside of the Differential CTs.
High Side
CTs
Low Side
CTs
HV
Breaker
LV
Breaker
Transforme
r
R
Y
B
Neutral
CT
Create a FAULT here.
After this, measure the current of High Side CTs and Low Side CTs in all the measurable points like FTs,
Ammeter, Diff. Relay, REF Relay etc.
Result,
1. Diff. Relay should not operate.
2. REF Relay should not operate.
Differential as well as REF Sensitivity Test
After this, measure the current of High Side CTs and Low Side CTs in all the measurable points like FTs,
Ammeter, Diff. Relay, REF Relay etc.
Result,
1. Diff. Relay should show Differential Current.
2. REF Relay should show Differential Current.
Same way you have to do for remaining Phases.
High Side
CTs
Low Side
CTs
HV
Breaker
LV
Breaker
Transforme
r
R
Y
B
Neutral
CT
Create a FAULT here.
You can create, 3-ph G fault in pace of doing individual, depends on requirement.
REF Stability
We already checked while doing Transformer Differential Stability, but I am displaying here another way to do
REF stability Phase by Phase.
Result,
1. REF Relay should not operate.
High Side
CTs
Low Side
CTs
HV
Breaker
LV
Breaker
Transforme
r
R
Y
B
Neutral
CT
Create a FAULT here.