Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Alarm Simplex 4010-0001

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Features

Up to 250 addressable TrueAlarm or IDNet points**


Four, 2 A notification appliance circuits (NACs)
with solid state current protection
UL listed to Standard 864
Installation convenience features:
Power-limited design with electronic modules
contained on one-piece chassis
Up-front terminal blocks for wiring access
Compact NEMA 1 rated cabinet is available in beige or
red and can be pre-shipped for early installation
Setup, programming, and maintenance features:
Device level ground fault search, locate and isolate
Auto Program, automatic module and device
programming for general alarm operation
TrueAlarm individual analog sensing with front panel
information and selection access**
Dirty TrueAlarm sensor maintenance alerts, service
and status reports including almost dirty
Default TrueAlarm sensor device type operation
Duplicate address error detection
Front panel or PC programming
TrueAlarm sensor peak value performance report
WALKTEST silent or audible system test

Software verification simulation mode


Supports the following IDNet devices** :
Addressable manual stations
Quad-state zone adapter modules (ZAMs) for initiating
device monitoring
IDNet ground fault/short circuit isolator base for
TrueAlarm sensors
Quad-state line powered individual addressable
modules (IAMs) for initiating device monitoring and
relay control
Avail able option modules include:
Simplex 4120 Network, DACT, or City interface
Equipment for Suppression Release Applications
(refer to data sheet S4010-0003)
RS-232 ports for printers or maintenance terminal
Class A NAC adapter module
Additional power supply
Compatible with Simplex:
TrueAlert Addressable Controllers and NAC power
extenders (IDNet controlled and conventional)
4003 Voice Control Panel
4081 Battery Cabinet with charger for 50 Ah batteries
Simplex WALKTEST systemtest is protected under U.S. patent # 4,725,818.
4010 TrueAlarm Fire Alarm Control Panel
Description
TrueAlarm fire al arm control panels have the ability
to provide location accuracy for monitoring and control.
When equipped with TrueAlarm analog sensing for
smoke and heat detection, the processing power of the
control panel also has the ability to analyze conditions at
each location to provide accurate detection with
significantly reduced maintenance costs.
The Simplex 4010 TrueAlarm Fire Alarm Control Panel
has been specifically designed to provide addressable
operation and analog detection in a cost-effective package
for application sizes that previously were considered only
appropriate for conventional zoned monitoring.
Installation and Service Ease. The 4010 mounts on a
single chassis for quick installation and removal.
Terminal blocks are large and up-front for easy access
and inspection. Optional modules are easily and quickly
installed and programmed as required.
The 4010 cabinet provides convenient stud markers for
drywall thickness and nail-hole knockouts for quicker
mounting. Smooth cabinet surfaces are provided for
locally cutting conduit entrance holes exactly where
required. 4010 cabinets and electronics can be ordered
separately, allowing early cabinet installation.
Ground Fault Assi stance. Ground fault problems
often occur during installation. The 4010 provides
isolating circuitry and software-controlled sequencing to
isolate ground faults to specific identified locations. This
assistance helps the installer to accurately locate the
wiring problem for quicker repair.
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFMListing
7170-0026:226 for allowable values and/or conditions concerning material presented in this
document. It is subject to re-examination, revision, and possible cancellation. Accepted for
use City of NewYork Department of Buildings MEA35-93E. Additional listings may be
applicable, contact Simplex for the latest status.
** Simplex TrueAlarmanalog smoke detection and IDNet addressable devices are
protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683; 5,543,777;
5,400,014; 5,552,765; 5,552,763; DES. 377,460.
TrueAlarm

Fire Alarm Controls


UL, ULC Listed; FM, CSFM, and Model 4010 Fire Alarm Control Panel for
NYC, MEA Approved* TrueAlarm

Analog Sensors and IDNet Addressable Devices


2000 Simplex Time Recorder Co. All rights reserved. S4010-0001-4 4/00
4010 Operator Control Summary
Extensive Feature List. The Simplex 4010 Fire Alarm
Control Panel provides access to an extensive feature list
that includes:
Providing easy and powerful operator information with
a logical, menu-driven display
Extensive and automatic diagnostics for maintenance
reduction
History Logs available from the LCD or capable of
(optionally) being printed
Software Verification, allowing detailed logic
programming simulation to be conducted without
activating connected outputs
Control Panel (or service PC) label editing
Password access control
Auto Program Quick Configuration (Quick-CFIG) of
connected modules and IDNet devices for general alarm
operation to quickly get the system up and running
4010 Display Panel and Diagnostic Mode
Convenient Status Information. With the locking
door closed, a window allows viewing of the status
display. The 4010 status panel provides a two line by 40
character, super-twist LCD information display and eight
status LED indicators as shown in the illustration below.
From this display, the LED indicators will describe the
general category of activity being displayed with the LCD
providing more detail. For the authorized user, unlocking
the door will provide access to the control switches and
allow further inquiry by scrolling the display for
additional detail. (Refer to control panel functional
illustration below.)
WALKTEST Diagnostic Operation Mode. The
patented Simplex WALKTEST process allows a single
person to perform system test. The system records test
inputs such as intentional alarms or trouble and either logs
the response (silent WALKTEST operation) or outputs a
brief, recognizable audible notification signal (audible
WALKTEST operation).
Simplex Time Recorder Co. 2 S4010-0001-4 4/00
** SYSTEM IS NORMAL **
12:02:15pm Mon 6-Mar-00
SUPV
ACK
SYSTEM
SUPERVISORY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENCED
SYSTEM
RESET
AC
POWER
MENU FUNCTION ENTER
DISABLE
ENABLE
EXIT
CLEAR
PREVIOUS
NEXT
CONTROL
PANEL VIEW
with 4010 door
closed
2X 40LCDREADOUT, LED backlighted during normal
conditions and abnormal operating conditions, provides
up to 40 characters for custom label information
THREE PROGRAMMABLE LEDs
provide customlabeling (labels insert
into a pocket), the top two LEDs are
selectable as red or yellow, the bottom
LED is selectable as green or yellow
SYSTEMRESET restores
control panel to normal when
all alarmed inputs are
returned to normal
ALARMACK acknowledges a Fire Alarm condition,
logs the acknowledge and silences the operator
panel and all annunciator tone-alerts
SUP ACK acknowledges system supervisory
conditions, logs the acknowledge, and silences the
operator panel and all annunciator tone-alerts
ALARMSILENCE causes audible notification appliances
to be silenced, used after evacuation is complete and
while alarm source is being investigated
TROUBLE ACK acknowledges systemtroubles,
logs the acknowledge, and silences the operator
panel and all annunciator tone-alerts
FIVE STATUS INDICATOR LEDs provide system status indications in
addition to LCD information, LEDs flash to indicate the condition and
then when acknowledged, remain on until reset
NINE EXTENDEDFUNCTIONKEYS(accessible with
door open) select and scroll through display prompts for
locating additional system information, performing
maintenance functions, or for front panel programming
Extended Operator Control Panel Functions
IDNet Addressable Interface
Overview. The 4010 provides IDNet addressable device
communications. Using a two wire circuit, individual
devices such as manual fire alarm stations, TrueAlarm
sensors, and sprinkler waterflow switches can be directly
connected (or interfaced) to the IDNet controller to
communicate their identity and status. This addressability
allows the location and condition of the connected device
to be displayed on the 4010 panel LCD and on system
annunciators. Additionally, control circuits (fans,
dampers, etc.) may be individually controlled by using a
relay IAM (individual addressable module). The 4009
IDNet NAC Extender or the TrueAlert Addressable
controller can be controlled for local or remote
notification appliance expansion. (Refer to individual
device documentation for further details.)
Capacity. A total of 250 addressable monitor and control
points may be intermixed on the same pair of wires. By
using Zone Adaptor Modules (ZAMs) or Individual
Addressable Modules (IAMs), conventional initiating
devices can be connected to the IDNet circuit.
IDNet Addressable Operation. The IDNet controller
continuously interrogates each addressable device on the
communication channel for status condition such as:
normal, off-normal, alarm, supervisory, or trouble.
Sophisticated poll and response communication
techniques ensure supervision integrity and allow for
"T-tapping" of the circuit for Class B (Style 4) operation.
Wiring. Up to 10,000 total feet (3048 m) of twisted,
shielded 18 AWG wire may be connected to the IDNet
channel. The distance from the panel to the farthest device
may be up to 2500 feet (762 m). Unshielded wire may be
used in certain retrofit applications. IDNet wiring can be
either Class B (Style 4) or Class A (Style 6) depending on
the system requirements.
TrueAlarm Analog Sensors
TrueAlarm System Operation. IDNet
communications are used for TrueAlarm smoke and
temperature sensors. Every four seconds, smoke sensors
transmit an output value based on their smoke chamber
condition. The 4010 CPU maintains a current value, peak
value, and an average value of each sensor's output. Status
is determined by comparing the current sensor value to its
average value. Tracking this average value as a
continuously shifting reference point filters out
environmental factors that cause shifts in sensitivity.
Programmabl e Sensitivity. The sensitivity of each
sensor can be field programmed at the 4010 Control Panel
for different levels of smoke obscuration (in percent) or
for specific heat detection levels. In order to evaluate
whether the sensitivity should be revised, the peak value
is stored in memory and can be easily read and compared
to the alarm threshold directly in percent.
TrueAlarm heat sensors can be selected for
rate-of-rise detection as either 15 F (8.3 C) or 20 F
(11.1 C) per minute with an independent fixed limit of
135 F (57 C) or 155 F (68 C). TrueAlarm heat sensors
can also be programmed as a utility device to monitor for
temperature extremes in the range from 32 F to 155 F
(0 C to 68 C). This feature can provide freeze warnings
or alert to HVAC system problems.
ALARM FIRE
PULL DOWN
SI MPL EX TIME REC ORDER CO. 4090-9002 R ELAY IAM INST AL. INSTR. 574-184 DATE CODE:
1
5
6
7
8
1
2
3
4
Addressable station
Monitor ZAMs and
Relay IAMs
Supervised IAM
Quick-Connect
TrueAlarm sensor
Modular TrueAlarm
sensor with base
Modular TrueAlarm sensor
with IDNet isolator base
To additional IDNet
devices, up to 250 total
POWER B EF OR E SERVI CI NG
CAUTION D ISCO NNECT
4009 IDNet NAC EXTENDER
TM
4009 IDNet NAC
Extender
TrueAlert Addressable Controller
POWER BEF ORE SERVICING
CAUTION DISCONNECT
TrueAlert AddressableController
TM
FIRE ALARM
CONTROL
DISCONNECT POWERBEFORE SERVICING
CAUTION
** SYSTEM IS NORMAL **
12:02:15pm Mon 8-Mar-99
SUPV ACK
SYSTEM SUPERVISORY
AL ARM ACK
FI RE AL ARM
TROUBLE ACK
SYSTEM TROUBL E
ALARM SI LENCE
ALARM SILENCED
SYSTEM RESET
AC POWER
4010 Control Panel with Typical IDNet Devices
Diagnostics and Default Device Type
TrueAlarm operation gives the 4010 system the ability to
automatically indicate when a sensor is almost dirty, dirty,
and excessively dirty. The NFPA 72 (National Fire Alarm
Code) requirement for a test of the sensitivity range of the
sensors is fulfilled by the TrueAlarm ability to maintain
the sensitivity level of each sensor.
Modular TrueAlarm sensors use the same base and
different sensor types (photoelectric smoke sensor, or heat
sensor) can be easily interchanged to meet specific
location requirements. This feature also allows intentional
sensor substitution during building construction. When
conditions are temporarily dusty, instead of covering the
smoke sensors (causing them to be disabled), heat sensors
may be installed without reprogramming the control
panel. Although the control panel will indicate an
incorrect sensor type, the heat sensor will operate at a
default sensitivity to provide heat detection for building
protection at that location.
Simplex Time Recorder Co. 3 S4010-0001-4 4/00
TrueAlarm Information Details
True Alarm sensor data can be displayed on the
system LCD, on a remote maintenance terminal, or
printed on a remote printer. With the proper operator
access, a TrueAlarm Service Report can be generated to
list the specific details of each TrueAlarm device. This
report, as well as the Status Report can either be displayed
on the remote maintenance terminal or captured
permanently by using a remote 80 character printer.
The figures below illustrate the format provided on either
the remote maintenance terminal or a printer. This
information is available at the system LCD by identifying
the specific point of interest and reading one point at a
time.
Compatible RS-232 devices include the Simplex model
4190-9006 Terminal and the Simplex model 4190-9007,
80 column, 24 pin dot matrix printer. (The 2190-9039,
24 VDC, 40 column printer is compatible with the 4010
for event printing only.)
(Contact Simplex for information on the complete line of
TrueAlarm analog sensing products.)
Remote Maintenance
Terminal (Simplex
model 4190-9006)
4010 Fire Alarm
Control Panel
RS-232 connections, one per device
Remote Printer
(Simplex model 4190-9007)
TIME: 1:56:10 custom title USER: 1
DATE: WED 9 OCT 96 Port 1 Card 5 A ACCESS: 1
ALARMS: 2 TROUBLES: 0 SUPERVISORIES: 0
1:42:05 PM WED 9 OCT 96 1ST FLOOR EAST WING
SMOKE DETECTOR ALARM
1:55:16 PM WED 9 OCT 96 1ST FLOOR EAST WING
PULL STATION ALARM
PF1= Ack, PF2= Silence, PF3= System Reset, PF4= Login>
FIRE ALARM CONTROL
DI SCONNECT POWERBEFORE SERVICING
CAUTION
** SYSTEM IS NORMAL **
12:02:15pm Mon 8-Mar-99
SUPV ACK
S YS TE M SUPE RVISORY
ALARM ACK
FIRE ALARM
TROUBLE ACK
S YS TE M T ROUBLE
ALARM S ILENCE
ALARM SILE NCED
S YS TE M RE SE T
AC POWE R
4010 Fire Alarm Control Panel
RS-232 Connection Options
Simplex Time Recorder Co. 4 S4010-0001-4 4/00
Simplex 4010 Fire Alarm System Page 1
REPORT 4 : TrueAlarm Service Report 2:56:09 pm Mon 6-Mar-00
Dev
Num Custom Label
Alarm
at:
Avg
val
Current/
% alarm
Peak/
% alarm
State
1 ANALOG PHOTO - CLEAN ROOM 0.5/ 83 67 68/ 1% 72/ 10% NOR
2 ANALOG ION - CLEAN ROOM 1.3/209 94 97/ 2% 101/ 1% NOR
3 ANALOG PHOTO - MAIN LOBBY 2.5/185 117 117/ 0% 125/ 42% NOR
4 ANALOG PHOTO - CONFERENCE ROOM 1 2.5/161 93 93/ 0% 93/ 0% NOR
10 HEAT DETECTOR - GARAGE 135F/253 -- 63/-67F 66/ 69F NOR
11 ANALOG PHOTO - KITCHEN 3.7/216 116 116/ 1% 110/ 36% NOR
END OF REPORT
Typical TrueAlarm Service Report Information Printout and/or Maintenance Terminal Screen
Simplex 4010 Fire Alarm System Page 1
REPORT 3 : TrueAlarm Status Report 2:43:03 pm Mon 6-Mar-00
Zone
Name Custom Label
Sensi-
tivity Device Status
Almost
Dirty
M1-1 ANALOG PHOTO CLEAN ROOM 0.5 % NORMAL
M1-2 ANALOG ION CLEAN ROOM 1.3 % NORMAL
M1-3 ANALOG PHOTO MAIN LOBBY 2.5 % NORMAL *YES*
M1-4 ANALOG PHOTO CONFERENCE ROOM 1 2.5 % NORMAL
M1-10 HEAT DETECTOR GARAGE 135 F NORMAL
M1-11 ANALOG PHOTO KITCHEN 3.7 % NORMAL *YES*
END OF REPORT
Typical TrueAlarm Status Report Information Printout and/or Maintenance Terminal Screen
TrueAlarm Status and Service Report Samples
Standard Panel Features
N2 Communications for Serial Annunciator
Control. Control for up to 6 remote Simplex
Annunciator products including 24 Point I/O Module, and
LCD Annunciator. Includes extensive troubleshooting
diagnostics.
Access Port. RS-232 service port for connecting PC
tools for service diagnostics and for programming the
CPU Flash EPROM memory.
IDNet Addressable Communi cations Channel.
Addressable channel provides communications for up to
250 remote addressable devices, including TrueAlarm
analog sensors and isolator bases (see descriptions on
page 3).
Four NACs. Class B output is standard, rated for 2 A @
24 VDC nominal, with solid state current protection.
Class A operation is optional with the addition of an
adapter module.
NAC operation can be selected for on-until-Silence or
on-until-Reset, and can be Temporal pattern, 60 or
120 bpm March Time pattern, or continuous. Each NAC
is also individually selectable to control Simplex
synchronized visible notification appliances and to control
audible notification appliances using SmartSync
control, allowing separate audible and visible appliance
operation using a common 2-wire circuit. (Contact
Simplex for more information.)
Two Auxi liary Output Circuits. Operation is
programmable for trouble, alarm, supervisory, or other
fire response functions. Output is one form C dry
contact each, rated 2 A @ 24 VDC. An optional relay kit
is available for switching up to 1/2 A at 120 VAC.
Power Suppl y. Standard output is 4 A @ 28 VDC,
filtered, non-regulated. Internal system power is provided
separately, allowing the 4 A to be available for NAC and
auxiliary power tap functions. Over-current protection is
solid state and self-resetting.
Auxiliary Power Tap. Provides up to 1/2 A of the
standard power supply voltage, over-current protected.
Battery Charger. Capable of charging up to 25 Ah
sealed lead-acid batteries (4010 cabinet mounted). A
recharge time of 24 hours is typical with stable 120 VAC
input. For applications requiring larger batteries, external
charger/cabinet assemblies are available.
A depleted battery cutout feature is front panel selectable
to advise and/or to reduce current when battery voltage is
low.
Optional Expansion Slot Modules
(The 4010 is available with a Simplex 4120 Network
Interface. 4010 points can be declared public.)
4120 Network Interface, Fi xed Media. Available for
wired applications.
4120 Network Interface, Modular Media. Available
for wired connections or fiber optic. Require separate
media modules. May be both wired, both fiber optic, or
one of each.
DACT, Point Reporting Module. Provides serial
output information that can send location details to a
remote receiving station.
DACT, Event Reporting Module. For applications
where simple event status information is required (Alarm,
Trouble, Supervisory, and AC power failure).
Dual RS-232 Module. Available for interfacing to
printers or a maintenance terminal.
Single RS-232 Module with Service Modem
Connection. Provides one port dedicated for connection
to a printer, and a second port dedicated for dial-in from a
service terminal, typically located off-site. With an off-
site terminal, programming changes and system
diagnostics can be performed remotely, reducing service
time for repair or reprogram. Security is maintained by
password protection.
Optional Chassis Mount Modules
Standard 4 A Expansion Module. Provides two taps
of 2 A each, 28 VDC, filtered, non-regulated, similar to
the standard power supply capacity.
Suppression Release Power Suppl y. This module
provides two taps of 2 A each, regulated at 24 VDC
10%. Also included is a suppression release appliqu.
(This module may also be used for other applications
requiring regulated voltage.)
Battery Meter Module. Provides ammeter and
voltmeter for power supply monitoring.
Dual Circuit Class A NAC Adapter Module. Mounts
on the main 4010 printed circuit assembly and provides
the additional circuitry needed for Class A operation.
Dual Ci rcuit City Connect Module. Provides the
interface required for direct wired reporting to
conventional city connection circuits. (Available with or
without disconnect switches.)
Expansion Power Di stribution Module. This
module provides two additional termination points for the
1/2 A auxiliary power output, or for one tap of the
expansion power supply.
External N2 Communications Modules
Up to six modules may be connected to the Simplex N2
serial communications bus.
4606-9101 LCD Annunci ators provide remote
acknowledge, reset, and alphanumeric status display.
(Refer to data sheet S4606-0001.)
4605 Series 24 Point I/O Modules are available for
remote mounting and provide 24 points that can be
programmed as either general purpose switch inputs or
system controlled outputs. Typical applications are for
remote annunciators and monitoring and control of other
related processes. (Refer to data sheet S4010-0002.)
Simplex Time Recorder Co. 5 S4010-0001-4 4/00
Simplex Time Recorder Co. 6 S4010-0001-4 4/00
Input Power Requirements Voltage Range Frequency Maximum Current
AC Input, 120 VAC base models 102 to 132 VAC 60 Hz 2 A
AC Input, 240 VAC base models 204 to 264 VAC 50/60 Hz 1 A
AC Input with 120 VAC expansion power supply 102 to 132 VAC 60 Hz 4 A
AC Input with 240 VAC expansion power supply 204 to 264 VAC 50/60 Hz 2 A
Environmental
Operating Temperature Range 32 to 120F (0 to 49 C)
Operating Humidity Range up to 93% RH, non-condensing @ 100.4 F (38 C) maximum
Output Ratings
Standard Power Supply Output 4 A total @ nominal 28 VDC
Auxiliary Power Tap
1/2 A maximum of standard power
supply voltage
Expansion Power Supply Output * Additional 4 A @ nominal 28 VDC
Suppression Release Power Supply Output * Additional 4 A @ 24 VDC 10%
Output switches to battery
backup during mains failure
or brownout conditions
* Each power supply provides two output taps of 2 A each.
Current Ratings for Optional Modules and Remote LCD Annunci ator
Model Module
Supervisory
Current
Alarm
Current
4010-9810 DACT (Common Event Reporting) 40 mA 40 mA
4010-9816 DACT (Point Reporting) 40 mA 40 mA
4010-9821 4120 Network, wired communications 125 mA 125 mA
4010-9817 4120 Network Modular, add media cards separately 24 mA 24 mA
4010-9818 4120 Network Wired Media 47 mA 47 mA
4010-9819 4120 Network Fiber Optic Media 36 mA 36 mA
4010-9811 Dual RS-232 75 mA 75 mA
4010-9812 Single RS-232 with Service Modem 100 mA 100 mA
4010-9806 Dual Class A NAC Adapter 0 mA 0 mA
4010-9809 Dual Circuit City Connect 20 mA 36 mA
4010-9829 Dual Circuit City Connect w/o disconnect switches 20 mA 36 mA
4606-9101 Remote LCD Annunciator (refer to data sheet S4606-0001) 65 mA 140 mA
System Current (supplied separate from power supply output)
Base System with:
Supervisory
Current**
Alarm
Current**
no IDNet devices 195 mA 295 mA
50 IDNet devices 230 mA 330 mA
100 IDNet devices 265 mA 365 mA
150 IDNet devices 300 mA 400 mA
200 IDNet devices 335 mA 435 mA
250 IDNet devices 370 mA 470 mA
** Current Calculation Information:
1. To determine total supervisory current, add currents of modules in panel to base system value and all auxiliary loads.
2. To determine total alarm current, add currents of modules in panel to base system alarm current and add all panel NAC
loads and all auxiliary loads.
4010 Operating Specifications
Simplex Time Recorder Co. 7 S4010-0001-4 4/00
Category Model* Description Voltage Color
4010-9101 Beige
4010-9102
120 VAC
Red
4010-9201 Beige
4010-9202
4010 Fire Alarm Control Panel with: door,
cabinet, power supply/battery charger, IDNet
interface, 4 NACs, 2 auxiliary relays, and external
N2 communications interface 240 VAC
Red
Control Panel
Assembl y
(select one)
4010-9150
4010 Fire Alarm Control Panel electronics onl y,
for pre-shipped cabinets, requires door
120 VAC NA
Optional Expansion Slot Features (two slots are available, select modules as required)
Category Model Description
4010-9810 DACT Module (Common Event Reporting)
4010-9816 DACT Module (Point Reporting)
Includes two, 7 ft long RJ 45 cables
4010-9821 4120 Network Interface Module with fixed, wired connections
Reporting and
Network
Modules
(select one)
4010-9817 4120 Network Interface Module, Modular, requires 2 media modules
4010-9811 Dual RS-232 Interface Module
RS-232
Communications
(select one)
4010-9812 Single RS-232 Interface Module with Service Modem connection
4010-9818 4120 Network Wired Media Module
Media Modules
(select 2 if using
4010-9817) 4010-9819 4120 Network Fiber Optic Media Module
Media modules mount on the 4010-9817
module without impact to slot allocation
space.
Chassis Mounted Expansion Modules (select as required)
Category Model Description
4010-9813 120 VAC input
4010-9823
4 A Expansion Power Supply
240 VAC input
4010-9814 120 VAC input
Additional
Power Suppl y
(select one)
4010-9824
Suppression Release Power Supply, 4 A @ 24 VDC,
regulated 10%, includes front panel suppression system appliqu
240 VAC input
4010-9820 Battery Meter Module, Ammeter and Voltmeter
Optional
Features
(select one)
4010-9825
24 VDC Expansion Power Distribution Module, provides two additional termination points
for an expansion power supply tap or the auxiliary power output
4010-9806 Dual Circuit Class A (Style Z) NAC Adapter Module, 2 maximum
4010-9809 Dual Circuit City Connect Module
Optional
Features
4010-9829 Dual Circuit City Connect Module w/o disconnect switches
select 1 maximum
Accessories (select as required)
Category Model Description
4010-9826
120 VAC Auxiliary Relay Kit, allows one auxiliary relay to control up to 1/2 A @120 VAC,
select as required, 2 maximum
2975-9801 Semi-flush trim, beige, 1 7/16 (37 mm) wide
Optional
Features
2975-9802 Semi-flush trim, red, 1 7/16 (37 mm) wide
2081-9272 6.2 Ah Battery, 12 VDC, 2 required
2081-9274 10 Ah Battery, 12 VDC, 2 required
2081-9288 12.7 Ah Battery, 12 VDC, 2 required
2081-9275 18 Ah Battery, 12 VDC, 2 required, Note: use will not allow bottom entry conduit
Batteries
(required if
batteries are
internal, select
one size)
2081-9287 25 Ah Battery, 12 VDC, 2 required
2975-9215 Red Cabinet
Cabinets
(select one if
pre-shipped)
2975-9214 Beige Cabinet
Dimensions: 22 H x 18 W x 5 3/8 D
(559 mm x 457 mm x 137 mm)
4010-9858 Red Door
Doors
(select one if
pre-shipped) 4010-9857 Beige Door
Dimensions: 22 H x 18 W x 7/8 D
(559 mm x 457 mm x 22 mm)
* ULC listed models are designated by a C or CF suffix such as 4010-9010C or 4010-9101CF. CF indicates French labels. Contact your
local Simplex representative for details.
4010 Fire Alarm Control Selection Chart and Module Location Rules (refer to diagrams on next page)
Simplex, the Simplex logo, TrueAlarm, WALKTEST, IDNet, SmartSync, and TrueAlert are either trademarks or registered trademarks of Simplex Time Recorder Co. in the U.S.
and/or other countries. NFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection Association (NFPA).
S4010-0001-4 4/00
Westminster, Massachusetts 01441-0001 USA
visit us on the world wide web at www.simplexnet.com
All specifications and other information shown were current as of printing and are subject to change without notice.
4010-9806
Class A
Module
4010-9806
Class A
Module
TB4 TB3
P2
TB1
NAC 1 NAC 2 NAC 3 NAC 4
S
H
L
D
S
H
L
D
EXT N2 IDNet
A
+
A
-
B
+
B
-
NC C NO
AUX2 AUX1 BATTERY AUX
POWER
NC C NO
4010-9813,
4098-9814
4010-9823,
or 4010-9824
Expansion Power Supply
4010-9809
or -9829
City Module
4010-9820
Meter Module
or
4010-9825
24 VDC Power
Distribution
Block
TB5 TB6 TB7 TB8
SUPV
ACK
SYSTEM
SUPERVISORY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENCED
SYSTEM
RESET
AC
POWER
MENU FUNCTION ENTER
DISABLE
ENABLE
EXIT
CLEAR
PREVIOUS NEXT
Expansion
Slots 1 & 2


Typical conduit entry area
(cut holes as required)
Knockout
screw/nail holes
(for semi-flush
mount)
Wall thickness guides
for 5/8" (16 mm)
wall board)
Wall thickness guides
for 1/2" (13 mm)
wall board
Door, 5/8"
(16 mm) thick
Battery Area
No conduit entry or wiring in this area
6 1/4"
(159 mm)
5 1/2"
(140 mm)
18" (457 mm)
21"
(533 mm)
14 1/2" (368 mm)
3/4"
(19 mm)
WATERFLOW-
LEFT WING
GROUND FAULT
WATERFLOW-
RIGHT WING
SUPV
ACK
SYSTEM
SUPERVISORY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENCED
SYSTEM
RESET
AC
POWER
MENU FUNCTION ENTER DISABLE
ENABLE
EXIT
CLEAR PREVIOUS NEXT
TB4 TB3
P2 TB1
TB5 TB6 TB7 TB8
Door and exposed
cabinet dimension
for semi-flush mount
1 3/8" (35 mm)
Wall board position
reference for
semi-flush mount
Shaded area is for non-power limited wiring
Internal straps are
provided for wiring
management
(2 each side)
4010 Module Layout Reference
Mounting Information

You might also like