Cerberus-PRO Data Sheet
Cerberus-PRO Data Sheet
Cerberus-PRO Data Sheet
Product Overview
The Cerberus PRO Intelligent Voice Communication from Used in conjunction with Models FV922 / FV924 is a new,
Siemens − Fire Safety is a technologically advanced, addressable innovative series of audible (sounder) bases. For example,
fire-with-voice system. Through the use of its unique Model ABHW-4B is the first base of its kind to attain agencies’
multiprocessor `Network’ design – along with its ability to utilize approval for its option to power directly from a signal line
intelligent detection devices – Cerberus PRO epitomizes a flexible circuit (SLC) in a two-wire configuration ― when used with
and highly configurable fire-protection system with integrated Cerberus PRO intelligent detectors.
voice evacuation. Designed for sleeping areas, Model ABHW-4S generates a 520
Cerberus PRO voice panels are ideally suited for small and mid- Hz, square-wave audio signal that complies with NFPA 72
market applications via each panel’s capability to provide up to Standard, as well as Underwriters’ Laboratories applications.
252 (Model FV922) and 504 (Model FV924) addressable, Additionally, the Cerberus PRO Advanced and Standard line of
networkable points. intelligent detectors presents distinctive features and cost-
Each Cerberus PRO fire-protection system with voice capability is efficient solutions that offer superior detection found in an
easily accessible for operation: push-button soft keys; a backlit array of Siemens system applications.
LCD screen, and a (4) four-way navigation push button are all Characteristics related with the Advanced and Standard line
located in the upper portion on the panel’s front end. include High Sensitivity with Very Early Warning Fire Detection
Cerberus PRO IVC panels are UL 864 9th Edition, UL1711, (VEWFD); Carbon Monoxide (CO) Gas Detection, and seven (7)
UL2017 & UL2572 Listed; ULC-S527& ULC-S559 Listed. field-adjustable heat-detection temperature settings.
BATTERY
MI CROPHONE
Inside a typical FI XI NG
BRACKET
OPTI ON MODULE
Model VTO2004-U3
Cerberus PRO
Intelligent Voice
Communication
System
300W
SOLI D-BLACK, INNER-DOOR PWR. SUPPLY
BLANK PLATE Model FP2012-U1
Model FHD2005-U1
s I ndustry, Inc.
–2– Cerberus PRO
Building Technologies Division
Main System Components Periphery Boards − (continued)
The periphery boards mount directly on the enclosure back
boxes of the Model FV922 and Model FV924 Cerberus PRO
panels. Models FCI2016-U1/ FCI2017-U1 provide two (2)
parallel auxiliary powered, short-circuit-protected connections
(regulated 24VDC, 1.5A max) that supply power to external
Standard Operating Unit Operating Unit with LEDs
devices or modules.
Operating Interface Unit
The Operating Interface Unit functions as the operator
interface and central microprocessor for the Fire Terminal
(Model FT924) and Cerberus PRO FACPs (Models FV922
and FV924). 300-Watt Power Supply
[Model FP2012-U1]
Model FCM2018-U3 the Standard Operating Unit, or
Model FCM2019-U3 – the Operating Interface Unit with Power Supply Module
LEDs each provides multi-use capabilities: The 300-Watt power supply (Model FP2012-U1) provides
Easily ‘Acknowledge’ events primary, regulated (24VDC, nominal) power for normal
Quickly control the notification-appliance circuits operation to the Cerberus PRO 252 / 504-point addressable
(NACs) of the corresponding FACP systems. Filtered and regulated, Model FP2012-U1 is rated
Permit a manual reset of the respective system
11.5 Amps at 24VDC, nominal.
Detailed information about the nature and location of the events
Each 300-Watt power supply incorporates two (2) 6.3A
are displayed via a 2”─x─ 4-3/4” (5.1 cm. ─x─ 12.1 cm.), backlit
replaceable, non-resettable slow-blow fuses on the primary
liquid-crystal-display (LCD) screen.
input and includes a built-in AC-line filter for surge and noise
Each Operating Interface Unit contains the site-specific program suppression. Model FP2012-U1 mounts into the Model
configuration created in the custom-configuration software tool, FHB2005-U1 / R1 backbox.
`Cerberus Works’.
For applications requiring greater than 300W of power, the
The controller in each interface module provides all system logic Model FP2013-U1 power supply can optionally power a Model
and supervision. Additionally, the Operating Interface Units FV922 or FV924 voice system.
allow for connection to the Remote Peripheral Module (Model
Model FP2013-U1 consists of two (2) power supply units and
FCA2018-U1) and / or the Remote Terminal Displays (Models
one (1) interconnection cable, in order to balance the power
FT2014-U3 / R3; FT2015-U3 / R3).
from Model FP2013-U1. Consequently, this power-supply
Note: For applications in Canada that require the use
of a Cerberus PRO operating unit with LEDs, configuration can provide up to 600W at 24VDC. Mounting
Model FCM2035-U3 must be ordered. for Model FP2013-U1 is provided on the back surface inside
each FACP’s 3HU backbox, Model FHB2005-U1.
FCI2016-U1 FCI2017-U1
[Periphery board for 252-point [Periphery board for 504-point
Cerberus PRO voice system] Cerberus PRO voice system]
Periphery Boards
The periphery boards (Models FCI2016-U1 and FCI2017-
U1) are integral components for operating the Cerberus Voice System Card Cage
PRO panels (Models FV922 and FV924). Each module [Model VCA2002-A1]
operates and monitors input-device identity; as well as Voice System Card Cage
controls the signaling-line circuits that communicate with
The voice-system card cage (Model VCA2002-A1) is used
smoke detectors and other field devices (i.e. ─ C-NET).
to support the mounting and field wiring for the following
Each periphery board is equipped with two (2) cards used on a Model FV922 / FV924 panel:
programmable ‘Class B’ (Style Y) or ‘one (1) Class A’ (Style the Voice CPU Card, Model VCC2001-A1
Z) NAC, providing 24VDC, nominal at a 5A per circuit [supports one (1) CPU card]
maximum of audible / visual notification appliances. the Voice I/O Card, Model VCC2002-A1
[supports one (1) I/O Card]
25V / 70V Voice Amplifier Card, Model VCI2001-U1
[supports one (1) to four (4) 50W amplifier cards]
Up to six (6) card-cage slots are configured for use.
s I ndustry, Inc.
–3– Cerberus PRO
Building Technologies Division
Voice System Components − (continued)
Up to four (4) Model VCI2001-U1 amplifiers are supported in
a 3-to1 backup, or 1-to-1 backup schematic on a single
Cerberus PRO intelligent voice-communication system:
configured as one (1), two (2) or three (3) main amplifiers,
and one (1) or two (2) optional backup amplifiers. Amplifiers
are mounted in the Model VCA2002-A1 card cage.
s I ndustry, Inc.
–4– Cerberus PRO
Building Technologies Division
Voice System Components − (continued) Battery Fixing Bracket
The battery fixing bracket (Model FHA2044-U1) is specifically
used in all Cerberus PRO IVC system configurations ― housing
and securing 33AH system battery sets, which provide auxiliary
system power. Model FHA2044-U1 bracket complies with
seismic certification.
Model EBA2004-A1 consists of a single board with two (2) Approximate size: 42" (106.7 cm.) high;
50W amplifiers, one (1) built-in battery charger, and 21" (53.3 cm.) wide,
removable terminal blocks for all field wiring. and 7.75" (19.7 cm.) deep.
Model FH2016-U1/R1 is the enclosure used to
house the 100W Booster Amplifier.
Approximate size: 23.6" (60 cm.) high;
18.1" (46 cm.) wide,
and 5.1" (13 cm.) deep.
s I ndustry, Inc.
–5– Cerberus PRO
Building Technologies Division
Voice System Components − (continued) Three-Height-Unit Blank Plate
Three-Height-Unit Backbox Instead of using a Lexan clear lens,
an installer has the option of using a
The three-height-unit backbox is part of the Cerberus PRO
3HU blank plate, Model FHD2009-
intelligent voice-communication system hardware for use
U1, which covers empty spaces in a
with 3HU system enclosures. Specifically, each backbox is Model
given row of a 3HU enclosure, FHD2009-U1
used to fasten with a 3HU outer door.
(in place of any redundant operator
Each 3HU backbox can be ordered in black interface switch and / or microphone option module).
(Model FHB2005-U1 or red (Model FHB2005-R1).
Three-Height-Unit Enclosure Trim Kit
Approximate size: 42" (106.7 cm.) high; This optional trim kit is used to provide a tidy appearance of
21" (53.3 cm.) wide, a 3HU enclosure when used in flush-mount applications.
and 7.75" (19.7 cm.) deep. Each trim kit can be
purchased in either red
(Model FHA2043-R1) or
Model FHA2043-U1/R1
S-Series License black (Model FHA2043-U1),
S-Series License KeysKeys [Three-Height-Unit (3HU)
[S1, Model FCA2033-A1 | S2, Model FCA2034-A1| S3, Model FCA2035-A1] and comes unassembled in Enclosure Trim Kit]
four (4) slats.
S-Series License Keys
The S1 license key (Model FCA2033-A1) allows for virtual
Inner Doors
monitoring and control between a Cerberus PRO IVC panel There are two (2) inner doors available for Cerberus PRO
and a personal computer. The S2 license key (Model system enclosures. The inner door, which is available
FCA2034-A1) is a BACnet output, and is used for exclusively in black, specifically stores the Standard Operating
monitoring-only purposes by a 3rd-party system for life- Unit, or the Operating Unit with LEDs.
safety objects. The S3 license key (Model FCA2035-A1) is Additionally, the Model FHD2004-U1 inner door supports one
a combination license key that allows for virtual (1) system operating unit, or one (1) to four (4) LED option
monitoring and control, as well as for distribution of modules. When less than four (4) LED option modules are
BACnet (monitoring-only) communications. used, the blank-option module (Model FCM2022-U3) covers
unused module spaces in the inner door.
Approximate size: 13.25" (33.7 cm.) high and
20" (50.8 cm.) wide
Note: Model FHD2005-U1 is a solid-black, inner-door blank plate
used to provide dead-front protection.
Model FHD2007-U3/R3
[Three-Height-Unit (3HU) Outer Door]
s I ndustry, Inc.
–6– Cerberus PRO
Building Technologies Division
Voice System Components − (continued)
VoI P Module
[Model VCI2003-A1]
Voice-over-IP Module
The VOIP module (Model VCI2003-A1) is used to convert
Electric Ethernet Module audio signals between analog and digital Voice-over-IP
[Model VN2001-A1] signals. This module is mounted to a connection point on the
Electric Ethernet Module voice CPU card (Model VCA2001), and is required for all
network voice applications.
The Electric Ethernet Module (Model VN2001-A1) serves as
a network connector between Siemens fire-only FACPs and For system configurations, the Voice CPU card provides
with intelligent voice-communication systems. voice-network support to the following:
a VoIP Module (Model VCI2003-A1)
Model VN2001-A1 mounts in either or both of: [for Voice-over-IP conversion of audio signals]
the Voice CPU Card, Model VCC2001-U1 up to four (4) CAT5 connections, via the Electric Ethernet
[used in voice systems] Module, Model VN2001-A1a single-mode (Model VN2003-A1)
the Modular Ethernet Switch, Model FN2012-A1 or a multi-mode (Model VN2002-A1) Ethernet module
[for use in FACP-only connections]
s I ndustry, Inc.
–7– Cerberus PRO
Building Technologies Division
Cerberus PRO FIRE Components Releasing Module
Model XCI2001-U1 supports activation of releasing valves
in pre-action / deluge systems (including double-interlock
pre-action systems, or Sinorix Engineered Fire
Suppression Systems). Model XCI2001-U1 supports only
`Class B’ releasing circuits.
C-WEB Network Module
[Model FN2001-U1]
s I ndustry, Inc.
–8– Cerberus PRO
Building Technologies Division
Cerberus PRO FIRE Components ─ (cont.’d) Digital Alarm Communicator Transmitter
The Digital Alarm Communicator Transmitter (DACT) is
used to provide communication between a 252 / 504-point
(FIRE or IVC) addressable FACP and an off-premises
monitoring station.
Each DACT (Model FCA2015-U1) can also support additional
Single-Mode / Multi-Mode Fiber-Optic Module third-party Internet Protocol (IP) and Global System Mobile
Single-Mode / Multi-Mode Fiber-Optic Module (GSM) communication technologies, which include: Bosch,
The single-mode (Model FN2006-U1) / multi-mode (Model Telguard and DSC. Consequently, Model FCA2015-U1 is
FN2007-U1) fiber-optic interface module can be used to UL Listed as compatible with third-party IP and GSM
transmit RS-485 communication for the Cerberus PRO FACP, as dialers.
well as the Model FT924 Fire Terminal. The Model FCA2015-U1 module mounts directly on the
back enclosure and connects to the periphery boards.
The single-mode / multi-mode fiber-optic module provides C-
The DACT enables remote transmission of alarms and
NET peer-to-peer network communication between the
events via a public telephone line.
Cerberus PRO 252-point and 504-point addressable systems.
Model FCA2015-U1 supports two (2) lines and four (4)
Models FN2006-U1 / FN2007-U1 require 24 Volts DC [nominal]
accounts, and can transmit serial information (including the
power, and the networked Cerberus PRO panel serves as the main
address of the event) to the monitoring station.
source in meeting this power requirement. Models FN2006-U1 /
FN2007-U1 can also be powered from any UL Listed, regulated
24VDC power supply, such as the Siemens (Model PAD-series)
Distributed Power Module & NAC Extender.
Models FN2006-U1 / FN2007-U1 can be mounted in a Cerberus
PRO one-height-unit or two-height unit enclosure, and can
operate in a daisy-chain configuration.
Two (2), high-quality duplex 9/125 fiber-optic cables and ST-
style fiber connectors are used for connection between single- Fire Terminal Board
mode fiber-optic modules. The duplex fiber-optic cable has two [Model FTI2001-U1]
(2) cables in a single shield that is similar to an electrical zip Fire Terminal Board (and equipment)
cord. When using single-mode fiber, each segment of the fiber
The Fire Terminal (Model FT924) consists of the Fire
network can be up to almost 10 miles (16.1 km).
Terminal Board (Model FTI2001-U1); the stores the
For ‘Class B’ installations, each FACP or terminal at either end of Standard Operating Unit (or the Operating Unit with
the daisy chain use one (1) duplex cable for connection to the LEDs), and a one-height-unit enclosure.
next networked panel or terminal. FACPs or terminals within
Each Model FT924 terminal contains one (1) backlit,
the daisy chain require two (2) duplex cables: one (1) duplex
2” ─x─ 4-3/4” (5.1 cm. ─x─ 12.1 cm.) Video Graphics
cable for connection to the previous FACP, and one (1) duplex
Array (VGA) monochrome LCD screen with LEDs for
cable for connection to the next FACP.
displaying system status. An audible will sound when
For ‘Class A’ installations, each FACP or terminal requires two (2) there are ‘unacknowledged’ events on the system.
duplex cables: one (1) duplex cable for connection to the
The display of each operating unit categorizes events by
previous FACP, and one (1) duplex cable for connection to the
type, providing a separate event tab for Alarm, Gas Alarm,
next FACP.
Supervisory, and Trouble events. The quantity of active
events of each type is listed in each event tab. The display
provides two (2) full lines of text message for each event.
Each event can have a 40-character custom message
describing the location for a given event. In addition to
the text message, the system displays the category of the
active event: (e.g. – Automatic Alarm, Water Flow,
Manual, etc.) – the category means more to responding
officials than models.
Digital Alarm
Communicator Transmitter The Fire Terminal Boards contain the site-specific program
[Model FCA2015-U1] configuration which is created in the custom-
configuration tool, ‘Cerberus Works’.
s I ndustry, Inc.
–9– Cerberus PRO
Building Technologies Division
Cerberus PRO FIRE Components ─ When Model PAL-1 is used with the remote peripheral
(cont.’d) module, Model FCA2018-U1 supervises the printer for
On / Off Line, Power On, Paper Out, Paper Jam, and
wiring-fault conditions, as required by UL for NFPA 72
proprietary systems.
Event and report printing is generated either at the
Standard Operating Interface Unit, or Operating Interface
NAC Expansion Module Unit with LEDs on the main Cerberus PRO system.
[Model FCI2011-U1]
s I ndustry, Inc.
– 10 – Cerberus PRO
Building Technologies Division
Related Documentation Details for Ordering − (continued)
Data Sheet — Cerberus PRO Voice Enclosure Kits —
Model Description
Number Part
— 9300 Cerberus DMS Management Station Model Description
Number
OH921 9900 Multi-Criteria Fire Detector Voice Enclosure Kit, Black
HI921 9901 Thermal (Heat) Detector Consists of the following:
OP921 9902 Photoelectric Smoke Detector two (2) Inner Doors
− − one (1)
Photoelectric Smoke Detector (Model FHD2004-U1) Outer Door, black
OP921 9902C FHK2004- S54400-
(for Canada) U3 C168-A1 − one (1) 3HU (Model FHD2007-U3)
backbox, black
Multi-Criteria Fire / CO Detector − one (1) 3HU
OOHC941 9903 (Model FHB2005-U1)
[with ASAtechnology] Outer Door
− two (2) Clear Lens Blank Plate, black
Multi-Criteria Fire / CO Detector (Model FHD2006-U1)
OOHC941 9903C (Model FHD2009-U1)
[with ASAtechnologyMC]
(for Canada) Voice Enclosure Kit, Red
Multi-Criteria Fire Detector Consists of the following:
OOH941 9904 two (2) Inner Doors
− − one (1)
[with ASAtechnology]
(Model FHD2004-U1) Outer Door, red
Multi-Criteria Fire Detector FHK2004- S54400-
OOH941 9904C R3 C169-A1 − one (1) 3HU (Model FHD2007-R3)
[with ASAtechnologyMC] backbox, red
(for Canada) − one (1) 3HU
(Model FHB2005-R1) Outer Door
FDCIO422 9905 4-Input / 4-Output Interface Module − two (2) Clear Lens Blank Plate, red
4-Input / 4-Output Interface Module (Model FHD2006-U1) (Model FHD2009-R1)
FDCIO422 9905C
(for Canada)
— Remote Microphone Kits —
See:
9906 ’FDBZ’ Series Air-Duct Housings Part
data sheet Model Description
Number
See: ’FDBZ’ Series Air-Duct Housings
9906C Remote Microphone Kit, Black
data sheet (for Canada)
See: Consists of the following:
9907 ’DB’ Series Detector Base
data sheet − One
(1) 1HU back box − One (1) Lexan
See: ’DB’ Series Detector Base (Model FHB2001-U1) clear lens
9907C S54400- (Model FHD2006-U1)
data sheet (for Canada) VR2005- C90-A1 − One (1) inner door
(Model FHD2004-U1) − One (1) microphone
ABHW-4B 9909 Intelligent Audible (Sounder) Base U3 option module
− One (1) outer door
ABHW-4S 9910 Audible (Sounder) Base (Model FHD2001-U3) (Model VTO2004-U1)
for Sleeping Areas − Two (2) blank plates − One (1) `Class B’
(Model FCM2022-U3) voice terminal board
(Model VTA2001-A1)
s I ndustry, Inc.
– 11 – Cerberus PRO
Building Technologies Division
Details for Ordering − (continued) Details for Ordering
— Parts — — Parts (continued) —
Part Part
Model Description Model Description
Number Number
Main Board FHB2005-R1 S54400-B110-A2 3HU Enclosure Backbox, Red
EBA2004-A1 S54400-B137-A1
(for the 100W Booster Amplifier) Inner Door, Black
FHD2004-U1 S54400-B52-A1
Digital Alarm (open center space for module access )
FCA2015-U1 S54400-A63-A1
Communicator Transmitter Inner Door, Solid Black
FHD2005-U1 S54400-B53-A1
FCA2016-U1 S54400-A39-A1 RS─485 Interface (no open space / insert)
FCA2018-U1 S54400-A65-A1 Remote Peripheral Module FHD2006-U1 S54400-C46-A1 Lexan® Clear-Lens Window
Module Network (MoNet) 3HU Outer Door, Black
FCA2031-A1 S54400-A153-A1
Connection Card FHD2007-U3 S54400-B113-A1 (contains three {3}
FCA2032-U1 S54400-B145-A1 Battery Disconnect Module window cutouts)
License Key (S1) for remote access | 3HU Outer Door, Red
FCA2033-A1 S54400-P154-A1
remote view | remote operation FHD2007-R3 S54400-B113-A2 (contains three {3}
License Key (S2) BACnet window cutouts)
FCA2034-A1 S54400-P155-A1
output (monitoring only) FHD2009-U1 S54400-B114-A1 3HU Blank Plate, Black
License Key (S3) for remote access | FHD2009-R1 S54400-B114-A2 3HU Blank Plate, Red
FCA2035-A1 S54400-P156-A1 remote view | remote operation | FHD2012-U1 S54400-C135-A1 Inner Door, Black
BACnet output [used in Canadian-RDT installs]
FCI2011-U1 S54400-A54-A1 NAC Expansion Module FN2001-U1 S54400-A60-A1 C-WEB Network Module
FCI2016-U1 S54400-A55-A1 Periphery Board (for 252-pt. panels) FN2012-A1 S54400-B152-A1 Modular Ethernet Switch
FCI2017-U1 S54400-A56-A1 Periphery Board (for 504-pt. panels) FP2012-U1 S54400-Z60-A1 300-Watt Power Supply
Optional Leased-Line / FP2013-U1 S54400-Z61-A1 600W Cascading Pwr. Supply
FCI2020-U1 S54400-A57-A1
City-Tie Module LED Annunciator Driver
FT2007-U1 S54400-A142-A1
FCM2018-U3 S54400-C40-A2 Operating Interface Unit
FT2008-U1 S54400-A143-A1 16-Zone Tab Annunciator, Black
Operating Interface Unit
FCM2019-U3 S54400-C41-A2 FT2008-R1 S54400-A144-A1 16-Zone Tab Annunciator, Red
[with LED]
FCM2022-U3 S54400-C44-A2 Front-End Blank Option Module FT2009-U1 S54400-A145-A1 32-Zone Tab Annunciator, Black
LED Option Module FT2009-R1 S54400-A146-A1 32-Zone Tab Annunciator, Red
FCM2023-U3 S54400-C45-A2 Red / Green bi-color LED FT2014-U3 S54400-B80-A1 Remote Display Terminal, Black
(one {1} standalone Yellow LED) FT2014-R3 S54400-B73-A1 Remote Display Terminal, Red
LED Option Module Remote Display Terminal, Black
FT2015-U3 S54400-B88-A1
FCM2034-U3 S54400-C138-A1 Red / Yellow bi-color LED (contains three {3} buttons)
(one {1} standalone Yellow LED) Remote Display Terminal, Red
Operating Interface Unit [w/ LED] FT2015-R3 S54400-B16-A1
FCM2035-U3 S54400-C140-A1 (contains three {3} buttons)
[used in Canadian-FACP installs] FTI2001-U1 S54400-A58-A1
Fire Terminal Board
Housing, Black VCA2002-A1 S54400-A47-A1
Voice System (4A) Card Cage
FH2016-U1 S54400-B138-A1
(for the 100W Booster Amplifier) VCC2001-A1 S54400-A40-A1
Voice CPU Card
Housing, Red
FH2016-R1 S54400-B136-A1 VCC2002-A1 S54400-A41-A1
Voice Input / Output Card
(for the 100W Booster Amplifier)
Voice Amplifier Card
FHA2031-U1 S54400-B44-A1 Optional DIN Rail Kit VCI2001-U1 S54400-A45-A1
(25V or 70V)
Three-Height-Unit (3HU)
FHA2041-R1 S54400-B93-A1 VCI2003-A1 S54400-A141-A1 VoIP Module
Enclosure Cover, Red
VN2001-A1 S54400-A42-A1 Electric Ethernet Module
33AH Battery Bracket
FHA2042-U1 S54400-B55-A1 (used with Cerberus intelligent VN2002-A1 S54400-A43-A1 Multi-Mode Ethernet Module
voice-communication FACPs) VN2003-A1 S54400-A44-A1 Single-Mode Ethernet Module
FHA2043-U1 S54400-B56-A1 Three-Height-Unit Trim Kit, Black VR2005-U3 S54400-C90-A1 Remote Microphone Kit, Black
FHA2043-R1 S54400-B57-A1 Three-Height-Unit Trim Kit, Red VR2005-R3 S54400-C92-A1 Remote Microphone Kit, Red
FHA2044-U1 S54400-B167-A1 Battery Fixing Bracket VTA2001-A1 S54400-F163-A1 Remote Terminal Board
(for the 100W Booster Amplifier) ( ` Class B’)
FHA2054-U1 S54400-B58-A1 Audio Transformer Kit VTO2001-U3 S54400-C60-A2 Option Module, 24 switches
FHB2005-U1 S54400-B110-A1 3HU Enclosure Backbox, Black VTO2004-U3 S54400-C61-A2 Option Module, Microphone
XCI2001-U1 S54400-A69-A1 Releasing Module
s Cerberus PRO NOTICE ─ The information contained in this data-sheet document is intended only as a summary,
and is subject to change without notice. The devices described here have specific
instruction sheets that cover various technical, limitation and liability information.
Siemens Industry, Inc. ─ Building Technologies Div. Copies of these instruction sheets and the General Product Warning and Limitations
8 Fernwood Road • Florham Park, NJ 07932 document, which also contains important information, are provided with the product,
and are available from the Manufacturer.
Tel: (973) 593-2600 • Fax: (908) 547-6877
Data contained in these documents should be consulted before specifying or using the product.
Web: www.USA.Siemens.com/CPI VC For further information or assistance concerning particular problems contact the Manufacturer.