Tri-MEC RMU

Download as pdf or txt
Download as pdf or txt
You are on page 1of 28

Leader in Electrics & Automation

Electric Equipment
Tri-MEC
Ring Main Units
Medium Voltage Secondary Distribution
Ring Main Units Up to 24kV, SF6-Insulated
Ring Main Units
Technology
Safety
Durability and usefulness
Saving Cost
CONTENTS
:
Applications 4
Features 5
Configurations 6
Modules 8
Ring switch module (RPL) 8
Fuse-switch module (RPF) 9
Circuit breaker module (RVB) 10
Outer assembly 11
RPS 11
RPF 12
RPL 13
RVB 14
RBR 15
Cable termination 16
Ring switch / Circuit breaker 16
Fuse-switch 16
Pannel connection 18
Accessories 19
Installation 24
Technical data 25
Quality assurance 26
Medium Voltage
Secondary Distribution
Ring Main Units
Up to 24kV,
SF6-Insulated
Applications Tri-MEC
4
Tri-MEC is designed for use in the following
applications:
Compact secondary substations
Small industries
Wind power plants
Hotels, shopping centers, office buildings, business centers etc.
Light mining applications, airports, hospitals, tunnels and underground railways
Note) Application range.
Ring Main Units
Transmission Distribution(24kV) Generation
Transmission
line
Commercial &
Industrial
customers
Power plant
Substation
5
Technology
Metal enclosed unit for indoor installation and type tested.
Insulated by SF6 Gas
Independent of climate.
ON-OFF-EARTH, three position load break switch.
Safety
Approachable and operable safely in the presence of power in the cables.
Clear indication of operation status via mimic diagram on front panel.
Fully automatic interlocking system.
Voltage detector to check the presence of voltage in the cable.
Durability and usefulness
Metal enclosed tank is hermetically sealed, it means this is independent of
environmental effects such as dirt, small insects, and moisture and so on.
Load break switch operating is possible in the front of Ring Main Units.
All switching operations can be made safely to personnel because of interlocking
system that operates automatically according to the switch position by the operator.
Remote operation available in case of using motor mechanism.
Fuse LBS will be tripped by a fuse striker pin connected to the mechanism
in the event of fault happening.
Individual panels and panel blocks can be freely combined and extended.
Saving cost
Only a little maintenance is required except replacement of HRC Power fuse after installation.
Compact design that requires minimum space to install and operate locally is
main advantage especially where the space is limited.
Materials can be recycled after the end of its service life.
Features
Configurations
6
General
Tri-MEC RMU is an extensible and non-extensible ring main unit for the secondary distribution
network. Tri-MEC RMU can be supplied in various different configurations suitable for most
switching applications in 24 kV distribution networks.
When combined with the Tri-MEC RMU, they represent a complete solution for 24kV
secondary distribution networks. Tri-MEC RMU is a completely sealed system with a stainless
steel tank, gas tight metal enclosure, containing all the live parts, Switching-disconnector, earth
switch, Fuse switch, the circuit breaker.
A sealed steel tank filled with SF6 gas ensures a high level of reliability as well as safety and a
maintenance-free system. The Tri-MEC RMU offers the user a choice of either a switch-
disconnector combined with fuse or circuit breaker with relay for protection of the transformer.
Tri-MEC RMU can be controlled completely with an feeder remote unit. Most of this switchgear
exists in version that are extensible on the right or on both sides, in order to provide for future
development.
Information of model name
R
Ring Main Units
RMU
P: Puffer
V :V.I
B: Bus
D: Double feeder
U: Upside down
L: LBS
F: Fuse
B: Breaker
R: Rising
S: Standard
Non-Extensible type
RPS
LBS
VD
LBS
VD
LBS
Fuse
1
5
3
5
1502
706
<2 LBS + 1 Fused LBS>
RPF(1R1F)
S
VD
SA
LBS
Fuse
1
5
3
7
6
9
5
706
880
1061
<1 Fused LBS + Bus rising>
Weight: 400kg
Weight: 275kg Note) *: Option
*
*
7
Extensible type
Configurations
Weight: 210kg
RPL
LBS
VD
1
7
5
0
456
7
3
0
<LBS Panel>
Weight: 275kg
RPF
LBS S
Fuse
1
7
5
0
6
8
3
730
765
611
<Fused switch Panel>
Weight: 260kg
RVB
VCB
2CT
Trip
OC 1
7
5
0
730
520
<Circuit Breaker Panel>
Weight: 160kg
RBR
VD
1
7
5
0
6
8
3
730
456
765
<Bus Rising Panel>
*
*
Note) *: Option
Modules
8
Ring switch module (RPL)
Feature
Three position load break switch and earthing switch.
Indicator of switch position for load break switch and earthing switch.
Voltage indicator lamp on panel makes it possible to check the presence of voltage in the cables.
Pressure gage indicates status of SF6 gas tank and make it check leakage of gas.
Intelligent interlock system
: To switch to Earth position, it should pass "OFF" position from "ON" position
Applied high-speed rotary puffer type for extinction of arc.
Dead front structure: It prevents an accident of touching because the live part is not exposed.
Electrical (Remote/Local)operation :
operated by controller which can communicate with FRU (Feeder Remote Unit)
Busbars, 630A
Ring Main Units
< ON position >
LBS
VD
EARTHING
SWITCH
Open Open
Close Earth
LOAD BREAK
SWITCH
< OFF position >
EARTHING
SWITCH
Open Open
Close Earth
LOAD BREAK
SWITCH
< EARTH position >
EARTHING
SWITCH
Open Open
Close Earth
LOAD BREAK
SWITCH
Feature
Fuse rating: 24kV, Max 63A HRC power fuse
Indicator of switch position for load break switch and earthing switch
The Fuses conforming to DIN 43625 are used.
Automatically tripped to protect from fault current when a fuse is blown
Applied high-speed rotary puffer type for extinction of arc.
Dead front structure: It prevents an accident of touching because the live part is not exposed.
Busbars 200A
Option: CTD (Condensor Trip Device)
9
Fuse-switch module (RPF)
LBS S
Fuse
A
B
C
< ON position >
A
B
FUSE SWTICH
EARTHING SWITCH
Open
Close
Open Earth
< OFF position >
FUSE SWTICH
EARTHING SWITCH
Open
Close
Open Earth
< EARTH position >
B C
FUSE SWTICH
EARTHING SWITCH
Open
Close
Open Earth
*
Note) *: Option
Modules
10
Circuit breaker module (RVB)
Mechanism operation time
Ring Main Units
Feature
200A vacuum circuit breaker
Rated breaking time: 3cycle
Latched mechanism - close and open coil
Protection as specified by customers
Motor charge type and Manual charge type
Option:CTD(Capacitor Trip Device), OCR
< ON position >
VCB
2CT
Trip
OC
< OFF position >
< Spring charge
indicator >
*
Note) *: Option
11
RPS (2LBS + 1Fuse-switch)
Outer assembly(Non-Extensible)
LBS operation part
Chamber
Control connector
Fixing bolt for cover
630A bushing
Elbow connector
Cable clamp
Nameplate
Gas pressure gauge
Voltage detector
Fuse holder Body
Fuse holder cap
Fuse strike link
200A bushing
Straight connector
Earth lug
Earth busbar
Lift lug
LBS
VD
LBS
VD
LBS
Fuse

Outer assembly(Extensible)
12
RPF (Fuse-switch)
Ring Main Units
630A bushing for connector
Chamber
Fuse holder body
200A bushing
Operating mechanism
Straight connector(Option)
Upper side cover
Earth connection hole
Gas pressure gauge
Control connector
Cable clamp
Fuse holder cap
Fuse strike link
CTD(option)
Pressure switch(option)
Nameplate
Fixing bolt for cover
Earthing busbar
Lift lug
LBS S
Fuse

13
RPL (Ring switch)
630A bushing for connector
600A bushing
Chamber
Elbow connection (option)
Cable clamp
Earth connection Hole
Upper side cover
Operation mechanism
Nameplate
Voltage detector
Gas pressure gauge
Fixing bolt for cover
Earthing busbar
Lift lug
LBS
VD

Outer assembly(Extensible)
14
RVB (Circuit breaker)
Ring Main Units
630A bushing for connector
630A bushing
Chamber
Elbow connection (Option)
Cable clamp
Gas pressure switch (Option)
Upper side cover
Operation mechanism
Gas filling valve
Nameplate
Voltage detector
Gas pressure gauge
CT
VCB
2CT
Trip
OC

*
Note) *: Option
15
RBR (Bus rising)
630A bushing for connector
630A bushing
Chamber
Elbow connection (Option)
Earthing busbar
Upper side cover
Gas pressure gauge
Nameplate
Voltage detector
Cable clamp
Fixing bolt for cover
Lift lug
VD

Cable termination
16
Ring switch / Circuit breaker (ANSI/IEEE Std. 386)
These connectors are designed for easy installation on extruded shield cable or metallic tape shielded cab. The connector
range is from 1/0 to 1000 kcmil for aluminum and copper conductors with insulation diam from o.640" to 1.935".
Ring Main Units
M
o
l
d
e
d

c
o
n
d
u
c
t
i
v
e

i
n
s
e
r
t
C
o
n
d
u
c
t
o
r

c
o
n
t
a
c
t
S
t
r
a
i
g
h
t

r
e
c
e
p
t
a
c
l
e

h
o
u
s
i
n
g
"
A
"
C
a
b
l
e
G
r
o
u
n
d
i
n
g

e
y
e
Bushing
for load
side
Bail
tip
Bail plate
Bail
Wire
Nut
Straight
receptacle
Stress relief adapter
Molded rubber adapter is sized to the cable insulation and
provides stress relief for the terminated shield. The radial
pressure exerted on the cable shield by the stress surface.
Suitable for installation on both extruded-surface. Suitable
for installation on both extruded-shield cable and tape-type
shield cable.
Spade terminal
Semi-permanent, crimped-bolted connector sized for the
specific conductor. Crimped on with standard tools and
dies, Also used in the 650Y splice.
Molded conductive shield
Outer jacket of 1/8 think molded conduction peroxide-
cured EPDM provides a virtually in destructible ground
shield for true dead-front construction. A patented ELASTI-
MOLD feature.
Grounding eye
Hole provides a convenient point to connect a ground wire
to the molded conduction shield, placing the molded shield
at ground potential.
Wrap-around conductive inserts
Inner shield of molded conductive peroxide-cured EPDM
precludes subjecting entrapped air to electrical stress. A
patented ELASTIMOLD feature.
Voltage test point cap
Molded conduction rubber cap fits over the test point and
onto the connector housing.
Voltage test point
The 1 hex nut located on the top of the insulation plug
allows the circuit to be tested without disturbing the
connection. The nut is fully insulated from the conductor
and pick up capacitance voltage. A torque wrench with a 1
hex socket attachment is required during installation.
Interference fit
Molded insulating peroxide-cured EPDM exerts uniform
con-centric-pressure on insulation of mating parts to
provide required creep-path length and watermeal.
Apparatus bushing
Epoxy product normally supplied on manufacturers
equipment. Can be welded or clamped to the apparatus.
Threaded stud
A removable threaded stud is included with every 655LR
and K655LR.
Fuse-switch
The straight receptacles are fully-shield, fully-submersible and separable insulated connectors. These will accommodate
conductor sizes of No. 4 solid through 4/0 stranded and cable insulation diameters from 0.495" through 0.985".


17
24kV cable termination selection table
*SA: Surge Arrestor
Company Voltage class Current Description Model number
K655BLR
600A
Power distribution K655BIP
Elastmold
24kV connectors K650CP
(PYUNGIL Co., Ltd)
K650ETP
200A Straight receptacles K151SR
EUROMOLD 24kV 600A Tee connector K400TE
5815-S
5815-T
3M 24kV 600A Modular splicing kit 5815-D
5815-E
5815-B
DT625, 635
Cooper power
24kV 600A Bol-T connector
DIP625AS, 635AS
system
CC6A-U
CA625, 635
Cable termination
1 way 1 way with SA 2 way 2 way with SA
Pannel connection
Electrical connection with special connectors
Mechanical Joint Panel to Panel
18
Ring Main Units
Plug
Mold cable
Clamping bolt
Washer
Spacer
Cross connector
Bushing
End connector
19
Fuse
Features
1. The LS HRC Power Fuses belong to the PRIME MEC
series.
It interrupts high currents before the peak value and
therefore cuts down the required withstand capacity of
the associated equipment on the electric system.
2. Though small in size, it has a high breaking capacity and
its enclosed type is suitable for use inside of the panel
board.
3. PRIME-MEC fuses are equipped with striker pins for
trip indicators as well as for inflicting impulse to trip
link of related load break switches.
Selection of fuses: According to IEC 60787(24kV)
Power fuse characteristic curve
Note) Please ask fuse maker for optimum selection of fuses.
Power Fuse rated current(A) Transformer rating capacity (kVA)
5 36-75
10 75-157
20 172-358
30 258-538
40 464-965
50 598-1246
63 745-1554
Accessaries
1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
0
.0
2
0
.0
4
0
.0
6
0
.0
8

0
.1

0
.2

0
.4

0
.6

0
.8

1

2

4

6

8

1
0

2
0

4
0

1
0
0

200A
160A
125A
100A
75A
63A
50A
40A
30A
20A
10A
5A
Cut-off characteristic
C
u
t
-
o
f
f

c
u
r
r
e
n
t
(
p
e
a
k

v
a
l
u
e
:
k
A
)

Prospective breaking current(rms:kA)


1000
800
600
400
200
100
80
60
40
20
10
8
6
4
2
1
0.8
0.6
0.4
0.2
0.1
0.08
0.06
0.04
0.02
0.01
2468
1
0
2
0

4
0
6
0
8
0
1
0
0
2
0
0
4
0
0
6
0
0

8
0
0
1
0
0
0
2
0
0
0

4
0
0
0

8
0
0
0

6
0
0
0

1
0
0
0
0

5A
10A
20A
30A
40A
50A
200A
160A
125A
100A
75A
63A
Pre-arcing time-current characteristics
O
p
e
r
a
t
i
n
g

t
i
m
e
(
s
e
c
.
)

Prospective breaking current (rms:A)


Accessaries
20
Vacuum Interrupter
Ring Main Units
Current path
Driving force
on the high
current ARC
ARC
Figure 1. Current flow and driving
force on arc for spiral
contact
In the closed position, normal current flows
through the interrupter. When a fault occurs
and interruption is required, the contacts are
quickly separated.
The arc drawn between the surfaces of
contacts is rapidly moved around the slotted
contact surface by self induced magnetic
effects, preventing gross contact erosion and
the formation of hot spot on the surface.
The arc burns in an ionized metal vapor,
which condenses on the surrounding metal
shield. At current zero the arc extinguishes
and vapor production ceases.
The metal vapor plasma is very rapidly
dispersed, cooled, recombined, and deionized,
and the metal vapor products are quickly
condensed so that the contacts withstand the
transient recovery voltage.
() Weld
() Bridge explosion
() Contact jets
() Shield involvement
() Arc instability
() Interruption
Current
zero
Recovery
voltage
Voltage Phenomena
() Arc reignition
() Restrikes
() B. I. L
() AC voltage
withstand
Arc initiation
High current arc mode
Fault
current
Time (ms) Time ()
Figure 2. AC arcing and interruption phenomena in vacuum.
21
Relay
LS Integrated Protection and Metering Device
Integrating the other panel meter, protection relay, control
switch on GIPAM
Option
- Transducer function
- Sequence of event
Special Features
- Simplication of the equipments
- Various display function
- Various protection function & easy event analysis
- Data communication function
- High reliability with self-diagnosis function
GIPAM
LS high performance Digital Protection Relay
Various unit types
OCR, OCR/OCGR, OVR(UVR), OVR/UVR, OVGR, SGR
Effective mutual back-up protecting. Setting range of time
and current is wide and subdivided.
Fault Recording function and SOE(Sequence of Event)
function provides quickly accurate information to user that is
used in analyzing causes of fault.
High speed data communication by I-NET communication
method, completely interface with SCADA
DPR
Devices
Protection/monitoring Code
GIPAM DPR-011S DPR-111S DPR-211S DPR-311S DPR-411S DPR-511S
Three-phase overcurrent 50-51
Zero-sequence overcurrent 50N-51N
Selective zero-sequence overcurrent 67G
Overvoltage 59
Undervoltage 27
Zero-sequence overvoltage 59N
Measuring
22
Ring Main Units
Accessaries
Bushing insert
Bushing
Shelded elbow
Grounding eye
Cable
Cable adapter
Spade terminal
Stud bolt
Surge arrester
Probe
Ground lead
Current transformer
Surge arrester
The 273ESA Elbow Arrester is combined with a loadbreak elbow connector interface.
Max. system voltage kV 0.6
Primary current A 100
Secondary current A 5
Rated burden VA 10
Accuracy class 10P10
Short time current kA/1s 16
Rated frequency Hz 60
Polarity Subtractive
Protective characteristics
Note) 1. MCOV- Maximum Continuous Operation Voltage.
2. The front of wave (FOW) protective level is the maximum discharge for a 5kA impulse current wave producing a voltage
wave cresting in 0.5 microseconds.
MCOV
Duty cycle Maximum discharge voltage (kV crest)
F.O.W. protective
(kVrms)
rating
820 microsecond current wave
level
(kVrms)
1.5kV 3kV 5kV 10kV 20kV
(kV crest)
25kV 8.4 10 30.5 32.5 34.5 38.5 43.5 38.5
class 10.2 12 40.0 42.5 45.0 50.0 56.5 50.0
12.7 15 48.0 51.0 54.0 60.0 68.0 60.0
15.3 18 56.5 60.0 64.0 71.0 80.5 71.0
17.0 21 65.5 69.5 74.0 82.5 93.0 82.5
Note2)
Note1)
23
CTD (Condenser trip device)
GAS pressure gauge Control connector Voltage detector
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
1
0
1
1
1
2
1
3
1
4
1
7
1
8
1
9
CTD is built as standard in the contactor with
AC control of instantaneous excitation so that
the contactor can be tripped within 30 seconds in
the event of an electricity failure. The automatic
trip circuit in the event of an electricity failure is
to be built by a customer.
Rating Description
Type CTD-100 CTD-200
Rated input voltage(V) AC 100/110 AC 200/220
Frequency(Hz) 50/60 50/60
Rated impulse
140/155 280/310
voltage(V)
Charging time Within 5 sec. Within 5 sec.
Trip command
Max. 30 sec. Max. 30 sec.
possible time
Input voltage range 85%~110% 85%~110%
Capacitor rating(F) 400 160
AC input DC output
(For discharge)
Control circuit diagram
Terminal
Closing coil (C)
The coil operated only when the power is applied
continuously over 45ms. It has built-in electrically anti-
pumping circuit.
Note 1) Range of the normal operating voltage: 85~110%
2) DC 24V is the underdeveloped rating.
Shunt coil (TC)
When the VCB is 'ON' position, even though the control
power of a shunt coil is 'OFF', the VCB maintains the 'ON'
position.
Note 1) Range of the normal operating voltage: 70~110%
2) DC 24V is the underdeveloped rating.
Rated voltage Rated current (A)
DC 24V 10
DC 110V 2.5
Rated voltage Rated current (A)
DC 24V 10
DC 110V 2.5
Screw type
Plug in type
Installation
24
Ring Main Units
D : Cable diameter
RPS RVB + RPL + RBR
1348
6
2
6
327 102
4
0524
77
1
2
0
327 102
4
6
6
77
1
2
0
4- 1838
Mounting hole
RPF
6
1
.
5
6
0
7
470
3
0
3
.
5
70.5
6-18
Mounting hole
RPL, RBR
6
1
.
5
70.5
6
0
7
315
4-18
Mounting hole
RVB
6
1
.
5 70.5
6
0
7
315
4-16
Mounting hole
377 144 144 315 315 90.5
6
1
.
5
6
0
7
12-16
Mounting hole
R = 10D
Installation type Indoor type
Rated voltage up to kV 24
Rated current A 630 A
Rated current (RVB,RPF) A 200
Rated power frequency Hz 50 / 60
Rated short current kA/1s 16
Rated making current kA 41.6
Power frequency withstand voltage kV 50
Rated impulse withstand voltage kV 125
Operation type electromotion / manual
Operating voltage V DC 110
Operating voltage (CTD Input) V AC 110
Insulation material SF6 Gas
Rated filling pressure (20 C) Mpa. 0.034 (5 psi.G)
Minimum operating pressure (20 C) Mpa. 0.014 (2 psi.G)
Transfer current (RPF) A 800
Electrical life E3
Electrical life (RVB) E1 , C1
Mechanical life M1
Standard IEC 60265-1, IEC 60420
Standard (RVB) IEC 62271-100
25
Technical data
26
Ring Main Units
Quality assurance
Certified quality: KEMA, ISO 9001, ISO 14001
LS Industrial systems has integrated a functional organization into each of its units, the main
purpose of which is to check quality and ensure the adherence to standards.
Routine quality check
While producing Tri-MEC RMU, various routine tests are taken for product capacity, which
testing items are as shown follows.
Filling pressure check
Tightness check
Opening and closing speed measurement
Dielectric check
Contact resistance check
Seismic tests
Application standard: JEAG5003-1999
27
Ordering Information
Test
Norminals
Structural
category
excitation level(g) Direction Freq.(Hz) Waveforms Duration(S) Operability
integrity
X/Y/Z
Resonance
X
search 0.1/0.1/0.1 Y 0.5-30 Random 328 N/A N/A
test
Z
Real
Kobe
earthquake 0.3/0.3/0.15 XYZ Earth- 82 OK OK
test
quake
0.3/0/0 X OK OK
0.3/0/0.15 XZ
5
OK OK
0/0.3/0 Y OK OK
0/0.3/0.15 YZ OK OK
0.3/0/0 X OK OK
Sine 30
0.3/0/0.15 XZ
10
Sine 30 OK OK
waves test
0/0.3/0 Y Wave Waves OK OK
0/0.3/0.15 YZ OK OK
0.3/0/0 X
37.8
OK OK
0.3/0/0.15 XZ OK OK
0/0.3/0 Y
12.2
OK OK
0/0.3/0.15 YZ OK OK
Resonance
X
search 0.1/0.1/0.1 Y 0.5-30 Random 328 N/A N/A
test
Z
LS Ring Main Unit
Switch type
R
RPF, RPL, RPS,
RVB, RBR
Operating type
M Automatic
B Manual
Rated Voltage
24 25.8(24)kV
Rated Current
2 200A
6 630A
Cable connection type
D Dead Break Type
M
Dead Break &
Plug-in Type
Switch and circuit type
21 2L-1F (RPS)
1L 1 LBS (RPL)
1F
1Fuse-Combination
LBS (RPF)
1R Bus Rising (RVR)
1V 1VCB (RVB)
21V 2L-1VCB (RVS)
Rated impulse
withstand voltage
12 125kV BIL
LGS R M 24 6 12 RT D
For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
Safety Instructions
Leader in Electrics & Automation
www.lsis.biz
LS Industrial Systems (Middle East) FZE Dubai, U.A.E.
Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E.
Tel: 971-4-332-8289 Fax: 971-4-332-9444 e-mail: hwyim@lsis.biz
Dalian LS Industrial Systems Co., Ltd. Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn
LS Industrial Systems (Wuxi) Co., Ltd. Wuxi, china
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn
LS-VINA Industrial Systems Co., Ltd. Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@hn.vnn.vn
LS Industrial Systems Tokyo Office Tokyo, Japan
Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz
LS Industrial Systems Shanghai Office Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn
LS Industrial Systems Beijing Office Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
LS Industrial Systems Guangzhou Office Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.biz
LS Industrial Systems Chengdu Office Chengdu, China
Address: 12Floor, Guodong Buiding, No52 Jindun Road Chengdu, 610041, P.R. China
Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn
LS Industrial Systems Qingdao Office Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn
HEAD OFFICE
Yonsei Jaedan Severance Bldg., 84-11, Namdaemunno 5ga,
Jung-gu, Seoul, 100-753, Korea
Tel. (82-2)2034-4870
Fax. (82-2)2034-4713
CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea