Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Shear Wall Design Theory

Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

Worked Examples for Eurocode 2

Draft Version














All advice or information from The Concrete Centre is intended for those who will evaluate
the significance and limitations of its contents and take responsibility for its use and
application.

No liability (including that for negligence) for any loss resulting from such advice or
information is accepted by the Concrete Centre or their subcontractors, suppliers or
advisors.

Readers should note that this is a draft version of a document and will be subject to
revision from time to time and should therefore ensure that they are in possession of the
latest version.
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 2 of 15
6 Walls
6.1 General
Walls are defined as being vertical elements whose lengths are four times greater than
their thicknesses. Their design does not differ significantly from the design of columns in
that axial loads and moments about each axis are assessed and designed for.
Generally, the method of designing walls is as follows:
1. Determine design life. <BS EN 1990 & NA Table NA 2.1>
2. Assess actions on the column. <BS EN 1991 (10 parts) & UK
NAs>
3. Determine which combinations of actions
apply.
<BS EN 1990 & NA Tables NA
A1.1 & NA A1.2(B)>
4. Assess durability requirements and determine
concrete strength.
<BS 85001>
5. Check cover requirements for appropriate fire
resistance period.
<Approved Document B
BS 199212>
6. Determine cover for fire, durability and bond. <BS EN 199211 Cl. 4.4.1>
7. Analyse structure for critical combination
moments and axial forces.
<BS EN 199211 Section 5>
8. Check slenderness and determine design
moments.
<BS EN 199211 Section 5.8>
9. Determine area of reinforcement required. <BS EN 199211 Section 6.1>
10. Check spacing of bars <BS EN 199211 Sections 8 & 9>
Example 6.2 shows the design of a simple linear shear wall as typically used in medium rise
buildings. Similar principals may be applied to walls that are shaped as C, L, T, Z and rectangles
in-plan but issues of limiting flange dimensions and shear at corners need be addressed. The
example shows only ULS design as, apart from minimum areas of steel to control cracking, SLS
issues are generally non-critical in medium-rise structures. For shear walls in high-rise
structures, reference should be made to specialist literature (ref to CIRIA R102 Design of shear
wall buildings).

6.2 Shear wall (Wall A)
Wall A is 200 mm thick and in addition to providing vertical support to 200 mm flat slabs at
roof level and floors 1 to 3, it helps to provide lateral stability to the four storey office block.
Assuming the stair itself provides no lateral stability, the wall is to be designed for the critical
section at ground and first floor level using BS EN 1990 Exp. (6.10). The concrete is C30 / 37.
The wall is supported on pad foundations and the ground floor is ground bearing.

Figure 6.1
Typical floor plan
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 3 of 15


Figure 6.2
Section XX
The example is intended to show how a shear wall providing part of the lateral stability in
one direction in a medium rise structure might be designed by hand.
Axial loads and first order moments are determined. The designs consider slenderness in
order to determine design moments, M
Ed
in the plane perpendicular to the wall. The effects
of allowing for imperfections are also illustrated.
6.2.1 Actions
kN / m
2

g
k
q
k

Roof
Paving 40 mm 1.00 <Section 2.3.2>
Waterproofing 0.50
Insulation 0.10
Suspended ceiling 0.15
Services 0.30
Self-weight 200 mm slab 5.00
7.05
Variable action 0.60
Floor slabs
Carpet 0.03
Raised floor 0.30
Suspended ceiling 0.15
Services 0.30
Self-weight 200 mm slab 5.00
5.78
Variable action 2.50
Ground floor slab (ground bearing)
Carpet 0.03
Raised floor 0.30
Services 0.15
Self-weight 200 mm slab 5.00
5.48
Variable action 2.50
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 4 of 15
Stairs
150 waist @ 30 4.40
Treads 0.15 0.25 25 4 / 2 = 1.88
Screed 0.05 22 = 1.10
Plaster 0.21
Tiles and bedding 1.00
8.59
Variable 2.50
Cavity wall
102 mm brickwork 2.37
50 mm insulation 0.02
100 mm blockwork 1.40
Plaster 0.21
4.00
RC wall
200 mm wall 5.00
Plaster both sides 0.42
5.42

1.10 Wind W
k
=


<BS EN 199114 & NA>
6.2.2 Load take down
Consider whole wall
G
k
Q
k

@ level @ level
Roof (6.0 / 2 + 2.5 / 2) (4.4 + 1.5 / 2) (7.05 + 0.6) = 154.3 13.1
Roof (6.0 / 2) (1.3 / 2) (7.05 + 0.6) = 13.7 1.2
Wall 3.3 4.4 5.42 = 78.7
246.7 14.3
@ above 3
rd
floor 246.7 14.3
3
rd

floor
(6.0 / 2) (1.3 / 2 + 4.4 + 1.5 / 2) (5.78 + 2.5) = 100.6 43.5
Landing (2.5 / 2 1.5 / 2) (5.78 + 2.5) 11.6 5.0
Wall a. b. 78.7
Stair say 1.1 4.4 (8.59 + 2.5) 41.6 12.1
232.5 60.6
@ above 2nd floor 479.2 74.9
2nd floor, landing, wall and stair a. b. 232.5 60.6
@ above 1st floor 711.7 135.5
1st floor, landing, wall and stair a. b. 232.5 60.6
@ above ground floor 944.2 196.1
Ground floor assume 1 m all round =
2 (1.3 / 2 + 4.40 + 1.5 / 2) (5.48 + 2.5) = 63.6 29.0
250 mm wall to foundation 4.4 0.2 0.6 25 = 13.2
76.8 29.0
@ above foundation 1021.0 225.1
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 5 of 15
6.2.3 Design actions due to vertical load at ground 1st
G
k
= 944.2 G
k
/m = 944.2 / 4.4 = 214.6 kN / m
Q
k
=
n
196.1
where

n
= 1.1 n / 10
where
n =no. of storeys qualifying for reduction
*

= 3
<BS EN 1991-1-1 6.3.1.2(11) & NA>
= 1.1 3 / 10 = 0.8
Q
k
= 0.8 196.1 = 156.9 kN Q
k
/m = 156.9 / 4.4 = 35.7 kN /m
6.2.4 Vertical loads from wind action: moments in plane
Consider wind loads, NS









Figure 6.3 Lateral stability against wind loads NS
Check relative stiffness of lift shaft and wall A to determine share of load on wall A.
Lift shaft: I
LS
= 2.4
4
/ 12 2.0
4
/ 12 0.2 1.6
3
/ 12
= 1.36 m
4

Wall A: I
WallA
= 0.2 4.4
3
/ 12
= 1.41 m
4

Wall A takes = 1.41 / (1.41 + 1.36) = 51% of wind load.
Check shear centre to resolve the effects of torsion.
Determine centre of reaction of lift shaft
Area x A
x

2.4 2.4 = 5.76 1.2 6.912
2.0 2.0 = 4.00 1.2 4.800
1.6 0.2 =
0.32 2.3 0.732
1.44 1.38


*
Includes storeys supporting Categories A (residential & domestic), B (office), C (areas of
congregation) and D (shopping) but excludes E (storage and industrial), F (traffic), G (traffic) and H
(roofs).
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 6 of 15

Figure 6.4 Lift shaft
x = A
x
/ A = 1.38 / 1.44 = 0.956 m
i.e. from face of lift shaft to CoG of shaft
= 2.40 0.956 = 1.444 m



Shear centre, C
w
of walls, from centreline of wall A
I
LS
(1.44 + 24.00 + 0.05

) 1.36 25.49
=
I
LS
+ I
WallA

=
1.36 + 1.41
= 12.56 m from wall A

or = 12.56 + 2.80 0.05 = 15.31 from east end of building













Figure 6.5 Shear centres
Note: centre of action and shear centre (almost) coincide. There is no torsion to resolve in the stability
system for wind in a NS direction. (Had there been significant torsion this would have been resolved into
+/ forces in a couple based on the shear walls.)

Assuming centreline of wall A is 50 mm to right hand side of grid.


x
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 7 of 15
Wall A takes 51% of wind load
so characteristic wind load on wall A,
W
k
= 51% w
k
L
x
= 51% 1.1 30.7 = 17.2 kN / m
at just above ground floor, characteristic in-
plane moment in wall A, M
k

= 17.2 141
2
/ 2 = 1709.8 kNm
Resolving into couple using 1 m either end of wall

,
characteristic wind load in each end, W
k

= 1709.8 / 3.4 = 502.9 kN





Figure 6.6 Wall A wind loads NS



6.2.5 Effects of global imperfections in plane of wall A

Figure 6.7 Global imperfections

For medium rise shear walls there are a number of methods of design. Cl. 9.6.1 suggests strut-and-
tie (see Section xx). Another method [ref to Concrete Buildings Design manual] is to determine elastic
tensile and compression stresses from N
Ed
/bL +/ 6M
Ed
/bL
2

and determine reinforcement
requirements based on those maxima. The method used here assumes a couple, consisting of 1.0 m of
wall either end of the wall. The reinforcement in tension is assumed to act at the centre of one end and
the concrete in compression (with a rectangular stress distribution) acts at the centre of the other
end. The forces generated by the couple add or subtract from the axial load in the 1 m ends of the
walls. The method is useful for typical straight shear walls of say 2.5 to 5.0 m in length.
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 8 of 15
Global imperfections can be represented by forces H
i
at floor level where
H
i
=
i
(N
b
N
a
) <Exp. (5.4)>
where

i
= (1 / 200)
h

m

where
<5.2(1),
5.2(5), 5.2(8)
& NA>

h
= 0.67 2 / l
0.5
1.0
= 0.67 2 / 14.7
0.5
1.0
= 0.67 0.52

1.0
= 0.67

m
= [0.5(1 + 1 / m)]
0.5

where
m = no. of members contributing to the total effect
= 25 vertical elements on 4 floors
= 100

m
= 0.71

i
= 0.67 0.71 / 200
= 0.0024
N
b
, N
a
= axial forces in members below and above
(N
b
N
a
) = axial load from each level
At roof level
Area = 30.4 14.5 1.3 2.5 3.6 4.8 = 420.3 m
3

Perimeter = 2 (30.4 + 14.5) = 89.8 m
(N
a
N
b
) = axial load from roof level
= 420.3 (7.05 + 0.6) + 89.8 0.9 4.0 = 3286.4 + 252.2 kN
At 3rd floor
(N
a
N
b
) = 420.3 (5.78 + 2.5) + 89.8 3.3 4.0 = 3615.7 + 1050.8 kN
At 2nd floor
(N
a
N
b
) = 3615.7 + 1050.8 kN
At 1st floor
(N
a
N
b
) = 3615.7 + 1050.8 kN

H
iR
= 0.0024 (3286.4 + 252.2) = 7.9 + 0.6 = 8.5 kN
H
i3
= H
i2
= H
i1
= 0.0024 (3615.7 + 1050.8) = 8.7 + 2.5 = 11.2 kN
Characteristic design moment at ground floor
M
k
= 8.5 13.2 + 11.2 (9.90 + 6.60 + 3.30)
= 112.2 + 221.8 = 334.0 kNm
As before, wall A resists 51% of this moment. Resolving into couple using 1 m either end of wall,
G
kH

= 0.51 334.0 / 3.4 = 50.1 kN


i.e. G
kH
= 50.1 kN / m

As H
i
derives mainly from permanent actions its resulting effects are considered as being a
permanent action too.
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 9 of 15
6.2.6 Design moments perpendicular to plane of wall



Figure 6.8 Plan of wall A and location of sections
A A and B B
Figure 6.9 Section A A
Section A A @ 1
st
floor.
The slab frames into the wall. For the purposes of assessing fixed end moments, the width of slab
contributing to the moments in the wall is assumed to be the length of the wall plus distances half
way to adjacent supports either end. Therefore, consider the fixed end moment for 1.50/2 + 4.40 +
1.30/ 2 = 5.8 m width of adjoining slab framing into the 4.4 m long shear wall (see Figure 6.8).


Figure 6.10 Subframe section A A @ 1st floor

FEM
**
Assuming variable action is a leading action:
= nl
2
/8
= 5.8 (1.35 5.78 + 1.5 2.5) 6.0
2
/ 8
<BS EN 1990 Exp.
(6.10) & NA>
= 5.8 11.6 6
2
/ 8 = 302.8 kNm
k
w
= EI / l = E 4400 200
3
/ (12 3300)
= E 8.88 10
5


**
FEM Fixed End Moment for 1 m width of adjoining slab.
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 10 of 15
k
s
= EI / 2l = E 5800 200
3
/ (2 12 6000)
= E 3.22 10
5

M = 302.8 8.88 / (2 8.8 + 3.22)
= 302.8 0.42 = 121.2 kNm
i.e. 121.2 / 4.40 = 27.5 kNm / m @ ULS
Similarly, assuming variable action is an accompanying action:
M = 5.8 (1.35 5.78 + 0.7 1.5 2.5) 6
2
/ 8
= 5.8 10.4 6
2
/ 8 = 271.4 kNm
271.4 0.42 / 4.40 = 25.9 kNm / m @ ULS

Section A A @ ground floor. By inspection not critical nominal moment.
Section B B @ 1st. Consider the landing influences half of wall (2.2 m long) and that this section of
wall is subject to supporting half the slab considered before at 1st floor level at Section AA.

Figure 6.11 Section B B
FEM
Assuming variable action is a leading action:
= 302.8 / 2 = 151.4 kNm
k
w
= I / l
= 2200 200
3
/ (12 1650) = 8.88 10
5


k
s
= 3.22 10
5
/ 2 = 1.61 10
5

M = 151.4 8.88 / (2 8.88 + 1.61)
= 151.4 0.46
= 69.6 kNm
i.e. 63.8 / 2.2 = 31.6 kNm / m @ ULS
Similarly, assuming variable action is an accompanying action:
M = 5.8 (1.35 5.78 + 0.7 1.5 2.5) 6
2
/ 8
= 5.8 10.4 6
2
/ 8 = 271.4 kNm
271.4 0.46 / (2 2.2) = 28.4 kNm / m @ ULS

Section B B at landing level and ground floor. By inspection not critical.
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 11 of 15
6.2.7 Consider slenderness of wall at ground floor (max.)


Effective length, l
0
= 0.75 (3300 200) = 2325 <Concise Table 5.1>
= 3.46 l
0
/ h = 3.46 2325 / 200 = 40.2 <5.8.3.2(1)>
Limiting slenderness,
lim
= 20 ABC / n
0.5

where
<5.8.3.1(1),
Exp. (5.13N)>
A = 0.7
B = 1.1
C = 1.7 r
m

where
r
m
= M
01
/ M
02

= say = 0.25
= 1.95
n = N
Ed
/ A
c
f
d

where
N
Ed
= 214.6 1.25 + 31.2 1.5 0.7 + 502.9 1.5 + 98.2 1.5 0.7


= 268.3 + 32.8 + 754.4 + 103.1
= 1158.6 kN
A
c
f
d
= 200 1000 0.85 30 / 1.5 = 3400 kN
n = 0.34

lim
= 20 0.7 1.1 1.95 / 0.34
0.5
= 51.5
As <
lim
wall is not slender and no secondary moments
6.2.8 Summary: design forces on wall, ground 1
st
floor
At ground to 1st consider maxima.
Vertical loads G
k
= 214.6 kN / m
Q
k
= 35.7 kN / m
Vertical load due to in-plane bending and wind
W
k
= 502.9 kN / m
Vertical load due to in-plane bending and imperfections
G
kH
= 50.1 kN / m
Maximum moment out of plane, floor imposed load as leading action
M = 31.6 kN / m @ ULS
Maximum moment out of plane, floor imposed load as accompanying action
M = 28.4 kN / m @ ULS
6.2.9 Combinations of actions at ground 1
st
floor
a) At ULS, for maximum axial load, W
k
is leading variable action.
N
Ed
= 1.35G
k
+ 1.5Q
k1
+ 1.5
0
Q
ki

= 1.35 (214.6 + 50.1) + 1.5 502.9 + 1.5 0.7 35.7
= 357.3 + 754.4 + 37.5
= 1149.2 kN / m
M
Ed
= M + e
i
N
Ed
e
0
N
Ed

where
<5.8.8.2(1)
6.1.4>
M = moment from 1st order analysis
= 28.4 kNm / m
e
i
= l
0
/ 400 = 2325 / 400 = 5.8 mm <5.2(7), 5.2(9)>
e
0
= h / 30 20 mm = 20 mm <6.1.4>
M
Ed
= 28.4 + 0.0058 1149.2.1 0.020 1149.2
= 28.4 + 6.7 23.0 = 35.1 kNm/m

Ignoring effect of landing.

Assuming wind load is lead variable action.


WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 12 of 15
b) At ULS, for minimum axial load, W
k
is leading variable action.
N
Ed
= 1.0 214.6 1.35 50.1 1.5 502.9 + 0 35.7
= 607.4 kN / m (tension)
M
Ed
= 28.4

+ 0.0058 607.4 0.020 602.4


= 28.4 + 3.5 23.0
= 31.9 kNm / m
c) At ULS, for maximum out of plane bending assuming Q
k
is leading variable action.

N
Ed
= 1.35 (214.6 + 50.1) + 1.5 35.7 + 1.5 0.5 502.9
= 357.3 + 53.6 + 377.2
= 788.1 kN / m
M
Ed
= 31.6 + 0.0058 788.1 0.020 788.1
= 31.6 + 4.6 15.8
= 36.2 kNm / m
or N
Ed
= 1.0 214.6 1.35 50.1 0 31.2 1.5 0.5 502.9
= 214.6 67.6 0 377.2
= 230.2 kN / m (tension)
M
Ed
= 31.6 + 0.0058 230.2
= 33.0 kNm / m
Consolidate c) into a) and b) to consider two load cases:
N
Ed
= 1149.4 kN / m,
M
Ed
= 36.2 kN / m (out of plane)
and N
Ed
= 607.4 kN / m,
M
Ed
= 36.2 kN / m (out of plane)
6.2.10 Design: for cover
c
nom
= c
min
+ c
dev

where
c
min
= max[c
min,b
; c
min,dur]
] <Exp. (4.1)>
where
c
min,b
= diameter of bar = 20 mm vertical or 10 mm lacers
c
min,dur
= for XC1 = 15 mm
c
dev
= 10 mm
c
nom
= 15 + 10 = 25 mm to lacers
(35 mm to vertical bars)
6.2.11 Fire resistance
Assuming 1 hour fire resistance required for, as a worst case,
fi
= 0.7
and fire on both sides.

Min. thickness = 140 mm, min. axis distance = 10 mm i.e. not critical <BS EN 199212:
Table 5.4>
6.2.12 Design using charts
For compressive load:
d
2
/ h = (25 + 10 + 16 / 2) / 200 = 0.215
interpolate between charts 15.5d and 15.5e for <Concise EC2 Figs
15.5d, 15.5e>
N
Ed
/ bhf
ck
= 1149.4 10
3
/ (200 1000 30) = 0.192
M
Ed
/ bh
2
f
ck
= 36.2 10
6
/ (200
2
1000 30) = 0.030

Strictly incompatible with Q


k
= 0. However, allow Q
k
= 0.
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 13 of 15
Gives:
A
s
f
yk
/ bhf
ck


= 0 minimum area of reinforcement required

= 0.002 A
c

= 0.002 200 1000
<9.6.2 & NA>
= 400 mm
2
/ m
= 200 mm
2
/ m each face
max. 400 mm cc, min. 12 mm diameter <9.6.2(3),SMDSC>
Try T12 @ 400


Figure 6.12 Stresses and strains in wall subject to tension and out of plane moment
For tensile load and moment:
Working from first principles, referring to Figure 6.12 and ignoring contribution from concrete in tension
N
Ed
= (
st1
+
st2
) A
s
/ 2
and M
Ed
= (
st1

st2
) A
s
/ 2 (d d
2
)
so
st1
+
st2
= 2N
Ed
/ A
s

and
st1

st2
= 2M
Ed
/ [(d d
2
)A
s
]
2
st1
= 2N
Ed
/ A
s
+ 2M
Ed
/ [(d d
2
)A
s
]
A
s
= (N
Ed
/
st1
) + M
Ed
/ (d d
2
)
st1


st1
= f
yk
/
m
= 500 / 1.15 = 434.8
A
s
= 607.4 10
3
/ 434.8 + 36.2 10
6
/ [(157 43) 434.8]
= 1397 + 730
= 2127 mm
2

st2
= 2N
Ed
/ A
s

st1
= 571.7 434.8 = 136 MPa
By inspection all concrete is in tension zone and may be ignored.
Use 6 no. H16 @ 200 cc both sides for at least 1 m each end of wall (2412 mm
2
)
6.2.13 Horizontal reinforcement
A
s, hmin
= 0.001A
s
or 25% A
s vert
<9.6.3(1) & NA>
= 200 mm
2
or 0.25 2036 = 509 mm
2
/ m
requires 254 mm
2
/ m each side
Spacing 400 mm <9.6.3(2)>
Links not required <9.6.4(1)>
Use H10 @ 300 (262 mm
2
/ m) both sides.

WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 14 of 15
6.2.14 Check for tension at top of foundation
Permanent and variable (see Section6.2.2) <Section 6.2.2>
G
k
= 1021.0 / 4.4 = 232.0 kN / m
Q
k
= 225.1 / 4.4 = 51.2 kN / m
Wind <Section 6.2.4>
M
k
= 17.2 14.1 [14.1 / 2 + 0.6] = 1855.3 kN / m
Resolved into couple 1 m either end of wall
W
kw
= 1855.3 / 3.4 = +/- 545.7 kN / m
Global imperfections(see Section 6.2.5) <Section 6.2.5>
M
k
= 8.5 13.8 + 11.2 (10.5 + 7.2 + 3.9 + 0.6)
= 365.9 kNm
G
kH
= 365.9 0.51 / 3.4 = 54.9 kN / m
At ULS for maximum axial tension W
k
is lead variable action:
N
Ed
= 1.0 232.0 1.35 54.9 1.5 545.7 + 0 51.2
= 660.7 kN / m
M
Ed
= nominal = e2N
Ed
= 0.02 660.7 <6.1.4>
= 13.2 kNm / m
As before
N
Ed
M
Ed


A
s
=
f
yk
/
m

+
(d d
2
)f
yk
/
m

= 660.7 10
3
/ 434.8 + 13.2 10
6
/ [(157 43) 434.8]
= 1520 + 266
= 1786 mm
2
i.e. not critical
Use 6 no. H16 @ 200 cc b.s. for at least 1 m either end of wall.
6.2.15 Check stability
Assume base extends 0.3 m beyond either end of wall A, i.e. is 5.0 m long
and is 1.2 m wide by 0.9 m deep

Overturning moments <BS EN 1990 Table
A1.2(A) & NA>
Wind (see Figure 6.6)
M
k
= 0.51 x 17.2 14.1 [14.1 / 2 + 1.5] = 1057.5
Global imperfections (see Figure 6.7)
M
k
= 0.51 x [8.5 14.7 + 11.2 (11.4 + 8.1 + 4.8 + 1.5)]
= 0.51 x [125.0 + 11.2 25.8]
= 0.51 x 414.0
= 211 kNm
Restoring moment
M
k
= (1021.0 + 5.0 x 1.2 x 0.9 x 25 + 0 x 225.1 ) x (0.3 + 2.2)
= 2890 kNm
At ULS of EQU,
Overturning moment
= fn(
Q,1
Q
k1
+
G,sup
G
k
)
= 1.5 x 1057.5 + 1.1 x 211.0 = 1818.4 kNm
<BS EN 1990 Table
A1.2(A) & NA>
Restoring moment
= fn(
G,inf
G
k
)
= 0.9 x 2890 = 2601 kNm i.e. > 1818.4 kNm
<BS EN 1990 Table
A1.2(A) & NA>
OK
WE 6 Walls v7a chg 17 Sep 07.doc 17 Sep. 07 Page 15 of 15

6.2.16 Design summary


Figure 6.13 Wall design summary

You might also like