Linx Enterprise: Getting Results Guide
Linx Enterprise: Getting Results Guide
Linx Enterprise: Getting Results Guide
ii
Contact Rockwell Customer Support Telephone 1.440.646.3434
Online Support http://www.rockwellautomation.com/support/
Copyright Notice 2009 Rockwell Automation Technologies, Inc. All rights reserved. Printed in USA.
This document and any accompanying Rockwell Software products are copyrighted by Rockwell Automation
Technologies, Inc. Any reproduction and/or distribution without prior written consent from Rockwell Automation
Technologies, Inc. is strictly prohibited. Please refer to the license agreement for details.
Trademark Notices Allen-Bradley, ControlLogix, FactoryTalk, PLC-5, Rockwell Automation, Rockwell Software, RSLinx, RSView, the
Rockwell Software logo, and VersaView are registered trademarks of Rockwell Automation, Inc.
The following logos and products are trademarks of Rockwell Automation, Inc.:
RSBizWare, the RSBizWare logo, RSBizWare Batch, FactoryTalk Batch, RSLogix, Logix5000, RSOPC Gateway,
FactoryTalk Gateway, Data Highway Plus, DH+, RSView, FactoryTalk View, RSView Studio, FactoryTalk View
Studio, PanelView, RSView Machine Edition, RSView ME Station, RSView32, FactoryTalk Activation, FactoryTalk
Administration Console, FactoryTalk Alarms and Events, FactoryTalk Automation Platform, FactoryTalk Services
Platform, FactoryTalk Diagnostics, FactoryTalk Directory, FactoryTalk Live Data, RSAssetSecurity, FactoryTalk
Security, RSSql, FactoryTalk Transaction Manager, GuardLogix, GuardPLC, MicroLogix, PanelView, RSLinx Classic,
RSLinx Enterprise, RSNetWorx, RSNetWorx for ControlNet, RSNetWorx for DeviceNet, SLC 5, SLC 500,
Powermonitor, Powermonitor 1000, and Powermonitor 3000.
Other Trademarks Microsoft, Windows, Windows ME, Windows NT, Windows 2000, Windows Server 2003, and Windows XP are either
registered trademarks or trademarks of Microsoft Corporation in the United States and/or other countries.
Adobe, Acrobat, and Reader are either registered trademarks or trademarks of Adobe Systems Incorporated in the
United States and/or other countries.
ControlNet is a registered trademark of ControlNet International.
DeviceNet is a trademark of the Open DeviceNet Vendor Association, Inc. (ODVA).
Ethernet is a registered trademark of Digital Equipment Corporation, Intel, and Xerox Corporation.
OLE for Process Control (OPC) is a registered trademark of the OPC Foundation.
All other trademarks are the property of their respective holders and are hereby acknowledged.
Warranty This product is warranted in accordance with the product license. The products performance may be affected by system
configuration, the application being performed, operator control, maintenance, and other related factors. Rockwell
Automation is not responsible for these intervening factors. The instructions in this document do not cover all the
details or variations in the equipment, procedure, or process described, nor do they provide directions for meeting every
possible contingency during installation, operation, or maintenance. This products implementation may vary among
users.
This document is current as of the time of release of the product; however, the accompanying software may have
changed since the release. Rockwell Automation, Inc. reserves the right to change any information contained in this
document or the software at anytime without prior notice. It is your responsibility to obtain the most current information
available from Rockwell when installing or using this product.
Version: CPR 9 Service Release 2
Modified: March 17, 2009
CONTENTS
iii
Contents
1 Introduction 1
Intended audience. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Where to find additional information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Release Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Training programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Knowledgebases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Consulting services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Welcome to RSLinx Enterprise 3
What is RSLinx Enterprise?. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Overview of basic concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FactoryTalk Services Platform. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FactoryTalk Directory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FactoryTalk Live Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FactoryTalk Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FactoryTalk Administration Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
FactoryTalk Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Local applications vs. Network applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
FactoryTalk Administration Console and FactoryTalk View Studio. . . . . . . . . . . 7
Design-time vs. runtime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installation and configuration checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Installing RSLinx Enterprise 9
Minimum system requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Hardware requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Software requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Software compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installing RSLinx Enterprise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Updating an existing installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Updating a system that already has a FactoryTalk-enabled product installed . . . 12
RSLINX ENTERPRISE GETTING RESULTS GUIDE
iv
1
1
1
P
l
a
c
e
h
o
l
d
e
r
Introduction
The Getting Results Guide provides you with information on installing, navigating, and
using RSLinx Enterprise.
This chapter includes the following information:
Intended audience
Where to find additional information
Intended audience
You should be familiar with:
Microsoft Windows operating systems
Allen-Bradley programmable logic controllers (PLCs)
Rockwell Automations PLC programming tools
FactoryTalk Administration Console
Where to find additional information
For additional information about RSLinx Enterprise, consult the following resources:
Help
The Help includes all overview, procedural, screen, and reference information for the
product. The Help contains these basic components:
Overview topics
Quick-start topics
Step-by-step procedures
Dialog box descriptions
To view the Help while working in FactoryTalk Administration Console:
Select Contents from the Help menu on FactoryTalk Administration Console main
window, then select the book, Work with RSLinx Enterprise, or
Click Help on any RSLinx Enterprise dialog box or property page, or
Press F1, or
From the Start menu, select Programs > Rockwell Software > FactoryTalk Tools >
FactoryTalk Help > Work with RSLinx Enterprise.
The Getting Results Guide is included in a portable document format (PDF) on your FactoryTalk
Services installation CD. These files must be viewed using the Adobe Acrobat Reader software,
which is also included on the CD.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
2
Release Notes
The electronic Release Notes provide a list of the hardware and software that is necessary
to use RSLinx Enterprise effectively and a list of known anomalies, anomalies fixed, and
new features that are available in the current release.
The Release Notes are available from the FactoryTalk Services installation CD. The
Release Notes for all FactoryTalk components, including RSLinx Enterprise, are available
from the FactoryTalk Help. FactoryTalk Help can be launched from FactoryTalk
Administration Console or from the Start menu as described in the previous section.
Training programs
Rockwell Automation offers a wide range of training programs, from regularly scheduled
classes to custom-tailored classes conducted at your site.
If you would like more information about these training programs, visit the Rockwell
Automation site on the Web or contact the Rockwell Automation Training Coordinator.
The Web address and telephone numbers appear on page ii of this document.
Knowledgebases
The Rockwell Automation Customer Support Center offers an extensive online database
that includes frequently asked questions and the latest patches. Please visit
www.rockwellautomation.com/support and select Knowledgebase under Self-Service
Support to access this database.
Consulting services
Rockwell Automation provides expert consulting and turnkey implementations for
making optimal use of Rockwell Software products. Please contact your local
representative for more information.
3
2
2
W
e
l
c
o
m
e
Welcome to RSLinx Enterprise
This chapter includes the following information:
What is RSLinx Enterprise?
Features and benefits
Overview of basic concepts
Installation and configuration checklist
What is RSLinx Enterprise?
RSLinx Enterprise is a FactoryTalk Live Data server and FactoryTalk Alarms and
Events server. RSLinx Enterprise configurations, which you create and modify using the
Communication Setup editor, are used by your applications to communicate with devices
(such as controllers and I/O scanners) on the plant floor. This enables you to see values,
such as sensor readings and other controller data from your plant floor devices, on your
desktop computer or dedicated PanelView Plus terminal.
An RSLinx Enterprise configuration consists of:
A list of communication devices and their settings (for example, node, baud rate, etc.).
Device drivers and their associated properties.
A list of potential target devices with which RSLinx Enterprise can communicate (that
is, exchange data).
Shortcuts. A shortcut is a name that stands for the device you want to connect to and
the data that device contains. The communication path associated with the shortcut
tells the application where to find that data.
For FactoryTalk View Machine Edition applications, you can pre-configure
RSLinx Enterprise-based communications needed for the runtime applications using the
design software, FactoryTalk View Studio.You can also edit configurations using
Windows CE-based tools on the PanelView Plus.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
4
P
l
a
c
e
h
o
l
d
e
r
Overview of basic concepts
It is important to understand some basic concepts about FactoryTalk and RSLinx
Enterprise before you begin working with RSLinx Enterprise within the FactoryTalk
Administration Console. For more detailed information about FactoryTalk, refer to the
FactoryTalk Help.
FactoryTalk Services Platform
Formerly known as FactoryTalk Automation Platform, the FactoryTalk Services Platform
is an underlying architecture and set of services that Rockwell Automation software
products build upon.
The FactoryTalk Services Platform:
provides common services (such as diagnostic messages, health monitoring services,
access to real-time data) and shares plant resources (such as tags and graphic displays)
throughout an automation system.
allows defining plant-floor resources once, and then allows simultaneous access to
those resources across product boundaries.
supports centralized security services.
The FactoryTalk Services Platform includes the following components:
FACTORYTALK DIRECTORY
FactoryTalk Directory allows products to share a common address book, which finds and
provides access to plant-floor resources, such as data tags and graphic displays.
The FactoryTalk Services Platform includes two separate directories: a Local Directory
and a Network Directory. In a Local Directory, a Directory Server, all project
information, and all participating software products are located on a single computer.
Local applications cannot be shared across a network. A Network Directory organizes
project information from multiple FactoryTalk products across multiple computers on a
network.
FACTORYTALK LIVE DATA
FactoryTalk Live Data manages connections between FactoryTalk products and data
servers. It reads values from, and writes values to, OPC-DA servers (OLE for Process
Control - Data Access) and Live Data servers on behalf of client software products, such
as FactoryTalk View and FactoryTalk Transaction Manager.
FACTORYTALK DIAGNOSTICS
FactoryTalk Diagnostics collects and provides access to activity, status, warning, and error
messages generated throughout a FactoryTalk system.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
6
P
l
a
c
e
h
o
l
d
e
r
FactoryTalk Administration Console and FactoryTalk View
Studio
To edit RSLinx Enterprise configurations, use FactoryTalk Administration Console or
FactoryTalk View Studio as follows:
In a Network (distributed) application, you can use either FactoryTalk Administration
Console and FactoryTalk View Studio.
In a Local application, you can edit locally or remotely using FactoryTalk
Administration Console, or you can edit locally or remotely within FactoryTalk View
Studio.
To edit a FactoryTalk View Machine Edition (ME) project, use FactoryTalk View
Studio because of the specific needs of FactoryTalk View ME.
Design-time vs. runtime
RSLinx Enterprise is comprised of design-time and runtime components. The design-time
components provide the user interface that enables you to set up devices, drivers, and
shortcuts that are ultimately used by the runtime components. Based on this configuration
data, the runtime components execute read/write requests received during runtime
operation.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
8
11. Create shortcuts that point to your target devices. Creating shortcuts on page 27.
9
3
3
I
n
s
t
a
l
l
i
n
g
a
n
d
S
t
a
r
t
i
n
g
Installing RSLinx Enterprise
This chapter contains the following information:
System requirements
Installing RSLinx Enterprise software for the first time
Updating an existing installation
Minimum system requirements
To use RSLinx Enterprise, your personal computer must meet the following minimum
hardware and software requirements:
Hardware requirements
To install RSLinx Enterprise, you will need the following hardware:
Minimum: Intel Pentium III, 600MHz, 512MB RAM
Recommended: Intel Pentium 4, 2GHz or faster, 1GB or more RAM
Software requirements
To run RSLinx Enterprise, you will require Microsoft Internet Explorer 6.0 (or later), and
one of the following operating systems:
Microsoft Windows Server 2008
Microsoft Windows Vista Business
Microsoft Windows XP Professional, Service Pack 2
Microsoft Windows 2000 Professional, Service Pack 4 with Windows installer 3.0
Microsoft Windows 2000 Server, Service Pack 4 with Windows installer 3.0
Microsoft Windows 2003 Server, Service Pack 1, Service Pack 2, Standard Edition
Microsoft Windows 2003 Server, R2, Standard Edition
Microsoft Windows 2003 Server, R2, Service Pack 2
The user installing RSLinx Enterprise must have administrative rights in Windows on the
computers where the software is being installed. The Windows domain Administrator
account has these rights, for example.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
10
Software compatibility
All Rockwell Software components must be of the same Coordinated Product Release
(CPR) version. Be sure that you install RSLinx Enterprise v5.20.00 (CPR 9 Service
Release 2) with Rockwell Automation's CPR 9 or CPR 9 Service Release 2 products.
To check the CPR version of each Rockwell Software product, select Start > Settings >
Control Panel > Add or Remove Programs. The CPR version number is shown next to
the product name (for example, RSLinx Enterprise (CPR 9 Service Release 2)).
Installing RSLinx Enterprise
To install RSLinx Enterprise, use the follow procedure:
1. Insert the FactoryTalk Services CD into the CD-ROM drive.
2. Select Install RSLinx Enterprise.
3. Follow the instructions in the order they are presented on the screen.
View RSLinx Enterprise Release Notes: The Release Notes may contain more
up-to-date information than was available when this document was published.
Read the Release Notes for the product you are installing before continuing with
the installation.
View How to Activate Rockwell Software Products: This option displays what
you need to know and do to activate RSLinx Enterprise. For more information
about activations, refer to Appendix A.
View RSLinx Enterprise Getting Results Guide: This selection provides the
RSLinx Enterprise Getting Results Guide in a searchable PDF file. Read and
understand this guide before working with RSLinx Enterprise.
The user installing RSLinx Enterprise must have administrative rights in Windows on the
computers where the software is being installed. The Windows domain Administrator account
has these rights, for example.
If autorun is: Then:
enabled The Setup program starts automatically, and the FactoryTalk Services
opening screen displays. Proceed to step 2.
disabled a. Click Start, and then click Run. The Run dialog box displays.
b. In the Open control, type x:\setup, where x is the letter of the
drive containing the FactoryTalk Services CD, and click OK.
The FactoryTalk Services opening screen displays.
3 INSTALLING RSLINX ENTERPRISE
11
P
l
a
c
e
h
o
l
d
e
r
Install FactoryTalk Services Platform: Click this step to start the installation
wizard for FactoryTalk Services Platform. FactoryTalk Services Platform CPR 9
Service Release 1 must be installed on the computer before you install RSLinx
Enterprise.
Included with this installation is FactoryTalk Administration Console, which is a
stand-alone tool that allows you to configure and manage FactoryTalk-enabled
applications, such as RSLinx Enterprise. For more information about FactoryTalk
and FactoryTalk Administration Console, refer to the FactoryTalk Help.
Install FactoryTalk Activation Client: This step installs the FactoryTalk
Activation Client software. If you are not using FactoryTalk Activation to activate
RSLinx Enterprise (that is, for this release you are using your existing EvRSI
activation), then you can skip this step. Note that activation is not required for
Local applications (i.e., FactoryTalk View Machine Edition or FactoryTalk View
Site Edition Local products).
Install RSLinx Enterprise: Click this step to start the installation wizard for
RSLinx Enterprise. You will be prompted to do the following for each installation:
Accept the license agreement
Enter your user name and organization
Select a setup type:
Standard Feature Set Installation to Default Location. This is the default
selection, which installs both the runtime and the design-time components
to C:\Program Files\Rockwell Software\.
Custom Location Selection and/or Custom Feature Selection. Select this
option if you want to install RSLinx Enterprise to a directory other than the
default.
Check for Product Updates: Click this step to launch the Product Updates page,
which provides links to any late-breaking product updates and to the Rockwell
Automation Support Knowledgebase.
4. When you are finished installing the software, click Exit, remove the FactoryTalk
Services CD from the CD-ROM drive, and store it in a safe place.
If you have already installed another CPR 9 Service Release 1 FactoryTalk Services-
enabled product, you already have Factory Talk Services Platform installed on your
computer. Refer to Restart your computer. on page 12 for more information.
You must restart your computer after installing Rockwell Software products. If you are
installing multiple products, you must restart your computer after all of the products are
installed.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
12
P
l
a
c
e
h
o
l
d
e
r
4. Select Modify from the Program Maintenance screen.
5. Verify the installation status of FactoryTalk Administration Console. Check the box to
install it, if it is not already checked.
6. Click Install.
7. Click Finish when the installation is complete.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
14
15
4
4
E
x
p
l
o
r
i
n
g
t
h
e
i
n
t
e
r
f
a
c
e
Starting RSLinx Enterprise and exploring
the user interface
This chapter includes the following information:
Starting FactoryTalk Administration Console
Basic FactoryTalk Administration Console user interface components
Exploring the Communication Setup editor
Starting FactoryTalk Administration Console
RSLinx Enterprise is launched from within Factory Talk Administration Console. To start
FactoryTalk Administration Console, use the following procedure:
1. From the Start menu, select Programs > Rockwell Software > FactoryTalk
Administration Console.
2. Select the FactoryTalk Directory you want to use. Refer to chapter 2 for more
information about Network and Local applications.
NOTE: Depending on the security settings, you may be required to enter a User name and
Password to open an application. Refer to the FactoryTalk Help for more information.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
16
P
l
a
c
e
h
o
l
d
e
r
Adding RSLinx Enterprise to the FactoryTalk application
To begin using RSLinx Enterprise after you install it, you must first add it to a
FactoryTalk application, which is created in the FactoryTalk Directory. Use the following
procedure to add RSLinx Enterprise to an application.
1. In the Explorer window, position the mouse cursor on the area or application to which
you want to add the RSLinx Enterprise server.
2. Right-click the area or application, point to Add New Server in the context menu, and
then select Rockwell Automation Device Server (RSLinx Enterprise).
3. In the RSLinx Enterprise Server Properties tabs, set the server properties. These tabs
are described in Chapter 5.
4. Click OK to add the RSLinx Enterprise server to the application.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
18
P
l
a
c
e
h
o
l
d
e
r
2 Tab(s) contain a communications tree control representing the communication topology.
Depending on your product, you will see the following tabs:
FactoryTalk View Site Edition (SE) Local: Primary tab
FactoryTalk View Site Edition (SE) Network: Primary tab and, if server redundancy is
selected, Secondary tab.
Use the tabs to add, remove, and modify devices and drivers.
Menu options are displayed by right-clicking on the various nodes within the
communications tree.
3 Mode: Indicates if you are Online or Offline.
4 Browse status: Indicates whether or not RSLinx Enterprise is interrogating the network to
determine if there are additional devices present.
5 Shortcut Properties Table indicates the properties associated with the selected shortcut.
6 Status messages assist you as you configure your shortcuts.
OK Saves any changes and closes the Communication Setup editor.
Cancel Closes the Communication Setup editor without saving the current changes.
Verify Displays a summary of the shortcuts you created and their associated status messages.
Help Displays Help.
Item Description
RSLINX ENTERPRISE GETTING RESULTS GUIDE
20
E
x
p
l
o
r
i
n
g
t
h
e
i
n
t
e
r
f
a
c
e
Defining RSLinx Enterprise server
properties
This chapter includes the following information:
Defining General server properties
Setting up RSLinx Enterprise to support redundant servers (optional)
Setting up RSLinx Enterprise to support FactoryTalk Alarms and Events (optional)
To launch the Communication Setup editor, double-click Communication Setup from
the Explorer under the RSLinx Enterprise server icon. The RSLinx Enterprise Server
Properties dialog displays.
Defining General server properties
Both Local and Network applications require you to specify server properties on the
General tab of the RSLinx Enterprise Server Properties dialog.
The server name is RSLinx Enterprise and cannot be changed after the server has been
created.
Use the Description field to describe a components location, to identify a contact
person or number in the event of failure, or to keep track of changes or version
information.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
22
For Local applications, the computer hosting the RSLinx Enterprise server defaults to
localhost and cannot be changed. For Network applications, identify the computer
where the RSLinx Enterprise server resides by either clicking Browse or typing the
computer name.
If you are going to set up a redundant server, click the Redundancy tab. Otherwise, click
Apply to save the server information, and then click OK to close the dialog.
Setting up RSLinx Enterprise to support a redundant server
(optional)
The Redundancy tab of the RSLinx Enterprise Server Properties dialog box enables
you to set up a secondary (redundant) server that will take over in the event that there
is loss of service of the primary RSLinx Enterprise server.
The secondary server cannot be hosted on the same computer as the primary
server.You can set up a redundant data server for a network (distributed) application
only. Refer to the RSLinx Enterprise Help for more information about redundant
servers.
To set up a redundant server, on the Redundancy tab:
1. Select Provide redundancy using a secondary server.
2. Type the name of the computer that the secondary server will run on, or click
Browse to locate and select a computer.
3. Select a switchover option.
5 DEFINING RSLINX ENTERPRISE SERVER PROPERTIES
23
P
l
a
c
e
h
o
l
d
e
r
If you are going to set up FactoryTalk Alarms and Events support, click the Alarms and
Events tab. Otherwise, click Apply to save the server information, and then click OK to
close the dialog.
Setting up RSLinx Enterprise to support FactoryTalk Alarms and
Events (optional)
The Alarms and Events tab on the RSLinx Enterprise Server Properties dialog allows you
to configure the selected server for FactoryTalk Alarm and Event device-based alarm
monitoring. Refer to the RSLinx Enterprise Help or click Help on the property page
before attempting to set up FactoryTalk Alarms and Events support.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
24
25
6
6
C
r
e
a
t
i
n
g
a
C
o
n
f
i
g
u
r
a
t
i
o
n
Creating a configuration
This chapter includes the following information:
Adding a driver
Adding a device
Creating shortcuts
To begin working with RSLinx Enterprise, you must add an RSLinx Enterprise data
server to the FactoryTalk Directory. This procedure is described in chapter 4. Once you
have added RSLinx Enterprise and configured its properties, use the Communication
Setup editor to add drivers, set up driver and device properties, and set up device
shortcuts.
To launch the Communication Setup editor, double-click Communication Setup from
the Explorer under the RSLinx Enterprise data provider.
Adding a driver
A driver is software that interacts with a network interface (such as the interface that
connects your computer to the Ethernet network) and manages the exchange of
communication packets over the network to which the interface is attached. Refer to the
RSLinx Enterprise Help for information about the drivers that are supported.
If you are running on an Ethernet network
To add a driver if you are running on an Ethernet network, right-click on the network
shown (Ethernet), and select Start Browsing to populate the driver with devices.
If you are running on any network other than Ethernet
To add a driver if you are running on any network other than Ethernet, right-click the
device shown at this workstation, and select Add Driver.
Some Ethernet devices may not support the browse protocol used by RSLinx Enterprise on
Ethernet. If the devices you expect to appear during the browse do not display, manually add the
devices to the workstation's Ethernet network by right-clicking on the network and selecting Add
Device.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
26
Adding a device
You can add devices by browsing the network, or you can manually add devices.
Automatically adding a device by browsing
The list of potential device targets for RSLinx Enterprise can be gathered during online
browsing. During a browse cycle, RSLinx Enterprise scans the network addresses,
determines the present devices, and displays them in tree format. The display shows the
set of devices discovered during the most recent browse cycle.
If a device is not found during a browse, it does not appear on the display, regardless of
whether or not that device was previously discovered.
If you are running on an Ethernet network, right-click the network shown (Ethernet) to
start browsing. The network is automatically populated with devices.
BROWSING THE VIRTUAL BACKPLANE
When you select the virtual backplane on the user interface, RSLinx Enterprise may not
automatically discover devices that reside in it. This is most likely to happen if you have
added the device with a separate software package such as the SoftLogix Chassis Monitor
or RSLinx Classic.
If you think you have devices resident in your virtual backplane that are not showing up
on the RSLinx Enterprise user interface, you can right-click the virtual backplane and
select Start Browsing or Show All Devices to see those devices. Note that saved
configuration data is not lost if the devices do not appear.
Manually adding a device
You can manually add the devices to the workstation's network using the following
procedure:
1. Right-click the network or driver and select Add Device.
A list of Available Devices that applies only to the network you selected displays.
6 CREATING A CONFIGURATION
27
P
l
a
c
e
h
o
l
d
e
r
2. Select the device you wish to add and click OK. The device is added below the driver
or network on the communications tree. Unless your application requires a specific
device version, you should select the most recent revision of that device.
For information on device revisions in the device list, see the drivers, device, and
shortcuts section of Frequently Asked Questions in the Help. The Help also provides
information about how to add and configure drives and devices.
Creating shortcuts
Your application uses a configuration file to communicate with devices on the network.
This file contains at least one shortcut, which is a name that stands for the device you want
to connect to and the data that device contains. The communication path associated with
the shortcut tells the application where to find that data.
Here are some important aspects about device shortcuts:
A shortcut needs to be configured for each device that the application needs to access.
The connected device must be capable of providing data to the application.
Shortcuts are stored on a per-FactoryTalk application basis instead of being associated
with the RSLinx Enterprise server itself.
Shortcuts are added, deleted, or modified using the Shortcut Editor in the Device
Shortcuts area of the Communication Setup editor.
To create a shortcut, use the following procedure:
1. In the Device Shortcuts area of the Communication Setup editor, click Add. A default
shortcut named "New_Shortcut" is created.
2. If you wish to change the name of the shortcut, you can enter the new name at this
point.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
28
F
i
n
d
i
n
g
i
n
f
o
r
m
a
t
i
o
n
Troubleshooting
This chapter includes the following information:
What to check first if youre having problems
Troubleshooting tools for RSLinx Enterprise
Answers to common questions
How to contact technical support
What to check first if youre having problems
Does your PC meet the minimum hardware and software requirements? Refer to
chapter 3 for these requirements.
Is the FactoryTalk Administration Console installed on your PC? Verify that
FactoryTalk Administration Console is installed using the following procedure:
1. Select Start > Settings > Control Panel > Add or Remove Programs.
2. Select FactoryTalk Automation Platform from the Add or Remove Programs
screen.
3. Select Change to start the installation wizard.
4. Select Modify from the Program Maintenance screen.
5. Verify the installation status of FactoryTalk Administration Console. Select to install
it, if it is not already selected.
6. Click Install.
7. Click Finish when the installation is complete.
Troubleshooting tools for RSLinx Enterprise
RSLinx Enterprise provides of diagnostic tools that enable you to troubleshoot problems
if they occur:
FactoryTalk Diagnostics event log
Predefined items
RSLINX ENTERPRISE GETTING RESULTS GUIDE
30
P
l
a
c
e
h
o
l
d
e
r
Why cant I edit my Machine Edition configuration?
Editing HMI servers within applications, namely FactoryTalk View Site Edition
Distributed, Site Edition (SE) Local, and Machine Edition (ME), is not supported in the
FactoryTalk Administration Console. The FactoryTalk Administration Console is
intended to configure and manage your application. To edit SE or ME configurations, you
must use FactoryTalk Studio.
How do I know if I have a valid activation?
Check the FactoryTalk Diagnostics log. An information message is logged if the
activation file is not detected by the system when you launch RSLinx Enterprise. Refer to
the FactoryTalk Help for more information about diagnostic messages. Also remember
that SE Local (stand-alone) applications and FactoryTalk View ME applications do not
require any type of RSLinx Enterprise activation. Applications that are Networked such
as FactoryTalk View SE Distributed or FactoryTalk Transaction Manager do require an
RSLinx Enterprise activation.
Can I run RSLinx Enterprise and RSLinx Classic on the same
computer?
RSLinx Enterprise and RSLinx Classic can run simultaneously on the same computer,
although there are some considerations that you must be aware of to avoid resource
conflicts between these two applications. Refer to Appendix C for more information.
How to contact technical support
Questions concerning installation and use of RSLinx Enterprise software are handled by
the Rockwell Automation Customer Support Center. The center is staffed Monday
through Friday, except on U.S. holidays, from 8 AM to 5 PM Eastern time zone for calls
originating within the U.S. and Canada.
To reach the Customer Support Center, call 440-646-3434 and follow the prompts. For
calls originating outside the U.S./Canada, locate the number in your country by visiting
support.rockwellautomation.com/contact information.
When you call, you should be at your computer and prepared to give the following
information:
The product serial number and version number, which can be found by selecting
Start > Settings > Control Panel > Add or Remove Programs. Click the product
name, and then click Click here for support information.
The type of hardware you are using.
The exact wording of any errors or messages that appeared on your screen.
A description of what happened and what you were doing when the problem occurred.
A description of how you attempted to solve the problem.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
32
33
A
A
F
r
a
m
e
M
a
k
e
r
Q
u
i
c
k
T
i
p
s
Activating RSLinx Enterprise
Rockwell Automation's Windows-based software products are copy protected and require
an activation key, located in an activation file, to run the software.
RSLinx Enterprise version 5.20.00 (CPR 9 Service Release 2) supports the following
activation tools:
FactoryTalk Activation: If you are a new user, you will need to activate your
software using FactoryTalk Activation.
EvRSI activation: If you are a current user upgrading to CPR 9 Service Release 2,
your activation is already installed and will be used automatically.
EvRSI activation will be replaced by FactoryTalk Activation in a future release. If you
are using EvRSI activation, please contact your local Rockwell Automation Sales
office or Technical Support for information on migrating your activations to
FactoryTalk Activation.
For Rockwell Automation Technical Support in the U.S. call (440) 646-3434.
Outside the U.S. see http://www.rockwellautomation.com/locations/.
Refer to the product insert How to Activate Rockwell Software Products for the
activation procedure. You can also view this document from the FactoryTalk Services
installation CD. Note that RSLinx Enterprise v5.20.00 (CPR 9 Service Release 2)
supports floating, concurrent activations.
For assistance at any point during the activation process or for more information, click the
Help button on any FactoryTalk Activation Tool dialog or FactoryTalk Activation
Transfer Tool dialog, or click the Help link on the Rockwell Software Activation website:
https://licensing.software.rockwell.com.
If you cannot connect to the Internet, an activation file can be delivered via email or fax.
For assistance, call Rockwell Automation Technical Support. In the U.S., call
(440) 646-3434. Outside the U.S., see http://www.rockwellautomation.com/locations/.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
34
35
B
B
F
r
a
m
e
M
a
k
e
r
Q
u
i
c
k
T
i
p
s
Advanced topics
The following topics are presented in this section:
About the virtual backplane
Supported network routes
Moving RSLinx Enterprise configurations
Managing CIP connections
About the virtual backplane
The virtual backplane is a driver service that provides connectivity between RSLinx
Enterprise and various device drivers and other applications within the RSLinx Enterprise
server. It allows the software modules and communications resources contained in the
server to be configured and visualized in a manner similar to the devices in a
ControlLogix system.
For example, both the PCICS and PKTCS device drivers plug into the virtual backplane.
Packets received by one of these communications interface cards can be routed across the
virtual backplane to (or through) any other interface card whose driver plugs into the
virtual backplane, or to any application that plugs into the virtual backplane, such as the
SoftLogix5xxx controller.
This is very similar to having a 1756-CNB and a 1756-ENBT module plugged into a
ControlLogix chassis: packets received across the ENBT can be routed across the
backplane and out the CNB module, or to a controller sitting in the backplane.
Note that RSLinx Enterprise occupies a slot in the virtual backplane (as can RSLinx
Classic), which means that it is able to be both a source and a destination for packets sent
over the backplane.
This chassis-like model is carried over to the PanelView Plus platforms in a minimalistic
fashion. For ControlNet support, those platforms implement two-slot virtual backplanes,
where RSLinx Enterprise sits in one slot (slot #0) and the 2711P-RN15S ControlNet
Scanner card sits in the other (slot #1).
RSLINX ENTERPRISE GETTING RESULTS GUIDE
36
P
l
a
c
e
h
o
l
d
e
r
MOVING SHORTCUTS ON THE SAME COMPUTER: DIFFERENT APPLICATION
1. Identify the computer on which your FactoryTalk Directory Server is located.
2. On that FactoryTalk Directory Server computer, locate the shortcuts.xml file in:
C:\Documents and Settings\All Users\Application Data\Rockwell\RNAServer\
Global\RnaStore\your_application_name\any_area_or_sub_areas_you_have\
your_RSLinx_Enterprise_server_name
(This assumes you have not changed your documents and settings location and that
you installed Windows to the C:\ drive.)
Your_application_name is the name of your application, and within the application are
folders and sub folders for areas and sub areas, if used.
Any_area_or_sub_areas_you_have will match a file directory of the same name.
Your_RSLinx_Enterprise_server_name will match the name of your RSLinx
Enterprise data server in the application (the default is RSLinx Enterprise).
3. Move the shortcuts.xml file to the path where your new application is; all your
shortcuts NAMES will be moved there.
For example:
C:\Documents and Settings\All Users\Application Data\Rockwell\RNAServer\
Global\RnaStore\your_NEW_application_name\any_area_or_sub_areas_you_have\
your_RSLinx_Enterprise_server_name
4. For each shortcut, you must reapply the path to the end device.
This method works for moving shortcuts between Local applications (remembering that
Local applications always use the computer on which it runs as the "Local" FactoryTalk
Directory server) and for moving shortcuts between Local and Networked applications.
The path for local shortcuts is:
C:\Documents and Settings\All Users\Application Data\Rockwell\RNAServer\Local\
RnaStore\your_application_name_here\your_RSLinx_Enterprise_server_name.
MOVING SHORTCUTS FROM ONE COMPUTER TO ANOTHER: DIFFERENT
APPLICATION
To move shortcuts between computers and between applications, follow the same path on
the FactoryTalk Directory server as described in the previous section. Keep in mind that
the FactoryTalk Directory server will have a directory for each application and for each
RSLinx Enterprise server.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
38
P
l
a
c
e
h
o
l
d
e
r
Using the following procedure for these scenarios may enable you to:
copy I/O configurations
avoid losing user-assigned device names
avoid having to reapply shortcuts for applications copied from the source computer
1. Shut down the RSLinx Enterprise service using the Windows Service Control Panel
on both the source and the target computers.
2. Use Windows Explorer to locate the file an RSLinxNG.xml file in the directory
C:\Documents and Settings\All Users\Application Data\Rockwell\RSLinx Enterprise.
(This assumes you have not changed your documents and settings location and that
you installed Windows to the C:\ drive).
3. Copy RSLinxNG.xml from the source computer to the target computer and restart the
computer hosting RSLinx Enterprise. This results in an exact copy of the source
computers hardware configuration.
Managing CIP connections
Prior to CPR 9 Service Release 2, RSLinx Enterprise would, by default, open up to five
CIP connections to a Logix controller: Four for read operations and one for write
operations. In some system configurations, the maximum connection resources in a
controller or bridge module could be reached fairly quickly. In this situation, if the client
load changed, problems could result (for example, if an HMI terminal was introduced into
the system, it could cause performance variation among all terminals in the system, or you
might not be able to go online with programming software).
With CPR 9 Service Release 2, RSLinx Enterprise checks for devices that support a
relatively small number of CIP connections and limits the number of read connections.
(The number of write connections remains fixed at 1.) These devices are described in the
following sections. By default, all other devices and bridge modules still open as many as
four read connections and one write connection.
RSLinx Enterprise will restart if a Rockwell Automation application attempts to use this
service. Rockwell Automation applications that use RSLinx Enterprise must be stopped
or shut down before you proceed. This will prevent the service from automatically starting
while you are moving the configuration file.
Any time you change the RSLinx Enterprise physical configuration (RSLinxNG.xml), you may
break existing application shortcut assignments. Check all shortcut assignments in all
applications that use the RSLinx Enterprise service on the same host workstation to ensure
that the correct devices are assigned.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
40
P
l
a
c
e
h
o
l
d
e
r
Changing the allocation of CIP connections
Configuration parameters in the registry file or the RSLinxNG.xml file can be used to
override the default values. Refer to Knowledgebase Answer ID 39366 for information on
manually changing the connection allocation
RSLINX ENTERPRISE GETTING RESULTS GUIDE
42
43
C
C
F
r
a
m
e
M
a
k
e
r
Q
u
i
c
k
T
i
p
s
Using RSLinx Enterprise with RSLinx
Classic
RSLinx Enterprise and RSLinx Classic can run simultaneously on the same computer.
This is a common setup if you need to create or edit a program using RSLogix 5,
RSLogix 500, and RSLogix 5000 software (which require RSLinx Classic) for use in an
application and you must accomplish this using only one computer.
Vista and Windows 2008 operating systems
If your RSLinx Enterprise configuration consists of a:
Dual-channel 1784-PKTX(D) driver
As of CPR 9 SR 2, RSLinx Enterprise and RSLinx Classic both install and use the same
1784-PKTX(D) driver. RSLinx Enterprise uses the first channel (assigned by default and
cannot be changed). RSLinx Classic uses the second channel.
If you are running on Vista or Windows 2008, and your RSLinx Enterprise or RSLinx
Classic configuration consists of a dual-channel 1784-PKTX(D) driver, you configure the
driver for both RSLinx Enterprise and RSLinx Classic.
See Configure the 1784-PKTX(D) driver for RSLinx Enterprise and RSLinx Classic in
the Help for this procedure.
NOTE: This applies only to the dual-channel 1784-PKTX(D) driver; the single-channel1784-
PKTX driver can be configured in only one RSLinx product at a time.
All supported operating systems
If your RSLinx Enterprise configuration consists of a:
1784-PKTX driver
If your RSLinx Enterprise configuration consists of a 1784-PKTX driver, and you need
RSLinx Classic to communicate using that same driver, then you must share the driver
within RSLinx Enterprise with RSLinx Classic.
See Sharing an RSLinx Enterprise driver with RSLinx Classic in the Help for this
procedure.
TIP: You can use this procedure for Vista and Windows XP operating systems; however,
the previous procedure is the preferred method.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
44
W
e
l
c
o
m
e
Glossary
activation file. A read-only system file that activates a Rockwell Software product. The
software will run only if your system can find the correct activation file.
application. A set of data elements used to implement a control system. See Network
application, Local application.
area. Areas organize and subdivide a distributed Network application into logical or
physical divisions. For example, separate areas may correspond with separate
manufacturing lines in a facility, separate plants in different geographical locations, or
different manufacturing processes. Areas are not available with Local applications.
bus. In RSLinx Enterprise, a bus is defined as a network, a driver, or chassis.
channel. In RSLinx Enterprise, a channel is a driver.
CIP. Control and Information Protocol.
client. A component or subsystem that uses data or functionality provided by some other
component or subsystem (the server). The term can also refer to the computer that
executes this software, connecting to a server computer across a communications
network.
configuration. A file that contains information about the physical structure you defined
for your system. This file includes all network paths, defined drivers and devices, data
providers, and object protocols.
CPR. Coordinated Product Release.
data access server. A server that provides tags.
data element. An individually addressable item of data. For example, a tag (e.g., OPC or
HMI) or an HMI Project Component (e.g., a graphic display, event file, node, channel,
etc.).
Data Provider. Logic that knows how to speak to a particular class of products. One of
the building blocks of RSLinx Enterprise, a Data Provider acts as a multiplexor for
multiple clients and optimizes what data can be read together for more efficient handling.
deploy. To copy and distribute project files to designated directories on other computers.
distributed application. See Network application.
driver. Software that interacts with a network interface (such as the interface that
connects your computer to the Ethernet network) and manages the exchange of
communication packets over the network to which the interface is attached.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
46
P
l
a
c
e
h
o
l
d
e
r
GLOSSARY
online data item. A data item (tag) whose server is currently available to supply data.
Online data items are read directly from a controller, just as they are defined in that
controller.
OPC. A set of industry-standard specifications that define interfaces for communicating
with automation devices and services. Applying OPC standards makes interoperability
possible among automation and control applications, field systems and devices, and
business and office applications that are supplied by different vendors.
packet. The transmission unit exchanged at the network layer.
PCCC (PC
3
). Programmable Controller Communication Commands.
redundancy. Having to do with the availability of a standby hardware or software module
that can assume the responsibilities of a primary hardware or software module if that
primary module fails.
reference. A link from one data element to another. The referring element is called the
source element and the referenced element is called the target element. A graphic
display, for example, typically reference tags, which supply it with runtime data.
runtime. Having to do with the operation of a control system.
server. A subsystem that provides services for clients using a set of interfaces.
shortcut. Represents a device that you want to connect to on the network and the data that
device contains. The communication path associated with the shortcut tells the application
where to find that data. This symbolic reference to a physical device is similar to a topic in
RSLinx Classic.
stand-alone application. All application components in a stand-alone application are
located on a single computer and are only accessible from the computer where they reside.
Stand-alone applications do not support areas. Also called Local applications.
tag. A logical name for a variable in a device or in local memory. For example, a tag can
represent a process variable in a Logix 5000 controller.
RSLINX ENTERPRISE GETTING RESULTS GUIDE
48
INDEX
49
I
n
d
e
x
Index
A
activation 31
installing 11
adding a data server 17
adding a device
automatically 26
manually 26
adding drivers 25
Alarms and Events tab 23
applications, about 6
autorun 10
B
browsing
for devices 26
tag 30
virtual backplane 26
C
checklist, installation and configuration 8
CIP (Control and Information Protocol) 36
Communication Setup editor, exploring 18
configurations
creating 25
moving 36
consulting services 2
contacting
Customer Support Center 31
creating shortcuts 27
Customer Support Center, contacting 31
D
data server, adding 17
design-time component 7
device shortcuts, creating 27
devices
adding 26
moving 38
drivers
adding 25
moving 38
E
Ethernet network, adding drivers to 25
event log, FactoryTalk Diagnostics 30
F
FactoryTalk Activation 6
FactoryTalk Administration Console 6
starting 15
user interface components 15, 16
FactoryTalk Diagnostics 5, 30
FactoryTalk Directory 5
FactoryTalk Live Data 5
FactoryTalk Security 6
FactoryTalk Services Platform
about 5
installing 11
FactoryTalk View Machine Edition 31
FactoryTalk View Site Edition 31
FactoryTalk View Studio 7, 30
FactoryTalk, basic concepts 5
G
General tab 21
H
hardware requirements, RSLinx Enterprise 9
Help, accessing 1
I
installation and configuration checklist 8
installing RSLinx Enterprise 9
K
Knowledgebase 2
RSLINX ENTERPRISE GETTING RESULTS GUIDE
50
L
Local applications 6
M
Machine Edition, FactoryTalk View 31
moving
devices and drivers 38
RSLinx Enterprise configurations 36
shortcuts 36
N
Network applications 6
network routes, supported 36
O
offline tag file 28
P
PCCC networks 36
predefined items 30
R
Redundancy tab 22
Release Notes 2, 10
RSLinx 2.x, see RSLinx Classic
RSLinx Classic 31
RSLinx Classic, using with RSLinx Enterprise
43
RSLinx Enterprise
adding a device 26
adding drivers 25
basic concepts 5
Communication Setup editor 18
creating a configuration 25
creating shortcuts 27
definition 3
design-time vs runtime 7
features and benefits 4
installing 9
moving configurations 36
system requirements 9
troubleshooting 29
updating an existing installation 12
using with RSLinx Classic 43
RSLinx Enterprise Server properties, General
tab 21
RSLinx Enterprise Server Properties,
Redundancy tab 22
runtime component 7
S
shortcuts
creating 27
moving 36
Site Edition, FactoryTalk View 31
software requirements, RSLinx Enterprise 9
system requirements, RSLinx Enterprise 9
T
tag browsing 30
technical support 31
training programs 2
troubleshooting 29
U
updates, checking for 11
updating an existing RSLinx Enterprise
installation 12
V
virtual backplane
about 35
browsing 26