PROFIBUS-DP option
Additional Manual
15.720092-V1.0
PROFIBUS-DP en
Imprint
TrueDos with PROFIBUS-DP option
Additional Manual
Version 1.0
Issued by
ALLDOS Eichler GmbH
Reetzstraße 85 • 76327 Pfinztal (Söllingen)
Postfach 1210 • 76318 Pfinztal
Tel. ++49 (0) 72 40 61-0 / Fax. ++49 (0) 72 40 61-177
Mail: alldos.de@alldos.com
Internet: www.alldos.com
© 2004 by ALLDOS Eichler GmbH
Subject to change.
2 15.720092-V1.0
PROFIBUS-DP en
Content
1 General .................................................................................4
1.1 Technical data ......................................................................4
1.2 Connecting the TrueDos to the PROFIBUS-DP V0 ..............5
1.2.1 PROFIBUS-DP V0 ............................................................ 5
1.2.2 Device master data file (GSD) .......................................... 5
2 Electrical Connections ..........................................................6
2.1 Connection to the TrueDos Pump ........................................6
2.1.1 Pin Assignment, Socket 6 ................................................. 6
2.1.2 Bus connection ................................................................. 7
2.2 Accessories: Connector for PROFIBUS-DP ........................7
3 Operating the Pump Using PROFIBUS-DP ..........................8
3.1 Activating Profibus ................................................................8
3.1.1 Display .............................................................................. 8
3.1.2 Opening the second function level ................................... 8
3.1.3 Activating PROFIBUS on the pump .................................. 9
3.1.4 Bus Error .......................................................................... 9
3.2 Communication Between the Profibus Master and the
Pump ..................................................................................10
3.2.1 General / Classification of remote control and local
operation ......................................................................... 10
3.3 Data Protocol ......................................................................11
3.3.1 Remote control of pump using PROFIBUS-DP
Data flow from the Profibus master to the pump ............ 11
3.3.2 Messages Returned from the Pump
Data flow from the pump to the Profibus master ............ 13
V1.0 III
PROFIBUS-DP en
1 General
Note
These additional guidelines describe the connection of the TrueDos
dosing pump with Profibus option to the PROFIBUS-DP V0 as a slave.
! Warning
First read the general operation instructions for the pump. Only the
additional functions are described in these additional guidelines,
“TrueDos pump with PROFIBUS-DP option”.
1.1 Technical data
PROFIBUS
PROFIBUS-DP V0
Auto detect baud rate
The following baud rates are recognized automatically:
12Mbps, 6 Mbps, 3 Mbps, 1.5 Mbps,
500kbps, 187 kbps, 93.75 kbps, 45.45 kbps, 19.2 kbps, 9.6 kbps
Maximum permitted baud rate (transfer rate)
1.5 Mbps
Bus connection
Via M12 connector
Device name / variants
The variant of the TrueDos pump with PROFIBUS-DP option is displayed on
the nameplate of the pump as follows:
Index No. Pump Type Display Supply Voltage
E070 TrueDos 209 D Diagonal 110-120 / 220-240V 50/60Hz
E071 TrueDos 209 D Horizontal 110-120 / 220-240V 50/60Hz
E072 TrueDos 209 D Diagonal 24 V DC
E073 TrueDos 209 D Horizontal 24 V DC
E076 TrueDos 209 M Diagonal 110-115V 50/60Hz
E077 TrueDos 209 M Diagonal 220-240V 50Hz
E078 TrueDos 209 M Horizontal 110-115V 50/60Hz
E079 TrueDos 209 M Horizontal 220-240V 50Hz
Type of protection: IP 65
Warning
IP 65 can only be guaranteed if the connectors have been screwed on
correctly.
4 15.720092-V1.0
PROFIBUS-DP en General
V1.0 5
PROFIBUS-DP en
2 Electrical Connections
Warning
Electrical connections should only be connected by qualified
personnel!
First read the general operation instructions for the pump.
IP 65 can only be guaranteed if the connectors have been screwed on
correctly.
2.1 Connection to the TrueDos Pump
1
3
5
4
6 15.720092-V1.0
PROFIBUS-DP en Electrical Connections
V1.0 7
PROFIBUS-DP en
Note
First read the general operation instructions. Only the additional
functions are described in this section, “Operating the Pump Using
PROFIBUS-DP”.
3.1.1 Display
As soon as Profibus operation has been activated, the Profibus module
starts trying to accept bus operation. While bus operation is functioning
correctly, 'BUS' is shown in the display. If an error occurs, this is indicated by
the flashing symbols 'error' and 'BUS'.
3.1.2 Opening the second function level
In the second function level, Profibus operation is activated and the bus
address (slave address) is entered.
Stop Stop
Start Start
Menu
Stop
Start
keep pressed for 3 seconds
Menu
- Flow on / off
- Memory on / off
- analog w eighting
- Batch
- Timer
- Calibration
- Profibus
- Slow Mode
- display or reset of total
dosing capacity
- display of operating hours
8 15.720092-V1.0
PROFIBUS-DP en Operating the Pump Using PROFIBUS-DP
Menu
Up
Stop Stop
Up On Start 108 Start
BUS BUS Down
OFF
BUS set bus address
Down
indication
OFF with 'Up' / 'Down'
Menu BUS
Menu
V1.0 9
PROFIBUS-DP en
Note
Pump settings (in local operation) are not saved as new setpoints in
the Profibus master. Instead they are simply sent to the Profibus
master as status messages. As soon as the function "Release
setpoint" or "Release operating mode" is executed in the Profibus
master (automatically or manually), the settings from the Profibus
master apply.
Remote Control via PROFIBUS-DP
In remote control via PROFIBUS, orders are sent from the Profibus master
(e.g. SPS) to the bus slaves (e.g. the pump), which means the pump is
controlled by control signals from the Profibus master.
When using remote control via PROFIBUS, the following operating modes
are possible:
• Manual
• Contact mode
• Current control (0 - 20 mA and 4 - 20 mA)
Remote Start/Stop via PROFIBUS-DP
Starting and stopping the pump using remote control via
PROFIBUS has the same effects on the pump as external remote switching
off via a contact signal at the "Remote On / Off" input port.
External remote switching off, and switching off via PROFIBUS switch the
pump off independently of each other.
Local Operation
When operating the pump locally, the settings are made directly on the
pump.
All operating modes in manual, contact, or current control are available for
local operation:
• Manual
• Contact mode
• Batch dosing with manual/contact start
• Timer mode with manual/contact start
• Current control (0 - 20 mA and 4 - 20 mA)
Local operation can be restricted using the code function or lock 'run' (locks
the Start/Stop key).
10 15.720092-V1.0
PROFIBUS-DP en Operating the Pump Using PROFIBUS-DP
V1.0 11
PROFIBUS-DP en
Note
The maximum flow rate of the pump must not be exceeded!
For current control / analog operating mode, the setpoint (with or
without weighting) must always be assigned with reference to 20 mA.
Please refer to the additional description of current control in the
operating instructions for the pump!
Setting and executing additional control functions
• Remote On / Off (byte 2 / bit 0)
• Switches the pump on and off - for switching on, the pump cannot be
manually stopped or have been switched off via external remote on/
off. External remote switching off, and switching off via PROFIBUS
switch the pump off independently of each other.
• Slow mode (byte 2 / bit 1)
• Slow mode operation is switched on and off.
• Continuous operation for deaeration and suction (byte 2 / bit 2)
• Deletion (resetting) of the total capacity dosed (byte 2 / bit 3)
• The display of the total capacity dosed (since the pump was last
reset) is reset to zero.
• Error confirmation (byte 2 / bit 4)
• Confirmation of an error that has occurred and restarting of the pump,
if it is on 'Start' locally
• Dosing controller (byte 2 / bit 5)
• For TrueDos M, the dosing controller must always be switched on, for
TrueDos D, an installed dosing controller can be switched on and off.
Bit Byte 2: Control functions
Remote on/off
0 0 = Off
1 = On
Slow mode
1 0 = Off
1 = On
Continuous operation
2 0 = Off
1 = On
Deletion (resetting) of the total capacity dosed
3
0->1 = Reset the total capacity dosed display
Error confirmation
4
0->1 = Confirm error
Dosing controller
5 0 = Off
1 = On
6, 7 Reserve
12 15.720092-V1.0
PROFIBUS-DP en Operating the Pump Using PROFIBUS-DP
The following data is sent from the pump to the Profibus master via
PROFIBUS-DP:
• Dosing flow / volume flow in ml/h (byte 1,2)
• For TrueDos M (with activated dosing controller), the measured
volume flow is transferred,
• For TrueDos D, the entered setpoint is transferred (in ml/h).
• Display of the total capacity dosed (byte 3, 4)
• Display of the total capacity dosed since the last deletion
in dl (decilitres) .
• Error messages (byte 5, 6 / bit 15 - 0)
• Dosing controller
• Diaphragm breakage signal
• External pre-empty signal
• Empty signal
• Hall sensor/Motor monitoring
• Profibus communication
• Current control - for operating mode "manual" 4 - 20 mA, an error
message is sent if the current input is < 2 mA.
• Internal pre-empty signal (only TrueDos M)
Bit Byte 5, 6: Error messages
Dosing controller
0 0 = No error
1 = Error
Diaphragm breakage safety device (MBS)
1 0 = No error
1 = Error
Pre-empty signal
2 0 = No error
1 = Error
Empty signal
3 0 = No error
1 = Error
V1.0 13
PROFIBUS-DP en
14 15.720092-V1.0
PROFIBUS-DP en Operating the Pump Using PROFIBUS-DP
V1.0 15
PROFIBUS-DP en
16 15.720092-V1.0