RTU560

Data Sheet Bus Connection Unit 560BCU04


Doc.-No.: 1KGT 150 727 V003 1 1
Bus Connection Unit
560BCU04
Application
The Bus Connection Unit 560BCU04 R0001 is
designed to make the RTU560s TSI, TSO, Alarm
and Warning signals accessible to the outside.
By using the bus connection unit 560BCU04
R0001, up to 8 560CMUxx communication units
can be used in a rack configuration (23TP22,
560MPR03).
To expand the RTU560 system bus to another
rack (23TP22, 560MPR03), an 8 pole RJ 45 con-
nector is available. For cabling, a shielded 8 pole
RJ 45 patch cable can be used.
Characteristics
The Bus Connection Unit 560BCU04 R0001 is
used in the racks 23TP22 or 560MPR03. It is
available in two versions: The 560BCU04 R0001,
containing a basic board and a termination board,
and the 560BCU04 R0002, containing the exten-
sion boards for the connection of additional
CMUs.
The 560BCU04 R0001 basic board is mounted on
the 19 pole process interface connector of the
rightmost used CMU slot in the rack. The 2nd or
next CMUs are connected by using the
560BCU04 R0002 extension board. Via ribbon
cables, the 560BCU04 connects the RTU560
communications bus to all CMU slots.
The leftmost CMU needs a bus termination real-
ized by means of the 560BCU04 R0001 termina-
tion board. It is essential to always place the ter-
mination board as last board in the rack (see Fig.
3).
All supply voltages and control signals are inter-
faced by a ribbon cable connection from the rack
to the 560BCU04 R0001. To enable operation us-
ing a 23TP22 rack, +24 VDC needs to be con-
nected to a screw terminal connector.
The system signals ALARM and WARNING can
be accessed via relay contacts and are super-
vised with a watchdog function. If the trigger from
the communication unit is missing for more than
30 seconds, both relay contacts are activated and
the contacts are closed.
The external minute interrupt of a real time clock
560RTCxx is connected to the system via an in-
ternal isolated optical-coupler (TSI) and routed to
the time master of the RTU560 system. The mi-
nute pulse output (TSO) is available for other ap-
plications.
Also the signals for supervising redundant power
supply units are distributed.
If it is intended to use a single CMU inside a
standalone rack only a unit 560BCU04 R0003 is
required for correct bus termination (see Fig. 4).
Thus without usage of ALR, WRN, TSI, TSO and
supervision of redundant power supply units.
Figure 1: Function Block Diagram
560BCU04 R0001 Basic board
RTU560
Data Sheet Bus Connection Unit 560BCU04
Doc.-No.: 1KGT 150 727 V003 1 2
Figure 2: Basi c board, part 1 of 560BCU04 R0001
Figure 3: Extension board, 560BCU04 R0002
Figure 4: Termination board, part 2 of 560BCU04 R0001
RTU560
Data Sheet Bus Connection Unit 560BCU04
Doc.-No.: 1KGT 150 727 V003 1 3
Figure 5: Termination board 560BCU04 R0003
for si ngl e CPU usage
Figure 6: Assembl y 560MPR03, 560BCU04 R0001 and R0002
RTU560
Data Sheet Bus Connection Unit 560BCU04
Doc.-No.: 1KGT 150 727 V003 1 4
Figure 7: Assembl y 560MPR03 and 560BCU04 R0003
RTU560

Data Sheet Bus Connection Unit 560BCU04
Doc.-No.: 1KGT 150 727 V003 1 5
Technical Data
In addition to the general technical data of the
RTU560, the following applies:
Minute Pulse Input (TSI)
X11 Plug-in terminal strip 2-pole,
24 VDC input, isolated
Minute Pulse Output (TSO)
X10 Plug-in terminal strips 2-pole,
24 V DC output
Rack-to-Rack Interface
X17 RJ 45 connector 90
Signal Outputs
ALARM
WARNING
Plug-in terminal strips 2-pole
each
Relay contact Active closed, WARNING is
set also in case of ALARM.
1 A / 60 V DC / 30 W
Watchdog
Supervision
time
Approx. 30 seconds
Compliances
EMC
Environmental
Safety
EN550011, EN61000
EN60255, IEC60870
EN60950
Voltage Supply
Supply 5 V DC / approx. 80 mA
24 V DC / approx. 60 mA
Supply (external)
+24V Screw terminal connection
only in case of 23TP22 rack
Mechani cs
PCB 126 x 92 mm
Weight Approx. 0.1 kg
Connection Type
X19 19 pol. Process interface
connector
Environmental Conditi ons
Nominal operating
temperature range
Startup
Storage temperature
range
-25C +70C
-40C
-40C +85C
Relative Humidity
(EN60068 2-30)
5 95 %
(non condensing)
Ordering Information
560BCU04 R0001
(part 1: Basic board
part 2: Termination
board)
1KGT 022300 R0001
560BCU04 R0002
(Extension board)
1KGT 022300 R0002
560BCU04 R0003
(Termination board)
1KGT 022300 R0003
RTU560

Data Sheet Bus Connection Unit 560BCU04
Doc.-No.: 1KGT 150 727 V003 1 6
Note:
We reserve the right to make technical changes or modify the contents
of this document without prior notice. With regard to purchase orders,
the agreed particulars shall prevail. ABB AG does not accept any re-
sponsibility whatsoever for potential errors or possible lack of infor-
mation in this document.
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents - in whole or in parts is forbidden
without prior written consent of ABB AG.
Copyright2013 ABB