RTU560

Data Sheet
Command Output Monitoring 23BA23
Application
The 23BA23 board is intended for the use in the
Remote Terminal Unit RTU560.
The 23BA23 board should be installed if the output
circuit of an object command has to be checked before the actual command is given. The 23BA23
board executes an 1 out of n check. It checks if only
one interposing relay will be activated in the output
circuit. This is feasible only if all interposing relays
connected to one check circuit have the same resistance value.

ST
PST
TM1

B
U
S
M
O
D
U
L
E

The 23BA23 board is functional and pin-compatible


to the 23BA22 board only in a RTU560 system. The
essential additional tasks are:
Galvanic isolation of the check circuit
Suppression of line frequency during measuring

"GO
Relais

k1

TM0
CO
LOC

UDV
-

DC

X502

X501
+

DC
2

(1 out of n)
check

BO
-

k5

The 23BA23 board allows to check two different interposing relay types by using two separated check
circuits. The permissible tolerance range is defined
by means of parameters.
Up to 16 23BA23 boards can be used in one
RTU560.

23BA23

LOC

k4

k3

P2

k2

+ P2 -

P1

+ P1 2-pole connection

Further
23BA20

23BA20

W1
k01

A1

W2

k08
A8

k11
A9

k18
A16

Interposing relay
process
1: Monitoring switching voltage UD
2: Monitoring UD during command output
3: Resistance measurement of output circuit (1 out of n)-check

Characteristics

Fig.1: Block diagram 23BA23

Figure 1 shows the connection of a binary output


board 23BA20 and a 23BA23 board in two-pole activation for the (1 out of n)-check.

An auxiliary test voltage is not necessary. During


measuring the 23BA23 board switches the respective check circuit (P1 or P2) two-pole and
therefore separates both.

The check circuit for measuring the resistance of


the relay coil is galvanic isolated against the electronic voltage and against the switching voltage
(UD) of the interposing relays. This is done by
means of a galvanic isolated DC/DC-converter and
optocouplers.

In the (1 out of n)-check the 23BA23 board


measures the resistance value in the output circuit and compares this value with the configured
upper and lower limit values.
If the resistance value is within the limits the selected interposing relay can be activated. The
object command will be acknowledged positively.
If the measured resistance value is outside the
tolerance limits the 23BA23 blocks the output
and indicates the error to the CMU (CMU =
communication unit).
The central unit controls and coordinates the
appropriate 23BA20 and 23BA23 boards.
After the 23BA20 has switched on the 23BA23
gets the order to check and to output the object
command. The 23BA23 switches the output circuit to the check circuit via relay k3 (check circuit
1) or relay k5 (check circuit 2).The resistance is
determined by the arising measuring circuit voltage by output of a constant current. The output

Doc-No.: 1KGT 150 752 V001 1

RTU560
Data Sheet Command Output Monitoring 23BA23
constant current is defined by the configured upper
coil resistance. If the measured resistance value is
within the tolerance range, relay k3 (k5) is switched
off and relay k2 (k4) is switched on. After that relay
k1 switches the selected interposing relay and releases the object command.

+ UD -

Boost
k1

23BA23

+
UDV

X502

The limits of the coil resistance for the interposing


relay can be adjusted in steps of 10 in the range
of 100 to 10 000 by means of parameters. Line
frequency ripple voltages will be filtered by the A/D
converter.
The direct activation of process relays on electrical
apparatus (isolators, circuit-breakers) is possible by
using an additional booster relay (Fig. 2)
At command output not the output circuit itself is
switched by k1 but the booster relay (KB) instead.
This booster relay connects the switching voltage
UD1 via relay kB and k2 (k4) to the process relay
with higher switching current. This ensures that the
relay contacts k2 (k4) of the 23BA23 and k01 to
k18 of the 23BA20 are switched without load.
The selection of the booster relay depends on the
switching capacity on the electrical apparatus. It
must be taken into consideration that the relay
characteristics of the output boards 23BA20 and
23BA23 are not exceeded.
For diagnostic purposes switching through of the
switching voltage can be inhibited by pressing the
LOCAL key (LOC). The relays k2 (k4) and k1 then
will be blocked. All other output functions including
the (1 out of n)-check will be carried out.

KB

X501
+
BO

k3

kB
+
kB

UD1
-

k2

+ P1 -

23BA20

W2

A1

W1

An+8

Process relay
apparatus

Fig 2: Relay activation by means of a


booster relay
To ensure correct output the board carries out
several monitoring functions before and during
command output:
Monitoring of output duration and reset in
case of fault
Monitoring of switching voltage before and
during the command output
Operating states and faults are displayed by
light emitting diodes on the front panel of the
23BA23:
ST
PST:

Common malfunction
Display of process fault conditions
when monitoring responds (Command output error)
TM0,TM1: Display of active operating states
of the two test circuits
CO:
Display of active command output
Command Output)
LOC:
LOCAL function activated
The micro-controller of the board is responsible
for interactive communication with the RTU system bus. All configuration characteristics and
processing parameters are downloaded from the
communication unit. Therefore no parameter
settings on the board are required (Exception:
Line frequency for the ripple voltage suppression
function).

Doc-No.: 1KGT 150 752 V001 1

RTU560
Data Sheet Command Output Monitoring 23BA23
The board is equipped with both a serial and a parallel interface to the RTU system bus.
During initialization and operation the board carries
out a number of tests. If a fault occurs this is reported to the communication unit. All fault condi-

tions impairing the function of the board are displayed as common fault signal with the light
emitting diode (ST) on the front panel. A failure
of the board is detected by the communication
unit.

+ UD -

23BA23

23BA20

(1 out of n)-check

Check circuit P1/P2

k01 k02 k03 k04 k05 k06 k07 k08 k11 k12 k13 k14 k15 k16 k17 k18

"GO"Relay

k
1

W2 W1

+ P2
-

+ P1 -

Second group of interposing relays (different relay


type)

To additional 23BA20 boards


with same interposing relay type

Fig. 3 :-Block diagram: Object command output with (1 out of n)-check at 1.5 pole connection
+ UD
-

23BA20

23BA23
(1 out of n)-check

k1

Check circuit P1/P2

k01 k02 k03 k04 k05 k06 k07 k08 k11 k12 k13 k14 k15 k16 k17 k18

"GORelay

W2 W1

+ P2 -

+ P1 -

Second group of interposing


relays (different relay type)
To additional 23BA20 boards
with same interposing relay type

Fig. 4: Block diagram: Object command output with (1 out of n)-check at 2 pole connection

23BA20 relays (k01...k18)


(1 out of n) check
Switch over from CHECK to SWITCH
Output pulse given by GO relay

output pulse

Fig. 5: Timing diagram of command output: Coordination of 23BA23 and 23BA20 by communication
unit

Doc-No.: 1KGT 150 752 V001 1

RTU560
Data Sheet
Command Output Monitoring 23BA23
Technical Data

Power Supply

In addition to the general technical data of the


RTU560 the following applies:

Supply:

5 V / max. 130 mA
24 V / max. 70 mA without
24 V / max. 100 mA with
command output

Output Channels
Test and switching
circuits:
Measuring range of
test circuits:
Resolution:
Measuring current:
Ripple voltage:
suppression:
Input voltage range of
the measuring circuit
(this limits the max.
allowed ripple voltage):

Mechanical Layout
Printed circuit board:

100 ... 10000


10
0,25 5 mA

Front panel:
Weight:

16 2/3 / 50 and 60 Hz

Connection Type

3HE, Euro-card format


(160 x 100 mm)
4R, 1 slot (20 mm)
Approx. 0.2 kg

Connector:
- 0,5 ... + 6 V

Relay characteristics in connection


with 23BA23
Switching voltage (UD) Max. 60 V DC
Max. switching capacity:
- resitive load
60 W
- inductive load at
40 VA (at 60 V DC)
L/R = 30 ms

Indirect, 48 pole
Type F DIN 41612
Environmental Conditions
Temperature:
-20 - 70 C
Relative humidity:
5 ... 95 %
(non condensing)

Ordering Information
23BA23

1KGT 020 800 R0001

Characteristics in connection with a


booster relay
Switching voltage (UD)

Max. 60 V DC

Continuous current:

4A
(at object command
duration 25 sek.)

Note:
We reserve the right to make technical changes or modify
the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or
utilization of its contents - in whole or in parts is forbidden without prior
written consent of ABB AG.
Copyright 2011 ABB
All rights reserved

Doc-No.: 1KGT 150 752 V001 1