Preamble: Monitoring Water Quality
Preamble: Monitoring Water Quality
Preamble: Monitoring Water Quality
BACTERIOLOGICAL STANDARDS
I. Water entering the Distribution system Coliform count in any sample of 100 ml should be Zero. A
sample of the water entering the distribution system that does not conform to this standard calls for an
immediate investigation in to both the efficacy of the purification process and the method of sampling.
II.Water in the distribution system
1. E.coli count in 100ml of any sample should be zero. 2. Coliform organisms not more than 10 per
100 ml in any sample. 3. Coliform organisms should not be present in 100 ml of any two consecutive
samples or more than 5% of the samples collected for the year.
PRIVATE SAMPLES
Besides monitoring the Quality of water supplied by Metro Water, the C.M.W.S.S.B. facilitates the public to
assess the water quality of their own sources (Well / Bore Well water) by testing for Physical and Chemical
examination on nominal charges as follows:
The following parameters are tested for Physical and Chemical Examination: Colour and Transparency,
Odour, Turbidity (N.T.U.), Dissolved Solids mg/l, Calcium mg/l (as Ca), Magnesium mg/l (as Mg),
Total Hardness mg/l (as CaCO3), Chlorides mg/l (as Cl), Ammoniacal Nitrogen mg/l ( as N), Albuminoid
Nitrogen mg/l (as N), Nitrous Nitrogen mg/l (as N), Nitric Nitrogen mg/l ( as N), Oxygen absorbed mg/l,
(Tidy's 4 hrs test), Hydrogen ion concentration (pH), Alkalinity to Phenolphthalein mg/l (as CaCO3 ),
Alkalinity to Methyl orange mg/l (as CaCO 3 ), Sulphates mg/l (as SO4 ), Phosphates mg/l (as PO 4), Iron
mg/l (as Fe), Fluorides mg/l (as F) and Specific Conductance (micro siemens/cm) at 25 o C.
In case of water quality for Construction purpose the following parameters are tested for its suitability
1.To neutralise 200 ml of sample of water , using Phenolphthalein as an indicator, it should not require more
than 2.0 ml of 0.1 (N/10) Normal sodium hydroxide.
2.To neutralise 200 ml of sample of water, using methyl orange as an indicator, it should not require more
than 10 ml of 0.1 (N/10) Normal Hydro chloric acid.
3. Suspended matter, Sulphate (as SO4), Chlorides as Cl, Inorganic solids, Organic solids