International Log Building Standards
International Log Building Standards
International Log Building Standards
55
STANDARDS
COMMENTARY
Preface
1. In these Standards the word shall means
mandatory, and the word may means discretionary.
2. The 2000 Log Building Standards are comprised
of both the Standards and the Commentary.
Section 1 FOUNDATIONS
Shall conform to applicable building codes and
accepted engineering practice.
Section 2 LOG WALLS
2.A. Log Specifications
2.A.1. The minimum diameter of wall logs shall be
20 centimeters (8 inches).
2.A.2. Green or dry logs may be used for construction.
2.A.3. Logs shall have all bark removed, and shall
be of sound wood.
Table 2.A
RIGHT HAND
LEFT HAND
LESS THAN 1:30
STRAIGHT
MODERATE
1:20 TO 1:10
1:30 TO 1:20
SEVERE
Section 1 FOUNDATIONS
Like all buildings the foundation of a log building must be of sufficient design to support safely the loads imposed as determined from the character of the soil. In addition to the
loads imposed by gravity, the foundation is important in
connecting the building to the ground as it resists wind or
seismic forces and accelerations. Therefore the connection
between the building and the foundation must also be
capable of resisting the sliding, uplift and overturning associated with local wind and seismic conditions.
STANDARDS
COMMENTARY
Section 2.A.4 describes the ways builders can help hold spiral
logs in place in the walls. Logs that are more likely to twist
are used lower in the wall, where there is more weight on
them. For spiral types (a), (b), and (c) the standards can
be relaxed somewhat if you use four additional methods to
restrict twisting. A log that has at least two full notches is
more likely to stay put than a log with one notch (condition #1). A full notch is more stabilizing than a splice notch
(condition #2). A spiral log with a window sill cut-out is
more likely to behave like it is one piece if no more than
two-thirds of a logs diameter is removed (condition #3).
And, when a wall log extends beyond a notch more than 4'
to a door or window opening, this portion of the log is
more likely to twist (condition #4).
These tables refer to green logs, slope of grain will
change as logs dry.
Figure 2.A
2.B. Log Walls
Shall be constructed of logs laid in horizontal
courses, scribe-fit one to another, with interlocking notches at the corners.
2.C. Sill Logs
2.C.1. Shall be not less than 20 centimeters (8
inches) in diameter.
2.C.2. Shall be flattened on their bottom side for
their entire bearing length to a width of not
less than 10.2 centimeters (4 inches).
2.C.3. Shall not be in direct contact with masonry.
2.C.4. Shall be set on a vapor, weather, and air
barrier.
2.C.5. Shall have a drip cut or flashing that directs
water away from the underside of the sill log.
2.C.6. Shall be anchored to resist applicable wind
and seismic loads.
2.C.7. Shall be a minimum of 30.5 centimeters (12
inches) above grade
2.D. Long Grooves
2.D.1. Logs in walls shall have a continuous
scribe-fit long groove along the length of each
log. A long groove is required wherever a log
wall separates unheated from heated space,
or heated space from the exterior of the
building.
Sill Logs are the bottom logs of the building, the first logs above
the foundation in each wall.
2.C.1. See also the log specifications in Section 2.A.
2.C.2. A continuous sawn flat provides bearing area and stability
for sill logs.
2.C.3. Untreated wood should not be in direct contact with
masonry because of the likelihood of decay.
2.C.4. Caulks, sealants and gaskets can provide vapor, air and
water barriers.
2.C.5. To avoid decay, it is important that rainwater be directed
away from under the sill logs.
2.C.6. The amount and kind of anchoring depends upon local
conditions and codes. In areas of extreme wind and seismic load conditions, continuous through-bolting the full
height of the log wall to the foundation can be an effective
technique.
2.C.7. Sill logs can be prone to decay if they are too close to
grade and rainwater and soil splashes on them.
57
STANDARDS
COMMENTARY
Figure 2.D
2.D.2. Long grooves shall be self-draining or shall
have gaskets, and in all cases shall restrict
water, air, and insect infiltration.
2.D.3. The minimum width of the long groove shall
be 6.3 centimeters (2.5 inches) and this minimum width shall extend for no more than
30.5 centimeters (12 inches) in continuous
length. At all times, however, the long groove
shall conceal and protect through-bolts, pins,
dowels, kerfs, electrical holes, and the like,
and shall be wide enough to restrict weather
and insect infiltration.
2.D.4. The maximum width of the long groove
shall be three-eighths (3/8) of the log diameter at each point along the log. In cases of
extremely irregular log contours the width
may be increased to one-half (1/2) of the log
diameter, but this increased allowance shall
extend for no more than 46 centimeters (18
inches) in continuous length.
2.D.5. The long groove may have the following
cross-sectional profiles: rectangular, shallow
cove, W shaped, or double-scribed.
2.D.6. The depth to which the groove is cut shall
be no more than one-quarter (1/4) the diameter of the log (see also Section 2.J.2).
2.E. Log Extensions
2.E.1. The maximum length of log extensions shall
be based on weather protection criteria
described in Section 7.D.
2.E.2. The minimum length of log extensions shall
be 23 centimeters (9 inches) measured from
the edge of the notch to the end of the log
overhang. This standard applies to both interior and exterior log extensions. Dovetail corner
notches are exempt from this requirement.
2.E.3. Exterior log extensions shall not have a
tight fit to the log extensions below. See
Figure 3.B.3
58
STANDARDS
COMMENTARY
fastener
3/4" trim
(secure to 3/4" nailer only)
3/4" nailer
settling space
batt insulation
frame extension
if required
jamb trim
EXTERIOR
INTERIOR
15
sealant
Sill Log
Figure 2.H
ILBA Log Buiding Standards
59
STANDARDS
COMMENTARY
2.H.2. Figure 2.H.1 illustrates one way to install settling boards and
avoid water infiltration.
60
Plate Logs are the top logs on each wall. The roof framing rests on the
plate logs.
2.I.1. Wall plate logs are prone to twisting and shifting and need extra steps
to keep them in place. Square notches and lock notches can provide
restraint, as can any number of methods using bolts, threaded rod,
and pegs. The number, type, size and spacing of mechanical fasteners used for this purpose must be determined by accepted engineering practice. Continuous gable end plate logs are very effective at
resisting roof thrust, and so are recommended when it is necessary
to counteract these forces. When continuous gable end plate logs are
not used, or are not used in a manner that will resist roof thrust, this
force must be restrained or eliminated by other methods.
Roof uplift caused by wind, for example, can be counteracted by
locking together the top rounds of each wall. Smooth pins such as
dowels, smooth shaft steel, and wooden pegs are not sufficient for
preventing uplift, and this is why lag bolts and through-bolts are
specifically mentioned.
2.I.2-3. A recent study of Minnesota log homes found the intersection of
roof framing and the plate log to be the source of considerable air
infiltration. Special steps are required to make this area weathertight. Permanently sealing the vapor barrier to the plate log is an
accepted method of reducing air infiltration and retarding the migration of water vapor. Stapling the vapor retarder to the plate log is, by
itself, not sufficient.
2.J. Kerfing
2.J.1. The kerf is usually, though not always, a cut made with a chainsaw.
Logs are known to check, or crack, in those places where wood has
been removed closest to the pith, (or the center) of the log. Kerfing is
therefore an effective way to control the location of checks as green
logs dry.
Because dry logs already have seasoning checks, kerfing usually will
not change the location of checks, and therefore kerfing is not
required for dry logs.
2.J.2. The kerf must be deep enough to promote checking. Note that even
those long groove profiles that do not require kerfing (like the double-cut) are nevertheless required to be the depth of at least onequarter of the diameter of the log at every point along the top of the
log. (See also Section 2.D.5.)
After a log has both the kerf and the long groove cut, there must still
be at least one-half of the diameter of the log remaining un-cut.
Removing more than half the diameter of the log for kerf and groove
combined would weaken the log, and so should be avoided.
The amount of wood removed by the kerf (or special long groove
profile) must be between 1/4 and 1/2 of the log diameter (Section
2.D.6). When the kerf is 1/4 of the diameter of the log deep, then the
groove must be no more than 1/4 of the log diameter deep (1/4 plus
1/4 equals 1/2). When the kerf is 1/3 of the log diameter deep, then
the groove must be no more than 1/6 of the log diameter deep (1/6
plus 1/3 equals 1/2).
2.J.3. Because kerfs are not self-draining, that is, they can catch rainwater
and hold it, kerfs must always be protected by being fully covered by
the groove of the log above or by a notch (also see Section 2.D.3). In
practical terms, this means that kerfs are never visible in a completed wall.
STANDARDS
COMMENTARY
2.J.5. No kerf shall be required when the long-groove profile encourages checking on the top of wall logs as in Figure 2.D #2, as
long as the groove and kerf along the top of the log is at least
1/4 of the diameter of the log.
2.J.6. No kerf shall be required on the top of the half-log sill logs.
2.J.7. No kerf shall be cut in exterior log extensions.
frame wall
Plan View
log wall
Plan View
At least 55%
of log cross
section to
remain intact
at each notch.
FIGURE 2.K.1
2.K.2. Where wood is removed at the intersection of a log wall and
frame wall, the log wall shall have 55% or more of its cross-sectional area remain intact and uncut. See Figure 2.K.2 below.
55% or more of
cross section to
remain intact.
stud wall
let into a
log wall
PLAN VIEW
stud wall
let into a
log wall
55% or more of
cross section to
remain intact.
SECTION VIEW
CL
Figure 2.K.2
61
STANDARDS
COMMENTARY
2.K.3. Where two frame walls are closer than 122 centimeters (4
feet) to each other, and on opposite sides of a log wall, the
cross section of the log wall, after both dados are cut, must
have at least one-third of the wall area remain un-cut,
Figure 2.K.3 Note, also, that Section 2.K.1 still applies
each single cut shall leave 55% or more of the cross sectional area at each intersection un-cut and intact. See
Figure 2.K.3.
2.K.4. Cutting past the center of a log wall weakens it, and should
be avoided.
2.K.5. The first stud attached to the log wall must be fastened in
such a way as to allow the log wall to shrink and settle. One
common method is for lag screws to be attached to the logs
through vertical slots cut in the stud, not just round holes.
The lag screw and washer should be attached near the top
of the slot, and allowed to slide down the slot as the log wall
behind shrinks in height.
The frame wall must also allow a second floor, or the first
floor ceiling, to lose elevation as the log walls shrink in
height. (See Section 6 for more on settling.)
0"122 cm
less 4'than
(4 feet)
Figure 2.K.3
Plan View
Section 3 NOTCHES
3.A. Self-draining
Self-draining means that notch surfaces slope in a way that
restrict water from getting into areas where it can be held,
promoting decay. Interlocking means that notches will tend
to be stable when exposed to stresses and loads that the
corner can reasonably be anticipated to experience. Shrinkfit and compression-fit notches are designed to remain tight
fitting as the wall logs shrink in size as they dry. (Note that a
round notch which is designed to function as a compression-fit notch also meets this criteria.)
STANDARDS
COMMENTARY
This means that the notch, when in place over the log below,
should touch the log below only on its scribed edges, and
should touch at no other place. (If it touches on some inside
place it causes a hang up. ) The concave area created by
scooping out the notch in this way not only prevents internal
hang-ups, but also can be used to place materials that will
prevent air infiltration through the notch (gaskets and insulation, for example)an important consideration in all climates.
3.B.2. The scribed edge of notches should be sharp, strong, and
cleanly cut. The edges should not crush or permanently
deform under the load they support. Ragged wood fibers
indicate weak notch edges or a notch cut past the scribe line.
3.B.3. There are techniques that help keep notches tight as green
logs season and dry. One technique is to remove wood at the
top of a notch to allow the notch to compress onto the log
below as it dries. The extra wood removed from the top of a
notch creates a gap that should be nearly invisible when the
corner is assembled, that is, the gap should be covered by
the notch of the next log. Figure 3.B.3.
Cutting saddles, or saddle scarfs, is another technique that
helps. Saddle scarfs should not be simply chainsawed off,
but should be finished to a smoother surface. See Figure
3.B.3.
3.B.4. After a notch has been cut there shall be no less than one
third of the logs original cross-sectional area or diameter at
the notch remaining uncut. Removing more than two-thirds
of the log area or diameter by notching weakens a log,
sometimes even to the point where the log extensions may
break off. Good log selection avoids the problem of notches
that remove more than two-thirds the diameter of the log at
the notch.
3.B.5. Dovetail notches are unlike most other notches, and are not
required to follow the standards of Section 3.B.
63
STANDARDS
COMMENTARY
Figure 4.C
4.D. Where log or timber joists are supported by a log wall, the
wall logs shall be notched to receive the joists in such a way
as to prevent failure in the supporting log wall.
B
A
Figure 4.D
Notch A: Too shallow, inadequate bearing,
edge of long groove could break out.
Notch B: Insufficient wood left
below notch.
Notch C: Adequate support.
Square notch
Figure 4.F
STANDARDS
COMMENTARY
4.G. Where an interior beam extends through a wall to the exterior it shall be protected from the weather so that its structural integrity is maintained. The intersection of the beam and
wall shall be constructed to restrict weather and insect infiltration. See also Sections 7.F and 7.G.
4.H. Log joists and beams shall be flattened on top to a minimum of 2.5 centimeters (1 inch) where they support flooring or framing.
4.G. Cantilevered log beams that extend outside the building (even if they are only
notched through the wall and have relatively short log extensions) need protection against decay. Metal flashings,
waterproof membranes and wide roof
overhangs are recommended. The top of
any deck supported by logs or other
structural members must slope so that
water will drain in a manner that protects
the house from damage. This type of
detailing is important because of the susceptibility of unprotected log ends to
decay, and the great difficulty and
expense in repairing or replacing such
logs once degradation occurs.
Carpenter
rough opening
Log builder
rough opening
exterior trim
(secure to rough buck)
window jamb
(provide pilot holes for
fasteners connecting
jamb to rough buck.
interior trim
;;
;;;
;
shim space
rough buck with dado
cut to allow screw to
be mounted flush with
2x surface
steel angle
in kerf
wood screws
Figure 5.D.1
Carpenter
rough opening
Log builder
rough opening
window jamb
(provide pilot holes for
fasteners connecting
jamb to rough buck.
interior trim
shim space
exterior trim
(secure to rough buck)
rough buck
2x key
in keyway
Figure 5.D.2
5.E. All exterior sills shall be beveled to allow water to drain to
the outside face of the log wall.
ILBA Log Buiding Standards
65
STANDARDS
COMMENTARY
5.F. The position of openings in walls constructed of horizontal logs shall conform to the
following:
5.F.1. The distance from the side of window and
door openings to the centerline of an intersecting log wall shall be a minimum of
25.4 centimeters (10 inches) plus one half
the average wall log diameter.
25.4 cm (10")
+ 1/2 average
wall log diameter
CL
Section 6 SETTLING
window or
door opening
Figure 5.F
66
6.A. Settling is the term that describes the loss of log wall height
over time. The principal causes of settling are: 1) shrinkage of
log diameter as logs dry to an in-service condition (also
known as equilibrium moisture content, or EMC) and 2) compression of wood fibers under the load of the building. A third
component is slumping, which occurs if logs check only in
the long groove. Slumping is nearly eliminated by kerfing,
which is one reason why kerfing is required, see Section 2.J.
6.A.1. Green logs (defined in Section 2.A.2 as logs with greater
than 19% moisture content) must be allowed to settle 6% (60
millimeters per meter, or 3/4 inch per foot) of wall height.
Note that logs cannot be expected to shrink to equilibrium
moisture content or completely settle by air-drying alone, but
must be expected to complete settling only after a period of
up to 5 years as part of a heated building. The time needed to
reach equilibrium moisture content depends on a number of
variables, including wood species, log diameter, initial moisture content, interior temperature, and humidity and climate.
In general, logs do not shrink much in length, and so only the
loss of diameter must be considered for settling. With
extremely long logs (more than 15 meters (50 feet) long),
however, it is advisable to investigate the loss of length as
they dry.
6.A.2. Dry logs (defined in Section 2.A.2 as logs with moisture
content equal to, or less than, 19%) may settle nearly as
much as green logs. In part, this is because of the nature of
the definitions of dry and green19% MC is a dry log and
20% MC is a green log, but these two logs will obviously differ very little in the amount they actually shrink in diameter
as they approach EMC.
It must be assumed that log walls made of dry logs will settle.
Further, it should be assumed that logs stored outside, not
covered by a roof, are not at EMC, and will shrink. The
amount of shrinkage depends upon the difference between
the actual moisture content of the logs (as determined by a
moisture meter, for example) and the final in-service EMC.
STANDARDS
COMMENTARY
67
STANDARDS
COMMENTARY
Drip Line
Point B
8
Point A
ridge
Shading represents
the area protected by the
6:1 gable end overhang.
All logs on the building
are to be protected by a
similar area created by
a sheltering overhang.
8
8
1
8
1
1
1
Figure 7.D
1 1/2"
Figure 7.F
7.E. The roof shall protect all roof structural members
from the weather associated with the site of the
building.
7.F. Log roof beams shall be flattened on top to a minimum width of 3.8 centimeters (1-1/2 inches)
where they support lumber or finish materials.
See Figure 7F.
7.G. Where log structural members pass through exterior frame walls they shall be notched slightly to
receive interior and exterior wall coverings.
Expandable gaskets shall be installed to restrict
weather and insect infiltration. Roof members
shall be designed to meet structural requirements
even after such notching.
7.H. Flashing and an expandable gasket shall be used
where conventionally framed gable end walls
meet a plate log.
7.I. Roof structures shall be designed and constructed
to resist the uplift loads associated with local wind
and seismic events.
68
STANDARDS
COMMENTARY
Section 8 ELECTRICAL
Common practice is to pre-drill vertical holes in
the log wall, from long groove to long groove,
so that the holes are completely hidden from
view and no electrical wiring is exposed inside
or out. (A diameter of 32 mm or 1-1/4 is often
used as a minimum.) Do not use conduit in a
log wall. Do not attach conduit to a log wall
without allowing for settling.
Outlets and switch boxes are usually mortised
into a log so that the cover plate is even with
the surface of the log, or, more commonly,
flush with a portion of the log that has been
flattened for this purpose, see Figure 8.
Section 8 ELECTRICAL
Shall comply with applicable codes, with accommodations
where necessary for pre-wiring and wall settling
allowance. (See also Section 6.B.)
cross-section of log wall
A diameter of
32 mm (1-1/4")
is a suggested
as a minimum
Section 9 PLUMBING
9.A. Investigate carefully the need for settling
allowances in all plumbing for log homes. It is
usually preferable to run plumbing in frame
walls vertically without horizontal offsets,
though offsets are possible, if settling considerations are carefully made. Supply pipes to a
second floor can allow for settling by incorporating a loop that opens as the second floor
loses elevation. Waste and vent pipes can have
a slip joint. See Figure 9..A, 9.B, 9.C, 9.D.
9.B. It is usually not advisable to run plumbing
waste, vent or supply pipes through or within
log walls. If they must, however, pipes can run
perpendicular and level through a log wall. A
pipe that runs vertically up through a log wall,
or a pipe that runs horizontally within a log wall
(for example, lying in a long groove) can never
again be serviced without cutting the log wall
aparta drastic event that is difficult to repair.
Because supply lines are known to age, fill with
scale and sometimes to leak and because the
venting of sewer gases is a matter of health and
safety it is best to not locate plumbing in log
walls.
wire
switch or
receptacle box
cover plate
hole drilled
through logs
Figure 8
Section 9 PLUMBING
9.A. Shall comply with applicable codes, with settling considerations. See also Section 6.
9.B. A plumbing pipe shall travel through a log wall only
perpendicular to the long axis of the logs, and shall be
level or nearly level.
69
STANDARDS
70
COMMENTARY
Figure 9.A
Figure 9.C
Figure 9.B
Figure 9.D
ILBA Log Buiding Standards
STANDARDS
COMMENTARY
Figure 10
ILBA, 2000
71
COMMENTARY
2.A.2. Same as full scribe. For purposes of chinking application, check with manufacturer as to proper moisture
content of logs at the time of chinking application.
2.B. See chink gap section 2.D. for more details.
72
Chink Gap
2.D. The chink gap is a continuous air space separating
logs between interlocking corners and/or window and
door openings; it should be interrupted only by
required structural blocking.
2.D.1. Chink gaps will be continuous without holdups at
any point along the length.
2.D.3. The width of chinking from inside face to outside face
will vary depending upon chink gap size and log diameter. 8 is the minimum log diameter.
2.D.7. Blocking supports the log walls at the span and at
door and window openings. The flats, being level in
both directions and centered on the chink gap, prevent
blocking from rolling in the chink gap. An engineering
analysis is recommended to determine distance
between blocking. Additional blocking may be
required at load bearing points. If blocking supports
the log end at an opening, it must be installed so as
not to hinder settling, buck installation and chink
installation. The blocking should fall in a vertical column. In addition, pinning will provide stability
Examples of blocking:
1x4 or 2x4 kiln dried lumber, 4 long
3 1/2" x4 plywood 1/8 and thicker
3 1/2 x4x1/8 masonite
30# felt
See diagrams 2.D.1. and 2.D.2.
2.D.8. The amount and kind of wall pinning depends upon
local conditions and codes. In areas of extreme wind
and seismic load conditions, continuous through bolting the full height of the logs can be an effective technique.
Examples of wall pinning:
Wood dowels, smooth shaft steel pins, through-bolts,
lag screws, steel bar or log stub walls.
2.D.9. Synthetic chinking should always be installed according to manufacturers specifications. Moisture content
of the logs should be checked. Some manufacturers
recommend a 20% or less moisture content. For traditional or local chink mixtures, check local building or
energy codes to see if they are acceptable. Cohesion
failure of the chinking is preferred because it is easier,
faster and much less expensive to repair.
2.E.5. All extensions between heated and unheated space
shall be chinked to cover blocking and pins. Others
areas are optional.
2.F.1. Same as full scribe standards.
2.G.3. Same as full scribe standard.
STANDARDS
COMMENTARY
73