Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Yaskawa A1000

Download as pdf or txt
Download as pdf or txt
You are on page 1of 354
At a glance
Powered by AI
The manual provides instructions for programming and operating the YASKAWA AC Drive-A1000 HHP inverter drive.

The manual is intended to guide users on properly configuring and using the A1000 HHP drive to ensure safe and effective operation.

The manual covers topics such as initialization parameters, operation modes, speed control, tuning, troubleshooting, and specifications.

YASKAWA AC Drive-A1000 HHP

High Performance Vector Control Drive

Programming Manual
Type: CIMR-AU
Models: 400 V Class, 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty
575 V Class, 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty
690 V Class, 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty
To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.

1
2
3
4
5
6
7
8
A

MANUAL NO. SIEP YEAHHP 01

Parameter Details

1
B

Troubleshooting

2
C

Parameter List

A
D

MEMOBUS/Modbus

B
E

This Page Intentionally Blank

Copyright 2011 YASKAWA AMERICA, INC. All rights reserved.


No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means,
mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent
liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly
striving to improve its high-quality products, the information contained in this manual is subject to change without notice.
Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
2

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Table of Contents
1. PARAMETER DETAILS ................................................................................... 9
1.1 A: Initialization ........................................................................................................... 10
A1: Initialization ....................................................................................................................... 10
A2: User Parameters............................................................................................................... 17

1.2 b: Application............................................................................................................. 18
b1: Operation Mode Selection................................................................................................. 18
b2: DC Injection Braking and Short Circuit Braking................................................................. 25
b3: Speed Search.................................................................................................................... 27
b4: Delay Timers ..................................................................................................................... 32
b5: PID Control........................................................................................................................ 33
b6: Dwell Function................................................................................................................... 42
b7: Droop Control (CLV, CLV/PM) .......................................................................................... 42
b9: Zero Servo......................................................................................................................... 43

1.3 C: Tuning.................................................................................................................... 45
C1: Acceleration and Deceleration Times ............................................................................... 45
C2: S-Curve Characteristics.................................................................................................... 47
C3: Slip Compensation............................................................................................................ 47
C4: Torque Compensation ...................................................................................................... 50
C5: Automatic Speed Regulator (ASR) ................................................................................... 52
C6: Carrier Frequency............................................................................................................. 56

1.4 d: Reference Settings ............................................................................................... 58


d1: Frequency Reference........................................................................................................ 58
d2: Frequency Upper/Lower Limits ......................................................................................... 60
d3: Jump Frequency................................................................................................................ 61
d4: Frequency Reference Hold and Up/Down 2 Function....................................................... 62
d5: Torque Control .................................................................................................................. 66
d6: Field Weakening and Field Forcing................................................................................... 71
d7: Offset Frequency............................................................................................................... 72

1.5 E: Motor Parameters ................................................................................................. 73


E1: V/f Pattern for Motor 1....................................................................................................... 73
E2: Motor 1 Parameters .......................................................................................................... 76
E3: V/f Pattern for Motor 2....................................................................................................... 79
E4: Motor 2 Parameters .......................................................................................................... 80

1.6 F: Option Settings ..................................................................................................... 83


F1: PG Speed Control Card Settings ...................................................................................... 83
F2: Analog Input Card Settings ............................................................................................... 85
F3: Digital Input Card Settings ................................................................................................ 86
F4: Analog Monitor Card Settings ........................................................................................... 86
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Table of Contents
F5: Digital Output Card Settings........................................................................................................ 87
F6: Communication Option Card....................................................................................................... 88
CC-Link Parameters.......................................................................................................................... 89
PROFIBUS-DP Parameters .............................................................................................................. 90
CANopen Parameters ....................................................................................................................... 90
DeviceNet Parameters ...................................................................................................................... 91

1.7 H: Terminal Functions.........................................................................................................93


H1: Multi-Function Digital Inputs ....................................................................................................... 93
H2: Multi-Function Digital Outputs................................................................................................... 103
H3: Multi-Function Analog Inputs .................................................................................................... 113
H4: Multi-Function Analog Outputs ................................................................................................. 119
H5: MEMOBUS/Modbus Serial Communication ............................................................................. 120
H6: Pulse Train Input/Output........................................................................................................... 122

1.8 L: Protection Functions ....................................................................................................125


L1: Motor Protection ........................................................................................................................ 125
L2: Momentary Power Loss Ride-Thru............................................................................................ 131
L3: Stall Prevention ......................................................................................................................... 137
L4: Speed Detection........................................................................................................................ 141
L5: Fault Restart.............................................................................................................................. 143
L6: Torque Detection....................................................................................................................... 144
L7: Torque Limit .............................................................................................................................. 147
L8: Drive Protection......................................................................................................................... 148

1.9 n: Special Adjustments.....................................................................................................154


n1: Hunting Prevention.................................................................................................................... 154
n2: Speed Feedback Detection Control (AFR) Tuning.................................................................... 154
n3: High Slip Braking (HSB) and Overexcitation Braking................................................................ 155

1.10 o: Operator Related Settings............................................................................................157


o1: Digital Operator Display Selection............................................................................................. 157
o2: Digital Operator Keypad Functions ........................................................................................... 158
o3: Copy Function ........................................................................................................................... 160
o4: Maintenance Monitor Settings................................................................................................... 161
q: DriveWorksEZ Parameters.......................................................................................................... 162
r: DriveWorksEZ Connection Parameters ....................................................................................... 162

1.11 T: Motor Tuning .................................................................................................................163


T1: Parameter Settings during Induction Motor Auto-Tuning .......................................................... 163

1.12 U: Monitor Parameters ......................................................................................................166


U1: Operation Status Monitors ........................................................................................................ 166
U2: Fault Trace................................................................................................................................ 166
U3: Fault History.............................................................................................................................. 166
U4: Maintenance Monitors .............................................................................................................. 166
U5: PID Monitors ............................................................................................................................. 166
U6: Operation Status Monitors ........................................................................................................ 166
U8: DriveWorksEZ Monitors............................................................................................................ 167

2. TROUBLESHOOTING.......................................................................................... 169
2.1 Section Safety....................................................................................................................170
2.2 Motor Performance Fine-Tuning ......................................................................................172
Fine-Tuning V/f Control and V/f Control with PG............................................................................. 172
Fine-Tuning Open Loop Vector Control .......................................................................................... 172
Parameters to Minimize Motor Hunting and Oscillation .................................................................. 173
4

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Table of Contents

2.3 Drive Alarms, Faults, and Errors .....................................................................................175


Types of Alarms, Faults, and Errors................................................................................................ 175
Alarm and Error Displays ................................................................................................................ 175

2.4 Fault Detection ..................................................................................................................180


Fault Displays, Causes, and Possible Solutions ............................................................................. 180

2.5 Alarm Detection .................................................................................................................198


Alarm Codes, Causes, and Possible Solutions ............................................................................... 198

2.6 Operator Programming Errors .........................................................................................207


Operator Programming Error Codes, Causes, and Possible Solutions........................................... 207

2.7 Auto-Tuning Fault Detection ............................................................................................211


Auto-Tuning Codes, Causes, and Possible Solutions..................................................................... 211

2.8 Copy Function Related Displays .....................................................................................216


Tasks, Errors, and Troubleshooting ................................................................................................ 216

2.9 Diagnosing and Resetting Faults.....................................................................................218


Fault Occurs Simultaneously with Power Loss ............................................................................... 218
If the Drive Still has Power After a Fault Occurs ............................................................................. 218
Viewing Fault Trace Data After Fault .............................................................................................. 218
Fault Reset Methods ....................................................................................................................... 219

2.10 Troubleshooting without Fault Display ...........................................................................220


Common Problems.......................................................................................................................... 220
Cannot Change Parameter Settings ............................................................................................... 220
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External Run
Command ...................................................................................................................................... 221
Motor is Too Hot.............................................................................................................................. 222
Drive Does Not Allow Selection of the Desired Auto-Tuning Mode................................................. 223
oPE02 Error Occurs When Lowering the Motor Rated Current Setting .......................................... 223
Motor Stalls during Acceleration or Acceleration Time is Too Long................................................ 223
Drive Frequency Reference Differs from the Controller Frequency Reference Command ............. 224
Excessive Motor Oscillation and Erratic Rotation............................................................................ 224
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled .................................. 224
Noise From Drive or Motor Cables When the Drive is Powered On ............................................... 225
Ground Fault Circuit Interrupter (GFCI) Trips During Run .............................................................. 225
Connected Machinery Vibrates When Motor Rotates ..................................................................... 225
PID Output Fault.............................................................................................................................. 226
Insufficient Starting Torque ............................................................................................................. 226
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)..... 226
Output Frequency is Not as High as Frequency Reference............................................................ 226
Sound from Motor............................................................................................................................ 226
Motor Does Not Restart after Power Loss....................................................................................... 227

A. PARAMETER LIST............................................................................................... 229


A.1 Understanding Parameter Descriptions..........................................................................230
A1-02 Control Modes, Symbols, and Terms ................................................................................... 230

A.2 Parameter Groups .............................................................................................................231


A.3 A: Initialization Parameters ..............................................................................................232
A1: Initialization ............................................................................................................................... 232
A2: User Parameters....................................................................................................................... 233

A.4 b: Application.....................................................................................................................234
b1: Operation Mode Selection......................................................................................................... 234
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Table of Contents
b2: DC Injection Braking and Short Circuit Braking......................................................................... 235
b3: Speed Search............................................................................................................................ 236
b4: Timer Function .......................................................................................................................... 237
b5: PID Control................................................................................................................................ 237
b6: Dwell Function........................................................................................................................... 239
b7: Droop Control ............................................................................................................................ 239
b9: Zero Servo................................................................................................................................. 240

A.5 C: Tuning............................................................................................................................241
C1: Acceleration and Deceleration Times ....................................................................................... 241
C2: S-Curve Characteristics............................................................................................................ 242
C3: Slip Compensation.................................................................................................................... 242
C4: Torque Compensation .............................................................................................................. 243
C5: Automatic Speed Regulator (ASR) ........................................................................................... 244
C6: Carrier Frequency..................................................................................................................... 245

A.6 d: References.....................................................................................................................246
d1: Frequency Reference................................................................................................................ 246
d2: Frequency Upper/Lower Limits ................................................................................................. 247
d3: Jump Frequency........................................................................................................................ 247
d4: Frequency Reference Hold and Up/Down 2 Function............................................................... 248
d5: Torque Control .......................................................................................................................... 249
d6: Field Weakening and Field Forcing........................................................................................... 249
d7: Offset Frequency....................................................................................................................... 250

A.7 E: Motor Parameters .........................................................................................................251


E1: V/f Pattern for Motor 1............................................................................................................... 251
E2: Motor 1 Parameters .................................................................................................................. 252
E3: V/f Pattern for Motor 2............................................................................................................... 253
E4: Motor 2 Parameters .................................................................................................................. 254

A.8 F: Options...........................................................................................................................255
F1: PG Speed Control Card (PG-X3/PG-B3) .................................................................................. 255
F2: Analog Input Card (AI-A3)......................................................................................................... 257
F3: Digital Input Card (DI-A3).......................................................................................................... 257
F4: Analog Monitor Card (AO-A3) ................................................................................................... 257
F5: Digital Output Card (DO-A3) ..................................................................................................... 258
F6, F7: Communication Option Card............................................................................................... 258

A.9 H Parameters: Multi-Function Terminals ........................................................................263


H1: Multi-Function Digital Inputs ..................................................................................................... 263
H2: Multi-Function Digital Outputs................................................................................................... 267
H3: Multi-Function Analog Inputs .................................................................................................... 270
H4: Analog Outputs ......................................................................................................................... 273
H5: MEMOBUS/Modbus Serial Communication ............................................................................. 273
H6: Pulse Train Input/Output........................................................................................................... 274

A.10 L: Protection Function ......................................................................................................276


L1: Motor Protection ........................................................................................................................ 276
L2: Momentary Power Loss Ride-Thru............................................................................................ 277
L3: Stall Prevention ......................................................................................................................... 278
L4: Speed Detection........................................................................................................................ 279
L5: Fault Restart.............................................................................................................................. 280
L6: Torque Detection....................................................................................................................... 280
L7: Torque Limit .............................................................................................................................. 281
L8: Drive Protection......................................................................................................................... 282

A.11 n: Special Adjustment.......................................................................................................284


6

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Table of Contents
n1: Hunting Prevention.................................................................................................................... 284
n2: Speed Feedback Detection Control (AFR) Tuning.................................................................... 284
n3: High Slip Braking (HSB) and Overexcitation Braking................................................................ 284

A.12 o: Operator-Related Settings ...........................................................................................286


o1: Digital Operator Display Selection............................................................................................. 286
o2: Digital Operator Keypad Functions ........................................................................................... 286
o3: Copy Function ........................................................................................................................... 287
o4: Maintenance Monitor Settings................................................................................................... 287

A.13 DriveWorksEZ Parameters ...............................................................................................289


q: DriveWorksEZ Parameters.......................................................................................................... 289
r: DriveWorksEZ Connection Parameters ....................................................................................... 289

A.14 T: Motor Tuning .................................................................................................................290


T1: Induction Motor Auto-Tuning..................................................................................................... 290

A.15 U: Monitors.........................................................................................................................292
U1: Operation Status Monitors ........................................................................................................ 292
U2: Fault Trace................................................................................................................................ 294
U3: Fault History.............................................................................................................................. 296
U4: Maintenance Monitors .............................................................................................................. 296
U5: PID Monitors ............................................................................................................................. 299
U6: Operation Status Monitors ........................................................................................................ 299
U8: DriveWorksEZ Monitors............................................................................................................ 300

A.16 Control Mode Dependent Parameter Default Values .....................................................301


A1-02 (Motor 1 Control Mode) Dependent Parameters .................................................................. 301
E3-01 (Motor 2 Control Mode) Dependent Parameters .................................................................. 302

A.17 V/f Pattern Default Values.................................................................................................303


A.18 Defaults by Drive Model and Duty Rating ND/HD...........................................................304

B. MEMOBUS/MODBUS COMMUNICATIONS........................................................ 307


B.1 MEMOBUS/Modbus Configuration ..................................................................................308
B.2 Communication Specifications ........................................................................................309
B.3 Connecting to a Network ..................................................................................................310
Network Cable Connection.............................................................................................................. 310
Wiring Diagram for Multiple Connections ........................................................................................ 310
Network Termination ....................................................................................................................... 311

B.4 MEMOBUS/Modbus Setup Parameters ...........................................................................313


MEMOBUS/Modbus Serial Communication.................................................................................... 313

B.5 Drive Operations by MEMOBUS/Modbus........................................................................316


Observing the Drive Operation........................................................................................................ 316
Controlling the Drive........................................................................................................................ 316

B.6 Communications Timing...................................................................................................317


Command Messages from Master to Drive..................................................................................... 317
Response Messages from Drive to Master ..................................................................................... 317

B.7 Message Format ................................................................................................................318


Message Content ............................................................................................................................ 318
Slave Address ................................................................................................................................. 318
Function Code ................................................................................................................................. 318
Data................................................................................................................................................. 318
Error Check ..................................................................................................................................... 318
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Table of Contents

B.8 Message Examples ...........................................................................................................320


Reading Drive MEMOBUS/Modbus Register Contents .................................................................. 320
Loopback Test................................................................................................................................. 320
Writing to Multiple Registers............................................................................................................ 320

B.9 MEMOBUS/Modbus Data Table........................................................................................322


Command Data ............................................................................................................................... 322
Monitor Data.................................................................................................................................... 323
Broadcast Messages....................................................................................................................... 334
Fault Trace Contents....................................................................................................................... 335
Alarm Register Contents ................................................................................................................. 337

B.10 Enter Command.................................................................................................................338


Enter Command Types ................................................................................................................... 338
Enter Command Settings when Upgrading the Drive...................................................................... 338

B.11 Communication Errors .....................................................................................................339


MEMOBUS/Modbus Error Codes.................................................................................................... 339
Slave Not Responding..................................................................................................................... 339

B.12 Self-Diagnostics ................................................................................................................340

INDEX ................................................................................................................... 341

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1
Parameter Details
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12

A: INITIALIZATION................................................................................................10
B: APPLICATION...................................................................................................18
C: TUNING..............................................................................................................45
D: REFERENCE SETTINGS..................................................................................58
E: MOTOR PARAMETERS....................................................................................73
F: OPTION SETTINGS...........................................................................................83
H: TERMINAL FUNCTIONS...................................................................................93
L: PROTECTION FUNCTIONS............................................................................125
N: SPECIAL ADJUSTMENTS..............................................................................154
O: OPERATOR RELATED SETTINGS................................................................157
T: MOTOR TUNING..............................................................................................163
U: MONITOR PARAMETERS..............................................................................166

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.1 A: Initialization

1.1

A: Initialization

The initialization group contains parameters associated with initial drive setup, including parameters involving the display
language, access levels, initialization, and password.

u A1: Initialization
n A1-00: Language Selection
Selects the display language for the digital operator.
Note:

This parameter is not reset when the drive is initialized using parameter A1-03.

No.
A1-00

Parameter Name
Language Selection

Setting Range
0,1

Default
0

Setting Range
0 to 2

Default
2

Setting 0: English
Setting 1: Japanese

n A1-01: Access Level Selection


Allows or restricts access to drive parameters.
No.
A1-01

Parameter Name
Access Level Selection

Setting 0: Operation only

Access to only parameters A1-01, A1-04, and all U monitor parameters.


Setting 1: User Parameters

Access to only a specific list of parameters set to A2-01 through A2-32. These User Parameters can be accessed using the
Setup Mode of the digital operator.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)

All parameters can be viewed and edited.


Notes on Parameter Access

If the drive parameters are password protected by A1-04 and A1-05, parameters A1-00 through A1-03, A1-06, and all A2
parameters cannot be modified.
If a digital input terminal programmed for Program lockout (H1-oo = 1B) is enabled, parameter values cannot be
modified, even if A1-01 is set to 1 or 2.
If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the
digital operator until an Enter command is issued to the drive from the serial communication.

n A1-02: Control Method Selection


Selects the Control Method (also referred to as the control mode) that the drive uses to operate the motor. Parameter A1-02
determines the control mode for motor 1 when the drive is set up to run two motors.
Note:

No.
A1-02

When changing control modes, all parameter settings depending upon the setting of A1-02 will be reset to the default.

Parameter Name
Control Method Selection

Setting Range
0, 1, 2, 3

Default
2

Control Modes for Induction Motors (IM)


Setting 0: V/f Control for Induction Motors

Use this mode for simple speed control and for multiple motor applications with low demands to dynamic response or speed
accuracy. This control mode is also used when the motor parameters are unknown and Auto-Tuning cannot be performed. The
speed control range is 1:40.

10

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.1 A: Initialization
Setting 1: V/f Control with PG Speed Feedback

Use this mode for general-purpose applications that require high speed accuracy but do not require high dynamic response.
This control mode is also used when the motor parameters are unknown and Auto-Tuning cannot be performed. The speed
control range is 1:40.
Setting 2: Open Loop Vector Control

Use this mode for general, variable-speed applications with a speed control range of 1:200 that require precise speed control,
quick torque response, and high torque at low speed without using a speed feedback signal from the motor.
Setting 3: Closed Loop Vector Control

Use this mode for general, variable-speed applications that require precise speed control down to zero speed, quick torque
response or precise torque control, and a speed feedback signal from the motor. The speed control range is up to 1:1500.

n A1-03: Initialize Parameters


Resets parameters to default values. After initialization, the setting for A1-03 automatically returns to 0.
No.
A1-03

Parameter Name
Initialize Parameters

Setting Range
0, 1110, 2220, 3330, 5550

Default
0

Setting 1110: User Initialize

Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to
1: Set defaults.
Note:

User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to
clear the user-defined default values.

Setting 2220: 2-Wire Initialization

Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.
Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence on page 100 for more information on
digital input functions.
Setting 3330: 3-Wire Initialization

Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse
respectively. Refer to Setting 0: 3-Wire Sequence on page 94 for more information on digital input functions.
Setting 5550: oPE04 Reset

An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed
in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.
Notes on Parameter Initialization

The parameters shown in Table 1.1 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. Although
the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.
No.
A1-00
A1-02
C6-01
E1-03
F6-08
o2-04

Parameter Name
Language Selection
Control Method Selection
Duty Selection
V/f Pattern Selection
Communication Parameter Reset
Drive/kVA Selection

n A1-04, A1-05: Password and Password Setting


Parameter A1-04 enters the password when the drive is locked; parameter A1-05 is a hidden parameter that sets the password.
No.
A1-04
A1-05

Parameter Name
Password
Password Setting

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Setting Range

Default

0000 to 9999

0000

Parameter Details

Table 1.1 Parameters Not Changed by Drive Initialization

11

1.1 A: Initialization
How to Use the Password

The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to
unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following
parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01, A1-02,
A1-03, A1-06, and A2-01 through A2-33.
The instructions below demonstrate how to set password 1234. An explanation follows on how to enter that password to
unlock the parameters.
Table 1.2 Setting the Password for Parameter Lock
Step
1.

Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz

Turn on the power to the drive. The initial display appears.

U1-02= 0.00Hz LSEQ


U1-03= 0.00A LREF
JOG FWD FWD/REV

- MODE PRG
Programming

2.

Press

or

until the Parameter Setting Mode screen appears.


HELP FWD DATA

-PRMSET- PRG
Initialization

3.

Press

A1-00= 0
Select Language

to enter the parameter menu tree.

FWD

-PRMSET- PRG
Select Language

4.

F2

F1

Select the flashing digits by pressing

left

right

A1-00=

, or

0 *0*
English
FWD

-PRMSETPRG
Enter Password

5.

6.

Select A1-04 by pressing

Press

A1- 04 =
0
(0~9999)
0
FWD

while holding down

Note:

at the same time. A1-05 will appear.

A1-05 is hidden and will not display by pressing only

-PRMSETPRG
Select Password
A1- 05 =
04
(0~9999)
0
FWD

-PRMSETPRG
Select Password

7.

Press

A1- 05 = 0000
(0~9999)
0
FWD

-PRMSETPRG
Select Password

8.

9.

F2

F1

Use

Press

left

right

and

to enter the password.

to save what was entered.

A1-05= 1234
(0~9999)
0
FWD

Entry Accepted

-PRMSETPRG
Select Password

10. The display automatically returns to the display shown in step 6.

A1- 05 =
04
(0~9999)
0
FWD

12

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.1 A: Initialization
Table 1.3 Check if A1-02 is Locked (continuing from step 10 above)
Step

Display/Result
-PRMSETPRG
Control Method

1.

2.

Press

A1-02= 2 *2*
Open LoopVector

to display A1-02.

Press

FWD

, making sure that the setting values cannot be changed.


- MODE PRG
Programming

3.

Press

to return to the first display.


HELP FWD DATA

Table 1.4 Enter the Password to Unlock Parameters (continuing from step 3 above)
Step

Display/Result
-PRMSET- PRG
Initialization

1.

Press

to enter the parameter setup display.

A1-00= 0
Select Language

FWD

-PRMSET- PRG
Select Language

2.

F2

F1

Press

left

right

A1-00=

to select the flashing digits as shown.

0 *0*
English
FWD

-PRMSETPRG
Enter Password

3.

Press

to scroll to A1-04 and

A1- 04 =
0
(0~9999)
0
FWD

-PRMSETPRG
Enter Password

4.

Enter the password 1234.

A1- 04 = 1234
(0~9999)
0
FWD

5.

Press

to save the new password.

Entry Accepted

-PRMSETPRG
Enter Password

6.

Drive returns to the parameter display.

A1- 04 =
0
(0~9999)
0
FWD

-PRMSETPRG
Control Method

Press

and scroll to A1-02.

A1-02= 2 *2*
Open LoopVector

FWD

Parameter Details

7.

-PRMSETPRG
Control Method

8.

Press

to display the value set to A1-02. If the first 0 blinks, parameter settings are unlocked.

A1-02= 2 *2*
Open LoopVector

FWD

-PRMSETPRG
Control Method

9.

Use
and
to change the value if desired (though changing the control mode at this point is
not typically done).

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A1-02= 0 *2*
V/F Control
2
FWD

13

1.1 A: Initialization
Step
10.

Press

to save the setting, or press

Display/Result

to return to the previous display without saving changes.

Entry Accepted

-PRMSETPRG
Control Method

11.

A1-02= 0 *0*
V/F Control

The display automatically returns to the parameter display.

Note:

FWD

1. Parameter settings can be edited after entering the correct password.


2. Performing a 2-Wire or 3-Wire initialization resets the password to 0000.

n A1-06: Application Preset


Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters
to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
Setting 1: Water Supply Pump Application
Table 1.5 Water Supply Pump: Parameter Settings

No.
A1-02
b1-04
C1-01
C1-02
C6-01
E1-03
E1-07
E1-08
L2-01
L3-04

Name
Control Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Duty Rating
V/f Pattern Selection
Mid Output Frequency
Mid Output Frequency Voltage
Momentary Power Loss Operation Selection
Stall Prevention Selection during Deceleration

Default Setting
0: V/f Control
1: Reverse Prohibited
1.0 s
1.0 s
1: Normal Duty
0FH
30.0 Hz
50.0 V
1: Enabled
1: Enabled

Table 1.6 Water Supply Pump: User Parameters (A2-01 to A2-16)

No.
b1-01
b1-02

Parameter Name
Frequency Reference Selection
Run Command Selection

No.
E1-08
E2-01

b1-04

Reverse Operation Selection

H1-05

C1-01

Acceleration Time 1

H1-06

C1-02

Deceleration Time 1

H1-07

E1-03
E1-07

V/f Pattern Selection


Mid Output Frequency

L5-01

Parameter Name
Mid Output Frequency Voltage
Motor Rated Current
Multi-Function Digital Input Terminal S5 Function
Selection
Multi-Function Digital Input Terminal S6 Function
Selection
Multi-Function Digital Input Terminal S7 Function
Selection
Number of Auto Restart Attempts

Setting 2: Conveyor Application


Table 1.7 Conveyor: Parameter Settings

No.
A1-02
C1-01
C1-02

14

Parameter Name
Control Method Selection
Acceleration Time 1
Deceleration Time 1

Default Setting
0: V/f Control
3.0 s
3.0 s

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.1 A: Initialization
No.
C6-01
L3-04

Parameter Name
Duty Rating
Stall Prevention Selection during Deceleration

Default Setting
0: Heavy Duty
1: Enabled

Table 1.8 Conveyor: User Parameters (A2-01 to A2-16)

No.
A1-02
b1-01
b1-02
C1-01

Parameter Name
Control Method Selection
Frequency Reference Selection
Run Command Selection
Acceleration Time 1

No.
C1-02
E2-01
L3-04

Parameter Name
Deceleration Time 1
Motor Rated Current
Stall Prevention Selection during Deceleration

Setting 3: Exhaust Fan Application


Table 1.9 Exhaust Fan: Parameter Settings

No.
A1-02
b1-04
C6-01
E1-03
E1-07
E1-08
L2-01
L3-04

Parameter Name
Control Method Selection
Reverse Operation Selection
Duty Selection
V/f Pattern Selection
Mid Output Frequency
Mid Output Frequency Voltage
Momentary Power Loss Operation Selection
Stall Prevention Selection during Deceleration

Default Setting
0: V/f Control
1: Reverse Prohibited
1: Normal Duty
0FH
30.0 Hz
50.0 V
1: Enabled
1: Enabled

Table 1.10 Exhaust Fan: User Parameters (A2-01 to A2-16)

No.
b1-01
b1-02
b1-04

Parameter Name
Frequency Reference Selection
Run Command Selection
Reverse Operation Selection

No.
E1-07
E1-08
E2-01

b3-01

Speed Search Selection at Start

H1-05

C1-01

Acceleration Time 1

H1-06

C1-02

Deceleration Time 1

H1-07

E1-03

V/f Pattern Selection

L5-01

Parameter Name
Mid Output Frequency
Mid Output Frequency Voltage
Motor Rated Current
Multi-Function Digital Input Terminal S5 Function
Selection
Multi-Function Digital Input Terminal S6 Function
Selection
Multi-Function Digital Input Terminal S7 Function
Selection
Number of Auto Restart Attempts

Setting 4: HVAC Fan Application


Table 1.11 HVAC Fan: Parameter Settings

Parameter Name
Control Method Selection
Reverse Operation Selection
Run Command at Power Up
Duty Rating
Carrier Frequency Selection
Terminals P2 Function Selection

L2-01

Momentary Power Loss Operation Selection

L8-03
L8-38

Overheat Pre-Alarm Operation Selection


Carrier Frequency Reduction

Default Setting
0: V/f Control
1: Reverse Prohibited
1: Run command issued, motor operation start
1: Normal Duty
1: 2.0 kHz
39: Watt Hour Pulse Output
2: CPU Power Active - Drive will restart if power returns prior
to control power supply shut down.
4: Operation at lower speed
2: Enabled across entire frequency range.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

15

Parameter Details

No.
A1-02
b1-04
b1-17
C6-01
C6-02
H2-03

1.1 A: Initialization
Table 1.12 HVAC Fan: User Parameters (A2-01 to A2-16)

No.
b1-01
b1-02
b1-03
b1-04
C1-01
C1-02
C6-02
d2-01

Parameter Name
Frequency Reference Selection
Run Command Selection
Stopping Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Carrier Frequency Selection
Frequency Reference Upper Limit

No.
d2-02
E1-03
E1-04
E2-01
H3-11
H3-12
L2-01
o4-12

Parameter Name
Frequency Reference Lower Limit
V/f Pattern Selection
Max Output Frequency
Motor Rated Current
Terminal A2 Gain Setting
Terminal A2 Input Bias
Momentary Power Loss Operation Selection
kWh Monitor Initial Value Selection

Setting 5: Compressor Application


Table 1.13 Compressor: Parameter Settings

No.
A1-02
b1-04
C1-01
C1-02
C6-01
E1-03
L2-01
L3-04

Parameter Name
Control Method Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1
Duty Rating
V/f Pattern Selection
Momentary Power Loss Operation Selection
Stall Prevention Selection during Deceleration

Default Setting
0: V/f Control
1: Reverse Prohibited
5.0 s
5.0 s
0: Heavy Duty
0F Hex
1: Enabled
1: Enabled

Table 1.14 Compressor: User Parameters (A2-01 to A2-16):

No.
b1-01
b1-02
b1-04
C1-01
C1-02

Parameter Name
Frequency Reference Selection
Run Command Selection
Reverse Operation Selection
Acceleration Time 1
Deceleration Time 1

No.
E1-03
E1-07
E1-08
E2-01

Parameter Name
V/f Pattern Selection
Mid Output Frequency
Mid Output Frequency Voltage
Motor Rated Current

n A1-07: DriveWorksEZ Function Selection


Enables and disables the DriveWorksEZ program inside the drive.
DriveWorksEZ is a software package for customizing drive functionality or adding PLC functionality by the interconnection
and configuration of basic software function blocks. The drive performs user-created programs in 1 ms cycles.
Note:

1. If DriveWorksEZ has assigned functions to any of the multi-function output terminals, those functions will remain set to those terminals
even after disabling DriveWorksEZ.
2. For more information on DriveWorksEZ, contact a Yaskawa representative.

No.
A1-07

Parameter Name
DriveWorksEZ Function Selection

Setting Range
0 to 2

Default
0

Setting 0: DWEZ disabled


Setting 1: DWEZ enabled
Setting 2: Digital input

If a digital input is programmed for DWEZ enable/disable (H1-oo = 9F), DWEZ will be enabled when the input is opened.

16

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.1 A: Initialization

u A2: User Parameters


n A2-01 to A2-32: User Parameters 1 to 32
The user can select up to 32 parameters and assign them to parameters A2-01 through A2-32 to provide quicker access by
eliminating the need to scroll through multiple menus. The User Parameter list can also save the most recently edited
parameters.
No.

Parameter Name

Setting Range

A2-01 to A2-32

User Parameters 1 to 32

b1-01 to o4-13

Default
Determined by
A1-06 <1>

<1> A1-06 determines how parameters edited by the user are saved to the list of User Parameters, A2-01 through A2-32.

Saving User Parameters

To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then enter
the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01 to 1 to
restrict access so users can only set and refer to the parameters saved as User Parameters.

n A2-33: User Parameter Automatic Selection


Determines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to A2-32) for
quicker access.
No.

Parameter Name

Setting Range

A2-33

User Parameter Automatic Selection

0, 1

Default
Determined by
A1-06

Setting 0: Do not save list of recently edited parameters

Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.
Setting 1: Save list of recently edited parameters

Parameter Details

Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are saved
with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the User Parameters
using the Setup Mode of the digital operator.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

17

1.2 b: Application

1.2

b: Application

u b1: Operation Mode Selection


n b1-01: Frequency Reference Selection 1
Selects the frequency reference source 1 for the REMOTE mode.
Note:

1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will light and the STOP indicator will flash.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.

No.
b1-01

Parameter Name
Frequency Reference Selection 1

Setting Range
0 to 4

Default
1

Setting 0: Operator keypad

Using this setting, the frequency reference can be input by:


switching between the multi-speed references in the d1-oo parameters.
entering the frequency reference on the operator keypad.
Setting 1: Terminals (analog input terminals)

Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in Table 1.15 for the input
used.
Table 1.15 Analog Input Settings for Frequency Reference Using Voltage Signals
Parameter Settings
Terminal
A1
A2
A3

Signal Level
0 to 10 Vdc
-10 to +10 Vdc
0 to 10 Vdc

Signal Level
Selection
H3-01 = 0
H3-01 = 1
H3-09 = 0

-10 to +10 Vdc

H3-09 = 1

H3-10 = 0
(Frequency Reference Bias)

0 to 10 Vdc
-10 to +10 Vdc

H3-05 = 0
H3-05 = 1

H3-06 = 0
(Frequency Reference Bias)

Gain

Bias

H3-02 = 0
(Frequency Reference Bias)

H3-03

H3-04

H3-11

H3-12

Set DIP switch S1 on the


terminal board to V for
voltage input.

H3-07

H3-08

Set DIP switch S4 on the


terminal board to AI.

0 to 10 V

Drive

Drive
+V 10.5 V, 20 mA power supply

2k

Notes

Function Selection

+V 10.5 V, 20 mA power supply

4k

A1 Analog Input 1
A2 Analog Input 2

OR

-10 to 10 V

A1 Analog Input 1
A2 Analog Input 2

A3 Analog Input 3

A3 Analog Input 3

AC Analog input common

AC Analog input common

-V

-V

-10.5 V, 20 mA power supply

-10.5 V, 20 mA power supply

Figure 1.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1

Use the wiring example shown in Figure 1.1 for any other analog input terminals. When using input A2 make sure DIP switch
S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to Table 1.16 to set terminal A2 for current input.

18

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application
Table 1.16 Analog Input Settings for Frequency Reference Using a Current Signal
Terminal

A2

Signal
Level
4 to 20 mA

Signal Level
Selection
H3-09 = 2

0 to 20 mA

H3-09 = 3

Parameter Settings
Function
Gain
Selection
H3-10 = 0
(Frequency Bias)

H3-11

DIP switch S1
V

Notes

Bias
H3-12

Make sure to set DIP switch S1 on


the terminal board to I for
current input.

Drive

+V 10.5 V, 20 mA power supply


A1 Analog Input 1
0 or 4 to 20 mA

A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
-V

-10.5 V, 20 mA power supply

Figure 1.2 Setting the Frequency Reference as a Current Signal to Terminal A2

Switching between Main/Auxiliary Frequency References

The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs. Refer
to Multi-Step Speed Selection on page 58 for details on using this function.
Setting 2: MEMOBUS/Modbus Communications

This setting requires entering the frequency reference via the RS-485/422 serial communications port (control terminals R+,
R-, S+, S-).
Setting 3: Option card

This setting requires entering the frequency reference via an option board plugged into connector CN5-A on the drive control
board. Consult the option board manual for instructions on integrating the drive with the communication system.
Note:

If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Operator Programming
Error will be displayed on the digital operator and the drive will not run.

Setting 4: Pulse Train Input

This setting requires a pulse train signal to terminal RP to provide the frequency reference. Follow the directions below to
verify that the pulse signal is working properly.
Verifying the Pulse Train is Working Properly

Set b1-04 to 4 and set H6-01 to 0.


Set the H6-02 to the pulse train frequency value that equals 100% of the frequency reference.
Enter a pulse train signal to terminal RP and check for the correct frequency reference on the display.
Parameter Details

n b1-02: Run Command Selection 1


Determines the Run command source 1 in the REMOTE mode.
No.
b1-02

Parameter Name
Run Command Selection 1

Setting Range
0 to 3

Default
1

Setting 0: Operator

This setting requires entering the Run command via the digital operator RUN key and also illuminates the LO/RE indicator
on the digital operator.
Setting 1: Control Circuit Terminal

This setting requires entering the Run command via the digital input terminals using one of following sequences:
2-Wire sequence 1:
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

19

1.2 b: Application
Two inputs (FWD/Stop-REV/Stop). Set A1-03 to 2220 to initialize the drive and preset terminals S1 and S2 to these
functions. This is the default setting of the drive. Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2Wire Sequence on page 100.
2-Wire sequence 2:
Two inputs (Start/Stop-FWD/REV). Refer to Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2 on
page 101.
3-Wire sequence:
Three inputs (Start-Stop-FWD/REV). Set A1-03 to 3330 to initialize the drive and preset terminals S1, S2, and S5 to these
functions. Refer to Setting 0: 3-Wire Sequence on page 94.
Setting 2: MEMOBUS/Modbus Communications

This setting requires entering the frequency reference via the RS-485/422 serial communications port (control terminals R+,
R-, S+, S-).
Setting 3: Option Card

This setting requires entering the Run command via the communication option board by plugging a communication option
board into the CN5-A port on the control PCB. Refer to the option board manual for instructions on integrating the drive into
the communication system.
Note:

If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operator programming error will be displayed on the digital
operator and the drive will not run.

n b1-03: Stopping Method Selection


Selects how the drive stops the motor when the Run command is removed or when a Stop command is entered.
No.
b1-03

Parameter Name
Stopping Method Selection

Setting Range
0 to 3

Default
0

Setting 0: Ramp to Stop

When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the
active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed Control,
or Short Circuit Braking, depending on the selected control mode. Refer to b2-01: DC Injection Braking Start Frequency
on page 25 for details.
Setting 1: Coast to Stop

When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to
stop. The stopping time is determined by the inertia and the friction in the driven system.
Run
command

ON

Output
frequency

OFF

Drive output is shut off

Motor speed

Figure 1.3 Coast to Stop


Note:

After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do
not enter Run command until it has come to a complete stop. Use DC Injection at Start (Refer to b2-03: DC Injection Braking Time at
Start on page 26) or Speed Search (Refer to b3: Speed Search on page 27) to restart the motor before it has completely stopped.

Setting 2: DC Injection Braking to Stop

When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time
(L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC current set in parameter b2-02
into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly faster compared
to Coast to Stop.

20

Note:

This function is not available in the control modes for PM motors (A1-02 = 5, 6, 7).

Note:

PM motor control modes are not available in A1000 HHP drive models.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application
Run
command

ON

OFF
DC Injection Braking
with the current set in
b2-02

Output
frequency

Motor speed
Motor coasts

Minimum Baseblock
Time (L2-03)

Figure 1.4 DC Injection Braking to Stop

DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is
removed. It can be calculated by:
DC Injection brake time

(b2-04) 10 Output frequency


Max. output frequency (E1-04)

DC Injection braking time


b2-0410

b2-04

10%

Output frequency when


Stop command was entered

100%
(Maximum output
frequency)

Figure 1.5 DC Injection Braking Time Depending on Output Frequency


Note:

If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no
longer occurs.

Setting 3: Coast to Stop with Timer

When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start
if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t
after t has expired to start the drive.

Output
frequency

ON

OFF

ON

OFF

ON

Drive output shut off

Parameter Details

Run command

Run wait time t

Figure 1.6 Coast to Stop with Timer

The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

21

1.2 b: Application
Run wait time t
Active deceleration time

Min Baseblock Time (L2-03)

Min output
frequency

Output frequency
when Stop command
was entered

100%
(Max output
frequency)

Figure 1.7 Run Wait Time Depending on Output Frequency

n b1-04: Reverse Operation Selection


Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause
problems (e.g., air handling units, pumps, etc.).
No.
b1-04

Parameter Name
Reverse Operation Selection

Setting Range
0, 1

Default
0

Setting 0: Reverse operation enabled

Possible to operate the motor in both forward and reverse directions.


Setting 1: Reverse operation disabled

Drive disregards a Reverse run command or a negative frequency reference.

n b1-05: Action Selection below Minimum Output Frequency (CLV and CLV/PM)
Note:

PM motor control modes are not available in A1000 HHP drive models.

Sets the operation when the frequency reference is lower than the minimum output frequency set in parameter E1-09.
No.
b1-05

Parameter Name
Action Selection below Minimum Output Frequency

Setting Range
0 to 3

Default
0

Setting 0: Follow the Frequency Reference

The drive adjusts the motor speed following the speed reference, even if the frequency reference is below the setting of
parameter E1-09. When the Run command is removed and the motor speed is smaller than the setting of b2-01, Zero Speed
Control (not position lock) is performed for the time set in parameter b2-04 before the drive output shuts off.
Run
Command

OFF

ON

E1-09 Min.
Frequency
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.

Motor
Speed

Zero Speed
Control

Zero Speed
Control
b2-01 Zero
Speed Level

b2-03
Zero Speed Time at Start

E1-09
b2-04
Zero Speed Time at Stop

Figure 1.8 Run at the Frequency Reference

Setting 1: Coast to Stop

The motor starts when the frequency reference exceeds the parameter E1-09 setting. When the motor is running and the
frequency reference falls below E1-09, the drive output shuts off and the motor coasts. When the motor speed falls below the
zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.

22

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application
Run
Command

OFF

ON

E1-09 Min.
Frequency
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.

Motor
Speed

Motor
Coasts
b2-01 Zero
Speed Level

b2-03
Zero Speed Time at Start

Zero Speed
Control

b2-04
Zero Speed Time at Stop

Figure 1.9 Coast to Stop

Setting 2: Run at the minimum frequency

When a Run command is active and the frequency reference is smaller than the parameter E1-09 setting, the drive runs the
motor at the speed set in E1-09. When the Run command is removed, the drive decelerates the motor. As soon as the motor
speed reaches the zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
Run
Command

OFF

ON

E1-09 Min.
Frequency
Frequency
reference
IM: Initial Excitation
PM: Zero Spd. Contr.

Motor
Speed

Run at
E1-09

Run at
E1-09

Zero Speed
Control

b2-01 Zero
Speed Level
b2-04
Zero Speed Time at Stop

b2-03
Zero Speed Time at Start

Figure 1.10 Run at the Minimum Frequency

Setting 3: Zero Speed Control

The drive applies Zero Speed Control whenever the frequency reference setting is below the value of parameter E1-09. When
the Run command is removed, Zero Speed Control is activated for the time set in b2-04, even if it was already active before.
Run
Command

OFF

ON

E1-09 Min.
Frequency
Frequency
reference

Zero
IM: Initial Excitation Speed
Control
PM: Zero Spd. Contr.

Motor
Speed

Zero Speed
Control
b2-01 Zero
Speed Level

b2-03
Zero Speed Time at Start

E1-09
b2-04
Zero Speed Time at Stop

Figure 1.11 Zero Speed Control

n b1-06: Digital Input Reading


No.
b1-06

Name
Digital Input Reading

Setting Range
0, 1

Parameter Details

Defines how the digital inputs are read. The inputs are acted upon every 1 ms or 2 ms depending upon the setting.
Default
1

Setting 0: Read once (1 ms scan)

The state of a digital input is read once. If the state has changed, the input command is immediately processed. With this setting
the drive responds more quickly to digital inputs, but a noisy signal could cause erroneous operation.
Setting 1: Read twice (2 ms scan)

The state of a digital input is read twice. The input command is processed only if the state does not change during the double
reading. This reading process is slower than the Read once process, but it is more resistant to noisy signals.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

23

1.2 b: Application

n b1-07: LOCAL/REMOTE Run Selection


The drive has three separate control sources that can be switched using digital inputs (H1-oo = 1 (LOCAL/REMOTE
Selection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator. Refer to Setting 1: LOCAL/REMOTE
Selection on page 94, Refer to Setting 2: External Reference 1/2 Selection on page 95 and Refer to o2-01: LO/RE
(LOCAL/REMOTE) Key Function Selection on page 158 for details.
LOCAL: Digital operator. The digital operator sets the frequency reference and Run command.
REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.
REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16.
When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run command
may already be present at the location at which the source is being switched. In this case, use parameter b1-07 to determine
how the Run command is treated.
No.
b1-07

Parameter Name
LOCAL/REMOTE Run Selection

Setting Range
0, 1

Default
0

Setting 0: Run command must be cycled

When the Run command source differs between the old source and the new source (e.g., the old source was the terminals and
the new source is serial communication), and the Run command is active at the new source as the switchover occurs, the drive
will not start or the drive will stop operation if it was previously running. The Run command must be cycled at the new source
to restart the drive.
Setting 1: Accept Run command at the new source

When the Run command is active at the new source, the drive starts or continues operation if it was previously running.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel
from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.

n b1-08: Run command selection while in Programming Mode


As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being used
to adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode).
If required by the application, set b1-08 to allow the drive to run while in Programming Mode.
No.
b1-08

Parameter Name
Run Command Selection while in Programming Mode

Setting Range
0 to 2

Default
0

Setting 0: Disabled

A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled

A Run command is accepted in any digital operator mode.


Setting 2: Prohibit programming during run

It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be
displayed during Run.

n b1-14: Phase Order Selection


Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No.
b1-14

Parameter Name
Phase Order Selection

Setting Range
0, 1

Default
0

Setting Range
0 to 4

Default
0

Setting 0: Standard Phase Order


Setting 1: Switched Phase Order

n b1-15: Frequency Reference Selection 2


Refer to b1-01: Frequency Reference Selection 1 on page 18.
No.
b1-15

24

Parameter Name
Frequency Reference Selection 2

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application

n b1-16: Run Command Selection 2


Refer to b1-02: Run Command Selection 1 on page 19.
No.
b1-16

Parameter Name
Run Command Selection 2

Setting Range
0 to 3

Default
0

n b1-17: Run Command at Power Up


Determines whether an external Run command that is active during power up will start the drive.
No.
b1-17

Parameter Name
Run Command at Power Up

Setting Range
0, 1

Default
0

Setting 0: Run Command at Power Up Is Not Issued

Cycle the Run command to start the drive.


Note:

For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is issued at
power up, the RUN indicator LED will flash quickly.

Setting 1: Run Command at Power Up Is Issued

If an external Run command is active when the drive is powered up, the drive will begin operating the motor once the internal
start up process is complete.
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin
rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to
powering up the drive. Failure to comply may cause serious injury.

u b2: DC Injection Braking and Short Circuit Braking


These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.

n b2-01: DC Injection Braking Start Frequency


Active when Ramp to Stop is selected as the stopping method (b1-03 = 0).
No.

Name

Setting Range

b2-01

DC Injection Braking Start Frequency

0.0 to 10.0 Hz

Default
Determined by
A1-02

The function triggered by parameter b2-01 depends on the control mode that has been selected.
V/f, V/f w/PG, and OLV (A1-02 = 0, 1, 2)

For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output
frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency

DC Injection
Braking

Time
b2-04

Note:

If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency
falls to the value set to E1-09.

CLV (A1-02 = 3)
Note:

PM motor control modes are not available in A1000 HHP drive models.

For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at stop. When
the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter b2-04 provided
b1-05 is set to 0.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

25

Parameter Details

Figure 1.12 DC Injection Braking at Stop for V/f, V/f w/PG and OLV

1.2 b: Application
E1-09 Min. Frequency
b2-01 Zero Speed Level
Output
frequency

Zero Speed
Control

Time
b2-04

Figure 1.13 Zero Speed Control at Stop in CLV and CLV/PM


Note:

If b2-01 is set lower than the minimum frequency (E1-09), then Zero Speed Control begins at the frequency set to E1-09.

n b2-02: DC Injection Braking Current


Sets the DC Injection Braking current as a percentage of the drive rated current. The carrier frequency is automatically reduced
to 1 kHz when this parameter is set to more than 50%.
No.
b2-02

Name
DC Injection Braking Current

Setting Range
0 to 100%

Default
50%

The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft.
Increasing the current level will increase the amount of heat generated by the motor windings. Do not set this parameter higher
than the level necessary to hold the motor shaft.

n b2-03: DC Injection Braking Time at Start


Sets the time of DC Injection Braking (Zero Speed Control in CLV and CLV/PM) at start. Used to stop a coasting motor before
restarting it or to apply braking torque at start. Disabled when set to 0.00 s.
No.
b2-03
Note:

Name
DC Injection Braking Time at Start

Setting Range
0.00 to 10.00 s

Default
0.00 s

Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), use DC Injection or Speed Search to stop the
motor or detect motor speed before starting it. Otherwise, motor stalling and other faults can occur.

n b2-04: DC Injection Braking Time at Stop


Sets the time of DC Injection Braking (Zero Speed Control in CLV and CLV/PM) at stop. Used to completely stop a motor
with high inertia load after ramp down. Increase the value if the motor still coasts by inertia after it should have stopped.
Disabled when set to 0.00 s.

26

No.

Name

Setting Range

b2-04

DC Injection Braking Time at Stop

0.00 to 10.00 s

Default
Determined by
A1-02

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application

n b2-08: Magnetic Flux Compensation Value


Sets the magnetic flux compensation at start as a percentage of the no-load current value (E2-03). This function allows for the
development of more flux to facilitate starting machines that require high starting torque or motors with a large rotor time
constant.
No.
b2-08

Name
Magnetic Flux Compensation Value

Setting Range
0 to 1000%

Default
0%

When a Run command is issued, the DC current level injected into the motor changes linearly from the level set to b2-08 to
the level set to E2-03 within the time set to b2-03.

Output frequency
b2-08

E2-03
Magnetizing Current
Reference

b2-03

Time

Figure 1.14 Magnetic Flux Compensation

The level of the DC current injected to the motor is limited to 80% of the drive rated current or to the motor rated current,
whichever value is smaller.
Note:

1. If b2-08 is set below 100%, it can take a relatively long time for flux to develop.
2. If b2-08 is set to 0%, the DC current level will be the DC Injection current set to b2-02.
3. As DC Injection can generate a fair amount of noise, b2-08 may need to be adjusted to keep noise levels acceptable.

u b3: Speed Search


The Speed Search function allows the drive to detect the speed of a rotating motor shaft that is driven by external forces and
start the motor operation directly from the detected speed without first stopping the machine.
Example: When a momentary loss of power occurs, the drive output shuts off and the motor coasts. When power returns, the
drive can find the speed of the coasting motor and restart it directly.
For PM motors, only parameter b3-01 is needed to enable Speed Search.
For induction motors, the drive offers two types of Speed Search than can be selected by parameter b3-24 (Speed Estimation
and Current Detection). Both methods are explained below and followed by a description of all relevant parameters.
Current Detection Speed Search detects the motor speed by looking at motor current in IM motors. When Speed Search is
started it reduces the output frequency starting from either the maximum output frequency or the frequency reference while
increasing the output voltage using the time set in parameter L2-04. As long as the current is higher than the level set to b3-02,
the output frequency is lowered using the time constant set to b3-03. If the current falls below b3-02, the drive assumes that
the output frequency and motor speed are the same and accelerates or decelerates to the frequency reference.
Be aware that sudden acceleration may occur when using this method of Speed Search with relatively light loads.
Figure 1.15 illustrates Current Detection Speed Search operation after a momentary power loss (L2-01 must be set to 1 or 2):

Parameter Details

n Current Detection Speed Search (b3-24 = 0)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

27

1.2 b: Application
Output frequency before
momentary power loss
AC power
supply

ON

Decel time
set to b3-03

Waits for twice


as long as L2-04

OFF
Selected
frequency
reference

Output
frequency

Speed Search operation


current set to b3-02
Output
current

Min. Baseblock Time (L2-03)

b3-05

Figure 1.15 Current Detection Speed Search after Power Loss


Note:

After power is restored, the drive waits until the time set to b3-05 has passed before performing Speed Search. Thereby the Speed Search
may start not at the end of L2-03 but even later.

When Speed Search is applied automatically with the Run command, the drive waits for the minimum baseblock time set to
L2-03 before starting Speed Search. If L2-03 is lower than the time set to parameter b3-05, then b3-05 is used as the wait time.
Decel time set
set to b3-03

Run command

OFF

Waits for twice


as long as L2-04

ON

Max. output frequency


or the specified
frequency reference

Selected
frequency
reference

Output
frequency

b3-02

Output current
Minimum Baseblock Time (L2-03)

Figure 1.16 Current Detection Speed Search at Start or Speed Search Command by Digital Input

Notes on Using Current Detection Type Speed Search

Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection Speed
Search.
Current Detection Speed Search is not available when using OLV Control for PM motors.
Increase the minimum baseblock time set to L2-03 if an overcurrent or overvoltage fault occurs when performing Speed
Search after power is restored following a momentary power loss.

n Speed Estimation Type Speed Search (b3-24 = 1)


This method can be used for a single induction motor connected to a drive. Do not use this method if the motor is one or more
frame size smaller than the drive, at motor speeds above 200 Hz, or when using a single drive to operate more than one motor.
Speed Estimation is executed in the two steps described below:
Step 1: Back EMF Voltage Estimation

This method is used by Speed Search after baseblock (e.g., a power loss where the drive CPU continued to run and the Run
command was kept active). Here, the drive estimates the motor speed by analyzing the back EMF voltage and outputs the
estimated frequency and increases the voltage using the time constant set in parameter L2-04. After that, the motor is accelerated
or decelerated to the frequency reference starting from the detected speed. If there is not enough residual voltage in the motor
windings to perform the calculations described above, the drive will automatically proceed to step 2.

28

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application

AC power
supply

ON

Selected
frequency
reference

OFF
Starts at the speed
that was detected

Output
frequency

Output
current
Several miliseconds
Min. Baseblock Time
(L2-03)

b3 -05 <1>

Figure 1.17 Speed Search after Baseblock

<1> After AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than
the minimum baseblock time set to L2-03, the drive will wait until the time set to b3-05 has passed after power is restored
before starting Speed Search.
Step 2: Current Injection

Current Injection is performed when there is insufficient residual voltage in the motor after extended power losses, when Speed
Search is applied with the Run command (b3-01 = 1), or when an External search command is used.
This feature injects the amount of DC current set to b3-06 to the motor and detects the speed by measuring the current feedback.
The drive then outputs the detected frequency and increases the voltage using the time constant set to parameter L2-04 while
looking at the motor current.
The output frequency is reduced if the current is higher than the level in b3-02. When the current falls below b3-02, the motor
speed is assumed to be found and the drive starts to accelerate or decelerate to the frequency reference.
Decelerates at the Speed
Search decel time set to b3-03

Run command

OFF

Output
frequency

Waits twice as long as L2-04

ON
Frequency reference
set to the drive
Starts at the speed
speed that was detected

b3-02

Output
current

1.0 s

Min. Baseblock Time (L2-03) <1>

<1> The wait time for Speed Search (b3-05) determines the lower limit.
Notes on Using Speed Estimation Speed Search

Perform Stationary Auto-Tuning for Line-to-Line Resistance (T1-01 = 2). If the there is a change in the cable length between
the drive and motor.
Use Current Detection to search for speeds beyond 200 Hz if the application is running multiple motors from the same drive
or if the motor is considerably smaller than the capacity of the drive.
Speed Estimation may have trouble finding the actual speed if the motor cable is very long. Use Current Detection in these
instances.

n Speed Search Activation


Speed Search can be activated using any of the methods 1 through 5 described below. The Speed Search type must be selected
in parameter b3-24 independent of the activation method.
Method 1. Automatically activate Speed Search with every Run command. External Speed Search commands are ignored.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

29

Parameter Details

Figure 1.18 Speed Search at Start

1.2 b: Application
Method 2. Activate Speed Search using the digital input terminals.
Use the input functions for H1-oo in Table 1.17.
Table 1.17 Speed Search Activation by Digital Inputs

Setting
61
62

Description
External Search
Command 1
External Search
Command 2

b3-24 = 0
b3-24 = 1
Closed: Activate Current Detection Speed Search from the
maximum output frequency (E1-04).
Activate Speed Estimation
Closed: Activate Current Detection Speed Search from the Speed Search
frequency reference.

To activate Speed Search by a digital input, the input must be set together with the Run command or the Run command must
be entered after giving the Speed Search command.
Method 3. After automatic fault restart.
When the number of maximum fault restarts in parameter L5-01 is set higher than 0, the drive will automatically perform
Speed Search as specified by b3-24 following a fault.
Method 4. After momentary power loss.
This mode requires that the Power Loss Ride-Thru function is enabled during CPU operation (L2-01 = 1 or 2). Refer to L2-01:
Momentary Power Loss Operation Selection on page 131.
Method 5. After external baseblock is released.
The drive will resume the operation starting with Speed Search if the Run command is present and the output frequency is
above the minimum frequency when the Baseblock command (H1-oo = 8 or 9) is released. For this operation mode, set the
operation during an external Baseblock command to hold the output frequency (H1-13 = 0).

n b3-01: Speed Search Selection at Start


Determines if Speed Search is automatically performed when a Run command is issued.
No.

Parameter Name

Setting Range

b3-01

Speed Search Selection at Start

0, 1

Default
Determined by
A1-02

Setting 0: Disabled

This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed
Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled

This setting performs Speed Search when the Run command is entered. The drive begins running the motor once Speed Search
is complete.

n b3-02: Speed Search Deactivation Current


Sets the operating current for Speed Search as a percentage of the drive rated current. Normally there is no need to change
this setting. Lower this value if the drive has trouble restarting.
No.

Name

Setting Range

b3-02

Speed Search Deactivation Current

0 to 200%

Note:

Default
Determined by
A1-02

When parameter A1-02 = 0 (V/f Control) the factory default setting is 120. When parameter A1-02 = 2 (Open Loop Vector) the factory
default setting is 100.

n b3-03: Speed Search Deceleration Time


Sets the output frequency reduction ramp used by Current Detection Speed Search (b3-24 = 0) and by the Current Injection
Method of Speed Estimation (b3-24 = 1). The time entered into b3-03 will be the time to decelerate from maximum frequency
(E1-04) to minimum frequency (E1-09).
No.
b3-03

30

Name
Speed Search Deceleration Time

Setting Range
0.1 to 10.0 s

Default
2.0 s

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application

n b3-04: V/f Gain During Speed Search


During Speed Search, the output voltage calculated from the V/f pattern is multiplied with this value. Changing this value can
help reduce the output current during Speed Search.
No.

Name

Setting Range

b3-04

V/f Gain During Speed Search

10 to 100%

Note:

Default
Determined by
o2-04

Available control modes for parameter b3-04 vary by drive model:


CIMR-Ao2A0004 to 2A0415 and 4A0002 to 4A0675: Available when A1-02 = 0, 1.
CIMR-Ao4A0930 to 4A1200 and A1000 HHP : Available when A1-02 = 0.

n b3-05: Speed Search Delay Time


In cases where an output contactor is used between the drive and the motor, the contactor must be closed before Speed Search
can be performed. This parameter can be used to delay the Speed Search operation, giving the contactor enough time to close
completely.
No.
b3-05

Name
Speed Search Delay Time

Setting Range
0.0 to 100.0 s

Default
0.2 s

n b3-06: Output Current 1 During Speed Search


Sets the current injected to the motor at the beginning of Speed Estimation Speed Search as a factor of the motor rated current
set in E2-01 (E4-01 for motor 2). If the motor speed is relatively slow when the drive starts to perform Speed Search after a
long period of baseblock, it may be helpful to increase the setting value. The output current during Speed Search is automatically
limited by the drive rated current.
No.

Name

Setting Range

b3-06

Output Current 1 during Speed Search

0.0 to 2.0

Note:

Default
Determined by
o2-04

Use Current Detection Speed Search if Speed Estimation is not working correctly even after adjusting b3-06.

n b3-10: Speed Search Detection Compensation Gain


Sets the gain for the detected motor speed of the Speed Estimation Speed Search. Increase the setting only if an overvoltage
fault occurs when the drive restarts the motor.
No.
b3-10

Name
Speed Search Detection Compensation Gain

Setting Range
1.00 to 1.20

Default
1.05

n b3-14: Bi-Directional Speed Search Selection


Sets how the drive determines the motor rotation direction when performing Speed Estimation Speed Search.
No.

Parameter Name

Setting Range

b3-14

Bi-Directional Speed Search Selection

0, 1

Default
Determined by
A1-02

Setting 0: Disabled
Setting 1: Enabled

The drive detects the motor rotation direction to restart the motor.

n b3-17: Speed Search Restart Current Level


Sets the current level at which Speed Estimation is restarted as a percentage of drive rated current to avoid overcurrent and
overvoltage problems since a large current can flow into the drive if the difference between the estimated frequency and the
actual motor speed is too big when performing Speed Estimation.
No.
b3-17

Name
Speed Search Restart Current Level

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Setting Range
0 to 200%

Default
150%

31

Parameter Details

The drive uses the frequency reference to determine the direction of motor rotation to restart the motor.

1.2 b: Application

n b3-18: Speed Search Restart Detection Time


Sets the time for which the current must be above the level set in b3-17 before restarting Speed Search.
No.
b3-18

Name
Speed Search Restart Detection Time

Setting Range
0.00 to 1.00 s

Default
0.10 s

n b3-19: Number of Speed Search Restarts


Sets the number of times the drive should attempt to find the speed and restart the motor. If the number of restart attempts
exceeds the value set to b3-19, the SEr fault will occur and the drive will stop.
No.
b3-19

Name
Number of Speed Search Restarts

Setting Range
0 to 10

Default
3

Setting Range
0, 1

Default
0

n b3-24: Speed Search Method Selection


Sets the Speed Search method used.
No.
b3-24

Parameter Name
Speed Search Method Selection

Setting 0: Current Detection Speed Search


Setting 1: Speed Estimation Speed Search
Note:

Refer to Current Detection Speed Search (b3-24 = 0) on page 27 and Refer to Speed Estimation Type Speed Search (b3-24 = 1) on page
28 for explanations of the Speed Search methods.

n b3-25: Speed Search Wait Time


Sets the wait time between Speed Search restarts. Increase the wait time if problems occur with overcurrent, overvoltage, or
if the SEr fault occurs.
No.
b3-25

Name
Speed Search Wait Time

Setting Range
0.0 to 30.0 s

Default
0.5 s

u b4: Delay Timers


The timer function is independent of drive operation and can delay the switching of a digital output triggered by a digital input
signal and help eliminate chattering switch noise from sensors. An on-delay and off-delay can be set separately.
To enable the timer function, set a multi-function input to Timer input (H1-oo = 18) and set a multi-function output to
Timer output (H2-oo = 12). Only one timer can be used.

n b4-01, b4-02: Timer Function On-Delay, Off-Delay Time


b4-01 sets the on-delay time for switching the timer output. b4-02 sets the off-delay time for switching the timer output.
No.
b4-01
b4-02

Name
Timer Function On-Delay Time
Timer Function Off-Delay Time

Setting Range
0.0 to 3000.0 s
0.0 to 3000.0 s

Default
0.0 s
0.0 s

n Timer Function Operation


The timer function switches on when the timer function input closes for longer than the value set to b4-01. The timer function
switches off when the timer function input is open for longer than the value set to b4-02. The following diagram illustrates
the timer function operation:
Multi-function Contact
Input: Timer Function

ON

Multi-function Contact
Output: Timer Function

ON

b4-01

On (Closed)
Off (Open)

ON

On (Closed)
Off (Open)

ON

b4-02

b4-01

b4-02

Figure 1.19 Timer Operation

32

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application

u b5: PID Control


The drive has a built-in Proportional + Integral + Derivative (PID) controller that uses the difference between the target value
and the feedback value to adjust the drive output frequency to minimize deviation and provide accurate closed loop control
of system variables such as pressure or temperature.

n P Control
The output of P control is the product of the deviation and the P gain so that it follows the deviation directly and linearly. With
P control, only an offset between the target and feedback remains.

n I Control
The output of I control is the integral of the deviation. It minimizes the offset between target and feedback value that typically
remains when pure P control is used. The integral time (I time) constant determines how fast the offset is eliminated.

n D Control
D control predicts the deviation signal by multiplying its derivative (slope of the deviation) with a time constant, then adds
this value to the PID input. This way the D portion of a PID controller provides a braking action to the controller response and
can reduce the tendency to oscillate and overshoot.
D control tends to amplify noise on the deviation signal, which can result in control instability. Only use D control when
absolutely necessary.

n PID Operation
To better demonstrate PID functionality, the diagram below illustrates how the PID output changes when the PID input
(deviation) jumps from 0 to a constant level.
PID input
Time

PID output
I control
PID Output

D control

P control
Time

Figure 1.20 PID Operation

n Using PID Control


Applications for PID control are listed in the following table.

Speed Control
Pressure
Fluid Control
Temperature
Control

Description
Sensors Used
Machinery speed is fed back and adjusted to meet the target value. Synchronous control is Tachometer
performed using speed data from other machinery as the target value
Maintains constant pressure using pressure feedback.
Pressure sensor
Keeps flow at a constant level by feeding back flow data.
Flow rate sensor
Thermocoupler,
Maintains a constant temperature by controlling a fan with a thermostat.
Thermistor

Parameter Details

Application

n PID Setpoint Input Methods


The PID setpoint input depends on the PID function setting in parameter b5-01.
If parameter b5-01 is set to 1 or 2, the frequency reference in b1-01 (or b1-15) or one of the inputs listed in Table 1.18 becomes
the PID setpoint.
If b5-01 is set to 3 or 4, then the PID setpoint can be input from one of the sources listed in Table 1.18.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

33

1.2 b: Application
Table 1.18 PID Setpoint Sources

PID Setpoint Source


Analog Input A1
Analog Input A2
Analog Input A3
MEMOBUS/Modbus Register 0006 H
Pulse Input RP
Parameter b5-19
Note:

Settings
Set H3-02 = C
Set H3-10 = C
Set H3-06 = C
Set bit 1 in register 000F H to 1 and input the setpoint to register 0006 H
Set H6-01 = 2
Set parameter b5-18 = 1 and input the PID setpoint to b5-19

A duplicate allocation of the PID setpoint input will cause an oPE alarm.

n PID Feedback Input Methods


Input one feedback signal for normal PID control or input two feedback signals can for controlling a differential process value.
Normal PID Feedback

Input the PID feedback signal from one of the sources listed below:
Table 1.19 PID Feedback Sources

PID Feedback Source


Analog Input A1
Analog Input A2
Analog Input A3
Pulse Input RP
Note:

Settings
Set H3-02 = B
Set H3-10 = B
Set H3-06 = B
Set H6-01 = 1

A duplicate allocation of the PID feedback input will cause an oPE alarm.

Differential Feedback

The second PID feedback signal for differential feedback can come from the sources listed below. The differential feedback
function is automatically enabled when a differential feedback input is assigned.
Table 1.20 PID Differential Feedback Sources

PID Differential Feedback Source

Note:

34

Settings

Analog Input A1

Set H3-02 = 16

Analog Input A2
Analog Input A3

Set H3-10 = 16
Set H3-06 = 16

A duplicate allocation of the PID differential feedback input will cause an oPE alarm.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Off

Z-1

PID Soft
Starter b5-17

PID Feedback
(U5-01)

not B

not 1

not 2

not C

+
Derivative
+
Time 2 or 4
b5-05
b5-01
1 or 3

PID Set Point


(U5-04)

Adjusted
PID Feedback
(U5-06)

PID SFS Cancel DI


H1-oo=34
On

b5-01 = 3/4

not 1

PID Differential
Feedback
(U5-05)

H3-02/10
= 16

not 16

H3-02/10=B

H6-01=1

Reg. 0Fh, bit 1


1

H6-01=2

H3-02/10=C

b5-18=1

b5-01 = 1/2

PID Mode

Parameter Details

Analog Input A1/A2/A3

Analog Input A1/A2/A3

Pulse Input

PID Feedback

MEMOBUS Reg. 0006h

Pulse Input

Analog Input A1/A2/A3

b5-19

PID Target

Pulse Input

Option Card

Serial Comm

Analog Input A1/A2/A3

Frequency Reference 1 to 16
d1-01 to d1-16

Frequency
Reference
b1-01/15

PID Input
Limit
b5-35

PID Input
(U5-02)

0
1
PID Input
Characteristic
H1-oo=35 or
b5-09

-1

Proportional
Gain
b5-02
1

I-time
b5-03
1/s

Z-1

Integral Hold
H1-oo=31

PID Ouput
(U5-03)

+
+

+
+

Derivative
Time

b5-05

Z-1

0
1

+ +

2 or 4

1 or 3

Lower Limit 0

Upper Limit
Fmax x109%

-1

PID Output
Characteristic
b5-09

b5-08

PID Delay
Time

Lower Limit
Fmax x109%

Upper Limit
Fmax x109%

PID Output
Upper/Lower
Limit
b5-06 / b5-34

b5-01

Integral Reset
H1-oo=30

I - limit
b5-04

Enabled

Disabled

PID disable when:


- b5-01=0
- a JOG Command is Input
- PID Disable by Digital Input Enabled

+
-

SFS
C1-oo

b5-07

PID Offset

PID Output
Gain

b5-10

Always 1 when
b5-01 = 3/4

RUN
On/Off

Output
Frequency

Enable / Disable Reverse


Operation when PID
Output is Negative

b5-11

Delay
Timer

b5-16

Sleep Function

b5-15
Sleep Level

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual
+

Frequency Reference

1.2 b: Application

n PID Block Diagram

Figure 1.21 PID Block Diagram

35

1.2 b: Application

n b5-01: PID Function Setting


Enables or disables the PID operation and selects the PID operation mode.
No.
b5-01

Parameter Name
PID Function Setting

Setting Range
0 to 4

Default
0

Setting 0: PID disabled


Setting 1: Output frequency = PID output 1

The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.
Setting 2: Output frequency = PID output 2

The PID controller is enabled and the PID output builds the frequency reference. The PID feedback is D controlled.
Setting 3: Output frequency = frequency reference + PID output 1

The PID controller is enabled and the PID output is added to the frequency reference. The PID input is D controlled.
Setting 4: Output frequency = frequency reference + PID output 2

The PID controller is enabled and the PID output is added to the frequency reference. The PID feedback is D controlled.

n b5-02: Proportional Gain Setting (P)


Sets the P gain applied to the PID input. Larger values will tend to reduce the error but may cause oscillations if set too high,
while lower values may allow too much offset between the setpoint and feedback.
No.
b5-02

Name
Proportional Gain Setting (P)

Setting Range
0.00 to 25.00

Default
1.00

n b5-03: Integral Time Setting (I)


Sets the time constant used to calculate the integral of the PID input. The shorter the integral time set to b5-03, the faster the
offset will be eliminated. If the integral time is set too short, however, overshoot or oscillation may occur. To turn off the
integral time, set b5-03 to 0.00.
No.
b5-03

Name
Integral Time Setting (I)

Setting Range
0.0 to 360.0 s

Default
1.0 s

n b5-04: Integral Limit Setting


Sets the maximum output possible from the integral block as a percentage of the maximum frequency (E1-04).
No.
b5-04
Note:

Name
Integral Limit Setting

Setting Range
0.0 to 100.0%

Default
100.0%

On some applications, especially those with rapidly varying loads, the output of the PID function may show a fair amount of oscillation.
Program b5-04 to apply a limit to the integral output and suppress this oscillation.

n b5-05: Derivative Time (D)


Sets the time the drive predicts the PID input/PID feedback signal based on the derivative of the PID input/PID feedback.
Longer time settings improve the response but can cause vibrations, while shorter time settings reduce the overshoot but reduce
controller responsiveness. D control is disabled by setting b5-05 to zero seconds.
No.
b5-05

Name
Derivative Time (D)

Setting Range
0.00 to 10.00 s

Default
0.00 s

n b5-06: PID Output Limit


Sets the maximum output possible from the entire PID controller as a percentage of the maximum frequency (E1-04).
No.
b5-06

Name
PID Output Limit

Setting Range
0.0 to 100.0%

Default
100.0%

n b5-07: PID Offset Adjustment


Sets the offset added to the PID controller output as a percentage of the maximum frequency (E1-04).
36

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application
No.
b5-07

Name
PID Offset Adjustment

Setting Range
-100.0 to 100.0%

Default
0.0%

n b5-08: PID Primary Delay Time Constant


Sets the time constant for the filter applied to the output of the PID controller. Normally, change is not required.
No.
b5-08
Note:

Name
PID Primary Delay Time Constant

Setting Range
0.00 to 10.00 s

Default
0.00 s

Useful when there is a fair amount of oscillation or when rigidity is low. Set to a value larger than the cycle of the resonant frequency.
Increasing this time constant may reduce the responsiveness of the drive.

n b5-09: PID Output Level Selection


Reverses the sign of the PID controller output signal. Normally a positive PID input (feedback smaller than setpoint) leads to
positive PID output.
No.
b5-09

Parameter Name
PID Output Level Selection

Setting Range
0, 1

Default
0

Setting 0: Normal Output

A positive PID input causes an increase in the PID output (direct acting).
Setting 1: Reverse Output

A positive PID input causes a decrease in the PID output (reverse acting).

n b5-10: PID Output Gain Setting


Applies a gain to the PID output and can be helpful when the PID function is used to trim the frequency reference (b5-01 = 3
or 4).
No.
b5-10

Name
PID Output Gain Setting

Setting Range
0.00 to 25.00

Default
1.00

n b5-11: PID Output Reverse Selection


Determines whether a negative PID output reverses the direction of drive operation. This parameter has no effect when the
PID function trims the frequency reference (b5-01 = 3 or 4) and the PID output will not be limited (same as b5-11 = 1).
No.
b5-11

Parameter Name
PID Output Reverse Selection

Setting Range
0, 1

Default
0

Setting 0: Reverse Disabled

Negative PID output will be limited to 0 and the drive output will be stopped.
Setting 1: Reverse Enabled

Negative PID output will cause the drive to run in the opposite direction.
The PID feedback loss detection function detects broken sensors or broken sensor wiring. It should be used when PID control
is enabled to prevent critical machine conditions (e.g., acceleration to max. frequency) caused by a feedback loss.
Feedback loss can be detected in two ways:
Feedback Low Detection
Detected when the feedback falls below a certain level for longer than the specified time. This function is set up using
parameters b5-12 to b5-14.
Feedback High Detection
Detected when the feedback rises above a certain level for longer than the specified time. This function is set up using
parameters b5-12, b5-36, and b5-37.
The following figure illustrates the working principle of feedback loss detection when the feedback signal is too low. Feedback
high detection works in the same way.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

37

Parameter Details

n PID Feedback Loss Detection

1.2 b: Application
PID feedback value

PID
Feedback
Detection
Loss Level
(b5-13)
no FbL
detection
PID Feedback
Loss Detection Time
(b5-14)

time
FbL detection

PID Feedback
Loss Detection Time
(b5-14)

Figure 1.22 PID Feedback Loss Detection

n b5-12: PID Feedback Loss Detection Selection


Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.
No.
b5-12

Parameter Name
PID Feedback Loss Detection Selection

Setting Range
0 to 5

Default
0

Setting 0: Digital Output Only

A digital output set for PID feedback low (H2-oo = 3E) will be triggered if the PID feedback value is below the detection
level set to b5-13 for the time set to b5-14 or longer. A digital output set for PID feedback high (H2-oo = 3F) will be
triggered if the PID feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a
fault nor an alarm is displayed on the digital operator and the drive will continue operation. The output resets when the feedback
value leaves the loss detection range.
Setting 1: Feedback Loss Alarm

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a FBL - Feedback Low
alarm will be displayed and a digital output set for PID feedback low (H2-oo = 3E) will be triggered. If the PID feedback
value exceeds the level set to b5-36 for longer than the time set to b5-37, a FBH - Feedback High alarm will be displayed
and a digital output set for PID feedback high (H2-oo = 3F) will be triggered. Both events trigger an alarm output (H1oo = 10). The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection
range.
Setting 2: Feedback Loss Fault

If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a FbL - Feedback Low
fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a FbH
- Feedback High fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the
motor.
Setting 3: Digital output only, even if PID is disabled by digital input

Same as b5-12 = 0. Detection remains active when PID is disabled by a digital input (H1-oo = 19).
Setting 4: Feedback loss alarm, even if PID is disabled by digital input

Same as b5-12 = 1. Detection remains active when PID is disabled by a digital input (H1-oo = 19).
Setting 5: Feedback loss fault, even if PID is disabled by digital input

Same as b5-12 = 2. Detection remains active when PID is disabled by a digital input (H1-oo = 19).

n b5-13: PID Feedback Low Detection Level


Sets the feedback level used for PID feedback low detection. The PID feedback must fall below this level for longer than the
time set to b5-14 before feedback loss is detected.
No.
b5-13

Name
PID Feedback Low Detection Level

Setting Range
0 to 100%

Default
0%

n b5-14: PID Feedback Low Detection Time


Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.

38

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application
No.
b5-14

Name
PID Feedback Low Detection Time

Setting Range
0.0 to 25.5 s

Default
1.0 s

n b5-36: PID Feedback High Detection Level


Sets the feedback level used for PID feedback high detection. The PID feedback must exceed this level for longer than the
time set to b5-37 before feedback loss is detected.
No.
b5-36

Name
PID Feedback High Detection Level

Setting Range
0 to 100%

Default
100%

n b5-37: PID Feedback High Detection Time


Sets the time that the PID feedback must exceed the value set to b5-36 before feedback loss is detected.
No.
b5-37

Name
PID Feedback High Detection Time

Setting Range
0.0 to 25.5 s

Default
1.0 s

n PID Sleep
The PID Sleep function stops the drive when the PID output or the frequency reference falls below the PID Sleep operation
level for a certain time. The drive will resume operating when the PID output or frequency reference rise above the PID Sleep
operation level for the specified time. An example of PID Sleep operation appears in the figure below.
PID Output
PID Sleep Level ( b5-15)
Sleep Delay Time
Internal Run
command

b5-16
Run

b5-16

Sleep Delay Time

Stop
Run command enabled

External Run
command
During Run

Continues to output During Run

Figure 1.23 PID Sleep Operation

Notes on using the PID Sleep function

The PID Sleep function is active even when PID control is disabled.
The PID Sleep function stops the motor according to the stopping method set to b1-03.
The parameters necessary to control the PID Sleep function are explained below.

n b5-15: PID Sleep Function Start Level

No.
b5-15

Name
PID Sleep Function Start Level

Setting Range
0.0 to 400.0 Hz

Default
0.0 Hz

Setting Range
0.0 to 25.5 s

Default
0.0 s

Parameter Details

Sets the level that triggers PID Sleep.


The drive goes into Sleep mode if the PID output or frequency reference is smaller than b5-15 for longer than the time set to
b5-16. The drive resumes operation when the PID output or frequency reference is above b5-15 for longer than the time set
to b5-16.

n b5-16: PID Sleep Delay Time


Sets the delay time to activate or deactivate the PID Sleep function.
No.
b5-16

Name
PID Sleep Delay Time

n b5-17: PID Accel/Decel Time


The PID acceleration/deceleration time is applied on the PID setpoint value.
When the setpoint changes quickly, the normal C1-oo acceleration times reduce the responsiveness of the system as they
are applied after the PID output. The PID accel/decel time helps avoid the hunting and overshoot and undershoot that can
result from the reduced responsiveness.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

39

1.2 b: Application
The PID acceleration/deceleration time can be canceled using a digital input programmed for PID SFS cancel (H1-oo =
34).
No.
b5-17

Name
PID Accel/Decel Time

Setting Range
0.0 to 6000.0 s

Default
0.0 s

Setting Range
0, 1

Default
0

Setting Range
0.00 to 100.00%

Default
0.00%

n b5-18: PID Setpoint Selection


Enables or disables parameter b5-19 for PID setpoint.
No.
b5-18

Parameter Name
PID Setpoint Selection

Setting 0: Disabled

Parameter b5-19 is not used as the PID setpoint.


Setting 1: Enabled

Parameter b5-19 is used as PID setpoint.

n b5-19: PID Setpoint Value


Used as the PID setpoint if parameter b5-18 = 1.
No.
b5-19

Name
PID Setpoint Value

n b5-20: PID Setpoint Scaling


Determines the units for the PID Setpoint Value (b5-19) and monitors U5-01 and U5-04.
No.
b5-20

Parameter Name
PID Setpoint Scaling

Setting Range
0 to 3

Default
1

Setting 0: Hz

The setpoint and PID monitors are displayed in Hz with a resolution of 0.01 Hz.
Setting 1: %

The setpoint and PID monitors are displayed as a percentage with a resolution of 0.01%.
Setting 2: r/min

The setpoint and PID monitors are displayed in r/min with a resolution of 1 r/min.
Setting 3: User Defined

Parameters b5-38 and b5-39 determine the units and resolution used to display the values the setpoint in b5-19, and PID
monitors U1-01 and U1-04.

n b5-34: PID Output Lower Limit


Sets the minimum possible PID controller output as a percentage of the maximum output frequency (E1-04). The lower limit
is disabled when set to 0.00%
No.
b5-34

Name
PID Output Lower Limit

Setting Range
-100.0 to 100.0%

Default
0.00%

n b5-35: PID Input Limit


Sets the maximum allowed PID input as a percentage of the maximum output frequency (E1-04). Parameter b5-35 acts as a
bipolar limit.
No.
b5-35

Name
PID Input Limit

Setting Range
0 to 1000.0%

Default
1000.0%

n b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID
feedback monitors (U5-01, U5-04).
40

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No.

Name

Setting Range

b5-38

PID Setpoint User Display

1 to 60000

b5-39

PID Setpoint Display Digits

0 to 3

Default
Determined by
b5-20
Determined by
b5-20

n b5-40: Frequency Reference Monitor Content During PID


Sets the content of the frequency reference monitor display (U1-01) when PID control is active.
No.
b5-40

Name
Frequency Reference Monitor Content During PID

Setting Range
0, 1

Default
0

Setting 0: Frequency Reference after PID

Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
Setting 1: Frequency Reference

Monitor U1-01 displays the frequency reference value.

n Fine-Tuning PID
Follow the directions below to fine tune PID control parameters:
Table 1.21 PID Fine Tuning
Goal

Tuning Procedure

Result
Response

Suppress overshoot

Reduce the derivative time (b5-05)


Increase the integral time (b5-03)

Before adjustment

After adjustment

Time
Response

Achieve stability quickly while


allowing some overshoot

After adjustment

Before adjustment

Decrease the integral time (b5-03)


Increase the derivative time (b5-05)

Time
Before adjustment

Suppress long cycle oscillations


(longer than the integral time setting) Increase the integral time (b5-03)

Parameter Details

Response

After adjustment

Time

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

41

1.2 b: Application
Goal

Suppress short cycle oscillations

Tuning Procedure

Result

If oscillation cycle time is close to the


derivative time, reduce the derivative
time (b5-05).
If the derivative time is set to 0.00 s and
oscillations are still a problem, reduce
the proportional gain (b5-02) or increase
the PID primary delay time (b5-08)

Before adjustment

Response

After adjustment

Time

u b6: Dwell Function


The Dwell function temporarily holds the frequency reference at a predefined value for a set time then continues accelerating
or decelerating.
The Dwell function helps prevent speed loss when starting and stopping a heavy load with induction motors. When running
a PM motor in V/f control, the pause in acceleration allows the PM motor rotor to align with the stator field of the motor and
reduce the starting current.
The figure below illustrates how the Dwell function works.
Note:

Set the stopping method to "Ramp to Stop" (b1-03 = 0) to use the Dwell function.

OFF
Run Command

OFF

ON

b6-01

b6-03

Output Frequency
b6-02

b6-04

Figure 1.24 Dwell Function at Start and Stop

n b6-01, b6-02: Dwell Reference, Dwell Time at Start


Parameter b6-01 determines the frequency that is held for the time set in b6-02 during acceleration.
No.
b6-01
b6-02

Name
Dwell Reference at Start
Dwell Time at Start

Setting Range
0.0 to 400.0 Hz
0.0 to 10.0 s

Default
0.0 Hz
0.0 s

n b6-03, b6-04: Dwell Reference, Dwell Time at Stop


Parameter b6-03 determines the frequency that is held for the time set in b6-04 during deceleration.
No.
b6-03
b6-04

Name
Dwell Reference at Stop
Dwell Time at Stop

Setting Range
0.0 to 400.0 Hz
0.0 to 10.0 s

Default
0.0 Hz
0.0 s

u b7: Droop Control (CLV, CLV/PM)


Note:

PM motor control modes are not available in A1000 HHP drive models.

Droop control automatically balances the load level between two motors driving the same load. Droop control must be activated
in one of the drives controlling these motors. The drive in which Droop control is activated shifts the load from one motor to
another by automatically reducing the speed when the torque reference rises, and automatically increasing the speed when the
torque reference falls.

42

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.2 b: Application
Motor A runs faster than B, pulling more load

= 100% Load

= 90% Load

Motor B runs faster than A, pulling more load

fref_A = constant

fref_B decrease

= 80% Load

= 90% Load

fref_A = constant

fref_B increase

= 80% Load

= 90% Load

Droop Control increases the speed reference in


drive B accomplishing load balance

= 100% Load

= 90% Load

Droop Control decreases the speed reference in


drive B accomplishing load balance

Figure 1.25 Droop Control Application

n b7-01: Droop Control Gain


Sets the amount of speed reduction when the torque reference is 100%. The gain is set as a percentage of the maximum output
frequency. A setting of 0.0% disables the Droop control function.
No.
b7-01

Parameter Name
Droop Control Gain
Speed

Setting Range
0.0 to 100.0%

Default
0.0%

Speed reference
Droop control gain
b7-01

Torque
0

100%

Figure 1.26 Droop Control Gain

n b7-02: Droop Control Delay Time


Adjusts the responsiveness of Droop control. Reduce the setting if the reaction time is too long, and increase the setting if
hunting occurs.
No.
b7-02

Parameter Name
Droop Control Delay Time

Setting Range
0.03 to 2.00 s

Default
0.05 s

Setting Range
0, 1

Default
1

n b7-03: Droop Control Limit Selection


No.
b7-03

Parameter Name
Droop Control Limit Selection

Setting 0: Disabled
Setting 1: Enabled

u b9: Zero Servo


The Zero Servo function is a position loop that can be used in CLV and CLV/PM control modes to lock the motor at a certain
position.
To activate Zero Servo mode, use a digital input set for H1-oo = 72 and the drive will decelerate when this input is closed.
The drive goes into Zero Servo mode and holds the current position when the motor speed falls below the level set to parameter
b2-01. The drive accelerates when the input assigned to trigger the Zero Servo function is released and the Run command is
still present.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

43

Parameter Details

Enables or disables the droop control limit.

1.2 b: Application
OFF

ON

Run command

ON

Zero Servo command


Motor Speed
b2-01
DC Injection Braking
start frequency

OFF

Zero Servo
Operation

Figure 1.27 Zero Servo Operation

When Zero Servo mode is active, the deviation between the rotor position and the zero position is displayed in monitor U6-22
(monitor value must be divided by 4 to get the deviation in actual encoder pulses).
A digital output programmed for Zero Servo complete (H2-oo = 33) is turned on when the rotor position is within the zero
position, plus or minus the Zero Servo completion width set to parameter b9-02.
Note:

1. The Run command must remain on when using the Zero Servo function. Zero Servo will not hold the load in place if the Run command
is switched off.
2. When the Zero Servo command has shut off, the Zero Servo Completion digital output width also shuts off.
3. Avoid using Zero Servo to lock 100% load for long periods, as this can trigger a fault. If such loads need to be held in place for long
periods, either make sure the current is less than 50% of the drive rated current during Zero Servo, or use a larger capacity drive.
4. If the load rotates the motor when using CLV/PM, a dv4 fault may occur. To prevent this increase the Zero Servo gain (b9-01).

n b9-01: Zero Servo Gain


Adjusts the responsiveness of the Zero Servo position loop. Increase the value if the response is too slow and the deviation
from the zero position rises too high when load is applied. Decrease the value if vibrations occur during Zero Servo operation.
Note:

No.
b9-01

Before adjusting the Zero Servo gain, make sure the ASR parameters (C5-oo) are set up properly and vibration or hunting does not occur
when running with a zero speed reference.

Name
Zero Servo Gain

Setting Range
0 to 100

Default
5

n b9-02: Zero Servo Completion Width


Sets the output range of the Zero Servo completion signal. Enter the amount of deviation allowable from the desired position
to trigger Zero Servo. An output terminal set for Zero Servo (H2-oo = 33) will be triggered when the motor reaches the
position Zero Servo plus or minus b9-02.
No.
b9-02

44

Name
Zero Servo Completion Width

Setting Range
0 to 16383

Default
10

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.3 C: Tuning

1.3

C: Tuning

C parameters set the characteristics for acceleration, deceleration, and S-curves. Other parameters in the C group cover settings
for slip compensation, torque compensation, and carrier frequency.

u C1: Acceleration and Deceleration Times


n C1-01 to C1-08: Accel, Decel Times 1 to 4
Four different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched
automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).
Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02
are the default active accel/decel settings.
No.
C1-01
C1-02
C1-03
C1-04
C1-05
C1-06
C1-07
C1-08

Parameter Name
Acceleration Time 1
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
Acceleration Time 3 (Motor 2 Accel Time 1)
Deceleration Time 3 (Motor 2 Decel Time 1)
Acceleration Time 4 (Motor 2 Accel Time 2)
Deceleration Time 4 (Motor 2 Accel Time 2)

Setting Range

Default

0.0 to 6000.0 s <1>

10.0 s

<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.

Switching Acceleration Times by Digital Input

Accel/decel times 1 are active by default if no input is set. Activate accel/decel times 2, 3, and 4 by digital inputs
(H1-oo = 7 and 1A) as explained in Table 1.22.
Table 1.22 Accel/Decel Time Selection by Digital Input
Accel/Decel Time Sel. 1
H1-oo = 7

Accel/Decel Time Sel. 2


H1-oo = 1A

0
1
0
1

0
0
1
1

Active Times
Acceleration
C1-01
C1-03
C1-05
C1-07

Deceleration
C1-02
C1-04
C1-06
C1-08

Figure 1.28 shows an operation example for changing accel/decel. times. The example below requires that the stopping method
be set for Ramp to stop (b1-03 = 0).
Decel Time 1
Decel Time 3
Decel Time 2
(C1-02)
Accel Time 3 (C1-06)
Accel Time 2 (C1-04)
(C1-05)
(C1-03)
Accel Time 4
(C1-07)
Decel Time 1
(C1-02)

Decel Time 4
(C1-08)
Decel Time 1
(C1-02)

Parameter Details

Output
frequency

Accel Time 1
(C1-01)

Time

FWD (REV)
Run command

ON

Accel/Decel Time Selection 1


(Terminals S1 to S8, H1- oo = 7)

OFF

ON

ON

ON

OFF

ON

Accel/Decel Time Selection 2


(Terminals S1 to S8, H1- oo = 1A)

ON

OFF
ON

Figure 1.28 Timing Diagram of Accel/Decel Time Change

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

45

1.3 C: Tuning
Switching Acceleration and Deceleration Times by Motor Selection

When switching between motor 1 and 2 using a digital input (H1-oo= 16), parameters C1-01 to C1-04 become accel/decel
times 1 and 2 for motor 1, while C1-05 to C1-08 become accel/decel times 1 and 2 for motor 2. Accel/decel times 1 and 2 can
be switched for each motor using a digital inputs set to H1-oo = 7 like shown in Table 1.23.
Note:

1. The motor 2 selection function cannot be used with PM motors.


2. Attempting to use the digital input setting Accel/Decel time 2 selection (H1-oo = 1A) together with motor 1/2 switching triggers an
oPE03 error, indicating contradictory multifunction input settings.
Table 1.23 Motor Switching and Accel/Decel Time Combinations

Accel/Decel Time 1 (H1-oo = 7)

Motor 1 Selected
(Terminal set to H1-oo = 16 OFF)
Accel
C1-01
C1-03

Open
Closed

Motor 2 Selected
(Terminal set to H1-oo = 16 ON)

Decel
C1-02
C1-04

Accel
C1-05
C1-07

Decel
C1-06
C1-08

Switching Accel/Decel Times by a Frequency Level

The drive can switch between different acceleration and deceleration times automatically. The drive will switch from accel/
decel time 4 in C1-07 and C1-08 to the default accel/decel time in C1-01 and C1-02 (C1-05 and C1-06 for motor 2) when the
output frequency exceeds the frequency level set to parameter C1-11. When the frequency falls below this level, the accel/
decel times are switched back. Figure 1.29 shows an operation example.
Note:

Acceleration and deceleration times selected by digital inputs have priority over the automatic switching by the frequency level set to C1-11.
For example, if accel/decel time 2 is selected, the drive will use only accel/decel time 2; it will not switch from accel/decel time 4 to the
selected one.
Output Frequency

C1-11
Accel/Decel Time
Switch Frequency

C1-07
setting

C1-01
setting

C1-02
setting

C1-08
setting

When the output frequency


C1-11, drive uses Accel/Decel Time 1 (C1-01, -02)
When the output frequency < C1-11, drive uses Accel/Decel Time 2 (C1-07, -08)

Figure 1.29 Accel/Decel Time Switching Frequency

n C1-11: Accel/Decel Time Switching Frequency


Sets the frequency at which the drive switches between accel/decel time settings. See Refer to Switching Accel/Decel Times
by a Frequency Level on page 46.
No.

Parameter Name

Setting Range

C1-11

Accel/Decel Time Switching Frequency

0.0 to 400.0 Hz <1>

Default
Determined by
A1-02 <1>

<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 100.0%) instead of in Hz.
Note:

Setting C1-11 to 0.0 disables this function.

n C1-09: Fast Stop Time


Sets a special deceleration used when a select group of faults occur (e.g., L8-03 Overheat Pre-Alarm Operation Selection) or
when closing a digital input configured as H1-oo = 15 (N.O. input) or 17 (N.C. input). A momentary closure of the digital
input will trigger the Fast Stop operation; it does not have to be closed continuously.
The drive cannot be restarted after initiating a Fast Stop operation until after completing deceleration, clearing the Fast Stop
input, and cycling the Run command.
A digital output programmed for During Fast Stop (H2-oo = 4C) will be closed as long as Fast Stop is active.
No.
C1-09

Parameter Name
Fast Stop Time

Setting Range
0.0 to 6000.0 s

<1>

Default
10.0 s

<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s

46

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.3 C: Tuning
NOTICE: Rapid deceleration can trigger an overvoltage fault. The drive output shuts off when faulted and the motor coasts. Set an
appropriate Fast Stop time to C1-09 to avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely.

n C1-10: Accel/Decel Time Setting Units


Determines the units for the acceleration and deceleration times set to C1-01 through C1-09 using parameter C1-10.
No.
C1-10

Parameter Name
Accel/Decel Time Setting Units

Setting Range
0, 1

Default
1

Setting 0: 0.01 s units

The accel/decel times are set in 0.01 s units. The setting range will be 0.00 to 600.00 s. C1-10 cannot be set to 0 if any of the
parameters C1-01 to C1-09 are set to 600.1 seconds or more.
Setting 1: 0.1 s units

The accel/decel times are set in 0.1 s units. The setting range will be 0.0 to 6000.0 s.

u C2: S-Curve Characteristics


Use S-curve characteristics to smooth acceleration and deceleration and minimize abrupt shock to the load. Set S-curve
characteristic time during acceleration/deceleration at start and acceleration/deceleration at stop. Increase the value set to
C2-01 if the STo fault (Hunting Detection) occurs when starting a PM motor.

n C2-01 to C2-04: S-Curve Characteristics


C2-01 through C2-04 set separate S-curves for each section of the acceleration or deceleration.
No.

Parameter Name

Setting Range

C2-01

S-Curve Characteristic at Accel Start

C2-02
C2-03
C2-04

S-Curve Characteristic at Accel End


S-Curve Characteristic at Decel Start
S-Curve Characteristic at Decel End

0.00 to 10.00 s

Default
Determined by
A1-02
0.20 s
0.20 s
0.00 s

Figure 1.30 illustrates S-curve application.


FWD run
REV run

C2-02
Output
frequency

C2-03

C2-04

C2-01
C2-04

C2-01
C2-02

C2-03

Setting the S-curve will increase the acceleration and deceleration times.
Actual accel time = accel time setting + (C2-01 + C2-02) / 2
Actual decel time = decel time setting + (C2-03 + C2-04) / 2

u C3: Slip Compensation


The Slip Compensation function improves the speed accuracy of an induction motor. By adjusting the output frequency in
accordance with the motor load, it compensates the slip and makes the motor speed equal to the frequency reference.
Note:

Perform Auto-Tuning and make sure that the motor rated current (E2-01), the motor rated slip (E2-02), and the no-load current (E2-03)
have all been set properly before making any adjustments to slip compensation parameters.

n C3-01: Slip Compensation Gain


Sets the gain for the motor slip compensation function. Although this parameter rarely needs to be changed, adjustments may
be necessary under the following circumstances:
Increase the setting if the motor at constant speed is slower than the frequency reference.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

47

Parameter Details

Figure 1.30 S-Curve Timing Diagram - FWD/REV Operation

1.3 C: Tuning
Decrease the setting if the motor at constant speed is faster than the frequency reference.
No.

Parameter Name

Setting Range

C3-01

Slip Compensation Gain

0.0 to 2.5

Note:

Default
Determined by
A1-02

Default setting is 0.0 in V/f Control (A1-02 = 0), and 1.0 in Open Loop Vector Control (A1-02 = 2). In Closed Loop Vector Control, slip
compensation corrects inaccuracies that can result from temperature fluctuation in the rotor.

n C3-02: Slip Compensation Primary Delay Time


Adjusts the filter on the output side of the slip compensation function. Although this parameter rarely needs to be changed,
adjustments may be necessary in the following situations:
Decrease the setting when the slip compensation response is too slow.
Increase this setting when speed is unstable.
No.

Parameter Name

Setting Range

C3-02

Slip Compensation Primary Delay Time

0 to 10000 ms

Note:

Default
Determined by
A1-02

Default for V/f Control (A1-02 = 0) is 2000 ms. Default for Open Loop Vector Control (A1-02 = 2) is 200 ms.

n C3-03: Slip Compensation Limit


Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E2-02).
No.
C3-03

Parameter Name
Slip Compensation Limit

Setting Range
0 to 250%

Default
200%

The slip compensation limit is constant throughout the constant torque range (frequency reference E1-06). In the constant
power range (frequency reference E1-06), it is increased based on C3-03 and the output frequency as shown in the following
diagram.
E1-04
E1-06 C3-03
C3-03

Output Frequency
E1-06
Base
Frequency

E1-04
Maximum
Frequency

Figure 1.31 Slip Compensation Limit

n C3-04: Slip Compensation Selection during Regeneration


Enables or disables slip compensation during regenerative operation. When slip compensation during regeneration has been
activated and a regenerative load is applied, it might be necessary to use a dynamic braking option (braking resistor, braking
resistor unit, or braking unit).
This function does not operate when the output frequency is too low, regardless of whether it has been enabled.
No.
C3-04

Parameter Name
Slip Compensation Selection during Regeneration

Setting Range
0 to 2

Default
0

Setting 0: Disabled

Slip compensation is not provided. Depending on the load and mode of operation, the actual motor speed will be lower or
higher than the frequency reference.
Setting 1: Enabled (6 Hz and above)

Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
Setting 2: Enabled (compensation provided wherever possible)

Slip compensation is enabled during regenerative operation and at frequencies as low as 2 Hz. The drive uses the motor rated
slip set to E2-02 to automatically calculate the frequency range where compensation will be disabled.
48

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.3 C: Tuning

n C3-05: Output Voltage Limit Operation Selection


Determines if the motor flux reference is automatically reduced when output voltage reaches the saturation range.
If the input power supply voltage is low or the motor has a high voltage rating, this function improves the speed precision
when moving heavy loads at high speeds. When selecting the drive, remember that the reduction in flux causes a slightly
higher current at high speed when this function is enabled.
No.
C3-05
Note:

Parameter Name
Output Voltage Limit Operation Selection

Setting Range
0, 1

Default
0

Available control modes for parameter C3-05 vary by drive model:


CIMR-Ao2A0004 to 2A0415, 4A0002 to 4A0675, and 5A0003 to 5A0242: Available when A1-02 = 0, 1
CIMR-Ao4A0930 and 4A1200: Available when A1-02 = 2, 3, 6, 7
A1000 HHP: Available when A1-02 = 2 or 3

Setting 0: Disabled
Setting 1: Enabled

n C3-16: Output Voltage Limit Operation Start Level (Percentage Modulation)


Sets the output voltage limit operation start level (percentage modulation) when C3-05 is enabled.
Note:

No.
C3-16

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Parameter Name
Output Voltage Limit Operation Start Level

Setting Range
70.0 to 90.0%

Default
85.0%

n C3-17: Maximum Output Voltage Limit Level (Percentage Modulation)


Sets the output voltage limit operation determined by C3-18 (percentage modulation) when C3-05 is enabled.
Note:

No.
C3-17

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Parameter Name
Maximum Output Voltage Limit Level

Setting Range
85.0 to 100.0%

Default
90.0%

n C3-18: Output Voltage Limit Level


Sets the maximum percentage of output voltage reduction when C3-05 is enabled.
Note:

No.
C3-18

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Parameter Name
Output Voltage Limit Level

Setting Range
30.0 to 100.0%

Default
90.0%

n C3-21: Motor 2 Slip Compensation Gain


Improves the speed accuracy for motor 2 and functions in the same way that C3-01 functions for motor 1. Adjust this parameter
only after setting the motor rated current (E4-01), motor rated slip (E4-02), and the motor no-load current (E4-03).
Refer to C3-01: Slip Compensation Gain on page 47 for details on adjusting this parameter.

Note:

Parameter Name
Motor 2 Slip Compensation Gain

Setting Range
0.0 to 2.5

Default
Determined by E3-01

Default setting is 0.0 in V/f Control (A1-02 = 0). Default setting is 1.0 in Open Loop Vector Control (A1-02 = 2) and Closed Loop Vector
Control (A1-02 = 3). In Closed Loop Vector Control, slip compensation gain acts as an adaptable gain.

n C3-22: Motor 2 Slip Compensation Primary Delay Time


Functions for motor 2 the same way that C3-02 functions for motor 1.
Refer to C3-02: Slip Compensation Primary Delay Time on page 48 for details on adjusting this parameter.
No.
C3-22
Note:

Parameter Name
Motor 2 Slip Compensation Primary Delay Time

Setting Range
0 to 10000 ms

Default
Determined by A1-02

The default for V/f Control (A1-02 = 0) is 2000 ms. The default for Open Loop Vector Control (A1-02 = 2) is 200 ms.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

No.
C3-21

49

1.3 C: Tuning

n C3-23: Motor 2 Slip Compensation Limit


Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E4-02).
No.
C3-23

Parameter Name
Motor 2 Slip Compensation Limit

Setting Range
0 to 250%

Default
200%

The slip compensation limit is constant throughout the constant torque range (frequency reference E3-06). In the constant
power range (frequency reference E3-06), it is increased based on C3-23 and the output frequency as illustrated in the
following diagram.
E3-04
E3-06 C3-23
C3-23

Output Frequency
E3-06
Base
Frequency

E3-04
Maximum
Frequency

Figure 1.32 Slip Compensation Limit

n C3-24: Motor 2 Slip Compensation Selection during Regeneration


Functions for motor 2 the same way that C3-04 functions for motor 1.
Refer to C3-04: Slip Compensation Selection during Regeneration on page 48 for details on adjusting this parameter.
No.
C3-24

Parameter Name
Motor 2 Slip Compensation Selection during
Regeneration

Setting Range

Default

0 to 2

Setting 0: Disabled
Setting 1: Enabled (6 Hz and above)
Setting 2: Enabled (compensation provided wherever possible)

u C4: Torque Compensation


The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.
Note:

Set the motor parameters and V/f pattern properly before setting torque compensation parameters.

n C4-01: Torque Compensation Gain


Sets the gain for the torque compensation function.
No.

Parameter Name

Setting Range

C4-01

Torque Compensation Gain

0.00 to 2.50

Default
Determined by
A1-02

Torque Compensation in V/f, V/f w/PG, and OLV/PM:


Note:

PM motor control modes are not available in A1000 HHP drive models.

The drive calculates the motor primary voltage loss using the output current and the termination resistor value (E2-05 for IM
motors, E5-05 for PM motors) and adjusts the output voltage to compensate insufficient torque at start or when load is applied.
The effects of this voltage compensation can be increased or decreased using parameter C4-01.
Torque Compensation in OLV:

The drive controls the motor excitation current (d-Axis current) and torque producing current (q-Axis current) separately.
Torque compensation affects the torque producing current only. C4-01 works as a factor of the torque reference value that
builds the torque producing current reference.

50

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.3 C: Tuning
Adjustment

Although this parameter rarely needs to be changed, it may be necessary to adjust the torque compensation gain in small steps
of 0.05 in the following situations:
Increase this setting when using a long motor cable.
Decrease this setting when motor oscillation occurs.
Adjust C4-01 so the output current does not exceed the drive rated current.
Note:

1. Refrain from adjusting torque compensation in Open Loop Vector Control, as it can have a negative effect on torque accuracy.
2. Refrain from adjusting this parameter in OLV/PM. Setting this value too high can cause overcompensation and motor oscillation.

n C4-02: Torque Compensation Primary Delay Time


Sets the delay time used for applying torque compensation.
No.

Parameter Name

Setting Range

C4-02

Torque Compensation Primary Delay Time

0 to 60000 ms

Default
Determined by
A1-02

Adjustment

Although C4-02 rarely needs to be changed, adjustments may be necessary in the following situations:
Increase this setting if the motor vibrates.
Decrease this setting if the motor responds too slowly to changes in the load.

n C4-03: Torque Compensation at Forward Start (OLV)


Sets the amount of torque at start in the forward direction to improve motor performance during start with a heavy load.
Compensation is applied using the time constant set in parameter C4-05. Enable this function when the load pulls the motor
in reverse when starting with a Forward run command. Setting 0.0% disables this feature.
No.
C4-03

Parameter Name
Torque Compensation at Forward Start

Setting Range
0.0 to 200.0%

Default
0.0%

n C4-04: Torque Compensation at Reverse Start (OLV)


Sets the amount of torque reference at start in the reverse direction to improve motor performance during start with heavy
load. Compensation is applied using the time constant set in parameter C4-05. Enable this function if the load pulls the motor
in the forward direction when starting with a Reverse run command. Setting 0.0% disables this feature.
No.
C4-04

Parameter Name
Torque Compensation at Reverse Start

Setting Range
-200.0 to 0.0%

Default
0.0%

n C4-05: Torque Compensation Time Constant (OLV)


Sets the time constant for applying the torque compensation at start that is set to C4-03 and C4-04.
No.
C4-05

Parameter Name
Torque Compensation Time Constant

Setting Range
0 to 200 ms

Default
10 ms

n C4-06: Torque Compensation Primary Delay Time 2 (OLV)


No.
C4-06
Note:

Parameter Name
Torque Compensation Primary Delay Time 2

Setting Range
0 to 10000 ms

Parameter Details

Sets the time constant used during Speed Search or during regenerative operation. Adjust the value if an overvoltage fault
occurs with sudden changes in the load or at the end of acceleration with high inertia load.
Default
150 ms

If C4-06 is set to a relatively large value, increase the setting in n2-03 (AFR Time Constant 2) proportionally.

n C4-07: Motor 2 Torque Compensation Gain

Functions for motor 2 the same way that C4-01 functions for motor 1.
Refer to C3-01: Slip Compensation Gain on page 47 for details on adjusting this parameter.
No.
C4-07

Parameter Name
Motor 2 Torque Compensation Gain

Setting Range
0.00 to 2.50

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Default
1.00
51

1.3 C: Tuning

u C5: Automatic Speed Regulator (ASR)


The ASR controls the motor speed in V/f w/PG, CLV, AOLV/PM, and CLV/PM control modes and adjusts the output frequency
(V/f w/PG) or torque reference (CLV, AOLV/PM, CLV/PM) to minimize the difference between frequency reference and
actual motor speed.
The figures below illustrate ASR functionality:
Output frequency

Frequency
reference

Limit

ASR limit

Detected speed

Change
rate
limiter

C5-01
C5-03

I
C5-05
C5-02, C5-04

Figure 1.33 Speed Control Block Diagram for V/f Control with PG
Torque limits
C5-01, C5-03
Frequency
reference

Detected speed
<1>

I
C5-02, C5-04

I
limit

Torque reference

Primary
filter
+

C5-06
(C5-10)

L7-01 to L7-04

C5-08

Figure 1.34 Speed Control Block Diagram for CLV, AOLV/PM and CLV/PM

<1> AOLV/PM estimates the speed using the motor model and does not require an encoder feedback signal.
Note:

PM motor control modes are not available in A1000 HHP drive models.

n Adjusting the ASR Parameters


Perform Auto-Tuning and set up all motor data correctly prior to adjusting ASR parameters.
Use analog output signals to monitor the frequency reference after softstarter (U1-16) and the motor speed (U1-05) when
adjusting the ASR. Refer to H4: Multi-Function Analog Outputs on page 119 for details on setting up analog output
functions.
Generally when tuning the ASR, optimize the ASR gain before adjusting the integral time settings. Always make adjustments
with the load connected to the motor.
Adjusting the ASR Parameters in V/f Control with PG

In V/f Control with PG, the ASR settings change between two sets of parameters depending on the motor speed as described
in C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 53.
Perform the following steps for adjusting ASR parameters:

1.
2.
3.
4.
5.
6.

Run the motor at minimum speed and increase ASR gain 2 (C5-03) as much as possible without oscillation.
Run the motor at minimum speed and decrease ASR integral time 2 (C5-04) as much as possible without oscillation.
Check the output current monitor to make sure that the output current is less than 50% of the drive rated current. If
the value is higher than 50%, decrease C5-03 and increase C5-04.
Run the motor at maximum speed and increase ASR gain 1 (C5-01) as much as possible without oscillations.
Run the motor at maximum speed and decrease ASR integral time 1 (C5-02) as much as possible without oscillations.
If higher speed precision and faster response during acceleration or deceleration are required, enable integral control
during accel/decel by setting parameter C5-12 to 1. Change the speed and make sure no over/undershoot occurs.

Adjusting the ASR Parameters in CLV, AOLV/PM, and CLV/PM


Note:

52

PM motor control modes are not available in A1000 HHP drive models.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.3 C: Tuning
The drive is preset to use ASR settings C5-01/02 over the entire speed range in CLV, AOLV/PM, and CLV/PM. If required
by the application, a second set of ASR parameters (C5-03/04) can be automatically activated depending on the motor speed
or by using a digital input. Refer to C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on
page 53.
Perform the following steps for adjusting ASR parameters:

1.
2.
3.
4.

Run the motor at zero speed and increase the ASR gain (C5-01) as much as possible without oscillation.
Run the motor at zero speed and decrease the ASR integral time (C5-02) as much as possible without oscillation.
Run at the normal operating speed. Check for over/undershoot when changing speed and for any oscillation.
If problems occur in step 3, increase the integral time and reduce the gain.
Alternatively, use different ASR settings for high and low speed. Set the values from step 1 and 2 to parameters C5-03
and C5-04, then set an ASR switching frequency in parameter C5-07. Run the motor at a speed higher than C5-07
and repeat step 3 while adjusting C5-01 and C5-02.

Solving Problems During ASR Setup

Use Table 1.24 when making adjustments to ASR. Though the parameters listed below are for motor 1, the same changes can
be made to the corresponding motor 2 parameters when running a second motor.
Table 1.24 ASR Setup Problems and Corrective Actions

Problem

Possible Solutions
Speed reference

Slow response to speed changes or


speed deviation lasts for too long

Increase the ASR gain.


Decrease the integral time.

Motor Speed

Time
Motor Speed

Overshoot or undershoot at the end


of acceleration or deceleration

Decrease the ASR gain.


Increase the integral time.

Speed reference

Time
Speed reference

Vibration and oscillation occur at


constant speed

Decrease the ASR gain.


Increase the integral time.
Increase the ASR delay time (C5-06).

Motor Speed

Time

The motor slip is not fully


compensated when running in V/f
Control with PG

Motor Speed

Time

Integral operation is enabled in


V/f Control with PG (C5-12 = 1)
and over/undershoot occurs when
changing speed.
Oscillation at low speed and
response is too slow at high speed
(or vice versa)

Check the pulse number set to F1-01 and the gear ratio in F1-12
and F1-13.
Make sure the pulse signal from the encoder is set up properly.
Check monitor U6-04 and determine if the ASR is working at
its output limit (setting of C5-05). If the ASR is at the output
limit, increase C5-05.

Decrease the ASR gain.


Increase the integral time.
Reduce the ASR output limit set in C5-05.

V/f control: Use C5-01/02 and C5-03/04 to set up different


ASR settings at minimum and maximum speed.
CLV, AOLV/PM, CLV/PM: Use C5-01, C5-02 and C5-03,
C5-04 to define optimal ASR settings for high and low speed.
Use C5-07 to define a switching frequency.

n C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2


These parameters adjust the responsiveness of the ASR.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

Speed reference

53

1.3 C: Tuning
No.

Parameter Name

Setting Range

C5-01

ASR Proportional Gain 1

0.00 to 300.00

C5-02

ASR Integral Time 1

0.000 to 10.000 s

C5-03

ASR Proportional Gain 2

0.00 to 300.00

C5-04

ASR Integral Time 2

0.000 to 10.000 s

Default
Determined by
A1-02
Determined by
A1-02
Determined by
A1-02
Determined by
A1-02

These parameter settings will function differently depending on the control mode.
V/f Control with PG

Parameters C5-01 and C5-02 determine the ASR characteristics at maximum speed. Parameters C5-03 and C5-04 determine
the characteristics at minimum speed.
P = C5-01
I = C5-02

P and I setting

P = C5-03
I = C5-04

E1-09
Min. output frequency

Motor speed
E1-04
Max. output frequency

Figure 1.35 ASR Gain and Integral Time in V/f w/PG

CLV, AOLV/PM, and CLV/PM


Note:

PM motor control modes are not available in A1000 HHP drive models.

In these control modes, parameters C5-03 and C5-04 define the ASR gain an integral time at zero speed. The settings in C5-01
and C5-02 are used at speeds above the setting in C5-07. C5-07 is set to 0 as the default so that C5-01 and C5-02 are used
over the entire speed range. Refer to C5-07: ASR Gain Switching Frequency on page 55.
P, I

P = C5-01
I = C5-02

Ramp

P = C5-03
I = C5-04

C5-07

(Low speed)

Motor speed (Hz)

Figure 1.36 Low-speed and High-speed Gain Settings

The gain set in C5-03 can also be activated with a digital input programmed to ASR gain switch (H1-oo = 77). When the
terminal is open, the drive uses the ASR gain level set by the pattern in the figure above. When the terminal closes, C5-03 is
used. The integral time set to C5-02 is used to change linearly between these settings. The ASR gain switch command from
a multi-function input terminal overrides the switching frequency set to C5-07.
ASR Gain Switch signal
(Digital input)

OFF

ON
Proportional gain
determined
by motor speed.

Proportional gain (P)

C5-03 gain setting


C5-02

C5-02

Figure 1.37 ASR Proportional Gain Switch

ASR Gain Tuning (C5-01, C5-03)

The higher this setting, the faster the speed response, although a setting that is too high can lead to oscillation. Increase this
setting with larger loads to minimize the speed deviation.
54

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.3 C: Tuning
ASR Integral Time Tuning (C5-02, C5-04)

Determines how fast a continuous speed deviation problem is eliminated. A setting that is too long reduces the responsiveness
of the speed control. A setting that is too short can cause oscillation.

n C5-05: ASR Limit


Sets the ASR output limit as a percentage of the maximum output frequency (E1-04). If the motor rated slip is high, the setting
might need to be increased to provide proper motor speed control. Use the ASR output monitor U6-04 to determine if ASR is
working at the limit set in C5-05. If ASR is working at the limit, make sure the PG pulses (F1-01), PG gear teeth (F1-12,
F1-13), and the PG signal are set correctly before making further changes to C5-05.
No.
C5-05

Parameter Name
ASR Limit

Setting Range
0.0 to 20.0%

Default
5.0%

n C5-06: ASR Primary Delay Time Constant


Sets the filter time constant for the time from the speed loop to the torque command output. Increase this setting gradually in
increments of 0.01 for loads with low rigidity or when oscillation is a problem. This parameter rarely needs to be changed.
No.
C5-06

Parameter Name
ASR Primary Delay Time Constant

Setting Range
0.000 to 0.500 s

Default
Determined by A1-02

n C5-07: ASR Gain Switching Frequency


Sets the frequency where the drive should switch between ASR proportional gain 1 and 2 (C5-01, C5-03) as well as between
integral time 1 and 2 (C5-02, C5-04).
No.
C5-07
Note:

Parameter Name
ASR Gain Switching Frequency

Setting Range
0.0 to 400.0 Hz

Default
0.0 Hz

A multi-function input set for the ASR gain switch (H1-oo = 77) takes priority over the ASR gain switching frequency.

Switching the proportional gain and integral time in the low or high speed range can help stabilize operation and avoid resonance
problems. A good switching point is 80% of the frequency where oscillation occurs or at 80% of the target speed. Refer to
C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 53.

n C5-08: ASR Integral Limit


Sets the upper limit for ASR as a percentage of the rated load.
No.
C5-08

Parameter Name
ASR Integral Limit

Setting Range
0 to 400%

Default
400%

n C5-12: Integral Operation during Accel/Decel (V/f w/PG)


Enables integral operation during acceleration and deceleration. Use integral operation when driving a heavy load or a high
inertia load (default). Set C5-12 to 1 to use integral operation for low inertia/high performance loads. Enabling integral
operation may cause problems with overshoot at the end of acceleration and deceleration. Refer to ASR Setup Problems and
Corrective Actions on page 53 to solve such problems.
Parameter Name
Integral Operation during Accel/Decel

Setting Range
0, 1

Default
0
Parameter Details

No.
C5-12
Setting 0: Disabled

Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled

Integral operation is always enabled.

n C5-21, C5-23 / C5-22, C5-24: Motor 2 ASR Proportional Gain 1, 2 / Integral Time 1, 2
These parameters function for motor 2 the same way that C5-01 through C5-04 function for motor 1. Refer to C5-01, C5-03/
C5-02, C5-04: ASR Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 53 for details.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

55

1.3 C: Tuning
No.
C5-21
C5-22
C5-23
C5-24

Parameter Name
Motor 2 ASR Proportional Gain 1
Motor 2 ASR Integral Time 1
Motor 2 ASR Proportional Gain 2
Motor 2 ASR Integral Time 2

Setting Range
0.00 to 300.00
0.000 to 10.000 s
0.00 to 300.00
0.000 to 10.000 s

Default
Determined by E3-01
Determined by E3-01
Determined by E3-01
Determined by E3-01

n C5-25: Motor 2 ASR Limit


Functions for motor 2 the same way that C5-05 functions for motor 1. Sets the ASR output limit for motor 2 as a percentage
of the maximum output frequency (E4-04). Refer to C5-05: ASR Limit on page 55 for details.
No.
C5-25

Parameter Name
Motor 2 ASR Limit

Setting Range
0.0 to 20.0%

Default
5.0%

n C5-26: Motor 2 ASR Primary Delay Time Constant


Functions for motor 2 the same way that C5-06 functions for motor 1.Sets the filter time constant for the time from the speed
loop to the torque command output. Refer to C5-06: ASR Primary Delay Time Constant on page 55 for details. This parameter
rarely needs to be changed.
No.
C5-26

Parameter Name
Motor 2 ASR Primary Delay Time Constant

Setting Range
0.000 to 0.500 s

Default
0.004 s

n C5-27: Motor 2 ASR Gain Switching Frequency


Functions for motor 2 the same way that C5-07 functions for motor 1. Sets the frequency for motor 2 to change ASR proportional
gain 1 and 2 (C5-21, C5-23) as well as the integral time 1 and 2 (C5-22, C5-24). Refer to C5-01, C5-03/C5-02, C5-04: ASR
Proportional Gain 1, 2/ASR Integral Time 1, 2 on page 53 for details.
No.
C5-27
Note:

Parameter Name
Motor 2 ASR Gain Switching Frequency

Setting Range
0.0 to 400.0 Hz

Default
0.0 Hz

A multi-function input set for the ASR gain switch (H1-oo = 77) takes priority over the ASR gain switching frequency.

n C5-28: Motor 2 ASR Integral Limit


Functions for motor 2 the same way that C5-08 functions for motor 1. Sets the upper limit for ASR as a percentage of the rated
load. Refer to C5-08: ASR Integral Limit on page 55 for details.
No.
C5-28

Parameter Name
Motor 2 ASR Integral Limit

Setting Range
0 to 400%

Default
400%

n C5-32: Integral Operation during Accel/Decel for Motor 2


Functions for motor 2 the same way that C5-12 functions for motor 1. Enables integral operation during acceleration and
deceleration. Refer to C5-12: Integral Operation during Accel/Decel (V/f w/PG) on page 55 for details.
No.
C5-32

Parameter Name
Integral Operation during Accel/Decel for Motor 2

Setting Range
0, 1

Default
0

Setting 0: Disabled

Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled

Integral operation is always enabled.

u C6: Carrier Frequency


n C6-01: Drive Duty Mode Selection
The drive has two different duty modes from which to select based on the load characteristics. The drive rated current, overload
capacity, and maximum output frequency will change depending upon the duty mode selection. Use parameter C6-01 to select
Heavy Duty (HD) or Normal Duty (ND) for the application.

56

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.3 C: Tuning
No.
C6-01

Parameter Name
Duty Mode Selection

Setting Range
0, 1

Default
1 (ND)

Table 1.25 Differences between Heavy Duty and Normal Duty


Characteristics
C6-01

Heavy Duty Rating (HD)


0

Normal Duty Rating (ND)


1

Overload

150 %

Overload

120 %
Rated Load

100 %

Rated Load

100 %

Performance

Motor Speed

Use Heavy Duty Rating for applications requiring a high


overload tolerance with constant load torque, such as
extruders and conveyors.
Overload capability (oL2)
150% of drive rated Heavy Duty current for 60 s
Stall Prevention during
150%
Acceleration (L3-02)
Stall Prevention during
150%
Run (L3-06)
Default Carrier Frequency
2 kHz
Application

Note:

100 %

Motor Speed

100 %

Use Normal Duty Rating for applications in which the torque


requirements drop along with the speed, such as fans and
pumps where a high overload tolerance is not required.
120% of drive rated Normal Duty current for 60 s
120%
120%
2 kHz Swing PWM

Changing the Duty Mode selection automatically changes the maximum size motor that the drive can run, sets the E2-oo parameters to
appropriate values (E4-oo for motor 2), and recalculates parameter settings determined by motor capacity (e.g., b8-04, L2-03).

n C6-02: Carrier Frequency Selection


Sets the switching frequency of the drive output transistors. Changes to the switching frequency lower audible noise and reduce
leakage current.
No.
C6-02

Parameter Name
Carrier Frequency Selection

Setting Range
1

Default
1

Setting
Carrier Frequency

2.0 kHz

Parameter Details

C602

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

57

1.4 d: Reference Settings

1.4

d: Reference Settings

The figure below gives an overview of the reference input, selections, and priorities.
b1-01
(Freq. Reference Source 1)

Pulse Train Input


Option Card
MEMOBUS comm.
Terminal A1/A2/A3
d1-01
(Freq.Ref 1)

LO/RE Key on Digital Operator or


Digital Input H1-oo = 1

=4
=3
=2
=1
=0

Digital Input
H1-oo = 2

0
1

Remote

MS 1

Local
Set to supply the
auxiliary frequency reference

Terminal A2
b1-15
(Freq. Reference Source 2)

Pulse Train Input


Option card
MEMOBUS comm.
Terminal A1/A2/A3
d1-01
(Freq. Ref. 1)

H3-10 = 2

d1-02

=4

MS 2

H3-10 = 2

Terminal A3
H3-06 = 3

=3

d1-03

=2
=1

Frequency
Reference
4 through 16

=0

d1-04
d1-15
d1-16

Jog Frequency d1-17

MS 3

H3-06 = 3
MS 4

Open

NetRef
1

1 ComRef
0

Close

Frequency
Reference

Memobus Register 0001h, bit 4 if


standard 2 wire sequence selected,
usually 0

MS 15
MS 16
Jog

Multi-Step Speed

Set from Communications


Option Card, usually 0
Digital Input (H1-oo)
Jog Reference (=6),
FJOG(=12), RJOG(=13)

Figure 1.38 Frequency Reference Setting Hierarchy

u d1: Frequency Reference


n d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Frequency Reference
The drive lets the user switch between up to 17 preset frequency references during run (including the Jog reference) through
the digital input terminals. The drive uses the acceleration and deceleration times that have been selected when switching
between each frequency reference.
The Jog frequency overrides all other frequency references and must be selected by a separate digital input.
The multi-speed references 1, 2, and 3 can be provided by analog inputs.
No.
d1-01 to d1-16

Parameter Name
Frequency Reference 1 to 16

d1-17

Jog Frequency Reference

Setting Range

Default

0.00 to 150.00 Hz

<1> <2>

0.00 Hz

<2>

0.00 to 150.00 Hz

<1> <2>

6.00 Hz

<2>

<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).
<2> Setting units are determined by parameter o1-03. The default is Hz (o1-03 = 0) in V/f, V/f w/PG, OLV, CLV, and OLV/PM control modes. The
default for AOLV/PM and CLV/PM control modes expresses the frequency reference as a percentage (o1-03 = 1).

Multi-Step Speed Selection

To use several speed references for a multi-step speed sequence, set the H1-oo parameters to 3, 4, 5, and 32. To assign the
Jog reference to a digital input, set H1-oo to 6.
Notes on using analog inputs as Multi-Speed 1, 2, and 3:
The first frequency reference (Multi-Speed 1) comes from the source specified in b1-01. When using an analog input terminal
to supply the frequency reference, assign the frequency reference source to the control terminals (b1-01 = 1).
When an analog input is set to Auxiliary frequency 1 (H3-02, H2-06, or H2-10 = 2), the value set to this input will be used
as the Multi-Step Speed 2 instead of the value set to parameter d1-02. If no analog inputs are set for Auxiliary frequency
1, then d1-02 becomes the reference for Multi-Step Speed 2.
58

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.4 d: Reference Settings


When an analog input is set to Auxiliary frequency 2 (H3-02, H2-06, or H2-10 = 3), the value set to this input will be used
as the Multi-Step Speed 3 instead of the value set to parameter d1-03. If no analog inputs are set for Auxiliary frequency
2, then d1-03 becomes the reference for Multi-Step Speed 3.
Select the different speed references as shown in Table 1.26. Figure 1.39 illustrates the multi-step speed selection.
Table 1.26 Multi-Step Speed Reference and Terminal Switch Combinations
Reference
Frequency Reference 1 (set in b1-01)
Frequency Reference 2
(d1-02 or input terminal A1, A2, A3)
Frequency Reference 3
(d1-03 or input terminal A1, A2, A3)
Frequency Reference 4 (d1-04)
Frequency Reference 5 (d1-05)
Frequency Reference 6 (d1-06)
Frequency Reference 7 (d1-07)
Frequency Reference 8 (d1-08)
Frequency Reference 9 (d1-09)
Frequency Reference 10 (d1-10)
Frequency Reference 11 (d1-11)
Frequency Reference 12 (d1-12)
Frequency Reference 13 (d1-13)
Frequency Reference 14 (d1-14)
Frequency Reference 15 (d1-15)
Frequency Reference 16 (d1-16)
Jog Frequency Reference (d1-17) <1>

Multi-Step
Speed
H1-oo = 3
OFF

Multi-Step
Speed 2
H1-oo = 4
OFF

Multi-Step
Speed 3
H1-oo = 5
OFF

Multi-Step
Speed 4
H1-oo = 32
OFF

Jog Reference
H1-oo = 6

ON

OFF

OFF

OFF

OFF

OFF

ON

OFF

OFF

OFF

ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON

ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON

OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON

OFF

Parameter Details

<1> The Jog frequency overrides all other frequency references.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

59

1.4 d: Reference Settings


d1-16
Frequency
reference

d1-15
d1-14
d1-13
d1-12

d1-07
d1-06
d1-05

d1-01
(A1)

d1-02
(A2)

d1-01
(A3)

d1-04

d1-17
Time

FWD (REV) Run/Stop


ON
Multi-step Speed Ref. 1
Multi-step Speed Ref. 2

ON

ON

ON

ON
ON

ON

Multi-step Speed Ref. 3

ON

ON
ON

ON

ON

ON

Multi-step Speed Ref. 4

ON

Jog Reference

ON

Figure 1.39 Preset Reference Timing Diagram

u d2: Frequency Upper/Lower Limits


Upper and lower frequency limits prevent motor speed from going above or below levels that may cause resonance or
equipment damage.

n d2-01: Frequency Reference Upper Limit


Sets the maximum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
Even if the frequency reference is set to a higher value, the drive internal frequency reference will not exceed this value.
No.
d2-01

Parameter Name
Frequency Reference Upper Limit

Setting Range
0.0 to 110.0%

Default
100.0%

n d2-02: Frequency Reference Lower Limit


Sets the minimum frequency reference as a percentage of the maximum output frequency. This limit applies to all frequency
references.
If a lower reference than this value is entered, the drive will run at the limit set to d2-02. If the drive is started with a lower
reference than d2-02, it will accelerate up to d2-02.
No.
d2-02

60

Parameter Name
Frequency Reference Lower Limit

Setting Range
0.0 to 110.0%

Default
0.0%

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.4 d: Reference Settings


Internal frequency
reference
d2-01

Frequency Reference Upper Limit

Operating
range

Frequency Reference Lower Limit


d2-02
Set frequency reference

Figure 1.40 Frequency Reference: Upper and Lower Limits

n d2-03: Master Speed Reference Lower Limit


Sets a lower limit as a percentage of the maximum output frequency that will only affect a frequency reference entered from
the analog input terminals (A1, A2, or A3). This is unlike parameter d2-02, which affects all frequency references regardless
of their source.
Note:

No.
d2-03

When lower limits are set to both parameters d2-02 and d2-03, the drive uses the greater of those two values as the lower limit.

Parameter Name
Master Speed Reference Lower Limit

Setting Range
0.0 to 110.0%

Default
0.0%

u d3: Jump Frequency


n d3-01 to d3-04: Jump Frequencies 1, 2, 3 and Jump Frequency Width
The Jump frequencies are frequency ranges at which the drive will not operate. The drive can be programmed with three
separate Jump frequencies to avoid operating at speeds that cause resonance in driven machinery. If the speed reference falls
within a Jump frequency dead band, the drive will clamp the frequency reference just below the dead band and only accelerate
past it when the frequency reference rises above the upper end of the dead band.
Setting parameters d3-01 through d3-03 to 0.0 Hz disables the Jump frequency function.
No.
d3-01

Parameter Name
Jump Frequency 1

Setting Range

Default

0.0 to 150.0 Hz <1>

0.0 Hz <1>

d3-02

Jump Frequency 2

0.0 to 150.0 Hz <1>

0.0 Hz <1>

d3-03

Jump Frequency 3

0.0 to 150.0 Hz <1>

0.0 Hz <1>

d3-04

Jump Frequency Width

0.0 to 20.0 Hz <1>

1.0 Hz <1>

<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage instead of in Hz.

Parameter Details

Figure 1.41 shows the relationship between the Jump frequency and the output frequency.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

61

1.4 d: Reference Settings


Output
frequency

Frequency
reference
decreases

Frequency
reference
increases
Jump
Frequency
Width (d3-04)

Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Jump
Frequency 3
d3-03

Jump
Frequency 2
d3-02

Jump
Frequency 1
d3-01

Frequency
reference

Figure 1.41 Jump Frequency Operation


Note:

1. The drive will use the active accel/decel time to pass through the specified dead band range, but will not allow continuous operation in
that range.
2. When setting more than one Jump frequency, make sure that d3-01 d3-02 d3-03.

u d4: Frequency Reference Hold and Up/Down 2 Function


n d4-01: Frequency Reference Hold Function Selection
Determines whether the frequency reference or the frequency bias (Up/Down 2) value is saved when the Stop command is
entered or the power supply is shut down. This parameter is effective when either of the digital input functions listed below
are used:
Accel/decel ramp hold function (H1-oo= A)
Up/Down function (H1-oo = 10 and 11)
Up/Down 2 function (H1-oo = 75 and 76)
No.
d4-01

Parameter Name
Frequency Reference Hold Function Selection

Setting Range
0, 1

Default
0

The operation depends on the function used with parameter d4-01.


Setting 0: Disabled

Acceleration hold
The hold value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off. The active
frequency reference will be the value the drive uses when it restarts.
Up/Down
The frequency reference value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off.
The drive will start from 0 Hz when it is restarted.
Up/Down 2
The frequency bias is not saved when the Stop command is entered, or 5 s after the Up/Down 2 command has been released.
The Up/Down 2 function will start with a bias of 0% when the drive is restarted.
Setting 1: Enabled

Acceleration hold
The last hold value will be saved when the Run command or the drive power is switched off and the drive will use the saved
value as the frequency reference when it restarts. Make sure to continuously enable the multi-function input terminal set for
Accel/decel ramp hold (H1-oo = A) or the hold value will be cleared when the power is switched on.

62

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.4 d: Reference Settings


ON

Power supply

Forward Run / Stop


Hold Accel/Decel

ON
OFF

OFF

ON

OFF

ON

OFF
ON

OFF

ON

Frequency reference

Output frequency

d4-01 = 1
d4-01 = 0
Hold

Hold

Figure 1.42 Frequency Reference Hold with Accel/Decel Hold Function

Up/Down
The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will use
the frequency reference that was saved when it restarts.
Up/Down 2 with frequency reference from digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the Up/Down 2 bias value is
added to the frequency reference and then reset to 0. This new frequency reference is saved and will also be used to restart
the drive after the power is cycled.
Bias is added to frequency
reference and reset to 0

Output
frequency

Frequency
reference

Bias

5s

5s

Up 2 command

Figure 1.43 Up/Down 2 Example with Reference from Digital Operator and d4-01 = 1

Parameter Details

Up/Down 2 with frequency reference from input sources other than the digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the bias value will be saved
in parameter d4-06. When restarting after the power is switched off, the drive will add the value saved in d4-06 as a bias to
the frequency reference.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

63

1.4 d: Reference Settings


Bias is saved in parameter d4-06

Output
frequency

d4-06 value

Bias

5s
5s

Up 2 command

Figure 1.44 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note:

Set the limits for Up/Down 2 properly when using d4-01 = 1 in combination with the Up/Down 2 function. Refer to d4-08: Frequency
Reference Bias Upper Limit (Up/Down 2) on page 66 and Refer to d4-09: Frequency Reference Bias Lower Limit (Up/Down 2) on
page 66 for details on the limit settings.

Clearing the Saved Value

Depending on which function is used, it is possible to clear the saved frequency reference value by:
Releasing the input programmed for Acceleration hold.
Setting an Up or Down command while no Run command is active.
Resetting parameter d4-06 to zero. Refer to d4-06: Frequency Reference Bias (Up/Down 2) on page 65 for details.

n d4-03: Frequency Reference Bias Step (Up/Down 2)


Sets the bias added to or subtracted from the frequency reference by the Up/Down 2 function.
No.
d4-03

Parameter Name
Frequency Reference Bias Step (Up/Down 2)

Setting Range
0.00 to 99.99 Hz

Default
0.00 Hz

The operation depends on the set value:


Setting d4-03 = 0.0 Hz

While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel times determined
by parameter d4-04.
Output
frequency

Bias value is increased using the


accel/decel times as set in d4-04

Bias

Up 2 command

Figure 1.45 Up/Down 2 Bias when d4-03 = 0.0 Hz

Setting d4-03 0.0 Hz

When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for the value set in d4-03. The
frequency reference changes with the accel/decel times determined by parameter d4-04.

64

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.4 d: Reference Settings


Output
frequency

Bias

Bias value is increased in steps as


defined in d4-03
Drive uses accel/decel times as
set in d4-04

Up 2 command

Figure 1.46 Up/Down 2 Bias when d4-03 > 0.0 Hz

n d4-04: Frequency Reference Bias Accel/Decel (Up/Down 2)


Determines the accel/decel times used to increase or decrease the frequency reference or bias when using the Up/Down 2
function.
No.
d4-04

Parameter Name
Frequency Reference Bias Accel/Decel (Up/Down 2)

Setting Range
0, 1

Default
0

Setting 0: Current Accel/Decel Time

The drive uses the currently active accel/decel time.


Setting 1: Accel/Decel Time 4

The drive uses accel/decel time 4 set to parameters C1-07 and C1-08.

n d4-05: Frequency Reference Bias Operation Mode Selection (Up/Down 2)


Determines if the bias value is held when the Up/Down 2 inputs are both released or both enabled. The parameter is effective
only when parameter d4-03 is set to 0.00.
No.
d4-05

Parameter Name
Frequency Reference Bias Operation Mode Selection
(Up/Down 2)

Setting Range

Default

0, 1

Setting 0: Hold Bias Value

The bias value will be held if no input Up 2 or Down 2 is active.


Setting 1: Reset Bias Value

The bias is reset to 0% when inputs Up 2 and Down 2 are both on or both off. The drive will use the accel/decel time as selected
in d4-04 to accelerate or decelerate to the frequency reference value.
Saves the frequency reference bias value set by the Up/Down 2 function as a percentage of the maximum output frequency.
The function of this parameter depends on the Up/Down 2 function configuration. This parameter is not normally used when
the digital operator sets the frequency reference.
The value set to d4-06 will be applied during run, however the value is reset when the frequency reference changes (including
multi-step references) and is disabled when d4-01 = 0 and the Run command is removed.
When d4-01 = 0 and the frequency reference is set by a source other than the digital operator, the value set in d4-06 is added
to or subtracted from the frequency reference.
When d4-01 = 1 and the frequency reference is set by a source other than the digital operator, the bias value adjusted with
the Up/Down 2 inputs is stored in d4-06 when 5 s have passed after releasing the Up 2 or Down 2 command. The frequency
reference will return to the value without the Up/Down 2 command.
No.
d4-06

Parameter Name
Frequency Reference Bias (Up/Down 2)

Setting Range
-99.9 to 100.0%

Default
0.0%

Conditions that Reset or Disable d4-06

The Up/Down 2 function has not been assigned to the multi-function terminals.
The frequency reference source has been changed (including LOCAL/REMOTE or External reference 1/2 switch over by
digital inputs).
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

n d4-06: Frequency Reference Bias (Up/Down 2)

65

1.4 d: Reference Settings


d4-03 = 0 Hz, d4-05 = 1, and the Up/Down 2 commands are both open or both closed.
Any changes to the maximum frequency set to E1-04.

n d4-07: Analog Frequency Reference Fluctuation Limit (Up/Down 2)


Handles frequency reference changes while the Up 2 or Down 2 terminal is enabled. If the frequency reference changes for
more than the level set to d4-07, then the bias value will be held,and the drive will accelerate or decelerate following the
frequency reference. When the frequency reference is reached, the bias hold is released and the bias follows the Up/Down 2
input commands.
This parameter is applicable only if the frequency reference is set by an analog or pulse input.
No.
d4-07

Parameter Name
Analog Frequency Reference Fluctuation Limit (Up/Down 2)

Setting Range
0.1 to 100.0%

Default
1.0%

n d4-08: Frequency Reference Bias Upper Limit (Up/Down 2)


Sets the upper limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter d4-06. Set this
parameter to an appropriate value before using the Up/Down 2 function.
Note:

No.
d4-08

When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the frequency reference
if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. From that point, the bias can be increased up to the limit
set in d4-08 again.

Parameter Name
Frequency Reference Bias Upper Limit (Up/Down 2)

Setting Range
0.0 to 100.0%

Default
100.0%

n d4-09: Frequency Reference Bias Lower Limit (Up/Down 2)


Sets the lower limit of the Up/Down 2 bias (monitor U6-20) and the value that can be saved in parameter d4-06. Set this
parameter to an appropriate value before using the Up/Down 2 function.
Note:

No.
d4-09

When the frequency reference is set by the digital operator (b1-01 = 0) and d4-01 = 1, the bias value will be added to the frequency reference
if no Up/Down 2 command is received for 5 s, and will be reset to 0 afterwards. If the bias is increased using the Up 2 command, it cannot
be reduced with a Down 2 command when the limit set in d4-09 is 0. Set a negative lower limit in d4-09 to allow speed reduction in this
situation.

Parameter Name
Frequency Reference Bias Lower Limit (Up/Down 2)

Setting Range
-99.9 to 0.0%

Default
0.0%

n d4-10: Up/Down Frequency Reference Limit Selection


Selects how the lower frequency limit is set when using the Up/Down function. Refer to Setting 10, 11: Up/Down
Function on page 96 for details on the Up/Down function in combination with frequency reference limits.
No.
d4-10

Parameter Name
Up/Down Frequency Reference Limit Selection

Setting Range
0, 1

Default
0

Setting 0: Lower Limit is Determined by d2-02 or Analog Input

The higher value between d2-02 and an analog input programmed for Frequency bias (A1, A2, A3) determines the lower
frequency reference limit.
Note:

When using the External Reference 1/2 (H1-oo = 2) to switch between the Up/Down function and an analog input as the reference source,
the analog value becomes the lower reference limit when the Up/Down command is active. Set d4-10 to 1 to make the Up/Down function
independent of the analog input value.

Setting 1: Lower Limit is Determined by d2-02

Only parameter d2-02 sets the lower frequency reference limit.

u d5: Torque Control


Torque Control defines a setpoint for the motor torque and is available for CLV and CLV/PM (A1-02 = 3).
Note:

PM motor control modes are not available in A1000 HHP drive models.

n Torque Control Operation


Torque control can be enabled either by setting parameter d5-01 to 1 or by setting digital input (H1-oo = 71). Figure 1.47
illustrates the working principle.

66

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.4 d: Reference Settings


Torque Compensation
d5-02

External Torque Reference

U1-09

Torque Reference Delay


d5-08

C1-oo , C2-oo

External Speed Limit

Soft
Starter

+
+

1 d5-03
2

Speed Limit set in d5-04

L7-oo

Torque
Limits

Internal Torque
Reference

Speed Limiter
Compensated torque
reference

Speed Feedback
Speed Limit Bias d5-05

Figure 1.47 Torque Control Block Diagram

The externally input torque reference is the target value for the motor output torque. If the motor torque reference and the load
torque are not in balance when in Torque Control, the motor accelerates or decelerates. To prevent operation beyond the speed
limit, compensate the external torque reference value if the motor speed reaches the limit. The compensation value is calculated
using the speed limit, speed feedback, and the speed limit bias.
If an external torque compensation value is input, it is added to the speed limit compensated torque reference value. The value
calculated is limited by the L7-oo settings, and is then used as the internal torque reference, which can be monitored in
U1-09. The L7-oo settings have highest priority. The motor cannot be operated with a higher torque than the L7-oo settings
even if the external torque reference value is increased.

n Setting the Torque Reference, Speed Limit, and Torque Compensation Values
Torque Control Reference Sources

Set input values for Torque Control as explained in Table 1.27.


Table 1.27 Torque Control Input Value Selection

Input Value

Signal Source

Settings

Analog inputs A1/A2/


A3

H3-02, H3-06, or H3-10 = 13 <1>

Analog Option Card

F2-01 = 0
H3-02, H3-06, or H3-10 = 13 <1>

Torque Reference

Remarks
Match the input terminal signal level settings to
the signal being used. Refer to H3: MultiFunction Analog Inputs on page 113 for details
on adjusting analog input signals.
The F3-oo settings become effective for the
option board input terminals. Match the input
terminal signal level settings to the signal being
used. Refer to H3: Multi-Function Analog
Inputs on page 113 for details on adjusting
analog input signals.

Speed Limit

Set Register 000FH, Bit 2 = 1 to enable

Torque reference from register 0004H.


F6-06 = 1
Communication Option Refer to the option card manual for

Card
details about setting the torque
compensation value.
d5-03 = 1
Signal selected as
The speed limit is taken from the input The settings in C1-oo for accel/decel times and
frequency reference
selected as frequency reference source in C2-oo for S-curves are applied to the speed
source
limit value.
in parameter b1-01 or b1-15. <1>
Parameter d5-04
d5-03 = 2

Parameter Details

MEMOBUS Register
0004H

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

67

1.4 d: Reference Settings


Input Value

Torque
Compensation

Signal Source

Settings

Analog inputs A1/A2/


A3

H3-02, H3-06, or H3-10 = 14 <1>

Analog Option Card

F2-01 = 0
H3-02, H3-06, or H3-10 = 14 <1>

Remarks
Match the input terminal signal level settings to
the signal being used. Refer to H3: MultiFunction Analog Inputs on page 113 for details
on adjusting analog input signals.
The H3-oo settings become effective for the
option board input terminals. Match the input
terminal signal level settings to the signal being
used.

Set Register 000FH, bit 3 = 1 to enable


the torque compensation setting by
register 0005H.
F6-06 = 1
Communication Option Refer to the option card manual for
Card
details about setting the torque
compensation value.
MEMOBUS Register
0005H

<1> Sets analog input terminals A1, A2, and A3 to supply the speed limit, torque reference, or torque compensation. Setting two analog inputs for the
same function will trigger an oPE error.

Input Value Polarity

The direction of the input values described above depends on the polarity of the Run command and the input value.
Table 1.28 Torque Control Signal Polarity

Run Command Direction


Forward
Reverse

Input Value Polarity


+ (positive)
- (negative)
+ (positive)
- (negative)

Input Value Direction


Forward direction
Reverse direction
Reverse direction
Forward direction

Example:
The internal torque reference will be positive (forward) with a Forward run command and a positive torque reference signal.
The internal torque reference will be negative (reverse) with a Forward run command and a negative torque reference signal.
When using analog inputs, negative input values can be generated by:
Applying negative voltage input signals.
Using positive analog input signals while setting the analog input bias to negative values to make the input value negative.
When using MEMOBUS/Modbus communication or a communication option card, only positive input values can be set.
Independent of its input source, the polarity of the torque reference signal can be inverted using a digital input that is
programmed for H1-oo = 78. Use this function to input negative torque reference values when using MEMOBUS/Modbus
or a communication option card.

n Speed Limitation and Speed Limit Bias


The speed limit setting is read from the input selected in parameter d5-03. A bias can be added to this speed limit using
parameter d5-05 while parameter d5-08 determines how the speed limit bias is applied. Table 1.29 explains the relation between
these settings.
Table 1.29 Speed Limit, Speed Bias and Speed Limit Priority Selection

Run Command
Torque
Reference
Direction
Speed Limit
Direction
Normal
Operation
Direction

68

Forward

Operating Conditions
Forward
Forward

Forward

Positive (Forward)

Negative (Reverse)

Negative (Reverse)

Positive (Forward)

Positive (Forward)

Negative (Reverse)

Positive (Forward)

Negative (Reverse)

Forward

Reverse

Forward

Reverse

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.4 d: Reference Settings


Operating Conditions
Torque
Limit

Bidirectional
Speed Limit
Bias
(d5-08 = 0)
<1>

Torque
Speed Limit
n
Bias d5-05

Torque
Limit

Speed Limit
Bias d5-05

Torque
Limit

<1>

Torque
Limit

Speed
Limit Bias
d5-05

Speed
Internal
Torque
Reference

Torque
Limit

d5-05

Winder

Speed Torque

Speed Torque

Speed

Torque
n

Internal
Torque
Reference

Internal
Torque
Reference

Torque
Limit

Speed
Limit Bias
d5-05
Torque
Limit

Torque n
Limit

Speed Limit
0

Speed

Torque
Limit

Speed Limit
Bias d5-05

Internal
Torque
Reference

Internal
Torque
Reference

Speed
Limit

Torque

Speed Limit
Bias d5-05

Speed
Limit

Speed
Limit Bias
d5-05

Dn
Torque
Limit

Torque

Torque n
Limit

Speed

Speed

Torque
Limit

Application
Example

Internal
Torque
Reference

Torque

Speed
Limit

Internal
Torque
Reference

Speed Limit
Bias d5-05
Speed Limit

Speed
Limit

Torque
Torque n
Limit

Torque

Speed

Speed

Torque
Limit
Speed Limit
Bias d5-05

Speed
Limit

Internal
Torque
Reference

Speed Limit
Bias d5-05

Unidirectional
Speed Limit
Bias
(d5-08 = 1)

Torque

Speed
Limit

Speed
Speed
Limit Bias
d5-05
Torque
Limit

Torque
Limit

Unwinder

Torque Speed

Torque Speed

Line Direction

Line Direction

Line Direction

Line Direction

<1> The value of delta n in the drawings depends on the ASR setting in parameters C5-oo.

n Indicating Operation at the Speed Limit


Program a digital output to close when the drive operates at or beyond the speed limit (H2-oo = 32). Use this output to notify
a control device such as a PLC of abnormal operating conditions.

n Switching Between Torque and Speed Control

Note:

1. The switching delay time d5-06 is not applied when the Stop command is entered. Here the operation switches immediately to speed
control and the drive decelerates to stop at the torque limit.
2. Set d5-01 to 0 when switching between Torque Control and Speed Control. An oPE15 alarm will be triggered if parameter d5-01 is set
to 1 while H1-oo is set to 71 at the same time.

Parameter Details

Use a digital output to switch Torque Control and Speed Control (H1-oo = 71). When switching from Speed Control to
Torque Control, the torque limit becomes the torque reference and the speed reference becomes the speed limit. This change
is reversed when switching back to Speed Control.
If required by the application, set up a delay time using parameter d5-06. The reference values (torque reference/speed limit
in Torque Control or speed reference/torque limit in Speed Control) are held during this switch delay time. Change the reference
values from the controller within this delay time.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

69

1.4 d: Reference Settings

Run command

Operation Mode

Frequency reference
signal or d5-04

ON

OFF

Speed/Torque control
input (H1-oo = 71)

OFF

ON

ON

OFF

Speed Control

Torque Control

Speed Control

Torque Control

Speed Ref.

Speed Limit

Speed Ref.

Speed Limit

Torque reference signal/


Torque limit Torque Limit

Torque Reference

d5-06

Torque Limit

d5-06

Torque Reference

Speed Control

Speed Ref.

Torque Limit

d5-06

Figure 1.48 Speed/Torque Control Switching Time

n d5-01: Torque Control Selection


No.
d5-01

Parameter Name
Torque Control Selection

Setting Range
0, 1

Default
0

Setting 0: Disabled

Speed Control will be active. Also use this setting when H1-oo = 71 (Speed/Torque Control Switch).
Setting 1: Enabled

Torque Control is always enabled.

n d5-02: Torque Reference Delay Time


Apply a filter with the time constant set to parameter d5-02 to the torque reference signal to eliminate oscillation resulting
from an unstable torque reference signal. A higher filter time stabilizes control while reducing the responsiveness.
No.
d5-02

Parameter Name
Torque Reference Delay Time

Setting Range
0 to 1000 ms

Default
0 ms

Setting Range
1 or 2

Default
1

n d5-03: Speed Limit Selection


Determines how the speed limit is set.
No.
d5-03

Parameter Name
Speed Limit Selection

Setting 1: Frequency Reference Input

The frequency reference value at the active reference source (digital operator, External reference 1 or External reference 2)
will be used as speed limit. Note that in this case all settings for accel/decel times (C1-01 to C1-08) and S-curves (C2-01 to
C2-04) will apply for the speed limit.
Setting 2: d5-04

The speed limit is set by parameter d5-04.

n d5-04: Speed Limit


Sets the speed limit during torque control if parameter d5-03 is set to 2. Refer to Speed Limitation and Speed Limit Bias on
page 68.
No.
d5-04

Parameter Name
Speed Limit

Setting Range
-120 to 120%

Default
0%

n d5-05: Speed Limit Bias


Applies a bias set as a percentage of the maximum output frequency to the speed limit value. Refer to Speed Limitation and
Speed Limit Bias on page 68.
70

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.4 d: Reference Settings


No.
d5-05

Parameter Name
Speed Limit Bias

Setting Range
0 to 120%

Default
10%

Setting Range
0 to 1000 ms

Default
0 ms

Setting Range
0, 1

Default
1

n d5-06: Speed/Torque Control Switchover Time


Sets the delay time for switching between Speed Control and Torque Control.
No.
d5-06

Parameter Name
Speed/Torque Control Switchover Time

n d5-08: Unidirectional Speed Limit Bias


Selects how the speed limit bias is applied.
No.
d5-08

Parameter Name
Unidirectional Speed Limit Bias

Setting 0: Disabled

The speed limit bias is applied in the speed limit direction and the opposite direction.
Setting 1: Enabled

The speed limit bias is applied in the opposite direction of the speed limit only.

u d6: Field Weakening and Field Forcing


Field Weakening
The Field Weakening function reduces the output voltage to a predefined level to reduce the energy consumption of the motor.
To activate the Field Weakening function, use a digital input programmed for H1-oo = 63. Only use Field Weakening with
a known and unchanging light load condition. Use the Energy Saving function (b8-oo parameters) when Energy Saving for
various different load conditions is required.
Field Forcing
The Field Forcing function compensates the delaying influence of the motor time constant when changing the excitation current
reference and improves motor responsiveness. Field Forcing is ineffective during DC Injection Braking.

n d6-01: Field Weakening Level


Sets the level to which the output voltage is reduced when Field Weakening is activated. Set as percentage of the maximum
output voltage.
No.
d6-01

Parameter Name
Field Weakening Level

Setting Range
0 to 100%

Default
80%

n d6-02: Field Weakening Frequency Limit

No.
d6-02

Parameter Name
Field Weakening Frequency Limit

Setting Range
0 to 150.0 Hz

Default
0.0 Hz

Setting Range
0, 1

Default
0

Parameter Details

Sets the lower limit (in Hz) of the frequency range where field weakening control is valid. The field weakening command is
valid only at frequencies above this setting and only when output frequency is in agreement with the current output frequency
(speed agree).

n d6-03: Field Forcing Selection


Enables or disables the Field Forcing function.
No.
d6-03

Parameter Name
Field Forcing Selection

Setting 0: Disabled
Setting 1: Enabled

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

71

1.4 d: Reference Settings

n d6-06: Field Forcing Limit


Sets the maximum level at which the Field Forcing function can boost the excitation current reference. The value is set as a
percentage of the motor no load current. This parameter does not normally need to be changed.
No.
d6-06

Parameter Name
Field Forcing Limit

Setting Range
100 to 400%

Default
400%

u d7: Offset Frequency


n d7-01 to d7-03: Offset Frequency 1 to 3
Three different offset values can be added to the frequency reference. They can be selected using digital inputs programmed
for Offset frequency 1, 2, and 3 (H1-oo = 44, 45, 46). The selected offset values are added together if multiple inputs are
closed simultaneously.
Note:

This function can replace the Trim Control function (H1-oo = 1C, 1D) of older Yaskawa drives.

No.
d7-01
d7-02
d7-03

Parameter Name
Offset Frequency 1
Offset Frequency 2
Offset Frequency 3

Setting Range
-100.0 to 100.0%
-100.0 to 100.0%
-100.0 to 100.0%

Default
0%
0%
0%

Figure 1.49 illustrates the Offset frequency function.


Frequency
reference

SFS

Offset Frequency 1 [d7-01]


(Signed)

Multi-function
input (44) = on

Frequency
reference after
soft starter

Multi-function
input (45) = on
Offset Frequency 2 [d7-02]
(Signed)

Multi-function
input (46) = on
Offset Frequency 3 [d7-03]
(Signed)

Figure 1.49 Offset Frequency Operation

72

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.5 E: Motor Parameters

1.5

E: Motor Parameters

E parameters cover V/f pattern and motor data settings.

u E1: V/f Pattern for Motor 1


n E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal
voltage of the AC power supply.
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the
protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.

No.
E1-01

Parameter Name
Input Voltage Setting

Setting Range

Default

V <1>

460 V <1>

310 to 510

<1> Values shown are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690 V class
drives.

E1-01 Related Values

The input voltage setting determines the overvoltage and undervoltage detection levels, the operation levels of the braking
transistor, the KEB function, and the overvoltage suppression function.
(Approximate Values)
Voltage

400 V Class
575 V Class
690 V Class
Note:

Setting Value of E1-01

Uv Detection Level
(L2-05)

Desired DC Bus Voltage


during KEB (L2-11)

setting 400 V

380 Vdc

500 Vdc

ov Suppression /
Stall Prevention Level
(L3-17)
750 Vdc

setting < 400 V


575 V
794

350 Vdc
475 Vdc
570 Vdc

460 Vdc
635 Vdc
635 Vdc

750 Vdc
930 Vdc
930 Vdc

The braking transistor operation levels are valid for the drive internal braking transistor. When using an external CDBR braking chopper,
refer to the instruction manual of that unit.

n V/f Pattern Settings (E1-03)


The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference. There are 15 different predefined
V/f patterns (setting 0 to E) from which to select, each with varying voltage profiles, saturation levels (frequency at which
maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is available (setting F) that
requires the user to create the pattern using parameters E1-04 through E1-10.

n E1-03: V/f Pattern Selection


Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.
No.
E1-03

Parameter Name
V/f Pattern Selection

Setting Range
0 to

F <1>

Default
F

<2>

Parameter Details

<1> Settings 0 through E are not available when A1-02 = 2, 3.


<2> Parameter is not reset to the default value when the drive is initialized using A1-03.

Setting a Predefined V/f Pattern (Setting 0 to E)

Choose the V/f pattern that best meets the application demands from the table below. These settings are available only in
V/f Control modes. Set the correct value to E1-03. Parameters E1-04 to E1-13 can only be monitored, not changed.
Note:

1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

73

1.5 E: Motor Parameters


Table 1.30 Predefined V/f Patterns
Setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D

Specification
50 Hz
60 Hz
60 Hz (with 50 Hz base)
72 Hz (with 60 Hz base)
50 Hz, Heavy Duty 2
50 Hz, Heavy Duty 1
50 Hz, Heavy Duty 1
50 Hz, Heavy Duty 2
50 Hz, mid starting torque
50 Hz, high starting torque
60 Hz, mid starting torque
60 Hz, high starting torque
90 Hz (with 60 Hz base)
120 Hz (with 60 Hz base)

E
F

150 Hz (with 60 Hz base)

Characteristic

Application

Constant torque

For general purpose applications. Torque remains constant


regardless of changes to speed.

Variable torque

For fans, pumps, and other applications where the required


torque changes as a function of the speed.

High starting torque

60 Hz

<1>

Select high starting torque when:


Wiring between the drive and motor exceeds 150 m.
A large amount of starting torque is required.
An AC reactor is installed.

Constant output

Output voltage is constant when operating at greater than


60 Hz.

Constant torque

For general purpose applications. Torque remains constant


regardless of changes to speed.

<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.

The following tables show details on predefined V/f patterns.


Predefined V/f Patterns for all HHP models:

400 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
575 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
690 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty.
The values in the following graphs are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives.
Multiply the values by 1.725 for 690 V class drives.
Table 1.31 Rated Torque Characteristics, Settings 0 to 3
400

Setting = 1

60 Hz

Voltage (V)

Voltage (V)

Setting = 2

60 Hz

400

400

Setting = 3

24

24

24

24

12

12

12

12

0 1.3 2.5
50
Frequency (Hz)

50 60
0 1.5 3
Frequency (Hz)

0 1.5 3
60
Frequency (Hz)

72 Hz

400
Voltage (V)

50 Hz

Voltage (V)

Setting = 0

60 72
0 1.5 3
Frequency (Hz)

Table 1.32 Derated Torque Characteristics, Settings 4 to 7

10
0 1.3
25
50
Frequency (Hz)

74

50 Hz

Setting = 6

60 Hz

400

400

100
12

70
10

0 1.3
25
50
Frequency (Hz)

30
60
0 1.5
Frequency (Hz)

Setting = 7

60 Hz

400
Voltage (V)

Voltage (V)

70

Setting = 5

Voltage (V)

50 Hz

400

Voltage (V)

Setting = 4

100
12
0 1.5
30
60
Frequency (Hz)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.5 E: Motor Parameters


Table 1.33 High Starting Torque, Settings 8 to B

50 Hz

Setting = 9

Setting = A

30

40
18

14

Setting = B

60 Hz

400

30

40
22

14
0 1.5 3
60
Frequency (Hz)

0 1.3 2.5
50
Frequency (Hz)

0 1.3 2.5
50
Frequency (Hz)

60 Hz

400
Voltage (V)

Voltage (V)

Voltage (V)

50 Hz

400

400

Voltage (V)

Setting = 8

0 1.5 3
60
Frequency (Hz)

Table 1.34 Constant Output, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

150 Hz

Setting = F

60 Hz

24
12

24
12

0 1.5 3
60 90
Frequency (Hz)

0 1.5 3
60 120
Frequency (Hz)

400
Voltage (V)

400
Voltage (V)

Voltage (V)

400

Voltage (V)

460

27.6
13.8
0 1.5 3
60
Frequency (Hz)

24

Note: The values in this graph are


specific to 400 V class drives in
setting F. Multiply the values by
1.25 for 575 V class drives.
Multiply the values by 1.725 for
690 V class drives.

12
0 1.5 3
60 150
Frequency (Hz)

Setting a Custom V/f Pattern (Setting F: Default)

Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When initialized, the default values for parameters E1-04 to E1-13 will be equal to Predefined V/f pattern 1.

n V/f Pattern Settings E1-04 to E1-13


If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F. Refer to V/f Pattern on page 76 for an example custom V/f
pattern.
Certain E1-oo parameters might not be visible depending on the control mode. Refer to Parameter List on page 229 for details.

No.

Parameter Name

Setting Range

Default

E1-04

Maximum Output Frequency

40.0 to 150.0 Hz

<1>

V <3>

<1>

E1-05

Maximum Voltage

E1-06

Base Frequency

0.0 to [E1-04]

<1>

E1-07

Middle Output Frequency

0.0 to [E1-04]

<1>

E1-08

Middle Output Frequency Voltage

E1-09

Minimum Output Frequency

E1-10

Minimum Output Frequency Voltage

E1-11

Middle Output Frequency 2

0.0 to 510.0

0.0 to 510.0 V

<3>

<1>
<1>

0.0 to [E1-04]
0.0 to 510.0 V

<3>

0.0 to [E1-04]

E1-12

Middle Output Frequency Voltage 2

0.0 to 510.0 V

<3>

E1-13

Base Voltage

0.0 to 510.0 V

<3>

<1>

0.0 Hz <5>
0.0 V

<4> <5>

0.0 V

<4>

<1> Default setting is determined by the control mode.


<3> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<4> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
<5> Parameter ignored when E1-11 and E1-12 are set to 0.0.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

75

Parameter Details

Note:

1.5 E: Motor Parameters


Output Voltage (V)
E1-05
E1-12
E1-13

E1-08
E1-10
E1-09

E1-07 E1-06 E1-11 E1-04


Frequency (Hz)

Figure 1.50 V/f Pattern


Note:

1.
2.
3.
4.

The following condition must be true when setting up the V/f pattern: E1-09 E1-07 < E1-06 E1-11 E1-04
To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
Only use E1-11, E1-12, and E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.

u E2: Motor 1 Parameters


These parameters contain the motor data needed for motor 1. Performing Auto-Tuning (including Rotational Auto-Tuning
and Stationary Auto-Tuning 1 and 2) automatically sets these parameters. Manually enter the motor data into these parameters
when Auto-Tuning cannot be performed.
Note:

The function for switching between two motors cannot be used with a PM motor. E2-oo parameters are hidden when a PM motor control
mode is selected (A1-02 = 5, 6, or 7).

n E2-01: Motor Rated Current


Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.
No.

Parameter Name

E2-01

Motor Rated Current

Note:

Setting Range
10% to 200% of the drive
rated current

Default
Determined by
C6-01 and o2-04

1. The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This
value has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one
decimal place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly
to prevent this error.

n E2-02: Motor Rated Slip


Sets the motor rated slip in Hz to provide motor control, protect the motor, and calculate torque limits. This value is
automatically set during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1 and 2).
No.

Parameter Name

Setting Range

E2-02

Motor Rated Slip

0.00 to 20.00 Hz

Default
Determined by
C6-01 and o2-04

If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate and
the formula below:
E2-02 = f - (n p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)

n E2-03: Motor No-Load Current


Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive sets
E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load current
listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to receive a copy of the
motor test report.

76

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.5 E: Motor Parameters


No.

Parameter Name

E2-03

Motor No-Load Current

Note:

Setting Range
0 to [E2-01]
(unit: 0.01 A)

Default
Determined by
C6-01 and o2-04

The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal
place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW.

n E2-04: Number of Motor Poles


Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
E2-04

Parameter Name
Number of Motor Poles

Setting Range
2 to 48

Default
4

n E2-05: Motor Line-to-Line Resistance


Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is automatically
calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it manually.
When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
E-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
B-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
F-type insulation: Multiply 0.87 times the resistance value () listed on the test report at 115 C.
No.

Parameter Name

Setting Range

E2-05

Motor Line-to-Line Resistance

0.000 to 65000 m <1>

Default
Determined by
C6-01 and o2-04

<1> Units are expressed in m for models CIMR-Ao4A0930, 4A1200 and A1000 HHP.

n E2-06: Motor Leakage Inductance


Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. This value is automatically set
during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
No.

Parameter Name

Setting Range

E2-06

Motor Leakage Inductance

0.0 to 40.0%

Default
Determined by
C6-01 and o2-04

n E2-07: Motor Iron-Core Saturation Coefficient 1


Sets the motor iron saturation coefficient at 50% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then
this value is automatically calculated and set to E2-07. This coefficient is used when operating with constant output.
No.
E2-07

Parameter Name
Motor Iron-Core Saturation Coefficient 1

Setting Range
0.00 to 0.50

Default
0.50

Sets the motor iron saturation coefficient at 75% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then
this value is automatically calculated and set to E2-08. This coefficient is used when operating with constant output.
No.
E2-08

Parameter Name
Motor Iron-Core Saturation Coefficient 2

Setting Range
E2-07 to 0.75

Default
0.75

n E2-09: Motor Mechanical Loss

Sets the motor mechanical loss as a percentage of motor rated power (kW) capacity.
Adjust this setting in the following circumstances:
When there is a large amount of torque loss due to motor bearing friction.
When there is a large amount of torque loss in a fan or pump application.
The setting for the mechanical loss is added to the torque.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

n E2-08: Motor Iron-Core Saturation Coefficient 2

77

1.5 E: Motor Parameters


No.
E2-09

Parameter Name
Motor Mechanical Loss

Setting Range
0.0 to 10.0%

Default
0.0%

Default
Determined by
C6-01 and o2-04

n E2-10: Motor Iron Loss for Torque Compensation


Sets the motor iron loss in watts.
No.

Parameter Name

Setting Range

E2-10

Motor Iron Loss for Torque Compensation

0 to 65535 W

n E2-11: Motor Rated Power


Sets the motor rated power in kW. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be
saved to E2-11.
No.

Parameter Name

Setting Range

E2-11

Motor Rated Power

0.00 to 650.00 kW

Note:

Default
Determined by
o2-04

The display resolution depends on the rated output power of the drive after setting the Drive Duty in parameter C6-01. Drive models CIMRAo2A0004 to 4A0515 display this value in units of 0.01 kW (two decimal places). Drive models CIMR-Ao4A0675 to 4A1200 and HHP
models display this value in units of 0.1 kW (one decimal place).

n Setting Motor Parameters Manually


Follow the instructions below when setting motor-related parameters manually instead of Auto-Tuning. Refer to the motor
test report included with the motor to ensure the correct data is entered into the drive.
Set the Motor Rated Current

Enter the motor rated current listed on the nameplate of the motor to E2-01.
Set the Motor Rated Slip

Calculate the motor rated slip using the base speed listed on the motor nameplate. Refer to the formula below, then enter that
value to E2-02.
Motor rated slip = rated frequency [Hz] base speed [r/min] (no. of motor poles) / 120
Set the No-Load Current

Enter the no-load current at rated frequency and rated voltage to E2-03. This information is not usually listed on the nameplate.
Contact the motor manufacturer if the data cannot be found.
The default setting of the no-load current is for performance with a 4-pole Yaskawa motor.
Set the Number of Motor Poles

Only required in V/f Control with PG and Closed Loop Vector Control. Enter the number of motor poles as indicated on motor
nameplate.
Set the Line-to-Line Resistance

E2-05 is normally set during Auto-Tuning. If Auto-Tuning cannot be performed, contact the motor manufacturer to determine
the correct resistance between motor lines. The motor test report can also be used to calculate this value using the formulas
below:
E-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
B-type insulation: Multiply 0.92 times the resistance value () listed on the test report at 75 C.
F-type insulation: Multiply 0.87 times the resistance value () listed on the test report at 115 C.
Set the Motor Leakage Inductance

The motor leakage inductance set to E2-06 determines the amount of voltage drop relative to the motor rated voltage. Enter
this value for motors with a low degree of inductance, such as high-speed motors. This information is usually not listed on the
motor nameplate. Contact the motor manufacturer if the data cannot be found.
Set the Motor Iron-Core Saturation Coefficient 1, 2

E2-07 and E2-08 are set when Auto-Tuning is performed.

78

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.5 E: Motor Parameters


Set the Motor Mechanical Loss

Only required in Closed Loop Vector Control. The drive compensates for the degree of mechanical loss with torque
compensation. Although E2-09 rarely needs to be changed, adjustment may be necessary in the following circumstances:
When there is a large amount of torque loss due to motor bearing friction.
When there is a large amount of torque loss in a fan or pump application.
Set the Motor Iron Loss for Torque Compensation

Only required when using V/f Control. Enter this value in watts to E2-10. The drive uses this setting to improve the precision
of torque compensation.

u E3: V/f Pattern for Motor 2


These parameters set the V/f pattern used for motor 2. Refer to Setting 16: Motor 2 Selection on page 98 for details on
switching motors.
Note:

The function for switching between two motors cannot be used with a PM motor. E3-oo parameters are hidden when a PM motor control
mode is selected (A1-02 = 5, 6, or 7).

n E3-01: Motor 2 Control Mode Selection


Selects the control mode for motor 2. A control mode for PM motors cannot be selected for motor 2.
No.
E3-01
Note:

Parameter Name
Motor 2 Control Mode Selection

Setting Range
0 to 3

Default
0

L1-01 determines protection from motor overload (oL1) in motor 2 and motor 1.

Setting 0: V/f Control


Setting 1: V/f Control with PG
Setting 2: Open Loop Vector Control
Setting 3: Closed Loop Vector Control

n E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in Figure 1.51.
Certain E3-oo parameters might not be visible depending on the control mode. Refer to Parameter List on page 229 for details.

No.

Parameter Name

Setting Range

E3-04

Motor 2 Max Output Frequency

40.0 to 150.0 Hz
V <1>

E3-05

Motor 2 Max Voltage

E3-06

Motor 2 Base Frequency

0.0 to [E3-04]

E3-07

Motor 2 Mid Output Frequency

0.0 to [E3-04]

0.0 to 510.0

V <1>

Default
<2>
<1> <2>
<2>
<2>
<1> <2>

E3-08

Motor 2 Mid Output Frequency Voltage

E3-09

Motor 2 Minimum Output Frequency

0.0 to [E3-04]

<2>

E3-10

Motor 2 Minimum Output Frequency Voltage

0.0 to 510.0 V <1>

<1> <2>

E3-11

Motor 2 Mid Output Frequency 2

0.0 to [E3-04]

0.0 Hz <4>

E3-12

Motor 2 Mid Output Frequency Voltage 2

0.0 to 510.0 V <1>

E3-13

Motor 2 Base Voltage

0.0 to 510.0 V <1>

0.0 to 510.0

0.0 V

<3> <4>

0.0 V

<3>

<1> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<2> Default setting is determined by the control mode selected for motor 2 (E3-01).
<3> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
<4> Parameter ignored when E3-11 and E3-12 are set to 0.0.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

79

Parameter Details

Note:

1.5 E: Motor Parameters


Output (V)
E3-05
E3-12
E3-13

E3-08

E3-10
E3-09

E3-07 E3-06 E3-11 E3-04


Frequency (Hz)

Figure 1.51 V/f Pattern for Motor 2


Note:

1. The following conditions must be true when setting up the V/f pattern: E3-09 E3-07 < E3-06 3-11 E3-04
2. To make the V/f pattern a straight line at a frequency lower than E3-07, set E3-09 equal to E3-07. In this case the E3-08 setting is
disregarded.
3. Parameters E3-04 through E3-13 are reset to their default values when the drive is initialized.
4. Only use E3-11, E3-12, and E3-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.

u E4: Motor 2 Parameters


E4 parameters contain the motor data for motor 2. These parameters are usually set automatically during the Auto-Tuning
process for vector control modes (Rotational Auto-Tuning, Stationary Auto-Tuning 1 and 2). It may be necessary to set these
parameters manually if there is a problem performing Auto-Tuning.

n E4-01: Motor 2 Rated Current


Protects the motor and calculates torque limits. Set E4-01 to the full load amps (FLA) stamped on the nameplate of motor 2.
If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E4-01.
No.

Parameter Name

E4-01

Motor 2 Rated Current

Note:

Setting Range
10 to 200% of the drive rated
current.

Default
Determined by
C6-01 and o2-04

1. The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This
value has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one
decimal place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW.
2. An oPE02 error will occur if the motor rated current in E4-01 is set lower than the motor no-load current in E4-03. Set E4-03 correctly
to prevent this error.

n E4-02: Motor 2 Rated Slip


Sets the motor 2 rated slip frequency and is the basis for slip compensation value. The drive calculates this value automatically
during Auto-Tuning (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
Refer to E2-02: Motor Rated Slip on page 76 for information on calculating the motor rated slip.
No.

Parameter Name

Setting Range

E4-02

Motor 2 Rated Slip

0.00 to 20.00 Hz

Default
Determined by
C6-01 and o2-04

n E4-03: Motor 2 Rated No-Load Current


Sets the no-load current for motor 2 in amperes when operating at the rated frequency and the no-load voltage. The drive sets
E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor no-load current
listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer for a copy of the motor
test report.
No.

Parameter Name

Setting Range

E4-03

Motor 2 Rated No-Load Current

0 to [E4-01]

Note:

80

Default
Determined by
C6-01 and o2-04

The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal
place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.5 E: Motor Parameters

n E4-04: Motor 2 Motor Poles


Sets the number of poles for motor 2. If Auto-Tuning completes successfully, the value entered to T1-06 will be automatically
saved to E4-04.
No.
E4-04

Parameter Name
Motor 2 Motor Poles

Setting Range
2 to 48

Default
4

n E4-05: Motor 2 Line-to-Line Resistance


Sets the line-to-line resistance for the motor 2 stator winding. If Auto-Tuning completes successfully, this value is automatically
calculated. Enter this value as line-to-line and not for each motor phase. Refer to E2-05: Motor Line-to-Line Resistance on
page 77 to manually enter this parameter setting.
No.

Parameter Name

Setting Range

E4-05

Motor 2 Line-to-Line Resistance

0.000 to 65000 m <1>

Default
Determined by
C6-01 and o2-04

<1> Units are expressed in m for models CIMR-Ao4A0930, 4A1200 and A1000 HHP.

n E4-06: Motor 2 Leakage Inductance


Sets the voltage drop due to motor leakage inductance as a percentage of rated voltage of motor 2. This value is automatically
set during Auto-Tuning (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2).
No.

Parameter Name

Setting Range

E4-06

Motor 2 Leakage Inductance

0.0 to 40.0%

Default
Determined by
C6-01 and o2-04

n E4-07: Motor 2 Motor Iron-Core Saturation Coefficient 1


Sets the motor 2 iron saturation coefficient at 50% of magnetic flux. This value is automatically set during Rotational AutoTuning. Adjust this parameter when operating in the constant output range.
No.
E4-07

Parameter Name
Motor 2 Motor Iron-Core Saturation Coefficient 1

Setting Range
0.00 to 0.50

Default
0.50

n E4-08: Motor 2 Motor Iron-Core Saturation Coefficient 2


Sets the motor iron saturation coefficient at 75% of magnetic flux. This value is automatically set during Rotational AutoTuning. Adjust this parameter when operating in the constant output range.
No.
E4-08

Parameter Name
Motor 2 Motor Iron-Core Saturation Coefficient 2

Setting Range
[E4-07] to 0.75

Default
0.75

n E4-09: Motor 2 Mechanical Loss

No.
E4-09

Parameter Name
Motor 2 Mechanical Loss

Parameter Details

Sets the motor mechanical loss as a percentage of motor rated power (kW).
Although E4-09 rarely needs to be changed, adjustment may be necessary in the following circumstances:
When there is a large amount of torque loss due to motor bearing friction.
When there is a large amount of torque loss in a fan or pump application.
The setting for the mechanical loss is added to the torque.
Setting Range
0.0 to 10.0%

Default
0.0%

Default
Determined by
C6-01 and o2-04

n E4-10: Motor 2 Iron Loss


Sets the motor 2 iron loss in watts.
No.

Parameter Name

Setting Range

E4-10

Motor 2 Iron Loss

0 to 65535 W

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

81

1.5 E: Motor Parameters

n E4-11: Motor 2 Rated Power


Sets the motor 2 rated power. If Auto-Tuning completes successfully, the value entered to T1-02 will automatically be saved
to E4-11.
No.

Parameter Name

Setting Range

E4-11

Motor 2 Rated Power

0.00 to 650.00 kW

Note:

82

Default
Determined by
o2-04

The display resolution depends on the rated output power of the drive after setting the Drive Duty in parameter C6-01. Drive models CIMRAo2A0004 to 4A0515 display this value in units of 0.01 kW (two decimal places). Drive models CIMR-Ao4A0675 to 4A1200 and HHP
models display this value in units of 0.1 kW (one decimal place).

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.6 F: Option Settings

1.6

F: Option Settings

u F1: PG Speed Control Card Settings


Yaskawa offers a PG-X3 and PG-B3 motor encoder PG option card. Use the CN5-C port when using only one PG option card
and use the CN5-C and CN5-B ports when using two PG option cards. When programming one of the multi-function input
terminals to act as a switch between two motors (H1-oo= 16), use the card connected to port CN5-C for motor 1 and use the
card connected to CN5-B for motor 2.
Table 1.35 lists the parameters that must be set for each option card port.
Table 1.35 Option Card Ports and Corresponding Parameters

Port
Parameters
CN5-C and CN5-B (common) F1-02 to F1-04, F1-08 to F1-11, F1-14
CN5-C only
F1-01, F1-05, F1-06, F1-12, F1-13, F1-20 for A1000 HHP only, F1-21
CN5-B only
F1-31 to F1-37

n F1-01, F1-31: PG 1 and PG 2 Pulses Per Revolution


Sets the number encoder number of pulses per revolution.
No.
F1-01
F1-31

Parameter Name
PG 1 Pulses Per Revolution
PG 2 Pulses Per Revolution

Option Port
CN5-C
CN5-B

Setting Range
ppr <1>

0 to 60000
0 to 60000 ppr

Default
1024 ppr
1024 ppr

<1> Setting range is 0 to 15000 in PM motor control modes

n F1-02, F1-14: PG Open (PGo) Circuit Operation Selection, Detection Time


A PGo fault is triggered if the drive receives no pulse signal for longer than the time set in F1-14. Set the stopping method for
a PGo fault in parameter F1-02.
No.
F1-02
F1-14

Parameter Name
Operation Selection at PG Open Circuit (PGo)
PG Open-Circuit Detection Time

Option Port
CN5-B, CN5-C
CN5-B, CN5-C

Setting Range
0 to 3
0.0 to 10.0 s

Default
1
2.0 s

Parameter F1-02 Settings:


Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only
Note:

Due to potential damage to motor and machinery, refrain from using the Alarm only or No alarm display settings except under special
circumstances.

Note:

Due to potential damage to motor and machinery, refrain from using the Alarm only or No alarm display settings except under special
circumstances.

n F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An oS fault is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set in F1-09. Set the
stopping method for an oS fault in parameter F1-03.
No.
F1-03
F1-08
F1-09

Parameter Name
Operation Selection at Overspeed (oS)
Overspeed Detection Level
Overspeed Detection Delay Time

Option Port
CN5-B, CN5-C
CN5-B, CN5-C
CN5-B, CN5-C

Setting Range
0 to 3
0 to 120%
0.0 to 2.0 s

Default
1
115%
Determined by A1-02

Parameter F1-03 Settings:


Setting 0: Ramp to stop (uses the deceleration time set to C1-02)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

83

Parameter Details

Setting 4: No alarm display

1.6 F: Option Settings


Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only
Note:

Due to potential damage to motor and machinery, refrain from using the Alarm only setting except under special circumstances.

n F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time
A speed deviation error (dEv) is triggered when the difference between the frequency reference and the speed feedback exceeds
the value set in F1-10 for longer than the time set in F1-1. The stopping method when a speed deviation fault occurs can be
selected in parameter F1-04.
No.
F1-04
F1-10
F1-11

Parameter Name
Operation Selection at Deviation (dEv)
Excessive Speed Deviation Detection Level
Excessive Speed Deviation Detection Delay Time

Option Port
CN5-B, CN5-C
CN5-B, CN5-C
CN5-B, CN5-C

Setting Range
0 to 3
0 to 50%
0.0 to 10.0 s

Default
3
10%
0.5 s

Settings for Parameter F1-04:


Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (drive continues operating while dEv flashes on the screen)

n F1-05, F1-32: PG 1, PG 2 Rotation Selection


Determines the direction indicated by the pulses from the PG feedback encoder for motor 1 and motor 2.
See PG option card instruction manual for details on setting the direction for the PG encoder and the motor.
No.
F1-05
F1-32

Parameter Name
PG 1 Rotation Selection
PG 2 Rotation Selection

Option Port
CN5-C
CN5-B

Setting Range
0, 1
0, 1

Default
0
0

Setting 0: A pulse leads with Forward run command


Setting 1: B pulse leads with Forward run command

n F1-06, F1-35: PG 1, PG 2 Division Rate for PG Pulse Monitor


Sets the ratio between the pulse input and the pulse output of a PG option card as a three-digit number, where the first digit
(n) sets the numerator and the second and third digit (m) set the denominator as shown below:
fPulse Input = fPulse Output

(1 + n)
m

Example: Set F1-06 to 032 for a ratio of 1/32 between the PG card pulse input and output.
No.

Parameter Name

Option Port

Setting Range

Default

1
32

F1-06

PG 1 Division Rate for PG Pulse Monitor

CN5-C

1 to 132 (1 to )

F1-35

PG 2 Division Rate for PG Pulse Monitor

CN5-B

1 to 132 (1 to 32 )

n F1-12, F1-13, F1-33, F1-34: PG 1, PG 2 Gear Teeth 1, 2 (V/f w/PG only)


Sets the gear ratio between the motor shaft and the PG encoder. F1-12 and F1-33 set the number of gear teeth on the motor
side, while F1-13 and F-34 set the number of gear teeth on the load side. The drive uses the formula below to calculate the
motor speed:
r/min =

84

Input pulses from PG 60


Pulses per Rev (F1-01/31)

Load-side PG gear teeth (F1-12/33)


Motor-side PG gear teeth (F1-13/34)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.6 F: Option Settings


No.
F1-12
F1-13
F1-33
F1-34
Note:

Parameter Name
PG 1 Gear Teeth 1
PG 1 Gear Teeth 2
PG 2 Gear Teeth 1
PG 2 Gear Teeth 2

Option Port
CN5-C
CN5-C
CN5-B
CN5-B

Setting Range
0 to 1000
0 to 1000
0 to 1000
0 to 1000

Default
0
0
0
0

Setting Range
0, 1
0, 1

Default
1
1

A gear ratio of 1 will be used if any of these parameters are set to 0.

n F1-20, F1-36: PG Option Card Disconnect Detection


Sets whether the drive detects a fault when a PG-X3 card is disconnected.
No.
F1-20
F1-36

Parameter Name
PG Option Card Disconnection Detection 1
PG Option Card Disconnection Detection 2

Option Port
CN5-C
CN5-B

Setting 0: Disabled
Setting 1: Enabled

n F1-21, F1-37: PG 1, PG 2 Signal Selection (V/f w/PG only)


Determines whether the signal to the PG option card is single-channel or two-channel.
No.
F1-21
F1-37

Parameter Name
PG 1 Signal Selection
PG 2 Signal Selection

Option Port
CN5-C
CN5-B

Setting Range
0, 1
0, 1

Default
0
0

Setting 0: Single-channel (A channel only)


Setting 1: Two-channel (channels A and B)

n F1-30: PG Option Card Port for Motor 2 Selection


Specifies the drive port for the PG option card used for motor 2. Set this parameter when switching between motor 1 and motor
2, where both motors supply a speed feedback signal to the drive. Set F1-30 to 0 when using the same PG card for feedback
signals from both motors. Set F1-30 to 1 when each motor has its own PG card connected to the drive.
Note:

The motor 2 selection function cannot be used with PM motors.

No.
F1-30

Parameter Name
PG Option Card Port for Motor 2 Selection

Setting Range
0, 1

Default
1

Setting 0: CN5-C
Setting 1: CN5-B

These parameters set the drive for operation with the analog input option card AI-A3. This section describes parameters that
govern operation with an input option card. Refer to the option card instruction manual for specific details on installation,
wiring, input signal level selection, and parameter setup.

n F2-01: Analog Input Option Card Operation Selection


Determines how the input terminals on the AI-A3 option card are used.
No.
F2-01

Parameter Name
Analog Input Option Card Operation Selection

Setting Range
0, 1

Default
0

Setting 0: Separate functions for each terminal (V1, V2, V3 replace terminals A1, A2, A3)

Use the H3-oo parameters described in H3-03, H3-04: Terminal A1 Gain and Bias Settings on page 113 to set the functions
and gain and bias levels for an analog reference supplied by AI-A3.
Note:

Setting option card terminals for separate input functions (F2-01 = 0) while b1-01 = 3 will cause an oPE05 error.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

u F2: Analog Input Card Settings

85

1.6 F: Option Settings


Setting 1: Combine input terminal values to create frequency reference

This setting adds all three input signals on the AI-A3 option card to create the frequency reference. Set b1-01 to 3 when the
option card is the source of the frequency reference for the drive. Set the gain and bias settings for the frequency reference
supplied from AI-A3 with F2-02 and F2-03.

n F2-02, F2-03: Analog Input Option Card Gain, Bias


Parameter F2-02 sets the gain and parameter F2-03 sets the bias for the AI-A3 input signal when the card is used in the combined
input signals mode (F2-01 = 1). Both gain and bias are set as a percentage of the maximum output frequency.
No.
F2-02
F2-03
Note:

Parameter Name
Analog Input Option Card Gain
Analog Input Option Card Bias

Setting Range
-999.9 to 999.9%
-999.9 to 999.9%

Default
100.0%
0.0%

Enabled only when F2-01 = 1.

u F3: Digital Input Card Settings


These parameters set the drive for operation with the option card DI-A3. Refer to the instruction manual packaged with the
option card for specific details on installation, wiring, input signal level selection, and parameter setup.

n F3-01: Digital Input Option Card Input Selection


Determines the type of input for digital option card DI-A3 when o1-03 is set to 0 or 1.
No.
F3-01
Note:

Parameter Name
Digital Input Option Card Input Selection

Setting Range
0 to 7

Default
0

BCD input when o1-03 = 2 or 3. Units are determined by o1-03.

Setting 0: BCD, 1% units


Setting 1: BCD, 0.1% units
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5 digit input), 0.02 Hz units
Setting 7: Binary

n F3-03: Digital Input Option DI-A3 Data Length Selection


Determines the number of bits for the option card input that sets the frequency reference.
No.
F3-03

Parameter Name
Digital Input Option DI-A3 Data Length Selection

Setting Range
0 to 2

Default
2

Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit

u F4: Analog Monitor Card Settings


These parameters set the drive for operation with the analog output option card AO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.

86

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.6 F: Option Settings

n F4-01, F4-03: Terminal V1, V2 Monitor Selection


Selects the data to output from analog terminal V1. Enter the final three digits of Uo-ooto determine which monitor data
is output from the option card. Some monitors are only available in certain control modes.
No.
F4-01
F4-03

Parameter Name
Terminal V1 Monitor Selection
Terminal V2 Monitor Selection

Setting Range
000 to 999
000 to 999

Default
102
103

n F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set as
a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is limited to
10 V.
No.
F4-02
F4-04
F4-05
F4-06

Parameter Name
Terminal V1 Monitor Gain
Terminal V2 Monitor Gain
Terminal V1 Monitor Bias
Terminal V2 Monitor Bias

Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%

Default
100.0%
50.0%
0.0%
0.0%

Using Gain and Bias to Adjust Output Signal Level

When viewing the values set to F4-02 or F4-05 on the digital operator, a voltage equal to 100% of the parameter being viewed
(including current gain and bias settings) will be output from terminal V1 or V2. When viewing the value set to F4-05 or
F4-06, terminal V1 or V2 will output a voltage equal to 0% of the parameter being viewed (including current gain and bias
settings).
Example 1: F4-02 = 0%, F4-02 = 80%. When the parameter setting display for F4-02 is accessed using the digital operator,
terminal V1 will output a voltage of 8 V, even when the drive is stopped.
Example 2: F4-03 = 5%. When the parameter setting display for F4-03 is accessed using the digital operator, terminal V1 will
output a voltage of 0.5 V, even when the drive is stopped.

n F4-07, F4-08: Terminal V1, V2 Signal Level


Sets the output signal level for terminals V1 and V2.
No.
F4-07
F4-08

Parameter Name
Terminal V1 Signal Level
Terminal V2 Signal Level

Setting Range
0, 1
0, 1

Default
0
0

Setting 0: 0 to 10 V
Setting 1: -10 to 10 V

u F5: Digital Output Card Settings


These parameters set the drive for operation with the digital output option card DO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
Parameter Details

n F5-01 through F5-08: Digital Output Option Card Terminal Function Selection
When F5-09 = 2, the parameters listed in the table below assign functions to the output terminals on the option card.
No.
F5-01
F5-02
F5-03
F5-04
F5-05
F5-06
F5-07

Name
Terminal P1-PC Output Selection
Terminal P2-PC Output Selection
Terminal P3-PC Output Selection
Terminal P4-PC Output Selection
Terminal P5-PC Output Selection
Terminal P6-PC Output Selection
Terminal M1-M2 Output Selection

Setting Range
0 to 192
0 to 192
0 to 192
0 to 192
0 to 192
0 to 192
0 to 192

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Default
2: Speed agree
4: Frequency detection 1
6: Drive ready
37: During frequency output
F: Not used
F: Not used
0: During run

87

1.6 F: Option Settings


No.
F5-08

Name
Terminal M3-M4 Output Selection

Setting Range
0 to 192

Default
1: Zero speed

n F5-09: DO-A3 Output Mode Selection


Determines how the DO-A3 option card works with the drive.
No.
F5-09
Note:

Parameter Name
DO-A3 Output Mode Selection

Setting Range
0 to 2

Default
0

Refer to TOBP C730600 41 Yaskawa AC Drive-Option DO-A3 Installation Manual for more details on F5-09 settings.

Setting 0: Separate output functions for each of 8 terminals


Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08

u F6: Communication Option Card


These parameters configure communication option cards and communication fault detection methods.
Some parameters apply to all communication option cards and some parameters apply to certain network options only. The
option cards are applicable to the parameter rows marked with an O.
Parameter

CC-Link

Communication Protocol
MECHATROLINK-II
PROFIBUS-DP

CANopen

DeviceNet

F6-01 to F6-03,
F6-06 to F6-08

F6-04, F6-10,
F6-11, F6-14

F6-20 to F6-26
F6-30 to F6-32
F6-35 to F6-36
F6-50 to F6-63

n F6-01: Communications Error Operation Selection


Determines drive operation when a communication error occurs.
No.
F6-01

Parameter Name
Communications Error Operation Selection

Setting Range
0 to 3

Default
1

Setting 0: Ramp to stop (uses the deceleration time set to C1-02)


Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (continue operation)

n F6-02: External Fault from Comm. Option Detection Selection


Determines the detection method of an external fault initiated by a communication option (EF0).
No.
F6-02

Parameter Name
External Fault from Comm. Option Detection Selection

Setting Range
0, 1

Default
0

Setting 0: Always detected


Setting 1: Detection during run only

n F6-03: External Fault from Comm. Option Operation Selection


Determines drive operation when an external fault is initiated by a communication option (EF0).
88

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.6 F: Option Settings


No.
F6-03

Parameter Name
External Fault from Comm. Option Operation Selection

Setting Range
0 to 3

Default
1

Setting 0: Ramp to stop


Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)

n F6-06: Torque Reference/Torque Limit Selection from Comm. Option


Selects whether torque reference and torque limit values are assigned to the drive from the network.
No.
F6-06

Parameter Name
Torque Reference/Torque Limit Selection from Comm. Option

Setting Range
0, 1

Default
0

Setting Range
0, 1

Default
0

Setting 0: Enabled
Setting 1: Disabled

n F6-07: NetRef/ComRef Function Selection


Selects the treatment of multi-step speed inputs when the NetRef command is set.
No.
F6-07

Parameter Name
NetRef/ComRef Function Selection

Setting 0: Multi-step speed operation disabled

Multi-step speed input frequency references are disabled when the NetRef command is selected.
Setting 1: Multi-step speed operation enabled

Multi-step speed inputs are still active and can override the frequency reference from the communications option even when
the NetRef command is selected.

n F6-08: Reset Communication Parameters


Determines whether F6-oo communication-related parameters are reset after initialization.
No.
F6-08

Parameter Name
Reset Communication Parameters

Setting Range
0, 1

Default
0

Setting 0: Do not reset F6-oo parameters after initialization using A1-03


Setting 1: Reset F6-oo parameters after initialization using A1-03
Note:

F6-08 is not reset when the drive is initialized, but does determine whether initializing the drive resets the other F6-oo communication
parameters.

u CC-Link Parameters
Parameter Details

Parameters F6-04, F6-10, F6-11, and F6-14 set the drive to operate on a CC-Link network.

n F6-04: bUS Error Detection Time


Sets the delay time for bUS error detection.
No.
F6-04

Parameter Name
bUS Error Detection Time

Setting Range
0.0 to 5.0 s

Default
2.0 s

Setting Range
0 to 64

Default
0

n F6-10: CC-Link Node Address


Sets the node address of a CC-Link option board.
No.
F6-10

Parameter Name
CC-Link Node Address

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

89

1.6 F: Option Settings

n F6-11: CC-Link Communication Speed


Sets the communication speed for a CC-Link option card.
No.
F6-11

Parameter Name
CC-Link Communication Speed

Setting Range
0 to 4

Default
0

Settings:
F6-11
0
1
2

Communication Speed
156 kbps
625 kbps
2.5 Mbps

F6-11
3
4

Communication Speed
5 Mbps
10 Mbps

n F6-14: CC-Link bUS Error Auto Reset


Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
No.
F6-14

Parameter Name
CC-Link bUS Error Auto Reset

Setting Range
0, 1

Default
0

Setting Range
0 to 125

Default
0

Setting Range
0, 1

Default
0

Setting Range
0, 1

Default
0

Setting 0: Disabled, auto reset not possible


Setting 1: Enabled, auto reset possible

u PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set the drive to run on a PROFIBUS-DP network.

n F6-30: PROFIBUS-DP Node Address


Sets the node address of a PROFIBUS-DP option card.
No.
F6-30

Parameter Name
PROFIBUS-DP Node Address

n F6-31: PROFIBUS-DP Clear Mode Selection


Determines the operation when a Clear Mode command is received.
No.
F6-31

Parameter Name
PROFIBUS-DP Clear Mode Selection

Setting 0: Reset

Resets the drive operation (frequency reference, inputs, outputs etc.).


Setting 1: Maintain the previous state

Returns the drive status to the state prior to receiving the command.

n F6-32: PROFIBUS-DP Data Format Selection


Selects the data format used for PROFIBUS-DP communication.
No.
F6-32

Parameter Name
PROFIBUS-DP Data Format Selection

Setting 0: PPO-type data format


Setting 1: Conventional data format

u CANopen Parameters
Parameters F6-35 and F6-36 set the drive to operate on a CANopen network.

n F6-35: CANopen Node ID Selection


Selects the node ID of a CANopen option board.
90

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.6 F: Option Settings


No.
F6-35

Parameter Name
CANopen Node ID Selection

Setting Range
0 to 126

Default
0

Setting Range
0 to 8

Default
6

n F6-36: CANopen Communication Speed


Sets the communication speed for a CANopen option card.
No.
F6-36

Parameter Name
CANopen Communication Speed

Settings:
F6-36
0
1
2
3
4

Communication Speed
Auto detection
10 kbps
20 kbps
50 kbps
125 kbps

F6-36
5
6
7
8

Communication Speed
250 kbps
500 kbps
800 kbps
1 Mbps

u DeviceNet Parameters
Parameters F6-50 through F6-63 set the drive to operate on a DeviceNet network.

n F6-50: DeviceNet MAC Address


Sets the MAC address for a DeviceNet option card.
No.
F6-50

Parameter Name
DeviceNet MAC Address

Setting Range
0 to 64

Default
64

n F6-51: DeviceNet Communication Speed


Sets the communication speed for a DeviceNet option card.
To assign the baud rate for the drive from the upper controller, set F6-51 = 3.
To make the drive detect the network speed, set F6-51 = 4. The drive will automatically adjust itself after detecting the network
speed.
No.
F6-51

Parameter Name
DeviceNet Communication Speed

Setting Range
0 to 4

Default
4

Settings:
F6-51
0
1
2

Communication Speed
125 kbps
250 kbps
500 kbps

F6-51
3
4

Communication Speed
Adjustable from Network
Auto detection

n F6-52: DeviceNet PCA Setting


No.
F6-52

Parameter Name
DeviceNet PCA Setting

Setting Range
0 to 255

Default
21

Setting Range
0 to 255

Default
71

Parameter Details

Defines the format for data the drive receives from the DeviceNet master.

n F6-53: DeviceNet PPA Setting


Defines the format for data sent from the drive to the DeviceNet master.
No.
F6-53

Parameter Name
DeviceNet PPA Setting

n F6-54: DeviceNet Idle Mode Fault Detection


Determines whether the drive triggers an EF0 fault when no data is received from the master (e.g., when the master is idling).
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

91

1.6 F: Option Settings


No.
F6-54

Parameter Name
DeviceNet Idle Mode Fault Detection

Setting Range
0, 1

Default
0

Setting 0: Enabled
Setting 1: Disabled, no fault detection

n F6-55: DeviceNet Baud Rate Monitor


Displays the baud rate currently being used for network communications. F6-55 is used only as a monitor.
No.
F6-55

Parameter Name
DeviceNet Baud Rate Monitor

Setting Range
0 to 2 (read only)

Default
0

Settings:
F6-55
0
1

Communication Speed
125 kbps
250 kbps

F6-55
2

Communication Speed
500 kbps

n F6-56 to F6-61: DeviceNet Scaling Factors


These parameters define scaling factors for drive monitors in the DeviceNet Class ID 2AH - AC/DC Drive Object.
No.
F6-56
F6-57
F6-58
F6-59
F6-60
F6-61

Parameter Name
DeviceNet Speed Scaling
DeviceNet Current Scaling
DeviceNet Torque Scaling
DeviceNet Power Scaling
DeviceNet Voltage Scaling
DeviceNet Time Scaling

Setting Range
-15 to 15
-15 to 15
-15 to 15
-15 to 15
-15 to 15
-15 to 15

Default
0
0
0
0
0
0

Setting

The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value 2Scaling
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 26 = 32000.

n F6-62: DeviceNet Heartbeat Interval


Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the heartbeat function.
No.
F6-62

Parameter Name
DeviceNet Heartbeat Interval

Setting Range
0 to 10

Default
0

Setting Range
0 to 63 (read only)

Default
0

n F6-63: DeviceNet Network MAC ID


Displays the MAC ID assigned to the drive. F6-63 is used only as a monitor.
No.
F6-63

Parameter Name
DeviceNet Network MAC ID

n F6-64 to F6-71: Dynamic Assembly Parameters (Reserved)

92

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions

1.7

H: Terminal Functions

H parameters assign functions to the external terminals.

u H1: Multi-Function Digital Inputs


n H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in Table
1.36.
No.

Setting
Range

Parameter Name

Default

H1-01

Multi-Function Digital Input Terminal S1 Function Selection

1 to 9F

40 (F) <1> : Forward Run Command (2-Wire sequence)

H1-02

Multi-Function Digital Input Terminal S2 Function Selection

1 to 9F

H1-03
H1-04

Multi-Function Digital Input Terminal S3 Function Selection


Multi-Function Digital Input Terminal S4 Function Selection

0 to 9F
0 to 9F

41 (F) <1> : Reverse Run Command (2-Wire sequence)


24: External Fault
14: Fault Reset

H1-05

Multi-Function Digital Input Terminal S5 Function Selection

0 to 9F

3 (0) <1> : Multi-Step Speed Reference 1

H1-06

Multi-Function Digital Input Terminal S6 Function Selection

0 to 9F

4 (3) <1> : Multi-Step Speed Reference 2

H1-07

Multi-Function Digital Input Terminal S7 Function Selection

0 to 9F

H1-08

Multi-Function Digital Input Terminal S8 Function Selection

0 to 9F

6 (4) <1> : Jog Reference Selection


8: External Baseblock Command

<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization.
Table 1.36 Multi-Function Digital Input Terminal Settings
Function
3-Wire Sequence
LOCAL/REMOTE Selection
External Reference 1/2 Selection
Multi-Step Speed Reference 1
Multi-Step Speed Reference 2
Multi-Step Speed Reference 3
Jog reference Selection
Accel/Decel Time Selection 1
Baseblock Command (N.O.)
Baseblock Command (N.C.)
Accel/Decel Ramp Hold
Drive Overheat Alarm (oH2)
Analog Terminal Input Selection
PG Encoder Disable
ASR integral reset
Through Mode
Up Command
Down Command
Forward Jog
Reverse Jog
Fault Reset
Fast Stop (N.O.)
Motor 2 Selection
Fast Stop (N.C.)
Timer Function Input
PID Disable
Accel/Decel Time Selection 2
Program Lockout
Reference Sample Hold

Page
94
94
95
95
95
95
95
95
96
96
96
96
96
96
97
97
97
98
97
98
99
99
99
99

Setting
20 to 2F
30
31
32
34
35
40
41
42
43
44
45
46
47
60
61
62
63
65
66
67
6A
71
72
75
76
77
78

Function
External Fault
PID Integral Reset
PID Integral Hold
Multi-Step Speed Reference 4
PID Soft Starter Cancel
PID Input Level Selection
Forward Run Command (2-Wire sequence)
Reverse Run Command (2-Wire sequence)
Run Command (2-Wire sequence 2)
FWD/REV Command (2-Wire sequence 2)
Offset Frequency 1
Offset Frequency 2
Offset Frequency 3
Node Setup
DC Injection Braking Command
External Speed Search Command 1
External Speed Search Command 2
Field Weakening
KEB Ride-Thru 1 (N.C.)
KEB Ride-Thru 1 (N.O.)
Communications Test Mode
Drive Enabled
Speed/Torque Control Switch
Zero Servo
Up 2 Command
Down 2 Command
ASR Gain Switch
External Torque Reference Polarity Inversion

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Page
99
100
100
100
100
100
100
101

101
101
101
101
101
101
Parameter Details

Setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
10
11
12
13
14
15
16
17
18
19
1A
1B
1E

101
101
102
102
102

102
103
103

93

1.7 H: Terminal Functions


Setting
7E
90 to 97

Function
Forward/Reverse Detection (V/f control with
simple PG)
DriveWorksEZ Digital Input 1 to 8

Page

Setting
9F

103

Function
DriveWorksEZ Disabled

Page
103

103

Setting 0: 3-Wire Sequence

The digital input programmed for 3-Wire control becomes the forward/reverse directional input, S1 becomes the Run command
input, and S2 becomes the Stop command input.
The drive starts the motor when the input S1 set for the Run command closes for longer than 2 ms. The drive stops the operation
when the Stop input S2 releases for 2 ms. When the digital input programmed for a forward/reverse operation is open, the
drive is set for forward operation. When the digital input is closed, the drive is set for reverse operation.
Note:

Input the Run and Stop commands via S1 and S2 when selecting a 3-Wire sequence.
Stop Switch
(N.C.)

Run Switch
(N.O.)

DRIVE
S1
S2
S5
SC

Run Command (Runs when Closed)


Stop Command (Stops when Open)
FWD/REV (Multi-Function Input)
(H1-05 = 0)
Sequence Input Common

Figure 1.52 3-Wire Sequence Wiring Diagram


2 ms min.
Can be either ON or OFF

Run command
Stop command

OFF (stopped)

Forward/reverse
command

OFF (forward)

ON (reverse)

Motor speed
TIME
Stop

Forward

Reverse

Stop

Foward

Figure 1.53 3-Wire Sequence


Note:

1. The Run command must be closed for more than 2 ms.


2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the Run LED will flash to indicate
that protective functions are operating. If required by the application, set b1-17 to 1 to automatically issue the Run command upon drive
power up.

WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before applying
power to the drive. Failure to comply could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence
but set up for 2-Wire sequence (default). Make sure b1-17 is set to 0 (drive does not accept a Run command active at power up). When
initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.

Setting 1: LOCAL/REMOTE Selection

This setting allows the input terminal to determine if the drive will run in LOCAL mode or REMOTE mode.
Status
Closed
Open
Note:

94

Description
LOCAL: Frequency reference and Run command are input from the digital operator.
REMOTE: Frequency reference and Run command are input from the selected external reference. If a digital input set to H1-oo = 2
is active, they will be read from external reference source 2 (b1-15 and b1-16). In all other cases they will be read from external reference
source 1 (b1-01 and b1-02).
1. The LO/RE key on the digital operator is disabled when one of the multi-function input terminals is set to for LOCAL/REMOTE.
2. When the drive is set to LOCAL, the LO/RE LED will light.
3. The default setting of the drive does not allow switching between LOCAL and REMOTE during run. To allow the drive to switch
between LOCAL and REMOTE during run, Refer to b1-07: LOCAL/REMOTE Run Selection on page 24.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Setting 2: External Reference 1/2 Selection

This function switches the Run command and frequency reference source between External reference 1 and 2 if the drive is
in the REMOTE mode.
Status
Open
Closed
Note:

Description
External reference 1 is used (defined by parameters b1-01 and b1-02)
External reference 2 is used (defined by parameters b1-15 and b1-16)
Default drive settings do not allow switching between External reference 1 and 2 during run. Refer to b1-07: LOCAL/REMOTE Run
Selection on page 24 if this feature is required by the application.

Setting 3 to 5: Multi-Step Speed Reference 1 to 3

Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs. Refer to d1: Frequency Reference on page
58 for details.
Setting 6: Jog Reference Selection

The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes. Refer to d1:
Frequency Reference on page 58 for details.
Setting 7: Accel/Decel Time Selection 1

Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04). Refer to C1-01 to C1-08: Accel, Decel
Times 1 to 4 on page 45 for details.
Setting 8, 9: Baseblock Command (N.O., N.C.)

When the drive receives a baseblock command, the output transistors stop switching, the motor coasts to stop, and a bb alarm
flashes on the digital operator to indicate baseblock. When baseblock ends while a Run command is active, the drive performs
Speed Search to restart the motor.
Drive Operation

DIgital Input Function

Input Open
Baseblock (Interrupt output)
Normal operation

Setting 8 (N.C.)
Setting 9 (N.O.)

Input Closed
Normal operation
Baseblock (Interrupt output)

WARNING! Sudden Movement Hazard. When using a mechanical holding brake with the drive in a lifting application, close the brake when
the drive output is cut off by a baseblock command triggered by one of the input terminals. Failure to comply will result in a slipping load
from the motor suddenly coasting when the baseblock command is entered and may cause serious injury or death.
Run command

Baseblock input

Frequency
reference

OFF

ON

ON

Baseblock
release

Begin Speed Search from the


previous frequency reference

Parameter Details

Output frequency
Output off, motor coasts

Figure 1.54 Baseblock Operation During Run

Setting A: Accel/Decel Ramp Hold

When the digital input programmed for the Accel/decel ramp hold function closes, the drive locks (holds) the output frequency.
Acceleration or deceleration resumes when the input is reopened.
If the Accel/decel ramp hold function is enabled (d4-01 = 1), the drive saves the output frequency to memory when the Ramp
Hold input is closed. When the drive is restarted after stop or after power supply interruption, the saved output frequency
becomes the frequency reference (provided that the Accel/decel ramp hold input is still closed). Refer to d4-01: Frequency
Reference Hold Function Selection on page 62 for details.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

95

1.7 H: Terminal Functions


Setting B: Drive Overheat Alarm (oH2)

Triggers an oH2 alarm when the contact closes. Drive operation is not affected because this is an alarm.
Setting C: Analog Terminal Input Selection (Terminal A1, A2, A3)

When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog
terminals.
Setting D: PG Encoder Disable

When closed, the drive disregards PG feedback from the motor when using V/f Control with PG. When the terminal is reopened,
the drive resumes using PG feedback to control motor speed.
Setting E: ASR Integral Reset

Switches between PI control and P control by resetting the integral value. Integral operation is disabled when the terminal is
closed and the drive uses P control. PI control resumes when the terminal opens.
Setting F: Through Mode

Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in
the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/
Modbus communications.
Setting 10, 11: Up/Down Function

The Up/Down function allows the frequency reference to be set by two push buttons when one digital input is programmed
as the Up input (H1-oo= 10) to increase the frequency reference and the other digital input is programmed as the Down input
(H1-oo= 11) to decrease the frequency reference.
The Up/Down function takes priority over the frequency references from the digital operator, the analog inputs, and the pulse
input (b1-01 = 0, 1, 4). When using the Up/Down function, references provided by these sources will be disregarded.
The inputs operate as shown in the table below:
Status
Up (10)
Open
Closed
Open
Closed
Note:

Down (11)
Open
Open
Closed
Closed

Drive Operation
Hold current frequency reference
Increase frequency reference
Decrease frequency reference
Hold current frequency reference

1. An oPE03 alarm occurs when only one of the Up/Down functions is programmed to a digital input.
2. An oPE03 alarm occurs when the Up/Down function is assigned to the terminals and a different digital input is programmed for the
Accel/decel ramp hold function.
3. The Up/Down function can only be used for External reference 1. Consider this when using Up/Down and the external reference switching
command (H1-oo = 2).

Using the Up/Down Function with Frequency Reference Hold (d4-01)


If the frequency reference hold function is disabled (d4-01 = 0), the Up/Down frequency reference will be reset to 0 when
the Run command is cleared or the power is cycled.
When d4-01 = 1, the drive will save the frequency reference set by the Up/Down function. When the Run command or the
power is cycled, the drive will restart with the saved reference value. Close the Up or Down input without an active Run
command to reset the saved value. Refer to d4-01: Frequency Reference Hold Function Selection on page 62.
Using the Up/Down Function with Frequency Reference Limits
Parameter d2-01 determines the upper frequency reference limit.
The value for the lower frequency reference limit depends on the parameter d4-10 setting. This value can be set by an analog
input or parameter d2-02. Refer to d4-10: Up/Down Frequency Reference Limit Selection on page 66 for details. When a
Run command is applied, the lower limits function as follows:
If the lower limit is set by d2-02 only, the drive accelerates to this limit as soon as a Run command is entered.
If the lower limit is determined by an analog input only, the drive accelerates to the limit when both the Run command and
an Up or Down command are active. The drive will not start running if only the Run command is active.
If the lower limit is set by both an analog input and d2-02, and the analog limit is higher than the d2-02 value, the drive
accelerates to the d2-02 value when a Run command is input. When the d2-02 value is reached, the drive accelerates to the
analog limit only if an Up or Down command is set.
Figure 1.55 shows an Up/Down function example with a lower frequency reference limit set by d2-02, and the frequency
reference hold function both enabled and disabled.
96

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Output frequency
upper limit
Accelerates to
lower limit

Same
frequency

d4-01 = 1

Lower limit

d4-01 = 0

ON

FWD run/stop
ON

Up command

Frequency
reference
reset

ON
Down command

ON

ON

Power supply

Figure 1.55 Up/Down Command Operation

Setting 12, 13: Forward Jog, Reverse Jog

Digital inputs programmed as Forward Jog (H1-oo = 12) and Reverse Jog (H1-oo = 13) will be Jog inputs that do not
require a Run command. Closing the terminal set for Forward Jog input will cause the drive to ramp to the Jog frequency
reference (d1-17) in the forward direction. The Reverse Jog will cause the same action in the reverse direction. The Forward
Jog and Reverse Jog command can be set independently.
Note:

The Forward Jog and Reverse Jog commands override all other frequency references. However, if the drive is set to prohibit reverse rotation
(b1-04 = 1), activating Reverse Jog will have no effect. Inputting both the Forward Jog and Reverse Jog are simultaneously for 500 ms or
longer will trigger an alarm will and the drive will ramp to stop.
d1-17
Output
Frequency
d1-17

FJOG
RJOG

ON
ON

Figure 1.56 FJOG/RJOG Operation

Setting 14: Fault Reset

When the drive detects a fault condition, the fault output contact closes, the drive output shuts off, and the motor coasts to
stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). After removing the Run
command, clear the fault either by pressing the RESET key on the digital operator or closing a digital input configured as a
Fault Reset (H1-oo = 14).
Note:

Remove the Run command prior to resetting a fault. Fault Reset commands are ignored while the Run command is present.

The Fast Stop function operates similar to an emergency stop input to the drive. If a Fast Stop command is input while the
drive is running, the drive decelerates to a stop in the deceleration time set to C1-09 (Refer to C1-09: Fast Stop Time on page
46). The drive can only be restarted after bringing the drive to a complete stop, turning off the Fast Stop input, and switching
off the Run command.
To trigger the Fast Stop function with an N.O. switch, set H1-oo = 15.
To trigger the Fast Stop function with an N.C. switch, set H1-oo = 17.
Figure 1.57 shows an operation example of Fast Stop.

Parameter Details

Setting 15, 17: Fast Stop (N.O., N.C.)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

97

1.7 H: Terminal Functions


Run/Stop
ON

Fast-Stop
H1= 17

ON

ON

ON

Decelerates at C1-09
Output Frequency

TIME

Figure 1.57 Fast Stop Sequence


NOTICE: Rapid deceleration can trigger an overvoltage fault. When faulted, the drive output shuts off, and the motor coasts. To avoid this
uncontrolled motor state and to ensure that the motor stops quickly and safely, set an appropriate Fast Stop time to C1-09.

Setting 16: Motor 2 Selection

The drive has the capability to control two induction motors independently. A second motor may be selected using a multifunction digital input as shown in Figure 1.58.
Note:

The motor 2 selection function cannot be used with PM motors.


Drive

Motor 1

Motor 2

Motor switch input

Figure 1.58 Motor Selection

When switching between motor 1 and motor 2, the parameters used to control those motors also change. Below, Table 1.37
lists the parameters that correspond to each motor:
Table 1.37 Parameters for Switching Between Two Motors

No.
C1-oo: Acceleration/Deceleration
Time
C3-oo : Motor Slip Compensation
C4-oo: Motor Torque
Compensation
C5-oo: Speed Control (ASR)
E1-oo, E3-oo: V/f Pattern
E2-oo, E4-oo: Motor Parameters
F1-oo (PG Constant)
Note:

1.
2.
3.
4.

Setting 16 Open (Motor 1)

Setting 16 Closed (Motor 2)

C1-01 to C1-04

C1-05 to C1-08

C3-01 to C3-04, C3-15

C3-21 to C3-25

C4-01

C4-07

C5-01 to C5-08, C5-12, C5-15

C5-21 to C5-28, C5-32, C5-35

E1-oo, E2-oo

E3-oo to E4-oo

F1-01 to F1-21

F1-02 to F1-04, F1-08 to F1-11, F1-14,


F1-31 to F1-37

When using 2 motors, the motor overload protection selection (oL1) set to L1-01 applies to both motor 1 and motor 2.
Attempting to switch between motor 1 and motor 2 during run will trigger the rUn alarm.
There is a 500 ms delay when switching between motors equipped with a PG encoder for feedback.
The motor 2 selection function cannot be used with PM motors.

If a digital output is programmed for Motor 2 selection (H1-01, H1-02, or H1-03 = 1C), the motor will be selected when
the output is closed.
Setting 18: Timer Function Input

This setting configures a digital input terminal as the input for the timer function. Use this setting combination with the timer
function output (H2-oo = 12). Refer to b4: Delay Timers on page 32 for details.

98

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Setting 19: PID Disable

Close a digital input to indefinitely disable the PID function. When the input is released, the drive resumes PID operation.
Refer to PID Block Diagram on page 35.
Setting 1A: Accel/Decel Time Selection 2

Selects accel/decel times 1 to 4 in combination with the Accel/decel time selection 1 command. Refer to C1-01 to C1-08:
Accel, Decel Times 1 to 4 on page 45 for details.
Setting 1B: Program Lockout

Parameter values cannot be changed when an input is programmed for Program Lockout and the input is open. It is still possible,
however, to view and monitor parameter settings.
Setting 1E: Reference Sample Hold

This function allows the user to sample an analog frequency reference signal being input to terminal A1, A2, or A3 and hold
the frequency reference at the sampled level. When the Analog Frequency Reference Sample/Hold function is held for at least
100 ms, the drive reads the analog input and changes the frequency reference to the newly sampled speed as illustrated in
Figure 1.59.
When the power is shut off and the sampled analog frequency reference is cleared, the frequency reference is reset to 0.
Frequency
reference
g
alo

na

sig

An

Time
OFF

Referenece
Sample Hold Input
100 ms

ON
100 ms

Figure 1.59 Analog Frequency Reference Sample/Hold

An oPE03 error will occur when one of the following functions is used simultaneously with the Analog frequency reference
sample/hold command:
Hold accel/decel stop (setting: A)
Up command, Down command (setting: 10, 11)
Offset frequency (setting: 44 to 46)
Up or Down functions (setting: 75, 76)
The External fault command stops the drive when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to a value between 20 and 2F. The digital
operator will display EFo where o is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal S3, EF3 will be displayed.
Select the value to be set in H1-oo from a combination of any of the following three conditions:
Signal input level from peripheral devices (N.O., N.C.)
External fault detection method
Operation after external fault detection
The following table shows the relationship between the conditions and the value set to H1-oo:
Terminal statuses, detection conditions, and stopping methods marked with an O are applicable to the corresponding settings.
Terminal Status <1>
Setting
20
21

N.O.

Detection Conditions <2>

N.C.

Always
Detected

O
O

Detected
during Run
only

Stopping Method
Ramp to Stop
(fault)

Coast to Stop
(fault)

Fast Stop
(fault)

Alarm Only
(continue
running)

O
O

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

99

Parameter Details

Setting 20 to 2F: External Fault

1.7 H: Terminal Functions


Terminal Status <1>
Setting
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F

N.O.

N.C.

Detection Conditions <2>


Detected
Always
during Run
Detected
only

O
O

O
O

Stopping Method
Ramp to Stop
(fault)

Coast to Stop
(fault)

O
O
O
O

O
O

O
O
O

O
O
O

O
O

O
O

Alarm Only
(continue
running)

O
O

O
O

Fast Stop
(fault)

O
O

O
O

O
O

O
O

<1> Determine the terminal status for each fault, i.e., whether the terminal is normally open or normally closed.
<2> Determine whether detection for each fault should be enabled only during run or always detected.

Setting 30: PID Integral Reset

Configuring one of the digital inputs for PID integral reset (H1-oo = 30) resets the value of the integral component in PID
control to 0 when the terminal is closed. Refer to PID Block Diagram on page 35 for more details.
Setting 31: PID Integral Hold

Configuring a digital input for Integral Hold (H1-0o = 31) locks the value of the integral component of the PID control as
long as the input is active. The PID controller resumes integral operation from the hold value as soon as the integral hold input
is released. Refer to PID Block Diagram on page 35 for more information on this function.
Setting 32: Multi-Step Speed Reference 4

Selects the multi-step speeds d1-09 to d1-16 in combination with the input terminal set for Multi-Step Speed 1, 2 and 3. Refer
to d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Frequency Reference on page 58.
Setting 34: PID Soft Starter Cancel

A digital input configured as a PID soft starter cancel input (H1-0o = 34) enables or disables the PID soft starter and cancels
the PID accel/decel time (b5-17). Refer to PID Block Diagram on page 35.
Setting 35: PID Input Level Selection

Allows an input terminal to switch the sign of the PID input. Refer to PID Block Diagram on page 35 for details.
Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence

Configures the drive for a 2-Wire sequence.


When an input terminal set to 40 closes, the drive operates in the forward direction. When an input set for 41 closes, the drive
operates in reverse. Closing both inputs simultaneously will result in an external fault.
Note:

1. This function cannot be used simultaneously with settings 42 and 43.


2. The same functions are assigned to terminals S1 and S2 when the drive is initialized for 2-Wire sequence.
Drive
Forward Run

S1

Reverse Run
S2
SC Digital Input Common

Figure 1.60 Example Wiring Diagram for 2-Wire Sequence


100

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2

Sets the drive for 2-Wire sequence 2.


When an input terminal programmed for 42 closes, the drive will operate in the selected direction. The drive will stop when
the input opens.
The input programmed for 43 selects the direction. If the input is open, forward direction is selected. If the input is closed,
reverse direction is selected.
Note:

This function cannot be used simultaneously with settings 40 and 41.

Setting 44, 45, 46: Offset Frequency 1, 2, 3

These inputs add offset frequencies d7-01, d7-02, and d7-03 to the frequency reference. Refer to d7-01 to d7-03: Offset
Frequency 1 to 3 on page 72 for details.
Setting 47: Node Setup

If the S1-S3 option card is connected, closing this terminal sets a node address for operation on a CANopen network.
Setting 60: DC Injection Braking Command

DC Injection Braking is activated when a DC Injection Braking command is input while the drive is stopped. DC Injection
Braking is released when a Run command or a Jog command is input. Refer to b2: DC Injection Braking and Short Circuit
Braking on page 25 for details on setting up the DC Injection Braking function.
The diagram below illustrates DC Injection Braking:
DC Injection braking
command

FWD Run command

OFF

OFF

DC Injection
braking
Output frequency

ON

OFF

OFF

ON

DC Injection Braking
Start Frequency
(b2-01)

DC Injection
braking

Figure 1.61 DC Injection Braking Input Timing Diagram

Setting 61, 62: External Speed Search Command 1, 2

These input functions enable Speed Search even if parameter b3-01 = 0 (no Speed Search at start). Refer to Speed Search
Activation on page 29 for details on how to use the input signals. Refer to b3: Speed Search on page 27 for more about Speed
Search.
Note:

Simultaneously assigning Speed Search 1 and Speed Search 2 to the input terminals will trigger an oPE03 error.

Setting 63: Field Weakening

Enabled in V/f Control. When this input is closed, Field Weakening is performed. For details, see d6: Field Weakening and
Field Forcing.
Setting 65, 66: KEB Ride-Thru 1 (N.C.), 2 (N.O.)

Enables the KEB Ride-Thru. Refer to KEB Ride-Thru Function on page 132 for more information on this function.

Setting 65 (N.C.)
Setting 66 (N.O.)
Note:

Drive Operation
Input Open
KEB Ride-Thru Deceleration
Normal operation

Parameter Details

DIgital Input Function

Input Closed
Normal operation
KEB Ride-Thru Deceleration

Simultaneously assigning KEB Ride-Thru 1 and KEB Ride-Thru 2 to the input terminals will trigger an oPE03 error.

Setting 67: Communication Test Mode

The drive has a built-in function to self-diagnose serial communications operation. The test involves wiring the send and
receive terminals of the RS-485/422 port together. The drive transmits data and then confirms that the communications are
received normally.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

101

1.7 H: Terminal Functions


Setting 6A: Drive Enable

A digital input configured as a Drive enable (H1-oo = 6A) will prevent the drive from executing a Run command until
the input is closed. When the input is open, the digital operator will display dnE to indicate that the drive is disabled.
If a Run command is enabled before the terminal set for Drive enable closes, then the drive will not run until the Run
command is cycled (i.e., a new Run command is required). If the input is opened while the drive is running, the drive will stop
according to the stop method set to b1-03 (Refer to b1-03: Stopping Method Selection on page 20).
Setting 71: Speed/Torque Control Switch

Switches the drive between Torque Control and Speed Control. Torque Control is enabled when the terminal is closed, and
Speed Control is enabled when the terminal is open. Set parameter d5-01 to 0 when using this function. Refer to d5: Torque
Control on page 66 and Switching Between Torque and Speed Control on page 69.
Setting 72: Zero Servo

Activates the Zero Servo function to lock the rotor at a certain position. Refer to b9: Zero Servo on page 43 for details.
Setting 75, 76: Up 2/Down 2 Function

The Up/Down 2 function adds a bias to the frequency reference. The input programmed for 75 will increase the bias and the
input programmed for 76 will decrease the bias. Table 1.38 explains how the Up/Down 2 function works depending on the
frequency reference source and parameters d4-01, d5-03, and d4-05. Refer to d4: Frequency Reference Hold and Up/Down
2 Function on page 62 for detailed explanations of these and other Up/Down 2 related parameters.
Note:

1. The Up/Down 2 functions must be set as a pair.


2. When using the Up/Down 2 function, set appropriate bias limit values to parameters d4-08 and d4-09.
Table 1.38 Up/Down 2 Operations

Condition

Freq. Ref.
Source

d4-03

d4-05

2
Multi-Step Speed
Reference

102

Accelerates (increases the bias) while the Up 2


terminal is closed.
Decelerates (decreases the bias) while Down 2 is
closed.
Holds output frequency (holds the bias) when no
Up 2 or Down 2 input or both active.
Resets the bias when the reference changes.
Operates with the frequency reference in all other
situations.

--

Multi-Step Speed
Reference

Value
other
than 0

--

Operation

d4-01

Other (analog
comm., etc.)

Accelerates (increases the bias) while the Up 2


terminal is closed.
Decelerates (decreases the bias) while Down 2 is
closed.
Otherwise operates at the frequency reference.
When the Up 2 is enabled, the drive accelerates to
the frequency reference plus d4-03 (bias is
increased for d4-03).
When Down 2 is enabled, the drive decelerates to
the frequency reference minus d4-03 (bias is
decreased for d4-03).
Holds output frequency (holds the bias) when
neither Up/Down 2 inputs are active or both inputs
are active.
Resets the bias when the reference changes.
Operates with the frequency reference in all other
situations.
Accelerates (increases the bias) while the Up 2
terminal is closed.
Decelerates (decreases the bias) while Down 2 is
closed.
Holds output frequency (holds the bias) when
neither Up/Down 2 inputs are active or both inputs
are active.
If the frequency reference changes for more than
the time set to d4-07 during accel/decel, bias value
is held until the output frequency meets the
reference (speed agree).

Frequency Saved
Not saved

If the bias and frequency reference


are constant for 5 s, the bias is
added to the active frequency
reference and reset afterwards.

Not saved

Not saved

If the bias and frequency reference


are constant for 5 s, the bias is
added to the active frequency
reference and reset afterwards.

Not saved

If the bias is constant for 5 s, it is


saved to parameter d4-06. The
frequency reference cannot be
overwritten, so only the bias is
saved.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Condition

Freq. Ref.
Source

d4-03

d4-05

--

Other (analog
comm, etc.)
Value
other
than 0

10

d4-01

--

Operation

Frequency Saved

Accelerates (increases the bias) while the Up 2


terminal is closed.
Decelerates (decreases the bias) while Down 2 is
closed.
Otherwise operates at the frequency reference
When Up 2 is enabled, drive accelerates to the
frequency reference plus d4-03 (increases the bias
for d4-03).
When Down 2 is enabled, drive decelerates to the
frequency reference minus d4-03 (decreases the
bias for d4-03).
If the frequency reference changes for more than
d4-07 during accel/decel, bias value is held until the
output frequency meets the reference (speed agree).

Not saved

Not saved
If the bias is constant for 5 s, it is
saved to parameter d4-06. The
frequency reference cannot be
overwritten, so only the bias is
saved.

Setting 77: ASR Gain Switch

Switches the ASR gain between the values set to C5-01 and C5-03. The gain set to C5-03 is enabled when the terminal is
closed, and C5-01 is enabled when the terminal reopens. Refer to C5-01, C5-03/C5-02, C5-04: ASR Proportional Gain 1, 2/
ASR Integral Time 1, 2 on page 53 for a more detailed description.
Setting 78: External Torque Reference Polarity Inversion

Reverses the direction of the torque reference when the terminal closes. Refer to d5: Torque Control on page 66 and Setting
the Torque Reference, Speed Limit, and Torque Compensation Values on page 67 for details.
Setting 7E: Forward/Reverse Detection (for V/f Control with Simple PG Feedback)

Determines the motor rotation direction for V/f Control with Simple PG feedback (A1-02 = 0 and H6-01 = 3). If the input is
open, the speed feedback signal is considered to be forward. If the input is closed, it is considered to be reverse. Refer to H6:
Pulse Train Input/Output on page 122.
Setting 90 to 97: DriveWorksEZ Digital Input 1 to 8

These settings are for digital input functions used in DriveWorksEZ. Changing these settings is not typically required.
Setting 9F: DriveWorksEZ Disable

This function is used to enable or disable a DriveWorksEZ program in the drive. An input programmed for this function is
effective only if A1-07 = 2.
Status
Open
Closed

Description
DriveWorksEZ enabled
DriveWorksEZ disabled

u H2: Multi-Function Digital Outputs


n H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection
No.
H2-01
H2-02
H2-03

Parameter Name
Terminal M1-M2 Function Selection (relay)
Terminal M3-M4 Function Selection (relay)
Terminal M5-M6 Function Selection (relay)

Setting Range
0 to 192
0 to 192
0 to 192

Default
0: During run
1: Zero Speed
2: Speed agree 1

Table 1.39 Multi-Function Digital Output Terminal Settings


Setting
0
1
2
3
4
5

Function
During Run
Zero Speed
Speed Agree 1
User-Set Speed Agree 1
Frequency Detection 1
Frequency Detection 2

Page
104
104
105
105
106
106

Setting
6
7
8
9
A
B

Function
Drive Ready
DC Bus Undervoltage
During Baseblock (N.O.)
Frequency Reference Source
Run Command Source
Torque Detection 1 (N.O.)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Page
106
107
107
107
107
107

103

Parameter Details

The drive has three multi-function output terminals. Table 1.39 lists the functions available for theses terminals using H2-01,
H2-02, and H2-03.

1.7 H: Terminal Functions


Setting
C
E
F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
22

Function
Frequency Reference Loss
Fault
Through Mode
Minor Fault
Fault Reset Command Active
Timer Output
Speed Agree 2
User-Set Speed Agree 2
Frequency Detection 3
Frequency Detection 4
Torque Detection 1 (N.C.)
Torque Detection 2 (N.O.)
Torque Detection 2 (N.C.)
During Reverse

Page
107
107
107
108
108
108
108
108
109
109
107
107
110

During Baseblock (N.C.)


Motor 2 Selection
During regeneration
Restart Enabled
Motor Overload Alarm (oL1)
Drive Overheat Pre-Alarm (oH)
Mechanical Weakening Detection

110
110
110
110
111
111
111

Setting
2F
30
31
32
33
37
38
39
3C
3D
3E
3F
4A
4C

Function
Maintenance Period
During Torque Limit
During Speed Limit
During Speed Limit in Torque Control
Zero Servo Complete
During Frequency Output
Drive Enabled
Watt Hour Pulse Output
LOCAL/REMOTE Status
During Speed Search
PID Feedback Low
PID Feedback High
During KEB Operation
During Fast Stop

Page
111
111
111
111
111
111
112
112
112
112
112
112
112
112

4D
60
90
91
92
100 to 192

oH Pre-Alarm Time Limit


Internal Cooling Fan Alarm
DriveWorksEZ Digital Output 1
DriveWorksEZ Digital Output 2
DriveWorksEZ Digital Output 3
Functions 0 to 92 with Inverse Output

112
112
112
112

Setting 0: During Run

Output closes when the drive is outputting a voltage.


Status
Open
Closed

Description
Drive is stopped.
A Run command is input or the drive is in deceleration or DC injection.
Run command

OFF

Baseblock
command

OFF

ON
ON

Output
frequency

During Run

OFF

ON

Figure 1.62 During Run Time Chart

Setting 1: Zero Speed

Terminal closes when the output frequency or motor speed (CLV, CLV/PM) falls below the minimum output frequency set
to E1-09 or b2-01.
Status
Open
Closed
Note:

104

Description
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
In CLV and CLV/PM control modes, the zero speed level is defined by b2-01. In all other control modes, the zero speed level is the minimum
output frequency set to E1-09.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Output frequency
or
motor speed

Zero Speed

E1-09 (Max. Output Frequency) or


b2-01 (Zero Speed Level)

OFF

ON

Figure 1.63 Zero-Speed Time Chart

Setting 2: Speed Agree 1 (fref/fout Agree 1)

Closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status
Open
Closed
Note:

Description
Output frequency or motor speed does not match the frequency reference while the drive is running.
Output frequency or motor speed is within the range of frequency reference L4-02.
Detection works in forward and reverse.
Frequency
reference
Output Frequency
or Motor Speed

L4-02

L4-02
Speed agree 1

OFF

ON

Figure 1.64 Speed Agree 1 Time Chart

Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 141 for more details.
Setting 3: User-Set Speed Agree 1 (fref/fset Agree 1)

Closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the speed
agree width (L4-02) of the programmed speed agree level (L4-01).
Status
Open
Closed
Note:

Description
Output frequency or motor speed and frequency reference are not both within the range of L4-01 L4-02.
Output frequency or motor speed and the frequency reference are both within the range of L4-01 L4-02.
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Frequency reference + L4-02
Frequency reference

L4-01

L4-01 L4-02

During
Forward

0 Hz

Parameter Details

L4-01 + L4-02
Frequency reference L4-02
Output frequency

During Reverse
L4-01 + L4-02

Output frequency

L4-01
Frequency reference + L4-02
L4-01 L4-02
Frequency reference
User Set
Speed Agree 1

Frequency reference L4-02


OFF

ON

OFF

ON

ON

OFF

ON

Figure 1.65 User Set Speed Agree 1 Time Chart

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

105

1.7 H: Terminal Functions


Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 141 for more instructions.
Setting 4: Frequency Detection 1

The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-01 plus
the detection width set in L4-02. The terminal remains open until the output frequency or motor speed fall below the level set
in L4-01.
Status
Open
Closed
Note:

Description
Output frequency or motor speed exceeded L4-01 + L4-02.
Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Output Frequency
or Motor Speed

L4-02
L4-01

L4-01
L4-02
Frequency
detection 1

ON

OFF

Figure 1.66 Frequency Detection 1 Time Chart

Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 141 for more details.
Setting 5: Frequency Detection 2

The output closes when the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-01. The
terminal remains closed until the output frequency or motor speed fall below L4-01 minus the setting of L4-02.
Status
Open
Closed
Note:

Description
Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Output frequency or motor speed exceeded L4-01.
Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
Output Frequency
or Motor Speed

L4-02
L4-01

L4-01
L4-02
Frequency
Detection 2

OFF

ON

Figure 1.67 Frequency Detection 2 Time Chart

Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 141 for more details.
Setting 6: Drive Ready

The output closes when the drive is ready to operate the motor. The terminal will not close under the conditions listed below,
and any Run commands will be disregarded.
When the power is shut off
During a fault
When the internal power supply of the drive has malfunctioned
When a parameter setting error makes it impossible to run
106

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Although stopped, an overvoltage or undervoltage situation occurs
While editing a parameter in the Programming Mode (when b1-08 = 0)
Setting 7: DC Bus Undervoltage

The output closes when the DC bus voltage or control circuit power supply drops below the trip level set in L2-05. A fault in
the DC bus circuit will also cause the terminal set for DC bus undervoltage to close.
Status
Open
Closed

Description
DC bus voltage is above the level set to L2-05.
DC bus voltage has fallen below the trip level set to L2-05.

Setting 8: During Baseblock (N.O.)

The output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status
Open
Closed

Description
Drive is not in a baseblock state.
Baseblock is being executed.

Setting 9: Frequency Reference Source

Displays the currently selected frequency reference source.


Status
Open
Closed

Description
Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15).
Frequency reference is being sourced from the digital operator.

Setting A: Run Command Source

Displays the currently selected Run command source.


Status
Open
Closed

Description
Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Run command is being sourced from the digital operator.

Setting B, 17, 18, 19: Torque Detection 1 (N.O., N.C.), Torque Detection 2 (N.O., N.C.)

Setting

Status

Closed

17

Open

18

Closed

19

Open

Description
Torque detection 1 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 1 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
Torque detection 2 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.
Torque detection 2 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.

Setting C: Frequency Reference Loss

An output set for this function closes when frequency reference loss is detected. Refer to L4-05: Frequency Reference Loss
Detection Selection on page 142 for details.

Setting E: Fault

The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Setting F: Through Mode

Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function in
the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or MEMOBUS/
Modbus communications.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

These digital output functions signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below. Refer to L6: Torque Detection on page
144 for details.

107

1.7 H: Terminal Functions


Setting 10: Minor Fault

The output closes when a minor fault condition is present.


Setting 11: Fault Reset Command Active

The output closes when there is an attempt to reset a fault situation from the control circuit terminals, via serial communications,
or using a communications option card.
Setting 12: Timer Output

This setting configures a digital output terminal as the output for the timer function. Refer to b4: Delay Timers on page 32
for details.
Setting 13: Speed Agree 2 (fref /fout Agree 2)

The output closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04)
of the current frequency reference, regardless of the direction.
Status
Open
Closed
Note:

Description
Output frequency or motor speed does not match the frequency reference while the drive is running.
Output frequency or motor speed is within the range of frequency reference L4-04.
Detection works in forward and reverse.
Frequency
reference
L4-04

Output Frequency
or Motor Speed

L4-04
Speed Agree 2

OFF

ON

Figure 1.68 Speed Agree 2 Time Chart

Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 142 for more details.
Setting 14: User-Set Speed Agree 2 (fref /fset Agree 2)

The output closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within
the speed agree width (L4-04) of the programmed speed agree level (L4-03).
Status
Open
Closed
Note:

108

Description
Output frequency or motor speed and frequency reference are both outside the range of L4-03 L4-04.
Output frequency or motor speed and the frequency reference are both within the range of L4-03 L4-04.
The detection level L4-03 is a signed value; detection works in the specified direction only.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Frequency reference + L4-04
Frequency reference
L4-03 + L4-04
Frequency reference L4-04
L4-03
L4-03 L4-04

During
Forward

Output frequency

0 Hz
Output frequency

Frequency
reference
User Set
Speed Agree 2

OFF

ON

OFF

ON

Figure 1.69 User-Set Speed Agree 2 Example with a Positive L3-04 Value

Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 142 for more details.
Setting 15: Frequency Detection 3

The output opens when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set
in L4-03. The detection level L4-03 is a signed value; detection works in the specified direction only.
Status
Open
Closed

Description
Output frequency or motor speed exceeded L4-03 plus L4-04.
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
Output Frequency
or Motor Speed

L4-04
L4-03

Frequency
detection 3

ON

OFF

Figure 1.70 Frequency Detection 3 Example with a Positive L3-04 Value

Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 142 for more details.
Setting 16: Frequency Detection 4

Status
Open
Closed
Note:

Parameter Details

The output closes when the output frequency or motor speed (CLV, CLV/PM) is above the detection level set in L4-03. The
terminal remains closed until the output frequency or motor speed falls below L4-03 minus the setting of L4-04.
Description
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03.
Output frequency or motor speed exceeded L4-03.
The detection level L4-03 is a signed value; detection works in the specified direction only.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

109

1.7 H: Terminal Functions


Output Frequency
or Motor Speed

Frequency
Detection 4

OFF

L4-04
L4-03

ON

Figure 1.71 Frequency Detection 4 Example with Positive L3-04 Value

Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 142 for more details.
Setting 1A: During Reverse

A digital output set for During reverse closes when the drive is running the motor in the reverse direction.
Status
Open
Closed

Description
Motor is being driven in the forward direction or stopped.
Motor is being driven in reverse.
Output frequency

FWD Run command

REV Run command

During Reverse

OFF

ON
time

Figure 1.72 Reverse Direction Output Example Time Chart

Setting 1B: During Baseblock (N.C.)

The output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not switch
and no main circuit voltage is output.
Status
Open
Closed

Description
Baseblock is being executed.
Drive is not in a baseblock state.

Setting 1C: Motor 2 Selection

Indicates which motor is selected when another output terminal is set to switch drive operation between two motors (H1oo = 16). Refer to Setting 16: Motor 2 Selection on page 98 for details on switching motors.
Status
Open
Closed

Description
Motor 1 is selected.
Motor 2 is selected.

Setting 1D: During Regeneration

Terminal closes when the motor is driven in the regenerative mode.


Setting 1E: Restart Enabled

An output set for Restart enabled closes when the drive attempts to restart after a fault has occurred.

110

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


The fault restart function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has attempted to restart. If the drive cannot successfully restart within the number of attempts permitted
by L5-01, a fault will be triggered and the terminal set to 1E will open. Refer to L5: Fault Restart on page 143 for details on
automatic restart.
Setting 1F: Motor Overload Alarm (oL1)

The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection level.
Refer to L1-01: Motor Overload Protection Selection on page 125.
Setting 20: Drive Overheat Pre-Alarm (oH)

The output closes when the drive heatsink temperature reaches the level specified by parameter L8-02. Refer to L8-02:
Overheat Alarm Level on page 148 for details on drive overheat detection.
Setting 22: Mechanical Weakening Detection

The output closes when a mechanical weakening situation is detected. Refer to Mechanical Weakening Detection on page
145 for details.
Setting 2F: Maintenance Period

The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined
by the estimated performance life span of those components. Components performance life is displayed as a percentage on
the digital operator screen.
Setting 30: During Torque Limit
Note:

PM motor control modes are not available in A1000 HHP drive models.

The output closes when the motor is operating at the torque limit specified by the L7-oo parameters or an analog input. This
setting can only be used in OLV, CLV, AOLV/PM and CLV/PM control modes. Refer to L7-01 to L7-04: Torque Limits on
page 147 for details.
Setting 31: During Speed Limit
Note:

PM motor control modes are not available in A1000 HHP drive models.

The output closes when the speed limit has been reached. This function can be used in CLV and CLV/PM control modes.
Status
Open
Closed

Description
The conditions described below are not present.
1. The frequency reference has reached the upper limit set in d2-01.
2. The frequency reference has fallen to the lower limit set in d2-02 or d2-03.
3. Parameter b1-05 is set to 1, 2, or 3, and the frequency reference has fallen below the minimum output frequency
(E1-09).

Setting 32: During Speed Limit in Torque Control

The motor torque and load torque are not in balance, causing the motor to accelerate. The output closes when the motor reaches
the speed limit. Refer to d5: Torque Control on page 66 and Indicating Operation at the Speed Limit on page 69 for details.
Setting 33: Zero Servo Complete

The output closes when Zero Servo is enabled and the load is locked into position within the allowable deviation (b9-02).
Refer to b9: Zero Servo on page 43 for information on Zero Servo operation.
Setting 37: During Frequency Output
Status
Open
Closed

Parameter Details

The output closes when the drive is outputting a frequency.


Description
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Drive is outputting frequency.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

111

1.7 H: Terminal Functions


run command
baseblock
command

OFF

ON

OFF

ON

output
frequency

during run

OFF

during frequency
output

OFF

ON
ON

Figure 1.73 During Frequency Output Time Chart

Setting 38: Drive Enable

Reflects the status of a digital input configured as a Drive enable input (H1-oo = 6A). If that digital input closes, then the
digital output set for Drive enable will also close.
Setting 39: Watt Hour Pulse Output

Outputs a pulse to indicate the watt hours. Refer to H2-06: Watt Hour Output Unit Selection on page 113 for details.
Setting 3C: LOCAL/REMOTE Status

The output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status
Open
Closed

Description
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference
and Run command source.
LOCAL: The digital operator is used as frequency reference and Run command source.

Setting 3D: During Speed Search

The output terminal closes while Speed Search is being performed. Refer to b3: Speed Search on page 27 for details.
Setting 3E: PID Feedback Low

The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the
level set to b5-13 for longer than the time set to b5-14. Refer to PID Feedback Loss Detection on page 37 for details.
Setting 3F: PID Feedback High

The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the
level set to b5-36 for longer than the time set to b5-37. Refer to PID Feedback Loss Detection on page 37 for details.
Setting 4A: During KEB Operation

The output terminal closes while KEB is being performed. Refer to KEB Ride-Thru Function on page 132 for a KEB function
description.
Setting 4C: During Fast Stop

The output terminal closes when a Fast Stop is being executed. Refer to Setting 15, 17: Fast Stop (N.O., N.C.) on page 97.
Setting 4D: oH Pre-Alarm Time Limit

The output terminal closes when the drive is reducing the speed due to a drive overheat alarm (L8-03 = 4) and the overheat
alarm has not disappeared after 10 frequency reduction operation cycles. Refer to L8-03: Overheat Pre-Alarm Operation
Selection on page 148 for a more detailed description.
Setting 60: Internal Cooling Fan Alarm

The output closes when the drive internal cooling fan has failed.
Setting 90 to 92: DriveWorksEZ Digital Output 1 to 3

These settings are for output functions used in DriveWorksEZ. Normally there is no need to change these settings.
Setting 100 to 192: Functions 0 to 92 with Inverse Output

These settings have the same function as settings 0 to 92 but with inverse output. Set as 1oo, where the 1 indicates inverse
output and the last two digits specify the setting number of the function.
112

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


Examples:
For inverse output of 8: During baseblock, set 108.
For inverse output of 4A: During KEB set 14A.

n H2-06: Watt Hour Output Unit Selection


When one of the multi-function terminals is set to output the number of watt hours (H2-01, H2-02, or H2-03 = 39), parameter
H2-06 determines the units for the output signal.
This output function provides a watt hour meter or a PLC input by a 200 ms pulse signal. H2-06 determines the frequency that
pulses are issued to keep track of the kWh for the drive.
No.

Parameter Name

H2-06

Watt Hour Output Unit Selection

Note:

Setting Range
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units

Default
0

1. A negative power output (i.e., regeneration) does not subtract from the total watt hours.
2. The drive keeps track of the watt hours as long as the control circuit has power. The value is reset when the power supply is shut off.
H2-06
(Pulse Output Unit)

Integral Power (every 100 ms)


H2-01 to 03
(Multi-function Output)

OFF

ON

OFF

0.2 s

Figure 1.74 Watt Hour Output Example

u H3: Multi-Function Analog Inputs


The drive is equipped with three multi-function analog input terminals: A1, A2, and A3. Refer to Multi-Function Analog
Input Terminal Settings on page 116 for a listing of the functions that can be set to these terminals.

n H3-01: Terminal A1 Signal Level Selection


Selects the input signal level for analog input A1.
No.
H3-01

Name
Terminal A1 Signal Level Selection

Setting Range
0 to 1

Default
0

Setting 0: 0 to 10 Vdc

Setting 1: -10 to 10 Vdc

The input level is -10 to 10 Vdc. If the resulting voltage is negative after being adjusted by gain and bias settings, then the
motor will rotate in reverse.

n H3-02: Terminal A1 Function Selection


Selects the input signal level for analog input A3. Refer to Multi-Function Analog Input Terminal Settings on page 116 for
instructions on adjusting the signal level.
No.
H3-02

Name
Terminal A1 Function Selection

Setting Range
0 to 31

Default
0

n H3-03, H3-04: Terminal A1 Gain and Bias Settings


Parameter H3-03 sets the level of the selected input value that is equal to 10 Vdc input at terminal A1 (gain).
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

113

Parameter Details

The input level is 0 to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal due to gain and bias
settings will be read as 0%.

1.7 H: Terminal Functions


Parameter H3-04 sets the level of the selected input value that is equal to 0 V input at terminal A1 (bias).
Use both parameters to adjust the characteristics of the analog input signal to terminal A1.
No.
H3-03
H3-04

Name
Terminal A1 Gain Setting
Terminal A1 Bias Setting

Setting Range
-999.9 to 999.9%
-999.9 to 999.9%

Default
100.0%
0.0%

Setting Examples

Gain H3-03 = 200%, bias H3-04 = 0, terminal A1 as frequency reference input (H3-02 = 0):
A 10 Vdc input is equivalent to a 200% frequency reference and 5 Vdc is equivalent to a 100% frequency reference. Since
the drive output is limited by the maximum frequency parameter (E1-04), the frequency reference will be equal to E1-04
above 5 Vdc.
H3-01 = 0

H3-01 = 1

Gain = 200 %

Gain = 200 %

Frequency
reference

100%
E1-04
-10 V

100 %
E1-04

-5 V
0V 5V

10 V

-100%
E1-04
Bias = 0 %

Gain = -200 %
0V

5V

10 V

Figure 1.75 Frequency Reference Setting by Analog Input with Increased Gain

Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
When parameter H3-01 = 1, the motor will rotate in reverse between -10 and 2 Vdc input.
H3-01 = 0
100 %

Frequency
reference

H3-01 = 1
100%

H3-01 = 0
-10 V -6.0 V
2.0 V
-25%
0

2.0 V

10 V
Analog Input
Voltage

-25%
H3-01 = 1

10 V
Analog Input
Voltage

-100%
E1-04
-150%

Figure 1.76 Frequency Reference Setting by Analog Input with Negative Bias

n H3-05: Terminal A3 Signal Level Selection


Determines the function assigned to analog input terminal A3. Refer to Multi-Function Analog Input Terminal Settings on
page 116 for a list of functions and descriptions.
No.
H3-05

Name
Terminal A3 Signal Level Selection

Setting Range
0, 1

Default
0

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 0: 0 to 10 Vdc on page 113.
Setting 1: -10 to 10 Vdc

The input level is -10 to 10 Vdc. See the explanation provided for H3-01. Refer to Setting 1: -10 to 10 Vdc on page 113.

114

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions

n H3-06: Terminal A3 Function Selection


Determines the function assigned to analog input terminal A3. Refer to Multi-Function Analog Input Terminal Settings on
page 116 for a list of functions and descriptions.
No.
H3-06

Name
Terminal A3 Function Selection

Setting Range
0 to 31

Default
2

n H3-07, H3-08: Terminal A3 Gain and Bias Setting


Parameter H3-07 sets the level of the selected input value that is equal to 10 Vdc input at terminal A3 (gain).
Parameter H3-08 sets the level of the selected input value that is equal to 0 V input at terminal A3 (bias).
No.
H3-07
H3-08

Name
Terminal A3 Gain Setting
Terminal A3 Bias Setting

Setting Range
-999.9 to 999.9%
-999.9 to 999.9%

Default
100.0%
0.0%

n H3-09: Terminal A2 Signal Level Selection


Selects the input signal level for analog input A2. Set DIP switch S1 on the terminal board accordingly for a voltage input or
current input.
No.
H3-09

Name
Terminal A2 Signal Level Selection

Setting Range
0 to 3

Default
2

Setting 0: 0 to 10 Vdc

The input level is 0 to 10 Vdc. Refer to Setting 0: 0 to 10 Vdc on page 113.


Setting 1: -10 to 10 Vdc

The input level is -10 to 10 Vdc. Refer to Setting 1: -10 to 10 Vdc on page 113.
Setting 2: 4 to 20 mA Current Input

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA Current Input

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n H3-10: Terminal A2 Function Selection


Determines the function assigned to analog input terminal A2. Refer to Multi-Function Analog Input Terminal Settings on
page 116 for a list of functions and descriptions.
No.
H3-10

Name
Terminal A2 Function Selection

Setting Range
0 to 31

Default
0

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way
as parameters H3-03 and H3-04 for analog input A1.
No.
H3-11
H3-12

Name
Terminal A2 Gain Setting
Terminal A2 Bias Setting

Setting Range
-999.9 to 999.9%
-999.9 to 999.9%

Default
100.0%
0.0%

n H3-13: Analog Input Filter Time Constant


Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter prevents erratic drive control when using a noisy analog reference. Drive operation becomes more
stable as the programmed time becomes longer, but it also becomes less responsive to rapidly changing analog signals.
No.
H3-13

Name
Analog Input Filter Time Constant

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Setting Range
0.00 to 2.00 s

Default
0.03 s
115

Parameter Details

n H3-11, H3-12: Terminal A2 Gain and Bias Setting

1.7 H: Terminal Functions

n H3-14: Analog Input Terminal Enable Selection


When one of the multi-function digital input parameters is set for Analog input enable (H1-oo = C), the value set to H3-14
determines which analog input terminals are enabled and which terminals are disabled when the input is closed. All analog
input terminals will be enabled all of the time if H1-oo is not set to C.
No.
H3-14

Name
Analog Input Terminal Enable Selection

Setting Range
1 to 7

Default
7

Setting 1: A1 only enabled


Setting 2: A2 only enabled
Setting 3: A1 and A2 only enabled
Setting 4: A3 only enabled
Setting 5: A1 and A3 only enabled
Setting 6: A2 and A3 only enabled
Setting 7: All analog input terminals enabled

n H3-16 to H3-18: Terminal A1/A2/A3 Offset


Set the offset level of the selected input value to terminals A1, A2, or A3 that is equal to 0 Vdc input. These parameters rarely
require adjustment.
No.
H3-16
H3-17
H3-18

Name
Terminal A1 Offset
Terminal A2 Offset
Terminal A3 Offset

Setting Range
-500 to 500
-500 to 500
-500 to 500

Default
0
0
0

n Multi-Function Analog Input Terminal Settings


See Table 1.40 for information on how H3-02, H3-10, and H3-06 determine functions for terminals A1, A2, and A3.
Note:

The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting
and adjusting analog input functions.
Table 1.40 Multi-Function Analog Input Terminal Settings

Setting
0
1
2
3
4
5
6
7
8
9
B
C
D
E

Function
Frequency Bias
Frequency Gain
Auxiliary Frequency Reference 1
Auxiliary Frequency Reference 2
Output Voltage Bias
Accel/Decel Time Gain
DC Injection Braking Current
Torque Detection Level
Stall Prevention Level During Run
Output Frequency Lower Limit Level
PID Feedback
PID Setpoint
Frequency Bias
Motor Temperature (PTC Input)

Page
116
117
117
117
117
117
117
117
118
118
118
118
118
118

Setting
F
10
11
12
13
14
15
16
17 <1>
1F
30
31
32

Function
Through Mode
Forward Torque Limit
Reverse Torque Limit
Regenerative Torque limit
Torque Limit Using Torque Reference/Speed Limit
Torque Compensation
General Torque Limit
Differential PID Feedback

Page
118
118
118
118
118
118

Motor Thermistor (NTC)

118

Through Mode
DriveWorksEZ Analog Input 1
DriveWorksEZ Analog Input 2
DriveWorksEZ Analog Input 3

118
118

<1> This function is available in models CIMR-Ao4A0930 to 4A1200 and A1000 HHP.

Setting 0: Frequency Bias

The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency
reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also
when only one of the analog inputs is used to supply the frequency reference.
116

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference
by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input
terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.
Setting 1: Frequency Gain

The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog
input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.
Setting 2: Auxiliary Reference 1

Sets the auxiliary frequency reference 1 when multi-step speed operation is selected. Refer to Multi-Step Speed Selection on
page 58 for details.
Setting 3: Auxiliary Reference 2

Sets the auxiliary frequency reference 2 when multi-step speed operation is selected. Refer to Multi-Step Speed Selection on
page 58 for details.
Setting 4: Output Voltage Bias

Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available
only when using V/f Control.
Setting 5: Accel/Decel Time Gain

Adjusts the gain level for the acceleration and deceleration times set to parameters C1-01 through C1-08.
The drive acceleration time is calculated by multiplying the gain level to C1-oo as follows:
C1-oo Accel/decel time gain = Drive accel/decel time
100%

Acceleration/deceleration gain from 1 to 10 V


(10 V)

Input Voltage (V)

50%

10 (%)

20%
10%
0 1V

2V

5V

10 V

Figure 1.77 Accel/Decel Time Gain with Analog Input Terminal

Setting 6: DC Injection Braking Current

The current level used for DC Injection Braking is set as a percentage of the drive rated current.
DC Injection Braking Current Level

100%

0
(4)

Parameter Details

Drive Rated
Current

10 V
(20 mA)

Figure 1.78 DC Injection Braking Current Using an Analog Input Terminal

Setting 7: Torque Detection Level

Using this setting, the overtorque/undertorque detection level for torque detection 1 (L6-01) can be set by an analog input.
The analog input replaces the level set to L6-02. An analog input of 100% (10 V or 20 mA) sets a torque detection level equal
to 100% drive rated current/motor rated torque. Adjust the analog input gain if higher detection level settings are required.
Refer to L6: Torque Detection on page 144 for details on torque detection.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

117

1.7 H: Terminal Functions


Setting 8: Stall Prevention Level

Allows an analog input signal to adjust the Stall Prevention level. Figure 1.79 shows the setting characteristics. The drive will
use the lower value of the Stall Prevention level set to L3-06 or the level coming from the selected analog input terminal.
Stall Prevention Level during Run

100%

30%

30%

100%

Analog Input Level

Figure 1.79 Stall Prevention During Run Using an Analog Input Terminal

Setting 9: Output Frequency Lower Limit Level

The user can adjust the lower limit of the output frequency using an analog input signal.
Setting B: PID Feedback

Supplies the PID feedback value. This setting requires PID operation to be enabled in b5-01. Refer to PID Feedback Input
Methods on page 34.
Setting C: PID Setpoint

Supplies the PID setpoint value and makes the frequency reference selected in parameter b1-01 no longer the PID setpoint.
PID operation to be enabled in b5-01 to use this setting. Refer to PID Setpoint Input Methods on page 33.
Setting D: Frequency Bias

The input value of an analog input set to this function will be added to the frequency reference. This function can be used with
any frequency reference source.
Setting E: Motor Temperature

In addition to motor overload fault detection oL1, it is possible to use a Positive Temperature Coefficient (PTC) thermistor
for motor insulation protection. Refer to Motor Protection Using a Positive Temperature Coefficient (PTC) Thermistor on
page 127 for a detailed explanation.
Setting F, 1F: Through Mode

When set to F or 1F, an input does not affect any drive function, but the input level can still be read out by a PLC via a
communication option or MEMOBUS/Modbus communications.
Setting 10, 11, 12, 15: Forward, Reverse, Regenerative, General Torque Limit (OLV, CLV, AOLV/PM, CLV/PM)
Note:

PM motor control modes are not available in A1000 HHP drive models.

These functions set a torque limit using analog inputs for different operating conditions. Refer to L7: Torque Limit on page
147 for details.
Setting 13: Torque Limit Using Torque Reference/Speed Limit

Sets the torque reference (when in Torque Control) or the torque limit (when in Speed Control). Refer to Setting the Torque
Reference, Speed Limit, and Torque Compensation Values on page 67 for details.
Setting 14: Torque Compensation

Sets a torque compensation value when using Torque Control. Refer to Setting the Torque Reference, Speed Limit, and
Torque Compensation Values on page 67 for details.
Setting 16: Differential PID Feedback

If an analog value is set for this function, the PID controller is set for differential feedback. The difference of the PID feedback
input value and the differential feedback input value builds the feedback value used to calculate the PID input. Refer to PID
Feedback Input Methods on page 34.
Setting 17: Motor Thermistor (NTC)

Used as a complement or a substitution for oL1. Refer to Motor Protection Using an NTC Thermistor Input on page 129
for details.
Setting 30, 31, 32: DriveWorksEZ Analog Inputs 1, 2, and 3

These settings are for DriveWorksEZ functions. Normally there is no need to change or apply these settings.
118

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions

u H4: Multi-Function Analog Outputs


These parameters assign functions to analog output terminals FM and AM for monitoring a specific aspect of drive
performance.

n H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection


Sets the desired drive monitor parameter Uo-oo to output as an analog value via terminal FM and AM. Refer to U: Monitor
Parameters on page 166 for a list of all monitors. The Analog Output Level column indicates whether a monitor can be
used for analog output.
Example: Enter 103 for U1-03.
No.
H4-01
H4-04

Name
Multi-Function Analog Output Terminal FM Monitor Selection
Multi-Function Analog Output Terminal AM Monitor Selection

Setting Range
000 to 999
000 to 999

Default
102
103

A setting of 031 or 000 applies no drive monitor to the analog output. With this setting, terminal functions as well as FM and
AM output levels can be set by a PLC via a communication option or MEMOBUS/Modbus (through mode).

n H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias

H4-05, H4-06: Multi-Function Analog Output Terminal AM Gain and Bias

Parameters H4-02 and H4-05 set the terminal FM and AM output signal level when the value of the selected monitor is at
100%. Parameters H4-03 and H4-06 set the terminal FM and AM output signal level when the value of the selected monitor
is at 0%. Both are set as a percentage, where 100% equals 10 Vdc or 20 mA analog output and 0% equals 0 V or 4 mA. The
output voltage of both terminals is limited to +/-10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and
H4-08. Figure 1.80 illustrates how gain and bias settings work.
No.
H4-02
H4-03
H4-05
H4-06

Name
Multi-Function Analog Output Terminal FM Gain
Multi-Function Analog Output Terminal FM Bias
Multi-Function Analog Output Terminal AM Gain
Multi-Function Analog Output Terminal AM Bias

Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%

Default
100.0%
0.0%
50.0%
0.0%

Using Gain and Bias to Adjust Output Signal Level

When viewing a gain setting parameter (H4-02 or H4-05) on the digital operator, the analog output will supply a voltage signal
equal to 100% of the monitor value (including changes made from bias and gain settings). When viewing a bias setting
parameter (H4-03 or H4-06), the analog output voltage will supply a signal equal to 0% monitor value.
Example 1: Set H4-02 to 50% for an output signal of 5 V at terminal FM when the monitored value is at 100%.
Example 2: Set H4-02 to 150% for an output signal of 10 V at terminal FM when the monitored value is at 76.7%.
H4-07, 08 = 0

H4-07, 08 = 1
15 V
Gain = 150%
Bias = 0%

Output Voltage
10 V

Output Voltage

Gain 150%
Bias 0%

5V

Gain 100%
Bias 0%

Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%

5V
-100%

Gain 50%
Bias 0%

-5 V

Parameter Details

10 V

100%
Monitor Value

-10 V

0V
0%

Monitor Value

100%

-15 V

Figure 1.80 Analog Output Gain and Bias Setting Example 1 and 2

Example 3: Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

119

1.7 H: Terminal Functions


H4-07, 08 = 0

Gain = 100%
Bias = 30%

H4-07, 08 = 1
10V

10 V

Gain = 100%
Bias = 0%

Output Voltage
Bias 30%
Gain 100%

Output Voltage

3V
-100%

Bias 0%
Gain 100%

3V

-4 V

0V

100%
Monitor Value

-10 V
0%

Monitor Value

100%

Figure 1.81 Analog Output Gain and Bias Setting Example 3

n H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.
No.

Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection

H4-07
H4-08

Setting Range

Default

0 to 2

0 to 2

Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA

u H5: MEMOBUS/Modbus Serial Communication


Serial communication is possible in the drive using the built-in RS-422/485 port (terminals R+, R-, S+, S-) and programmable
logic controllers (PLCs) or similar devices running the MEMOBUS/Modbus protocol.
The H5-ooparameters set the drive for MEMOBUS/Modbus Communications.

n H5-01: Drive Slave Address


Sets the drive slave address used for communications.
Note:

Cycle the power after changing this parameter to enable the new setting.

No.
H5-01

Name
Drive Slave Address

Setting Range
0 to

FFH <1>

Default
1FH

<1> If the address is set to 0, no response will be provided during communications.

Each slave drive must be assigned a unique slave address for serial communications to work. Setting H5-01 to any value
besides 0 assigns the drive its address in the network. Slave addresses do not need to be assigned in sequential order, but no
two drives may share the same address.

n H5-02: Communication Speed Selection


Sets the MEMOBUS/Modbus communications speed.
Note:

Cycle the power after changing this parameter to enable the new setting.

No.
H5-02
H5-02
0
1

120

Name
Communication Speed Selection
Communication Speed
1200 bps
2400 bps

Setting Range
0 to 5
H5-02
5
6

Default
3

Communication Speed
38400 bps
57600 bps

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions


H5-02
2
3
4

Communication Speed
4800 bps
9600 bps
19200 bps

H5-02
7
8

Communication Speed
76800 bps
115200 bps

n H5-03: Communication Parity Selection


Sets the parity used for communications.
Note:

Cycle the power after changing this parameter to enable the new setting.

No.
H5-03

Name
Communication Parity Selection

Setting Range
0 to 2

Default
0

Setting Range
0 to 3

Default
3

Setting Range
0 or 1

Default
1

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n H5-04: Stopping Method after Communication Error


Selects the stopping method after a communications error (CE) has occurred.
No.
H5-04

Name
Stopping Method after CE

Setting 0: Ramp to stop (uses the deceleration time currently enabled)


Setting 1: Fast Stop (uses the deceleration time in C1-09)
Setting 2: Coast to stop
Setting 3: Alarm only (continue operation)

n H5-05: Communication Fault Detection Selection


Enables or disables the CE detection for communications.
No.
H5-05

Name
Communication Fault Detection Selection

Setting 0: Disabled

No communication error detection. The drive continues operation.


Setting 1: Enabled

If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and
the drive will operate as determined by parameter H5-04.

n H5-06: Drive Transmit Wait Time


Sets the time the drive waits after receiving data from a master until responding data.
Name
Drive Transmit Wait Time

Setting Range
5 to 65 ms

PLCDrive

DrivePLC

PLCDrive

Command message

Response message

Command message

24 bit length

Default
5 ms
Parameter Details

No.
H5-06

Time

H5-06 setting

Figure 1.82 Drive Transmit Wait Time Setting

n H5-07: RTS Control Selection


Enables or disables RTS control.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

121

1.7 H: Terminal Functions


No.
H5-07

Name
RTS Control Selection

Setting Range
0 or 1

Default
1

Setting 0: Disabled. RTS is always on.

Use this setting with point-to-point or multi-drop RS-422 communications.


Setting 1: Enabled. RTS switches while sending.

Use this setting when using RS-485 signals for communications or when using the RS-422 signals for point-to-point
communications.

n H5-09: CE Detection Time


Sets the time the communications must be lost before the drive triggers a CE fault.
No.
H5-09

Name
CE Detection Time

Setting Range
0.0 to 10.0 s

Default
2.0 s

n H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H


Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
No.
H5-10

Name
Unit Selection for MEMOBUS/Modbus Register 0025H

Setting Range
0 or 1

Default
0

Setting 0: 0.1 V units


Setting 1: 1 V units

n H5-11: Communications Enter Function Selection


Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications. Refer
to Enter Command on page 338.
No.
H5-11

Name
Communications Enter Function Selection

Setting Range
0 or 1

Default
1

Setting 0: Enter command necessary

Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary

Parameter value changes become effective immediately without the need to send an Enter command.

n H5-12: Run Command Method Selection


Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No.
H5-12

Name
Run Command Method Selection

Setting Range
0 or 1

Default
0

Setting 0: FWD/Stop, REV/Stop

Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive in the forward direction. Setting bit 1 will start and
stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV

Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive. Setting bit 1 changes the direction.

u H6: Pulse Train Input/Output


A one-track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse train
signal can be used as the frequency reference, for PID functions, or as the speed feedback signal in V/f Control.
The pulse output monitor terminal MP can output drive monitor values as a pulse train signal with a maximum frequency of
32 kHz in sinking or sourcing mode.
Use parameters H6-oo to set the scale and other aspects of the pulse input terminal RP and pulse output terminal MP.
122

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.7 H: Terminal Functions

n H6-01: Pulse Train Input Terminal RP Function Selection


Selects the function of pulse train input terminal RP.
No.
H6-01

Name
Pulse Train Input Terminal RP Function Selection

Setting Range
0 to 3

Default
0

Setting 0: Frequency reference

If the pulse input is set for this function and the frequency reference source is set to pulse input (b1-01, b1-15 = 4), the drive
reads the frequency value from terminal RP.
Setting 1: PID feedback value

Using this setting, the feedback value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID
Control on page 33 for details on PID control.
Setting 2: PID setpoint value

Using this setting, the setpoint value for PID control can be supplied as a pulse signal at terminal RP. Refer to b5: PID
Control on page 33 for details on PID control.
Setting 3: Speed feedback (V/f Control with Simple Speed Feedback)

This setting can be used in V/f control to increase the speed control precision by using a motor speed feedback signal. The
drive reads the speed feedback from terminal RP, compares it to the frequency reference and compensates the motor slip using
a speed regulator (ASR, set up in the C5-oo parameters) like shown in Figure 1.83. Because input terminal RP is incapable
of detecting motor direction, a separate way of determining motor direction still needs to be set up:

1.

Using a Digital Input

2.

If a digital input programmed for Forward/reverse detection (H1-oo = 7E) is closed, the drive assumes reverse
rotation. If open, then the drive assumes that the motor is rotating forwards.
Using the Frequency Reference Direction
If no digital input is set to Forward/reverse detection (H1-oo = 7E), the drive uses the direction of the frequency
reference as the direction for the speed feedback detected at the pulse input.

Figure 1.83 Speed Control with ASR in V/f with Simple Speed Feedback

Enabling V/f Control with Simple Speed Feedback:

1.
2.
3.
4.
Note:

Set the drive to V/f Control (A1-02 = 0).


Connect the motor speed pulse signal to the pulse input RP, set H6-01 = 3, and set the pulse signal frequency that
is equal to the maximum speed to H6-02 (pulse input scaling). Make sure the pulse input bias (H6-04) is 0% and the
gain (H6-03) is 100%.
Decide on the signal used for detecting the direction. Set H1-oo = 7F if using a digital input.
Use the ASR gain and integral time parameters described in C5: Automatic Speed Regulator (ASR) on page 52
for adjusting the responsiveness.
1. C5 parameters will appear when using V/f Control (A1-02 = 0) and when the pulse input RP function is set for simple PG feedback in
V/f Control (H6-01 = 3).

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

123

Parameter Details

Motor speed

1.7 H: Terminal Functions


2. If running two motors from the same drive, V/f Control with simple PG feedback can be used for motor 1 only.

n H6-02: Pulse Train Input Scaling


Sets the pulse signal frequency that is equal to 100% of the input value selected in parameter H6-01.
No.
H6-02

Name
Pulse Train Input Scaling

Setting Range
100 to 32000 Hz

Default
1440 Hz

n H6-03: Pulse Train Input Gain


Sets the level of the input value selected in H6-01 when a pulse train signal with the frequency set in H6-02 is input to terminal
RP.
No.
H6-03

Name
Pulse Train Input Gain

Setting Range
0.0 to 1000.0%

Default
100.0%

n H6-04: Pulse Train Input Bias


Sets the level of the input value selected in H6-01 when no signal (0 Hz) is input to terminal RP.
No.
H6-04

Name
Pulse Train Input Bias

Setting Range
-100.0 to 100.0%

Default
0.0%

Setting Range
0.00 to 2.00 s

Default
0.10 s

n H6-05: Pulse Train Input Filter Time


Sets the pulse train input filter time constant in seconds.
No.
H6-05

Name
Pulse Train Input Filter Time

n H6-06: Pulse Train Monitor Selection


Selects the monitor to output as a pulse train signal via terminal MP. Enter the three digits in Uo-oo to indicate which
monitor to output. Refer to U: Monitor Parameters on page 166 for a complete list of monitors. Monitors that can be selected
by H6-06 appear in the table below.
No.
H6-06

Name
Pulse Train Monitor Selection

Setting Range
000

<1> ,

031, 101, 102, 105,


116, 501, 502,
801 to 809

Default
102

<1> Set 000 when the terminal is not used or when using the terminal in the through mode.

n H6-07: Pulse Train Monitor Scaling


Sets the output frequency at terminal MP when the specified monitor item is at 100%. Set H6-06 to 102 and H6-07 to 0 to
make the pulse train monitor output synchronous to the output frequency.
No.
H6-07

Name
Pulse Train Monitor Scaling

Setting Range
0 to 32000 Hz

Default
1440 Hz

n H6-08: Pulse Train Input Minimum Frequency


Sets the minimum output frequency detected by the pulse train input. Increasing this setting reduces the time the drive needs
to react to changes in the input signal.
The pulse input value becomes 0 when the pulse input frequency falls below this level.
Enabled when H6-01 = 0, 1, or 2.
When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency
becomes the detection time for PG disconnect (F1-14).
No.
H6-08

124

Name
Pulse Train Input Minimum Frequency

Setting Range
0.1 to 1000.0 Hz

Default
0.5 Hz

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

1.8

L: Protection Functions

u L1: Motor Protection


n L1-01: Motor Overload Protection Selection
The drive has an electronic overload protection function that estimates the motor overload level based on output current, output
frequency, thermal motor characteristics, and time. When the drive detects a motor overload an oL1 fault is triggered and the
drive output shuts off.
L1-01 sets the overload protection function characteristics according to the motor being used.
No.

Name

Setting Range

L1-01

Motor Overload Protection Selection

0 to 6

Note:

Default
Determined by
A1-02

1. When the motor protection function is enabled (L1-01 0), an oL1 alarm can be output through one of the multi-function outputs by
setting H2-01 to 1F. The output closes when the motor overload level reaches 90% of the oL1 detection level.
2. Set L1-01 to a value between 1 and 5 when running a single motor from the drive to select a method to protect the motor from overheat.
An external thermal relay is not necessary.

Setting 0: Disabled (motor overload protection is not provided)

Use this setting if no motor overheat protection is desired or if multiple motors are connected to a single drive. If multiple
motors are connected to a single drive, install a thermal relay for each motor as shown in Figure 1.84.
Power
supply

Drive

M1
MC1

L10

MC2

L20

M2

MC1, MC2: Magnetic contactors


L10, L20: Thermal relays

Figure 1.84 Example of Protection Circuit Design for Multiple Motors


NOTICE: Thermal protection cannot be provided when running multi-motors simultaneously with the same drive, or when using motors with
a relatively high current rating compared to other standard motors (such as a submersible motor). Failure to comply could result in motor
damage. Disable the electronic overload protection of the drive (L1-01 = 0: Disabled) and protect each motor with individual motor thermal
overloads.
Note:

Close MC1 and MC2 before operating the drive. MC1 and MC2 cannot be switched off during run.

Setting 1: General-purpose motor (standard self-cooled)

Overload Tolerance

Torque (%)

150

60 s

Cooling Ability

Overload Characteristics

Motor designed to operate from line


power.
Motor cooling is most effective when
running at rated base frequency (check
the motor nameplate or specifications).

Continuous operation at less than line


power frequency with 100% load can
trigger motor overload protection
(oL1). A fault is output and the motor
will coast to stop.

Rated Speed=100% Speed


A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

100
90
60
50 Continuous
A

B
C

05 33

100 120 167 200


Speed (%)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

125

Parameter Details

Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the motor from overheat
throughout the entire speed range.

1.8 L: Protection Functions


Setting 2: Drive dedicated motor (speed range for constant torque: 1:10)

Use this setting when operating a drive duty motor that allows constant torque in a speed range of 1:10. The drive will allow
the motor to run with 100% load from 10% up to 100% speed. Running at slower speeds with full load can trigger an overload
fault.
Overload Tolerance
150

Torque (%)

Overload Characteristics

Rated Speed=100% Speed

60 s

A: Max. speed for 200LJ and above


B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

100

55
50

Cooling Ability

Motor is designed to effectively cool


itself even at low speeds.
A

Continuous

Continuous operation with 100% load


from 6 Hz to E1-06, Motor Base
Frequency.

B
C

0 110

100120 167 200


Speed (%)

Setting 3: Vector motor (speed range for constant torque: 1:100)

Use this setting when operating a drive-dedicated motor that allows constant torque in a speed range of 1:100. This motor type
is allowed to run with 100% load from 1% up to 100% speed. Running slower speeds with full load can trigger an overload
fault.
Overload Tolerance
150

Overload Characteristics

Rated Speed=100% Speed


A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

60 s
Torque (%)

Cooling Ability

100
90

50 Continuous

Motor is designed to effectively cool


itself at speeds near 0.6 Hz.

Continuous operation with 100% load


from 0.6 Hz to E1-06, Motor Base
Frequency.
Continuous operation below 0.6 Hz
may cause an oL1 or oL2 fault.

C
0 1

100120 167 200


Speed (%)

Setting 6: General-purpose motor


Note:

General-purpose motors are designed with a base speed that operates at line frequency (50/60 Hz depending on geographic region).

Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics and protects the motor from overheat
throughout the entire speed range.
Overload Tolerance

Torque (%)

150

60 s

Cooling Ability

Overload Characteristics

Motor designed to operate from line


power. Motor cooling is most effective
when running at rated base frequency
(check the motor nameplate or
specifications)

Continuous operation at less than line


power frequency with 100% load can
trigger motor overload protection
(oL1). A fault is output and the motor
will coast to stop.

Rated Speed=100% Speed


A: Max. speed for 200LJ and above
B: Max. speed for 160MJ to 180 LJ
C: Max. speed for 132MJ and below

100
90
60
50 Continuous
A

B
C

05 33

126

100 120 167 200


Speed (%)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

n L1-02: Motor Overload Protection Time


Sets the detection time of motor overheat due to overload. This setting rarely requires adjustment, but should correlate with
the motor overload tolerance protection time for performing a hot start.
No.
L1-02

Name
Motor Overload Protection Time

Setting Range
0.1 to 5.0 minutes

Default
1.0 minutes

Defaulted to operate with an allowance of 150% overload operation for one minute in a hot start.
Figure 1.85 illustrates an example of the electrothermal protection operation time using a general-purpose motor operating at
the value of E1-06, Motor Base Speed, with L1-02 set to one minute.
During normal operation, motor overload protection operates in the area between a cold start and a hot start.
Cold start: Motor protection operation time in response to an overload situation that was suddenly reached when starting a
stationary motor.
Hot start: Motor protection operation time in response to an overload situation that occurred during sustained operation at
rated current.
Operation time (minutes)

10
7
3
Cold start
1

0.4

Hot start

0.1
0

100

150

200

Motor current (%)


E2-01 = 100% motor current

Figure 1.85 Motor Protection Operation Time

n Motor Protection Using a Positive Temperature Coefficient (PTC) Thermistor


Connect a motor PTC can to an analog input of the drive for motor overheat protection.
The motor overheat alarm level triggers an oH3 alarm and the drive continues the operation selected in L1-03. The overheat
fault level triggers an oH4 fault, outputs a fault signal, and the drive stops the motor using the stop method selected in L1-04.
Connect the PTC between terminals AC and A3 and set jumper S4 on the terminal board to PTC as shown in Figure 1.86.
Set H3-05 to 0 and H3-06 to E.

MA
MB

DIP Switch S4
PTC

Fault output

MC

Parameter Details

Drive

Multi-function input

M1
M2

AI

A3 (0-10 V)

M3
M4

Multi-function
digital outputs

M5
M6

PTC
thermistor

AC

Figure 1.86 Connection of a Motor PTC

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

127

1.8 L: Protection Functions


The PTC must exhibit the characteristics shown in Figure 1.87 in one motor phase. The motor overload protection of the drive
expects 3 of these PTCs to be connected in a series.
Class H
180 C

Class F
150 C

Resistance ( )

Tr: threshold value

Tr
Tr - 5K (oH3 Alarm Level)

Tr

Temperature

Tr + 5K (oH4 Fault Level)

Figure 1.87 Motor PTC Characteristics

Set up overheat detection using a PTC using parameters L1-03, L1-04, and L1-05 as explained in the following sections.

n L1-03: Motor Overheat Alarm Operation Selection (PTC input)


Sets the drive operation when the PTC input signal reaches the motor overheat alarm level (oH3).
No.
L1-03

Name
Motor Overheat Alarm Operation Selection (PTC input)

Setting Range
0 to 3

Default
3

Setting 0: Ramp to stop

The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to stop

The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop

The drive stops the motor using the Fast Stop time set in parameter C1-09.
Setting 3: Alarm only

The operation is continued and an oH3 alarm is displayed on the digital operator.

n L1-04: Motor Overheat Fault Operation Selection (PTC input)


Sets the drive operation when the PTC input signal reaches the motor overheat fault level (oH4).
No.
L1-04

Name
Motor Overheat Fault Operation Selection (PTC input)

Setting Range
0 to 2

Default
1

Setting 0: Ramp to Stop

The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to Stop

The drive output is switched off and the motor coasts to stop.
Setting 2: Fast Stop

The drive stops the motor using the Fast Stop time set in parameter C1-09.

n L1-05: Motor Temperature Input Filter Time (PTC input)


Sets a filter on the PTC input signal to prevent erroneous detection of a motor overheat fault.
No.
L1-05

Name
Motor Temperature Input Filter Time (PTC input)

Setting Range
0.00 to 10.00 s

Default
0.20 s

n L1-13: Continuous Electrothermal Operation Selection


Determines whether to hold the current value of the electrothermal motor protection (L1-01) when the power supply is
interrupted.
128

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions


No.
L1-13

Name
Continuous Electrothermal Operation Selection

Setting Range
0, 1

Default
1

Setting 0: Disabled
Setting 1: Enabled

n Motor Protection Using an NTC Thermistor Input


Motor protection is possible for models CIMR-Ao4A0930, 4A1200 and A1000 HHP by connecting the NTC thermistor input
in the motor windings to one of the drive analog input terminals.
This enables the drive to provide torque compensation in response to changes in motor temperature and protect the motor from
overheating.
If the NTC input signal using the drive multi-function analog input terminal exceeds the overheat alarm level set to L1-16 (or
L1-18 for motor 2), then oH5 will flash on the digital operator screen. The drive will respond to the alarm according to the
setting of L1-20 (default setting is to continue operation when an oH5 alarm occurs).
Figure 1.88 shows a circuit using the NTC thermistor and the terminal resistance values. Set DIP switch S1 on the drive to
"V" for voltage input when wiring the NTC thermistor input to terminal A2 on the drive.
Note:

This example assumes that H3-10 = 17, H3-09 = 10, and that DIP switch S1 has been set for voltage input.
Drive

+V
(+10.5 V, 20 mA)
Voltage Divider
2 kW
A2 (0-10 V)
NTC Thermistor
AC

DIP Switch S1
V

Figure 1.88 Motor Protection Circuit Using NTC Input


Resistance (W)
25,000
20,000
15,000

5,000
0

2733
716
-50

50

100

Temperature ( C)
150

Figure 1.89 Temperature and Resistance of NTC Thermistor

L1-15 to L1-20 can determine the overheat protection settings using the NTC thermistor input. Parameter descriptions are
listed below.

n L1-15: Motor 1 Thermistor Selection (NTC)


Note:

No.
L1-15

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Name
Motor 1 Thermistor Selection (NTC)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Setting Range
0 to 2

Parameter Details

10677

10,000

Default
0

129

1.8 L: Protection Functions


Setting 0: Disabled
Setting 1: Thermistor input by Analog input
Setting 2: Thermistor input by special Thermistor input

n L1-16: Motor 1 Overheat Temperature


Note:

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Sets the temperature that will trigger an overheat fault (oH5) for motor 1.
No.
L1-16

Name
Motor 1 Overheat Temperature

Setting Range
50 to 200 C

Default
120

n L1-17: Motor 2 Thermistor Selection (NTC)


Note:

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

No.
L1-17

Name
Motor 2 Thermistor Selection (NTC)

Setting Range
0 to 2

Default
0

Setting 0: Disabled
Setting 1: Thermistor input by Analog input
Setting 2: Thermistor input by special Thermistor input

n L1-18: Motor 2 Overheat Temperature


Note:

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Sets the temperature that will trigger an overheat fault (oH5) for motor 2.
No.
L1-18

Name
Motor 2 Overheat Temperature

Setting Range
50 to 200 C

Default
120

n L1-19: Operation Time at Thermistor Disconnect (NTC)


Note:

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Determines drive operation when a thermistor disconnect fault (THo) occurs.


No.
L1-19

Name
Operation Time at Thermistor Disconnect (NTC)

Setting Range
0 to 3

Default
3

Setting 0: Ramp to stop

The drive stops the motor using the deceleration time set in parameter C1-02.
Setting 1: Coast to stop

The drive output is switched off and the motor coasts to a stop.
Setting 2: Fast stop

The drive stops the motor using the Fast stop time set in parameter C1-09.
Setting 3: Alarm only

The operation is continued and a THo alarm is displayed on the digital operator.

n L1-20: Operation at Motor Overheat


Note:

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

Determines drive operation when a motor overheat fault (oH5) occurs.


No.
L1-20

Name
Operation at Motor Overheat

Setting Range
0 to 3

Default
1

Setting 0: Ramp to stop

The drive stops the motor using the deceleration time set in parameter C1-02.
130

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions


Setting 1: Coast to stop

The drive output is switched off and the motor coasts to a stop.
Setting 2: Fast stop

The drive stops the motor using the Fast stop time set in parameter C1-09.
Setting 3: Alarm only

The operation is continued and an oH5 alarm is displayed on the digital operator.

n L1-21: Thermally Sensitive Resistor Selection


Sets the type of thermistor input for Motor 1 and Motor 2.
No.
L1-21

Name
Thermally Sensitive Resistor Selection

Setting Range
0, 1

Default
0

Setting 0: H5 Table Selection


Setting 1: Pt100 Table Selection

u L2: Momentary Power Loss Ride-Thru


n L2-01: Momentary Power Loss Operation Selection
When a momentary power loss occurs (DC bus voltage falls below the level set in L2-05), the drive can automatically return
to the operation it was performing prior to the power loss based on certain conditions.
No.
L2-01

Name
Momentary Power Loss Operation Selection

Setting Range
0 to 5

Default
0

Setting 0: Disabled (default)

If power is not restored within 15 ms, a Uv1 fault will result and the motor coasts to stop.
Setting 1: Recover within L2-02

When a momentary power loss occurs, the drive output will be shut off. If the power returns within the time set to parameter
L2-02, the drive will perform Speed Search and attempt to resume operation. If the power does not return within this time, it
will trigger a Uv1 fault.
Setting 2: Recover as long as CPU has power

When a momentary power loss occurs, the drive output will be shut off. If the power returns and the drive control circuit has
power, the drive will attempt to perform Speed Search and resume the operation. This will not trigger a Uv1 fault.
Setting 3: Kinetic Energy Backup (KEB) Ride-Thru operation within L2-02

The drive decelerates using regenerative energy from the motor until the time set in L2-02 has expired. It then tries to accelerate
back to the frequency reference. If the power does not return within the time set to L2-02, it will trigger a Uv1 fault and the
drive output will shut off.
Setting 4: KEB Ride-Thru as long as CPU has power

The drive decelerates using regenerative energy from the motor until the power returns and then restarts. If the motor comes
to a stop before the power returns, the drive loses control power and the drive output shuts off. A Uv1 fault is not triggered.
The drive ramps to stop using the regenerative energy from the motor. Even if the power is restored, the drive will continue
to decelerate until the motor comes to a complete stop. If an input terminal set for KEB 1 (H1-oo = 65, 66) is triggered while
the drive is decelerating, it will accelerate back up to speed when the input is released.
Notes on Settings 1 through 5

Uv will flash on the operator while the drive is attempting to recover from a momentary power loss. A fault signal is not
output at this time.
A Momentary Power Loss Unit is available to allow for a longer momentary power loss ride through time in models
CIMR-Ao2A0004 to 2A0056 and 4A0002 to 4A0031. This option makes it possible to continue running the drive after up
to two seconds of power loss.
When using a magnetic contactor between the motor and the drive, keep the magnetic contactor closed as long as the drive
performs KEB operation or attempts to restart with Speed Search.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

131

Parameter Details

Setting 5: Ramp to stop with KEB deceleration

1.8 L: Protection Functions


Keep the Run command active during KEB operation or the drive cannot accelerate back to the frequency reference when
the power returns.

n KEB Ride-Thru Function


When the drive detects a power loss, KEB Ride-Thru decelerates the motor and uses regenerative energy to keep the main
circuit operating. Despite power loss, the drive output is not interrupted.
Single Drive KEB Ride-Thru 1

After KEB Ride-Thru begins, the drive uses regenerative energy from the motor to keep the DC bus voltage at the level set
to L2-11 while adjusting the rate of deceleration.

n KEB Ride-Thru Start


KEB operation is triggered independently of the selected KEB operation mode. When the KEB function is selected as the
function to be executed when power loss operation occurs (L2-01 = 3, 4, or 5), then KEB Ride-Thru will be activated if one
of the following conditions becomes true:
A digital input programmed for H1-oo = 65 or 66 is activated. This will start the KEB operation.
The DC bus voltage fell below the level specified in L2-05.
When using a digital input to trigger KEB operation and the device controlling the input acts relatively slow, set a minimum
KEB operation time in parameter L2-10. In the example below, the DC bus voltage triggers KEB operation and a digital input
triggers the Hold command.
Main Power Supply
0V

Power loss
L2-10

KEB digital input is


set with in L2-10

KEB Digital Input

DC bus voltage
L2-11 (Desired DC Bus Voltage)
L2-05 (Uv Detection Level)
0V
Input holds KEB operation,
even though voltage has
returned

Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz

Figure 1.90 KEB Operation Using a KEB Input

n KEB Ride-Thru End Detection


The KEB function end detection depends on the setting of parameter L2-01 and whether a digital input programmed for KEB
(H1-oo = 65, 66) is used.
KEB Ride-Thru Operation in L2-02, Input Terminals Not Used

Here, L2-01 = 3 and the input terminals have not been set for KEB Ride-Thru (H1-oo does not equal 65, 66). After
decelerating for the time set in parameter L2-02, the drive ends KEB operation and attempts to accelerate back to the frequency
reference. A Uv1 fault occurs and the drive output shuts off if the power does not return within the time set to L2-02.

132

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions


Power Loss shorter than L2-02

Power Loss longer than L2-02


Power Loss

Power Loss

Main Power Supply

0V

0V

DC Bus Voltage
L2-11 (Desired DC
Bus Voltage)

L2-11 (Desired DC Bus Voltage)

L2-05 (Uv Detection Level)

L2-05 (Uv Detection Level)


0V

0V
L2-02
(Power Loss
Ride-Thru Time)

Output Frequency

L2-02
(Power Loss
Ride-Thru Time)

Acceleration using L2-07 or


C1-01/03/05/07 if L2-07 = 0

Drive attempts to restart but


power has not returned
Uv1 fault is triggered
KEB Deceleration

KEB Deceleration
0 Hz

0 Hz

Figure 1.91 KEB Operation Using L2-02, Without KEB Input

KEB Ride-Thru Operation Within L2-02, Input Terminals Used

Here, L2-01 = 3 and an input terminal is set to issue KEB Ride-Thru (H1-oo = 65, 66). After decelerating for the time set
in parameter L2-02, the drive checks the DC bus voltage and the status of the digital input. If the DC bus voltage is still below
the level set in L2-11 or if the KEB digital input is still active, KEB deceleration continues. If the voltage level has risen above
the value set to L2-11, then normal operation is resumed.
Note:

If L2-10 is set to a longer time than L2-02, the drive checks the DC bus voltage level and the status of the terminal assigned to KEB RideThru after the time set to L2-02 passes. The drive will then try to restart.
Power loss shorter than L2-02

Power loss longer than L2-02

Power Loss

Main Power Supply


0V

Power Loss
0V

L2-10

L2-10

KEB Digital Input

DC bus voltage

L2-11 (Desired DC Bus Voltage)

L2-11 (Desired DC Bus Voltage)

L2-05 (Uv Detection Level)


0V

L2-05 (Uv Detection Level)


0V

L2-02
(Power Loss
Ride-Thru Time)

KEB restart after


L2-02 has passed

L2-02
(Power Loss
Ride-Thru Time)

KEB restart triggered by


digital input release

Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz

KEB deceleration is
triggered by DC bus voltage
0 Hz

Figure 1.92 KEB Operation Using L2-02 and KEB Input

Here, L2-01 = 4 and the input terminals have not been set for KEB Ride-Thru (H1-oo does not equal 65, 66). After
decelerating for the time set to parameter L2-10, the drive checks the DC bus voltage level. Deceleration continues if the DC
bus voltage is lower than the level set in L2-11. Normal operation resumes when the DC bus voltage rises above the value of
L2-11.

Parameter Details

KEB Ride-Thru Operation as Long as CPU Has Power, KEB Input Not Used

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

133

1.8 L: Protection Functions


Power Loss Shorter than L2-10

Power Loss Longer than L2-10

Power Loss

Main Power Supply

Power Loss

0V

0V

DC Bus Voltage
L2-11 (Desired DC Bus Voltage)

L2-11 (Desired DC Bus Voltage)

L2-05 (Uv Detection Level)


0V

L2-05 (Uv Detection Level)


0V

L2-10
(Min. KEB Operation
Time)

Output Frequency

L2-10
(Min. KEB
Op. Time)

Acceleration using L2-07 or


C1-01/03/05/07 if L2-07 = 0

KEB Deceleration

Acceleration using L2-07 or


C1-01/03/05/07 if L2-07 = 0

KEB Deceleration

0 Hz

0 Hz

Figure 1.93 KEB Operation Using L2-10, Without KEB Input

KEB Ride-Thru Operation as Long as CPU Has Power, KEB Input Used

Here, L2-01 = 3 and an input terminal is set to issue KEB Ride-Thru (H1-oo = 65, 66). After decelerating for the time set
to parameter L2-10, the drive checks the DC bus voltage and the status of the digital input. Deceleration continues if the DC
bus voltage is still below the level set in L2-11 or if the digital input assigned to KEB Ride-Thru is still active. Normal operation
resumes when the DC bus voltage rises above the value of L2-11 and the terminal that initiated KEB Rid-Thru is released.
Power loss shorter than L2-10

Power loss longer than L2-10

Power Loss

Main Power Supply

Power Loss

0V

0V

KEB Digital Input


DC bus voltage

L2-11 (Desired DC Bus Voltage)

L2-11 (Desired DC Bus Voltage)

L2-05 (Uv Detection Level)


0V

L2-05 (Uv Detection Level)


0V

L2-10 (Minimum KEB


Operation Time)

L2-10 (Min.
KEB
Operation
Time)

KEB restart after


L2-02 has passed

KEB restart after


L2-02 has passed

Output Frequency
KEB deceleration is
triggered by DC bus voltage
0 Hz

KEB deceleration is
triggered by DC bus voltage
0 Hz

Figure 1.94 KEB Operation Using L2-10 and KEB Input

L2-01 = 5

KEB operation ends when the motor has come to a stop, even if the power returns and the digital input terminal that initiated
KEB Ride-Thru is cleared.

n KEB Operation Wiring Example


Figure 1.95 shows a wiring example to trigger the KEB Ride-Thru at power loss using an undervoltage relay. When a power
loss occurs, the undervoltage relay triggers KEB Ride-Thru at terminal S6 (H1-06 = 65, 66). Note that using System KEB
Ride-Thru requires an additional dynamic braking option.
Note:

134

Do not switch off the Run command during momentary power loss. If the Run command is shut off, the drive will not accelerate back to
speed when the power is restored.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

B1

B2

L1

R/L1

U/T1

L2

S/L2

V/T2

L3

T/L3

W/T3

UV Detection
Relay

S6 - KEB command 1
S1 - Start command
SC

Figure 1.95 KEB Function Wiring Example

n Parameters for KEB Ride-Thru


Table 1.41 lists parameters needed to set up KEB Ride-Thru.
Table 1.41 KEB Function Related Adjustments

Parameter

Name

Setting Instructions

C2-03

S-Curve at Deceleration Start

L2-05

Undervoltage Detection
Level

L2-07

KEB Acceleration Time

L2-10

KEB Detection Time

L2-11

Desired DC Bus Voltage


during KEB

C1-09

Fast Stop Time

KEB
Mod
e
0

Increase if an overvoltage fault occurs during KEB deceleration.


Decrease if an undervoltage fault occurs during KEB deceleration.
Shorten if undervoltage occurs immediately after KEB Ride-Thru is triggered.
Lengthen this setting if overvoltage occurs immediately after KEB operation
starts.
Increase if an undervoltage fault occurs at KEB operation start to let the drive detect
power loss more quickly.
Adjust to the desired acceleration time. If set to 0, standard acceleration times are
used (C1-01, C1-03, C1-05, C1-07).
Increase when a digital input is set for KEB Ride-Thru and an undervoltage fault
occurs after power was lost because the device controlling the input does not react
quickly enough.
If the DC bus voltage overshoots after KEB Ride-Thru begins (and no input
terminal is set to KEB Ride-Thru), increase L2-10 to longer than the overshoot.
Set to approximately 1.22 times the input voltage for Single Drive KEB RideThru 2.
Set to approximately 1.4 times the input voltage for Single Drive KEB Ride-Thru
1 and System KEB Ride-Thru modes.

YES
YES
YES
YES

YES

YES

Sets the maximum time allowed to ride through a power loss. If power loss operation exceeds this time, the drive will attempt
to accelerate back to the frequency reference. This parameter is valid if L2-01 = 1 or 3.
Note:

The amount of time the drive is capable of recovering after a power loss is determined by the capacity of the drive. Drive capacity determines
the upper limit for L2-02.

No.

Name

Setting Range

L2-02

Momentary Power Loss Ride-Thru Time

0.0 to 25.5 s

Default
Determined by C6-01
and o2-04

n L2-03: Momentary Power Loss Minimum Baseblock Time


Sets the minimum baseblock time when power is restored following a momentary power loss. This determines the time the
drive waits for the residual voltage in the motor to dissipate. Increase this setting if overcurrent or overvoltage occurs at the
beginning of Speed Search, after a power loss, or during DC Injection Braking.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

135

Parameter Details

n L2-02: Momentary Power Loss Ride-Thru Time

1.8 L: Protection Functions


No.

Name

Setting Range

L2-03

Momentary Power Loss Minimum Baseblock Time

0.1 to 5.0 s

Default
Determined by C6-01
and o2-04

n L2-04: Momentary Power Loss Voltage Recovery Ramp Time


Sets the time for the drive to restore the output voltage to the level specified by the V/f pattern after Speed Search. The setting
value determines the time for the voltage to go from 0 V to the maximum voltage.
No.

Name

Setting Range

L2-04

Momentary Power Loss Voltage Recovery Ramp Time

0.0 to 5.0 s

Default
Determined by
C6-01 and o2-04

n L2-05: Undervoltage Detection Level (Uv)


Determines the voltage at which a Uv1 fault is triggered or at which the KEB function is activated. This setting rarely needs
to be changed.
No.

Name

Setting Range

L2-05

Undervoltage Detection Level

300 to 420 Vdc <1>

Default
Determined by
A1-02, C6-01, E1-01
and o2-04 <2>

<1> Values shown are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690 V class
drives.
<2> The default setting for 400 V class drives depends on whether the drive input voltage is over 400 V or under 400 V.
Note:

1. Install an AC reactor option on the input side of the power supply when setting L2-05 below the default value to prevent damage to
drive circuitry.
2. If using KEB Ride-Thru and L2-05 is set too low, then undervoltage in the DC bus (Uv1) will be triggered before KEB Ride-Thru can
be executed. Take caution not to set this value too low.

n L2-07: KEB Acceleration Time


Sets the time to reaccelerate from the speed when KEB was deactivated to the frequency reference.
When set to 0.0 s, the drive will accelerate to speed according to the active deceleration time set by C1-01, C1-03, C1-05, or
C1-07.
No.
L2-07

Name
KEB Acceleration Time

Setting Range
0.00 to 6000.0

s <1>

Default
0.00 s

<1> Setting range is determined by the accel/decel time units set in C1-10. If the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes
0.00 to 600.00 s.

n L2-10: KEB Detection Time (Minimum KEB Time)


Determines the duration of KEB Ride-Thru operation after it is triggered. Refer to KEB Ride-Thru End Detection on page
132 for details.
No.
L2-10

Name
KEB Detection Time

Setting Range
0 to 2000 ms

Default
50 ms

n L2-11: DC Bus Voltage Setpoint during KEB


Determines the setpoint (target value) for the DC bus voltage during Single KEB Ride-Thru 2. For Single KEB Ride-Thru 1
and System KEB Ride-Thru, parameter L2-11 defines the voltage level to end KEB Ride-Thru.
No.

Name

Setting Range

L2-11

DC Bus Voltage Setpoint during KEB

300 to 800 Vdc <1>

Default
Determined by
E1-01

<1> Values shown are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690 V class
drives.

136

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

u L3: Stall Prevention


The motor may experience excessive slip because it cannot keep up with the frequency reference when the load is too high or
acceleration and deceleration times are too short. If the motor slops during acceleration, it usually causes an overcurrent fault
(oC), drive overload (oL2), or motor overload (oL1). If the motor slips during deceleration, it can cause excessive regenerative
power to flow back into the DC bus capacitors, and eventually cause the drive to fault out from overvoltage (oV). The Stall
Prevention Function prevents the motor from stalling and while allowing the motor to reach the desired speed without requiring
the user to change the acceleration or deceleration time settings. The Stall Prevention function can be set separately for
acceleration, operating at constant speeds, and deceleration.

n L3-01: Stall Prevention Selection during Acceleration


Stall Prevention during acceleration prevents tripping with overcurrent (oC), motor overload (oL1), or drive overload (oL2)
faults common when accelerating with heavy loads.
L3-01 determines the type of Stall prevention the drive should use during acceleration.
No.
L3-01

Name
Stall Prevention Selection during Acceleration

Setting Range
0 to 2 <1>

Default
1

<1> Setting 2 is not available for OLV/PM.

Setting 0: Disabled

No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to speed
fast enough, causing an overload fault.
Setting 1: Enabled

Enables Stall Prevention during acceleration. Operation varies depending on the control mode.
V/f Control, V/f Control with PG, and Open Loop Vector Control:
Acceleration is reduced when the output current value exceeds 85% of the level set to parameter L3-02 for a longer than the
time set to L3-27. The acceleration stops when the current exceeds L3-02. Acceleration continues when the current falls
below L3-02 for longer than the time set to L3-27.
The Stall Prevention level is automatically reduced in the constant power range. Refer to L3-03: Stall Prevention Limit
during Acceleration on page 138.
Output current

L3-02

Stall Prevention Level


During Acceleration

L3-02
-15%

Time

Parameter Details

Output frequency

Controls the output frequency


to prevent the motor from stalling
Time

Figure 1.96 Stall Prevention During Acceleration for Induction Motors

Open Loop Vector Control for PM:


Acceleration stops when the output current reaches the level set to parameter L3-02. When the time set to parameter L3-27
passes, the drive decelerates using the deceleration time set to L3-22 (Refer to L3-22: Deceleration Time at Stall Prevention
during Acceleration on page 138). Deceleration stops when the current falls below 85% of L3-02,. The drive will attempt
to reaccelerate after the time set to L3-27.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

137

1.8 L: Protection Functions

Output current
L3-02

15 % of L3-02

Time
Output frequency
L3-27
L3-27
Time
Deceleration
using L3-22

Figure 1.97 Stall Prevention During Acceleration for Permanent Magnet Motors
Note:

PM motor control modes are not available in A1000 HHP drive models.

Setting 2: Intelligent Stall Prevention

The drive disregards the selected acceleration time and attempts to accelerate in the minimum time. The acceleration rate is
adjusted so the current does not exceed the value set to parameter L3-02.

n L3-02: Stall Prevention Level during Acceleration


Sets the output current level at which the Stall Prevention during acceleration is activated.
No.
L3-02

Name
Stall Prevention Level during Acceleration

Setting Range
0 to 150%

<1>

Default
<1>

<1> The upper limit and default value is determined by the duty rating and the carrier frequency derating selection (C6-01 and L8-38 respectively).

Lower L3-02 if stalling occurs when using a motor that is relatively small compared to the drive.
Also set parameter L3-03 when operating the motor in the constant power range.

n L3-03: Stall Prevention Limit during Acceleration


The Stall Prevention level is automatically reduced when the motor is operated in the constant power range. L3-03 sets the
lower limit for this reduction as a percentage of the drive rated current.
No.
L3-03

Name
Stall Prevention Limit during Acceleration

Setting Range
0 to 100%

Default
50%

Stall Prevention level during Acceleration

L3-02

L3-03

Output frequency
E1-06
Base frequency

Figure 1.98 Stall Prevention Level and Limit During Acceleration

n L3-22: Deceleration Time at Stall Prevention during Acceleration


Sets the brief deceleration time used when stalling occurs while accelerating a PM motor. When set to 0, this function is
disabled and the drive decelerates at the selected deceleration time when stalling occurs.
The function is effective only in OLV/ PM control and when parameter L3-01 is set to 1.
138

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions


No.
L3-22

Name
Deceleration Time at Stall Prevention During Acceleration

Setting Range
0 to 6000.0 s

Default
0.0 s

n L3-04: Stall Prevention Selection during Deceleration


Stall Prevention during deceleration controls the deceleration based on the DC bus voltage and prevents an overvoltage fault
caused by high inertia or rapid deceleration.
No.
L3-04

Name
Stall Prevention Selection During Deceleration

Setting Range
0 to

5 <1> <2> <3>

Default
1

<1> Settings 3 through 5 are not available in OLV/PM. Settings 2 through 5 are not available in AOLV/PM and CLV/PM.
<2> Setting 3 is not available for models CIMR-Ao4A0930 and 4A1200.
<3> HHP models only have settings 0, 1, 4, and 5

Setting 0: Disabled

The drive decelerates according to the set deceleration time. With high inertia loads or rapid deceleration, an overvoltage fault
may occur. If an overvoltage fault occurs, use dynamic braking options or switch to another L3-04 selection.
Setting 1: General-purpose Stall Prevention

The drive tries to decelerate within the set deceleration time. The drive pauses deceleration when the DC bus voltage exceeds
the Stall Prevention level and then continues deceleration when the DC bus voltage drops below that level. Stall Prevention
may be triggered repeatedly to avoid an overvoltage fault. The DC bus voltage level for Stall Prevention depends on the input
voltage setting E1-01.
Drive Input Voltage
400 V Class
575 V Class
690 V Class
Note:

Stall Prevention Level during Deceleration


750 Vdc
930 Vdc
930 Vdc

1. Do not use this setting in combination with a Dynamic Braking Resistor or other dynamic braking options. If Stall Prevention during
deceleration is enabled, it will be triggered before the braking resistor option can operate.
2. This method may lengthen the total deceleration time compared to the set value. If this is not appropriate for the application consider
using a dynamic braking option.

Figure 1.99 illustrates the function of Stall Prevention during deceleration.


Output Frequency
Deceleration characteristics
when Stall Prevention was
triggered during deceleration

Time
specified deceleration time

Figure 1.99 Stall Prevention During Deceleration

The drive adjusts the deceleration rate so the DC bus voltage is kept at the level set to parameter L3-17. This produces the
shortest possible deceleration time while protecting the motor from stalling. The selected deceleration time is disregarded and
the achievable deceleration time cannot be smaller than 1/10 of the set deceleration time.
This function uses the following parameters for adjusting the deceleration rate:
DC bus voltage gain (L3-20)
Deceleration rate calculations gain (L3-21)
Inertia calculations for motor acceleration time (L3-24)
Load inertia ratio (L3-25)
Note:

The deceleration time is not constant. Do not use Intelligent Stall Prevention in applications where stopping accuracy is a concern. Use
dynamic braking options instead.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

139

Parameter Details

Setting 2: Intelligent Stall Prevention

1.8 L: Protection Functions


Setting 3: Stall Prevention with dynamic braking option

Enables the Stall Prevention function while using a dynamic braking resistor. Overvoltage problems in the DC bus can occur
if Stall Prevention during deceleration is disabled (L3-04) in OLV and a dynamic braking option is installed. Set L3-04 to 3
to remedy this situation.
Setting 4: Overexcitation Deceleration 1

Overexcitation Deceleration 1 (increasing the motor flux) is faster than deceleration with no Stall Prevention (L3-04 = 0).
Setting 4 changes the selected decel time and functions to provide protection from an overvoltage trip. Refer to Overexcitation
Deceleration (Induction Motors) on page 155 for details.
Setting 5: Overexcitation Deceleration 2

Overexcitation Deceleration 2 slows down the motor while trying to maintain the DC bus voltage at the level set to parameter
L3-17. This function shortens the achievable deceleration time more than by using Overexcitation Deceleration 1. Setting 5
will shorten/lengthen the decel time to maintain the L3-17 bus level. Refer to Overexcitation Deceleration (Induction
Motors) on page 155 for details.

n L3-05: Stall Prevention Selection during Run


Determines how Stall Prevention works during Run. Stall Prevention during run prevents the motor from stalling by
automatically reducing the speed when a transient overload occurs while the motor is running at constant speed.
No.
L3-05
Note:

Name
Stall Prevention Selection During Run

Setting Range
0 to 2

Default
1

1. This parameter is available in V/f, V/f w/PG, and OLV/PM.


2. Stall Prevention during run is disabled when the output frequency is 6 Hz or lower regardless of the L3-05 and L3-06 settings.

Setting 0: Disabled

Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an oC or oL fault.
Setting 1: Decelerate using C1-02

If the current exceeds the Stall Prevention level set in parameter L3-06, the drive will decelerate at decel time 1 (C1-02). When
the current level drops below the value of L3-06 minus 2% for 100 ms, the drive accelerates back to the frequency reference
at the active acceleration time.
Setting 2: Decelerate using C1-04

Same as setting 1 except the drive decelerates at decel time 2 (C1-04).

n L3-06: Stall Prevention Level during Run


Sets the current level to trigger Stall Prevention during run. Depending on the setting of parameter L3-23, the level is
automatically reduced in the constant power range (speed beyond base speed).
The Stall Prevention level can be adjusted using an analog input. Refer to Multi-Function Analog Input Terminal Settings
on page 116 for details.
No.
L3-06

Name
Stall Prevention Level During Run

Setting Range
30 to 150

<1>

Default
<1>

<1> The upper limit and default for this setting is determined by C6-01 and L8-38.

n L3-23: Automatic Reduction Selection for Stall Prevention during Run


Reduces the Stall Prevention during run level in the constant power range.
No.
L3-23

Name
Automatic Reduction Selection for Stall Prevention During Run

Setting Range
0, 1

Default
0

Setting 0: Disabled

The level set in L3-06 is used throughout the entire speed range.
Setting 1: Enabled

The Stall Prevention level during run is reduced in the constant power range. The lower limit will be 40% of L3-06.

140

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

n Overvoltage Suppression Function


Suppresses overvoltage faults by decreasing the regenerative torque limit and slightly increasing the output frequency when
the DC bus voltage rises. This function can drive loads with cyclic regenerative operation, such as a punch press or other
applications that involve repetitive crank movements.
The regenerative torque limit and the output frequency are adjusted during ov suppression so that the DC bus voltage does
not exceed the level set to parameter L3-17.
Note:

1. The motor speed will exceed the frequency reference when overvoltage suppression is triggered. Consequently, overvoltage suppression
is not appropriate in applications that require a perfect match between the frequency reference and the motor speed.
2. Disable overvoltage suppression when using a braking resistor.
3. Overvoltage may still occur if there is a sudden increase to a regenerative load.
4. This function is enabled only when operating just below the maximum frequency. Overvoltage suppression does not increase the output
frequency beyond the maximum frequency. If the application requires this, increase the maximum frequency and change the base
frequency setting.

n L3-11: Overvoltage Suppression Function Selection


Enables or disables the overvoltage suppression function.
No.
L3-11

Name
Overvoltage Suppression Function Selection

Setting Range
0, 1

Default
0

Setting 0: Disabled

The regenerative torque limit and the output frequency are not adjusted. A regenerative load may trip the drive with an
overvoltage fault. Use this setting if dynamic braking options are installed.
Setting 1: Enabled

When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by decreasing the regenerative
torque limit and increasing the output frequency.

n L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention
Sets the target DC bus voltage level used by the overvoltage suppression function (L3-11 = 1), Intelligent Stall Prevention
during deceleration (L3-04 = 2).
No.
L3-17

Name
Target DC Bus Voltage for Overvoltage Suppression
and Stall Prevention

Setting Range
300 to 800 Vdc <1>

Default
740 Vdc

<1> <2>

<1> Values are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690 V class drives,
but set the value below 1040 Vdc (overvoltage protection level).
<2> This value is initialized when E1-01 is changed.

n L3-27: Stall Prevention Detection Time


Sets a delay time from when the Stall Prevention level is reached and the actual Stall Prevention function is activated.
No.
L3-27

Name
Stall Prevention Detection Time

Setting Range
0 to 5000 ms

Default
50 ms

These parameters set up the speed agree and speed detection functions that can be assigned to the multi-function output
terminals.

n L4-01, L4-02: Speed Agreement Detection Level and Detection Width


Parameter L4-01 sets the detection level for the digital output functions Speed agree 1, User-set speed agree 1, Frequency
detection 1, and Frequency detection 2.
Parameter L4-02 sets the hysteresis level for these functions.
No.
L4-01

Name
Speed Agreement Detection Level

Setting Range
0.0 to 150.0 Hz

L4-02

Speed Agreement Detection Width

0.0 to 20.0 Hz

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Default
0.0 Hz
Determined by
A1-02
141

Parameter Details

u L4: Speed Detection

1.8 L: Protection Functions


Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 103, Settings 2, 3, 4, and 5.

n L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-)
Parameter L4-03 sets the detection level for the digital output functions Speed agree 2, User-set speed agree 2, Frequency
detection 3, and Frequency detection 4.
Parameter L4-04 sets the hysteresis level for these functions.
No.
L4-03

Name
Speed Agreement Detection Level (+/-)

Setting Range
-150.0 to 150.0 Hz

L4-04

Speed Agreement Detection Width (+/-)

0.0 to 20.0 Hz

Default
0.0 Hz
Determined by
A1-02

Refer to H2-01 to H2-03: Terminal M1-M2, M3-M4, and M5-M6 Function Selection on page 103, Settings 13, 14, 15, and
16.

n L4-05: Frequency Reference Loss Detection Selection


The drive can detect a loss of an analog frequency reference from input A1, A2, or A3. Frequency reference loss is detected
when the frequency reference drops below 10% of the reference or below 5% of the maximum output frequency within 400
ms.
100%

Analog
frequency
reference

10%
400 ms

Loss of
Reference
output

OFF

ON
time

Figure 1.100 Loss of Reference Function

Set H2-01, H2-02, or H2-03 to C for a digital output to trigger when frequency reference loss occurs. Refer to Setting C:
Frequency Reference Loss on page 107 for details on setting the output function.
Parameter L4-05 selects the operation when a frequency reference loss is detected.
No.
L4-05

Name
Frequency Reference Loss Detection Selection

Setting Range
0, 1

Default
0

Setting 0: Stop

Drive follows the frequency reference (which is no longer present) and stops the motor.
Setting 1: Continue operation with reduced frequency reference

The drive will continue operation at the frequency reference value set to parameter L4-06. When the external frequency
reference value is restored, the operation is continued with the frequency reference.

n L4-06: Frequency Reference at Reference Loss


Sets the frequency reference level at which the drive runs when L4-05 = 1 and when detecting a reference loss. The value is
set as a percentage of the frequency reference before the loss was detected.
No.
L4-06

Name
Frequency Reference at Reference Loss

Setting Range
0.0 to 100.0%

Default
80.0%

n L4-07: Speed Agreement Detection Selection


Determines when frequency detection is active using parameters L4-01 through L4-04.
No.
L4-07

Name
Speed Agreement Detection Selection

Setting Range
0, 1

Default
0

Setting 0: No Detection during Baseblock


Setting 1: Detection always Enabled

142

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

u L5: Fault Restart


After a fault has occurred, Fault Restart attempts to automatically restart the motor and continue operation instead of stopping.
The drive can perform a self-diagnostic check and resume the operation after a fault has occurred. If the self-check is successful
and the cause of the fault has disappeared, the drive restarts by first performing Speed Search (Refer to b3: Speed Search on
page 27 for details).
Note:

1. The wiring sequence should remove the Forward/Reverse command when a fault is triggered and output is shut off.
2. When the Forward/Reverse command is removed, the drive can perform a self-diagnostic check and attempt to restart the fault
automatically.

WARNING! Sudden Movement Hazard. Do not use the fault restart function in lifting applications. Fault restart may cause the machine to
drop the load, which could result in death or serious injury.

The drive can attempt to restart itself following the faults listed below.
Fault
GF
LF
oC
oH1
oL1
oL2
oL3

Name
Ground Fault
Output Open Phase
Overcurrent
Drive Overheat
Motor Overload
Drive Overload
Overtorque 1

Fault
oL4
ov
PF
rH
rr
Uv1
STo

Name
Overtorque 2
DC Bus Overvoltage
Input Phase Loss
Braking Resistor Fault
Braking Transistor Fault
DC Bus Undervoltage <1>
Pull-Out Detection

<1> When L2-01 is set to 1 through 4 (continue operation during momentary power loss)

Use parameters L5-01 to L5-05 to set up automatic fault restart.


Set H2-01, H2-02, or H2-03 to 1E. to output a signal during fault restart.

n L5-01: Number of Auto Restart Attempts


Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,
the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter
reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
The drive operates normally for 10 minutes following a fault restart.
A fault is cleared manually after protective functions are triggered.
The power supply is cycled.
No.
L5-01

Name
Number of Auto Restart Attempts

Setting Range
0 to 10 Times

Default
0 Times

n L5-02: Auto Restart Fault Output Operation Selection


No.
L5-02

Name
Auto Restart Fault Output Operation Selection

Setting Range
0, 1

Parameter Details

Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.
Default
0

Setting 0: No Fault Output


Setting 1: Fault Output Is Set

n L5-04: Fault Reset Interval Time

Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.
No.
L5-04

Name
Fault Reset Interval Time

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Setting Range
0.5 to 600.0 s

Default
10.0 s

143

1.8 L: Protection Functions

n L5-05: Fault Reset Operation Selection


No.
L5-05

Name
Fault Reset Operation Selection

Setting Range
0, 1

Default
0

Setting 0: Count Successful Restarts

The drive will continuously attempt to restart. If it restarts successfully, the restart counter is increased. This operation is
repeated each time a fault occurs until the counter reaches the value set to L5-01.
Setting 1: Count Restart Attempts

The drive will attempt to restart using the time interval set to parameter L5-04. A record is kept of the number of attempts to
restart to the drive, regardless of whether those attempts were successful. When the number of attempted restarts exceeds the
value set to L5-01, the drive stops attempting to restart.

u L6: Torque Detection


The drive provides two independent torque detection functions that trigger an alarm or fault signal when the load is too heavy
(oL), or suddenly drops (UL). These functions are set up using the L6-oo parameters. Program the digital outputs as shown
below to indicate the underload or overload condition to an external device:
Note:

When overtorque occurs in the application, the drive may stop due to overcurrent (oC) or overload (oL1). To prevent the drive from stopping,
use torque detection to indicate an overload situation to the controller before oC or oL1 occur. Use undertorque detection to discover
application problems like a torn belt, a pump shutting off, or other similar trouble.

H2-01, H2-02, H2-03


Setting
B
17
18
19

Description
Torque detection 1, N.O. (output closes when overload or underload is detected)
Torque detection 1, N.C. (output opens when overload or underload is detected)
Torque detection 2, N.O. (output closes when overload or underload is detected)
Torque detection 2, N.C. (output opens when overload or underload is detected)

Figure 1.101 and Figure 1.102 illustrate the functions of overtorque and undertorque detection.
Motor current / torque
10 % hysteresis

10 % hysteresis

L6-02/05

L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO)

L6-03/06

ON

ON

Figure 1.101 Overtorque Detection Operation


Motor current / torque

10 % hysteresis

L6-02/05

L6-03/06
Torque detection 1 (NO)
or
Torque detection 2 (NO)

L6-03/06

ON

ON

Figure 1.102 Undertorque Detection Operation


Note:

144

1. The torque detection function uses a hysteresis of 10% of the drive rated output current and motor rated torque.
2. In V/f, V/f w/PG and OLV/PM, the level is set as a percentage of the drive rated output current. In OLV, CLV, AOLV/PM and CLV/
PM, the level is set as a percentage of the motor rated torque.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

n L6-01, L6-04: Torque Detection Selection 1, 2


The torque detection function is triggered when the current or torque exceed the levels set to L6-02 and L6-05 for longer than
the times set to L6-03 and L6-06. L6-01 and L6-04 select the conditions for detection and the operation that follows.
No.
L6-01
L6-04

Name
Torque Detection Selection 1
Torque Detection Selection 2

Setting Range
0 to 8
0 to 8

Default
0
0

Setting 0: Disabled
Setting 1: oL3, oL4 at speed agree (Alarm)

Overtorque detection is active only when the output speed is equal to the frequency reference (i.e., no detection during
acceleration and deceleration). The operation continues after detecting overtorque and triggering an oL3/oL4 alarm.
Setting 2: oL3, oL4 at run (Alarm)

Overtorque detection works as long as the Run command is active. The operation continues after detecting overtorque and
triggering an oL3/oL4 alarm.
Setting 3: oL3, oL4 at speed agree (Fault)

Overtorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation stops and triggers an oL3/oL4 fault.
Setting 4: oL3, oL4 at run (Fault)

Overtorque detection works as long as a Run command is active. The operation stops and triggers an oL3/oL4 fault.
Setting 5: UL3, UL4 at speed agree (Alarm)

Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation continues after detecting overtorque and triggering a UL3/UL4 alarm.
Setting 6: UL3, UL4 at Run (Alarm)

Undertorque detection works as long as the Run command is active. The operation continues after detecting overtorque and
triggering a UL3/UL4 alarm.
Setting 7: UL3, UL4 at Speed Agree (Fault)

Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during
acceleration and deceleration. The operation stops and triggers a UL3/UL4 fault.
Setting 8: UL3, UL4 at run (Fault)

Undertorque detection works as long as a Run command is active. The operation stops and triggers a UL3/UL4 fault.

n L6-02, L6-05: Torque Detection Level 1, 2


These parameters set the detection levels for torque detection functions 1 and 2. In V/f and OLV/PM control modes, these
levels are set as a percentage of the drive rated output current. In vector control modes, these levels are set as a percentage of
the motor rated torque.

Note:

Name
Torque Detection Level 1
Torque Detection Level 2

Setting Range
0 to 300%
0 to 300%

Default
150%
150%

The torque detection level 1 (L6-02) can also be supplied by an analog input terminal set to H3-oo = 7. Here, the analog value has priority
and the setting in L6-02 is disregarded. Torque detection level 2 (L6-05) cannot be set by an analog input.

n L6-03, L6-06: Torque Detection Time 1, 2


These parameters determine the time required to trigger an alarm or fault after exceeding the levels in L6-02 and L6-05.
No.
L6-03
L6-06

Name
Torque Detection Time 1
Torque Detection Time 2

Setting Range
0.0 to 10.0 s
0.0 to 10.0 s

Default
0.1 s
0.1 s

n Mechanical Weakening Detection


This function detects the mechanical weakening of a machine that leads to overtorque or undertorque situations after a set
machine operation time has elapsed.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

No.
L6-02
L6-05

145

1.8 L: Protection Functions


The function is activated in the drive when the cumulative operation counter U4-01 exceeds the time set to parameter L6-11.
Mechanical Weakening Detection uses the torque detection 1 settings (L6-01, L6-02, L6-03) and triggers an oL5 fault when
overtorque or undertorque occurs in the speed range determined by parameter L6-08 and L6-09. The oL5 operation is set by
parameter L6-08.
Set H2-oo to 22 to output a signal for Mechanical Weakening Detection.

n L6-08: Mechanical Weakening Detection Operation


Sets the speed range to detect mechanical weakening and the action to take when mechanical weakening is detected.
No.
L6-08

Name
Mechanical Weakening Detection Operation

Setting Range
0 to 8

Default
0

Setting 0: Disabled
Setting 1: Continue running if the speed is greater than L6-09 (Signed) (Alarm)

Detection when the speed is above L6-09 (signed). Operation continues and triggers an oL5 alarm after detection.
Setting 2: Continue running if the speed is greater than L6-09 (Alarm)

Detection when the speed is above L6-09 (unsigned). Operation continues and triggers an oL5 alarm after detection.
Setting 3: Stop when motor speed is greater than L6-09 (Signed)

Detection when the speed is above L6-09 (signed). Operation stops and triggers an oL5 fault after detection.
Setting 4: Stop when Motor Speed is Greater than L6-09

Detection when the speed is above L6-09 (unsigned). Operation stops and triggers an oL5 fault after detection.
Setting 5: Continue running if the speed is less than L6-09 (Signed) (Alarm)

Detection when the speed is below L6-09 (signed). Operation continues and triggers an oL5 alarm after detection.
Setting 6: Continue running if the speed is less than L6-09 (Alarm)

Detection when the speed is below L6-09 (unsigned). Operation continues and triggers an oL5 alarm after detection.
Setting 7: Stop when Motor Speed is less than L6-09 (Signed)

Detection when the speed is below L6-09 (signed). Operation stops and triggers an oL5 fault after detection.
Setting 8: Stop when motor speed is less than L6-09

Detection when the speed is below L6-09 (unsigned). Operation stops and triggers an oL5 fault after detection.

n L6-09: Mechanical Weakening Detection Speed Level


Sets the speed level for Mechanical Weakening Detection as a percentage of the maximum frequency. If L6-08 is set for
unsigned speed detection (L6-08 = 2, 4, 6, 8), the absolute value of L6-09 is used (negative settings are treated as positive
values).
No.
L6-09

Name
Mechanical Weakening Detection Speed Level

Setting Range
-110.0 to 110.0%

Default
110%

n L6-10: Mechanical Weakening Detection Time


Sets the time permitted for the situation selected in parameter L6-08 to arise before detecting mechanical weakening.
No.
L6-10

Name
Mechanical Weakening Detection Time

Setting Range
0.0 to 10.0 s

Default
0.1 s

n L6-11: Mechanical Weakening Detection Start Time


Sets the cumulative drive operation time at which Mechanical Weakening Detection is activated. The function activates when
U4-01 reaches the L6-11 value.
No.
L6-11

146

Name
Mechanical Weakening Detection Start Time

Setting Range
0 to 65535 h

Default
0h

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

u L7: Torque Limit


The torque limit function limits the torque in each of the four quadrants individually to protect machinery in OLV, CLV,
AOLV/PM, and CLV/PM control modes. Set the limit through parameters, analog inputs, or by switching a digital output
programmed for During torque limit (H2-01, H2-02, H2-03 = 30) when the drive is operating at the torque limit.

n Setting Torque Limits


Parameters L7-01 to L7-04 define the torque limits for each of the four operation quadrants. it is also possible to use Analog
inputs to define a general limit for all operation conditions (H3-02, H3-06, H3-10 = 15) or to set separate limits for each
operation condition (H3-02, H3-06, H3-10 = 10, 11, or 12). Figure 1.103 shows limit setting is applied in each quadrant.
If two limit values are defined for the same operation conditions, the drive will use the lower value.
Note:

The maximum output torque is ultimately limited by the drive output current (max. 150% of drive rated current in HD, 120% in ND). Output
torque will not exceed the drive rated current limit even if the torque limits are set to higher values.

Example: If parameter L7-01 = 130%, L7-02 to L7-04 = 200%, and an analog input sets a general torque limit of 150% (H3-02,
H3-06, H3-10 = 15), then the torque limit will be 130% in quadrant 1, but 150% in the other quadrants.
Positive torque reference
REV run regenerative

FWD run motoring

10: Positive Torque Limit


12: Regenerative Torque Limit
15: Torque Limit
Parameter L7-04

10: Positive Torque Limit


15: Torque Limit
Parameter L7-01

REV motor rotation

Quadrant 2

Quadrant 1

Quadrant 3

Quadrant 4

FWD motor rotation


11: Negative Torque Limit
12: Regenerative Torque Limit
15: Torque Limit
Parameter L7-02
FWD run regenerative

11: Negative Torque Limit


15: Torque Limit
Parameter L7-03
REV run motoring
Negative torque reference

Figure 1.103 Torque Limit Parameters and Analog Input Settings

n L7-01 to L7-04: Torque Limits


These parameters set the torque limits in each operation mode.
No.
L7-01
L7-02
L7-03
L7-04
Note:

Name
Forward Torque Limit
Reverse Torque Limit
Forward Regenerative Torque Limit
Reverse Regenerative Torque Limit

Setting Range
0 to 300%
0 to 300%
0 to 300%
0 to 300%

Default
200%
200%
200%
200%

If the multi-function analog input is programmed for 10: Forward torque limit, 11: Reverse torque limit, 12: Regenerative torque
limit, or 15: General torque limit, the drive uses the lowest value from L7-01 through L7-04, or analog input torque limit.

Sets the integral time constant for the torque limit function. Decrease the setting for faster torque limit response. Increase the
setting if oscillation occurs when operating at the torque limit.
No.
L7-06

Name
Torque Limit Integral Time Constant

Setting Range
5 to 10000 ms

Default
200 ms

n L7-07: Torque Limit Control Method Selection during Accel/Decel


Selects the function of torque limit during acceleration and deceleration.
No.
L7-07

Name
Torque Limit Control Method Selection during Accel/Decel

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Setting Range
0, 1

Parameter Details

n L7-06: Torque Limit Integral Time Constant

Default
0

147

1.8 L: Protection Functions


Setting 0: Proportional control

The torque limit function works with P control during accel and decel, and switches to I control at constant speed. Use this
setting when accelerating or decelerating to the desired speed has priority over the torque limit during speed changes.
Setting 1: Integral control

The torque limit function always uses I control. Use this setting when a highly accurate torque limit is required, even during
speed changes. Using this function may increase the acceleration time, or prevent the motor speed from reaching the frequency
reference if the torque limit is reached first.

n L7-16: Torque Limit Process at Start


Assigns a time filter to allow the torque limit to build at start.
No.
L7-16

Name
Torque Limit Process at Start

Setting Range
0, 1

Default
1

Setting 0: Disabled

Torque limit is created at start without a delay time. Disable L7-16 to maximize the response time when the application requires
sudden acceleration or deceleration at start.
Setting 1: Enabled

A delay time of 64 ms is added to allow the torque limit to build at start.

n L7-30: Regenerative Torque Limit Mode Selection


Special function of regenerative Torque limit for Omron (same as G5HHP).
No.
L7-30

Name
Regenerative Torque Limit Mode Selection

Setting Range
0, 1

Default
0

Setting 0: Standard mode

Torque limit from all analogs and communications effective.


Setting 1: Independent mode

Only L7-03, L7-04, and H3-oo= 12H (regenerative torque limit) are effective.

u L8: Drive Protection


n L8-02: Overheat Alarm Level
Sets the overheat alarm (oH) detection level.
The drive outputs an alarm when the heatsink temperature exceeds the overheat alarm level. If the drive is set to continue
operation after this alarm occurs (L8-03 = 4) and the temperature reaches the overheat fault level, the drive will trigger an oH1
fault and stop operation.
When an output terminal is set for the oH pre-alarm (H2-oo = 20), the switch will close when the heatsink temperature rises
above L8-02.
No.

Name

Setting Range

L8-02

Overheat Alarm Level

50 to 150 C

Default
Determined by
C6-01 and o2-04

Setting Range
0 to 4

Default
3

n L8-03: Overheat Pre-Alarm Operation Selection


Sets the operation when an overheat pre-alarm is detected.
Note:

Change L8-03 setting only when necessary.

No.
L8-03

Name
Overheat Pre-Alarm Operation Selection

Setting 0: Ramp to stop

If an overheat alarm occurs, the drive decelerates to stop using the currently selected deceleration time. If a digital output is
programmed for fault (H2-oo = E), this output will be triggered.

148

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions


Setting 1: Coast to stop

If an overheat alarm occurs, the drive switches off the output and the motor coasts to stop. If a digital output is programmed
for fault (H2-oo = E), this output will be triggered.
Setting 2: Fast Stop

If an overheat alarm occurs, the drive decelerates to stop using the Fast Stop time (C1-09). If a digital output is programmed
for fault (H2-oo = E), this output will be triggered.
Setting 3: Alarm only

If an overheat alarm occurs, an alarm is output and the drive continues operation.
Setting 4: Operation with reduced speed

If an overheat alarm occurs, the operation continues with the speed reduced to the level set to parameter L8-19. If the oH alarm
is still present after 10 s, the speed is reduced again. The amount of speed reduction depends on how often the alarm repeats.
If the oH alarm disappears while the drive is operating at a reduced speed, the drive will switch to the previous speed in 10 s
increments until reaching base frequency. Figure 1.104 explains the operation with reduced speed during an oH alarm. A
digital output programmed for 4D is switched when the oH alarm is still active after ten reduction cycles.
Output frequency
10 s

10 s

10 s

10 s

10 s

10 s

10 s

fref

fref (L8-19)
fref (L8-19)2

oH
Alarm
oH
Alarm

Reset oH
Alarm

Reset oH
Alarm

oH
Alarm

fref (L8-19)3

etc.

oH
Alarm

fref (L8-19)4
time

oH alarm number
Digital ouput (4D)

Figure 1.104 Output Frequency Reduction During Overheat Alarm

n L8-19: Frequency Reduction Rate during Overheat Pre-Alarm


No.
L8-19

Name
Frequency Reduction Rate During Overheat Pre-Alarm

Setting Range
0.1 to 0.9

Default
0.8

Setting Range
0, 1

Default
1

Parameter Details

Specifies the output frequency reduction when L8-03 is set to 4 and an oH alarm is present. Set as a factor of the maximum
output frequency.

n L8-05: Input Phase Loss Protection Selection


Enables or disables the input phase loss detection.
No.
L8-05

Name
Input Phase Loss Protection Selection

Setting 0: Disabled
Setting 1: Enabled

Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage
imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
The drive is decelerating.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

149

1.8 L: Protection Functions


No Run command is active.
Output current is less than or equal to 30% of the drive rated current.

n L8-07: Output Phase Loss Protection Selection


Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.
Note:

1. Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable
this parameter in such cases.
2. Output phase loss detection is not possible when the drive is running a PM motor with light load.

No.
L8-07

Name
Output Phase Loss Protection Selection

Setting Range
0 to 2

Default
1

Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost

An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.
Setting 2: Fault when Two Phases Are Lost

An output phase loss fault (LF) is triggered when two output phases are lost. The output shuts off and the motor coasts to stop.

n L8-09: Output Ground Fault Detection Selection


Enables or disables the output ground fault detection.
No.
L8-09

Name
Output Ground Fault Detection Selection

Setting Range
0, 1

Default
1

Setting 0: Disabled

Ground faults are not detected.


Setting 1: Enabled

A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.

n L8-10: Heatsink Cooling Fan Operation Selection


Selects the heatsink cooling fan operation.
No.
L8-10

Name
Heatsink Cooling Fan Operation Selection

Setting Range
0, 1

Default
0

Setting 0: Run with timer

The fan is switched on when a Run command is active and switched off with the delay set to parameter L8-11 after releasing
the Run command. This setting extends the fan lifetime.
Setting 1: Run always

The fan runs when power is supplied to the drive.

n L8-11: Heatsink Cooling Fan Off-Delay Time


Sets the cooling fan switch off-delay time if parameter L8-10 is set to 0.
No.
L8-11

Name
Heatsink Cooling Fan Off-Delay Time

Setting Range
0 to 300 s

Default
60 s

n L8-12: Ambient Temperature Setting


This setting eliminates the need to reduce the drive rated current when the temperature where the drive is mounted is above
the specified values.
No.
L8-12

150

Name
Ambient Temperature Setting

Setting Range
-10 to 50 C

Default
40 C

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions

n L8-15: oL2 Characteristics Selection at Low Speeds


Selects whether the drive overload capability (oL fault detection level) is reduced at low speeds to prevent premature output
transistor failures.
Note:

Contact Yaskawa for consultation before disabling this function. Disabling this function may shorten the operating life of the power
transistors.

No.
L8-15

Name
oL2 Characteristics Selection at Low Speed

Setting Range
0, 1

Default
1

Setting 0: Protection Disabled at Low Speed

The overload protection level is not reduced. Frequently operating the drive with high output current at low speed can lead to
premature drive faults.
Setting 1: Protection Enabled at Low Speed

The overload protection level (oL2 fault detection level) is automatically reduced at speeds below 6 Hz. At zero speed, the
overload is derated by 50%.

n L8-18: Software Current Limit Selection


Enables or disables the Software Current Limit (CLA) protection function to prevent main circuit transistor failures caused
by high current.
Note:

Do not change this setting unless absolutely necessary. Leave the Software CLA enabled for proper drive protection and operation.

No.
L8-18

Name
Software Current Limit Selection

Setting Range
0, 1

Default
0

Setting 0: Software CLA Disabled

The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.
Setting 1: Software CLA Enabled

When the Software CLA current level is reached, the drive reduces the output voltage to reduce the current. Normal operation
continues when the current level drops below the Software CLA level.

n L8-32: Main Contactor and Cooling Fan Power Supply Failure Selection
Determines drive operation when a FAn fault occurs.
No.
L8-32

Name
Main Contactor and Cooling Fan Power Supply Failure Selection

Setting Range
0 to 4

Default
1

Setting 0: Ramp to stop

The drive stops the motor using the deceleration time set in parameter C1-02.
Setting 1: Coast to stop

The drive output is switched off and the motor coasts to a stop.
Setting 2: Fast stop

The drive stops the motor using the Fast stop time set in parameter C1-09.
Setting 3: Alarm only
Parameter Details

The operation is continued and a FAn alarm is displayed on the digital operator.
Setting 4: Operation with reduced speed

The operation is continued, but the speed is reduced to the level set in parameter L8-19.
Note:

FAn is detected as an error when Settings 0 or 2 are selected; it is detected as an alarm when Settings 3 or 4 are selected.

n L8-38: Carrier Frequency Reduction Selection


Selects the operation of the carrier frequency reduction function. Reduces the carrier frequency when the output current exceeds
a certain level. This temporarily increases the overload capability (oL2 detection), allowing the drive to run through transient
load peaks without tripping.
Note:

This function cannot be used in AOLV/PM.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

151

1.8 L: Protection Functions


No.

Name

Setting Range

L8-38

Carrier Frequency Reduction Selection

0 to 2

Default
Determined by
A1-02, C6-01 and
o2-04

Setting 0: Disabled

No carrier frequency reduction at high current.


Setting 1: Enabled for output frequencies below 6 Hz

The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive
returns to the normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.
Setting 2: Enabled for entire frequency range

The carrier frequency is reduced at the following speeds:


Below 6 Hz when the current exceeds 100% of the drive rated current.
Above 7 Hz when the current exceeds 112% of the drive rated current.
The drive uses the delay time set in parameter L8-40 and a hysteresis of 12% when switching the carrier frequency back to
the set value.

n L8-40: Carrier Frequency Reduction Off-Delay Time


Sets a hold time before returning to the original carrier frequency setting after the carrier frequency has been temporarily
derated as determined by L8-38. The carrier frequency reduction function is disabled when this value is 0.00 s.
No.

Name

Setting Range

L8-40

Carrier Frequency Reduction Off-Delay Time

0.00 to 2.00 s

Default
Determined by
A1-02

n L8-41: High Current Alarm Selection


Triggers a high current alarm (HCA) when the output current exceeds 150% of the drive rated current.
No.
L8-41

Name
High Current Alarm Selection

Setting Range
0, 1

Default
0

Setting 0: Disabled

No alarm is detected.
Setting 1: Enabled

An alarm is triggered when the output current exceeds 150% of the drive rated current. A digital output set for an alarm
(H2-oo = 10) will close.

n L8-78: Power Unit Output Phase Loss Protection


Protects the power unit from phase loss.
Note:

This parameter is only available in models CIMR-Ao4A0930, 4A1200, and A1000 HHP.

No.
L8-78

Name
Power Unit Output Phase Loss Protection

Setting Range
0, 1

Default
1

Setting Range
0 to 5

Default
1

Setting 0: Disabled
Setting 1: Enabled

n L8-86: Detection Selection when Panel Fan Fails


Detects the loss of the drive panel fan by the panel fan input.
Note:

No.
L8-86

152

Settings 3 or 4 reduce inverter O/L level from 100% to 80%

Name
Detection selection when Panel Fan Fails

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.8 L: Protection Functions


Setting 0: Ramp Stop (Fault)
Setting 1: Coast Stop (Fault)
Setting 2: Fast Stop (Fault)
Setting 3: Continue Running (Alarm)
Setting 4: Continue Running at L8-19 Speed
Setting 5: Disabled

n L8-87: Detection Selection when Diode Converter Fans Fail


Detects the loss of the Diode Converter fans by the fan control input.
Note:

No.
L8-87

Settings 3 or 4 reduce drive O/L level from 100% to 80%

Name
Detection Selection when Diode Converter Fans Fail

Setting Range
0 to 5

Default
1

Parameter Details

Setting 0: Ramp Stop (Fault)


Setting 1: Coast Stop (Fault)
Setting 2: Fast Stop (Fault)
Setting 3: Continue Running (Alarm)
Setting 4: Continue Running at L8-19 Speed
Setting 5: Disabled

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

153

1.9 n: Special Adjustments

1.9

n: Special Adjustments

These parameters control a variety of specialized adjustments and functions, including Hunting Prevention, AFR Control,
High Slip Braking and resistance between motor lines.

u n1: Hunting Prevention


Hunting Prevention prevents the drive from hunting as a result of low inertia and operating with light load. Hunting often
occurs with a high carrier frequency and an output frequency below 30 Hz.

n n1-01: Hunting Prevention Selection


Enables or disables the Hunting Prevention function.
Note:

This function is available only when using V/f Control. Disable Hunting Prevention when drive response is more important than suppressing
motor oscillation. This function may be disabled without problems in applications with high inertia loads or relatively heavy loads.

No.
n1-01

Name
Hunting Prevention Selection

Setting Range
0, 1

Default
1

Setting Range
0.00 to 2.50

Default
1.00

Setting 0: Disabled
Setting 1: Enabled

n n1-02: Hunting Prevention Gain Setting


Sets the gain for the Hunting Prevention Function.
No.
n1-02

Name
Hunting Prevention Gain Setting

Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
If the motor vibrates while lightly loaded and n1-01 = 1, increase the gain by 0.1 until vibration ceases.
If the motor stalls while n1-01 = 1, decrease the gain by 0.1 until the stalling ceases.

n n1-03: Hunting Prevention Time Constant


Determines the responsiveness of the Hunting Prevention function (affects the primary delay time for Hunting Prevention).
No.

Name

Setting Range

n1-03

Hunting Prevention Time Constant

0 to 500 ms

Default
Determined by
o2-04

Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
Increase this value for applications with a large load inertia. A higher setting leads to slower response, which can result in
oscillation at lower frequencies.
Lower this setting if oscillation occurs at low speed.

n n1-05: Hunting Prevention Gain while in Reverse


This parameter functions the same as n1-02, except it is used when rotating in reverse. See the explanation for n1-02.
Note:

n1-02 is enabled for forward and reverse operation when n1-05 = 0.0 ms.

No.
n1-05

Name
Hunting Prevention Gain while in Reverse

Setting Range
0.00 to 2.50

Default
0.00

u n2: Speed Feedback Detection Control (AFR) Tuning


These parameters help achieve speed stability when a load is suddenly applied or removed.
Note:

Properly set all motor parameters or perform Auto-Tuning before making changes to the AFR parameters.

n n2-01: AFR Gain


Sets the internal speed feedback detection control gain in the AFR.

154

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.9 n: Special Adjustments


No.
n2-01

Name
AFR Gain

Setting Range
0.00 to 10.00

Default
1.00

Although this parameter rarely needs to be changed, it may require adjustment in the following situations:
If hunting occurs, increase the setting value in steps of 0.05 while checking the response.
If response is low, decrease the setting value in steps of 0.05 while checking the response.

n n2-02, n2-03: AFR Time Constant 1, 2


Parameter n2-02 sets the time constant normally used by AFR.
Parameter n2-03 sets the time constant during Speed Search or regenerative operation.
No.
n2-02
n2-03
Note:

Name
AFR Time Constant 1
AFR Time Constant 2

Setting Range
0 to 2000 ms
0 to 2000 ms

Default
50 ms
750 ms

Setting parameter n2-02 higher than n2-03 will trigger an oPE08 error.

Although these parameters rarely need to be changed, they may require adjustment in the following situations:
If hunting occurs, increase n2-02. If response is low, decrease it.
Increase n2-03 if overvoltage occurs with high inertia loads at the end of acceleration or with sudden load changes.
If setting n2-02 to a higher value, increase C4-02 (Torque Compensation Delay Time Constant 1) proportionally.
If setting n2-03 to a higher value, increase C4-06 (Torque Compensation Delay Time Constant 2) proportionally.

u n3: High Slip Braking (HSB) and Overexcitation Braking


n High Slip Braking (V/f)
HSB works in V/f Control only and decreases the stopping time compared to normal deceleration without using dynamic
braking options. HSB reduces the output frequency in large steps to stop the motor and produce a high slip, which dissipates
the regenerative energy created from decelerating the load in the motor windings. Due to the increased temperature of the
motor windings, do not use HSB to frequently stop the motor. The duty cycle should be around 5% or lower.
Notes on using High Slip Braking

The set deceleration time is ignored during HSB. Use Overexcitation Deceleration 1 (L3-04 = 4) or a dynamic braking option
to stop the motor within a specified time.
Braking time varies based on the load inertia and motor characteristics.
Enabling HSB and KEB Ride-Thru simultaneously will trigger an oPE03 error.
HSB must be triggered by a digital input set to H1-oo = 68. After the HSB command is given, the drive will not restart
until the motor is completely stopped and the Run command is cycled.

n Overexcitation Deceleration (Induction Motors)


Increases the flux during deceleration and allows shorter deceleration time settings without the use of a braking resistor.
Enabled by setting L3-04 to 4 or 5. Refer to L3-04: Stall Prevention Selection during Deceleration on page 139.
Frequently applying Overexcitation Deceleration raises the motor temperature because regenerative energy is mainly
dissipated as heat in the motor. In cases where frequent application is required, make sure the motor temperature does not
exceed the maximum allowable value or consider using a braking resistor option in lieu of Overexcitation Deceleration.
During Overexcitation Deceleration 2, Hunting Prevention in V/f Control and torque limits in OLV Control are disabled.
Do not use Overexcitation Deceleration in combination with a braking resistor option.
Overexcitation Deceleration can be used in OLV and CLV, but it lowers the accuracy of Torque Control and braking
efficiency. It can be most efficiently used in a V/f Control.
Overexcitation Deceleration cannot be used with PM motors.
Parameter Adjustments

Use parameters n3-13 through n3-23 to adjust Overexcitation Deceleration.


When repetitive or long Overexcitation Deceleration causes motor overheat, lower the overexcitation gain (n3-13) and reduce
the overslip suppression current level (n3-21).
During Overexcitation Deceleration 1 (L3-04 = 4), the drive decelerates at the active deceleration time (C1-02, C1-04, C1-06,
or C1-08). Set this time so no overvoltage (ov) fault occurs.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

155

Parameter Details

Notes on Overexcitation Deceleration

1.9 n: Special Adjustments


During Overexcitation Deceleration 2 (L3-04 = 5), the drive decelerates using the active deceleration time while adjusting
the deceleration rate to keep the DC bus voltage at the level set to L3-17. The actual stopping time will be longer or shorter
than the set deceleration time depending on the motor characteristics and the load inertia. Increase the deceleration time if
overvoltage occurs (ov).
Entering a Run command during Overexcitation Deceleration cancels overexcitation operation and the drive reaccelerates
to the specified speed.

n n3-13: Overexcitation Deceleration Gain


Multiplies a gain to the V/f pattern output value during Overexcitation Deceleration to determine the level of overexcitation.
The drive returns to the normal V/f value after the motor has stopped or when it is accelerating to the frequency reference.
No.
n3-13

Name
Overexcitation Deceleration Gain

Setting Range
1.00 to 1.40

Default
1.10

The optimum setting for n3-13 depends on the motor flux saturation characteristics.
Gradually increase the gain to 1.25 to 1.30 to improve the braking power of Overexcitation Deceleration.
Lower n3-13 when flux saturation characteristics cause overcurrent. A high setting sometimes causes overcurrent (oC),
motor overload (oL1), or drive overload (oL2). Lowering n3-21 can also help remedy these problems.

n n3-21: High Slip Suppression Current Level


If the motor current exceeds the value set to n3-21 during Overexcitation Deceleration due to flux saturation, the drive
automatically reduces the overexcitation gain. Parameter n3-21 is set as a percentage of the drive rated current.
Set this parameter to a relatively low value to optimize deceleration. If overcurrent, oL1, or oL2 occur during Overexcitation
Deceleration, reduce the high slip suppression current level.
No.
n3-21

Name
High Slip Suppression Current Level

Setting Range
0 to 150%

Default
100%

n n3-23: Overexcitation Operation Selection


Limits the Overexcitation Deceleration operation selected in parameter L3-04 to forward only or reverse only.
No.
n3-23

Name
Overexcitation Operation Selection

Setting Range
0 to 2

Default
0

Setting 0: Overexcitation Operation as Selected in L3-04 in Forward and Reverse Direction


Setting 1: Overexcitation Operation as Selected in L3-04 in Forward Direction Only
Setting 2: Overexcitation Operation as Selected in L3-04 in Reverse Direction Only

156

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.10 o: Operator Related Settings

1.10 o: Operator Related Settings


These parameters control the various functions, features, and display of the digital operator.

u o1: Digital Operator Display Selection


These parameters determine the data display on the digital operator.

n o1-01: Drive Mode Unit Monitor Selection


The frequency reference display appears when the drive is powered up. Pressing the up arrow key will display the following
data: frequency reference rotational direction output frequency output current o1-01 selection.
Parameter o1-01 selects the content of the last monitor in this sequence.
No.

Name

o1-01

Drive Mode Unit Monitor Selection

Setting Range
104 to 813
U1-04 (Control Mode) to
U8-13 (DWEZ Custom
Monitor 3) <1>

Default
106 (U1-06)

<1> U2-oo and U3-oo parameters cannot be selected.

n o1-02: User Monitor Selection after Power Up


Selects which monitor parameter is displayed upon power up by entering the 1- oo part of U1-oo. Certain monitors are
not available in some control modes. Refer to U: Monitor Parameters on page 166 for a list of monitors.
No.
o1-02

Name
User Monitor Selection after Power Up

Setting Range
1 to 5

Default
1

Setting 1: Frequency reference (U1-01)


Setting 2: Motor direction
Setting 3: Output frequency (U1-02)
Setting 4: Output current (U1-03)
Setting 5: User-selected monitor (set by o1-01)

n o1-03: Digital Operator Display Selection


Sets the units used to display the frequency reference and output frequency. Set o1-03 to 3 for user-set units before setting
parameters o1-10 and o1-11.
No.

Name

Setting Range

o1-03

Digital Operator Display Selection

0 to 3

Default
Determined by
A1-02

Setting 1: 0.01% units (100% = max. output frequency)


Setting 2: r/min units (calculated by the max output frequency and the no. of motor poles)
Setting 3: User-set units (use o1-10, o1-11)

Set the value used for the maximum frequency reference to o1-10. Set the placement of the decimal point in this number to
o1-11.
For example, to have the maximum output frequency displayed as 100.00, set o1-10 = 1000 and o1-11 = 2 (i.e., 1000 with
2 decimal points).
Note:

1. Parameter o1-03 allows the programmer to change the units used in the following parameters and monitors:
U1-01: frequency reference
U1-02: output frequency
U1-05: motor speed
U1-16: output frequency after softstarter (accel/decel ramp generator)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

157

Parameter Details

Setting 0: 0.01 Hz units

1.10 o: Operator Related Settings


d1-01 to d1-17: frequency references
2. Setting o1-03 to 2 requires entering the number of motor poles to E2-04, E4-04, and E5-04.

n o1-04: V/f Pattern Display Unit


Note:

PM motor control modes are not available in A1000 HHP drive models.

Determines the units used for the frequency reference when setting parameters that create the V/f pattern: E1-04, E1-06, E1-09,
E1-11, and E2-04. For motor 2, this includes parameters E3-04, E3-06, E3-07, E3-09, and E3-11. Enabled only in vector
control modes (CLV, AOLV/PM, CLV/PM).
No.
o1-04

Name
V/f Pattern Display Unit

Setting Range
0, 1

Default
0

Default
Determined by
o1-03

Setting 0: Hertz
Setting 1: r/min
Note:

For motor 2, o1-04 can only be set to 0 for Hertz.

n o1-10: User-Set Display Units Maximum Value


Determines the display value that is equal to the maximum output frequency.
No.

Name

Setting Range

o1-10

User-Set Display Units Maximum Value

1 to 60000

n o1-11: User-Set Display Units Decimal Display


Determines how many decimal points should be used to set and display the frequency reference.
No.

Name

Setting Range

o1-11

User-Set Display Units Decimal Display

0 to 3

Default
Determined by
o1-03

Setting 0: No Decimal Point


Setting 1: One Decimal Point
Setting 2: Two Decimal Points
Setting 3: Three Decimal Points

u o2: Digital Operator Keypad Functions


These parameters determine the functions assigned to the operator keys.

n o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection


Determines whether the LO/RE key on the digital operator will be enabled for switching between LOCAL and REMOTE.
No.
o2-01

Name
LO/RE Key Function Selection

Setting Range
0, 1

Default
1

Setting 0: Disabled

The LO/RE key is disabled.


Setting 1: Enabled

The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is
selected, the LED indicator on the LO/RE key will light up.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07. Table 1.42 lists the setting combinations for o2-01 and b1-07.
Table 1.42 LO/RE Key and b1-07

o2-01
0

158

b1-07
0
1

Switch from LOCAL to REMOTE


Not possible
Not possible

Switch from REMOTE to LOCAL


Not possible
Not possible

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.10 o: Operator Related Settings


o2-01

b1-07
0

1
1

Switch from LOCAL to REMOTE


Switch from REMOTE to LOCAL
Will not run until a new Run command is
Run not possible
entered.
If a Run command is entered, the drive will start
running as soon as the LO/RE key is pushed to Run not possible
change from LOCAL to REMOTE.

n o2-02: STOP Key Function Selection


Determines if the STOP key on the digital operator will stop drive operation when the drive is controlled from a remote source
(i.e., not from digital operator).
No.
o2-02

Name
STOP Key Function Selection

Setting Range
0, 1

Default
1

Setting 0: Disabled
Setting 1: Enabled

The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle
the Run command to restart the drive if the drive has been stopped by pressing the STOP key.

n o2-03: User Parameter Default Value


After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,
parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters
to the user-set default values. Refer to A1-03: Initialize Parameters on page 11 for details on drive initialization.
No.
o2-03

Name
User Parameter Default Value

Setting Range
0 to 2

Default
0

Setting 0: No Change (Awaiting Command)


Setting 1: Set User Initialize Values

The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values

All user-set defaults for User Initialize are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and
returns the display to 0.

n o2-04: Drive Model Selection


Set this parameter when replacing the control board or the terminal board. Refer to Defaults by Drive Model and Duty Rating
ND/HD on page 304 for information on drive model selection.
NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.

No.

Name

Setting Range

o2-04

Drive Model Selection

Change o2-04 setting only when necessary.

n o2-05: Frequency Reference Setting Method Selection


Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in the
Drive Mode.
No.
o2-05

Name
Frequency Reference Setting Method Selection

Setting Range
0, 1

Default
0

Setting 0: ENTER key required

The ENTER key must be pressed every time the frequency reference is changed using the digital operator for the drive to
accept the change.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

Note:

Default
Determined by
drive capacity

159

1.10 o: Operator Related Settings


Setting 1: ENTER key not required

The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital operator.
The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after remaining unchanged
for 5 seconds.

n o2-06: Operation Selection when Digital Operator is Disconnected


Determines whether the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is set
to 0. When the operator is reconnected, the display will indicate that it was disconnected.
No.
o2-06

Name
Digital Operator Disconnection Operation

Setting Range
0, 1

Default
1

Setting 0: Continue operation

The operation continues.


Setting 1: Trigger a fault

The operation stops and triggers an oPr fault. The motor coasts to stop.

n o2-07: Motor Direction at Power Up when Using Operator


Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the digital
operator.
Note:

This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).

No.
o2-07

Name
Motor Direction at Power Up when Using Operator

Setting Range
0, 1

Default
0

Setting 0: Forward
Setting 1: Reverse

u o3: Copy Function


These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the
memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, and
same control mode setting. Refer to Copy Function Related Displays on page 216 for a description of errors and displays.

n o3-01: Copy Function Selection


Instructs the drive to Read, Write, or Verify parameter settings.
No.
o3-01

Name
Copy Function Selection

Setting Range
0 to 3

Default
0

Setting 0: Copy Select (no function)


Setting 1: INV --> OP READ

Copies all parameters from the drive to the digital operator.


Note:

The copy protection for the digital operator is enabled by default. Set o3-01 to 1 to unlock copy protection.

Setting 2: OP --> INV WRITE

Copies all parameters from the digital operator to the drive.


Setting 3: OP<-->INV VERIFY

Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.

n o3-02: Copy Allowed Selection


Allows and restricts the use of the Copy function.
No.
o3-02

160

Name
Copy Allowed Selection

Setting Range
0, 1

Default
0

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.10 o: Operator Related Settings


Setting 0: Disabled
Setting 1: Enabled

u o4: Maintenance Monitor Settings


n o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note:

The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative operation time counter to 300 h. 300 h will also
be displayed in monitor U4-01.

No.
o4-01

Name
Cumulative Operation Time Setting

Setting Range
0 to 9999 h

Default
0h

n o4-02: Cumulative Operation Time Selection


Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in monitor U4-01.
No.
o4-02

Name
Cumulative Operation Time Selection

Setting Range
0, 1

Default
0

Setting 0: Power on time

The drive logs the time it is connected to a power supply, regardless of whether the motor is running.
Setting 1: Run time

The drive logs the time that the output is active including when the Run command is active (even if the motor is not rotating)
and when there is voltage output.

n o4-03: Cooling Fan Operation Time Setting


Sets the value for how long the cooling fan has been operating. This value can be viewed in monitor U4-03. Parameter o4-03
also sets the base value used for the cooling fan maintenance, which is displayed in U4-04. Reset this parameter to 0 after
replacing the cooling fan.
Note:

No.
o4-03

1. The value in o4-03 increases after every 10 hours of use. A setting of 30 will set the cooling fan operation time counter to 300 h. 300
will be displayed in monitor U4-03.
2. The cooling fan may require maintenance at an earlier date in harsher environments.

Name
Cooling Fan Operation Time Setting

Setting Range
0 to 9999 h

Default
0h

n o4-05: Capacitor Maintenance Setting


Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the DC bus capacitors.
Note:

No.
o4-05

The actual maintenance time will depend on the environment where the drive is used.

Name
Capacitor Maintenance Setting

Setting Range
0 to 150%

Default
0%
Parameter Details

n o4-07: DC Bus Pre-Charge Relay Maintenance Setting


Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a percentage of the total expected
performance life. Reset this value to 0 after replacing the bypass relay.
Note:

No.
o4-07

The actual maintenance time will depend on the environment where the drive is used.

Name
DC Bus Pre-charge Relay Maintenance Setting

Setting Range
0 to 150%

Default
0%

n o4-09: IGBT Maintenance Setting


Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total expected performance life. Reset
this value to 0 after replacing the IGBTs.
Note:

The actual maintenance time will depend on the environment where the drive is used.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

161

1.10 o: Operator Related Settings


No.
o4-09

Name
IGBT Maintenance Setting

Setting Range
0 to 150%

Default
0%

n o4-11: U2, U3 Initialization


Resets the fault trace and fault history monitors (U2-oo and U3-oo). Initializing the drive using A1-03 does not reset these
monitors.
No.
o4-11

Name
U2, U3 Initialization

Setting Range
0, 1

Default
0

Setting 0: No Action

The drive keeps the previously saved record concerning fault trace and fault history.
Setting 1: Reset Fault Data

Resets the data for the U2-oo and U3-oo monitors. Setting o4-11 to 1 and pressing the ENTER key erases fault data and
returns the display to 0.

n o4-12: kWh Monitor Initialization


Resets the kWh monitors U4-10 and U4-11. Initializing the drive or cycling the power does not reset these monitors.
No.
o4-12

Name
kWh Monitor Initialization

Setting Range
0, 1

Default
0

Setting 0: No Action

The kWh data are maintained.


Setting 1: Reset kWh Data

Resets the kWh counter. The monitors U4-10 and U4-11 will display 0 after they are initialized. Setting o4-12 to 1 and
pressing the ENTER erases kWh data and returns the display to 0.

n o4-13: Number of Run Commands Counter Initialization


Resets the Run command counter displayed in U4-02. Initializing the drive or cycling the power does not reset this monitor.
No.
o4-13

Name
Number of Run Commands Counter Initialization

Setting Range
0, 1

Default
0

Setting 0: No Action

The Run command data are kept.


Setting 1: Number of Run Commands Counter

Resets the Run command counter. The monitor U4-02 will show 0. Setting o4-13 to 1 and pressing the ENTER key erases the
counter value and returns the display to 0.

u q: DriveWorksEZ Parameters
These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.

n q1-01 to q6-07: Reserved for Use by DriveWorksEZ


These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.

u r: DriveWorksEZ Connection Parameters


These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.

n r1-01 to r1-40: DriveWorksEZ Connection Parameters


These parameters are reserved for use with DriveWorksEZ. Refer to the DriveWorksEZ manual for more information.

162

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.11 T: Motor Tuning

1.11 T: Motor Tuning


Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.

u T1: Parameter Settings during Induction Motor Auto-Tuning


The T1-oo parameters set the Auto-Tuning input data for induction motor tuning.
Note:

For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is complete, change
E1-04, Maximum Output Frequency, to the desired value.

n T1-00: Motor 1/Motor 2 Selection


Selects the motor to be tuned when motor 1/2 switching is enabled (i.e., a digital input is set for function H1-oo = 16). This
parameter is not displayed if motor 1/2 switching is disabled.
No.
T1-00

Name
Motor 1/Motor 2 Selection

Setting Range
1, 2

Default
1

Setting 1: Motor 1

Auto-Tuning automatically sets parameters E1-oo and E2-oo for motor 1.


Setting 2: Motor 2

Auto-Tuning automatically sets parameters E3-oo and E4-oo for motor 2. Make sure that motor 2 is connected to the drive
for Auto-Tuning.

n T1-01: Auto-Tuning Mode Selection


Sets the type of Auto-Tuning to be used.
No.

Name

T1-01

Auto-Tuning Mode Selection

Setting Range
2, (V/f)
0 to 2, 4 (OLV, CLV)

Default
2 (V/f, V/f w/PG)
0 (OLV, CLV)

Default
Determined by o2-04
and C6-01

Setting 0: Rotational Auto-Tuning


Setting 1: Stationary Auto-Tuning 1
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 4: Stationary Auto-Tuning 2

n T1-02: Motor Rated Power


Sets the motor rated power according to the motor nameplate value.
No.

Name

Setting Range

T1-02

Motor Rated Power

0.00 to 650.00 kW

Sets the motor rated voltage according to the motor nameplate value. Enter the voltage base speed here if the motor is operating
above base speed.
Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03 for better control precision
around rated speed when using a vector control mode. The no-load voltage can usually be found in the motor test report
available from the manufacturer. If the motor test report is not available, enter approximately 90% of the rated voltage printed
on the motor nameplate. This may increase the output current and reduce the overload margin.
No.
T1-03

Name
Motor Rated Voltage

Setting Range
0.0 to 510.0

V <1>

Default

400.0 V <1>

<1> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter Details

n T1-03: Motor Rated Voltage

163

1.11 T: Motor Tuning

n T1-04: Motor Rated Current


Sets the motor rated current according to the motor nameplate value. Set the motor rated current between 50% and 100% of
the drive rated current for optimal performance in OLV or CLV. Enter the current at the motor base speed.
No.

Name

T1-04

Motor Rated Current

Setting Range
10 to 200% of drive rated
current

Default
E2-01 (E4-01)

n T1-05: Motor Base Frequency


Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used or
the motor is used in the field weakening area, enter the maximum frequency to E1-04 (E3-04 for motor 2) after Auto-Tuning
is complete.
No.
T1-05

Name
Motor Base Frequency

Setting Range
0.0 to 400.0 Hz

Default
60.0 Hz

Setting Range
2 to 48

Default
4

n T1-06: Number of Motor Poles


Sets the number of motor poles according to the motor nameplate value.
No.
T1-06

Name
Number of Motor Poles

n T1-07: Motor Base Speed


Sets the motor rated speed according to the motor nameplate value. Enter the speed at base frequency when using a motor
with an extended speed range or if using the motor in the field weakening area.
No.
T1-07

Name
Motor Base Speed

Setting Range
0 to 24000 r/min

Default
1750 r/min

n T1-08: PG Number of Pulses Per Revolution


Sets the number of pulses from the PG encoder. Set the actual number of pulses for one full motor rotation.
No.
T1-08
Note:

Name
PG Number of Pulses Per Revolution

Setting Range
1 to 60000 ppr

Default
1024 ppr

T1-08 will only be displayed in CLV.

n T1-09: Motor No-Load Current


Sets the no-load current for the motor. The default setting displayed is no-load current automatically calculated from the output
power set in T1-02 and the motor rated current set to T1-04. Enter the data listed on the motor test report. Leave this data at
the default setting if the motor test report is not available.
No.

Name

T1-09

Motor No-Load Current

Note:

Setting Range
0 A to [T1-04]
(Max: 0 to 2999.9)

Default

The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value
has two decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal
place (0.1 A) if the maximum applicable motor capacity is higher than 11 kW.

n T1-10: Motor Rated Slip


Sets the rated slip for the motor. The default setting displayed is the rated slip for a Yaskawa motor calculated from the output
power set in T1-02. Enter the data listed on the motor test report.
No.
T1-10

164

Name
Motor Rated Slip

Setting Range
0.00 to 20.00 Hz

Default

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.11 T: Motor Tuning

n T1-11: Motor Iron Loss


Provides iron loss information to determine the Energy Saving coefficient. T1-11 will first display the value for the motor iron
loss that the drive automatically calculated the when motor capacity was entered to T1-02. Enter the motor iron loss value
listed to T1-11 if the motor test report is available.
Name

Setting Range

T1-11

Motor Iron Loss

0 to 65535 W

Default
14 W
Differs depending
on motor code and
motor parameter
settings.

Parameter Details

No.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

165

1.12 U: Monitor Parameters

1.12 U: Monitor Parameters


Monitor parameters let the user view various aspects of drive performance using the digital operator display. Some monitors
can be output from terminals FM and AM by assigning the specific monitor parameter number (Uo-oo) to H4-01 and H4-04.
Refer to H4-01, H4-04: Multi-Function Analog Output Terminal FM, AM Monitor Selection on page 119 for details on
assigning functions to an analog output.

u U1: Operation Status Monitors


Status monitors display drive status data such as output frequency and output current. Refer to U1: Operation Status
Monitors on page 292 for a complete list of U1-oo monitors and descriptions.

u U2: Fault Trace


Use these monitor parameters to view the status of various drive aspects when a fault occurs.
This information is helpful for determining the cause of a fault. Refer to U2: Fault Trace on page 294 for a complete list of
U2-oo monitors and descriptions.
U2-oo monitors are not reset when the drive is initialized. Refer to o4-11: U2, U3 Initialization on page 162 for instructions
on how to reset these monitor values.

u U3: Fault History


These parameters display faults that have occurred during operation as well as the drive operation time when those faults
occurred. Refer to U3: Fault History on page 296 for a complete list of U3-oo monitors and descriptions.
U3-oo monitors are not reset when the drive is initialized. Refer to o4-11: U2, U3 Initialization on page 162 for instructions
on how to reset these monitor values.

u U4: Maintenance Monitors


Maintenance monitors show:
Runtime data of the drive and cooling fans and number of Run commands issued
Maintenance data and replacement information for various drive components
kWh data
Highest peak current that has occurred and output frequency at the time the peak current occurred
Motor overload status information
Detailed information about the present Run command and frequency reference source selection
Refer to U4: Maintenance Monitors on page 296 for a complete list of U4-oo monitors and descriptions.

u U5: PID Monitors


These monitors display various aspects of PID control. Refer to PID Block Diagram on page 35 for details on how these
monitors display PID data.
Refer to U5: PID Monitors on page 299 for a complete list of U5-oo monitors and descriptions.

u U6: Operation Status Monitors


Control monitors show:
Reference data for the output voltage and vector control
Data on PM motor rotor synchronization, forward phase compensation, and flux positioning
Pulse data from the PG motor encoder
Pulse data for Zero Servo control
ASR and Feed Forward control monitors
Refer to Figure 1.33 and Figure 1.34 on page 52 for details and an illustration showing where monitors are located in the
ASR block.
The offset value added to the frequency reference by the frequency offset function. Refer to Setting 44, 45, 46: Offset
Frequency 1, 2, 3 on page 101.
166

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

1.12 U: Monitor Parameters


The bias value added to the frequency reference by the Up/Down 2 function (see Setting 75, 76: Up 2/Down 2 Function)
Refer to U6: Operation Status Monitors on page 299 for a complete list of U6-oo monitors and descriptions.

u U8: DriveWorksEZ Monitors

Parameter Details

These monitors are reserved for use with DriveWorksEZ.


A complete description of the U8-oo monitors can be found in the DriveWorksEZ instruction manual.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

167

1.12 U: Monitor Parameters

This Page Intentionally Blank

168

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2
Troubleshooting
This chapter provides descriptions of the drive faults, alarms, errors, related displays, and guidance for
troubleshooting. This chapter can also serve as a reference guide for tuning the drive during a trial run.

2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10

SECTION SAFETY...............................................................................................170
MOTOR PERFORMANCE FINE-TUNING...........................................................172
DRIVE ALARMS, FAULTS, AND ERRORS........................................................175
FAULT DETECTION.............................................................................................180
ALARM DETECTION...........................................................................................198
OPERATOR PROGRAMMING ERRORS............................................................207
AUTO-TUNING FAULT DETECTION..................................................................211
COPY FUNCTION RELATED DISPLAYS...........................................................216
DIAGNOSING AND RESETTING FAULTS.........................................................218
TROUBLESHOOTING WITHOUT FAULT DISPLAY..........................................220

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

169

2.1 Section Safety

2.1

Section Safety
DANGER
Electrical Shock Hazard

Do not connect or disconnect wiring while the power is on.


Failure to comply will result in death or serious injury.

WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may illustrate drives without covers or safety shields to display details. Be sure to reinstall covers
or shields before operating the drives and run the drives according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the motor case.
Do not touch terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor remains charged even after the drive
input power is turned off. After shutting off the power, wait for at least the amount of time specified on the drive before
touching any components.
After blowing a fuse or tripping a GFCI, do not attempt to restart the drive or operate peripheral devices until five
minutes pass and CHARGE lamp is OFF.
Failure to comply could result in death, serious injury, and damage to the drive.
Check wiring and peripheral device ratings to identify the cause of trips.
Contact your supplier if the cause cannot be identified.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only by authorized personnel familiar with installation,
adjustment and maintenance of AC drives.
Do not perform work on the drive while wearing loose clothing, jewelry, or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing and wear eye protection before beginning work
on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.

Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming drive input power before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.

170

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.1 Section Safety

NOTICE

Troubleshooting

Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance. Use shielded twisted-pair wires
and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a dynamic braking option to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for modification of the product made by the user.
Check all the wiring after installing the drive and connecting other devices to ensure that all connections are correct.
Failure to comply could result in damage to the drive.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

171

2.2 Motor Performance Fine-Tuning

2.2

Motor Performance Fine-Tuning

This section offers helpful information for counteracting oscillation, hunting, and other problems that occur while performing
a trial run. Refer to the section below that corresponds to the motor control method used.
Note:

This section describes commonly edited parameters that may be set incorrectly. Consult Yaskawa for more information on detailed settings
and for fine-tuning the drive.

u Fine-Tuning V/f Control and V/f Control with PG


Table 2.1 Parameters for Fine-Tuning Performance in V/f and V/f w/PG
Problem

Motor hunting and


oscillation at speeds
between 10 and 40 Hz

Poor torque or speed


response
Motor hunting and
oscillation
Poor motor torque at
speeds below 10 Hz
Motor hunting and
oscillation
Poor motor torque at
low speeds
Motor instability at
motor start

Parameter No.

Corrective Action

Reduce the setting if insufficient motor torque relative to the size


of the load causes hunting.

Increase
the setting when motor hunting and oscillation occur
Hunting Prevention Gain with a light
load.
(n1-02)
Reduce the setting if hunting occurs when using a motor with a
relatively low inductance, such as a high-frequency motor or a
motor with a larger frame size.
Torque Compensation
Primary Delay Time
(C4-02)

Reduce the setting if motor torque and speed response are too
slow.
Increase the setting if motor hunting and oscillation occur.

Torque Compensation
Gain (C4-01)

Increase the setting if motor torque is insufficient at speeds


below 10 Hz.
Reduce the setting if motor hunting and oscillation with a
relatively light load.

Mid Output Voltage A


(E1-08)
Minimum Output
Voltage (E1-10)

Increase the setting if motor torque is insufficient at speeds


below 10 Hz.
Reduce the setting If motor instability occurs at motor start.

Default

Suggested
Setting

1.00

0.10 to 2.00

200 ms

100 to 1000 ms

1.00

0.50 to 1.50

Depends on
o2-04, Drive Default setting
Model
5 V
Selection
0.0
(no slip
compensation)

Poor speed precision


(V/f control)

the motor-rated current (E2-01), motor-rated slip (E2-02), and


Slip Compensation Gain Set
motor no-load current (E2-03), then adjust the slip compensation
(C3-01)
gain (C3-01).

Poor speed precision


(V/f control with PG)

ASR Proportional Gain 1


Proportional
(C5-01)
gain =
Adjust
the
ASR
proportional
gain
1
(C5-01)
and
the
ASR
integral
C5-01:
0.20
ASR Integral Time 1
0.10 to 1.00
time
1
(C5-02).
C5-02:
0.200
(C5-02)
Integral time =
<1> <2>
0.100 to 2.000

0.5 to 1.5

<1> ASR in V/f Control with PG only controls the output frequency, and does not allow the same high gain settings as CLV control.
<2> Refer to C5: Automatic Speed Regulator (ASR) on page 52 for details on ASR.

u Fine-Tuning Open Loop Vector Control


Table 2.2 Parameters for Fine-Tuning Performance in OLV
Corrective Action

Default

Suggested
Setting

Poor motor torque


and speed response
AFR Gain
Motor hunting and
(n2-01)
oscillation at speeds
between 10 and 40 Hz

Gradually reduce the setting in 0.05 increments if motor torque


and speed response are too slow.
Gradually increase the setting in 0.05 increments if motor hunting
and oscillation occur.

1.00

0.50 to 2.00

Poor motor torque


and speed response
AFR Time Constant 1
Motor hunting and
(n2-02)
oscillation at speeds
between 10 and 40 Hz

Gradually reduce the setting in 10 ms increments and check the


performance to improve motor torque speed response.
Gradually increase the setting by 50 ms increments and check the
performance if motor hunting and oscillation occur as a result of
load inertia.
Note:
Ensure that n2-02 n2-03. When changing n2-02, set
C4-02 (Torque Compensation Primary Delay Time
Constant 1) accordingly.

50 ms

50 to 2000 ms

Problem

172

Parameter No.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.2 Motor Performance Fine-Tuning


Problem

Parameter No.

AFR Time Constant 2


(n2-03)
Overvoltage trips when
accelerating,
decelerating, or during
sudden speed or load
changes
Torque Compensation
Primary Delay Time
Constant 2 (C4-06)

Corrective Action
Gradually increase the setting in 50 ms increments if overvoltage
occurs.
Gradually reduce the setting in 10 ms increments if response is
slow.
Note:
Ensure that n2-02 n2-03. When making adjustments
to n2-03, increase the value of C4-06 (Torque
Compensation Primary Delay Time 2)
proportionally.
Gradually increase the setting in 10 ms increments and check the
performance if overvoltage trips occur.
Gradually reduce the setting in 2 ms increments and check the
performance if response is slow.
Note:
Ensure that C4-02 C4-06. When changing C4-06
(Torque Compensation Primary Delay Time
Constant 2), increase the value of n2-03
proportionally.
Gradually reduce the setting in 2 ms increments and check the
performance to improve motor torque speed response.
Gradually increase the setting in 10 ms increments if motor
hunting and oscillation occur.
Note:
Ensure that C4-02 C4-06. When making
adjustments to C4-02, increase the AFR time constant
(n2-02) proportionally.
Gradually reduce the setting in 10 ms increments if response is
slow.
Gradually increase the setting in 10 ms increments if speed is
unstable.

Default

Suggested
Setting

750 ms

750 to 2000 ms

150 ms

150 to 750 ms

20 ms

20 to 100 ms

200 ms

100 to 500 ms

1.0

0.5 to 1.5

Poor motor torque


and speed response
Motor hunting and
oscillation

Torque Compensation
Primary Delay Time
Constant 1 (C4-02)

Poor speed response


and stability

Slip Compensation
Primary Delay Time
Constant (C3-02)

Poor speed precision

Gradually increase the setting in 0.1 ms increments if speed is too


slow.
Slip Compensation Gain
(C3-01)
Gradually reduce the setting in 0.1 ms increments if speed is too
fast.

Poor speed precision


during regenerative
operation

Slip Compensation
Selection During
Regeneration (C3-04)

Enable slip compensation during regeneration by setting parameter


C3-04 = 1.

Poor motor torque at


low speeds
Poor speed response
Motor instability at
start

Mid Output Voltage A


(E1-08)
Minimum Output
Voltage (E1-10)

Increase the setting if motor torque and speed response are too
Depends on
slow.
o2-04,
Reduce the setting if the motor exhibits excessive instability at
Drive
start-up.
Model
Note:
When working with a relatively light load, increasing Selection
this value too much can cause overtorque.

Default setting
2 V

When using OLV, leave the torque compensation gain (C4-01) at its default setting of 1.00.

u Parameters to Minimize Motor Hunting and Oscillation


Parameters in Table 2.3 indirectly affect motor hunting and oscillation.
Table 2.3 Parameters that Affect Control Performance in Applications
Application
Prevents motor speed loss by maintaining the output frequency when working with heavy loads or when there
is powerful backlash on the machine side.
Adjusting accel and decel times will affect the torque presented to the motor during acceleration or
deceleration.
Prevents shock at the beginning and end of acceleration and deceleration.
Skips over the resonant frequencies of connected machinery.
Prevents fluctuation in the analog input signal due to noise.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Troubleshooting

Name
(Parameter No.)
Dwell Function
(b6-01 through b6-04)
Accel/Decel Time
(C1-01 through C1-11)
S-Curve Characteristics
(C2-01 through C2-04)
Jump Frequency
(d3-01 through d3-04)
Analog Filter Time Constant
(H3-13)

173

2.2 Motor Performance Fine-Tuning


Name
(Parameter No.)
Stall Prevention
(L3-01 through L3-06, L3-11)
Torque Limits
(L7-01 through L7-04, L7-06, L7-07)

174

Application
Prevents motor speed loss and overvoltage when the load is too heavy or during sudden acceleration/
deceleration.
Adjustment is not normally necessary because Stall Prevention is enabled as a default. Set L3-04 to 0 to
disable Stall Prevention during deceleration when using a braking resistor.
Sets the maximum torque for OLV Control.
Ensure that the drive capacity is greater than the motor capacity when increasing this setting. Motor speed
loss may occur with heavy loads.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.3 Drive Alarms, Faults, and Errors

2.3

Drive Alarms, Faults, and Errors

u Types of Alarms, Faults, and Errors


Check the digital operator for information about possible faults if the drive or motor fails to operate.
If problems occur that are not covered in this manual, contact the nearest Yaskawa representative with the following
information:
Drive model
Software version
Date of purchase
Description of the problem
Table 2.4 contains descriptions of the various types of alarms, faults, and errors that may occur while operating the drive.
Table 2.4 Types of Alarms, Faults, and Errors

Faults

Minor Faults and


Alarms

Operation Errors

Tuning Errors

Copy Function Errors

Drive Response
When the drive detects a fault:
The digital operator displays text indicating the specific fault and the ALM indicator LED remains lit until the fault is reset.
The fault interrupts drive output and the motor coasts to a stop.
Some faults allow the user to select the stopping method when the fault occurs.
Fault output terminals MA-MC will close, and MB-MC will open.
The drive will remain inoperable until the fault is cleared. Refer to Fault Reset Methods on page 219.
When the drive detects an alarm or a minor fault:
The digital operator displays text indicating the specific alarm or minor fault, and the ALM indicator LED flashes.
The drive continues running the motor, although some alarms allow the user to select a stopping method when the alarm
occurs.
A multi-function contact output set to be tripped by a minor fault (H2- oo = 10) closes. If the output is set to be tripped
by an alarm, the contact will not close.
The digital operator displays text indicating a specific alarm and the ALM indicator LED flashes.
Remove the cause of the problem to reset a minor fault or alarm.
An operation error occurs when parameter settings conflict or do not match hardware settings (such as with an option card).
When the drive detects an operation error:
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
The drive will not operate the motor until the error has been reset. Correct the settings that caused the operation error to clear
the error.
Tuning errors occur while performing Auto-Tuning.
When the drive detects a tuning error:
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
Motor coasts to stop.
Remove the cause of the error and repeat the Auto-Tuning process.
Copy Function Errors occur when using the digital operator or the USB Copy Unit to copy, read, or verify parameter settings.
The digital operator displays text indicating the specific error.
Multi-function contact outputs do not operate.
Pressing any key on the digital operator will clear the fault. Investigate the cause of the problem (such as model incompatibility)
and try again.

u Alarm and Error Displays


n Faults
Table 2.5 gives an overview of possible fault codes. Conditions such as overvoltages can trip faults and alarms. It is important
to distinguish between faults and alarms to determine the proper corrective actions.
When the drive detects a fault, the ALM indicator LED lights, the fault code appears on the digital operator, and the fault
contact MA-MB-MC triggers. An alarm is present if the ALM LED blinks and the fault code on the digital operator flashes.
Refer to Minor Faults and Alarms on page 177 for a list of alarm codes.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

175

Troubleshooting

Type

2.3 Drive Alarms, Faults, and Errors


Table 2.5 Fault Displays
Digital Operator
Display

,
<1>

,
,
<2>

to
,
to
<3>

Braking Transistor Overload Fault

180

bUS

Option Communication Error

180

CE

MEMOBUS/Modbus Communication
Error

180

CF

Control Fault

180

CPF11 to Control Circuit Error


CPF14
CPF16 to Control Circuit Error
CPF19

187

to

oFA30 to Comm Option Card Connection Error


oFA43 (CN5-A)

187

Option Card Fault (CN5-B)

188

oFb02

Option Card Fault (CN5-B)

188

oFb03,
oFb11

Option Card Error (CN5-B)

188

CPF06

EEPROM Memory Data Error

181

,
to

181

CPF20, Control Circuit Error


CPF21

181

CPF22

Hybrid IC Error

182

CPF23

Control Board Connection Error

182

CPF24

Drive Unit Signal Fault

182

,
to

182

182
182

<3>

oFb12 to Option Card Connection Error


oFb17 (CN5-B)

188

oFC00

Option Card Connection Error


(CN5-C)

188

oFC01

Option Card Fault (CN5-C)

188

oFC02

Option Card Fault (CN5-C)

188

oFC03, Option Card Error (CN5-C)


oFC11

189

oFC12 to Option Card Connection Error


oFC17 (CN5-C)

189

oH

Heatsink Overheat

189

oH1

Heatsink Overheat

189

oH3

Motor Overheat Alarm (PTC input)

189

oH4

Motor Overheat Fault (PTC input)

190

oH5

Motor Overheat (NTC Input)

190

Converter heating

190

dv1

Z Pulse Fault Detection

183

oH6

dv2

Z Pulse Noise Fault Detection

183

oL1

Motor Overload

190

DriveWorksEZ Fault

183

oL2

Drive Overload

191

SI-T3 Watchdog Timer Error

183

oL3

Overtorque Detection 1

191

Abnormal Panel Fan

183

oL4

Overtorque Detection 2

191

Option Card External Fault

183

oL5

Mechanical Weakening Detection 1

191

External Fault
(input terminal S1 to S8)

184

oPr

Operator Connection Fault

192

Err

EEPROM Write Error

184

oS

Overspeed
(for Control Mode with PG)

192

FAn

Internal Fan Fault

184

ov

Overvoltage

192

Input Phase Loss

193

PG Disconnect
(for Control Mode with PG)
PG Hardware Fault
(when using PG-X3)

193

Fuse is Open

193

E5
EFAn
EF0

176

oFA12 to Option Card Connection Error


oFA17 (CN5-A)

oFb01

181

dWFL

EF1 to
EF8

to

to

181

Control Board Connection Error

Abnormal Diode Module Fan

187

188

CPF03

Excessive Speed Deviation


(for Control Mode with PG)

oFA10, Option Card Error


oFA11 (CN5-A)

Page

Option Card Connection Error


(CN5-B)

181

CPF26 to
CPF34
CPF40 to Control Circuit Error
CPF45

Name

oFb00

A/D Conversion Error

CPF07, Terminal Board Connection Error


CPF08

Digital Operator
Display

181

CPF02

dFAn

<3>

Page

boL

dEv

to

Name

FbH

Excessive PID Feedback

185

PF

FbL

PID Feedback Loss

185

PGo

GF

Ground Fault

185

LF

Output Phase Loss

185

LF2

Current Imbalance

186

LF3

Power Unit Output Phase Loss 3

186

rF

Braking Resistor Fault

194

rH

Dynamic Braking Resistor

194

rr

Dynamic Braking Transistor

194

nSE

Node Setup Error

186

oC

Overcurrent

186

oFA00

Option Card Connection Error


(CN5-A)

187

oFA01

Option Card Fault (CN5-A)

187

oFA03 to Option Card Error


oFA06 (CN5-A)

187

PGoH
PUF

<4>

<3>

193

SC

IGBT Short Circuit or Ground Fault

194

SEr

Too Many Speed Search Restarts

194

SvE

Zero-Servo Fault

195

THo

Thermistor Disconnect

195

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.3 Drive Alarms, Faults, and Errors


Digital Operator
Display

<3>

Name

Page

UL3

Undertorque Detection 1

195

UL4

Undertorque Detection 2

195

UL5

Mechanical Weakening Detection 2

UnbC

Digital Operator
Display

Name

Page

Uv3

Soft Charge Circuit Fault

196

Uv4

Gate Drive Board Undervoltage

196

195

Uv5

MC/FAN power malfunction

197

voF

Output Voltage Detection Fault

197

Current Unbalance

195

Uv1

Undervoltage

196

Uv2

Control Power Supply Undervoltage

196

<3>

<1> Displayed as
when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
.
<2> Displayed as
when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display will show
.
<3> Detected in models CIMR-Ao4A0930 and 4A1200.
<4> Available in drive software versions 1015 and later for standard A1000 and 1012 and later for A1000 HHP models.

n Minor Faults and Alarms


Refer to Table 2.6 for an overview of possible alarm codes. Conditions such as overvoltages can trip faults and alarms. It is
important to distinguish between faults and alarms to determine the proper corrective actions.
When the drive detects an alarm, the ALM indicator LED blinks and the alarm code display flashes. Most alarms trigger a
digital output programmed for alarm output (H2-oo = 10). A fault (not an alarm) is present if the ALM LED lights without
blinking. Refer to Faults on page 175 for information on fault codes.
Table 2.6 Minor Fault and Alarm Displays
Page

YES

198

LT-1

output
Cooling Fan Maintenance Time No <1>

202

No output

198

LT-2

Capacitor Maintenance Time

No output

202

Transistor Overload
boL Braking
Fault
Card Communications
bUS Option
Error
Communication
CALL Serial
Transmission Error
MEMOBUS/Modbus
CE
Communication Error

YES

198

LT-3

Soft Charge Bypass Relay


Maintenance Time

No output

202

LT-4

output
IGBT Maintenance Time (50%) No <1>

202

oH

Heatsink Overheat

YES

203

oH2

Drive Overheat

YES

203

CrST

Cannot Reset

YES

199

oH3

Motor Overheat

YES

203

dEv

Excessive Speed Deviation


(for Control Mode with PG)

YES

199

oH5

Motor Overheat (NTC Input)

YES

203

dFAn

Abnormal Diode Module Fan

YES

200

oL3

Overtorque 1

YES

204

Drive Disabled

YES

200

oL4

Overtorque 2

YES

204

YES

183

oL5

YES

204

oS

Mechanical Weakening
Detection 1
Overspeed
(for Control Mode with PG)

YES

204

ov

Overvoltage

YES

204

bb

dnE

Name
SI-T Station Number Setting
Error (CC-Link, CANopen,
MECHATROLINK-II)
Drive Baseblock

dWAL DriveWorksEZ Alarm

YES

198

YES

199

YES

199

E5

SI-T3 Watchdog Timer Error

YES

183

EF

Run Command Input Error

YES

200

YES

200

YES

200

YES

200

EFAn Abnormal Panel Fan


EF0

Option Card External Fault

EF1 to External Fault


EF8 (input terminal S1 to S8)
FbH

Excessive PID Feedback

YES

201

FbL

PID Feedback Loss

YES

201

Hbb

Safe Disable Signal Input <3>

YES

201

HbbF

Safe Disable Signal Input <3>

YES

201

HCA

Current Alarm

YES

202

Digital Operator
Display

<2>

Name

<1>
<1>

Test Mode No output


PASS MEMOBUS/Modbus
Complete
Disconnect
PGo PG
YES
(for Control Mode with PG)
Hardware Fault
PGoH PG
YES
(when using PG-X3)
Run 2, Motor Switch
rUn During
YES
Command Input
MEMOBUS/Modbus Test Mode
SE
YES
Fault

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Page

205
205

Troubleshooting

AEr

to

Minor Fault
Output
(H2-oo =
10)

Minor Fault
Output
(H2-oo =
10)

Digital Operator
Display

205
205
205

177

2.3 Drive Alarms, Faults, and Errors


Digital Operator
Display
<2>

Name

Minor Fault
Output
(H2-oo =
10)

Page

Minor Fault
Output
(H2-oo =
10)

Page

Mechanical Weakening
Detection 2

YES

195

Digital Operator
Display

Name

THo

Thermistor Disconnect

YES

205

UL5

TrPC

IGBT Maintenance Time (90%)

YES

205

Uv

Undervoltage

YES

206

UL3

Undertorque 1

YES

206

voF

Output Voltage Detection Fault

YES

206

UL4

Undertorque 2

YES

206

<1> Output when H2-oo = 2F.


<2> Detected in models CIMR-Ao4A0930, 4A1200 and A1000 HHP.
<3> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.

n Operation Errors
Table 2.7 Operation Error Displays
Digital Operator
Display

Name

Page

Digital Operator
Display

Name

Page

oPE01

Drive Unit Setting Error

207

oPE08

Parameter Selection Error

209

oPE02

Parameter Setting Range Error

207

oPE09

PID Control Selection Error

209

oPE03

Multi-Function Input Setting Error

207

oPE10

V/f Data Setting Error

209

oPE04

Terminal Board Mismatch Error

208

oPE13

Pulse Train Monitor Selection Error

210

oPE05

Run Command Selection Error

208

oPE15

Torque Control Setting Error

210

oPE06

Control Method Selection Error

208

oPE16

Energy Saving Constants Error

210

oPE07

Multi-Function Analog Input Selection


Error

208

oPE18

Online Tuning Parameter Setting Error

210

Name

Page

n Auto-Tuning Errors
Table 2.8 Auto-Tuning Error Displays
Digital Operator
Display

Name

Page

Digital Operator
Display

End1

Excessive V/f Setting

211

Er-08

Rated Slip Error

213

End2

Motor Iron Core Saturation Coefficient


Error

211

Er-09

Acceleration Error

213

End3

Rated Current Setting Alarm

211

Er-10

Motor Direction Error

213

Adjusted Slip Value Fell Below Lower


Limit

Er-11

Motor Speed Error

213

End4

211

Er-12

Current Detection Error

213

End5

Resistance Between Lines Error

211

Er-13

Leakage Inductance Error

214

Motor Speed Error 2

214

End6

Leakage Inductance Alarm

211

Er-14

End7

No-Load Current Alarm

212

Er-15

Torque Saturation Error

214

Er-01

Motor Data Error

212

Er-17

Reverse Prohibited Error

214

Induction Voltage Error

214

Er-02

Alarm

212

Er-18

Er-03

STOP Button Input

212

Er-19

PM Inductance Error

214

Stator Resistance Error

214

Z Pulse Correction Error

215

Er-04

Line-to-Line Resistance Error

212

Er-20

Er-05

No-Load Current Error

212

Er-21

n Errors and Displays When Using the Copy Function


Table 2.9 Copy Errors
Digital Operator
Display

178

Name

Page

CoPy

Writing parameter settings (flashing)

216

Digital Operator
Display

Name

dFPS

Drive model mismatch

216

Page

CPEr

Control mode mismatch

216

End

Task complete

216

CPyE

Error writing data

216

iFEr

Communication error

216

CSEr

Copy unit error

216

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.3 Drive Alarms, Faults, and Errors


Digital Operator
Display

Name

Page

Model, voltage class, capacity


mismatch

217

rdEr

Error reading data

217

rEAd

Reading parameter settings (flashing)

217

Name

Page

vAEr

Voltage class, capacity mismatch

217

vFyE

Parameter setting mismatch

217

vrFy

Comparing parameter settings


(flashing)

217

Troubleshooting

ndAT

Digital Operator
Display

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

179

2.4 Fault Detection

2.4

Fault Detection

u Fault Displays, Causes, and Possible Solutions


Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal MA-MB-MC.
Remove the cause of the fault and manually clear the fault before attempting to run the drive again.
Table 2.10 Detailed Fault Displays, Causes, and Possible Solutions
Digital Operator Display
boL
Cause
The wrong braking resistor is installed

Fault Name
Braking Transistor Overload Fault
The braking transistor reached its overload level.
Possible Solution
Select the correct braking resistor.

Digital Operator Display

Fault Name
Option Communication Error

bUS
Cause
No signal was received from the PLC

The connection was lost after establishing initial communication.


Only detected when the run command frequency reference is assigned to an option card.
Possible Solution

Check for faulty wiring.


Faulty communications wiring or an existing Correct the wiring.
short circuit
Check for disconnected cables and short circuits and repair as needed.

Communication data error occurred due to


noise

Check the various options available to minimize the effects of noise.


Counteract noise in the control circuit, main circuit, and ground wiring.
Ensure that other equipment such as switches or relays do not cause noise. Use surge absorbers if
necessary.
Use only recommended cables or other shielded line. Ground the shield on the controller side or the
drive input power side.
Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive
power supply input.

The option card is damaged

Replace the option card if there are no problems with the wiring and the error continues to occur.
The option card is not properly connected to The connector pins on the option card do not line up properly with the connector pins on the drive.
the drive
Reinstall the option card.
Digital Operator Display

Fault Name
MEMOBUS/Modbus Communication Error
CE
Control data was not received for the CE detection time set to H5-09.
Cause
Possible Solution
Check for faulty wiring.
Faulty communications wiring or an existing Correct the wiring.
short circuit
Check for disconnected cables and short circuits and repair as needed.
Check the various options available to minimize the effects of noise.
Counteract noise in the control circuit, main circuit, and ground wiring.
Use only recommended cables or other shielded line. Ground the shield on the controller side or the
Communication data error occurred due to
drive input power side.
noise
Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if
required.
Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive
power supply input.
Digital Operator Display
CF
Cause
Motor parameters are set improperly
Torque limit is too low

180

Fault Name
Control Fault
The torque limit was reached continuously for three seconds or longer while ramping to stop in OLV
Control.
Possible Solution
Check the motor parameter settings and repeat Auto-Tuning.
Set the torque limit to the most appropriate setting (L7-01 through L7-04).

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Adjust the deceleration time (C1-02, C1-04, C1-06, C1-08).
Set the frequency to the minimum value and interrupt the Run command when the drive finishes
decelerating.

Load inertia is too big


Digital Operator Display
CPF11 to CPF14
or
CPF16 to CPF19
Cause

Fault Name
Control Circuit Error
Possible Solution

Cycle power to the drive.


There is a self-diagnostic error in the control
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
circuit
representative for instructions on replacing the control board.
Connector on the operator is damaged
Replace the operator.
Digital Operator Display
CPF02
Cause

Fault Name
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Possible Solution
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Control circuit is damaged


Digital Operator Display
CPF03
Cause
There is a connection error

Drive fails to operate properly due to noise


interference

Fault Name
Control Board Connection Error
Connection error between the control board and the drive
Possible Solution
Turn off the power and check the connection between the control board and the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Check the various options available to minimize the effects of noise.
Counteract noise in the control circuit, main circuit, and ground wiring.
Use only recommended cables or other shielded line. Ground the shield on the controller side or the
drive input power side.
Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors if
required.
Separate all communication wiring from drive power lines. Install an EMC noise filter to the drive
power supply input.

Digital Operator Display


CPF06

Fault Name
EEPROM Memory Data Error
Error in the data saved to EEPROM

Cause

Possible Solution
Turn off the power and check the connection between the control board and the drive.
There is an error in EEPROM control circuit If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
The power supply was switched off while
Reinitialize the drive using parameter A1-03.
parameters were being saved to the drive
Digital Operator Display
CPF08
Cause
There is a faulty connection between the
terminal board and the control board

Fault Name
Terminal Board Connection Error
Possible Solution
Turn off the power and check the connection between the control board and the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Digital Operator Display


CPF20 or CPF21

or
Cause

Fault Name

Control Circuit Error


Possible Solution

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Troubleshooting

CPF07

181

2.4 Fault Detection


Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Hardware is damaged
Digital Operator Display
CPF22

Fault Name
Hybrid IC Failure

Cause

Possible Solution

Hybrid IC failure on the power board

Cycle power to the drive.


If the problem continues, replace the power board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the power board.

Digital Operator Display


CPF23
Cause
Hardware is damaged
Digital Operator Display
CPF24
Cause
Hardware is damaged

Fault Name
Control Board Connection Error
Connection error between the control board and the drive
Possible Solution
Turn off the power and check the connection between the control board and the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Fault Name
Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
Possible Solution
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Digital Operator Display


to
to

CPF26 to CPF34
CPF40 to CPF45
Cause

Fault Name
Control Circuit Error
CPU error
Possible Solution
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Hardware is damaged
Digital Operator Display
dEv

Fault Name
Speed Deviation (for Control Mode with PG)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for
longer than the time set to F1-11.

Cause

Possible Solution

Load is too heavy


Acceleration and deceleration times are set too
short
The load is locked up
Parameters are not set appropriately

Reduce the load.


Increase the acceleration and deceleration times (C1-01 through C1-08).

Check the machine.


Check the settings of parameters F1-10 and F1-11.
Set H6-02 to the same value as the speed feedback signal frequency when the motor runs at maximum
speed.
Incorrect speed feedback scaling when using
terminal RP as speed feedback input in V/f
Adjust the speed feedback signal using parameters H6-03 through H6-05.
control
Make sure the speed feedback signal frequency does not exceed the maximum input frequency of
terminal RP.
Motor brake is engaged
Ensure the motor brake releases properly.
Digital Operator Display
dFAn
Cause

182

Fault Name
Abnormal Diode Module Fan
Displays when diode converter module(s) has a fan fault
Possible Solution

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Cycle power to the drive.
Check for fan operation.
Diode module cooling fan has malfunctioned. Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative operation
time of the fan maintenance timer with U4-04.
If the cooling fan has exceeded its expected performance life or is damaged in any other way, replace
the cooling fan.
Digital Operator Display
dv1

Fault Name
Z Pulse Fault
The motor turned one full rotation without the Z Pulse being detected.
Possible Solution

Cause
PG encoder is disconnected, improperly
Make sure the PG encoder is properly connected and all shielded lines are properly grounded.
wired, or the PG option card or PG encoder are
If the problem continues after cycling power, replace the PG option card or the PG encoder.
damaged
Digital Operator Display
dv2

Fault Name
Z Pulse Noise Fault Detection
The Z Pulse is out of phase by more than 5 degrees for the number of times specified in parameter F1-17.

Cause
Possible Solution
Noise interference along the PG cable
Separate the PG cable lines from the source of the noise.
PG cable is not wired properly
Rewire the PG encoder and properly ground all shielded lines.
PG option card or the PG encoder are damaged If the problem continues after cycling power, replace the PG option card or the PG encoder.
Digital Operator Display
dWAL
dWFL
Cause
Fault output by DriveWorksEZ

Fault Name
DriveWorksEZ Fault
Possible Solution
Correct the cause of the fault.

Digital Operator Display


E5
Cause
Data has not been received from the PLC

Fault Name
SI-T3 Watchdog Timer Error
The watchdog timed out.
Possible Solution
Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and
proceed to phase 3. Refer to the SI-T3 Option Technical Manual for more details on troubleshooting.

Digital Operator Display


EFAn

Fault Name
Abnormal Panel Fan
Displays when the Panel Fan Control detects a fan fault

Cause

Possible Solution

Digital Operator Display


EF0
Cause

Fault Name
Option Card External Fault
An external fault condition is present.

Troubleshooting

Panel fan or panel fan control has


malfunctioned

Cycle power to the drive.


Check for fan operation.
Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative operation
time of the fan maintenance timer with U4-04.
If the cooling fan has exceeded its expected performance life or is damaged in any other way, replace
the cooling fan.

Possible Solution

An external fault was received from the PLC Remove the cause of the external fault.
and F6-03 is set to a value other than 3.
Remove the external fault input from the PLC.
Problem with the PLC program
Check the PLC program and correct problems.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

183

2.4 Fault Detection


Digital Operator Display
EF1
EF2
EF3
EF4
EF5
EF6
EF7

Fault Name
External Fault (input terminal S1)
External fault at multi-function input terminal S1.
External Fault (input terminal S2)
External fault at multi-function input terminal S2.
External Fault (input terminal S3)
External fault at multi-function input terminal S3.
External Fault (input terminal S4)
External fault at multi-function input terminal S4.
External Fault (input terminal S5)
External fault at multi-function input terminal S5.
External Fault (input terminal S6)
External fault at multi-function input terminal S6.
External Fault (input terminal S7)
External fault at multi-function input terminal S7.

External Fault (input terminal S8)


External fault at multi-function input terminal S8.
Cause
Possible Solution
An external device tripped an alarm function Remove the cause of the external fault and reset the fault.
Properly connect the signal lines to the terminals assigned for external fault detection
(H1-oo = 20 to 2F).
Wiring is incorrect
Reconnect the signal line.
Check for unused terminals set for H1-oo = 20 to 2F (External Fault).
Multi-function contact input setting is
incorrect
Change the terminal settings.
EF8

Digital Operator Display

Fault Name
EEPROM Write Error

Err
Cause

Data cannot be written to the EEPROM


Possible Solution
Press ENTER on the digital operator.
Correct the parameter setting.
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Noise has corrupted data while writing to the

EEPROM

Hardware problem
Digital Operator Display
FAn
Cause

Fault Name
Internal Fan Fault
Fan or magnetic contactor failure
Possible Solution

Internal cooling fan has malfunctioned

Cycle power to the drive.


Check for fan operation.
Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative operation
time of the fan maintenance timer with U4-04.
If the cooling fan has exceeded its expected performance life or is damaged in any other way, replace
the cooling fan.

Fault detected in the internal cooling fan or


magnetic contactor to the power supply.

Cycle power to the drive.


If the fault continues to occur, replace the power board/gate drive board or the entire drive.
Contact Yaskawa or a Yaskawa representative for instructions on replacing the power board/gate drive
board.

184

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Digital Operator Display
FbH
Cause
Parameters are set inappropriately
Incorrect PID feedback wiring
There is a problem with the feedback sensor
Digital Operator Display
FbL
Cause
Parameters are set inappropriately
Incorrect PID feedback wiring
There is a problem with the feedback sensor

Fault Name
Excessive PID Feedback
PID feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12
to 2 or 5 to enable fault detection.
Possible Solution
Check b5-36 and b5-37 settings.
Correct the wiring.
Check the sensor on the control side.
Replace the sensor if damaged.
Fault Name
PID Feedback Loss
This fault occurs when PID feedback loss detection is programmed to trigger a fault (b5-12 = 2) and the
PID feedback level is below the detection level set to b5-13 for longer than the time set to b5-14.
Possible Solution
Check b5-13 and b5-14 settings.
Correct the wiring.
Check the sensor on the control side.
Replace the sensor if damaged.

Digital Operator Display


GF
Cause

Fault Name
Ground Fault
A current short to ground exceeded 50% of rated current on the output side of the drive.
Setting L8-09 to 1 enables ground fault detection.
Possible Solution
Check the insulation resistance of the motor.
Replace the motor.

Motor insulation is damaged

A damaged motor cable is creating a short


circuit

Excessive leakage current at the drive output

Check the motor cable.


Remove the short circuit and reapply power to the drive
Check the resistance between the cable and the ground terminal
Replace the cable.

Reduce the carrier frequency.


Reduce the amount of stray capacitance.

The set value exceeds the allowable setting range while the drive automatically adjusts the current
offset. This only happens when attempting to restart a PM motor that is coasting to stop.
The drive started to run during a current offset Set b3-01 to 1 to enable Speed Search at Start.
fault or while coasting to a stop
Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.
Note:
Speed Searches 1 and 2 are the same when using OLV/PM.
If
the
problem
continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
Hardware problem
representative for instructions on replacing the control board.
Digital Operator Display

Fault Name
Output Phase Loss

LF

Phase loss on the output side of the drive.


Setting L8-07 to 1 or 2 enables Phase Loss Detection.

Cause

Possible Solution

The motor winding is damaged

Check the resistance between motor lines.


Replace the motor if the winding is damaged.

The output terminal is loose

Check for loose terminals.

The rated current of the motor being used is


less than 5% of the drive rated current

Check the drive and motor capacities.

An output transistor is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Troubleshooting

The output cable is disconnected

Check for wiring errors and properly connect the output cable.
Correct the wiring.

185

2.4 Fault Detection


A single-phase motor is being used

The drive cannot operate a single phase motor.

Digital Operator Display


LF2

Fault Name
Output Current Imbalance
One or more of the phases in the output current are lost.

Cause

Possible Solution

Phase loss has occurred on the output side of Check for faulty wiring or poor connections on the output side of the drive.
the drive
Correct the wiring.
Terminal wires are loose on the output side of Check for loose terminals.
the drive
The output circuit is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Motor impedance or motor phases are uneven

Measure the line-to-line resistance for each motor phase. Ensure all values match.
Replace the motor.

Digital Operator Display


LF3
Cause
The gate drive board in the power unit is
damaged.
Cable to the current detection circuit in the
power unit is damaged or not connected
properly.

Fault Name
Power Unit Output Phase Loss 3
Phase loss occurred on the output side
Setting L8-78 to 1 enables Power Unit Output Phase Loss Protection
Possible Solution
Cycle the power supply. Refer to Diagnosing and Resetting Faults on page 218 for details. If the fault
continues to occur, replace the gate drive board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the gate drive board.
Check for incorrect wiring and correct any wiring mistakes.

Cable between the output rector and the power Contact Yaskawa or your nearest sales representative for instructions.
unit is loose or not connected.

Digital Operator Display


nSE
Cause
The node setup terminal closed during run.
A Run command was issued while the node
setup function was active.

Fault Name
Node Setup Error
A terminal assigned to the node setup function closed during run.
Possible Solution
Stop the drive when using the node setup function.

Digital Operator Display


oC

Fault Name
Overcurrent
Drive sensors detected an output current greater than the specified overcurrent level.

Cause
The motor has been damaged due to
overheating or the motor insulation is
damaged
One of the motor cables has shorted out or
there is a grounding problem

The load is too heavy

186

Possible Solution
Check the insulation resistance.
Replace the motor.
Check the motor cables.
Remove the short circuit and reapply power to the drive.
Check the resistance between the motor cables and the ground terminal
Replace damaged cables.

Measure the current flowing into the motor.


Replace the drive with a larger capacity drive if the current value exceeds the rated current.
Determine if there is sudden fluctuation in the current level.
Reduce the load to avoid sudden changes in the current level or switch to a larger drive.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration
time. If it is not possible to set the proper amount of torque, make the following changes:
The acceleration or deceleration times are too Increase the acceleration time (C1-01, C1-03, C1-05, C1-07)
short
Increase the S-curve characteristics (C2-01 through C2-04)
Increase the capacity of the drive.
The drive is attempting to operate a
specialized motor or a motor larger than the
maximum size allowed

Check the motor capacity.


Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the
motor nameplate.

Magnetic contactor (MC) on the output side of Set up the operation sequence so the MC does not trip while the drive is outputting current.
the drive has turned on or off
V/f setting is not operating as expected

Check the ratios between the voltage and frequency.


Set parameters E1-04 through E1-10 appropriately (E3-04 through E3-10 for motor 2).
Lower the voltage if it is too high relative to the frequency.

Excessive torque compensation

Check the amount of torque compensation.


Reduce the torque compensation gain (C4-01) until there is no speed loss and less current.

Drive fails to operate properly due to noise


interference

Review the possible solutions provided for handling noise interference.


Review the section on handling noise interference on page 225 and check the control circuit lines,
main circuit lines, and ground wiring.

Overexcitation gain is set too high

Check if the fault occurs simultaneously with overexcitation function operation.


Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).

Set b3-01 to 1 to enable Speed Search at Start.


Run command was applied while motor was
Program the Speed Search command input through one of the multi-function contact input terminals
coasting
(H1-oo = 61 or 62).
The motor control method and motor do not
match

Check the control mode.


For IM motors, set A1-02 to 0, 1, 2, or 3.

The rated output current of the drive is too


small

Use a larger drive.

Digital Operator Display


oFA00

Fault Name
Option Card Connection Error at Option Port CN5-A
Option compatibility error
Possible Solution

Cause
The option card installed into port CN5-A is Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.
incompatible with the drive
A PG option card is connected to option port PG option cards are supported by option ports CN5-B and CN5-C only. Connect the PG option card to
CN5-A
the correct option port.
Digital Operator Display
oFA01

Fault Name
Option Card Fault at Option Port CN5-A
Option not properly connected

Cause

Possible Solution
Turn off the power and reconnect the option card.
The option card connection to port CN5-A is Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
If the option is not a communication option card, try to use the card in a different option port. If the
faulty
option card works properly in a different option port, CN5-A is damaged, and the drive requires
replacement. If the error persists (oFb01 or oFC01 occur), replace the option card.
Fault Name

to

oFA03 to oFA06

oFA10, oFA11

to

oFA12 to oFA17

Option Card Connection Error (CN5-A)

to

oFA30 to oFA43

Communication Option Card Connection Error (CN5-A)

Cause
Option card or hardware is damaged

Option Card Error Occurred at Option Port CN5-A

Possible Solution
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

187

Troubleshooting

Digital Operator Display

2.4 Fault Detection


Digital Operator Display
oFb00
Cause
The option card installed into port CN5-B is
incompatible with the drive
A communication option card has been
installed in option port CN5-B

Fault Name
Option Card Fault at Option Port CN5-B
Option compatibility error
Possible Solution
Make sure the drive supports the option card to be installed. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.

Digital Operator Display


oFb01

Fault Name
Option Card Fault at Option Port CN5-B
Option not properly connected

Cause

Possible Solution
Turn off the power and reconnect the option card.
The option card connection to port CN5-B is Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
Try to use the card in a different option port (in case of a PG option, use port CN5-C). If the option
faulty
card works properly in a different option port, CN5-B is damaged, and the drive requires replacement.
If the error persists (oFA01 or oFC01 occur), replace the option card.
Digital Operator Display

Cause
An option card of the same type is already
installed in option port CN5-A

Fault Name
Option Card Fault at Option Port CN5-B
Same type of option card is currently connected
Possible Solution
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.

An input option card is already installed in


option port CN5-A

Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.

oFb02

Digital Operator Display


to

oFb03 to oFb11

to

oFb12 to oFb17
Cause

Option card or hardware is damaged


Digital Operator Display
oFC00
Cause
The option card installed into port CN5-C is
incompatible with the drive
A communication option card has been
installed in option port CN5-C

Fault Name
Option card error occurred at Option Port CN5-B
Possible Solution
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Fault Name
Option Card Connection Error at Option Port CN5-C
Option compatibility error
Possible Solution
Confirm that the drive supports the option card to be installed. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.

Digital Operator Display


oFC01

Fault Name
Option Card Fault at Option Port CN5-C
Option not properly connected

Cause

Possible Solution
Turn the power off and reconnect the option card.
The option card connection to port CN5-C is Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
Try to use the card in a different option port (in case of a PG option, use port CN5-B). If the option
faulty.
card works properly in a different option port, CN5-C is damaged, and the drive requires replacement.
If the error persists (oFA01 or oFb01 occur), replace the option card.
Digital Operator Display
oFC02

188

Fault Name
Option Card Fault at Option Port CN5-C
Same type of option card is currently connected

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Cause
An option card of the same type is already
installed in option port CN5-A or CN5-B.
An input option card is already installed in
option port CN5-A or CN5-B.
Three PG option boards are installed.

Possible Solution
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.
Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.
A maximum of two PG option boards can be used simultaneously. Remove the PG option board installed
into option port CN5-A.

Digital Operator Display


to

oFC03 to oFC11

to

oFC12 to oFC17
Cause

Option card or hardware is damaged

Fault Name
Option Card Error Occurred at Option Port CN5-C
Possible Solution
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.

Digital Operator Display

Fault Name
Heatsink Overheat

oH

The heatsink temperature exceeded the overheat pre-alarm level set to L8-02. The default value for L8-02
is determined by drive capacity (o2-04).

Cause

Possible Solution

Surrounding temperature is too high

Check the temperature surrounding the drive. Verify temperature is within drive specifications.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.

Load is too heavy

Measure the output current.


Decrease the load.

Internal cooling fan is stopped

Replace the cooling fan.


After replacing the cooling fan, set parameter o4-03 to 0 to reset the cooling fan maintenance.

Digital Operator Display

Fault Name
Overheat 1 (Heatsink Overheat)

oH1

The heatsink temperature exceeded the drive overheat level. Overheat level is determined by drive
capacity (o2-04).

Cause

Possible Solution

Load is too heavy

Measure the output current.


Reduce the load.

Digital Operator Display


oH3
Cause

Motor has overheated

Check the temperature surrounding the drive.


Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.

Fault Name
Motor Overheat Alarm (PTC Input)
The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the alarm detection level.
Detection requires setting multi-function analog inputs H3-02, H3-06, or H3-10 to E.
Possible Solution
Check the size of the load, the accel/decel times, and the cycle times.
Decrease the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
Check the motor rated current.
Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
Ensure the motor cooling system is operating normally.
Repair or replace the motor cooling system.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

189

Troubleshooting

Surrounding temperature is too high

2.4 Fault Detection


Digital Operator Display
oH4
Cause

Motor has overheated

Digital Operator Display


oH5
Cause
Motor has overheated

Fault Name
Motor Overheat Fault (PTC Input)
The motor overheat signal to analog input terminal A1, A2, or A3 exceeded the fault detection level.
Detection requires setting multi-function analog inputs H3-02, H3-06, or H3-10 to E.
Possible Solution
Check the size of the load, the accel/decel times, and the cycle times.
Decrease the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
Check the motor rated current.
Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
Ensure the motor cooling system is operating normally.
Repair or replace the motor cooling system.
Fault Name
Motor Overheat (NTC Input)
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2)
Possible Solution
Reduce the load.
Check the ambient temperature.

Digital Operator Display


oH6

Fault Name
Converter Heating
Displays when a Diode Converter Module(s) have a heat sink overtemperature

Cause

Possible Solution

Surrounding temperature of converter


heatsink is too high.

Digital Operator Display


oL1
Cause

Check the temperature surrounding the drive. Verify temperature is within drive specifications.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool the surrounding area.
Remove anything near the drive that might be producing excessive heat.

Fault Name
Motor Overload
The electronic motor overload protection tripped
Possible Solution
Reduce the load.

Load is too heavy


Cycle times are too short during acceleration Increase the acceleration and deceleration times (C1-01 through C1-08).
and deceleration
Reduce the load.
A general-purpose motor is driven below the Increase the speed.
rated speed with a high load
If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
Adjust the user-set V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
The output voltage is too high
Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
Check the motor-rated current.
The wrong motor rated current is set to E2-01
Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
Check the rated frequency indicated on the motor nameplate.
The maximum output frequency is set
incorrectly
Enter the rated frequency to E1-06 (Base Frequency).
Multiple motors are running off the same drive Set L1-01 to 0 to disable the motor protection function and then install a thermal relay to each motor.
Check the motor characteristics.
The electrical thermal protection
characteristics and motor overload
Correct the type of motor protection that has been selected (L1-01).
characteristics do not match
Install an external thermal relay.
The electrical thermal relay is operating at the Check the current rating listed on the motor nameplate.
wrong level
Check the value set for the motor rated current (E2-01).

190

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Overexcitation increases the motor loss and the motor temperature. Excessive duration of
overexcitation may cause motor damage. Prevent excessive overexcitation operation or apply proper
Motor overheated by overexcitation operation cooling to the motor.
Reduce the excitation deceleration gain (n3-13).
Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
Check values set to Speed Search related parameters.
Parameters related to Speed Search are set
Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively).
incorrectly
After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.
Output current fluctuation due to input phase Check the power supply for phase loss.
loss
Digital Operator Display
oL2

Fault Name
Drive Overload
The thermal sensor of the drive triggered overload protection.

Cause

Possible Solution

Load is too heavy

Reduce the load.

Acceleration or deceleration time is too short Increase the settings for the acceleration and deceleration times (C1-01 through C1-08).
The output voltage is too high

Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
Do not lower E1-08 and E1-10 excessively. This reduces load tolerance at low speeds.

Drive capacity is too small

Replace the drive with a larger model.

Overload occurred when operating at low


speeds

Reduce the load when operating at low speeds.


Replace the drive with a model that is one frame size larger.

Excessive torque compensation

Reduce the torque compensation gain in parameter C4-01 until there is no speed loss but less current.

Parameters related to Speed Search are set


incorrectly

Check the settings for all Speed Search related parameters.


Adjust the current used during Speed Search (b3-03) and the Speed Search deceleration time (b3-02).
After Auto-Tuning, set b3-24 to 1 to enable Speed Estimation Speed Search.

Output current fluctuation due to input phase Check the power supply for phase loss.
loss
Digital Operator Display
oL3

Fault Name
Overtorque Detection 1
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time
(L6-03).

Cause
Parameter settings are not appropriate for the Check L6-02 and L6-03 settings.
load
Fault on the machine side (e.g., machine is
locked up)
Digital Operator Display
oL4

Possible Solution

Check the status of the load. Remove the cause of the fault.
Fault Name
Overtorque Detection 2
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable
time (L6-06).
Possible Solution

Cause
Parameter settings are not appropriate for the Check the settings of parameters L6-05 and L6-06.
load

oL5

Fault Name
Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.
Possible Solution

Troubleshooting

Digital Operator Display

Cause
Overtorque triggered mechanical weakening Identify the cause of mechanical weakening.
detection level set to L6-08

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

191

2.4 Fault Detection


Digital Operator Display

Fault Name
External Digital Operator Connection Fault
The external operator has been disconnected from the drive.

oPr

An oPr fault will occur when all of the following conditions are true:
Output is interrupted when the operator is disconnected (o2-06 = 1).
The Run command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).
Cause
Possible Solution
Check the connection between the operator and the drive.
External operator is not properly connected to Replace the cable if damaged.
the drive
Turn off the drive input power and disconnect the operator. Reconnect the operator and reapply drive
input power.
Digital Operator Display
oS
Cause

Note:

Fault Name
Overspeed (for Control Mode with PG)
The motor speed feedback exceeded the F1-08 setting.
Possible Solution

Overshoot is occurring

Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control
Integral Time 1).
If using Closed Loop Vector mode, enable Feed Forward and perform Inertia Auto-Tuning.

Incorrect speed feedback scaling if terminal


RP is used as speed feedback input in V/f
control

Set H6-02 to the value of the speed feedback signal frequency when the motor runs at the maximum
speed.
Adjust the input signal using parameters H6-03 through H6-05.

Incorrect number of PG pulses has been set


Inappropriate parameter settings

Check and correct parameter F1-01.


Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).

Digital Operator Display

Fault Name
Overvoltage

ov

Voltage in the DC bus has exceeded the overvoltage detection level.


For 400 V class drives: approximately 820 V (740 V when E1-01 is less than 400)
For 575 V class drives: approximately 1040 V
For 690 V class drives: approximately DC1200 V

Cause

Possible Solution

Increase the deceleration time (C1-02, C1-04, C1-06, C1-08).


Deceleration time is too short and regenerative Install a dynamic braking resistor or a dynamic braking resistor unit.
energy is flowing from the motor into the drive Set L3-04 to 1 to enable stall prevention during deceleration. Stall Prevention is enabled as the default
setting.

Fast acceleration time causes the motor to


overshoot the speed reference

Excessive braking load

The braking torque was too high, causing regenerative energy to charge the DC bus. Reduce the braking
torque, use a dynamic braking option, or lengthen decel time.

Surge voltage entering from the drive input


power
Ground fault in the output circuit causes the
DC bus capacitor to overcharge

Check if sudden drive acceleration triggers an overvoltage alarm.


Increase the acceleration time.
Use longer S-curve acceleration and deceleration times.
Enable the Overvoltage Suppression function (L3-11 = 1).
Lengthen the S-curve at acceleration end.

Install a DC link choke.


Note:

Voltage surge can result from a thyristor convertor and phase advancing capacitor using
the same input power supply.

Check the motor wiring for ground faults.


Correct grounding shorts and reapply power.

Check the settings for Speed Search-related parameters.


Improper parameters related to Speed Search Enable Speed Search restart function (b3-19 greater than or equal to 1 to 10).
(including Speed Search after a momentary Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03 respectively).
power loss and after a fault restart)
Perform Stationary Auto-Tuning for line-to-line resistance and then set b3-14 to 1 to enable Speed
Estimation Speed Search.
Drive input power voltage is too high

192

Check the voltage.


Lower drive input power voltage within the limits listed in the specifications.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


The braking transistor or braking resistor are Check braking transistor and braking resistor wiring for errors.
wired incorrectly
Properly rewire the braking resistor device.
PG cable is disconnected

Reconnect the cable.

PG cable wiring is wrong

Correct the wiring.

Noise interference along the PG encoder


wiring

Separate the wiring from the source of the noise. Often, this is the output lines from the drive.

Drive fails to operate properly due to noise


interference

Review the list of possible solutions provided for controlling noise.


Review the section on handling noise interference on page 225 and check the control circuit lines,
main circuit lines, and ground wiring.

Load inertia is set incorrectly

Check the load inertia settings when using KEB, overvoltage suppression, or Stall Prevention during
deceleration.

Braking function is being used in OLV/PM

Connect a braking resistor.

Motor hunting occurs

Adjust the parameters that control hunting.


Set the gain for Hunting Prevention (n1-02).
Adjust the AFR time constant (n2-02 and n2-03).

Digital Operator Display

Fault Name
Input Phase Loss

PF

Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when
L8-05 is set 1 (enabled).

Cause

Possible Solution

There is phase loss in the drive input power

Check for wiring errors in the main circuit drive input power.
Correct the wiring.

There is loose wiring in the drive input power Ensure the terminals are tightened properly.
terminals
Check for loose terminals.
There is excessive fluctuation in the drive
input power voltage

Check the voltage from the drive input power.


Review the possible solutions for stabilizing the drive input power.

There is poor balance between voltage phases Stabilize drive input power or disable phase loss detection.

Digital Operator Display


PGo
Cause
PG cable is disconnected
PG cable wiring is wrong
PG has no power
PG encoder brake is clamped shut
Digital Operator Display
PGoH
Cause
PG cable is disconnected

Check for problems with the drive input power. If drive input power appears normal but the alarm
continues to occur, replace either the control board or the entire drive. For instructions on replacing the
control board, contact Yaskawa or a Yaskawa representative.
Fault Name
PG Disconnect (for any control modes using a PG option card)
No PG pulses are received for longer than the time set to F1-14.
Possible Solution
Reconnect the cable.
Correct the wiring.
Check the power line to the PG encoder.
Ensure the motor brake releases properly.
Fault Name
PG Hardware Fault (detected when using a PG-X3 option card)
PG cable is not connected properly.
Possible Solution
Reconnect the cable and check the setting of F1-20.

Digital Operator Display


PUF
Cause

Troubleshooting

The main circuit capacitors are worn

Check the maintenance time for the capacitors (U4-05).


Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor, contact
Yaskawa or a Yaskawa representative.

Fault Name
Fuse is Open
One of the Module DC Bus Fuses is/are open.

Possible Solution

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

193

2.4 Fault Detection


Main transistor failure, or one or more module Use monitor U2-28 to identify the defective module(s)
DC Bus Fuses is/are open
Replace or repair the defective module..
Digital Operator Display
rF

Fault Name
Braking Resistor Fault
The resistance of the braking resistor is too low.

Cause

Possible Solution

The proper braking resistor option has not


been installed

Select a braking resistor option that it fits the drive braking transistor specification.

Digital Operator Display


rH

Fault Name
Braking Resistor Overheat
Braking resistor protection was triggered.

Cause

Possible Solution

Deceleration time is too short and excessive


regenerative energy is flowing back into the
drive

Check the load, deceleration time, and speed.


Reduce the load inertia.
Increase the deceleration times (C1-02, C1-04, C1-06, C1-08, C1-09).
Replace the dynamic braking option with a larger device that can handle the power that is discharged.

Excessive braking inertia

Recalculate braking load and braking power. Reduce the braking load by adjusting braking resistor
settings.

The braking operation duty cycle is too high Check the braking operation duty cycle. Braking resistor protection for ERF-type braking resistors
The proper braking resistor has not been
installed
Note:

Check the specifications and conditions for the braking resistor device.
Select the optimal braking resistor.

The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more
frequently than its rating permits will trip the alarm even when the braking resistor surface is not very hot.

Digital Operator Display


rr
Cause
The braking transistor is damaged
The control circuit is damaged

Fault Name
Dynamic Braking Transistor
The built-in dynamic braking transistor failed.
Possible Solution
Cycle power to the drive and check for reoccurrence of the fault.
Replace either the control board or the entire drive. For instructions on replacing the control board,
contact Yaskawa or a Yaskawa representative.

Digital Operator Display


SC

<1>

Cause
IGBT fault
IGBT short circuit detection circuit fault

Fault Name
IGBT Short Circuit or Ground Fault
Possible Solution
Check motor wiring.
Turn off the power supply, then turn it on. If the problem continues, contact your Yaskawa
representative or the nearest Yaskawa sales office.

<1> Available in drive software versions 1015 and later for standard A1000 and 1012 and later for A1000 HHP models.
Digital Operator Display

Fault Name
Too Many Speed Search Restarts
SEr
The number of Speed Search restarts exceeded the value set to b3-19.
Cause
Possible Solution
Reduce the detection compensation gain during Speed Search (b3-10).
Parameters related to Speed Search are set to Increase the current level when attempting Speed Search (b3-17).
the wrong values
Increase the detection time during Speed Search (b3-18).
Repeat Auto-Tuning.
The motor is coasting in the opposite direction Set b3-14 to 1 to enable Bi-Directional Speed Search.
of the Run command

194

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Digital Operator Display
SvE
Cause
Torque limit is set too low
Excessive load torque
Noise interference along PG encoder wiring
Digital Operator Display
THo
Cause
The motor thermistor is not connected
properly.

Digital Operator Display


UL3

Fault Name
Zero Servo Fault
Position deviation during zero servo.
Possible Solution
Set the torque limit to an appropriate value using parameters L7-01 to L7-04.
Reduce the amount of load torque.
Check the PG signal for noise interference.
Fault Name
Thermistor Disconnect
The thermistor that detects motor temperature has become disconnected.
Possible Solution
Check the thermistor wiring.

Fault Name
Undertorque Detection 1
The current has fallen below the minimum value set for torque detection (L6-02) for longer than the
allowable time (L6-03).

Cause
Possible Solution
Parameter settings are not appropriate for the Check the settings of parameters L6-02 and L6-03.
load
There is a fault on the machine side
Digital Operator Display
UL4

Check the load for any problems.


Fault Name
Undertorque Detection 2
The current has fallen below the minimum value set for torque detection (L6-05) for longer than the
allowable time (L6-06).

Cause
Parameter settings are not appropriate for the Check L6-05 and L6-06 settings
load
There is a fault on the machine side
Digital Operator Display
UL5

Possible Solution

Check the load for any problems.


Fault Name
Mechanical Weakening Detection 2
The operation conditions matched the conditions set to L6-08.
Possible Solution

Cause
Undertorque was detected and matched the
conditions for mechanical loss detection set to Check the load side for any problems.
L6-08
Digital Operator Display

Cause
The internal current sensor has detected a
current unbalance situation.

Current Unbalance
Current flow has become unbalanced.
Possible Solution
Check wiring
Check for damaged transistors.
Check for short circuits or grounding problems on the connected motor.

Troubleshooting

UnbC

Fault Name

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

195

2.4 Fault Detection


Digital Operator Display

Fault Name
DC Bus Undervoltage

Uv1

Voltage in the DC bus fell below the undervoltage detection level (L2-05).
For 400 V class drives: approximately 380 V (350 V when E1-01 is less than 400)
For 575 V class drives: approximately 475 V
For 690 V class drives: approximately 570 V
The fault is output only if L2-01 is set to 0 or 1 and the DC bus voltage has fallen below the level set to
L2-05 for longer than the time set to L2-02.

Cause

Possible Solution
The main circuit drive input power is wired incorrectly.
Correct the wiring.

Input power phase loss

One of the drive input power wiring terminals Ensure there are no loose terminals.
is loose
Check for loose terminals.
Check the voltage.
There is a problem with the voltage from the Correct the voltage to be within the range listed in drive input power specifications.
drive input power
If there is no problem with the power supply to the main circuit, check for problems with the main
circuit magnetic contactor.
The power has been interrupted

Correct the drive input power.

The main circuit capacitors are worn

Check the maintenance time for the capacitors (U4-05).


Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or a Yaskawa representative.

The relay or contactor on the soft-charge


bypass circuit is damaged

Cycle power to the drive and see if the fault reoccurs.


If the problem continues, replace either the control board or the entire drive. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
Check monitor U4-06 for the performance life of the soft-charge bypass.
Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or a Yaskawa representative.

Digital Operator Display


Uv2
Cause

Fault Name
Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.
Possible Solution

In drive models CIMR-Ao2A0004 to


2A0056 or 4A0002 to 4A0031, L2-02 was
Correct the setting to L2-02 or install an optional Momentary Power Loss Ride-Thru unit.
changed from its default value without
installing a Momentary Power Loss Ride-Thru
unit
Cycle power to the drive. Check if the fault reoccurs.
Control power supply wiring is damaged
If the problem continues, replace the control board, the entire drive, or the control power supply. For
instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.
Cycle power to the drive. Check if the fault reoccurs.
Internal circuitry is damaged
If the problem continues, replace either the control board or the entire drive. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
Digital Operator Display
Uv3
Cause

The relay or contactor on the soft-charge


bypass circuit is damaged

Fault Name
Undervoltage 3 (Soft-Charge Bypass Circuit Fault)
The soft-charge bypass circuit failed.
Possible Solution
Cycle power to the drive and see if the fault reoccurs.
If the problem continues, replace either the control board or the entire drive. For instructions on
replacing the control board, contact Yaskawa or a Yaskawa representative.
Check monitor U4-06 for the performance life of the soft-charge bypass.
Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or a Yaskawa representative.

Digital Operator Display


Uv4

196

Fault Name
Gate Drive Board Undervoltage
Voltage drop in the gate drive board circuit

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.4 Fault Detection


Cause

Possible Solution
Cycle power to the drive and see if the fault reoccurs. Refer to Diagnosing and Resetting Faults on
Not enough power is being supplied to the gate page 218 for details.
drive board.
If the problem continues, replace either the gate drive board or the entire drive. For instructions on
replacing the gate drive board, contact Yaskawa or a Yaskawa representative.

Digital Operator Display

Uv5

Fault Name
MC/FAN power malfunction
Internal drive module MC / FAN power supply does not function properly.

Cause

Possible Solution

Internal drive module MC / FAN power


supply is low.

Power the drive ON/OFF to verify operation.


Refer to the manual section on how to restart the drive after an error.
If the error occurs again replace the defective module or defective circuit board..

Digital Operator Display

Fault Name

Output Voltage Detection Fault


Problem detected with the voltage on the output side of the drive.
Cause
Possible Solution
Hardware is damaged. Internal drive module Lower ambient temperature.
MC / FAN overheat protection circuit board is Replace the control board or the entire drive. For instructions on replacing the control board, contact
due to abnormal ambient operating power.
Yaskawa or a Yaskawa representative..

Troubleshooting

voF

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

197

2.5 Alarm Detection

2.5

Alarm Detection

u Alarm Codes, Causes, and Possible Solutions


Alarms are drive protection functions that do not necessarily cause the drive to stop. Once the cause of an alarm is removed,
the drive will return to the same status is was before the alarm occurred.
When an alarm has been triggered, the ALM light on the digital operator display blinks and the alarm code display flashes. If
a multi-function output is set for an alarm (H2-oo = 10), that output terminal will be triggered.
Note:

If a multi-function output is set to close when an alarm occurs (H2-oo = 10), it will also close when maintenance periods are reached,
triggering alarms LT-1 through LT-4 (triggered only if H2-oo = 2F).
Table 2.11 Alarm Codes, Causes, and Possible Solutions

Digital Operator Display

Minor Fault Name


Communication Option Station Number Setting Error (CC-Link, CANopen, MECHATROLINK-II)
AEr
Option card node address is outside of the acceptable setting range.
Cause
Possible Solutions
Station number is set outside the possible Set parameter F6-10 to the proper value when using a CC-Link option.
setting range.
Set parameter F6-35 to the proper value when using a CANopen option.
Digital Operator Display
bb

Minor Fault Name


Baseblock
Drive output interrupted as indicated by an external baseblock signal.
Possible Solutions

Cause
External baseblock signal was entered via
one of the multi-function input terminals Check external sequence and baseblock signal input timing.
(S1 to S8).
Digital Operator Display
boL
Cause
The proper braking resistor has not been
installed.

Minor Fault Name


Braking Transistor Overload Fault
The braking transistor in the drive has been overloaded.
Possible Solutions
Select the proper braking resistor.

Digital Operator Display

Minor Fault Name


Option Communication Error
bUS
The connection was lost after initial communication was established.
Assign a Run command frequency reference to the option.
Cause
Possible Solutions
Check for faulty wiring.
Connection is broken or master controller Correct the wiring.
stopped communicating.
Check for disconnected cables and short circuits. Repair as needed.
Option is damaged.
If there are no problems with the wiring and the fault continues to occur, replace the option.
The option is not properly connected to the The connector pins on the option are not properly lined up with the connector pins on the drive.
drive.
Reinstall the option.
Check options available to minimize the effects of noise.
Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring.
Try to reduce noise on the controller side.
Use surge absorbers on magnetic contactors or other equipment causing the disturbance.
A data error occurred due to noise.
Use recommended cables or some other type of shielded line. Ground the shield to the controller side or
on the input power side.
Separate the wiring for communication devices from the drive input power lines. Install an EMC noise
filter to the drive input power.

198

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.5 Alarm Detection


Digital Operator Display

Minor Fault Name


Serial Communication Transmission Error
CALL
Communication has not yet been established.
Cause
Possible Solutions
Communications wiring is faulty, there is a Check for wiring errors.
short circuit, or something is not connected Correct the wiring.
properly.
Check for disconnected cables and short circuits. Repair as needed.
Programming error on the master side.
Check communications at start-up and correct programming errors.
Perform a self-diagnostics check.
Communications circuitry is damaged.
If the problem continues, replace either the control board or the entire drive. For instructions on replacing
the control board, contact Yaskawa or your nearest sales representative.
Install
a termination resistor at both ends of a communication line. Set the internal termination resistor switch
Termination resistor setting is incorrect. correctly
on slave drives. Place DIP switch S2 to the ON position.
Digital Operator Display
CE

Minor Fault Name


MEMOBUS/Modbus Communication Error
Control data was not received correctly for two seconds.

Cause

A data error occurred due to noise.

Possible Solutions
Check options available to minimize the effects of noise.
Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground wiring.
Reduce noise on the controller side.
Use surge absorbers for the magnetic contactors or other components that may be causing the disturbance.
Use only recommended shielded line. Ground the shield on the controller side or on the drive input power
side.
Separate all wiring for communication devices from drive input power lines. Install an EMC noise filter
to the drive input power supply.

Communication protocol is incompatible.

Check the H5 parameter settings and the protocol setting in the controller.
Ensure settings are compatible.

The CE detection time (H5-09) is set


shorter than the time required for a
communication cycle to take place.

Check the PLC.


Change the software settings in the PLC.
Set a longer CE detection time using parameter H5-09.

Incompatible PLC software settings or


there is a hardware problem.

Check the PLC.


Remove the cause of the error on the controller side.

Communications cable is disconnected or Check the connector to make sure the cable has a signal.
damaged.
Replace the communications cable.
Digital Operator Display
CrST

Minor Fault Name


Cannot Reset

Possible Solutions

Ensure
that
a
Run
command
cannot
be
entered
from the external terminals or option during fault reset.
Fault reset was being executed when a Run
command was entered.
Turn off the Run command.
Digital Operator Display
dEv

Minor Fault Name


Speed Deviation (when using a PG option card)
The deviation between the speed reference and speed feedback is greater than the setting in F1-10 for longer
than the time in F1-11.
Possible Solutions
Reduce the load.

Cause
Load is too heavy
Acceleration and deceleration times are set Increase the acceleration and deceleration times (C1-01 through C1-08).
too short.
The load is locked up.
Check the machine.
Check the settings of parameters F1-10 and F1-11
Parameter settings are inappropriate.
.
Set H6-02 to value of the speed feedback signal frequency when the motor runs at the maximum speed.
Incorrect speed feedback scaling when
using terminal RP as speed feedback input Adjust the speed feedback signal using parameters H6-03 through H6-05.
Make sure the speed feedback signal frequency does not exceed the maximum input frequency of terminal
in V/f Control.
RP.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

199

Troubleshooting

Cause

2.5 Alarm Detection


The motor brake engaged.

Ensure the brake releases properly.

Digital Operator Display


dFAn

Minor Fault Name


Abnormal Diode Module Fan
Displays when diode converter module(s) has a fan alarm

Cause

Possible Solution

Cycle power to the drive. Check for fan operation..


Check for fan operation.
Diode module cooling fan has malfunctioned Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative operation
time of the fan maintenance timer with U4-04.
If the cooling fan has exceeded its expected performance life or is damaged in any other way, replace
the cooling fan.
Digital Operator Display
dnE
Cause
Drive Enable is set to a multi-function
contact input (H1-oo = 6A) and that
signal was switched off.
Digital Operator Display
EF
Cause
Sequence error

Minor Fault Name


Drive Disabled
Possible Solutions
Check the operation sequence.
Minor Fault Name
Forward/Reverse Run Command Input Error
Both forward run and reverse run closed simultaneously for longer than 0.5 s.
Possible Solutions
Check the forward and reverse command sequence and correct the problem.
Note:

When minor fault EF detected, motor ramps to stop.

Digital Operator Display


EFAn

Minor Fault Name


Abnormal Panel Fan
Displays when the Panel Fan Control detects a fan Alarm

Cause

Possible Solution

Panel fan or panel fan control has


malfunctioned

Cycle power to the drive.


Check for fan operation.
Verify the cumulative operation time of the fan with monitor U4-03, and verify the cumulative operation
time of the fan maintenance timer with U4-04.
If the cooling fan has exceeded its expected performance life or is damaged in any other way, replace
the cooling fan.

Digital Operator Display


EF0

Minor Fault Name


Option Card External Fault
An external fault condition is present.

Cause
Possible Solutions
An external fault was received from the
PLC with F6-03 set to 3, which allows the Remove the cause of the external fault.
drive to continue running after an external Remove the external fault input from the PLC.
fault occurs.
There is a problem with the PLC program. Check the PLC program and correct problems.
Digital Operator Display
EF1
EF2
EF3
EF4

200

Minor Fault Name


External Fault (Input Terminal S1)
External fault at multi-function input terminal S1.
External fault (input terminal S2)
External fault at multi-function input terminal S2.
External fault (input terminal S3)
External fault at multi-function input terminal S3.
External fault (input terminal S4)
External fault at multi-function input terminal S4.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.5 Alarm Detection


EF5
EF6
EF7
EF8
Cause
An external device has tripped an alarm
function.

External fault (input terminal S5)


External fault at multi-function input terminal S5.
External fault (input terminal S6)
External fault at multi-function input terminal S6.
External fault (input terminal S7)
External fault at multi-function input terminal S7.
External fault (input terminal S8)
External fault at multi-function input terminal S8.
Possible Solutions
Remove the cause of the external fault and reset the multi-function input value.

Wiring is incorrect.

Ensure the signal lines have been connected properly to the terminals assigned for external fault detection
(H1-oo = 20 to 2F).
Reconnect the signal line.

Multi-function contact inputs are set


incorrectly.

Check if the unused terminals have been set for H1-oo = 20 to 2F (External Fault).
Change the terminal settings.

Digital Operator Display


FbH

Minor Fault Name


Excessive PID Feedback
The PID feedback input is higher than the level set to b5-36 for longer than the time set to b5-37, and b5-12
is set to 1 or 4.

Cause
Parameter settings for b5-36 and b5-37 are Check parameters b5-36 and b5-37.
incorrect.
PID feedback wiring is faulty.
Feedback sensor has malfunctioned.
Feedback input circuit is damaged.

Correct the wiring.


Check the sensor and replace it if damaged.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.

Digital Operator Display


FbL

Possible Solutions

Minor Fault Name


PID Feedback Loss
The PID feedback input is lower than the level set to b5-13 for longer than the time set to b5-14, and b5-12
is set to 1 or 4.

Cause
Parameter settings for b5-13 and b5-14 are Check parameters b5-13 and b5-14.
incorrect.
PID feedback wiring is faulty.
Feedback sensor has malfunctioned.
Feedback input circuit is damaged.

Correct the wiring.


Check the sensor and replace it if damaged.
Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.

Digital Operator Display


Hbb

Possible Solutions

Minor Fault Name


Input <1>

Safe Disable Signal


Both Safe Disable Input channels are open.

Possible Solutions
Check signal status at the input terminals H1 and H2.
Both Safe Disable Inputs H1 and H2 are Check the Sink/Source Selection for the digital inputs.
open.
If the Safe Disable function is not utilized, determine if terminals H1-HC, and H2-HC are linked.
Internally, both Safe Disable channels are Replace either the control board or the entire drive. For instructions on replacing the control board, contact
broken.
Yaskawa or your nearest sales representative.
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
Digital Operator Display
HbbF

Minor Fault Name

<1>

Safe Disable Signal Input


One Safe Disable channel is open while the other channel is closed.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Troubleshooting

Cause

201

2.5 Alarm Detection


Cause
Possible Solutions
The signals to the Safe Disable inputs are Check signal status at the input terminals H1 and H2. If the Safe Disable function is not utilized, terminals
wrong or the wiring is incorrect.
H1-HC, and H2-HC must be linked.
either the control board or the entire drive. For instructions on replacing the control board, contact
One of the Safe Disable channels is faulty. Replace
Yaskawa or your nearest sales representative.
<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.
Digital Operator Display

Minor Fault Name


Current Alarm
HCA
Drive current exceeded overcurrent warning level (150% of the rated current).
Cause
Possible Solutions
Load is too heavy.
Rreduce the load for applications with repetitive operations (i.e., stops and starts.), or replace the drive.
Calculate the torque required during acceleration and for the inertia moment.
Acceleration and deceleration times are too If the torque level is not right for the load, take the following steps:
short.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Increase the capacity of the drive.
A special-purpose motor is being used, or
Check the motor capacity.
the drive is attempting to run a motor
greater than the maximum allowable
Use a motor appropriate for the drive. Ensure the motor is within the allowable capacity range.
capacity.
The current level increased due to Speed The alarm will only appear briefly. There is no need to take action to prevent the alarm from occurring in
Search after a momentary power loss or
while attempting to perform a fault restart. such instances.
Digital Operator Display
LT-1
Cause
The cooling fan has reached 90% of its
expected performance life.

Minor Fault Name


Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.
Note:

An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and H2-oo =
10) are set.
Possible Solutions

Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor.

Digital Operator Display

Minor Fault Name


Capacitor Maintenance Time

LT-2

The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note:

Cause
The main circuit and control circuit
capacitors have reached 90% of their
expected performance lives.
Digital Operator Display
LT-3

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.


Possible Solutions

Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
Minor Fault Name
Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.
Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.


Cause
Possible Solutions
The DC bus soft charge relay has reached Replace either the control board or the entire drive. For instructions on replacing the control board, contact
90% of expected performance life.
Yaskawa or your nearest sales representative.
Digital Operator Display
LT-4

Minor Fault Name


IGBT Maintenance Time (50%)
IGBTs have reached 50% of their expected performance life.
Note:

Cause

202

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.


Possible Solutions

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.5 Alarm Detection


IGBTs have reached 50% of their expected Check the load, carrier frequency, and output frequency.
performance life.
Digital Operator Display

Minor Fault Name


Heatsink Overheat

oH

The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02 (90-100 C). Default
value for L8-02 is determined by drive capacity (o2-04).

Cause

Possible Solutions

Surrounding temperature is too high

Internal cooling fan has stopped.

Replace the cooling fan.


After replacing the drive, set parameter o4-03 to 0 to reset the cooling fan operation time.

Airflow around the drive is restricted.

Check the surrounding temperature.


Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool surrounding area.
Remove anything near drive that may cause extra heat.

Provide proper installation space around the drive.


Allow for the proper space and ensure that there is sufficient circulation around the control panel.
Check for dust or other foreign materials clogging the cooling fan.
Clear debris caught in the fan that restricts air circulation.

Digital Operator Display


oH2
Cause
An external device triggered an overheat
warning in the drive.

Minor Fault Name


Drive Overheat Warning
Drive Overheat Warning was input to a multi-function input terminal, S1 through S8 (H1-oo= B).
Possible Solutions
Search for the device that tripped the overheat warning. Remove the cause of the problem.

Digital Operator Display


oH3

Minor Fault Name


Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02,
H3-06 or H3-10 = E).

Cause
Motor thermostat wiring is faulty (PTC
input).

Possible Solutions
Repair the PTC input wiring.

There is a fault on the machine side (e.g.,


the machine is locked up).

Check the status of the machine.


Remove the cause of the fault.

Note:

Motor has overheated.

oH5

Motor has overheated.

Refrain from lowering E1-08 and E1-10 excessively to prevent a reduction in load tolerance
at low speeds.
Check the motor-rated current.
Enter motor-rated current on motor nameplate (E2-01).
Ensure the motor cooling system is operating normally.
Repair or replace the motor cooling system.

Minor Fault Name


Motor Overheat (NTC Input)
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2)
Possible Solutions
Reduce the load.
Check the ambient temperature.

Troubleshooting

Digital Operator Display

Cause

Check the load size, accel/decel times, and cycle times.


Decrease the load.
Increase accel and decel times (C1-01 to C1-08).
Adjust the preset V/f pattern (E1-04 through E1-10). This involves reducing E1-08 and E1-10.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

203

2.5 Alarm Detection


Digital Operator Display

There is a fault on the machine side (e.g.,


the machine is locked up).

Minor Fault Name


Overtorque 1
Drive output current (or torque in OLV, CLV, AOLV/PM, and CLV/PM) was greater than L6-02 for longer
than the time set to L6-03.
Possible Solutions
Check parameters L6-02 and L6-03.
Check the status of the machine.
Remove the cause of the fault.

Digital Operator Display

Minor Fault Name

oL3
Cause
Inappropriate parameter settings.

oL4
Cause
Parameter settings are not appropriate.
There is a fault on the machine side (e.g.,
the machine is locked up).
Digital Operator Display
oL5

Overtorque 2
Drive output current (or torque in OLV, CLV, AOLV/PM, CLV/PM) was greater than L6-05 for longer than
the time set to L6-06.
Possible Solutions
Check parameters L6-05 and L6-06.
Check the status of the machine being used.
Remove the cause of the fault.
Minor Fault Name
Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.
Possible Solutions

Cause
Overtorque occurred, triggering the
mechanical weakening level set to L6-08. Check for the cause of mechanical weakening.
Digital Operator Display
oS
Cause
Overshoot is occurring.

Minor Fault Name


Overspeed (for Control Mode with PG)
The motor speed feedback exceeded the F1-08 setting.
Possible Solutions
Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control
Integral Time 1).
If using a Closed Loop Vector mode enable Feed Forward Control and perform Inertia Auto-Tuning.

Incorrect speed feedback scaling if terminal Set H6-02 to value of the speed feedback signal frequency when the motor runs at the maximum speed.
RP is used as speed feedback input in V/f
Adjust the input signal using parameters H6-03 through H6-05.
control
Incorrect PG pulse number has been set
Inappropriate parameter settings.

Check and correct parameter F1-01.


Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).

Digital Operator Display

Minor Fault Name


DC Bus Overvoltage

ov

The DC bus voltage exceeded the trip point.


For 400 V class drives: approximately 820 V (740 V when E1-01 is less than 400)
For 575 V class drives: approximately 1040 V
For 690 V class drives: approximately 1200 V

Cause
Surge voltage present in the drive input
power.

Possible Solutions
Install a DC link choke or an AC reactor.
Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on the same
drive input power system.

The motor is short-circuited.

Check the motor power cable, relay terminals and motor terminal box for short circuits.
Ground current has overcharged the main Correct grounding shorts and turn the power back on.
circuit capacitors via the drive input power.

Noise interference causes the drive to


operate incorrectly.

Review possible solutions for handling noise interference.


Review section on handling noise interference and check control circuit lines, main circuit lines and ground
wiring.
If the magnetic contactor is identified as a source of noise, install a surge protector to the MC coil.
Set number of fault restarts (L5-01) to a value other than 0.

PG cable is disconnected.

204

Reconnect the cable.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.5 Alarm Detection


PG cable wiring is wrong.

Correct the wiring.

Noise interference along PG encoder


wiring.

Separate PG wiring from the source of the noise (often output wiring from the drive).

Digital Operator Display


PASS
Cause
MEMOBUS/Modbus test has finished
normally.

Minor Fault Name


MEMOBUS/Modbus Comm. Test Mode Complete
Possible Solutions
This verifies that the test was successful.

Digital Operator Display

Minor Fault Name


PG Disconnect (for Control Mode with PG)
PGo
Detected when no PG pulses are received for a time longer than setting in F1-14.
Cause
Possible Solutions
PG cable is disconnected.
Reconnect the cable.
PG cable wiring is wrong.
Correct the wiring.
PG encoder does not have enough power. Make sure the correct power supply is properly connected to the PG encoder.
Brake is holding the PG.
Ensure the brake releases properly

PGoH
Cause
PG cable is disconnected.

Minor Fault Name


PG Hardware Fault (detected when using a PG-X3 option card)
PG cable has become disconnected.
Possible Solutions
Reconnect the cable and check the setting of F1-20.

Digital Operator Display


rUn
Cause
A motor switch command was entered
during run.
Digital Operator Display
SE
Cause
A digital input set to 67H (MEMOBUS/
Modbus test) was closed while the drive
was running.
Digital Operator Display
THo
Cause
The motor thermistor is not connected
properly.

Minor Fault Name


Motor Switch during Run
A command to switch motors was entered during run.
Possible Solutions
Change the operation pattern so that the motor switch command is entered while the drive is stopped.
Minor Fault Name
MEMOBUS/Modbus Communication Test Mode Error
Note:

This alarm will not trigger a multi-function output terminal that is set for alarm output
(H2-oo = 10).
Possible Solutions

Stop the drive and run the test again.


Minor Fault Name
Thermistor Disconnect
The thermistor used to detect motor temperature has become disconnected.
Possible Solutions
Check the thermistor wiring.

Digital Operator Display


TrPC

Troubleshooting

Digital Operator Display

Minor Fault Name


IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
Possible Solutions

Cause
IGBTs have reached 90% of their expected Replace the drive.
performance life.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

205

2.5 Alarm Detection


Digital Operator Display
UL3
Cause
Inappropriate parameter settings.
Load has dropped or decreased
significantly.
Digital Operator Display
UL4
Cause
Inappropriate parameter settings.
The load has dropped or decreased
significantly.

Minor Fault Name


Undertorque Detection 1
Drive output current (or torque in OLV, CLV, AOLV/PM, and CLV/PM) less than L6-02 for longer than
L6-03 time.
Possible Solutions
Check parameters L6-02 and L6-03.
Check for broken parts in the transmission system.
Minor Fault Name
Undertorque Detection 2
Drive output current (or torque in OLV, CLV, AOLV/PM, and CLV/PM) less than L6-05 for longer than
L6-06 time.
Possible Solutions
Check parameters L6-05 and L6-06.
Check for broken parts in the transmission system.

Digital Operator Display

Minor Fault Name


Undervoltage

Uv

One of the following conditions was true when the drive was stopped and a Run command was entered:
DC bus voltage dropped below the level specified in L2-05.
Contactor to suppress inrush current in the drive was opened.
Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage
is under L2-05.

Cause

Possible Solutions

Phase loss in the drive input power.

Check for wiring errors in the main circuit drive input power. Correct the wiring.

Loose wiring in the drive input power


terminals.

Check for loose terminals.


Ensure the terminals have been properly tightened.
Apply the tightening torque to the terminals.

There is a problem with the drive input


power voltage.

Check the voltage.


Lower the voltage of the drive input power so that it is within the limits listed in the specifications.

Drive internal circuitry is worn.

Check the maintenance time for the capacitors (U4-05).


Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on replacing
the control board, contact Yaskawa or your nearest sales representative.

The drive input power transformer is too Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed.
small and voltage drops when the power is
Check the capacity of the drive input power transformer.
switched on.
Air inside the drive is too hot.

Check the temperature inside the drive.

The CHARGE light is broken or


disconnected.

Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.

Digital Operator Display


voF
Cause
Hardware is damaged.

206

Minor Fault Name


Output Voltage Detection Fault
There is a problem with the output voltage.
Possible Solutions
Replace either the control board or the entire drive. For instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.6 Operator Programming Errors

2.6

Operator Programming Errors

u Operator Programming Error Codes, Causes, and Possible Solutions


An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to an
inappropriate value.
The drive will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however, does not
trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to Table 2.12 for the appropriate action. When
an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is causing the oPE.
Table 2.12 oPE Codes, Causes, and Possible Solutions
Digital Operator Display
oPE01
Cause
The drive model selection (o2-04) and the actual capacity of the drive are
not the same.

Error Name
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Possible Solutions
Correct the value set to o2-04.

Digital Operator Display

Error Name
Parameter Range Setting Error
oPE02
Use U1-18 to find parameters set outside the range.
Cause
Possible Solutions
Parameters were set outside the possible setting range.
Set parameters to the proper values.
Note:
When multiple errors occur simultaneously, other errors are given precedence over oPE02.
Digital Operator Display
oPE03
Cause
The same function is assigned to two multi-function inputs.
Excludes Not used and External Fault.

Error Name
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01
to H1-08.
Possible Solutions
Ensure all multi-function inputs are assigned to different functions.
Re-enter the multi-function settings to ensure this does not occur.

The Up command was set but the Down command was not, or vice versa
(settings 10 vs. 11).

Properly set the functions that required for use in combination with other
The Up 2 command was set but the Down 2 command was not, or vice versa functions.
(settings 75 vs. 76).
Properly set the functions that required for use in combination with other
functions.

Check if contradictory settings have simultaneously been assigned to the


multi-function input terminals.
Correct setting errors.

Set b5-01 to 0 to disable control PID or disable the Up/Down command.


Troubleshooting

Run/Stop command for a 2-wire sequence was set (H1-oo = 42), but
Forward/Reverse command (H1-oo = 43) was not.
Drive Enable is set to multi-function input S1 or S2 (H1-01 = 6A or
H1-02 = 6A).
Two of the following functions are set simultaneously:
Up/Down Command (10 vs. 11)
Up 2/Down 2 Command (75 vs. 76)
Hold Accel/Decel Stop (A)
Analog Frequency Reference Sample/Hold (1E)
Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
The Up/Down command (10, 11) and PID control (b5-01) are enabled
simultaneously.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

207

2.6 Operator Programming Errors


Settings for N.C. and N.O. input for the following functions were selected
simultaneously:
External Search Command 1 and External Search Command 2 (61 vs. 62)
Fast Stop N.O. and Fast Stop N.C. (15 vs. 17)
KEB for Momentary Power Loss and High Slip Braking
Check if contradictory settings have simultaneously been assigned to the
(65, 66 vs. 68)
multi-function input terminals.
Motor Switch Command and Accel/Decel Time 2 (16 vs. 1A)
Correct setting errors.
FWD Run Command (or REV) and FWD/REV Run Command (2-wire)
(40, 41 vs. 42, 43)
External DB Command and Drive Enable (60 vs. 6A)
Motor Switch Command and Up 2/Down 2 Command (16 vs. 75, 76)
One of the following settings was entered while H1-oo = 2 (External
Reference 1/2):
b1-15 = 4 (Pulse Train Input) but the pulse train input selection is not set
for the frequency reference (H6-01 > 0)
b1-15 or b1-16 set to 3 but no option card is connected
Although b1-15 = 1 (Analog Input) and H3-02 or H3-10 are set to 0
Correct the settings for the multi-function input terminal parameters.
(Frequency Bias)
H2-oo is set to 38 (Drive Enabled) and H1-oo is not set to 6A (Drive
Enable).
H1-oo is set to 7E (Direction Detection) and H6-01 is not set to 3 (for V/f
Control with PG using terminal RP as speed feedback input).
Digital Operator Display

Error Name
oPE04

Initialization Required

Cause
The drive, control board, or terminal board have been replaced and the
parameter settings between the control board and the terminal board no
longer match.

Possible Solutions
Set A1-03 to 555o to load the parameter settings stored in the terminal board
to the drive. Initialize parameters after drive replacement by setting A1-03
to 1110 or 2220.

Digital Operator Display

Error Name
oPE05

Run Command/Frequency Reference Source Selection Error

Cause
Frequency reference is assigned to an option card (b1-01 = 3) and an input
option card is not connected to the drive.
The Run command is assigned to an option card (b1-02 = 3) and an input
option card is not connected to the drive.
Frequency reference is assigned to the pulse train input (b1-01 = 4) and
terminal RP is not set for frequency reference input (H6-01 > 0)
Although the digital card input is set for BCD special for a 5-digit input
(F3-01 = 6), the data length is set for 8-bit or 12-bit (F3-03 = 0, 1).
The following values have been set while an AI-A3 option card is installed:
The source of frequency reference setting is assigned to an option card
(b1-01 = 3).
The action for the analog card is set for separate terminal input
(F2-01 = 0).
Digital Operator Display
oPE06
Cause
A control mode has been selected that requires a PG option card to be
installed, but no PG encoder is installed (A1-02 = 1, 3).
Digital Operator Display
oPE07
Cause

208

Possible Solutions
Reconnect the input option card to the drive.

Set H6-01 to 0.
Set F3-03 to 2 to set the input data for 16-bit.

Properly set parameters.

Error Name
Control Method Selection Error
Correct the setting for the control method.
Possible Solutions
Connect a PG option card.
Correct the value set to A1-02.
Error Name
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02,
H3-06, or H3-10 and PID functions conflict.
Possible Solutions

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.6 Operator Programming Errors


Change the settings to H3-02, H3-06, and H3-10 so that functions no longer
At least two analog input terminals are set to the same function (i.e., at least conflict.
two of these parameters have the same setting: H3-02, H3-06, or H3-10).
Note:
Both 0 (Frequency Reference Bias) and F (Not Used) can be
set to H3-02, H3-06, and H3-10 simultaneously.
The following simultaneous contradictory settings:
H3-02, H3-06, or H3-10 = B (PID Feedback) while H6-01
(Pulse Train Input) = 1 (PID Feedback)
H3-02, H3-06, or H3-10 = C (PID Target Value) while H6-01 = 2
(pulse train input sets the PID target value)
Disable one of the PID selections.
H3-02, H3-06, or H3-10 = C (PID Target Value) while b5-18 = 1
(enables b5-19 as the target PID value)
H6-01 = 2 (PID target) while b5-18 = 1
(enables b5-19 as the target PID value)
Digital Operator Display
oPE08
Cause
Attempted to use a function that is not valid for the selected control mode.
In OLV, n2-02 is longer than n2-03
In OLV, C4-02 is longer than C4-06
The following settings have occurred in OLV/PM:
E5-03 does not equal 0
E5-09 and E5-24 are both equal to 0, or neither equals 0

Error Name
Parameter Selection Error
A function has been set that cannot be used in the motor control method
selected.
Possible Solutions
Check the motor control method and the functions available.
Adjust parameter values so n2-02 is shorter than n2-03.
Adjust parameter values so C4-02 is shorter than C4-06.
Set E5-09 or E5-24 to the correct value, and set the other to 0.
Set the motor rated current for PM to 0 (E5-03).

b1-14 (Phase Order Selection) is set to 1 (Switch phase order) when using a Correct the parameter settings.
PG option card.
Note:

Use U1-18 to find parameters that are set outside the specified setting range. When multiple errors occur simultaneously, other errors are
given precedence over oPE08.
Digital Operator Display
oPE09

Error Name
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is
enabled (b5-01 = 1 to 4).

Cause
Possible Solutions
The following simultaneous contradictory settings have occurred:
Set b5-15 to a value other than 0.0.
b5-15 is not set to 0.0 (PID Sleep Function Operation Level)
The stopping method is set to either DC Injection Braking or coast to stop Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
with a timer (b1-03 = 2 or 3).

Digital Operator Display

oPE10

Cause
V/f pattern setting error.

Correct the parameter settings.


Correct the parameter settings.
Error Name
V/f Data Setting Error
One of the following setting errors has occurred:
E1-04 E1-06
E1-06 E1-07
E1-07 E1-09
or E1-09 E1-11
E3-04 E3-06
E3-06 E3-07
E3-07 E3-09
or E3-09 E3-11
Possible Solutions
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.
For motor 2, correct E3-04, E3-06, E3-07, E3-09, and E3-11.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Troubleshooting

b5-01 is set to 1 or 2, enabling PID control, but the lower limit for the
frequency reference (d2-02) is not set to 0 while reverse output is enabled
(b5-11 = 1).
b5-01 is set to 3 or 4, enabling PID control, but the lower limit for the
frequency reference (d2-01) is not 0.

209

2.6 Operator Programming Errors


Digital Operator Display

Error Name
Pulse Monitor Selection Error
oPE13
Incorrect setting of monitor selection for pulse train (H6-06).
Cause
Possible Solutions
Scaling for the pulse train monitor is set to 0 (H6-07 = 0) while H6-06 is not Change scaling for the pulse train monitor or set H6-06 to 101, 102, 105,
set to 101, 102, 105, or 116.
or 116.
Digital Operator Display

Error Name
Torque Control Setting Error
Parameter settings that are not allowed in combination with Torque Control
have been set.
Possible Solutions

oPE15

Cause
Torque Control is enabled (d5-01 = 1) while the Speed/Torque Control
switch function is assigned to a digital input (H1-oo = 71).
Either d5-01 is set to 1 to enable Torque Control, or the Speed/Torque Control
switch is assigned to a digital input H1-oo = 71, while at the same time: Correct the parameter settings.
Droop Control is enabled (b7-01 0), or
Intelligent Stall Prevention or Intelligent Stall Prevention 2 is enabled
(L3-04 = 2 or 5), or
Digital Operator Display

Error Name
oPE16

Energy Savings Constants Error

Cause
In AOLV/PM, the automatically calculated energy saving coefficients are
out of the allowable range.
Digital Operator Display
oPE18

Possible Solutions
Check and correct the motor data in E5 parameters.
Error Name
Online Tuning Parameter Setting Error
Parameters controlling online tuning are not set correctly.
Possible Solutions

Cause
One of the following errors occurred while online tuning was enabled in OLV
(A1-02 = 2):
E2-02 was set below 30% of the original default value
Set E2-02, E2-03, and E2-06 to the correct values.
E2-06 was set below 50% of the original default value
E2-03 = 0

210

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.7 Auto-Tuning Fault Detection

2.7

Auto-Tuning Fault Detection

When the Auto-Tuning faults shown below are detected, the fault is displayed on the operator and the motor coasts to a stop.
Auto-Tuning faults do not trigger a multi-function terminal set for fault or alarm output.
An Endo error indicates that although Auto-Tuning has successfully completed, there is some discrepancy in the calculations.
If an Endo error occurs, check for the cause of the error using the table below, and perform Auto-Tuning again after fixing
the problem. Start the application if no problem can be diagnosed despite the existence of the Endo error.

u Auto-Tuning Codes, Causes, and Possible Solutions


Table 2.13 Auto-Tuning Codes, Causes, and Possible Solutions
Digital Operator Display

Error Name
Excessive
V/f
Setting
(detected
only
during
Rotational
Auto-Tuning and displayed after Auto-Tuning is
End1
complete)
Cause
Possible Solutions
The torque reference exceeded 20% during Prior to Auto-Tuning, verify the information on the motor nameplate.
Auto-Tuning.
Enter proper values from motor nameplate to parameters T1-03 to T1-05 and repeat Auto-Tuning.
The results from Auto-Tuning the no-load If possible, disconnect the motor from the load and perform Auto-Tuning. If the load cannot be uncoupled,
current exceeded 80%.
use the current Auto-Tuning results.
Digital Operator Display
End2
Cause
Motor data entered during Auto-Tuning
was incorrect.

Error Name
Motor Iron-Core Saturation Coefficient (detected only during Rotational Auto-Tuning and displayed after
Auto-Tuning is complete)
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the


parameter setting range, assigning the iron- Check and correct faulty motor wiring.
core saturation coefficients (E2-07 and
Disconnect the motor from machine and perform Rotational Auto-Tuning.
E2-08) to temporary values.
Digital Operator Display
End3
Cause
The correct current rating printed on the
motor nameplate was not entered into
T1-04.

Error Name
Rated Current Setting Alarm (displayed after Auto-Tuning is complete)
Possible Solutions
Check the setting of parameter T1-04.
Check the motor data and repeat Auto-Tuning.

Digital Operator Display


End4

Error Name
Adjusted Slip Calculation Error

Cause

Possible Solutions

Make
sure
the
data
entered
for
Auto-Tuning
is correct.
The calculated slip is outside the allowable
range.
If possible, perform Rotational Auto-Tuning. If not possible, perform Stationary Auto-Tuning 2.
Digital Operator Display

The calculated resistance value is outside


the allowable range.

Resistance Tuning Error


Possible Solutions
Double-check the data entered for the Auto-Tuning process.
Check the motor and motor cable connection for faults.

Digital Operator Display


End6

Troubleshooting

End5
Cause

Error Name

Error Name
Leakage Inductance Alarm

Cause
Possible Solutions
The calculated leakage inductance value is Double-check the data entered for the Auto-Tuning process.
outside the allowable range.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

211

2.7 Auto-Tuning Fault Detection


Digital Operator Display
End7

Error Name
No-Load Current Alarm

Cause

Possible Solutions

The entered no-load current value was


Check and correct faulty motor wiring.
outside the allowable range.
Auto-Tuning results were less than 5% of Double-check the data entered for the Auto-Tuning process.
the motor rated current.
Digital Operator Display
Er-01
Cause
Motor data or data entered during
Auto-Tuning was incorrect
.

Error Name
Motor Data Error
Possible Solutions
Check that the motor data entered to T1 parameters matches motor nameplate input before Auto-Tuning.
Restart Auto-Tuning and enter the correct information.

Motor output power and motor-rated


Check the drive and motor capacities.
current settings (T1-02 and T1-04) do not
Correct the settings of parameters T1-02 and T1-04.
match.
Motor rated current and detected no-load Check the motor rated current and no-load current.
current are inconsistent.
Correct the settings of parameters T1-04 and E2-03.
Correct the settings of parameters T1-05 and T1-07.
Base frequency and motor rated speed
(T1-05 and T1-07) do not match.
Check that the correct number of poles were entered to T1-06.
Digital Operator Display
Er-02
Cause
An alarm was triggered during AutoTuning.

Error Name
Minor Fault
Possible Solutions
Exit the Auto-Tuning menu, check the alarm code, remove the alarm cause, and repeat Auto-Tuning.

Digital Operator Display


Er-03
Cause
Auto-Tuning canceled by pressing STOP
button.

Error Name
STOP Button Input
Possible Solutions
Auto-Tuning did not complete properly. Restart Auto-Tuning.

Digital Operator Display


Er-04
Cause
Motor data entered during Auto-Tuning
was incorrect.

Error Name
Line-to-Line Resistance Error
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the


parameter setting range or the tuning
Check and correct faulty motor wiring.
process took too long.
Faulty motor cable or cable connection.
Digital Operator Display
Er-05
Cause
Motor data entered during Auto-Tuning
was incorrect.

Error Name
No-Load Current Error
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the Check and correct faulty motor wiring.
parameter setting range or the tuning
Perform Rotational Auto-Tuning.
process took too long.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make
The load was too high during Rotational
sure the load is lower than 30%.
Auto-tuning.
If a mechanical brake is installed, make sure it is fully lifted during tuning.

212

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.7 Auto-Tuning Fault Detection


Digital Operator Display
Er-08
Cause
Motor data entered during Auto-Tuning
was incorrect.

Error Name
Rated Slip Error
Possible Solutions
Make sure the data entered to the T1 parameters match the information written on the motor nameplate.
Restart Auto-Tuning and enter the correct information.

Results from Auto-Tuning are outside the Check and correct faulty motor wiring.
parameter setting range or the tuning
Perform Rotational Auto-Tuning.
process took too long.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make
The load was too high during rotational
sure the load is lower than 30%.
Auto-tuning.
If a mechanical brake is installed, make sure it is fully lifted during tuning.
Digital Operator Display
Er-09
Cause
The motor did not accelerate for the
specified acceleration time.
Torque limit when motoring is too low
(L7-01 and L7-02).
The load was too high during Rotational
Auto-Tuning.

Error Name
Acceleration Error
Possible Solutions
Increase the acceleration time (C1-01).
Disconnect the machine from the motor if possible.
Check L7-01 and L7-02 settings.
Increase the setting.
Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be uncoupled make
sure the load is lower than 30%.
If a mechanical brake is installed, make sure it is fully lifted during tuning.

Digital Operator Display


Er-10

Error Name
Motor Direction Error

Cause
The encoder signal lines are not properly
connected to the drive.

Possible Solutions
Check and correct wiring to the PG encoder.

Motor direction and PG direction are


opposite.

Check the motor speed monitor U1-05 while manually turning the motor forward. If the sign displayed is
negative, change the setting of parameter F1-05.

The load pulled the motor in the opposite


direction of the speed reference and the
Uncouple the motor from the load and restart Auto-Tuning.
torque exceeded 100%.
Digital Operator Display
Er-11

Possible Solutions
Increase the acceleration time (C1-01).
Disconnect the machine from the motor if possible.

Torque reference is too high.


Digital Operator Display
Er-12

Error Name
Current Detection Error

Cause
Possible Solutions
One of the motor phases is missing:
Check motor wiring and correct any problems.
(U/T1, V/T2, W/T3).
The current exceeded the current rating of Check motor wiring for a short between motor lines.
the drive.
Close any magnetic contactors used between motors.
Replace the control board or the entire drive. For instructions on replacing the control board, contact
The current is too low.
Yaskawa or your nearest sales representative.
Attempted Auto-Tuning without motor
Connect the motor and restart Auto-Tuning.
connected to the drive.
Replace the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa
Current detection signal error.
or your nearest sales representative.

Troubleshooting

Cause

Error Name
Motor Speed Fault

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

213

2.7 Auto-Tuning Fault Detection


Digital Operator Display
Er-13

Error Name
Leakage Inductance Error

Cause

Possible Solutions

Drive was unable to complete tuning for


leakage inductance within 300 seconds.

Check all wiring and correct any mistakes.


Check the motor rated current value written on the motor nameplate and enter the correct value to T1-04.

Digital Operator Display


Er-14

Error Name
Motor Speed Error 2

Cause
The motor speed exceeded twice the
amplitude of speed reference during Inertia Reduce the ASR gain set to C5-01.
Tuning.
Digital Operator Display
Er-15

Possible Solutions

Error Name
Torque Saturation Error

Cause
Possible Solutions
The output torque reached the torque limit
set in L7-01 through L7-04 during Inertia Increase the torque limits in L7-01 through L7-04 within reasonable limits.
Tuning.
Digital Operator Display
Er-17

Error Name
Reverse Prohibited Error

Cause

Possible Solutions

Inertia
Auto-Tuning
cannot
be
performed
if the drive is restricted from rotating in reverse.
Drive is prohibited from rotating the motor
in reverse while attempting to perform
Assuming it is acceptable for the application to rotate in reverse, set b1-04 to 0 and then pertorm Inertia
Inertia Tuning.
Tuning.
Digital Operator Display
Er-18

Error Name
Induction Voltage Error

Cause
Possible Solutions
The result of Back EMF Constant Tuning
(induced voltage) exceeds the allowable Double-check the data entered to the T2-oo parameters and restart Auto-Tuning.
setting range.
Digital Operator Display
Er-19

Error Name
PM Inductance Error

Cause
Possible Solutions
The induced voltage constant attempted to
set a value to E5-08 or E5-09 that is outside Double-check the data entered to the T2-oo parameters and restart Auto-Tuning.
the allowable range.
Digital Operator Display
Er-20

Error Name
Stator Resistance Error

Cause
Possible Solutions
Stator resistance tuning attempted to set a
value to E5-06 that is outside the allowable Double-check the data entered to the T2-oo parameters and restart Auto-Tuning.
setting range.

214

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.7 Auto-Tuning Fault Detection


Digital Operator Display
Er-21

Z Pulse Correction Error


Possible Solutions
Make sure the motor has stopped completely. Restart Auto-Tuning.
Check the wiring for the motor and the PG encoder. Restart Auto-Tuning.
Check the direction and number of pulses set for the PG encoder. Restart Auto-Tuning.
Check the signal output from the PG encoder attached to the motor. Replace the PG if damaged.

Troubleshooting

Cause
Motor was coasting when Auto-Tuning
was performed.
Either the motor or the PG encoder on the
motor are not properly wired.
The direction for the PG encoder is set
incorrectly, or the number of pulses set for
the PG encoder is wrong.
PG encoder is damaged.

Error Name

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

215

2.8 Copy Function Related Displays

2.8

Copy Function Related Displays

u Tasks, Errors, and Troubleshooting


The table below lists the messages and errors that may appear when using the Copy function.
When executing the tasks offered by the Copy function, the operator will indicate the task being performed. When an error
occurs, a code appears on the operator to indicate the error. Note that errors related to the Copy function do not trigger a multifunction output terminal that has been set up to close when a fault or alarm occurs. To clear an error, simply press any key on
the operator and the error display will disappear.
Table 2.14 lists the corrective action that can be taken when an error occurs.
Note:

1. Whenever using the copy function, the drive should be fully stopped.
2. The drive will not accept a Run command while the Copy function is being executed.
3. Parameters can only be saved to a drive when the voltage class, capacity, control mode, and software version match.
Table 2.14 Copy Function Task and Error Displays
Digital Operator Display
CoPy

Cause
Parameters are being written to the drive.

Task
Writing Parameter Settings (flashing)
Possible Solutions
This is not an error.

Digital Operator Display


CPEr

Task
Control Mode Mismatch

Cause

Possible Solutions

Verify
the
control
mode
for
the
parameters
to be loaded onto the drive and the control mode on
Control mode of the parameters to be loaded onto
drive to which those parameters will be written.
the drive and the control mode set to the drive do
not match.
Set the same control mode using parameter A1-02 and retry.
Digital Operator Display
CPyE
Cause
Failed writing parameters

Task
Error Writing Data
Possible Solutions
Attempt to write parameters again.

Digital Operator Display


CSEr
Cause

Task
Copy Unit Error
Possible Solutions
Replace the operator or the USB Copy Unit.

Hardware fault
Digital Operator Display
dFPS

Task
Drive Model Mismatch

Cause
Possible Solutions
The drives used in the copy and write process are
not the same model.
Verify the model number of the drive from which the parameters were copied and the model of
the drive to which those parameters will be written.
The drive from which the parameters were
copied is a different model.
Make sure the two drives are the same model and have the same software version.
The drive to be written to is a different model.
Digital Operator Display
End

Task
Task Complete

Cause
Finished reading, writing, or verifying parameters. This is not an error.
Digital Operator Display
iFEr

Task
Communication Error

Cause
A communication error occurred between the drive Check the cable connection.
and the operator or the USB copy unit.

216

Possible Solutions

Possible Solutions

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.8 Copy Function Related Displays


A non-compatible cable is being used to connect
the USB Copy Unit and the drive.

Use the cable originally packaged with the USB Copy Unit.

Digital Operator Display


ndAT

Task
Model, Voltage Class, Capacity Mismatch

Cause

Possible Solutions

The drive from which the parameters were copied


and the drive to which the parameters will be
written have different electrical specifications,
Make sure model numbers and specifications are the same for both drives.
capacities, are set to different control modes, or are
different models.
The device being used to write the parameters is Make sure all connections are correct, and copy the parameter settings onto the USB Copy Unit or
blank and does not have any parameters saved on the operator.
it.
Digital Operator Display
rdEr

Task
Error Reading Data

Cause

Possible Solutions

Failed while attempting to read parameter settings Press and hold the READ key on the USB Copy Unit for at least one second to have the unit read
from the drive.
parameters from the drive.
Digital Operator Display
rEAd
Cause
Displayed while the parameter settings are being
read onto the USB Copy Unit.

Task
Reading Parameter Settings (flashing)
Possible Solutions
This is not an error.

Digital Operator Display


vAEr

Task
Voltage Class, Capacity Mismatch

Cause
Possible Solutions
The drive from which the parameters were copied
and the drive on which the Verify mode is being Make sure electrical specifications and capacities are the same for both drives.
performed have different electrical specifications
or are a different capacity.
Digital Operator Display
vFyE
Cause
Indicates that parameter settings that have been
Read and loaded onto the Copy Unit or Digital
Operator are different.

Task
Parameter settings in the drive and those saved to the copy function are not the same
Possible Solutions
To synchronize parameters, either write the parameters saved on the USB Copy Unit or digital
operator onto the drive, or Read the parameter settings on the drive onto the USB Copy Unit.

Digital Operator Display


vrFy

Task
Comparing Parameter Settings (flashing)
Possible Solutions

Troubleshooting

Cause
The Verify mode has confirmed that parameters
settings on the drive and parameters read to the copy This is not an error.
device are identical.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

217

2.9 Diagnosing and Resetting Faults

2.9

Diagnosing and Resetting Faults

When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault, then
restart the drive.
Note:

An oC/SC fault will be displayed in the event of an IGBT failure. It may not be possible to reset this fault until the IGBT problem is corrected.

u Fault Occurs Simultaneously with Power Loss


WARNING! Electrical Shock Hazard. Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or between
the ground and main circuit terminals before restarting the drive. Failure to comply may result in serious injury or death and will cause
damage to equipment.

1.
2.
3.

Note:

Turn on the drive input power.


Use monitor parameters U2-oo to display data on the operating status of the drive just before the fault occurred.
Remove the cause of the fault and reset.
1. To find out what faults were triggered, check the fault history in U2-02. Information on drive status when the fault occurred
such as the frequency, current, and voltage can be found in U2-03 through U2-20. Refer to Viewing Fault Trace Data
After Fault on page 218 for information on how to view fault data.
2. When the fault continues to be displayed after cycling power, remove the cause of the fault and reset.

u If the Drive Still has Power After a Fault Occurs


1.
2.
3.

Look at the digital operator for information on the fault that occurred.
Refer to Fault Displays, Causes, and Possible Solutions on page 180.
Reset the fault. Refer to Fault Reset Methods on page 219.

u Viewing Fault Trace Data After Fault


Step

Display/Result
- MODE - DRV Rdy
FREF (OPR)
U1-01= 0.00Hz

1. Turn on the drive input power. The first screen displays.

2. Press

3. Press

U1-02= 0.00Hz LSEQ


U1-03= 0.00A LREF
JOG FWD FWD/REV
- MODE - DRV Rdy
Monitor Menu
U1-01= 0.00Hz

or

until the monitor screen is displayed.

U1-02= 0.00Hz LSEQ


U1-03= 0.00A LREF
JOG FWD FWD/REV

-MONITR- DRV Rdy


Monitor
U1 -01= 0.00Hz

to display the parameter setting screen.

U1-02= 0.00Hz LSEQ


U1-03= 0.00A LREF
JOG FWD FWD/REV

and
to scroll to monitor U2-02. The fault code shown in U2-02
4. Press
is the fault that occurred most recently.

- MONITR - DRV Rdy


Last Fault
U2-02= oC
U2-03= 0.00Hz LSEQ
U2-04= 0.00Hz LREF
JOG FWD FWD/REV
- MONITR - DRV Rdy
Frequency Ref
U2-03= 0.00Hz

Press
to view drive status information when fault occurred.
5. Parameters U2-03 through U2-20 help determine the cause of a fault.
Parameters to be monitored differ depending on the control mode.

U2-04= 0.00Hz LSEQ


U2-05= 0.00A LREF
JOG FWD FWD/REV

- MONITR - DRV Rdy


Heatsink Temp
U2-20= XX C
U2-01= ----LSEQ
U2-02= ----LREF
JOG FWD FWD/REV

218

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.9 Diagnosing and Resetting Faults

u Fault Reset Methods


When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the different
ways to restart the drive.
After the Fault Occurs

Procedure
- MODE -

DRV

oC

Fix the cause of the fault, restart the drive, and


Press
reset the fault

Overcurrent
FWD RESET

on the digital operator.

F1

RESET

LO
RE

RESET

ENTER

RUN

Resetting via Fault Reset Digital Input S4

Close then open the fault signal digital input via


terminal S4. S4 is set for Fault Reset as default
(H1-04 = 14).

F2

ESC

STOP

Drive
Fault Reset Switch

S4 Fault Reset Digital Input


SC Digital Input Common

ON

OFF

Turn off the main power supply if the above methods do not reset the fault. Reapply power after the
digital operator display has turned off.

If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear
a fault situation.

Troubleshooting

Note:

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

219

2.10 Troubleshooting without Fault Display

2.10 Troubleshooting without Fault Display


This section describes troubleshooting problems that do not trip an alarm or fault.
The following symptoms indicate that the drive is not set correctly for proper performance with the motor. Refer to Motor
Performance Fine-Tuning on page 172 for guidance on troubleshooting.
Motor hunting and oscillation
Poor motor torque
Poor speed precision
Poor motor torque and speed response
Motor noise

u Common Problems
Common Problems
Cannot Change Parameter Settings
Motor Does Not Rotate
Motor Does Not Rotate Properly after Pressing RUN Button Motor Rotates in the Opposite Direction from the Run
or after Entering External Run Command
Command
Motor Rotates in One Direction Only
Motor is Too Hot
Drive Does Not Allow Selection of Rotational Auto-Tuning
oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Motor Stalls During Acceleration or With Large Loads
Drive Frequency Reference Differs from the Controller Frequency Reference Command
Excessive Motor Oscillation and Erratic Rotation
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled
Noise From Drive or Motor Cables When the Drive is Powered On
Ground Fault Circuit Interrupter (GFCI) Trips During Run
Unexpected Noise from Connected Machinery
Connected Machinery Vibrates When Motor Rotates
Oscillation or Hunting
PID Output Fault
Insufficient Starting Torque
Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection Braking)
Output Frequency is not as High as Frequency Reference
Buzzing Sound from Motor at 2 kHz
Motor Does Not Restart after Power Loss

Page
220
221
222
222
222
223
223
223
224
224
224
225
225
225
225
226
226
226
226
226
227

u Cannot Change Parameter Settings


Cause
The drive is running the motor
(i.e., the Run command is present).

Possible Solutions
Stop the drive and switch over to the Programming Mode.
Most parameters cannot be edited during run.

The Access Level is set to restrict access to parameter Set the Access Level to allow parameters to be edited (A1-01 = 2).
settings.
See what mode the operator is currently set for.
The operator is not in the Parameter Setup Mode
Parameters cannot be edited when in the Setup Mode (STUP). Switch modes so that PAr
(the screen will display PAr).
appears on the screen.
A multi-function contact input terminal is set to allow When the terminal is open, parameters cannot be edited.
or restrict parameter editing
Turn on the multi-function contact input set to 1B.
(H1-01 through H1-08 = 1B).

220

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.10 Troubleshooting without Fault Display


Cause

Possible Solutions
If the password entered to A1-04 does not match the password saved to A1-05, then drive
settings cannot be changed.
Reset the password.
If you cannot remember the password:

STOP
Scroll to A1-04. Press
and
simultaneously. Parameter A1-05 will appear.
Set a new password to parameter A1-05.
Check the drive input power voltage by looking at the DC bus voltage (U1-07).
Check all main circuit wiring.

The wrong password was entered.

Undervoltage was detected.

u Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External
Run Command

n Motor Does Not Rotate


Cause

Possible Solutions
Check if the DRV light on the digital operator is lit.
The drive is not in the Drive Mode.
Enter the Drive Mode to begin operating the motor.
Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the
source, the LO/RE button LED must be on. If the source is REMOTE, it must be off.
Take the following steps to solve the problem:
was pushed.

Push
.
If o2-01 is set to 0, then the LO/RE button will be disabled.
Auto-Tuning has just completed.

When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run command will
not be accepted unless the drive is in the Drive Mode.
Use the digital operator to enter the Drive Mode.

A Fast Stop was executed and has


not yet been reset.

Reset the Fast Stop command.

Check parameter b1-02 (Run Command Selection).


Set b1-02 so that it corresponds with the correct Run command source.
Settings are incorrect for the source 0: Digital operator
that provides the Run command.
1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
Check the wiring for the control terminal.
There is faulty wiring in the control Correct wiring mistakes.
circuit terminals.
Check the input terminal status monitor (U1-10).
Check parameter b1-01 (Frequency Reference Selection 1).
Set b1-01 to the correct source of the frequency reference.
The drive has been set to accept the 0: Digital operator
frequency reference from the
1: Control circuit terminal (default setting)
incorrect source.
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input (RP)
The terminal set to accept the main If the frequency reference is set at terminal A1, check parameter H3-01 for the correct signal level selection. If
speed reference is set to the incorrect terminal A2 is used, check DIP switch S1 parameter H3-08. If terminal A3 is used, check parameter H3-08.
voltage and/or current.
Check jumper S3.

Multi-function analog input is set up


to accept gain for the frequency
reference, but no voltage (current)
has been provided.

Frequency reference is too low.

Check the frequency reference monitor (U1-01).


Increase the frequency by changing the maximum output frequency (E1-09).
Check the multi-function analog input settings.
Check if analog input A1, A2, or A3 is set for frequency reference gain (H3-02, H3-10, H3-06 = 1). If so, check
if the correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is
applied to the gain input.
Check if H3-02, H3-10, and H3-06 have been set to the proper values.
Check if the analog input value has been set properly. (U1-13 to U1-15)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

221

Troubleshooting

Selection for the sink/source mode


and the internal/external power
supply is incorrect.

2.10 Troubleshooting without Fault Display


Cause

Possible Solutions

STOP

Pressing
will decelerate the drive to stop.
was pressed when the drive Switch off the Run command and then re-enter a new Run command.
was started from a REMOTE source.
STOP
Set o2-02 to 0 to disable
.
Motor starting torque is too low.
Refer to Motor Performance Fine-Tuning on page 172.
Frequency reference value is too low
or the drive does not accept the value Enter a value that is above the minimum output frequency determined by E1-09.
entered.
If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 through H1-08 are not
The sequence Start/Stop sequence is set to 0.
set up incorrectly.
If the drive is supposed to be set up for a 3-wire sequence, then one of the parameters H1-03 through H1-08 must
be set to 0. Terminal S1 will become the Start, terminal S2 will become the Stop input.
STOP

n Motor Rotates in the Opposite Direction from the Run Command


Cause

Possible Solutions

Check the motor wiring.


Switch two motor cables (U, V, and W) to reverse motor direction.
Phase wiring between the drive and motor is incorrect. Connect drive output terminals U/T1, V/T2, and W/T3 in the right order to match motor
terminals U, V, and W.
Change the setting of parameter b1-14.
Typically, forward is designated as being counterclockwise when looking from the motor shaft
(see figure below).

The forward direction for the motor is set up incorrectly.

2
1.
2.
The motor is running at almost 0 Hz and the Speed
Search estimated the speed to be in the opposite
direction.
Note:

Forward Rotating Motor (looking down the motor shaft)


Motor Shaft

Disable bi-directional search (b3-14 = 0) so that Speed Search is performed only in the
specified direction.

Check the motor specifications for the forward and reverse directions. The motor specifications will vary depending on the manufacturer
of the motor.

n Motor Rotates in One Direction Only


Cause
The drive prohibits reverse rotation.
A Reverse run signal has not been entered, although
3-Wire sequence is selected.

Possible Solutions
Check parameter b1-04.
Set parameter b1-04 to 0 to allow the motor to rotate in reverse.
Make sure that one of the input terminals S3 to S8 used for the 3-Wire sequence has been set
for reverse.

u Motor is Too Hot


Cause

The load is too heavy.

The air around the motor is too hot.

222

Possible Solutions
If the load is too heavy for the motor, the motor will overheat as it exceeds its rated torque value
for an extended period of time.
Keep in mind that the motor also has a short-term overload rating in addition to the possible
solutions provided below:
Reduce the load.
Increase the acceleration and deceleration times.
Check the values set for the motor protection (L1-01, L1-02) as well as the motor rated current
(E2-01).
Increase motor capacity.
Check the ambient temperature.
Cool the area until it is within the specified temperature range.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.10 Troubleshooting without Fault Display


Cause
The drive is operating in a vector control mode but
Auto-Tuning has not yet been performed.

Insufficient voltage insulation between motor phases.

The motor fan has stopped or is clogged.


The carrier frequency is too low.

Possible Solutions
Perform Auto-Tuning.
Calculate the motor value and reset the motor parameters.
Change the motor control method to V/f Control (A1-02 = 0).
When the motor cable is long, high voltage surges occur between the motor coils and drive
switching.
Normally, surges can reach up to three times the drive input power supply voltage.
Use a motor with a voltage tolerance higher than the max voltage surge.
Use an inverter-duty motor rated for use with AC drives when using the motor on drives rated
higher than 200 V class.
Install an AC reactor on the output side of the drive. The carrier frequency should be set to 2
kHz when installing an AC reactor.
Check the motor fan.
Increase the carrier frequency to lower the current harmonic distortion and lower the motor
temperature.

u Drive Does Not Allow Selection of the Desired Auto-Tuning Mode


Cause

Possible Solutions

Check
if
the
desired
tuning
mode
is available for the selected control mode.
The desired Auto-Tuning mode is not available for the
selected control mode.
Change the motor control method by setting A1-02.

u oPE02 Error Occurs When Lowering the Motor Rated Current Setting
Cause
Motor rated current and the motor no-load current
setting in the drive are incorrect.

Possible Solutions
The user is trying to set the motor rated current in E2-01 to a value lower than the no-load
current set in E2-03.
Make sure that value set in E2-01 is higher than E2-03.
If it is necessary to set E2-01 lower than E2-03, first lower the value set to E2-03, then change
the setting in E2-01 as needed.

u Motor Stalls during Acceleration or Acceleration Time is Too Long


Possible Solutions
Take the following steps to resolve the problem:
Reduce the load.
Increase motor capacity.
Note:
Although the drive has a Stall Prevention function and a Torque Compensation
Load is too heavy.
Limit function, accelerating too quickly or trying to drive an excessively large
load can exceed the capabilities of the motor.
Torque limit is not set properly.
Check the torque limit setting.
Check the maximum output frequency (E1-04).
Increase E1-04 if it is set too low.
Check U1-01 for proper frequency reference.
Frequency reference is too low.
Check if a frequency reference signal switch has been set to one of the multi-function input
terminals.
Check for low gain level set to terminals A1, A2, or A3 (H3-03, H3-11, H3-07).
Reduce the load so that the output current remains within the motor rated current.
In extruder and mixer applications, the load will sometimes increase as the temperature drops.
Load is too heavy.
Increase the acceleration time.
Check if the mechanical brake is fully releasing as it should.
Acceleration time has been set too long.
Check if the acceleration time parameters have been set too long (C1-01, C1-03, C1-05, C1-07).
Set the correct V/f pattern so that it matches the characteristics of the motor being used.
Motor characteristics and drive parameter settings are Check the V/f pattern set to E1-03.
incompatible with one another.
Execute Rotational Auto-Tuning.
Although the drive is operating in Open Loop Vector Perform Auto-Tuning.
motor control method, Auto-Tuning has not been
Calculate motor data and reset motor parameters.
performed.
Switch to V/f Control (A1-02 = 0).

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

223

Troubleshooting

Cause
Torque limit has been reached or current suppression
keeps the drive from accelerating.

2.10 Troubleshooting without Fault Display


Cause

Possible Solutions
Check the multi-function analog input settings. Multi-function analog input terminal A1, A2,
or A3 is set for frequency gain (H3-02, H3-10, or H3-06 is set to 1), but there is no voltage
or current input provided.
Incorrect frequency reference setting.
Make sure H3-02, H3-10, and H3-06 are set to the proper values.
See if the analog input value is set to the right value (U1-13 to U1-15).
Check the Stall Prevention level during acceleration (L3-02).
The Stall Prevention level during acceleration and
If L3-02 is set too low, acceleration may be taking too long.
deceleration set too low.
Increase L3-02.
Check the Stall Prevention level during run (L3-06).
The Stall Prevention level during run has been set too If L3-06 is set too low, speed will drop as the drive outputs torque.
low.
Increase the setting value.
The motor cable may be long enough (over 50 m) to require Auto-Tuning for line-to-line
resistance.
Drive reached the limitations of the V/f motor control Be aware that V/f Control is comparatively limited when it comes to producing torque at low
method.
speeds.
Consider switching to Open Loop Vector Control.

u Drive Frequency Reference Differs from the Controller Frequency Reference Command
Cause
The analog input gain and bias for the frequency
reference input are set to incorrect values.

A frequency bias signal is being entered via analog


input terminals A1 to A3.

Possible Solutions
Check the gain and bias settings for the analog inputs that are used to set the frequency reference.
Check parameters H3-03 and H3-04 for input A1, check parameters H3-11 and H3-12 for input
A2, and check parameters H3-07 and H3-08 for input A3.
Set these parameters to the appropriate values.
If more than one of multi-function analog inputs A1 to A3 is set for frequency reference bias
(H3-02, H3-10, or H3-06 is set to 0), then the sum of all signals builds the frequency reference.
Make sure that H3-02, H3-10, and H3-06 are set appropriately.
Check the input level set for terminals A1 to A3 (U1-13 to U1-15).

PID control is enabled, and the drive is consequently


adjusting the output frequency to match the PID
setpoint. The drive will only accelerate to the
If PID control is not necessary for the application, disable it by setting b5-01 to 0.
maximum output frequency set in E1-04 while PID
control is active.

u Excessive Motor Oscillation and Erratic Rotation


Cause
Poor balance between motor phases.
Hunting prevention function is disabled.

Possible Solutions
Check drive input power voltage to ensure that it provides stable power.
Enable Hunting Prevention (n1-01 = 1).
Increase the AFR gain (n2-01) or the AFR time constant (n2-02).

u Deceleration Takes Longer Than Expected with Dynamic Braking Enabled


Cause
L3-04 is set incorrectly.
The deceleration time is set too long.
Insufficient motor torque.

224

Possible Solutions
Check the Stall Prevention level during deceleration (L3-04).
If a dynamic braking option has been installed, disable Stall Prevention during deceleration
(L3-04 = 0).
Set deceleration to more appropriate time (C1-02, C1-04, C1-06, C1-08).
Assuming parameter settings are normal and that no overvoltage occurs when there is
insufficient torque, it is likely that the demand on the motor has exceeded the motor capacity.
Use a larger motor.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.10 Troubleshooting without Fault Display


Cause

Possible Solutions
Check the settings for the torque limit (L7-01 through L7-04).
If the torque limit is enabled, deceleration might take longer than expected because the drive
cannot output more torque than the limit setting. Ensure the torque limit is set to a high enough
value.
Increase the torque limit setting.
If multi-function analog input terminal A1, A2, or A3 is set to torque limit (H3-02, H3-10, or
H3-06 equals 10, 11, 12, or 15), ensure that the analog input levels are set to the correct levels.
Ensure H3-02, H3-10, and H3-06 are set to the right levels.
Ensure the analog input is set to the correct value (U1-13 to U1-15).

Reaching the torque limit.

Load exceeded the internal torque limit determined by Switch to a larger capacity drive.
the drive rated current.

u Noise From Drive or Motor Cables When the Drive is Powered On


Cause

Relay switching in the drive


generates excessive noise.

Possible Solutions
Install a noise filter on the input side of drive input power.
Install a noise filter on the output side of the drive.
Place the wiring inside a metal conduit to shield it from switching noise.
Ground the drive and motor properly.
Separate the main circuit wiring and the control lines.
Make sure wires and the motor have been properly grounded.

u Ground Fault Circuit Interrupter (GFCI) Trips During Run


Cause

Excessive leakage current trips


GFCI.

Possible Solutions
Check the wiring and rating of peripheral devices.
Increase the GFCI sensitivity or use GFCI with a higher threshold.
Reduce the length of the cable used between the drive and the motor.
Install a noise filter or reactor on the output side of the drive. Set the carrier frequency to 2 kHz when connecting
a reactor.
Disable the internal EMC filter.

u Connected Machinery Vibrates When Motor Rotates


n Unexpected Noise from Connected Machinery
Cause

Possible Solutions
Adjust the parameters used for the Jump frequency function (d3-01 through d3-04) to skip the
The drive output frequency is the same as the resonant problem-causing bandwidth.
frequency of the connected machinery.
Place the motor on a rubber pad to reduce vibration.

n Oscillation or Hunting
Cause

Gain is too low when using PID control.


The frequency reference is assigned to an external
source and the signal is noisy.

The cable between the drive and motor is too long.

Perform Auto-Tuning.
Refer to Motor Performance Fine-Tuning on page 172.
Refer to b5: PID Control on page 33 for details.
Ensure that noise is not affecting the signal lines.
Separate main circuit wiring and control circuit wiring.
Use twisted-pair cables or shielded wiring for the control circuit.
Increase the analog input time filter constant (H3-13).
Perform Auto-Tuning.
Reduce the length of the cable.

Troubleshooting

Insufficient tuning.

Possible Solutions

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

225

2.10 Troubleshooting without Fault Display

u PID Output Fault


Cause

No PID feedback input.

The level of detection and the target value do not


correspond with each other.

Possible Solutions
Check the multi-function analog input terminal settings.
Set multi-function analog input terminal A1, A2, or A3 for PID feedback (H3-02, H3-10, or
H3-06 = B).
A signal input to the terminal selection for PID feedback is needed.
Check the connection of the feedback signal.
Check the various PID-related parameter settings.
No PID feedback input to the terminal causes the value detected to be 0, causing a PID fault
and the drive to operate at max frequency.
PID control keeps the difference between target and detection values at 0. Set the input level
for the values relative to one another.
Use analog input gains H3-03 and H3-11 to adjust PID target and feedback signal scaling.

Reverse drive output frequency and speed detection.


When output frequency rises, the sensor detects a
Set PID output for reverse characteristics (b5-09 = 1).
speed decrease.
Adjustment made to PID parameter settings are
Refer to b5: PID Control on page 33 for details.
insufficient.

u Insufficient Starting Torque


Cause
Possible Solutions
Auto-Tuning has not yet been performed (required for Perform Auto-Tuning. Refer to Motor Performance Fine-Tuning on page 172.
vector control modes).
The control mode was changed after performing Auto- Perform Auto-Tuning again.
Tuning.
Only Stationary Auto-Tuning was performed.
Perform Rotational Auto-Tuning.

u Motor Rotates After the Drive Output is Shut Off (Motor Rotates During DC Injection
Braking)
Cause
DC Injection Braking is set too low and the drive
cannot decelerate properly.

Possible Solutions
Adjust the DC Injection braking settings.
Increase the current level for DC Injection Braking (b2-02).
Increase the DC Injection Braking time at stop (b2-04).

The stopping method is set so that the drive coasts to Set b1-03 (Stopping Method Selection) to 0 or 2.
stop.

u Output Frequency is Not as High as Frequency Reference


Cause

Possible Solutions
Adjust the parameters used for the Jump frequency function (d3-01, d3-02, d3-03).
Frequency reference is set within the range of the Jump
Enabling the Jump frequency prevents the drive from outputting the frequencies specified in
frequency.
the Jump range.
Set the maximum output frequency and the upper limit for the frequency reference to more
appropriate values (E1-04, d2-01).
Upper limit for the frequency reference has been
exceeded.
The following calculation yields the upper value for the output frequency:
E1-04 x d2-01 / 100
Large load triggered Stall Prevention function during Reduce the load.
acceleration.
Adjust the Stall Prevention level during acceleration (L3-02).

u Sound from Motor


Cause

Possible Solutions
If the output current rises too high at low speeds, the carrier frequency is automatically reduced
and causes a whining or buzzing sound.
Exceeded 110% of the rated output current of the drive If the sound is coming from the motor, disable carrier frequency derating (L8-38 = 0).
while operating at low speeds.
Disabling the automatic carrier frequency derating increases the chances of an overload fault
(oL2). Switch to a larger capacity motor if oL2 faults occur too frequently.
226

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

2.10 Troubleshooting without Fault Display

u Motor Does Not Restart after Power Loss


Possible Solutions
Check the sequence and wiring that has been set up to enter the Run command.
The Run command was not issued again when power
A relay should be set up to make sure the Run command remains enabled throughout any power
was restored.
loss.
The relay that is supposed to maintain the Run
Check wiring and circuitry for the relay intended to keep the Run command enabled.
command has been switched off.

Troubleshooting

Cause

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

227

2.10 Troubleshooting without Fault Display

This Page Intentionally Blank

228

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Appendix: A
Parameter List
This appendix contains a full listing of all parameters and settings available in the drive.

A.1
A.2
A.3
A.4
A.5
A.6
A.7
A.8
A.9
A.10
A.11
A.12
A.13
A.14
A.15
A.16
A.17
A.18

UNDERSTANDING PARAMETER DESCRIPTIONS...........................................230


PARAMETER GROUPS.......................................................................................231
A: INITIALIZATION PARAMETERS....................................................................232
B: APPLICATION.................................................................................................234
C: TUNING............................................................................................................241
D: REFERENCES.................................................................................................246
E: MOTOR PARAMETERS..................................................................................251
F: OPTIONS.........................................................................................................255
H PARAMETERS: MULTI-FUNCTION TERMINALS..........................................263
L: PROTECTION FUNCTION...............................................................................276
N: SPECIAL ADJUSTMENT................................................................................284
O: OPERATOR-RELATED SETTINGS................................................................286
DRIVEWORKSEZ PARAMETERS.......................................................................289
T: MOTOR TUNING..............................................................................................290
U: MONITORS......................................................................................................292
CONTROL MODE DEPENDENT PARAMETER DEFAULT VALUES................301
V/F PATTERN DEFAULT VALUES.....................................................................303
DEFAULTS BY DRIVE MODEL AND DUTY RATING ND/HD............................304

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

229

A.1 Understanding Parameter Descriptions

A.1 Understanding Parameter Descriptions


u A1-02 Control Modes, Symbols, and Terms
The table below lists terms and symbols used in this section to indicate which parameters are available in which control modes.
Table A.1 Symbols and Icons Used in Parameter Descriptions

Symbol
All Modes
V/f
V/f w PG

Description
Parameter is available in all control modes.
Parameter is available when operating the drive with V/f Control.
Parameter is available when operating the drive with V/f with PG Control.

OLV

Parameter is available when operating the drive with Open Loop Vector.

CLV

Parameter is available when operating the drive with Closed Loop Vector.

OLV/PM
AOLV/PM
CLV/PM

Parameter is available when operating the drive with Open Loop Vector for PM motors. <99>
Parameter is available when operating the drive with Advanced Open Loop Vector for PM motors. <99>
Parameter is available when operating the drive with Closed Loop Vector for PM motors. <99>
Parameter is NOT available when operating the drive in the control mode.
Parameter can be changed during run.

Motor 2

Refers to a second motor when the drive is operating two motors. Switch between these motors using the multifunction input terminals.

<99> PM motor control modes are not available in A1000 HHP drive models.

230

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.2 Parameter Groups

A.2 Parameter Groups


Parameter
Group
A1
A2

Initialization Parameters

232

Parameter
Group
H1

Multi-Function Digital Inputs

263

User Parameters

233

H2 <1>

Multi-Function Digital Outputs

267

Multi-Function Analog Inputs

270

Name

Page

Name

Page

b1

Operation Mode Selection

234

H3 <1>

b2

DC Injection Braking and Short Circuit


Braking

235

H4

Multi-Function Analog Outputs

273

Speed Search

236

H5

MEMOBUS/Modbus Serial Communication

273

b4

Timer Function

237

H6

Pulse Train Input/Output

274

b5

PID Control

237

L1 <1>

Motor Protection

276

b6

Dwell Function

239

L2

Momentary Power Loss Ride-Thru

277

b3 <1>

b7

Droop Control

239

L3 <1>

Stall Prevention

278

b8
b9
C1
C2

Energy Saving
Zero Servo
Acceleration and Deceleration Times
S-Curve Characteristics

240
241
242

L4
L5
L6
L7

Speed Detection
Fault Restart
Torque Detection
Torque Limit

279
280
280
281

Slip Compensation

242

Drive Protection

282

Torque Compensation

243

L8 <1>
n1

284

Automatic Speed Regulator (ASR)

244

n2

Carrier Frequency

245

n3

Hunting Prevention
Speed Feedback Detection Control (AFR)
Tuning
High Slip Braking (HSB) and Overexcitation
Braking

247
247

o1
o2

Digital Operator Display Selection


Digital Operator Keypad Functions

286
286

d4

Frequency Upper/Lower Limits


Jump Frequency
Frequency Reference Hold and Up/Down 2
Function

248

o3

Copy Function

287

d5
d6
d7
E1

Torque Control
Field Weakening and Field Forcing
Offset Frequency
V/f Pattern for Motor 1

249
249
250
251

o4
q
r
T1

Maintenance Monitor Settings


DriveWorksEZ Parameters
DriveWorksEZ Connection Parameters
Induction Motor Auto-Tuning

287
289
289
290

Motor 2 Parameters

254

Operation Status Monitors

292

PG Speed Control Card (PG-B3/PG-X3)

255

U1 <1>
U3

Fault History

296

Analog Input Card (AI-A3)

257

Maintenance Monitors

296

Digital Input Card (DI-A3)


Analog Monitor Card (AO-A3)
Digital Output Card (DO-A3)
Communication Option Card

257
257
258
258

U4 <1>
U5
U6
U8

PID Monitors
Operation Status Monitors
DriveWorksEZ Monitors

299
299
300

C3 <1>
C4
C5
C6 <1>
d2
d3

E4 <1>
F1
F2
F3
F4
F5
F6, F7

284
284

Parameter List

<1> Specifications differ for models CIMR-Ao4A0930, 4A1200 and A1000 HHP.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

231

A.3 A: Initialization Parameters

A.3 A: Initialization Parameters


The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.

u A1: Initialization
No.
(Addr.
Hex)
A1-00
(100)

Name
All Modes

Language Selection

<1>

A1-01
(101)

<1>

Values
Default: 0
Range: 0, 1

0: English
1: Japanese

Page

10

All Modes

Access Level Selection

<2>

A1-02
(102)

Description

0: View and set A1-01 and A1-04. Uo-oo parameters can also be viewed. Default: 2
1: User Parameters (access to a set of parameters selected by the user, A2-01 Range: 0 to 2
to A2-32)
2: Advanced Access (access to view and set all parameters)

10

All Modes

Control Method Selection

0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control

Default: 2
Range: 0 to 3

10

All Modes

0: No initialization
Default: 0
1110: User Initialize (parameter values must be stored using parameter o2-03) Range: 0 to 3330;
2220: 2-Wire initialization
5550
3330: 3-Wire initialization
5550: oPE04 error reset

A1-03
(103)

Initialize Parameters

A1-04
(104)

Password

Default: 0000
When the value set into A1-04 does not match the value set into A1-05,
Min.: 0000
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot Max.: 9999
be changed.

A1-05
(105)

Password Setting

Default: 0000
When the value set into A1-04 does not match the value set into A1-05,
Min.: 0000
parameters A1-01 through A1-03, A1-06, and A2-01 through A2-33 cannot Max.: 9999
be changed.

11

All Modes

11

All Modes

11

All Modes

A1-06
(127)

Application Preset

A1-07
(128)

DriveWorksEZ Function
Selection

0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6:
7:

Default: 0
Range: 0 to 7

14

Default: 0
Range: 0 to 2

16

All Modes

0: DWEZ Disabled
1: DWEZ Enabled
2: Digital input (enabled when H1-oo = 9F)

<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Application Preset selected with parameter A1-06.

232

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.3 A: Initialization Parameters

u A2: User Parameters


No.
(Addr.
Name
Hex)
A2-01 to
A2-32
(106 to User Parameters 1 to 32
125)

Description

Values

All Modes
Default: <1>
Recently edited parameters are listed here. The user can also select parameters Range: b1-01 to
to appear here for quicker access.
o4-13

Page

17

All Modes

A2-33
(126)

User Parameter Automatic


Selection

0: Parameters A2-01 to A2-32 are reserved for the user to create a list of User Default: 1 <2>
Parameters.
Range: 0, 1
1: Save history of recently viewed parameters. Recently edited parameters will
be saved to A2-17 through A2-32 for quicker access.

17

Parameter List

<1> Default setting value is dependent on the Application Preset selected with parameter A1-06.
<2> Default setting value is dependent on parameter A1-06. Default is 0 when A1-06 = 0, and 1 when A1-06 0.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

233

A.4 b: Application

A.4 b: Application
Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID
control, the Dwell function, Energy Savings, and a variety of other application-related settings.

u b1: Operation Mode Selection


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

b1-01
(180)

Frequency Reference
Selection 1

0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse input (terminal RP)

Default: 1
Range: 0 to 4

18

Default: 1
Range: 0 to 3

19

Default: 0
Range: 0 to 3 <1>

20

Default: 0
Range: 0, 1

22

Default: 0
Range: 0 to 3

22

All Modes

0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option PCB

b1-02
(181)

Run Command
Selection 1

b1-03
(182)

0: Ramp to stop
Stopping Method Selection 1: Coast to stop
2: DC Injection Braking to stop
3: Coast with timer

b1-04
(183)

Reverse Operation Selection 0: Reverse enabled.


1: Reverse disabled.

All Modes

All Modes

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

b1-05
(184)

Action Selection below


0: Operates according to frequency reference (E1-09 is disabled).
Minimum Output Frequency 1: Output shuts off (coast to stop if less than E1-09).
2: Operates according to E1-09 (frequency reference set to E1-09).
3: Zero speed (frequency reference becomes zero when less than E1-09).

b1-06
(185)

Digital Input Reading

0: Input status is read once and processed immediately (for quicker response) Default: 1
Range: 0, 1
1: Input is read twice and processed only if the status is the same in both
readings (robust against noisy signals)

b1-07
(186)

LOCAL/REMOTE Run
Selection

0: An external Run command must be cycled at the new source in order to be Default: 0
Range: 0, 1
activated.
1: An external Run command at the new source is accepted immediately.

b1-08
(187)

Run Command Selection in 0: Run command is not accepted while in Programming Mode.
Programming Mode
1: Run command is accepted while in Programming Mode.
2: Prohibit entering Programming Mode during run.

All Modes

23

All Modes

24

All Modes

b1-14
(1C3)

Phase Order Selection

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Default: 0
Range: 0 to 2

24

Default: 0
Range: 0, 1

24

Default: 0
Range: 0 to 4

24

CLV

0: Standard
1: Switch phase order (reverses the direction of the motor)
All Modes

b1-15
(1C4)

234

Frequency Reference
Selection 2

Enabled when an input terminal set for External reference (H1-oo = 2)


closes.
0: Digital operator
1: Terminals (analog input terminals)
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.4 b: Application
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

Enabled when a terminal set for External reference (H1-oo = 2) closes.


0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card

b1-16
(1C5)

Run Command
Selection 2

Default: 0
Range: 0 to 3

b1-17
(1C6)

Default: 0
Run Command at Power Up 0: Disregarded. A new Run command must be issued after power up.
1: Allowed. Motor will start immediately after power up if a Run command Range: 0, 1
is already enabled.

25

All Modes

25

<1> Settings 2 and 3 are not available in CLV.

u b2: DC Injection Braking and Short Circuit Braking


No.
(Addr.
Hex)

Name

b2-01
(189)

DC Injection Braking Start


Frequency

Default: <1>
Sets the frequency at which DC Injection Braking starts when Ramp to stop Min.: 0.0 Hz
Max.: 10.0 Hz
(b1-03 = 0) is selected.

b2-02
(18A)

DC Injection Braking
Current

Default: 50%
Min.: 0
Sets the DC Injection Braking current as a percentage of the drive rated current. Max.: 100

b2-03
(18B)

Default: 0.00 s
DC Injection Braking Time
OLV/PM
AOLV/PM
CLV/PM
Min.: 0.00
at Start
Sets DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) Max.: 10.00
time at start. Disabled when set to 0.00 seconds.

b2-04
(18C)

Default: <1>
DC Injection Braking Time
OLV/PM
AOLV/PM
CLV/PM
Min.: 0.00 s
at Stop
Sets DC Injection Braking (Zero Speed Control when in CLV and CLV/PM) Max.: 10.00 s
time at stop.

b2-08
(190)

Magnetic Flux
Compensation Value

Description

Values

Page

All Modes

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

V/f

V/f w PG

OLV

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

25

CLV

26

CLV

26

CLV

CLV

Sets the magnetic flux compensation as a percentage of the no-load current


value (E2-03).

Default: 0%
Min.: 0
Max.: 1000

26

27

Parameter List

<1> Default setting is determined by parameter A1-02, Control Method Selection.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

235

A.4 b: Application

u b3: Speed Search


No.
(Addr
Hex.)

Name

b3-01
(191)

Speed Search Selection at


Start

b3-02
(192)

Speed Search Deactivation


Current

b3-03
(193)

Speed Search Deceleration


Time

b3-04
(194)

V/f Gain during Speed


Search

b3-05
(195)

Speed Search Delay Time

b3-06
(196)

Output Current 1 during


Speed Search

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values

Page

CLV

Default: <1>
Range: 0, 1

30

Default: <1>
Min.: 0%
Sets the current level at which the speed is assumed to be detected and Speed Max.: 200%
Search is ended. Set as a percentage of the drive rated current.

30

0: Disabled
1: Enabled
CLV

CLV

Sets output frequency reduction time during Speed Search.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Default: 2.0 s
Min.: 0.1
Max.: 10.0

30

CLV

Determines how much to lower the V/f ratio during Speed Search.
Output voltage during Speed Search equals the V/f setting multiplied by b3-04. Default: <2>
Min.: 10%
Note:
Available control mode for parameter b3-04 varies by drive
Max.: 100%
model:
CIMR-Ao2A0004 to 2A0415, 4A0002 to 4A0675, and
5A0003 to 5A0242: Available when A1-02 = 0, 1
CIMR-Ao4A0930 and 4A1200: Available when A1-02 = 0

31

All Modes

Default: 0.2 s
When using an external contactor on the output side, b3-05 delays executing Min.: 0.0
Speed Search after a momentary power loss to allow time for the contactor to Max.: 100.0
close.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the current injected to the motor at the beginning of Speed Estimation
Speed Search. Set as a coefficient for the motor rated current.
V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

Speed Search Detection


Compensation Gain

b3-14
(19E)

Bi-Directional Speed Search OLV/PM


AOLV/PM
CLV/PM
Selection
0: Disabled (uses the direction of the frequency reference)
1: Enabled (drive detects which way the motor is rotating)

b3-17
(1F0)

Speed Search Restart


Current Level

b3-18
(1F1)

Speed Search Restart


Detection Time

b3-19
(1F2)

Number of Speed Search


Restarts

b3-24
(1C0)

Speed Search Method


Selection

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

Default: <1>
Range: 0, 1

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

CLV

CLV

Sets the number of times the drive can attempt to restart when performing
Speed Search.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

0: Current Detection
1: Speed Estimation

31

CLV

Sets the time to detect Speed Search restart.


OLV/PM

31

CLV

Default: 150%
Min.: 0
Sets the Speed Search restart current level as a percentage of the drive rated Max.: 200
current.
OLV/PM

31

CLV

Default: 1.05
Sets the gain which is applied to the speed detected by Speed Estimation Speed Min.: 1.00
Max.: 1.20
Search before the motor is reaccelerated. Increase this setting if ov occurs
when performing Speed Search after a relatively long period of baseblock.
OLV/PM

b3-10
(19A)

236

Default: <2>
Min.: 0.0
Max.: 2.0

31

31

Default: 0.10 s
Min.: 0.00
Max.: 1.00

32

Default: 3
Min.: 0
Max.: 10

32

Default: 0
Range: 0, 1

32

CLV

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.4 b: Application
No.
(Addr
Hex.)
b3-25
(1C8)

Name

Speed Search Wait Time

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values

Page

CLV

Default: 0.5 s
Min.: 0.0
Sets the time the drive must wait between each Speed Search restart attempt. Max.: 30.0

32

<1> Default setting is determined by parameter A1-02, Control Method Selection.


<2> Default setting is dependent on parameter o2-04, Drive Model Selection.

u b4: Timer Function


No.
(Addr.
Hex)

Name

b4-01
(1A3)

Timer Function On-Delay


Time

b4-02
(1A4)

Timer Function Off-Delay


Time

Description
All Modes

Sets the on-delay and off-delay times for a digital timer output
(H2-oo=12).
The output is triggered by a digital input programmed to
H1-oo=18).

Values
Default: 0.0 s
Min.: 0.0
Max.: 3000.0
Default: 0.0 s
Min.: 0.0
Max.: 3000.0

Page
32
32

u b5: PID Control


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

b5-02
(1A6)

PID Function Setting

All Modes

Default: 1.00
Min.: 0.00
Max.: 25.00

36

Default: 1.0 s
Min.: 0.0
Max.: 360.0

36

Proportional Gain Setting


(P)

Sets the proportional gain of the PID controller.

b5-03
(1A7)

Integral Time Setting (I)

Sets the integral time for the PID controller.

b5-04
(1A8)

Integral Limit Setting

All Modes
Default: 100.0%
Sets the maximum output possible from the integrator as a percentage of the Min.: 0.0
Max.: 100.0
maximum output frequency.

b5-05
(1A9)

Derivative Time (D)

Sets D control derivative time.

b5-06
(1AA)

PID Output Limit

Sets the maximum output possible from the entire PID controller as a
percentage of the maximum output frequency.

b5-07
(1AB)

PID Offset Adjustment

Applies an offset to the PID controller output. Set as a percentage of the


maximum output frequency.

b5-08
(1AC)

All Modes

All Modes

All Modes

All Modes

PID Primary Delay Time


Constant

All Modes

Sets a low pass filter time constant on the output of the PID controller.
All Modes

b5-09
(1AD)

PID Output Level Selection 0: Normal output (direct acting)


1: Reverse output (reverse acting)

b5-10
(1AE)

PID Output Gain Setting

All Modes

Sets the gain applied to the PID output.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

36

36

Default: 0.00 s
Min.: 0.00
Max.: 10.00

36

Default: 100.0%
Min.: 0.0
Max.: 100.0

36

Default: 0.0%
Min.: -100.0
Max.: 100.0

36

Default: 0.00 s
Min.: 0.00
Max.: 10.00

37

Default: 0
Range: 0, 1

37

Default: 1.00
Min.: 0.00
Max.: 25.00

37

Parameter List

b5-01
(1A5)

0: Disabled
1: Enabled (PID output becomes output frequency reference, deviation D
Default: 0
controlled)
Range: 0 to 4
2: Enabled (PID output becomes output frequency reference, feedback D
controlled)
3: Enabled (PID output added to frequency reference, deviation D controlled)
4: Enabled (PID output added to frequency reference, feedback D controlled)

A
237

A.4 b: Application
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

b5-11
(1AF)

PID Output Reverse


Selection

0: Negative PID output triggers zero limit.


1: Rotation direction reverses with negative PID output.
Note:

When using setting 1, make sure reverse operation is permitted


by b1-04.

Default: 0
Range: 0, 1

37

All Modes

b5-12
(1B0)

PID Feedback Loss


Detection Selection

b5-13
(1B1)

PID Feedback Loss


Detection Level

b5-14
(1B2)

PID Feedback Loss


Detection Time

b5-15
(1B3)

PID Sleep Function Start


Level

b5-16
(1B4)

PID Sleep Delay Time

b5-17
(1B5)

PID Accel/Decel Time

b5-18
(1DC)

PID Setpoint Selection

b5-19
(1DD)

PID Setpoint Value

0: No fault. Digital output only.


1: Fault detection. Alarm output, drive continues operation.
2: Fault detection. Fault output, drive output is shut off.
Default: 0
3: No fault. Digital output only. No fault detection when PID control is
Range: 0 to 5
disabled.
4: Fault detection. Alarm is triggered and drive continues to run. Fault
detection even when PID is disabled.
5: Fault detection. Drive output shuts off. No fault detection when PID control
is disabled.
All Modes

Sets the PID feedback loss detection level as a percentage of the maximum
output frequency.
All Modes

Sets a delay time for PID feedback loss.


All Modes

Sets the frequency level that triggers the sleep function.


All Modes

Sets a delay time before the sleep function is triggered.


All Modes

Sets the acceleration and deceleration time to PID setpoint.


All Modes

Default: 0%
Min.: 0
Max.: 100

38

Default: 1.0 s
Min.: 0.0
Max.: 25.5

38

Default: <1>
Min.: 0.0 Hz
Max.: 400.0 Hz

39

Default: 0.0 s
Min.: 0.0
Max.: 25.5
Default: 0.0 s
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0, 1

0: Disabled
1: Enabled

38

All Modes
Default: 0.00%
Sets the PID target value when b5-18 = 1. Set as a percentage of the maximum Min.: 0.00
Max.: 100.00
output frequency.

39
39

40

40

All Modes

0: 0.01 Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must entered)
3: User-set (set scaling to b5-38 and b5-39)

b5-20
(1E2)

PID Setpoint Scaling

b5-34
(19F)

PID Output Lower Limit

All Modes
Default: 0.00%
Sets the minimum output possible from the PID controller as a percentage of Min.: -100.00
Max.: 100.00
the maximum output frequency.

40

b5-35
(1A0)

PID Input Limit

All Modes
Default: 1000.0%
Limits the PID control input (deviation signal) as a percentage of the maximum Min.: 0.0
Max.: 1000.0
output frequency. Acts as a bipolar limit.

40

b5-36
(1A1)

PID Feedback High


Detection Level

All Modes
Default: 100%
Sets the PID feedback high detection level as a percentage of the maximum Min.: 0
Max.: 100
output frequency.

39

b5-37
(1A2)

PID Feedback High


Detection Time

b5-38
(1FE)

PID Setpoint User Display

238

All Modes

Sets the PID feedback high level detection delay time.

Default: 1
Range: 0 to 3

Default: 1.0 s
Min.: 0.0
Max.: 25.5

Default: <2>
Sets the display value of U5-01 and U5-04 when the maximum frequency is Min.: 1
Max.: 60000
output.

40

39

All Modes

40

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.4 b: Application
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

b5-39
(1FF)

0: No decimal places
PID Setpoint Display Digits 1: One decimal place
2: Two decimal places
3: Three decimal places

b5-40
(17F)

0: Display the frequency reference (U1-01) after PID compensation has been Default: 0
Frequency Reference
Monitor Content during PID added.
Range: 0, 1
1: Display the frequency reference (U1-01) before PID compensation has been
added.

Default: <2>
Range: 0 to 3

40

All Modes

41

<1> Default setting is determined by parameter A1-02, Control Method Selection.


<2> Default setting is dependent on parameter b5-20, PID Setpoint Scaling.

u b6: Dwell Function


No.
(Addr.
Hex)

Name

b6-01
(1B6)

Dwell Reference at Start

b6-02
(1B7)

Dwell Time at Start

b6-03
(1B8)

Dwell Reference at Stop

b6-04
(1B9)

Dwell Time at Stop

Description

Values

Default: 0.0 Hz
All Modes
Min.: 0.0
Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain Max.: 400.0
that frequency at start.
Default: 0.0 s
Min.: 0.0
Max.: 10.0
Default: 0.0 Hz
All Modes
Min.: 0.0
Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain Max.: 400.0
that frequency at stop.
Default: 0.0 s
Min.: 0.0
Max.: 10.0

Page
42
42
42
42

u b7: Droop Control


No.
(Addr.
Hex)

Name

b7-01
(1CA)

Droop Control Gain

b7-02
(1CB)

Droop Control Delay Time

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Default: 0.0%
Min.: 0.0
Sets the speed reduction gain applied at a torque reference of 100%. Set as a Max.: 100.0
percentage of motor base speed.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

43

Default: 0.05 s
Min.: 0.03
Max.: 2.00

43

Default: 1
Range: 0, 1

43

CLV

0: Disabled
1: Enabled

Parameter List

Droop Control Limit


Selection

Page

CLV

Adjusts the responsiveness of Droop Control.


b7-03
(17E)

Values

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

239

A.4 b: Application

u b9: Zero Servo


No.
(Addr.
Hex)

Name

b9-01
(1DA)

Zero Servo Gain

b9-02
(1DB)

Zero Servo Completion


Width

240

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the position loop gain for the Zero Servo function.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the range to trigger an output terminal set for Zero Servo Complete
during Zero Servo operation.

Values

Page

Default: 5
Min.: 0
Max.: 100

44

Default: 10
Min.: 0
Max.: 16383

44

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.5 C: Tuning

A.5 C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, slip compensation, torque compensation,
and carrier frequency selections.

u C1: Acceleration and Deceleration Times


No.
(Addr.
Hex)
C1-01
(200)

Name

Description
All Modes

Acceleration Time 1

Sets the time to accelerate from 0 to maximum frequency.

C1-02
(201)

Deceleration Time 1

Sets the time to decelerate from maximum frequency to 0.

C1-03
(202)

Acceleration Time 2

Sets the time to accelerate from 0 to maximum frequency.

Deceleration Time 2

Sets the time to decelerate from maximum frequency to 0.

C1-04
(203)
C1-05
(204)
C1-06
(205)
C1-07
(206)
C1-08
(207)

Values

All Modes

Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>

All Modes

All Modes

Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>

All Modes

Acceleration Time 3 (Motor


Sets the time to accelerate from 0 to maximum frequency.
2 Accel Time 1)
All Modes

Deceleration Time 3 (Motor


Sets the time to decelerate from maximum frequency to 0.
2 Decel Time 1)

Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>

All Modes

Acceleration Time 4 (Motor


Sets the time to accelerate from 0 to maximum frequency.
2 Accel Time 2)
All Modes

Deceleration Time 4 (Motor


Sets the time to decelerate from maximum frequency to 0.
2 Decel Time 2)

C1-09
(208)

Fast Stop Time

C1-10
(209)

Accel/Decel Time Setting


Units

C1-11
(20A)

Accel/Decel Time
Switching Frequency

All Modes

Sets the time for the Fast Stop function.


All Modes

0: 0.01 s (0.00 to 600.00 s)


1: 0.1 s (0.0 to 6000.0 s)
All Modes

Sets the frequency to switch between accel/decel time settings

Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>

Page

45

45

45

45

45

45

45

45

Default: 10.0 s
Min.: 0.0
Max.: 6000.0 <1>

46

Default: 1
Range: 0, 1

47

Default: 0.0 Hz
Min.: 0.0
Max.: 400.0

46

Parameter List

<1> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

241

A.5 C: Tuning

u C2: S-Curve Characteristics


No.
(Addr.
Hex)

Name

C2-01
(20B)

S-Curve Characteristic at
Accel Start

C2-02
(20C)

S-Curve Characteristic at
Accel End

C2-03
(20D)

S-Curve Characteristic at
Decel Start

C2-04
(20E)

S-Curve Characteristic at
Decel End

Description

Values

All Modes

The S-curve can be controlled at the four points shown below.


ON

Run Command
Output Frequency

OFF

C2-02

C2-03

C2-01

C2-04
Time

Default: 0.20 s
Min.: 0.00
Max.: 10.00
Default: 0.20 s
Min.: 0.00
Max.: 10.00
Default: 0.20 s
Min.: 0.00
Max.: 10.00
Default: 0.00 s
Min.: 0.00
Max.: 10.00

Page
<1>

47
47
47
47

<1> Default setting is determined by parameter A1-02, Control Method Selection.

u C3: Slip Compensation


No.
(Addr.
Hex)
C3-01
(20F)

Name

Slip Compensation Gain

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the gain for the motor slip compensation function used for motor 1.
C3-02
(210)

Slip Compensation Primary


Delay Time

C3-03
(211)

Slip Compensation Limit

C3-04
(212)

Slip Compensation
Selection during
Regeneration

C3-05
(213)

C3-16
(261)

Output Voltage Limit


Operation Selection

Output Voltage Limit


Operation Start Level
(Percentage Modulation)

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Adjusts the slip compensation function delay time used for motor 1.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

47

Default: <1>
Min.: 0 ms
Max.: 10000 ms

48

CLV

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

Default: 0
Range: 0 to 2

Default: 0
Available control mode for parameter C3-05 varies by drive Range: 0, 1
model:
CIMR-Ao2A0004 to 2A0415, 4A0002 to 4A0675, and
5A0003 to 5A0242: Available when A1-02 = 0,1.
CIMR-Ao4A0930 and 4A1200: Available when A1-02 = 2, 3.
A1000 HHP: Available when A1-02 = 2, 3.

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

48

CLV

0: Disabled.
1: Enabled. Automatically decreases motor flux when output voltage
saturation is reached.
Note:

48

CLV

0: Disabled.
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.
OLV/PM

Page

Default: <1>
Min.: 0.0
Max.: 2.5

Default: 200%
Min.: 0
Sets an upper limit for the slip compensation function as a percentage of motor Max.: 250
rated slip for motor 1 (E2-02).

49

CLV

Sets the output voltage limit operation start level (percentage modulation)
when C3-05 is enabled.
Note:

242

CLV

Values

Default: 85.0%
Min.: 70.0
Max.: 90.0

49

This parameter is only available in models CIMR-Ao4A0930,


4A1200, and A1000 HHP.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.5 C: Tuning
No.
(Addr.
Hex)

C3-17
(262)

Name

Maximum Output Voltage


Limit Level (Percentage
Modulation)

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

C3-18
(263)

C3-21
(33E)

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

C3-22
(241)

Motor 2 Slip Compensation


Primary Delay Time

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

CLV

Sets the slip compensation gain used for motor 2.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the slip compensation delay time used for motor 2.


V/f w PG

OLV

CLV

C3-23
(242)

Motor 2 Slip Compensation


OLV/PM
AOLV/PM
CLV/PM
Limit
Sets the upper limit for the slip compensation function for motor 2. Set as a
percentage of the motor rated slip (E4-02).

C3-24
(243)

Motor 2 Slip Compensation


OLV/PM
AOLV/PM
CLV/PM
Selection During
0: Disabled.
Regeneration
1: Enabled above 6 Hz.
2: Enabled whenever slip compensation is possible.

V/f

Default: 90.0%
Min.: 30.0
Max.: 100.0

49

Default: <2>
Min.: 0.0
Max.: 2.5

49

Default: <2>
Min.: 0 ms
Max.: 10000 ms

49

Default: 200%
Min.: 0
Max.: 250

50

Default: 0
Range: 0 to 2

50

This parameter is only available in models CIMR-Ao4A0930,


4A1200, and A1000 HHP.

OLV/PM

V/f

49

CLV

Output Voltage Limit Level Sets the maximum percentage of output voltage reduction when C3-05 is
enabled.

Motor 2 Slip Compensation


Gain

Default: 90.0%
Min.: 85.0
Max.: 100.0

This parameter is only available in models CIMR-Ao4A0930,


4A1200, and A1000 HHP.

OLV/PM

Note:

Page

CLV

Sets the output voltage limit operation determined by C3-18 (percentage


modulation) when C3-05 is enabled.
Note:

Values

V/f w PG

OLV

CLV

<1> Default setting is determined by parameter A1-02, Control Method Selection.


<2> Default setting is determined by parameter E3-01, Motor 2 Control Mode Selection.

u C4: Torque Compensation

C4-01
(215)

C4-02
(216)

Name

Torque Compensation Gain

Torque Compensation
Primary Delay Time 1

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the gain for the automatic torque (voltage) boost function and helps to
produce better starting torque. Used for motor 1.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the torque compensation filter time.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

C4-03
(217)

Torque Compensation at
Forward Start

C4-04
(218)

Torque Compensation at
Reverse Start

C4-05
(219)

Torque Compensation Time


OLV/PM
AOLV/PM
CLV/PM
Constant
Sets the time constant for torque compensation at forward start and reverse
start (C4-03 and C4-04).

Sets torque compensation at forward start as a percentage of motor torque.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets torque compensation at reverse start as a percentage of motor torque.


V/f

V/f w PG

OLV

CLV

Values

Page

Default: <1>
Min.: 0.00
Max.: 2.50

50

Default: <2>
Min.: 0 ms
Max.: 60000 ms

51

Default: 0.0%
Min.: 0.0
Max.: 200.0

51

Default: 0.0%
Min.: -200.0
Max.: 0.0

51

Default: 10 ms
Min.: 0
Max.: 200

51

Parameter List

No.
(Addr.
Hex)

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

243

A.5 C: Tuning
No.
(Addr.
Hex)
C4-06
(21A)
C4-07
(341)

Name
Torque Compensation
Primary Delay Time 2
Motor 2 Torque
Compensation Gain

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the torque compensation time 2.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the torque compensation gain used for motor 2.

Values

Page

Default: 150 ms
Min.: 0
Max.: 10000

51

Default: 1.00
Min.: 0.00
Max.: 2.50

51

<1> Default setting is determined by parameter A1-02, Control Method Selection.


<2> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.

u C5: Automatic Speed Regulator (ASR)


No.
(Addr.
Hex)
C5-01
(21B)

Name

ASR Proportional Gain 1

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the proportional gain of the speed control loop (ASR).


C5-02
(21C)

ASR Integral Time 1

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the integral time of the speed control loop (ASR).


C5-03
(21D)

ASR Proportional Gain 2

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the speed control gain 2 of the speed control loop (ASR).
C5-04
(21E)

ASR Integral Time 2

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the integral time 2 of the speed control loop (ASR).


C5-05
(21F)

ASR Limit

C5-06
(220)

ASR Primary Delay Time


Constant

C5-07
(221)

ASR Gain Switching


Frequency

C5-08
(222)

ASR Integral Limit

C5-12
(386)
C5-21
(356)
C5-22
(357)

244

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the upper limit for the speed control loop (ASR) as a percentage of the
maximum output frequency (E1-04).
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the filter time constant for the time from the speed loop to the torque
command output.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Motor 2 ASR Proportional


Gain 1
Motor 2 ASR Integral Time
1

Default: <1>
Min.: 0.00
Max.: 300.00

Page

<2>

Default: <1>
Min.: 0.000 s
Max.: 10.000 s

53

Default: <1>
Min.: 0.00
Max.: 300.00

53

<2>

Default: <1>
Min.: 0.000 s
Max.: 10.000 s

53

Default: 5.0%
Min.: 0.0
Max.: 20.0

55

Default: <1>
Min.: 0.000 s
Max.: 0.500 s

55

Default: 0.0 Hz
Min.: 0.0
Sets the frequency for switching between proportional gain 1, 2 and integral Max.: 400.0
time 1, 2.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

CLV

Sets the proportional gain of the speed control loop (ASR) for motor 2.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

55

Default: 400%
Min.: 0
Max.: 400

55

Default: 0
Range: 0, 1

55

CLV

0: Disabled. Integral functions are enabled only during constant speed.


1: Enabled. Integral functions are always enabled, during accel/decel and
during constant speed.
OLV/PM

53

CLV

Sets the ASR integral upper limit as a percentage of rated load torque.
Integral Operation during
Accel/Decel

Values

CLV

Sets the integral time of the speed control loop (ASR) for motor 2.

Default: <5>
Min.: 0.00
Max.: 300.00

<2>

Default: <5>
Min.: 0.000 s
Max.: 10.000 s

55

55

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.5 C: Tuning
No.
(Addr.
Hex)
C5-23
(358)
C5-24
(359)

Name
Motor 2 ASR Proportional
Gain 2
Motor 2 ASR Integral Time
2

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the speed control gain 2 of the speed control loop (ASR) for motor 2.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the integral time 2 of the speed control loop (ASR) for motor 2.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

C5-25
(35A)

Motor 2 ASR Limit

C5-26
(35B)

Motor 2 ASR Primary Delay OLV/PM


AOLV/PM
CLV/PM
Time Constant
Sets the filter time constant for the time from the speed loop to the torque
command output used for motor 2.

C5-27
(35C)

Motor 2 ASR Gain


Switching Frequency

Sets the upper limit for the speed control loop (ASR) for motor 2 as a
percentage of the maximum output frequency (E3-04).
V/f

C5-28
(35D)

C5-32
(361)

Motor 2 ASR Integral Limit

Integral Operation during


Accel/Decel for Motor 2

V/f w PG

OLV

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Values
Default: <5>
Min.: 0.00
Max.: 300.00 <2>

55

Default: <5>
Min.: 0.000 s
Max.: 10.000 s

55

Default: 5.0%
Min.: 0.0
Max.: 20.0

56

Default: <5>
Min.: 0.000 s
Max.: 0.500 s

56

CLV

Default: 0.0 Hz
Min.: 0.0
Sets the frequency for motor 2 used to switch between proportional gain 1 and Max.: 400.0
2, and between the integral time 1 and 2.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the ASR integral upper limit for motor 2 as a percentage of rated load
torque.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Page

Default: 400%
Min.: 0
Max.: 400

56

56

CLV

0: Disabled. Integral functions for motor 2 are enabled only during constant Default: 0
Range: 0, 1
speed.
1: Enabled. Integral functions are always enabled for motor 2, during accel/
decel and during constant speed.

56

<1> Default setting is determined by parameter A1-02, Control Method Selection.


<2> The setting range is 1.00 to 300.00 in CLV and AOLV/PM control modes.
<5> Default setting is determined by parameter E3-01, Motor 2 Control Mode Selection.

u C6: Carrier Frequency


No.
(Addr.
Hex)

Name

Description
All Modes

Drive Duty Selection

C6-02
(224)

Carrier Frequency Selection

0: Heavy Duty (HD) for constant torque applications.


1: Normal Duty (ND) for variable torque applications.
All Modes

1: 2.0 kHz

Page

Default: 1
Range: 0, 1

56

Default: 1
Range: 1

57

Parameter List

C6-01
(223)

Values

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

245

A.6 d: References

A.6 d: References
Reference parameters set the various frequency reference values during operation.

u d1: Frequency Reference


No.
(Addr.
Hex)
d1-01
(280)

d1-02
(281)

d1-03
(282)

d1-04
(283)

d1-05
(284)

d1-06
(285)

d1-07
(286)

d1-08
(287)

d1-09
(288)

d1-10
(28B)

d1-11
(28C)

d1-12
(28D)

d1-13
(28E)

246

Name

Description
All Modes

Frequency Reference 1

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 2

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 3

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 4

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 5

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 6

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 7

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 8

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 9

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 10

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 11

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 12

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 13

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.

Values

Page

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

<2>

<2>

<2>

<2>

<2>

<2>

<2>

<2>

<2>

<2>

<2>

<2>

<2>

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.6 d: References
No.
(Addr.
Hex)
d1-14
(28F)

d1-15
(290)

d1-16
(291)

d1-17
(292)

Name

Description
All Modes

Frequency Reference 14

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 15

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.
All Modes

Frequency Reference 16

Sets the frequency reference for the drive. Setting units are determined by
parameter o1-03.

Values

Page

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

Default: 0.00 Hz
Min.: 0.00
Max.: 150.00 <1>

58

<2>

<2>

<2>

Default: 6.00 Hz
Min.: 0.00
Sets the Jog frequency reference. Setting units are determined by parameter
Max.: 150.00 <1>
o1-03.
All Modes

Jog Frequency Reference

58

<2>

<1> Range upper limit is determined by parameters d2-01, Frequency Reference Upper Limit, and E1-04, Maximum Output Frequency.
<2> The setting range is 0.0 to 66.0 in AOLV/PM.

u d2: Frequency Upper/Lower Limits


No.
(Addr.
Hex.)

Name

Description
All Modes

d2-01
(289)

Frequency Reference Upper


Sets the frequency reference upper limit as a percentage of the maximum
Limit
output frequency.

d2-02
(28A)

Frequency Reference Lower


Sets the frequency reference lower limit as a percentage of the maximum
Limit
output frequency.

d2-03
(293)

Master Speed Reference


Lower Limit

All Modes

All Modes

Sets the lower limit for frequency references from analog inputs as a
percentage of the maximum output frequency.

Setting

Page

Default: 100.0%
Min.: 0.0
Max.: 110.0

60

Default: 0.0%
Min.: 0.0
Max.: 110.0

60

Default: 0.0%
Min.: 0.0
Max.: 110.0

61

u d3: Jump Frequency


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

d3-01
(294)

Jump Frequency 1

Eliminates problems with resonant vibration of the motor/machine by


Default: 0.0 Hz
avoiding continuous operation in predefined frequency ranges. The drive
Min.: 0.0
accelerates and decelerates the motor through the prohibited frequency ranges. Max.: 150.0
Setting 0.0 disables this function.
Parameters must be set so that d3-01 d3-02 d3-03.

61

All Modes

d3-02
(295)

Jump Frequency 2

Eliminates problems with resonant vibration of the motor/machine by


Default: 0.0 Hz
avoiding continuous operation in predefined frequency ranges. The drive
Min.: 0.0
accelerates and decelerates the motor through the prohibited frequency ranges. Max.: 150.0
Setting 0.0 disables this function.
Parameters must be set so that d3-01 d3-02 d3-03.

61

d3-03
(296)

Jump Frequency 3

Parameter List

All Modes

Eliminates problems with resonant vibration of the motor/machine by


Default: 0.0 Hz
avoiding continuous operation in predefined frequency ranges. The drive
Min.: 0.0
accelerates and decelerates the motor through the prohibited frequency ranges. Max.: 150.0
Setting 0.0 disables this function.
Parameters must be set so that d3-01 d3-02 d3-03.

61

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

247

A.6 d: References
No.
(Addr.
Hex)
d3-04
(297)

Name

Jump Frequency Width

Description

Values

All Modes
Default: <1>
Sets the dead-band width around each selected prohibited frequency reference Min.: 0.0
Max.: 20.0
point.

Page

61

<1> Default setting is determined by parameter A1-02, Control Mode Setting.

u d4: Frequency Reference Hold and Up/Down 2 Function


No.
(Addr.
Hex)

Name

d4-01
(298)

Frequency Reference Hold


Function Selection

Description

Values

Page

All Modes

d4-03
(2AA)
d4-04
(2AB)

Frequency Reference Bias


Step (Up/Down 2)
Frequency Reference Bias
Accel/Decel (Up/Down 2)

Default: 0
0: Disabled. Drive starts from zero when the power is switched on.
1: Enabled. At power up, the drive starts the motor at the Hold frequency that Range: 0, 1
was saved.
All Modes

Sets the bias added to the frequency reference when the Up 2 and Down 2
digital inputs are enabled (H1-oo = 75, 76).
All Modes

0: Use selected accel/decel time.


1: Use accel/decel time 4 (C1-07 and C1-08).

62

Default: 0.00 Hz
Min.: 0.00
Max.: 99.99

64

Default: 0
Range: 0, 1

65

All Modes

d4-05
(2AC)

Frequency Reference Bias


Operation Mode Selection
(Up/Down 2)

0: Bias value is held if no input Up 2 or Down 2 is active.


Default: 0
1: When the Up 2 reference and Down 2 reference are both on or both off, the Range: 0, 1
applied bias becomes 0. The specified accel/decel times are used for
acceleration or deceleration.

d4-06
(2AD)

Frequency Reference Bias


(Up/Down 2)

Default: 0.0%
The Up/Down 2 bias value is saved in d4-06 when the frequency reference is Min.: -99.9
not input by the digital operator. Set as a percentage of the maximum output Max.: 100.0
frequency.

d4-07
(2AE)

Limits how much the frequency reference is allowed to change while an input Default: 1.0%
Analog Frequency
Reference Fluctuation Limit terminal set for Up 2 or Down 2 is enabled. If the frequency reference changes Min.: 0.1
for more than the set value, then the bias value is held and the drive accelerates Max.: 100.0
(Up/Down 2)
or decelerates to the frequency reference. Set as a percentage of the maximum
output frequency.

65

All Modes

65

All Modes

d4-08
(2AF)
d4-09
(2B0)

d4-10
(2B6)

248

66

Frequency Reference Bias


Upper Limit (Up/Down 2)

All Modes
Default: 100.0%
Sets the upper limit for the bias and the value that can be saved in d4-06. Set Min.: 0.0
Max.: 100.0
as a percentage of the maximum output frequency.

66

Frequency Reference Bias


Lower Limit (Up/Down 2)

All Modes
Default: 0.0%
Sets the lower limit for the bias and the value that can be saved in d4-06. Set Min.: -99.9
Max.: 0.0
as a percentage of the maximum output frequency.

66

Up/Down Frequency
Reference Limit Selection

All Modes

0: The lower limit is determined by d2-02 or an analog input.


1: The lower limit is determined by d2-02.

Default: 0
Range: 0, 1

66

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.6 d: References

u d5: Torque Control


No.
(Addr.
Hex)

Name

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values

CLV

d5-01
(29A)

Torque Control Selection

Default: 0
0: Speed Control
Range: 0, 1
1: Torque Control
Set to 0 when using a digital input to switch between Speed and Torque Control
(H1-oo = 71).

d5-02
(29B)

Torque Reference Delay


Time

Default: 0 ms
Min.: 0
Sets a delay time for the torque reference signal. Used to suppress effects by Max.: 1000
noisy or fluctuating torque reference signals.

d5-03
(29C)

Speed Limit Selection

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

d5-04
(29D)

Speed Limit

Speed Limit Bias

OLV

Default: 1
Range: 1, 2

V/f w PG

OLV
CLV/PM

V/f

V/f w PG

OLV

Speed/Torque Control
Switchover Time

d5-08
(2B5)

Unidirectional Speed Limit


OLV/PM
Bias
0: Disabled
1: Enabled

V/f

AOLV/PM

CLV/PM

V/f w PG

OLV

AOLV/PM

CLV/PM

70

CLV

Default: 0 ms
Sets the delay time for switching between Speed and Torque Control using an Min.: 0
input terminal (H1-oo = 71). Reference values are held during this switch Max.: 1000
delay time.
OLV/PM

d5-06
(29F)

70

CLV

Default: 10%
Sets the speed limit bias as a percentage of the maximum output frequency. Min.: 0
The bias is applied to the specified speed limit and can adjust the margin for Max.: 120
the speed limit.
AOLV/PM

70

CLV

CLV/PM

OLV/PM

70

CLV

Default: 0%
Sets the speed limit during Torque Control as a percentage of the maximum Min.: -120
output frequency. Enabled when d5-03 = 2. A negative setting sets a limit in Max.: 120
the opposite direction of the Run command.
V/f

d5-05
(29E)

V/f w PG
AOLV/PM

70

CLV

1: Limit set by the frequency reference in b1-01.


2: Limit set by d5-04.
OLV/PM

Page

71

CLV

Default: 1
Range: 0, 1

71

u d6: Field Weakening and Field Forcing

d6-01
(2A0)

d6-02
(2A1)

d6-03
(2A2)

Name

Field Weakening Level

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values

CLV

Default: 80%
Sets the drive output voltage for the Field Weakening function as a percentage Min.: 0
of the maximum output voltage.
Max.: 100
Enabled when a multi-function input is set for Field Weakening (H1-oo =
63).
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Field Forcing Selection

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

71

CLV

0.0 Hz
Field Weakening Frequency Sets the lower limit of the frequency range where Field Weakening control is Default:
Min.: 0.0
valid.
Limit
The Field Weakening command is valid only at frequencies above this setting Max.: 150.0
and only when the output frequency matches the frequency reference (speed
agree).
V/f

Page

71

Parameter List

No.
(Addr
Hex.)

CLV

0: Disabled
1: Enabled

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Default: 0
Range: 0, 1

71

A
249

A.6 d: References
No.
(Addr
Hex.)

Name

Description
V/f

d6-06
(2A5)

Field Forcing Limit

V/f w PG

OLV

Values

CLV

Default: 400%
Sets the upper limit of the excitation current command during magnetic field Min.: 100
forcing. A setting of 100% is equal to motor no-load current. Disabled only Max.: 400
during DC Injection Braking.
OLV/PM

AOLV/PM

Page

CLV/PM

72

u d7: Offset Frequency


No.
(Addr.
Hex)

Name

Description

Setting

Page

d7-01
(2B2)

Offset Frequency 1

All Modes
Default: 0.0%
Added to the frequency reference when the digital input Frequency offset 1 Min.: -100.0
Max.: 100.0
(H1-oo = 44) is switched on.

72

d7-02
(2B3)

Offset Frequency 2

All Modes
Default: 0.0%
Added to the frequency reference when the digital input Frequency offset 2 Min.: -100.0
Max.: 100.0
(H1-oo = 45) is switched on.

72

d7-03
(2B4)

Offset Frequency 3

All Modes
Default: 0.0%
Added to the frequency reference when the digital input Frequency offset 3 Min.: -100.0
Max.: 100.0
(H1-oo = 46) is switched on.

72

250

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.7 E: Motor Parameters

A.7 E: Motor Parameters


u E1: V/f Pattern for Motor 1
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

This parameter must be set to the power supply voltage.


Input Voltage Setting

E1-03
(302)

V/f Pattern Selection

E1-04
(303)

Maximum Output
Frequency

E1-05
(304)

Maximum Voltage

E1-06
(305)

Base Frequency

E1-07
(306)

Middle Output Frequency

E1-08
(307)

Middle Output Frequency


Voltage

E1-09
(308)

Minimum Output Frequency

E1-10
(309)

Minimum Output Frequency


Voltage

E1-11
(30A)

Middle Output Frequency 2

<9>

E1-12
(30B)
<9>

E1-13
(30C)

Default: 460 V
WARNING! Electrical Shock Hazard. Drive input voltage (not motor Min.: 310
voltage) must be set in E1-01 for the protective features of the drive to Max.: 510 <1>
function properly. Failure to do so may result in equipment damage
and/or death or personal injury.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

All Modes

These parameters are only applicable when E1-03 is set to F.


To set linear V/f characteristics, set the same values for E1-07 and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure that the four
frequencies are set according to these rules:
E1-09 E1-07 < E1-06 E1-11 E1-04
Output Voltage (V)
E1-05
E1-12
E1-13

E1-08
E1-10

Middle Output Frequency


Voltage 2

Note:

73

CLV

0: 50 Hz, Constant torque 1


1: 60 Hz, Constant torque 2
2: 60 Hz, Constant torque 3 (50 Hz base)
3: 72 Hz, Constant torque 4 (60 Hz base)
4: 50 Hz, Variable torque 1
5: 50 Hz, Variable torque 2
6: 60 Hz, Variable torque 3
7: 60 Hz, Variable torque 4
8: 50 Hz, High starting torque 1
9: 50 Hz, High starting torque 2
A: 60 Hz, High starting torque 3
B: 60 Hz, High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f, E1-04 through E1-13 settings define the V/f pattern

E1-09

<1>

E1-07 E1-06 E1-11 E1-04


Frequency (Hz)

Default: F <2>
Range: 0 to 9;
A to F <3>

73

Default: <4>
Min.: 40.0
Max.: 150.0

75

Default: <4>
Min.: 0.0 V
Max.: 510.0 V <1>

75

Default: <4>
Min.: 0.0
Max.: 150.0

75

Default: <4>
Min.: 0.0
Max.: 150.0

75

Default: <4>
Min.: 0.0 V
Max.: 510.0 V <1>

75

Default: <4>
Min.: 0.0
Max.: 150.0

75

Default: <4>
Some parameters may not be available depending on the control Min.: 0.0 V <1>
Max.: 510.0 V
mode.

E1-07, E1-08, and E1-10 are available only in the following control modes:
V/f Control, V/f with PG, Open Loop Vector.
E1-11, E1-12, and E1-13 are available only in the following control modes:
V/f Control, V/f with PG, Open Loop Vector, Closed Loop Vector.

Base Voltage

75

Default: 0.0 Hz
Min.: 0.0
Max.: 150.0

75

Default: 0.0 V
Min.: 0.0
Max.: 510.0 V <1>

75

Default: 0.0 V <8>


Min.: 0.0
Max.: 510.0 V <1>

75

Parameter List

E1-01
(300)

<1> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 600 V class and 690 V class drives.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

251

A.7 E: Motor Parameters


<2>
<3>
<4>
<8>
<9>

Parameter setting value is not reset to the default value when the drive is initialized.
The setting value is F in OLV modes.
Default setting is dependent on parameters A1-02, Control Model Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.

u E2: Motor 1 Parameters


No.
(Addr.
Hex)

Name

Description

Default: <1>
Min.: 10% of drive
OLV/PM
AOLV/PM
CLV/PM
rated current
Sets the motor nameplate full load current in amps. Automatically set during Max.: 200% of
Auto-Tuning.
drive rated current
V/f

E2-01
(30E)

Motor Rated Current

Values

V/f w PG

OLV

Page

CLV

76

<2>

E2-02
(30F)

Motor Rated Slip

E2-03
(310)

Motor No-Load Current

E2-04
(311)

Number of Motor Poles

E2-05
(312)

Motor Line-to-Line
Resistance

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Default: <1>
Min.: 0.00 Hz
Max.: 20.00 Hz

76

Default: <1>
Min.: 0 A
<2>
Sets the no-load current for the motor. Automatically set during Auto-Tuning. Max.: E2-01

76

Sets the motor rated slip. Automatically set during Auto-Tuning.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

CLV

Sets the number of motor poles. Automatically set during Auto-Tuning.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the phase-to-phase motor resistance. Automatically set during


Auto-Tuning.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

Default: <1>
Min.: 0 m
Max.: 65000 m

77

Default: <1>
Min.: 0.0%
Sets the voltage drop due to motor leakage inductance as a percentage of motor Max.: 40.0%
rated voltage. Automatically set during Auto-Tuning.

Motor Leakage Inductance

E2-07
(314)

Motor Iron-Core Saturation


OLV/PM
AOLV/PM
CLV/PM
Coefficient 1
Sets the motor iron saturation coefficient at 50% of magnetic flux.
Automatically set during Auto-Tuning.

E2-08
(315)

Motor Iron-Core Saturation


OLV/PM
AOLV/PM
CLV/PM
Coefficient 2
Sets the motor iron saturation coefficient at 75% of magnetic flux.
Automatically set during Auto-Tuning.

E2-09
(316)

Motor Mechanical Loss

E2-10
(317)

Motor Iron Loss for Torque


Compensation

V/f

V/f w PG

OLV

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

CLV

CLV

Sets the motor mechanical loss as a percentage of motor rated power (kW).

Motor Rated Power

77

CLV

E2-06
(313)

E2-11
(318)

Default: 4
Min.: 2
Max.: 48

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the motor iron loss.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

77

Default: 0.50
Min.: E2-07
Max.: 0.50

77

Default: 0.75
Min.: E2-07
Max.: 0.75

77

Default: 0.0%
Min.: 0.0
Max.: 10.0

77

Default: <1>
Min.: 0 W
Max.: 65535 W

78

CLV

Default: <1>
Min.: 0.00 kW
Sets the motor rated power in kilowatts (1 HP = 0.746 kW). Automatically set Max.: 650.00 kW
during Auto-Tuning.

78

<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.

252

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.7 E: Motor Parameters

u E3: V/f Pattern for Motor 2


These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
No.
(Addr.
Hex)

Name

E3-01
(319)

Motor 2 Control Mode


Selection

E3-04
(31A)

Motor 2 Maximum Output


Frequency

E3-05
(31B)
E3-06
(31C)

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
V/f

V/f w PG

OLV

CLV

OLV/PM

AOLV/PM

CLV/PM

E3-12

Motor 2 Mid Output


Frequency

E3-08
(31E)

Motor 2 Mid Output


Frequency Voltage

E3-09
(31F)

Motor 2 Minimum Output


Frequency

E3-10
(320)

Motor 2 Minimum Output


Frequency Voltage

<3>

E3-12
(346)
<3>

E3-13
(347)

E3-13

E3-08
E3-10
E3-09

Note:
Motor 2 Mid Output
Frequency 2

Page

CLV

Default: 0
Range: 0 to 3

79

Default: <1>
Min.: 40.0
Max.: 150.0

79

These parameters are only applicable when E1-03 is set to F.


To set linear V/f characteristics, set the same values for E3-07 and E3-09. In Default: <1>
Motor 2 Maximum Voltage this case, the setting for E3-08 will be disregarded. Ensure that the four
Min.: 0.0 V
frequencies are set according to these rules or an oPE10 fault will occur:
Max.: 510.0 V <2>
E3-09 E3-07 < E3-06 E3-11 E3-04
Default: <1>
Output Voltage (V)
Motor 2 Base Frequency
Min.: 0.0
E3-05
Max.: 150.0

E3-07
(31D)

E3-11
(345)

Values

E3-07 E3-06 E3-11 E3-04


Frequency (Hz)

E3-07 and E3-08 are only available in the following control


modes: V/f, V/f w/PG and OLV.

Motor 2 Mid Output


Frequency Voltage 2
Motor 2 Base Voltage

79

79

Default: <1>
Min: 0.0
Max: 150.0

79

Default: <1>
Min: 0.0 V
Max: 510.0 V <2>

79

Default: <1>
Min.: 0.0
Max.: 150.0

79

Default: <1>
Min: 0.0 V
Max: 510.0 V <2>
Default: 0.0
Min.: 0.0
Max.: 150.0 <4>
Default: 0.0 V
Min.: 0.0
Max.: 510.0 <2>
Default: 0.0 V <5>
Min.: 0.0
Max.: 510.0 <2>

79

79

79

79

Parameter List

<1> Default setting is dependent on E3-01, Motor 2 Control Mode Selection. The value shown here is for V/f Control (0).
<2> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<3> Ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0.
<4> The setting range is 0.0 to 66.0 in AOLV/PM.
<5> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

253

A.7 E: Motor Parameters

u E4: Motor 2 Parameters


These parameters are hidden when a PM motor control mode has been selected for motor 1 (A1-02 = 5, 6, 7).
No.
(Addr.
Hex)

Name

Description

Default: <1>
Min.: 10% of drive
OLV/PM
AOLV/PM
CLV/PM
rated current
Sets the full load current for motor 2. Automatically set during Auto-Tuning. Max.: 200% of
drive rated current
V/f

E4-01
(321)

Motor 2 Rated Current

Values

V/f w PG

OLV

Page

CLV

80

<2>

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Default: <1>
Min.: 0.00 Hz
Max.: 20.00 Hz <2>

E4-02
(322)

Motor 2 Rated Slip

E4-03
(323)

Motor 2 Rated No-Load


Current

Default: <1>
Min.: 0 A
<2>
Sets the no-load current for motor 2. Automatically set during Auto-Tuning. Max.: E4-01

E4-04
(324)

Motor 2 Motor Poles

Default: 4
Min.: 2
Sets the number of poles of motor 2. Automatically set during Auto-Tuning. Max.: 48

E4-05
(325)

Motor 2 Line-to-Line
Resistance

Sets the rated slip for motor 2. Automatically set during Auto-Tuning.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

CLV

CLV

81

Default: <1>
Min: 0.0%
Max: 40.0%

81

81

Motor 2 Leakage Inductance

E4-07
(343)

Motor 2 Motor Iron-Core


Saturation Coefficient 1

Default: 0.50
Min.: 0.00
Set to the motor iron saturation coefficient at 50% of magnetic flux for motor Max.: 0.50
2. Automatically set during Auto-Tuning.

E4-08
(344)

Motor 2 Motor Iron-Core


Saturation Coefficient 2

Default: 0.75
Min.: E4-07
Set to the motor iron saturation coefficient at 75% of magnetic flux for motor Max.: 0.75
2. This value is automatically set during Auto-Tuning.

E4-09
(33F)

Motor 2 Mechanical Loss

E4-10
(340)

Motor 2 Iron Loss

E4-11
(327)

Motor 2 Rated Power

Sets the voltage drop for motor 2 due to motor leakage inductance as a
percentage of rated voltage. Automatically set during Auto-Tuning.
V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

CLV

CLV

Sets the motor mechanical loss for motor 2 as a percentage of motor rated
power (kW).
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the motor iron loss.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

81

Default: <1>
Min.: 0m
Max.: 65000 m

E4-06
(326)

OLV/PM

80

CLV

Sets the phase-to-phase resistance for motor 2. Automatically set during


Auto-Tuning.
OLV/PM

80

81

Default: 0.0%
Min.: 0.0
Max.: 10.0

81

Default: <1>
Min.: 0 W
Max.: 65535 W

81

CLV

Default: <1>
Min.: 0.00 kW
Sets the motor rated capacity in kW. Automatically set during Auto-Tuning. Max.: 650.00 kW

82

<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.

254

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.8 F: Options

A.8 F: Options
F parameters program the drive for PG feedback from the motor and to function with option cards.

u F1: PG Speed Control Card (PG-X3/PG-B3)


Parameters F1-01, F1-05, F1-06, F1-12, F1-20, F1-21 include PG 1 in the parameter name and are used to set up a PG option
card plugged into option port CN5-C of the drive.
Parameters F1-21 through F1-37 include PG 2 in the parameter name and are used to set up a PG option card plugged into
option port CN5-B of the drive.
Other parameters in the F1 group are used to set operation for PG options plugged into port CN5-C and CN5-B.

F1-01
(380)

F1-02
(381)

Name

PG 1 Pulses Per Revolution

Operation Selection at PG
Open Circuit (PGo)

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

F1-04
(383)

F1-05
(384)

F1-06
(385)

Operation Selection at
Overspeed (oS)

Operation Selection at
Deviation

PG 1 Rotation Selection

PG 1 Division Rate for PG


Pulse Monitor

F1-08
(387)

Overspeed Detection Level

F1-09
(388)

Overspeed Detection Delay


Time

Page

CLV

Default: 1024 ppr


Min.: 1
Sets the number of PG (pulse generator or encoder) pulses. Sets the number Max.: 60000
of pulses per motor revolution.

83

CLV

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.


1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
4: No alarm display
Note:

F1-03
(382)

Values

Default: 1
Range: 0 to 4

83

Default: 1
Range: 0 to 3

83

Default: 3
Range: 0 to 3

84

Default: <1>
Range: 0, 1

84

Due to potential damage to the motor and machinery, only use


the Alarm only and No alarm display settings under special
circumstances.

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.


1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.


1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

0: Pulse A leads
1: Pulse B leads
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the division ratio for the pulse monitor used of the PG option card installed Default: 1
Min.: 1
to port CN5-C.
Max.: 132
By setting xyz, the division ratio becomes = [(1 + x) / yz].
If only using the A pulse for one-track input, the input ratio will be 1:1
regardless of F1-06 setting.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the overspeed detection level as a percentage of the maximum output


frequency.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the time in seconds for an overspeed situation to trigger a fault (oS).

84

Default: 115%
Min.: 0
Max.: 120

83

Default: <1>
Min.: 0.0 s
Max.: 2.0 s

83

Parameter List

No.
(Addr.
Hex)

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

255

A.8 F: Options
No.
(Addr.
Hex)

Name

Description
V/f

V/f w PG

OLV

Values

CLV

F1-10
(389)

Default: 10%
Excessive Speed Deviation
OLV/PM
AOLV/PM
CLV/PM
Min.: 0
Detection Level
Sets the speed deviation detection level as a percentage of the maximum output Max.: 50
frequency.

F1-11
(38A)

Excessive Speed Deviation


Detection Delay Time

F1-12
(38B)

PG 1 Gear Teeth 1

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

84

Default: 0
Min.: 0
Sets the gear ratio between the motor shaft and the encoder (PG). A gear ratio Max.: 1000
of 1 will be used if F1-12 or F1-13 are set to 0.

84

Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if F1-12 or F1-13 are set to 0.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

PG 1 Gear Teeth 2

F1-14
(38D)

PG Open-Circuit Detection
Time

F1-20
(3B4)

PG Option Card Disconnect


OLV/PM
Detection 1
0: Disabled
1: Enabled

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

F1-30
(3AA)

PG Card Option Port for


Motor 2 Selection

F1-31
(3B0)

PG 2 Pulses Per Revolution

F1-32
(3B1)

F1-33
(3B2)

F1-34
(3B3)

CLV

CLV

Default: 2.0 s
Min.: 0.0
Max.: 10.0

83

Default: 1
Range: 0, 1

85

Default: 0
Range: 0, 1

85

Default: 1
Range: 0, 1

85

Default: 1024 ppr


Min.: 1
Max.: 60000

83

Default: 0
Range: 0, 1

84

Default: 0
Min.: 0
Max.: 1000

84

Default: 0
Min.: 0
Sets the gear ratio between the motor shaft and the encoder (PG). A gear ratio Max.: 1000
of 1 will be used if F1-33 or F1-34 are set to 0.

84

Sets the time required to trigger a PG Open fault (PGo).


V/f

PG 1 Signal Selection

CLV

V/f w PG

OLV

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

CLV

0: A pulse detection
1: AB pulse detection
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the port for the PG option card used by motor 2.


0: CN5-C
1: CN5-B
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the number of pulses for a PG option card connected to port CN5-B.
PG 2 Rotation Selection

PG 2 Gear Teeth 1

PG 2 Gear Teeth 2

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

0: Pulse A leads
1: Pulse B leads
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the gear ratio between the motor shaft and the encoder (PG).
A gear ratio of 1 will be used if F1-33 or F1-34 are set to 0.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

CLV

F1-35
(3BE)

PG 2 Division Rate for Pulse


Sets the division ratio for the pulse monitor used of the PG option card 2
Monitor
installed to port CN5-B.
By setting xyz, the division ratio becomes = [(1 + x) / yz].

F1-36
(3B5)

PG Option Card Disconnect


OLV/PM
Detection 2
0: Disabled
1: Enabled

V/f

256

84

Default: 0
Min.: 0
Max.: 1000

F1-13
(38C)

F1-21
(3BC)

84

CLV

Default: 0.5 s
Min.: 0.0
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv). Max.: 10.0
OLV/PM

Page

V/f w PG

OLV

AOLV/PM

CLV/PM

Default: 1
Min.: 1
Max.: 132

84

Default: 1
Range: 0, 1

85

CLV

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.8 F: Options
No.
(Addr.
Hex)
F1-37
(3BD)

Name

PG 2 Signal Selection

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values

Page

CLV

0: A pulse detection
1: AB pulse detection

Default: 0
Range: 0, 1

85

<1> Default setting is determined by parameter A1-02, Control Method Selection.

u F2: Analog Input Card (AI-A3)


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

F2-01
(38F)
F2-02
(368)
F2-03
(369)

Analog Input Option Card


Operation Selection

0: Option card input terminals V1, V2, and V3 replace drive input terminals Default: 0
A1, A2, and A3.
Range: 0, 1
1: Input signals to terminals V1, V2, and V3 are added together to create the
frequency reference.
All Modes

Analog Input Option Card


Gain

Sets the gain for the input signal to the analog card.

Analog Input Option Card


Bias

Sets the bias for the input signal to the analog card.

All Modes

85

Default: 100.0%
Min.: -999.9
Max.: 999.9

86

Default: 0.0%
Min.: -999.9
Max.: 999.9

86

u F3: Digital Input Card (DI-A3)


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
Default: 0
4: BCD, 0.1 Hz units
Range: 0 to 7
5: BCD, 0.01 Hz units
6: BCD customized setting (5-digit), 0.02 Hz units
7: Binary input
When the digital operator units are set to be displayed in Hertz or user-set units
(o1-03 = 2 or 3), the units for F3-01 are determined by parameter o1-03.

F3-01
(390)

Digital Input Option Card


Input Selection

F3-03
(3B9)

Digital Input Option DI-A3 0: 8 bit


Data Length Selection
1: 12 bit
2: 16 bit

86

All Modes

Default: 2
Range: 0 to 2

86

u F4: Analog Monitor Card (AO-A3)


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

F4-02
(392)

Terminal V1 Monitor
Selection

Sets the monitor signal for output from terminal V1. Set this parameter to the Default: 102
Range: 000 to 999
last three digits of the desired Uo-oo monitor. Some U parameters are
available only in certain control modes.
All Modes

Terminal V1 Monitor Gain Sets the gain for voltage output via terminal V1.

Default: 100.0%
Min.: -999.9
Max.: 999.9

87
Parameter List

F4-01
(391)

87

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

257

A.8 F: Options
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

F4-03
(393)
F4-04
(394)

Terminal V2 Monitor
Selection

Sets the monitor signal for output from terminal V2. Set this parameter to the Default: 103
Range: 000 to 999
last three digits of the desired Uo-oo monitor. Some U parameters are
available only in certain control modes.

87

All Modes

Default: 50.0%
Min.: -999.9
Max.: 999.9

87

All Modes

Default: 0.0%
Min.: -999.9
Max.: 999.9

87

Default: 0.0%
Min.: -999.9
Max.: 999.9

87

Default: 0
Range: 0, 1

87

Default: 0
Range: 0, 1

87

Terminal V2 Monitor Gain Sets the gain for voltage output via terminal V2.

F4-05
(395)

Terminal V1 Monitor Bias

Sets the amount of bias added to the voltage output via terminal V1.

F4-06
(396)

Terminal V2 Monitor Bias

Sets the amount of bias added to the voltage output via terminal V2.

F4-07
(397)

Terminal V1 Signal Level

0: 0 to 10 V
1: -10 to 10 V

F4-08
(398)

Terminal V2 Signal Level

0: 0 to 10 V
1: -10 to 10 V

All Modes

All Modes

All Modes

u F5: Digital Output Card (DO-A3)


No.
(Addr.
Hex)
F5-01
(399)

Terminal P1-PC Output


Selection

F5-02
(39A)

Terminal P2-PC Output


Selection

F5-03
(39B)

Name

Description

Values

Page

Default: 2
Range: 0 to 192

87

Default: 4
Range: 0 to 192

87

Terminal P3-PC Output


Selection

Default: 6
Range: 0 to 192

87

F5-04
(39C)

Terminal P4-PC Output


Selection

Default: 37
Range: 0 to 192

87

F5-05
(39D)

Terminal P5-PC Output


Selection

Default: F
Range: 0 to 192

87

F5-06
(39E)
F5-07
(39F)
F5-08
(3A0)

Terminal P6-PC Output


Selection
Terminal M1-M2 Output
Selection
Terminal M3-M4 Output
Selection

Default: F
Range: 0 to 192
Default: 0
Range: 0 to 192
Default: 1
Range: 0 to 192

87

F5-09
(3A1)

DO-A3 Output Mode


Selection

All Modes

Sets the function for contact output terminals M1-M2, M3-M4, and
photocoupler output terminals P1 through P6.

87
87

All Modes

Default: 0
0: Output terminals are each assigned separate output functions.
Range: 0 to 2
1: Binary code output.
2: Use output terminal functions selected by parameters F5-01 through F5-08.

88

u F6, F7: Communication Option Card


Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for CC-Link, CANopen, DeviceNet, PROFIBUS-DP, and
MECHATROLINK-II options. Other parameters in the F6 group are used for communication-protocol-specific settings. F7
parameters are used for EtherNet/IP, Modbus TCP/IP, and PROFINET options.

258

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.8 F: Options
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.


1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.

F6-01
(3A2)

Communications Error
Operation Selection

F6-02
(3A3)

External Fault from Comm.


Option Detection Selection 0: Always detected.
1: Detection during run only.

F6-03
(3A4)

External Fault from Comm. 0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
Option Operation Selection 1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only.

F6-04
(3A5)

bUS Error Detection Time

F6-06
(3A7)

Torque Reference/Torque
AOLV/PM
CLV/PM
Limit Selection from Comm. OLV/PM
0: Disabled. Torque reference/limit from option board disabled.
Option
1: Enabled. Torque reference/limit from option board enabled.

All Modes

Default: 1
Range: 0 to 3

88

Default: 0
Range: 0, 1

88

Default: 1
Range: 0 to 3

88

Default: 2.0 s
Min.: 0.0
Max.: 5.0

89

Default: 0
Range: 0, 1

89

Default: 0
Range: 0, 1

89

All Modes

All Modes

Sets the delay time for error detection if a bus error occurs.
V/f

F6-07
(3A8)
F6-08
(36A)
<1>

F6-10
(3B6)

V/f w PG

OLV

CLV

All Modes
Multi-Step Speed Enable/
Disable Selection when
0: Multi-step reference disabled (same as F7)
NefRef/ComRef is Selected 1: Multi-step reference enabled (same as V7)
All Modes

Reset Communication
Parameters

CC-Link Node Address

0: Communication-related parameters (F6-oo) are not reset when the drive Default: 0
is initialized using A1-03.
Range: 0, 1
1: Reset all communication-related parameters (F6-oo) when the drive is
initialized using A1-03.
Default: 0
All Modes
Min.: 0
Sets the node address if a CC-Link option is installed.
Max.: 64

89

89

All Modes

F6-11
(3B7)

CC-Link Communication
Speed

F6-14
(3BB)

CC-Link bUS Error Auto


Reset

F6-20
(36B)

MECHATROLINK Station
Sets the station address when the MECHATROLINK-II option has been
Address
installed.

F6-21
(36C)

MECHATROLINK Frame
Size

F6-22
(36D)

MECHATROLINK Link
Speed

F6-23
(36E)

MECHATROLINK
Monitor Selection (E)

Sets the MECHATROLINK-II monitor (E).

F6-24
(36F)

MECHATROLINK
Monitor Selection (F)

Sets the MECHATROLINK-II monitor (F).

All Modes

0: Disabled
1: Enabled
All Modes

All Modes

0: 32 byte
1: 17 byte
All Modes

0: 10 Mbps
1: 4 Mbps
All Modes

All Modes

Default: 0
Range: 0 to 4

90

Default: 0
Range: 0, 1

90

Default: 21
Min.: 20
Max.: 3F

Default: 0
Range: 0, 1

Default: 0
Range: 0, 1

Default: 0
Min.: 0
Max.: FFFF
Default: 0
Min.: 0
Max.: FFFF

Parameter List

0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

259

A.8 F: Options
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

F6-25
(3C9)

0: Ramp to stop. Decelerate using the deceleration time in C1-02.


Operation Selection at
Watchdog Timer Error (E5) 1: Coast to stop
2: Fast stop. Decelerate using the deceleration time in C1-09.
3: Alarm only

Default: 1
Range: 0 to 3

F6-26
(3CA)

MECHATROLINK bUS
Errors Detected

Sets the number of option communication errors (bUS).

F6-30
(3CB)

PROFIBUS-DP Node
Address

Sets the node address.

Default: 2
Min.: 2
Max.: 10
Default: 0
Min.: 0
Max.: 125

F6-31
(3CC)

PROFIBUS-DP Clear Mode


Default: 0
0: Resets drive operation with a Clear mode command.
Selection
Range: 0, 1
1: Maintains the previous operation state when Clear mode command is given.

F6-32
(3CD)

PROFIBUS-DP Data
Format Selection

F6-35
(3D0)

CANopen Node ID
Selection

All Modes

All Modes

90

All Modes

All Modes

0: PPO Type
1: Conventional
All Modes

Sets the node address.

90

Default: 0
Range: 0, 1

90

Default: 0
Min.: 0
Max.: 126

90

Default: 6
Range: 0 to 8

91

Default: 64
Min.: 0
Max.: 64

91

Default: 4
Range: 0 to 4

91

All Modes

F6-36
(3D1)

CANopen Communication
Speed

F6-50
(3C1)

DeviceNet MAC Address

0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
All Modes

Selects the drive MAC address.


All Modes

F6-51
(3C2)

0: 125 kbps
DeviceNet Communication 1: 250 kbps
Speed
2: 500 kbps
3: Adjustable from network
4: Detect automatically
All Modes

F6-52
(3C3)

DeviceNet PCA Setting

F6-53
(3C4)

DeviceNet PPA Setting

F6-54
(3C5)

DeviceNet Idle Mode Fault


0: Enabled
Detection
1: Disabled, no fault detection

Sets the format of the data set from the DeviceNet master to the drive.
All Modes

Sets the format of the data set from the drive to the DeviceNet master.
All Modes

Default: 21
Min.: 0
Max.: 255
Default: 71
Min.: 0
Max.: 255

91
91

Default: 0
Range: 0, 1

91

Default: 0
Range: 0 to 2

92

All Modes

F6-55
(3C6)

DeviceNet Baud Rate


Monitor

F6-56
(3D7)

DeviceNet Speed Scaling

F6-57
(3D8)

DeviceNet Current Scaling

260

Verifies the baud rate running on the network.


0: 125 kbps
1: 250 kbps
2: 500 kbps
All Modes

Sets the scaling factor for the speed monitor in DeviceNet.


All Modes

Sets the scaling factor for the output current monitor in DeviceNet.

Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15

92
92

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.8 F: Options
No.
(Addr.
Hex)

Name

Description
All Modes

F6-58
(3D9)

DeviceNet Torque Scaling

F6-59
(3DA)

DeviceNet Power Scaling

F6-60
(3DB)

DeviceNet Voltage Scaling

F6-61
(3DC)

DeviceNet Time Scaling

F6-62
(3DD)

DeviceNet Heartbeat
Interval

Sets the heartbeat interval for DeviceNet communications.

F6-63
(3DE)

DeviceNet Network MAC


ID

Saves and monitors settings 0 to 63 of F6-50 (DeviceNet MAC Address).

Reserved

Reserved for Dynamic I/O Assembly Parameters.

IP Address 1

F7-02
(3E6)

IP Address 2

F7-03
(3E7)

IP Address 3

F7-04
(3E8)

IP Address 4

F7-05
(3E9)

Subnet Mask 1

F7-06
(3EA)

Subnet Mask 2

F7-07
(3EB)

Subnet Mask 3

F7-08
(3EC)

Subnet Mask 4

F7-09
(3ED)

Gateway Address 1

F7-10
(3EE)

Gateway Address 2

F7-11
(3EF)

Gateway Address 3

F7-12
(3E0)

Gateway Address 4

<2>

<2>

<2>

All Modes

Sets the scaling factor for the voltage monitor in DeviceNet.


All Modes

Sets the scaling factor for the time monitor in DeviceNet.


All Modes

All Modes

92
92
92
92
92
92

All Modes

F7-01
(3E5)
<2>

All Modes

Sets the scaling factor for the power monitor in DeviceNet.

Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: 0
Max.: 10
Default: 63
Min.: 0
Max.: 63

Page

All Modes

Sets the most significant octet of network static IP address.


All Modes

Sets the second most significant octet of network static IP address.


All Modes

Sets the third most significant octet of network static IP address.


All Modes

Sets the fourth most significant octet of network static IP address.


All Modes

Sets the most significant octet of network static Subnet Mask.


All Modes

Sets the second most significant octet of network static Subnet Mask.
All Modes

Sets the third most significant octet of network static Subnet Mask.
All Modes

Sets the fourth most significant octet of network static Subnet Mask.
All Modes

Sets the most significant octet of network Gateway address.


All Modes

Sets the second most significant octet of network Gateway address.


All Modes

Sets the third most significant octet of network Gateway address.


All Modes

Sets the fourth most significant octet of network Gateway address.

Default: 192
Range: 0 to 255

Default: 168
Range: 0 to 255

Default: 1
Range: 0 to 255

Default: 20
Range: 0 to 255

Default: 255
Range: 0 to 255

Default: 255
Range: 0 to 255

Default: 255
Range: 0 to 255

Default: 0
Range: 0 to 255

Default: 192
Range: 0 to 255

Default: 168
Range: 0 to 255

Default: 1
Range: 0 to 255

Default: 1
Range: 0 to 255

Default: 2
Range: 0 to 2

Parameter List

F6-64 to
F6-71
(3DF to
3C8)

Sets the scaling factor for the torque monitor in DeviceNet.

Values

All Modes

F7-13
(3F1)

Address Mode at Startup

Select the option address setting method


0: Static <3>
1: BOOTP
2: DHCP

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

261

A.8 F: Options
No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

Selects duplex mode setting.


0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced

F7-14
(3F2)

Duplex Mode Selection

Default: 1
Range: 0 to 2

F7-15
(3F3)

Communication Speed
Selection

Sets the communication speed


10: 10 Mbps
100: 100 Mbps

Default: 10
Range: 10, 100

F7-16
(3F4)

Communication Loss
Timeout

Default: 0
Sets the timeout value for communication loss detection in tenths of a second. Min.: 0
A value of 0 disables the connection timeout.
Max.: 300
Example: An entered value of 100 represents 10.0 seconds.

F7-17
(3F5)

EtherNet/IP Speed Scaling


Factor

Default: 0
Min.: -15
Max.: 15

F7-18
(3F6)

All Modes
Default: 0
EtherNet/IP Current Scaling
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID Min.: -15
Factor
Max.: 15
2AH Object.

F7-19
(3F7)

EtherNet/IP Torque Scaling


Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH
Factor
Object.

Default: 0
Min.: -15
Max.: 15

F7-20
(3F8)

EtherNet/IP Power Scaling


Factor

Default: 0
Min.: -15
Max.: 15

F7-21
(3F9)

All Modes
Default: 0
EtherNet/IP Voltage Scaling
Min.: -15
Sets
the
scaling
factor
for
the
voltage
monitor
in
EtherNet/IP
Class
ID
2AH
Factor
Max.: 15
Object.

F7-22
(3FA)

EtherNet/IP Time Scaling

Default: 0
Min.: -15
Max.: 15

All Modes

All Modes

All Modes

Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.

All Modes

All Modes

Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.

All Modes

Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
All Modes

F7-23 to
F7-32
(3FB to
374)

Parameters used in Output Assembly 116. Each parameter contains a


Dynamic Output Assembly MEMOBUS/Modbus address. The value received for Output Assembly 116 Default: 0
Parameters
will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Output Assembly 116 will not be written to any MEMOBUS/Modbus register.

F7-33 to
F7-42
(375 to
37E)

Parameters used in Input Assembly 166. Each parameter contains a


MEMOBUS/Modbus address. The value sent for Input Assembly 166 will be
read from this corresponding MEMOBUS/Modbus address. A MEMOBUS/ Default: 0
Modbus address value of 0 means that the value sent for Input Assembly 166
is not defined by the user, therefore the option default register value will be
returned.

All Modes

Dynamic Input Assembly


Parameters

<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Cycle power for setting changes to take effect.
<3> If F7-13 is set to 0, all IP addresses (F7-01 to F7-04) must be unique.

262

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.9 H Parameters: Multi-Function Terminals

A.9 H Parameters: Multi-Function Terminals


H parameters assign functions to the multi-function input and output terminals.

u H1: Multi-Function Digital Inputs


No.
(Addr.
Hex)

Name

Description
All Modes

H1-01
(438)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S1 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

H1-02
(439)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S2 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

H1-03
(400)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S3 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

H1-04
(401)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S4 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

H1-05
(402)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S5 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

H1-06
(403)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S6 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

H1-07
(404)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S7 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

H1-08
(405)

Multi-Function Digital Input Assigns a function to the multi-function digital inputs.


Terminal S8 Function
Refer to pages 263 to 267 for descriptions of setting values.
Selection
Note:
Set unused terminals to F.

All Modes

All Modes

All Modes

All Modes

All Modes

All Modes

All Modes

Values

Page

Default: 40 (F) <1>


Min.: 1
Max.: 9F

93

Default: 41 (F) <1>


Min.: 1
Max.: 9F

93

Default: 24
Min.: 0
Max.: 9F

93

Default: 14
Min.: 0
Max.: 9F

93

Default: 3 (0) <1>


Min.: 0
Max.: 9F

93

Default: 4 (3) <1>


Min.: 0
Max.: 9F

93

Default: 6 (4) <1>


Min.: 0
Max.: 9F

93

Default: 8
Min.: 0
Max.: 9F

93

<1> Value in parenthesis is the default setting when a 3-Wire initialization is performed (A1-03 = 3330).
H1 Multi-Function Digital Input Selections
H1-oo
Setting

Function

Description

Page

All Modes

3-Wire sequence

Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)
Terminals S1 and S2 are automatically set up for the Run command and Stop command.

LOCAL/REMOTE selection

Open: REMOTE (parameter settings determine the source of the frequency Reference 1 or 2
(b1-01, b1-02 or b1-15, b1-16)
Closed: LOCAL, digital operator is run and reference source

External reference 1/2 selection

Open: Run command and frequency reference source 1 (determined by b1-01 and b1-02)
Closed: Run command and frequency reference source 2 (determined by b1-15 and b1-16)

94

Parameter List

All Modes

94

All Modes

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

95

A
263

A.9 H Parameters: Multi-Function Terminals


H1 Multi-Function Digital Input Selections
H1-oo
Setting

Function

Description

Page

95

All Modes

Multi-Step Speed Reference 1

When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.

Multi-Step Speed Reference 2

When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.

Multi-Step Speed Reference 3

When input terminals are set to Multi-Step Speed References 1 through 3, switching
combinations of those terminals will create a multi-step speed sequence using the frequency
references set in d1-01 through d1-08.

Jog reference selection

Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other reference
sources.

Accel/decel time selection 1

Used to switch between accel/decel time 1 (set in C1-01, C1-02) and accel/decel time 2 (set
in C1-03, C1-04).

Baseblock command (N.O.)

Baseblock command (N.C.)

All Modes

95

All Modes

95

All Modes

95

All Modes

All Modes

95
95

Closed: No drive output


All Modes

95

Open: No drive output


All Modes

Accel/decel ramp hold

Drive overheat alarm (oH2)

Analog terminal input selection

Open: Accel/decel is not held


Closed: The drive pauses during acceleration or deceleration and maintains the output
frequency.
All Modes

Closed: Closes when an oH2 alarm occurs

95

96

All Modes

PG encoder disable

ASR integral reset

Through mode

Open: Function assigned by H3-14 is disabled.


Closed: Function assigned by H3-14 is enabled.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Open: Speed feedback for V/f Control with PG is enabled.


Closed: Speed feedback disabled.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

96

96

CLV

Open: PI control
Closed: Integral reset

96

All Modes

Select this setting when using the terminal in a pass-through mode. The terminal does not
trigger a drive function but can be used as digital input for the controller the drive is connected
to.

96

All Modes

10

Up command

The drive accelerates when the Up command terminal closes, and decelerates when the Down
command closes. When both terminals are closed or both are open, the drive holds the
frequency reference. The Up and Down commands must always be used in conjunction with
one another.

96

All Modes

264

11

Down command

12

Forward Jog

The drive accelerates when the Up command terminal closes, and decelerates when the Down
command closes. When both terminals are closed or both are open, the drive holds the
frequency reference. The Up and Down commands must always be used in conjunction with
one another.
All Modes

Closed: Runs forward at the Jog frequency d1-17.

96

97

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.9 H Parameters: Multi-Function Terminals


H1 Multi-Function Digital Input Selections
H1-oo
Setting

Function

13

Reverse Jog

14

Fault reset

15

Fast Stop (N.O.)

Description
All Modes

Closed: Runs reverse at the Jog frequency d1-17.


All Modes

Closed: Resets faults if the cause is cleared and the Run command is removed.
All Modes

Closed: Decelerates at the Fast Stop time set to C1-09.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Page
97
97
97

CLV

16

Motor 2 selection

17

Fast Stop (N.C.)

18

Timer function input

Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction with the
timer function output (H2-oo = 12).

19

PID disable

Open: PID control enabled


Closed: PID control disabled

1A

Accel/decel time selection 2

Used in conjunction with an input terminal set for Accel/decel time selection 1
(H1-oo = 7), and allows the drive to switch between accel/decel times 3 and 4.

1B

Program lockout

Open: Parameters cannot be edited (except for U1-01 if the reference source is assigned to
the digital operator).
Closed: Parameters can be edited and saved.

1E

Reference sample hold

Open: Motor 1 (E1-oo, E2-oo)


Closed: Motor 2 (E3-oo, E4-oo)
All Modes

Open: Decelerates to stop at the Fast Stop time set to C1-09.

98

97

All Modes

98

All Modes

99

All Modes

99

All Modes

All Modes

Closed: Samples the analog frequency reference and operates the drive at that speed.

99

99

All Modes

20 to 2F

External fault

30

PID integral reset

31

PID integral hold

32

Multi-Step Speed
Reference 4

34

PID soft starter cancel

20: N.O., Always detected, ramp to stop


21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
All Modes

Closed: Resets the PID control integral value.

99

100

All Modes

100

All Modes

Used in combination with input terminals set to Multi-Step Speed Reference 1, 2, and 3. Use
parameters d1-09 to d1-16 to set reference values.

100

All Modes

Open: PID soft starter is enabled.


Closed: Disables the PID soft starter b5-17.

100

Parameter List

Open: Performs integral operation.


Closed: Maintains the current PID control integral value.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

265

A.9 H Parameters: Multi-Function Terminals


H1 Multi-Function Digital Input Selections
H1-oo
Setting

Function

35

PID input level selection

40

Forward run command


(2-Wire sequence)

Description
All Modes

Page
100

Closed: Inverts the PID input signal.


All Modes

Open: Stop
Closed: Forward run
Note:

100

Cannot be set together with settings 42 or 43.

All Modes

41

Reverse run command


(2-Wire sequence)

Open: Stop
Closed: Reverse run
Note:

100

Cannot be set together with settings 42 or 43.

All Modes

42

Run command
(2-Wire sequence 2)

Open: Stop
Closed: Run
Note:

101
Cannot be set together with settings 40 or 41.

All Modes

43

FWD/REV command
(2-Wire sequence 2)

44

Offset frequency 1

45

Offset frequency 2

46

Offset frequency 3

47

Node setup

60

DC Injection Braking command

Open: Forward
Closed: Reverse
Note:

101

Determines motor direction, but does not issue a Run command. Cannot be set
together with settings 40 or 41.

All Modes

Closed: Adds d7-01 to the frequency reference.


All Modes

Closed: Adds d7-02 to the frequency reference.


All Modes

Closed: Adds d7-03 to the frequency reference.


All Modes
V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

101
101
101

Closed: Node setup for SI-S3 enabled.


OLV/PM

101

CLV

101

Closed: Triggers DC Injection Braking.


61

External Speed Search


command 1

62

External Speed Search


command 2

63

Field weakening

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Closed: Activates Current Detection Speed Search from the maximum output frequency
(E1-04).
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

101

CLV

101

Closed: Activates Current Detection Speed Search from the frequency reference.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

101

Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
All Modes

65

KEB Ride-Thru 1 (N.C.)

66

KEB Ride-Thru 1 (N.O.)

67

Communications test mode

Tests the MEMOBUS/Modbus RS-485/422 interface. Displays PASS if the test completes
successfully.

Drive enable

Open: Drive disabled. If this input is opened during run, the drive will stop as specified by
b1-03.
Closed: Ready for operation.

Open: KEB Ride-Thru 1 enabled.


All Modes

Closed: KEB Ride-Thru 1 enabled.

101
101

All Modes

101

All Modes

6A

266

102

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.9 H Parameters: Multi-Function Terminals


H1 Multi-Function Digital Input Selections
H1-oo
Setting

Function

Description

71

Speed/Torque control Sswitch

72

Zero servo

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Page

CLV

102

Open: Speed Control


Closed: Torque Control
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

102

Closed: Zero Servo enabled


All Modes

75

Up 2 command

Used to control the bias added to the frequency reference by the Up/Down 2 function. The
Up 2 and Down 2 commands must always be used in conjunction with one another.

76

Down 2 command

Used to control the bias added to the frequency reference by the Up/Down 2 function. The
Up 2 and Down 2 commands must always be used in conjunction with one another.

102

All Modes

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

77

ASR gain switch

78

External torque reference polarity


OLV/PM
AOLV/PM
CLV/PM
inversion
Open: Forward torque reference.
Closed: Reverse polarity.

7E

90 to 97

CLV

103

Open: ASR proportional gain 1 (C5-01)


Closed: ASR proportional gain 2 (C5-03)
V/f

V/f w PG

OLV

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

102

CLV

103

CLV

Forward/reverse detection
(V/f Control with Simple PG
feedback)

Direction of rotation detection (for V/f with Simple PG Feedback)

DriveWorksEZ
digital inputs 1 to 8

Reserved for DWEZ input functions

103

All Modes

103

All Modes

9F

DriveWorksEZ disable

103

Open: DWEZ enabled


Closed: DWEZ disabled

u H2: Multi-Function Digital Outputs


No.
(Addr.
Hex)
H2-01
(40B)
H2-02
(40C)
H2-03
(40D)

Name
Terminal M1-M2 function
selection (relay)
Terminal M3-M4 function
selection (relay)
Terminal M5-M6 function
selection (relay)

Description

Values

Default: 0
Range: 0 to 192
Refer to H2 Multi-Function Digital Output Settings on pages 268 to 270 for
Default: 1
descriptions of setting values.
Range: 0 to 192
Default: 2
Range: 0 to 192
All Modes

Page
103
103
103

All Modes

Watt Hour Output Unit


Selection

Default: 0
Range: 0 to 4

113

Parameter List

H2-06
(437)

Outputs a 200 ms pulse signal when the watt-hour counter increases by the
units selected.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

267

A.9 H Parameters: Multi-Function Terminals


H2 Multi-Function Digital Output Settings
H2-oo
Setting

Function

Description
All Modes

During run

Zero speed

Speed agree 1

User-set speed agree 1

Closed: Output frequency and speed reference equal L4-01 (plus or minus the hysteresis set to
L4-02).

Frequency detection 1

Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis determined
by L4-02.

Frequency detection 2

Closed: Output frequency is greater than or equal to the value in L4-01 with hysteresis determined
by L4-02.

Drive ready

DC bus undervoltage

During baseblock (N.O.)

Frequency reference source

Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or b1-15).
Closed: Digital operator supplies the frequency reference.

Run command source

Open: External Reference 1 or 2 supplies the Run command (set in b1-02 or b1-16).
Closed: Digital operator supplies the Run command.

Torque detection 1 (N.O.)

Frequency reference loss

Fault

Through mode

10

Minor fault

11

Fault reset command active

12

Timer output

13

Speed agree 2

14

User-set speed agree 2

15

Frequency detection 3

Closed: A Run command is active or voltage is output.

Page
104

All Modes

Open: Output frequency is above the minimum output frequency set in E1-09.
Closed: Output frequency is below the minimum output frequency set in E1-09.
All Modes

Closed: Output frequency equals the speed reference (plus or minus the hysteresis set to L4-02).

104
105

All Modes

105

All Modes

106

All Modes

All Modes

Closed: Power up is complete and the drive is ready to accept a Run command.
All Modes

Closed: DC bus voltage is below the Uv trip level set in L2-05.


All Modes

Closed: Drive has entered the baseblock state (no output voltage).

106
106
107
107

All Modes

107

All Modes

All Modes

Closed: An overtorque or undertorque situation has been detected.


All Modes

Closed: Analog frequency reference has been lost.


All Modes

Closed: Fault occurred.


All Modes

Set this value when using the terminal in the pass-through mode.
All Modes

Closed: An alarm has been triggered, or the IGBTs have reached 90% of their expected life span.

107
107
107
107
107
108

All Modes

268

Closed: A command has been entered to clear a fault via the input terminals or from the serial
network.
All Modes

Closed: Timer output.


All Modes

Closed: When drive output frequency equals the frequency reference L4-04.
All Modes

Closed: When the drive output frequency is equal to the value in L4-03 L4-04.
All Modes

Closed: When the drive output frequency is less than or equal to the value in L4-03 L4-04.

108
108
108
108
109

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.9 H Parameters: Multi-Function Terminals


H2 Multi-Function Digital Output Settings
H2-oo
Setting

Function

16

Frequency detection 4

17

Torque detection 1 (N.C.)

18

Torque detection 2 (N.O.)

19

Torque detection 2 (N.C.)

1A

During reverse

1B

During baseblock (N.C.)

1C

Motor 2 selection

Description
All Modes

Closed: When the output frequency is greater than or equal to the value in L4-03 L4-04.

Page
109

All Modes

Open: Overtorque or undertorque has been detected.


All Modes

107

Closed: Overtorque or undertorque has been detected.


All Modes

Open: Overtorque or undertorque has been detected.


All Modes

Closed: Drive is running in the reverse direction.


All Modes

Open: Drive has entered the baseblock state (no output voltage).
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

107
110
110

CLV

110

Closed: Motor 2 is selected by a digital input (H1-oo = 16)


1D

During regeneration

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

110

Closed: Motor is regenerating energy into the drive.


1E

Restart enabled

1F

Motor overload alarm (oL1)

20

Drive overheat pre-alarm (oH)

22

Mechanical weakening
detection

2F

Maintenance period

30

During torque limit

All Modes

Closed: An automatic restart is performed


All Modes

Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm.
All Modes

Closed: Heatsink temperature exceeds the parameter L8-02 value.


All Modes

110
111
111
111

Closed: Mechanical weakening detected.


All Modes

Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require
maintenance.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

111

CLV

111

Closed: When the torque limit has been reached.


31

During speed limit

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

111

Closed: Speed limit has been reached.


32

33

During speed limit in Torque


Control

Zero Servo complete

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

111

Closed: Speed limit has been reached while using Torque Control.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

111

Closed: Zero Servo operation has finished.

37

During frequency output

38

Drive enabled

39

Watt hour pulse output

Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
All Modes

Closed: Multi-function input set for Drive enable is closed (H1-oo = 6A)
All Modes

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

111

112
112

269

Parameter List

All Modes

A.9 H Parameters: Multi-Function Terminals


H2 Multi-Function Digital Output Settings
H2-oo
Setting

Function

Description

Page

All Modes

3C

LOCAL/REMOTE status

3D

During speed search

112

Open: REMOTE
Closed: LOCAL
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

112

Closed: Speed Search is being executed.


3E

PID feedback low

3F

PID feedback high

4A

During KEB Ride-Thru

4C

During fast stop

4D

oH Pre-alarm time limit

60

Internal cooling fan alarm

90 to 92

DriveWorksEZ
digital outputs 1 to 3

All Modes

112

Closed: PID feedback level is too low.


All Modes

112

Closed: The PID feedback level is too high.


All Modes

112

Closed: KEB Ride-Thru is being performed.


All Modes

Closed: A Fast Stop command has been entered from the operator or input terminals.
All Modes

112
112

Closed: oH pre-alarm time limit has passed.


All Modes

112

Closed: Internal cooling fan alarm


All Modes

112

Reserved for DWEZ digital output functions.


All Modes

0 to 92 with inverse
100 to 192 Function
Inverts the output switching of the multi-function output functions.
output
Set the last two digits of 1oo to reverse the output signal of that specific function.

112

u H3: Multi-Function Analog Inputs


No.
(Addr.
Hex)

Name

H3-01
(410)

Terminal A1 Signal Level


Selection

H3-02
(434)

Terminal A1 Function
Selection

H3-03
(411)

Terminal A1 Gain Setting

H3-04
(412)

Terminal A1 Bias Setting

H3-05
(413)

Terminal A3 Signal Level


Selection

H3-06
(414)

Terminal A3 Function
Selection

H3-07
(415)

Terminal A3 Gain Setting

H3-08
(416)

Terminal A3 Bias Setting

270

Description
All Modes

0: 0 to 10 V
1: -10 to 10 V
All Modes

Sets the function of terminal A1.


All Modes

Sets the level of the input value selected in H3-02 when 10 V is input at
terminal A1.

Values
Default: 0
Range: 0, 1

113

Default: 0
Range: 0 to 31

113

Default: 100.0%
Min.: -999.9
Max.: 999.9

113

All Modes
Default: 0.0%
Sets the level of the input value selected in H3-02 when 0 V is input at terminal Min.: -999.9
Max.: 999.9
A1.
All Modes

0: 0 to 10 V
1: -10 to 10 V
All Modes

Sets the function of terminal A3.


All Modes

Sets the level of the input value selected in H3-06 when 10 V is input at
terminal A3.

Page

113

Default: 0
Range: 0, 1

114

Default: 2
Range: 0 to 31

114

Default: 100.0%
Min.: -999.9
Max.: 999.9

115

All Modes
Default: 0.0%
Sets the level of the input value selected in H3-06 when 0 V is input at terminal Min.: -999.9
Max.: 999.9
A3.

115

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.9 H Parameters: Multi-Function Terminals


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

H3-09
(417)

Terminal A2 Signal Level


Selection

0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:

H3-10
(418)

Terminal A2 Function
Selection

H3-11
(419)

Terminal A2 Gain Setting

H3-12
(41A)

Terminal A2 Bias Setting

H3-13
(41B)

Analog Input Filter Time


Constant

Default: 2
Range: 0 to 3

115

Default: 0
Range: 0 to 31

115

Use DIP switch S1 to set input terminal A2 for a current or a


voltage input signal.

All Modes

Sets the function of terminal A2.

All Modes
Default: 100.0%
Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input Min.: -999.9
Max.: 999.9
at terminal A2.
All Modes

Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is
input at terminal A2.

Default: 0.0%
Min.: -999.9
Max.: 999.9

All Modes
Default: 0.03 s
Sets a primary delay filter time constant for terminals A1, A2, and A3. Used Min.: 0.00
Max.: 2.00
for noise filtering.

115

115

115

All Modes

H3-14
(41C)

Analog Input Terminal


Enable Selection

H3-16
(2F0)

Terminal A1 Offset

H3-17
(2F1)

Terminal A2 Offset

H3-18
(2F2)

Terminal A3 Offset

Determines which analog input terminals will be enabled when a digital input
programmed for Analog input enable (H1-oo = C) is activated.
1: Terminal A1 only
Default: 7
2: Terminal A2 only
Range: 1 to 7
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Default: 0
All Modes
Min.: -500
Adds an offset when the analog signal to terminal A1 is at 0 V.
Max.: 500
All Modes

Adds an offset when the analog signal to terminal A2 is at 0 V.


All Modes

Adds an offset when the analog signal to terminal A3 is at 0 V.

116

116

Default: 0
Min.: -500
Max.: 500

116

Default: 0
Min.: -500
Max.: 500

116

H3 Multi-Function Analog Input Settings


H3-oo
Setting

Function

Description
All Modes

Frequency bias

Frequency gain

Auxiliary frequency reference 1


(used as a Multi-Step Speed 2)

10 V = E1-04 (maximum output frequency)

Auxiliary frequency reference 2


(3rd step analog)

10 V = E1-04 (maximum output frequency)

Output voltage bias

10 V = E1-04 (maximum output frequency)

Page
116

All Modes

All Modes

All Modes
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

117
117
117

CLV

117

10 V = E1-05 (motor rated voltage)


5

Accel/decel time gain

All Modes

10 V = 100%

117

Parameter List

0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100


to 0%.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

271

A.9 H Parameters: Multi-Function Terminals


H3 Multi-Function Analog Input Settings
H3-oo
Setting
6

Function
DC Injection Braking current

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Page

CLV

117

10 V = Drive rated current


7

Overtorque/undertorque
detection level

Stall Prevention level during run

All Modes

10 V = Drive rated current (V/f, V/f w PG)


10 V = Motor rated torque (OLV, CLV, OLV/PM, AOLV/PM, CLV/PM)
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

117

CLV

118

10 V = Drive rated current


9

Output frequency lower limit level

PID feedback

PID setpoint

Frequency bias

Motor temperature (PTC input)

Through mode

10

Forward torque limit

All Modes

10 V = E1-04 (maximum output frequency)


All Modes

118
118

10 V = 100%
All Modes

118

10 V = 100%
All Modes

10 V = E1-04 (maximum output frequency)


All Modes

118
118

10 V = 100%
All Modes

Set this value when using the terminal in the pass-through mode.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

118

CLV

118

10 V = Motor rated torque


11

Reverse torque limit

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

118

10 V = Motor rated torque


12

Regenerative torque limit

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

118

10 V = Motor rated torque


13

Torque reference/Torque limit

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

118

10 V = Motor rated torque


14

Torque compensation

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

118

10 V = Motor rated torque


15

General torque limit

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

118

10 V = Motor rated torque


16

Differential PID feedback

All Modes

118

10 V = 100%
All Modes

17

Motor Thermistor (NTC)

10 V = -9 C
0 V = 234 C
Note:

1F
30 to 32

272

Through mode
DriveWorksEZ
analog input 1 to 3

118
This function is only available in models CIMR-Ao4A0930, 4A1200 and
A1000 HHP.

All Modes

Set this value when using the terminal in the pass-through mode.
All Modes

Output is determined by the function selected using DWEZ.

118
118

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.9 H Parameters: Multi-Function Terminals

u H4: Analog Outputs


No.
(Addr.
Hex)

Name

Description

Values

Page

Default: 102
Range: 000 to 999

119

Default: 100.0%
Min.: -999.9
Max.: 999.9

119

All Modes

H4-01
(41D)
H4-02
(41E)
H4-03
(41F)

Multi-Function Analog
Output Terminal FM
Monitor Selection
Multi-Function Analog
Output Terminal FM Gain
Multi-Function Analog
Output Terminal FM Bias

Selects the data to be output through multi-function analog output terminal


FM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter 103 for U1-03.
All Modes

Sets the signal level at terminal FM that is equal to 100% of the selected
monitor value.

All Modes
Default: 0.0%
Sets the signal level at terminal FM that is equal to 0% of the selected monitor Min.: -999.9
Max.: 999.9
value.

119

All Modes

H4-04
(420)
H4-05
(421)
H4-06
(422)

Multi-Function Analog
Output Terminal AM
Monitor Selection
Multi-Function Analog
Output Terminal AM Gain
Multi-Function Analog
Output Terminal AM Bias

Selects the data to be output through multi-function analog output terminal


AM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter 103 for U1-03.
All Modes

Sets the signal level at terminal AM that is equal to 100% of the selected
monitor value.

Default: 103
Range: 000 to 999

119

Default: 50.0%
Min.: -999.9
Max.: 999.9

119

All Modes
Default: 0.0%
Sets the signal level at terminal AM that is equal to 0% of the selected monitor Min.: -999.9
Max.: 999.9
value.

119

All Modes

H4-07
(423)

Multi-Function Analog
Output Terminal FM Signal 0: 0 to 10 V
1: -10 to 10 V
Level Selection
2: 4 to 20 mA

H4-08
(424)

Multi-Function Analog
Output Terminal AM Signal 0: 0 to 10 V
1: -10 to 10 V
Level Selection
2: 4 to 20 mA

Default: 0
Range: 0 to 2

120

Default: 0
Range: 0 to 2

120

All Modes

u H5: MEMOBUS/Modbus Serial Communication


No.
(Addr.
Hex)
H5-01
(425)
<1>

Name

Description
All Modes

Drive Node Address

Selects drive station node number (address) for MEMOBUS/Modbus


terminals R+, R-, S+, S-. Cycle power for the setting to take effect.

Values

Page

Default: 1F (Hex)
Min.: 0
Max.: FF

120

Default: 3
Range: 0 to 8

120

Default: 0
Range: 0 to 2

121

H5-02
(426)

Communication Speed
Selection

H5-03
(427)

Communication Parity
Selection

All Modes

0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.

Parameter List

All Modes

0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

273

A.9 H Parameters: Multi-Function Terminals


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

H5-04
(428)

0: Ramp to stop
Stopping Method after
Communication Error (CE) 1: Coast to stop
2: Fast Stop
3: Alarm only

H5-05
(429)

Communication Fault
Detection Selection

H5-06
(42A)

Drive Transmit Wait Time

H5-07
(42B)

RTS Control Selection

0: Disabled. RTS is always on.


1: Enabled. RTS turns on only when sending.

H5-09
(435)

CE Detection Time

Sets the time required to detect a communications error.


Adjustment may be needed when networking several drives.

H5-10
(436)

Unit Selection for


MEMOBUS/Modbus
Register 0025H

Default: 0
Range: 0 to 3

121

Default: 0
Range: 0, 1

121

Default: 5 ms
Min.: 5
Max.: 65

121

Default: 1
Range: 0, 1

121

Default: 2.0 s
Min.: 0.0
Max.: 10.0

122

Default: 0
Range: 0, 1

122

All Modes

0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault
will occur.
All Modes

Set the wait time between receiving and sending data.


All Modes

All Modes

All Modes

0: 0.1 V units
1: 1 V units
All Modes

H5-11
(43C)

Communications ENTER
Function Selection

H5-12
(43D)

Run Command Method


Selection

0: Drive requires an Enter command before accepting any changes to


Default: 1
parameter settings.
Range: 0, 1
1: Parameter changes are activated immediately without the Enter command
(same as V7).
All Modes

Default: 0
Range: 0, 1

0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV

122

122

<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.

u H6: Pulse Train Input/Output


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

H6-01
(42C)

0: Frequency reference
Pulse Train Input Terminal 1: PID feedback value
Default: 0
RP Function Selection
Range: 0 to 3
2: PID setpoint value
3: V/f Control with Simple PG feedback (possible only when using motor 1
in V/f Control)

123

H6-02
(42D)

Pulse Train Input Scaling

All Modes
Default: 1440 Hz
Sets the terminal RP input signal frequency that is equal to 100% of the value Min.: 1000
Max.: 32000
selected in H6-01.

124

H6-03
(42E)

Pulse Train Input Gain

All Modes
Default: 100.0%
Sets the level of the value selected in H6-01 when a frequency with the value Min.: 0.0
Max.: 1000.0
set in H6-02 is input.

124

H6-04
(42F)

Pulse Train Input Bias

Sets the level of the value selected in H6-01 when 0 Hz is input.

H6-05
(430)

274

All Modes

All Modes

Pulse Train Input Filter Time Sets the pulse train input filter time constant.

Default: 0.0%
Min.: -100.0
Max.: 100.0

124

Default: 0.10 s
Min.: 0.00
Max.: 2.00

124

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.9 H Parameters: Multi-Function Terminals


No.
(Addr.
Hex)
H6-06
(431)

H6-07
(432)

Description

Values

Page

Default: 102
Range: 000 to 809

124

All Modes

Pulse Train Monitor


Selection

Select the pulse train monitor output function (value of the o-oo part of
Uo-oo).
For example, enter 501 for U5-01.
All Modes

Default: 1440 Hz
Pulse Train Monitor Scaling Sets the terminal MP output signal frequency when the monitor value is 100%. Min.: 0
To have the pulse train monitor output equal the output frequency, set H6-06 Max.: 32000
to 2 and H6-07 to 0.

124

All Modes
Default: 0.5 Hz
Pulse Train Input Minimum
Min.: 0.1
Sets
the
minimum
frequency
for
the
pulse
train
input
to
be
detected.
Enabled
Frequency
Max.: 1000.0
when H6-01 = 0, 1, or 2.

124

Parameter List

H6-08
(43F)

Name

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

275

A.10 L: Protection Function

A.10 L: Protection Function


L parameters provide protection to the drive and motor, including control during momentary power loss, Stall Prevention,
frequency detection, fault restarts, overtorque detection, torque limits, and other types of hardware protection.

u L1: Motor Protection


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

0: Disabled
1: General purpose motor (standard fan cooled)
2: Drive dedicated motor with a speed range of 1:10
3: Vector motor with a speed range of 1:100
Default: <1>
4: PM motor with variable torque
Range: 0 to 6
5: PM motor with constant torque control
6: General purpose motor (50 Hz)
The drive may not be able to provide protection when using multiple motors,
even if overload is enabled in L1-01. Set L1-01 to 0 and install separate thermal
relays to each motor.

L1-01
(480)

Motor Overload Protection


Selection

L1-02
(481)

Motor Overload Protection


Time

L1-03
(482)

Motor Overheat Alarm


Operation Selection
(PTC input)

Sets operation when the motor temperature analog input (H3-02, H3-06, or
H3-10 = E) exceeds the oH3 alarm level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)
3: Alarm only (oH3 will flash)

L1-04
(483)

Motor Overheat Fault


Operation Selection
(PTC input)

Sets stopping method when the motor temperature analog input (H3-02,
H3-06, or H3-10 = E) exceeds the oH4 fault level.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (decelerate to stop using the deceleration time in C1-09)

L1-05
(484)

Motor Temperature Input


Filter Time (PTC input)

L1-13
(46D)

Continuous Electrothermal
Operation Selection

All Modes

Sets the motor thermal overload protection (oL1) time.

125

Default: 1.0 min


Min.: 0.1
Max.: 5.0

127

Default: 3
Range: 0 to 3

128

Default: 1
Range: 0 to 2

128

Default: 0.20 s
Min.: 0.00
Max.: 10.00

128

Default: 1
Range: 0, 1

128

Default: 0
Range: 0 to 2

129

Default: 120 C
Min.: 50
Max.: 200

130

Default: 0
Range: 0 to 2

130

Default: 120 C
Min.: 50
Max.: 200

130

All Modes

All Modes

All Modes

Adjusts the filter for the motor temperature analog input (H3-02, H3-06, or
H3-10 = E).
All Modes

0: Disabled
1: Enabled
All Modes

L1-15
(440)

Motor 1 Thermistor
Selection (NTC)

L1-16
(441)

Motor 1 Overheat
Temperature

L1-17
(442)

Motor 2 Thermistor
Selection (NTC)

L1-18
(443)

Motor 2 Overheat
Temperature

Sets the input selection for Motor #1 Thermistor.


0: Disabled
1: Thermistor input by Analog Input
2: Thermistor input by special Thermistor Input

All Modes

Sets the range of the Motor #1 oH5 trip level.


All Modes

276

Sets the input selection for Motor #2 Thermistor.


0: Disabled
1: Thermistor input by Analog Input
2: Thermistor input by special Thermistor Input
All Modes

Sets the range of the Motor #2 oH5 trip level.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.10 L: Protection Function


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

L1-19
(444)

Operation at Thermistor
Disconnect (THo) (NTC)

Sets the action for when a thermistor open circuit is detected.


0: Ramp stop
1: Coast stop
2: Fast Stop (decelerate to stop using the deceleration time set to C1-09)
3: Alarm, Continue Running

Default: 3
Range: 0 to 3

130

Default: 1
Range: 0 to 3

130

Default: 0
Range: 0,1

131

All Modes

L1-20
(445)

Sets the action for when a oH5 is detected in either Motor #1 or Motor #2.
Operation at Motor Overheat 0: Ramp stop
(oH5)
1: Coast stop
2: Fast Stop (decelerate to stop using the deceleration time set to C1-09)
3: Alarm, Continue Running
All Modes

L1-21
(73A)

Thermally sensitive resistor Sets the type of thermistor input for Motor #1 and Motor #2: either NTC or
Pt100.
selection
0: H5 table selection
1: Pt100 table selection

<1> Default setting is determined by parameter A1-02, Control Method Selection.

u L2: Momentary Power Loss Ride-Thru


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

0: Disabled. Drive trips on Uv1 fault when power is lost.


1: Recover within the time set in L2-02. Uv1 will be detected if power loss is
Default: 0
longer than L2-02.
Range: 0 to 5
2: Recover as long as CPU has power. Uv1 is not detected.
3: KEB deceleration for the time set to L2-02.
4: KEB deceleration as long as CPU has power.
5: KEB deceleration to stop.

L2-01
(485)

Momentary Power Loss


Operation Selection

L2-02
(486)

Momentary Power Loss


Ride-Thru Time

L2-03
(487)

Momentary Power Loss


Minimum Baseblock Time

L2-04
(488)

Momentary Power Loss


Voltage Recovery Ramp
Time

Default: <1>
Min.: 0.0 s
Sets the time for the output voltage to return to the preset V/f pattern during Max.: 5.0 s
Speed Search.

L2-05
(489)

Undervoltage Detection
Level (Uv1)

Sets the DC bus undervoltage trip level.

L2-07
(48B)

KEB Acceleration Time

L2-10
(48E)

KEB Detection Time


(Minimum KEB Time)

L2-11
(461)

DC Bus Voltage Setpoint


during KEB

All Modes

Sets the Power Loss Ride-Thru time. Enabled only when L2-01 = 1 or 3.

Default: <1>
Min.: 0.0 s
Max.: 25.5 s

131

135

All Modes

<1>
Sets the minimum wait time for residual motor voltage decay before the drive Default:
Min.: 0.1 s
output reenergizes after performing Power Loss Ride-Thru.
Increasing the time set to L2-03 may help if overcurrent or overvoltage occur Max.: 5.0 s
during Speed Search or during DC Injection Braking.

V/f w PG

OLV

AOLV/PM

CLV/PM

CLV

All Modes

Default: 400 Vdc


<2> <3>

Min.: 300 Vdc


Max.: 420 Vdc <3>

All Modes
Default: 0.00 s
Sets the time to accelerate to the frequency reference when momentary power Min.: 0.00 <4>
Max.: 6000.0
loss is over. If set to 0.0, the active acceleration time is used.
Default: 50 ms
All Modes
Min.: 0
Sets the time to perform KEB Ride-Thru.
Max.: 2000
All Modes

Sets the desired value of the DC bus voltage during KEB Ride-Thru.

136

Default: <2>
[E1-01] 1.22
Min.: 300 Vdc
Max.: 800 Vdc <5>

136

136

136

136

<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter List

V/f

OLV/PM

135

277

A.10 L: Protection Function


<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<4> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<5> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.

u L3: Stall Prevention


No.
(Addr.
Hex)

L3-01
(48F)

Name

Stall Prevention Selection


during Acceleration

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Stall Prevention Level


during Acceleration

L3-03
(491)

Stall Prevention Limit


during Acceleration

Page

CLV

0: Disabled.
1: General purpose. Acceleration is paused as long as the current is above the Default: 1
Range: 0 to 2
L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without exceeding the
L3-02 level.
Note:

L3-02
(490)

Values

137

Setting 2 is not available when using OLV/PM.

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Used when L3-01 = 1 or 2. 100% is equal to the drive rated current.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets Stall Prevention lower limit during acceleration when operating in the
constant power range. Set as a percentage of drive rated current.

Default: <1>
Min.: 0%
Max.: 150%

<1>

Default: 50%
Min.: 0
Max.: 100

138

138

All Modes

L3-04
(492)

Stall Prevention Selection


during Deceleration

0: Disabled. Deceleration at the active deceleration rate. An ov fault may


occur.
1: General purpose. Deceleration is paused when the DC bus voltage exceeds
the Stall Prevention level.
2: Intelligent. Decelerate as fast as possible while avoiding ov faults.
Default: 1
3: Stall Prevention with braking resistor. Stall Prevention during deceleration
Range: 0 to 5 <2>
is enabled in coordination with dynamic braking.
4: Overexcitation Deceleration. Decelerates while increasing the motor flux.
5: Overexcitation Deceleration 2. Adjust the deceleration rate according to the
DC bus voltage.
Note:

L3-05
(493)

Stall Prevention Selection


during Run

L3-06
(494)

Stall Prevention Level


during Run

Setting 3 is not available in models CIMR-Ao4A0930 and


4A1200. A1000 HHP models only have settings 0, 1, 4, and 5.

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

0: Disabled. Drive runs at a set frequency. A heavy load may cause speed loss. Default: 1
1: Decel time 1. Uses the deceleration time set to C1-02 while Stall Prevention Range: 0 to 2
is performed.
2: Decel time 2. Uses the deceleration time set to C1-04 while Stall Prevention
is performed.
V/f

139

V/f w PG

OLV

140

CLV

Default: <1>
Min.: 30%
OLV/PM
AOLV/PM
CLV/PM
Enabled when L3-05 is set to 1 or 2. 100% is equal to the drive rated current. Max.: 150%

<1>

140

All Modes

Enables or disables the ov suppression function, which allows the drive to


change the output frequency as the load changes to prevent an ov fault.
0: Disabled
1: Enabled

L3-11
(4C7)

Overvoltage Suppression
Function Selection

L3-17
(462)

Default: 370 Vdc


All Modes
Target DC Bus Voltage for
<3> <8>
Sets the desired value for the DC bus voltage during overvoltage suppression
Overvoltage Suppression
Min.: 150
and
Stall
Prevention
during
deceleration.
and Stall Prevention
Max.: 400 <8>

278

Default: 0
Range: 0, 1

141

141

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.10 L: Protection Function


No.
(Addr.
Hex)
L3-22
(4F9)

Name
Deceleration Time at Stall
Prevention during
Acceleration

L3-23
(4FD)

Automatic Reduction
Selection for Stall
Prevention during Run

L3-27
(456)

Stall Prevention Detection


Time

<1>
<2>
<3>
<8>

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the deceleration time used for Stall Prevention during acceleration in
OLV/PM.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values
Default: 0.0 s
Min.: 0.0
Max.: 6000

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

138

CLV

0: Sets the Stall Prevention level set in L3-04 that is used throughout the entire Default: 0
Range: 0, 1
frequency range.
1: Automatic Stall Prevention level reduction in the constant output range. The
lower limit value is 40% of L3-06.
OLV/PM

Page

CLV

Sets the time the current must exceed the Stall Prevention level to activate
Stall Prevention.

Default: 50 ms
Min.: 0
Max.: 5000

140

141

Upper limit is dependent on parameters C6-01, Drive Duty Selection, and L8-38, Frequency Reduction Selection.
The setting range is 0 to 2 in OLV/PM control mode. The setting range is 0 and 1 in CLV or AOLV/PM control modes.
Default setting is dependent on parameter E1-01, Input voltage Setting.
Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.

u L4: Speed Detection


No.
(Addr.
Hex)

Name

Description

Values

Page

L4-01
(499)

Speed Agreement Detection


L4-01 sets the frequency detection level for digital output functions
Level
H2-oo = 2, 3, 4, 5.

Default: 0.0 Hz
Min.: 0.0
Max.: 150.0

141

L4-02
(49A)

Speed Agreement Detection All Modes


L4-02 sets the hysteresis or allowable margin for speed detection.
Width

Default: <1>
Min.: 0.0
Max.: 20.0

141

L4-03
(49B)

Speed Agreement Detection


L4-03 sets the frequency detection level for digital output functions
Level (+/-)
H2-oo = 13, 14, 15, 16.

Default: 0.0 Hz
Min.: -150.0
Max.: 150.0

142

L4-04
(49C)

Speed Agreement Detection All Modes


L4-04 sets the hysteresis or allowable margin for speed detection.
Width (+/-)

Default: <1>
Min.: 0.0
Max.: 20.0

142

L4-05
(49D)

Frequency Reference Loss


Detection Selection

Default: 0
Range: 0, 1

142

L4-06
(4C2)

Frequency Reference at
Reference Loss

L4-07
(470)

Speed Agreement Detection


0: No detection during baseblock.
Selection
1: Detection always enabled.

All Modes

All Modes

All Modes

0: Stop. Drive stops when the frequency reference is lost.


1: Run. Drive runs at a reduced speed when the frequency reference is lost.

All Modes
Default: 80%
Sets the percentage of the frequency reference that the drive should run with Min.: 0.0
Max.: 100.0
when the frequency reference is lost.
All Modes

Default: 0
Range: 0, 1

142

142

Parameter List

<1> Default setting is dependent on parameter A1-02, Control Method Selection.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

279

A.10 L: Protection Function

u L5: Fault Restart


No.
(Addr.
Hex)

Name

L5-01
(49E)

Number of Auto Restart


Attempts

L5-02
(49F)

Auto Restart Fault Output


Operation Selection

L5-04
(46C)

Fault Reset Interval Time

L5-05
(467)

Fault Reset Operation


Selection

Description

Values

All Modes
Default: 0
Sets the number of times the drive may attempt to restart after the following Min.: 0
Max.: 10
faults occur: GF, LF, oC, ov, PF, rH, rr, oL1, oL2, oL3, oL4, STo, Uv1.
All Modes

0: Fault output not active.


1: Fault output active during restart attempt.
All Modes

Sets the amount of time to wait between performing fault restarts.

Page

143

Default: 0
Range: 0, 1

143

Default: 10.0 s
Min.: 0.5
Max.: 600.0

143

All Modes

0: Continuously attempt to restart while incrementing restart counter only at Default: 0


a successful restart (same as F7 and G7).
Range: 0, 1
1: Attempt to restart with the interval time set in L5-04 and increment the
restart counter with each attempt (same as V7).

144

u L6: Torque Detection


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

L6-01
(4A1)

Torque Detection
Selection 1

L6-02
(4A2)

Torque Detection
Level 1

L6-03
(4A3)

Torque Detection
Time 1

0: Disabled
1: oL3 detection only active during speed agree, operation continues after
detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3
Default: 0
fault
4: oL3 detection always active during run, output shuts down on an oL3 fault Range: 0 to 8
5: UL3 detection only active during speed agree, operation continues after
detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3
fault
8: UL3 detection always active during run, output shuts down on an oL3 fault
All Modes

Sets the overtorque and undertorque detection level.


All Modes

Sets the time an overtorque or undertorque condition must exist to trigger


torque detection 1.

145

Default: 150%
Min.: 0
Max.: 300

145

Default: 0.1 s
Min.: 0.0
Max.: 10.0

145

All Modes

L6-04
(4A4)

Torque Detection
Selection 2

L6-05
(4A5)

Torque Detection
Level 2

L6-06
(4A6)

Torque Detection
Time 2

280

0: Disabled
1: oL4 detection only active during speed agree, operation continues after
detection
2: oL4 detection always active during run, operation continues after detection
3: oL4 detection only active during speed agree, output shuts down on an oL4
Default: 0
fault
4: oL4 detection always active during run, output shuts down on an oL4 fault Range: 0 to 8
5: UL4 detection only active during speed agree, operation continues after
detection
6: UL4 detection always active during run, operation continues after detection
7: UL4 detection only active during speed agree, output shuts down on an oL4
fault
8: UL4 detection always active during run, output shuts down on an oL4 fault
Default: 150%
All Modes
Min.: 0
Sets the overtorque and undertorque detection level.
Max.: 300
All Modes

Sets the time an overtorque or undertorque condition must exist to trigger


torque detection 2.

Default: 0.1 s
Min.: 0.0
Max.: 10.0

145

145

145

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.10 L: Protection Function


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

This function can detect an overtorque or undertorque in a certain speed range


as a result of machine fatigue. It is triggered by a specified operation time and
uses the oL1 detection settings (L6-01 and L6-03).
0: Mechanical Weakening Detection disabled.
1: Continue running (alarm only). Detected when the speed (signed) is greater
than L6-09.
2: Continue running (alarm only). Detected when the speed (not signed) is
greater than L6-09.
3: Interrupt drive output (fault). Detected when the speed (signed) is greater Default: 0
than L6-09.
Range: 0 to 8
4: Interrupt drive output (fault). Detected when the speed (not signed) is greater
than L6-09.
5: Continue running (alarm only). Detected when the speed (signed) is less
than L6-09.
6: Continue running (alarm only). Detected when the speed (not signed) is less
than L6-09.
7: Interrupt drive output (fault). Detected when the speed (signed) is less than
L6-09.
8: Interrupt drive output (fault). Detected when the speed (not signed) is less
than L6-09.

L6-08
(468)

Mechanical Weakening
Detection Operation

L6-09
(469)

Mechanical Weakening
Detection Speed Level

All Modes
Default: 110.0%
Sets the speed that triggers Mechanical Weakening Detection. When L6-08 is Min.: -110.0
set for an unsigned value, the absolute value is used if the setting is negative. Max.: 110.0

146

L6-10
(46A)

Mechanical Weakening
Detection Time

All Modes
Default: 0.1 s
Sets the time mechanical weakening has to be detected before an alarm or fault Min.: 0.0
Max.: 10.0
is triggered.

146

L6-11
(46B)

Mechanical Weakening
Detection Start Time

All Modes

Sets the operation time (U1-04) required before Mechanical Weakening


Detection is active.

Default: 0 h
Min.: 0
Max.: 65535

146

146

u L7: Torque Limit

L7-01
(4A7)

Name
Forward Torque Limit

L7-02
(4A8)

Reverse Torque Limit

L7-03
(4A9)

Forward Regenerative
Torque Limit

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the torque limit value as a percentage of the motor rated torque. Four
individual quadrants can be set.
Output Torque
Positive Torque
L7-01
L7-04
Motor
r/min
Regeneration
REV

FWD
Regeneration

L7-04
(4AA)

Reverse Regenerative
Torque Limit

L7-06
(4AC)

Torque Limit Integral Time


Constant

L7-07
(4C9)

Torque Limit Control


Method Selection during
Accel/Decel

Values

L7-02

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

L7-03
Negative Torque

CLV

Sets the integral time constant for the torque limit.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300
Default: 200%
Min.: 0
Max.: 300

Page
147
147
147

Default: 200%
Min.: 0
Max.: 300

147

Default: 200 ms
Min: 5
Max: 10000

147

CLV

0: Proportional control (changes to integral control at constant speed). Use this Default: 0
setting when acceleration to the desired speed should take precedence over the Range: 0, 1
torque limit.
1: Integral control. Set L7-07 to 1 if the torque limit should take precedence.

147

Parameter List

No.
(Addr.
Hex)

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

281

A.10 L: Protection Function


No.
(Addr.
Hex)

L7-16
(44D)

Name

Torque Limit Enable Time


delay at start

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

L7-30
(1FD)

Regenerative torque limit


mode selection

Page

CLV

Default: 1
Range: 0, 1

0: Disabled.
1: Enabled.
Note:

Values

147

Set this parameter to 0 to improve the response at the rapid


addition and subtraction velocity at start.

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Special Function of regenerative Torque limit for Omron (Same as G5HHP) Default: 0
0: Standard mode (torque limit from all analogs and communications
Range: 0, 1
effective).
1: Independent mode (Only L7-03, 04, and H3-xx=12H (regenerative torque
limit) are effective).

147

u L8: Drive Protection


No.
(Addr.
Hex)
L8-02
(4AE)

Name
Overheat Alarm Level

Description

Values

Default: <1>
An overheat alarm occurs when heatsink temperature exceeds the L8-02 level. Min.: 50 C
Max.: 150 C
All Modes

Page
148

All Modes

0: Ramp to stop. A fault is triggered.


1: Coast to stop. A fault is triggered.
Default: 3
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09. A fault Range: 0 to 4
is triggered.
3: Continue operation. An alarm is triggered.
4: Continue operation at reduced speed as set in L8-19.

L8-03
(4AF)

Overheat Pre-Alarm
Operation Selection

L8-05
(4B1)

Input Phase Loss Protection Selects the detection of input current phase loss, power supply voltage
imbalance, or main circuit electrolytic capacitor deterioration.
Selection
0: Disabled
1: Enabled

L8-07
(4B3)

Output Phase Loss


Protection Selection

L8-09
(4B5)

Output Ground Fault


Detection Selection

L8-10
(4B6)

Heatsink Cooling Fan


Operation Selection

L8-11
(4B7)

Heatsink Cooling Fan Off


Delay Time

L8-12
(4B8)

Ambient Temperature
Setting

L8-15
(4BB)

oL2 Characteristics
Selection at Low Speeds

L8-18
(4BE)

Software Current Limit


Selection

148

All Modes

Default: 1
Range: 0, 1

149

Default: 1
Range: 0 to 2

150

Default: <1>
Range: 0, 1

150

All Modes

282

0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
All Modes

0: Disabled
1: Enabled
All Modes

Default: 0
0: During run only. Fan operates only during run for L8-11 seconds after stop. Range: 0, 1
1: Fan always on. Cooling fan operates whenever the drive is powered up.
All Modes
Default: 60 s
Sets a delay time to shut off the cooling fan after the Run command is removed Min.: 0
Max.: 300
when L8-10 = 0.
Default: 40 C
All Modes
Min.: -10
Enter the ambient temperature. This value adjusts the oL2 detection level.
Max.: 50
All Modes

0: No oL2 level reduction below 6 Hz.


1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

0: Disabled
1: Enabled

150

150

150

Default: 1
Range: 0, 1

151

Default: 0
Range: 0, 1

151

CLV

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.10 L: Protection Function


No.
(Addr.
Hex)
L8-19
(4BF)

Name

Description

Values

All Modes
Default: 0.8
Frequency Reduction Rate
Specifies
the frequency reference reduction gain at overheat pre-alarm when Min.: 0.1
during Overheat Pre-Alarm
Max.: 0.9
L8-03 = 4.

Page

149

All Modes

L8-32
(4E2)

L8-38
(4EF)

Determines drive response when a fault occurs with the internal cooling fan.
Main Contactor and Cooling 0: Ramp to stop
Default: 1
Fan Power Supply Failure 1: Coast to stop
Range: 0 to 4
Selection
2: Fast stop (Decelerate to stop using the deceleration time set to C1-09)
3: Alarm only (FAn will flash)
4: Continue operation at reduced speed as set to L8-19.
Carrier Frequency
Reduction

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Default: <4>
Range: 0 to 2

0: Disabled
1: Enabled below 6 Hz
2: Enabled for the entire speed range
V/f

V/f w PG

OLV

AOLV/PM

151

CLV

Default: <5>
Sets the time that the drive continues running with reduced carrier frequency Min.: 0.00 s
after the carrier reduction condition is gone. Setting 0.00 s disables the carrier Max.: 2.00 s
frequency reduction time.
OLV/PM

151

CLV/PM

L8-40
(4F1)

Carrier Frequency
Reduction Off Delay Time

L8-41
(4F2)

High Current Alarm


Selection

Default: 0
0: Disabled
1: Enabled. An alarm is triggered at output currents above 150% of drive rated Range: 0, 1
current.

L8-78
(2CC)

Module Output Loss


Detection (LF3)

Detects the loss of an output phase in any of the inverter output modules.
0: Disabled
1: Enabled

152

All Modes

152

All Modes

Default: 1
Range: 0, 1

152

Default: 1
Range: 0, 5

152

Default: 1
Range: 0, 5

153

All Modes

L8-86
(2F3)

Detection selection when


panel fan fails

Detects the loss of the drive panel fan by the panel fan input.
0: Ramp Stop (Fault)
1: Coast Stop (Fault)
2: Fast Stop (Fault)
3: Continue Running (Alarm)
4: As for continue Running at L819 Speed
5: Disabled
Note:

Settings 3 and 4 reduce inverter O/L level from 100% to 80 %.

All Modes

L8-87
(2F4)

Detects the loss of the diode converter fan(s) by the fan control input.
0: Ramp Stop (Fault)
1: Coast Stop (Fault)
Detection selection when
2: Fast Stop (Fault)
diode converter(s) fan(s) fail 3: Continue Running (Alarm)
4: As for continue Running at L819 Speed
5: Disabled
Note:

Settings 3 and 4 reduce inverter O/L level from 100% to 80 %.

Parameter List

<1> Default setting is dependent on parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<4> Default setting is dependent on parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<5> Default setting is dependent on parameter A1-02, Control Method Selection.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

283

A.11 n: Special Adjustment

A.11 n: Special Adjustment


The n parameters adjust more advanced performance characteristics such as Hunting Prevention, speed feedback detection,
High Slip Braking, and Online Tuning for motor line-to-line resistance.

u n1: Hunting Prevention


No.
(Addr.
Hex)
n1-01
(580)

Name

Hunting Prevention
Selection

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

n1-02
(581)

Hunting Prevention Gain


Setting

n1-03
(582)

Hunting Prevention Time


Constant

n1-05
(530)

Hunting Prevention Gain


while in Reverse

Default: 1
Range: 0, 1

V/f w PG

OLV

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

154

CLV

Default: 1.00
Min.: 0.00
If the motor vibrates while lightly loaded, increase the gain by 0.1 until
vibration ceases. If the motor stalls, decrease the gain by 0.1 until the stalling Max.: 2.50
ceases.
OLV/PM

Page

CLV

0: Disabled
1: Enabled
V/f

Values

CLV

154

Default: <1>
Min.: 0 ms
Max.: 500 ms

154

Default: 0.00
Min.: 0.00
Sets the gain used for Hunting Prevention. If set to 0, the gain set to n1-02 is Max.: 2.50
used for operation in reverse.

154

Sets the time constant used for Hunting Prevention.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.

u n2: Speed Feedback Detection Control (AFR) Tuning


No.
(Addr.
Hex)

Name

n2-01
(584)

Speed Feedback Detection


Control (AFR) Gain

n2-02
(585)

Speed Feedback Detection


Control (AFR) Time
Constant 1

n2-03
(586)

Speed Feedback Detection


Control (AFR) Time
Constant 2

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values

CLV

Default: 1.00
Sets the internal speed feedback detection control gain in the automatic
Min.: 0.00
frequency regulator (AFR).
Max.: 10.00
If hunting occurs, increase the set value. If response is low, decrease the set
value.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the time constant used for speed feedback detection control (AFR).
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Page

Default: 50 ms
Min.: 0
Max.: 2000

154

155

CLV

Default: 750 ms
Min.: 0
Sets the AFR time constant to be used during Speed Search and during regen. Max.: 2000

155

u n3: High Slip Braking (HSB) and Overexcitation Braking


No.
(Addr.
Hex)

Name

Description
V/f

n3-13
(531)

284

V/f w PG

OLV

CLV

Overexcitation Deceleration
OLV/PM
AOLV/PM
CLV/PM
Gain
Sets the gain applied to the V/f pattern during Overexcitation Deceleration
(L3-04 = 4).

Values
Default: 1.10
Min.: 1.00
Max.: 1.40

Page

156

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.11 n: Special Adjustment


No.
(Addr.
Hex)
n3-21
(579)

High-Slip Suppression
Current Level

Overexcitation Operation
Selection

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Page

CLV

Sets output current level at which the drive will start reducing the
overexcitation gain in order to prevent a too high motor slip during
Overexcitation Deceleration. Set as a percentage of the drive rated current.
V/f

Values

Default: 100%
Min.: 0
Max.: 150

156

Default: 0
Range: 0 to 2

156

CLV

0: Enabled in both directions


1: Enabled only when rotating forward
2: Enabled only when in reverse

Parameter List

n3-23
(57B)

Name

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

285

A.12 o: Operator-Related Settings

A.12 o: Operator-Related Settings


The o parameters set up the digital operator displays.

u o1: Digital Operator Display Selection


No.
(Addr.
Hex)
o1-01
(500)

Name

Description
All Modes

Drive Mode Unit Monitor


Selection

Selects the content of the last monitor that is shown when scrolling through
Drive Mode display. Enter the last three digits of the monitor parameter
number to be displayed: Uo-oo.

Values

Page

Default: 106
(Monitor U1-06)
Range: 104 to 809

157

Default: 1
Range: 1 to 5

157

All Modes

o1-02
(501)

1: Frequency reference (U1-01)


User Monitor Selection after 2: Direction
Power Up
3: Output frequency (U1-02)
4: Output current (U1-03)
5: User-selected monitor (set by o1-01)
All Modes

o1-03
(502)

Digital Operator Display


Selection

o1-04
(503)

V/f Pattern Display Unit

o1-10
(520)

User-Set Display Units


Maximum Value

o1-11
(521)

User-Set Display Units


Decimal Display

Sets the units the drive should use to display the frequency reference and motor
speed monitors.
Default: <1>
0: 0.01 Hz
Range: 0 to 3
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

157

CLV

0: Hz
1: r/min
All Modes

Default: <1>
Range: 0, 1

158

Default: <2>
Range: 1 to 60000

158

These settings define the display values when o1-03 is set to 3.


o1-10 sets the display value that is equal to the maximum output frequency. Default: <2>
o1-11 sets the position of the decimal position.
Range: 0 to 3

158

<1> Default setting is dependent on parameter A1-02, Control Method Selection.


<2> Default setting is dependent on parameter o1-03, Digital Operator Display Selection.

u o2: Digital Operator Keypad Functions


No.
(Addr.
Hex)

Name

o2-01
(505)

LO/RE Key Function


Selection

o2-02
(506)

STOP Key Function


Selection

Description

Values

Page

All Modes

Default: 1
0: Disabled
Range: 0, 1
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
All Modes

0: Disabled. STOP key is disabled in REMOTE operation.


1: Enabled. STOP key is always enabled.

158

Default: 1
Range: 0, 1

159

Default: 0
Range: 0 to 2

159

All Modes

o2-03
(507)

User Parameter Default


Value

o2-04
(508)

Drive Model Selection

286

0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.

Default:
All Modes
Determined by
Enter the drive model. Setting required only if installing a new control board. drive capacity

159

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.12 o: Operator-Related Settings


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

o2-05
(509)

Frequency Reference
Setting Method Selection

o2-06
(50A)

Operation Selection when


Digital Operator is
Disconnected

o2-07
(527)

Motor Direction at Power


Up when Using Operator

Default: 0
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be adjusted using Range: 0, 1
the up and down arrow keys only.
All Modes

0: The drive continues operating if the digital operator is disconnected.


1: An oPr fault is triggered and the motor coasts to stop.

159

Default: 1
Range: 0, 1

160

Default: 0
Range: 0, 1

160

All Modes

o2-09
(50D)

0: Forward
1: Reverse
This parameter requires assigning drive operation to the digital operator.
Factory use.

Values

Page

u o3: Copy Function


No.
(Addr.
Hex)

Name

Description
All Modes

o3-01
(515)

Copy Function Selection

o3-02
(516)

Copy Allowed Selection

0: No action
Default: 0
1: Read parameters from the drive, saving them onto the digital operator.
Range: 0 to 3
2: Copy parameters from the digital operator, writing them to the drive.
3: Verify parameter settings on the drive to check if they match the data saved
on the operator.
All Modes

Default: 0
Range: 0, 1

0: Read operation prohibited


1: Read operation allowed

160

160

u o4: Maintenance Monitor Settings


Name

Description

Values

o4-01
(50B)

Default: 0 h
Cumulative Operation Time All Modes
Min.: 0
Setting
Sets the value for the cumulative operation time of the drive in units of 10 h. Max.: 9999

o4-02
(50C)
o4-03
(50E)

Cumulative Operation Time


Default: 0
0: Logs power-on time
Selection
Range: 0, 1
1: Logs operation time when the drive output is active (output operation time).
Default: 0 h
Cooling Fan Operation Time All Modes
Min.: 0
Setting
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Max.: 9999

o4-05
(51D)

Capacitor Maintenance
Setting

o4-07
(523)

DC Bus Pre-Charge Relay


Maintenance Setting

o4-09
(525)

IGBT Maintenance Setting

Page
161

All Modes

161

161

Default: 0%
Min.: 0
Max.: 150

161

Default: 0%
Min.: 0
Max.: 150

161

All Modes
Default: 0%
Sets the value of the Maintenance Monitor for the IGBTs. See U4-07 for IGBT Min.: 0
Max.: 150
replacement times.

161

All Modes

Sets the value of the Maintenance Monitor for the capacitors. See U4-05 to
check when the capacitors may need to be replaced.
All Modes

Sets the value of the Maintenance Monitor for the soft charge bypass relay.
See U4-06 to check when the bypass relay may need to be replaced.

All Modes

o4-11
(510)

U2, U3 Initialization

0: U2-oo and U3-oo monitor data is not reset when the drive is initialized Default: 0
(A1-03).
Range: 0, 1
1: U2-oo and U3-oo monitor data is reset when the drive is initialized
(A1-03).

162

Parameter List

No.
(Addr.
Hex)

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

287

A.12 o: Operator-Related Settings


No.
(Addr.
Hex)

Name

Description

Values

Page

All Modes

o4-12
(512)

Default: 0
0: U4-10 and U4-11 monitor data is not reset when the drive is initialized
Range: 0, 1
(A1-03).
1: U4-10 and U4-11 monitor data is reset when the drive is initialized (A1-03).

kWh Monitor Initialization

o4-13
(528)

Number of Run Commands 0: Number of Run commands counter is not reset when the drive is initialized Default: 0
(A1-03).
Counter Initialization
Range: 0, 1
1: Number of Run commands counter is reset when the drive is initialized
(A1-03).

162

All Modes

288

162

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.13 DriveWorksEZ Parameters

A.13 DriveWorksEZ Parameters


u q: DriveWorksEZ Parameters
No.
(Addr.
Hex)
q1-01 to
q6-07
(1600 to
1746)

Name

Description
All Modes

DriveWorksEZ Parameters

Reserved for DriveWorksEZ

Values

Page

Refer to Help in the


DWEZ software.

162

Values

Page

u r: DriveWorksEZ Connection Parameters

Default: 0
Min.: 0
Max.: FFFF

162

Parameter List

No.
(Addr.
Name
Description
Hex)
r1-01 to DriveWorksEZ Connection
All Modes
r1-40
Parameters
1
to
20
(upper/
DriveWorksEZ
Connection Parameters 1 to 20 (upper/lower)
(1840 to lower)
1867)

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

289

A.14 T: Motor Tuning

A.14 T: Motor Tuning


Enter data into the following parameters to tune the motor and drive for optimal performance.

u T1: Induction Motor Auto-Tuning


No.
(Addr.
Hex)
T1-00
(700)

T1-01
(701)
<1>

T1-02
(702)

Name

Motor 1/Motor 2 Selection

Auto-Tuning Mode
Selection

Motor Rated Power

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

T1-03
(703)

Motor Rated Voltage

Motor Rated Current

T1-05
(705)

Motor Base Frequency

T1-06
(706)

Number of Motor Poles

T1-07
(707)

Motor Base Speed

T1-08
(708)

PG Number of Pulses Per


Revolution

T1-10
(70A)

290

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

CLV

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the motor rated current as specified on the motor nameplate.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the rated frequency of the motor as specified on the motor nameplate.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the number of motor poles as specified on the motor nameplate.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Sets the rated speed of the motor as specified on the motor nameplate.

Motor No-Load Current


(Stationary Auto-Tuning)

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

Default: 0
Range: 0 ,1,2,4 <2>

163

Default: <3>
Min.: 0.00 kW
Max.: 650.00 kW

163

Default: 400.0 V
<4>

Sets the motor rated voltage as specified on the motor nameplate.

T1-04
(704)

T1-09
(709)

Use the following formula to convert horsepower into kilowatts:


1HP = 0.746 kW.

OLV/PM

163

CLV

Sets the motor rated power as specified on the motor nameplate.


Note:

Default: 1
Range: 1, 2
CLV

0: Rotational Auto-Tuning
1: Stationary Auto-Tuning 1
2: Stationary Auto-Tuning for Line-to-Line Resistance
4: Stationary Auto-Tuning 2
OLV/PM

Min: 0.0
Max: 510.0 <4>

164

Default: 60.0 Hz
Min.: 0.0
Max.: 400.0

164

Default: 4
Min.: 2
Max.: 48

164

Default: 1750 r/min


Min.: 0
Max.: 24000

164

CLV

V/f w PG

OLV

AOLV/PM

CLV/PM

164

CLV

OLV/PM
AOLV/PM
CLV/PM
Default:
Sets the no-load current for the motor. After setting the motor capacity to T1-02 Min.: 0 A
and the motor rated current to T1-04, this parameter will automatically display Max.: T1-04
the no-load current for a standard 4-pole Yaskawa motor. Enter the no-load
current as indicated on the motor test report.
V/f

163

Default: <3>
Min.: 10% of drive
rated current
Max.: 200% of
drive rated current

Default: 1024 ppr


Min.: 1
Sets the number of pulses per revolution for the PG being used (pulse generator Max.: 60000
or encoder).

OLV/PM

Page

CLV

1: Motor 1 (sets E1-oo, E2-oo)


2: Motor 2 (sets E3-oo, E4-oo)
OLV/PM

Values

164

CLV

Motor Rated Slip (Stationary


Sets the motor rated slip. After setting the motor capacity to T1-02, this
Auto-Tuning)
parameter will automatically display the motor slip for a standard 4-pole
Yaskawa motor. Enter the motor slip as indicated on the motor test report.

Default:
Min.: 0.00 Hz
Max.: 20.00 Hz

164

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.14 T: Motor Tuning


No.
(Addr.
Hex)

T1-11
(70B)

Name

Motor Iron Loss

Description
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

Values

Page

CLV

Default: 14 W <5>
Sets the iron loss for determining the Energy Saving coefficient.
Min.: 0
The value is set to E2-10 (motor iron loss) set when the power is cycled. If Max.: 65535
T1-02 is changed, a default value appropriate for the motor capacity that was
entered will appear.

165

The availability of certain Auto-Tuning methods depends on the control mode selected for the drive.
Default setting is determined by parameter A1-02, Control Method Setting.
Default setting is dependent on parameter o2-04, Drive Model Selection.
Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<5> Default setting value differs depending on the motor code value and motor parameter settings.

Parameter List

<1>
<2>
<3>
<4>

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

291

A.15 U: Monitors

A.15 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.

u U1: Operation Status Monitors


No.
(Addr.
Hex)

Name

U1-01
(40)

Frequency Reference

U1-02
(41)

Output Frequency

Analog Output
Level

Description
All Modes

Monitors the frequency reference. Display units are determined by o1-03.


All Modes

Displays the output frequency. Display units are determined by o1-03.

Unit

10 V: Max frequency

0.01 Hz

10 V: Max frequency

0.01 Hz

10 V: Drive rated
current

<1> <2>

No signal output
available

All Modes

U1-03
(42)

Output Current

Displays the output current.


Note:

This parameter is only available in models CIMRAo4A0930, 4A1200, and A1000 HHP.

All Modes

U1-04
(43)

Control Method

U1-05
(44)

Motor Speed

U1-06
(45)

Output Voltage Reference

U1-07
(46)

DC Bus Voltage

U1-08
(47)

Output Power

U1-09
(48)

Torque Reference

0: V/f Control
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

10 V: Max frequency

0.01 Hz

Displays the motor speed feedback. Display units are determined by o1-03.
All Modes

10 V: 200 Vrms

Displays the output voltage.


All Modes

10 V: 400 V

Displays the DC bus voltage.


All Modes

Displays the output power (this value is calculated internally).


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Monitors the internal torque reference.

<3>

<3>

10 V: Drive rated power


(kW)

0.1 Vac
1 Vdc
<4>

10 V: Motor rated
torque

0.1%

No signal output
available

All Modes

Displays the input terminal status.

U1 - 10= 00000000

1 Digital input 1
1

U1-10
(49)

1
Input Terminal Status

1
1
1
1
1

292

(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.15 U: Monitors
No.
(Addr.
Hex)

Name

Analog Output
Level

Description

Unit

All Modes

Displays the output terminal status.

U1 - 11= 00000000
1 Multi-Function
Digital Output
U1-11
(4A)

(terminal M1-M2)

1 Multi-Function
Digital Output

Output Terminal Status

1
0
1

(terminal P1)
Multi-Function
Digital Output
(terminal P2)
Not Used
Fault Relay
(terminal MA/MB-MC)

No signal output
available

No signal output
available

All Modes

Verifies the drive operation status.

U1 - 12= 00000000
U1-12
(4B)

Drive Status

1 During run
1 During zero-speed
1 During REV
fault reset
1 During
signal input
1 During speed agree
1 Drive ready
alarm
1 During
detection
1 During fault detection

U1-13
(4E)

Terminal A1 Input Level

U1-14
(4F)

Terminal A2 Input Level

U1-15
(50)

Terminal A3 Input Level

U1-16
(53)

Output Frequency after


Soft Starter

All Modes

Displays the signal level to analog input terminal A1.


All Modes

Displays the signal level to analog input terminal A2.


All Modes

Displays the signal level to analog input terminal A3.

10 V: 100%

0.1%

10 V: 100%

0.1%

10 V: 100%

0.1%

All Modes

Displays output frequency with ramp time and S-curves. Units determined 10 V: Max frequency
by o1-03.

0.01 Hz

All Modes

U1-17
(58)

DI-A3 Input Status

U1-18
(61)

oPE Fault Parameter

Displays the reference value input from the DI-A3 option card.
No signal output
Display will appear in hexadecimal as determined by the digital card input available
selection in F3-01.
3FFFF: Set (1 bit) + sign (1 bit) + 16 bit

All Modes

No signal output
Displays the parameter number that caused the oPEoo or Err (EEPROM available
write error) error.

All Modes

U1 - 19= 00000000
U1-19
(66)

MEMOBUS/Modbus
Error Code

1 CRC Error
1 Data Length Error
0 Not Used
1 Parity Error
1 Overrun Error
1 Framing Error
1 Timed Out
0 Not Used

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

No signal output
available

Parameter List

Displays the contents of a MEMOBUS/Modbus error.

A
293

A.15 U: Monitors
No.
(Addr.
Hex)

Name

Description

Analog Output
Level

Unit

U1-21
(77)

AI-A3 Terminal V1 Input All Modes


Voltage Monitor
Displays the input voltage to terminal V1 on analog input card AI-A3.

10 V: 100%

0.1%

U1-22
(72A)

AI-A3 Terminal V2 Input All Modes


Voltage Monitor
Displays the input voltage to terminal V2 on analog input card AI-A3.

10 V: 100%

0.1%

U1-23
(72B)

AI-A3 Terminal V3 Input All Modes


Voltage Monitor
Displays the input voltage to terminal V3 on analog input card AI-A3.

10 V: 100%

0.1%

U1-24
(7D)

Input Pulse Monitor

Determined by H6-02

1 Hz

U1-25
(4D)

Software Number of
Master CPU (Flash)

FLASH ID: Software number of Master CPU

U1-26
(5B)

Software No. of Slave


CPU (ROM)

ROM ID: Software number of Slave CPU

U1-27
(7A8)

MessageID (OPR)

U1-28
(7A9)

MessageID (INV)

All Modes

Displays the frequency to pulse train input terminal RP.


All Modes

All Modes

All Modes

Factory use
All Modes

Factory use

No signal output
available

No signal output
available

No signal output
available

No signal output
available

No signal output
available

All Modes

U1-29
(7AA)

Software No. (PWM)

PWM ID: Software No. of slave or inverter module axis processors


Note:

This parameter is only available in models CIMRAo4A0930, 4A1200, and A1000 HHP.

<1> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<3> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<4> The display resolution depends on the ND/HD selection in parameter C6-01. This value has two decimal places (0.01 kW) if the drive is set for a
maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 kW) if the maximum applicable motor capacity is
higher than 11 kW.

u U2: Fault Trace


No.
(Addr.
Hex)

Name

Description

U2-01
(80)

Current Fault

U2-02
(81)

Previous Fault

U2-03
(82)

Frequency Reference at
Previous Fault

Displays the frequency reference at the previous fault.

U2-04
(83)

Output Frequency at
Previous Fault

Displays the output frequency at the previous fault.

U2-05
(84)

Output Current at Previous All Modes


Fault
Displays the output current at the previous fault.

U2-06
(85)

Motor Speed at Previous


Fault

U2-07
(86)

Output Voltage at
Previous Fault

294

All Modes

Displays the current fault.


All Modes

Displays the previous fault.


All Modes

All Modes

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Displays the motor speed at the previous fault.


All Modes

Displays the output voltage at the previous fault.

Analog Output
Level

Unit

No signal output
available

No signal output
available

No signal output
available

0.01 Hz

No signal output
available

0.01 Hz

No signal output
available

<1> <2>

No signal output
available

0.01 Hz

No signal output
available

0.1 Vac

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.15 U: Monitors
No.
(Addr.
Hex)

Name

Description

U2-08
(87)

DC Bus Voltage at
Previous Fault

U2-09
(88)

Output Power at Previous All Modes


Fault
Displays the output power at the previous fault.

U2-10
(89)

Torque Reference at
Previous Fault

U2-11
(8A)

Input Terminal Status at


Previous Fault

U2-12
(8B)

Output Terminal Status at


Displays the output status at the previous fault. Displays the same status
Previous Fault
displayed in U1-11.

Analog Output
Level

Unit

No signal output
available

1 Vdc

No signal output
available

0.1 kW

No signal output
available

0.1%

No signal output
available

No signal output
available

U2-13
(8C)

Drive Operation Status at


No signal output
Displays the operation status of the drive at the previous fault. Displays the available
Previous Fault
same status displayed in U1-12.

U2-14
(8D)

Cumulative Operation
Time at Previous Fault

Displays the cumulative operation time at the previous fault.

U2-15
(7E0)

Soft Starter Speed


Reference at Previous
Fault

Displays the speed reference for the soft starter at the previous fault.

U2-16
(7E1)

Motor q-Axis Current at


Previous Fault

U2-17
(7E2)

Motor d-Axis Current at


Previous Fault

U2-19
(7EC)

Rotor Deviation at
Previous Fault

U2-20
(8E)

Heatsink Temperature at
Previous Fault

U2-27
(7FA)

Motor Temperature at
Previous Fault (NTC)

U2-28
(7FC)

Fault Slave Location


Monitor

All Modes

Displays the DC bus voltage at the previous fault.

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Displays the torque reference at the previous fault.


All Modes

Displays the input terminal status at the previous fault. Displayed as in


U1-10.
All Modes

All Modes

No signal output
available

1h

No signal output
available

0.01 Hz

No signal output
available

0.10%

No signal output
available

0.10%

No signal output
Displays the degree of rotor deviation when the most recent fault occurred available
(same status will appear as shown in U6-10).

0.1 deg

All Modes

All Modes

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Displays the q-axis current for the motor at the previous fault.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Displays the d-axis current for the motor at the previous fault.
V/f
OLV/PM

V/f w PG
AOLV/PM

OLV

CLV

CLV/PM

All Modes

Displays the temperature of the heatsink when the most recent fault
occurred.

No signal output
available

1 C

All Modes

1 C

<1> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
<2> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

Parameter List

Displays the temperature of the motor when the most recent fault occurred. No signal output
available
Note:
This parameter is only available in models CIMRAo4A0930, and 4A1200.
Displays the module where the Fault Slave occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
No signal output
Bit 2: Axis 3
available
Bit 3: Axis 4
Bit 4: Axis 5

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

295

A.15 U: Monitors

u U3: Fault History


No.
(Addr.
Hex)
U3-01 to
U3-04
(90 to 93
(800 to
803))

Name

Description

Analog Output
Level

Unit

All Modes

First to 4th Most Recent


Fault

Displays the first to the fourth most recent faults.

No signal output
available

U3-05 to
U3-10
(804 to
809)

5th to 10th Most Recent


Fault

Displays the fifth to the tenth most recent faults.


No signal output
After ten faults, data for the oldest fault is deleted. The most recent fault available
appears in U3-01, with the next most recent fault appearing in U3-02. The
data is moved to the next monitor parameter each time a fault occurs.

U3-11 to
U3-14
(94 to 97
(80A to
80D))

Cumulative Operation
Time at 1st to 4th Most
Recent Fault

Displays the cumulative operation time when the first to the fourth most
recent faults occurred.

U3-15 to
U3-20
(80E to
813)

Cumulative Operation
Time at 5th to 10th Most
Recent Fault

Displays the cumulative operation time when the fifth to the tenth most
recent faults occurred.

All Modes

All Modes

All Modes

No signal output
available

1h

No signal output
available

1h

u U4: Maintenance Monitors


No.
(Addr.
Hex)

Name

Description

Analog Output
Level

Unit

All Modes

Displays the cumulative operation time of the drive. The value for the
cumulative operation time counter can be reset in parameter o4-01. Use No signal output
parameter o4-02 to determine if the operation time should start as soon as available
the power is switched on or only while the Run command is present. The
maximum number displayed is 99999, after which the value is reset to 0.

U4-01
(4C)

Cumulative Operation
Time

U4-02
(75)

Number of Run
Commands

No signal output
Displays the number of times the Run command is entered. Reset the
number of Run commands using parameter o4-13. This value will reset to available
0 and start counting again after reaching 65535.

U4-03
(67)

Cooling Fan Operation


Time

Displays the cumulative operation time of the cooling fan. The default value No signal output
for the fan operation time is reset in parameter o4-03. This value will reset available
to 0 and start counting again after reaching 99999.

U4-04
(7E)

Cooling Fan Maintenance Displays main cooling fan usage time as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor.

U4-05
(7C)

Capacitor Maintenance

U4-06
(7D6)

Soft Charge Bypass Relay Displays the soft charge bypass relay maintenance time as a percentage of No signal output
Maintenance
its estimated performance life. Parameter o4-07 can be used to reset this available
monitor.

U4-07
(7D7)

IGBT Maintenance

U4-08
(68)

Heatsink Temperature

U4-09
(5E)

LED Check

1h

All Modes

1 Time

All Modes

All Modes

1h

No signal output
available

1%

No signal output
Displays main circuit capacitor usage time as a percentage of their expected available
performance life. Parameter o4-05 can be used to reset this monitor.

1%

All Modes

All Modes

296

All Modes

Displays IGBT usage time as a percentage of the expected performance


life. Parameter o4-09 can be used to reset this monitor.
All Modes

Displays the heatsink temperature.


All Modes

Lights all segments of the LED to verify that the display is working
properly.

1%

No signal output
available

1%

10 V: 100 C

1 C

No signal output
available

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.15 U: Monitors
No.
(Addr.
Hex)
U4-10
(5C)

kWh, Lower 4 Digits

U4-11
(5D)

kWh, Upper 5 Digits

U4-13
(7CF)

Peak Hold Current

U4-14
(7D0)

Peak Hold Output


Frequency

U4-16
(7D8)

Motor Overload Estimate


Shows the value of the motor overload detection accumulator. 100% is
(oL1)
equal to the oL1 detection level.

Name

Description

Analog Output
Level

No signal output
All Modes
available
Monitors the drive output power. The value is shown as a 9-digit number
displayed across two monitor parameters, U4-10 and U4-11.
Example:
No signal output
12345678.9 kWh is displayed as:
available
U4-10: 678.9 kWh
U4-11: 12345 MWh
All Modes

Displays the highest current value that occurred during run.


All Modes

Displays the output frequency when the current value shown in U4-13
occurred.

No signal output
available
No signal output
available

Unit
1 kWh

1 MWh

0.01 A

<1> <2>

0.01 Hz

All Modes

10 V: 100%

0.1%

All Modes

U4-18
(7DA)

Frequency Reference
Source Selection

U4-19
(7DB)
U4-20
(7DC)

Displays the source for the frequency reference as XY-nn.


X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Digital operator
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
5-01 = Pulse input
7-01 = DWEZ

No signal output
available

Frequency Reference from All Modes


MEMOBUS/Modbus
Displays the frequency reference provided by MEMOBUS/Modbus
Comm.
(decimal).

No signal output
available

0.01%

Option Frequency
Reference

No signal output
available

All Modes

Displays the frequency reference input by an option card (decimal).


All Modes

Run Command Source


Selection

U4-22
(7DE)

MEMOBUS/Modbus
Communications
Reference

Parameter List

U4-21
(7DD)

Displays the source for the Run command as XY-nn.


X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
7 = DWEZ
No signal output
nn: Run command limit status data
available
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to REMOTE
operation
03: Waiting for soft charge bypass contactor after power up (Uv or Uv1
flashes after 10 s)
04: Waiting for Run command prohibited time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during baseblock
09: Waiting for Enter command
All Modes

No signal output
Displays the drive control data set by MEMOBUS/Modbus
available
communications register no. 0001H as a four-digit hexadecimal number.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

297

A.15 U: Monitors
No.
(Addr.
Hex)
U4-23
(7DF)

Name
Communication Option
Card Reference

Description

Analog Output
Level

Unit

All Modes

No signal output
Displays drive control data set by an option card as a four-digit hexadecimal available
number.

All Modes

U4-32
(7FB)

No signal output
Motor Temperature (NTC) Displays the motor temperature (NTC).
U4-32 will display 20 C when a multi-function analog input is not set available
for motor thermistor input (H1-oo = 17H).

All Modes

U4-35
(1042)

UV Alarm Location
Monitor

Displays the module where the UV alarm occurred as a binary number.


Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5

No signal output
available

No signal output
available

No signal output
available

No signal output
available

No signal output
available

No signal output
available

0.10%

All Modes

U4-36
(1043)

OV Alarm Location
Monitor

Displays the module where the OV alarm occurred as a binary number.


Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
All Modes

U4-37
(1044)

oH Alarm Location
Monitor

Displays the module where the oH alarm occurred as a binary number.


Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
Note:

This parameter is only available in models CIMRAo4A0930, 4A1200, and A1000 HHP.

All Modes

U4-38
(1045)

FAn Alarm Location


Monitor

Displays the module where the FAn alarm occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
Note:

This parameter is only available in models CIMRAo4A0930, 4A1200, and A1000 HHP.

All Modes

U4-39
(1046)

voF Alarm Location


Monitor

Displays the module where the voF alarm occurred as a binary number.
Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5
Note:

This parameter is only available in models CIMRAo4A0930, 4A1200, and A1000 HHP.

All Modes

U4-41
(7FE)

UnbC Current Max


Location Monitor

Displays the maximum UnbC current detected.


Bit 0: Axis 1
Bit 1: Axis 2
Bit 2: Axis 3
Bit 3: Axis 4
Bit 4: Axis 5

<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.
<2> The unit is 1 A in models CIMR-Ao4A0930 and 4A1200.

298

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.15 U: Monitors

u U5: PID Monitors


No.
(Addr.
Hex)

Name

U5-01
(57)

PID Feedback

U5-02
(63)

PID Input

U5-03
(64)

PID Output

U5-04
(65)

PID Setpoint

Description
All Modes

Analog Output
Level

Unit

10 V: 100%

0.01%

10 V: 100%

0.01%

10 V: 100%

0.01%

10 V: 100%

0.01%

U5-05
(7D2)

PID Differential Feedback Displays the 2nd PID feedback value if differential feedback is used (H3- 10 V: 100%
oo = 16).

0.01%

U5-06
(7D3)

Displays the difference of both feedback values if differential feedback is 10 V: 100%


used (U5-01 - U5-05). If differential feedback is not used, then U5-01 and
U5-06 will be the same.

Displays the PID feedback value.


All Modes

Displays the amount of PID input (deviation between PID setpoint and
feedback).
All Modes

Displays PID control output.


All Modes

Displays the PID setpoint.


All Modes

All Modes

PID Adjusted Feedback

0.01%

u U6: Operation Status Monitors


Name

Description
All Modes

Analog Output
Level

Unit

U6-01
(51)

Motor Secondary Current


Displays the value of the motor secondary current (Iq). Motor rated
(Iq)
secondary current is 100%.

10 V: Motor secondary
rated current

0.1%

U6-02
(52)

Motor Excitation Current


10 V: Motor secondary
OLV/PM
AOLV/PM
CLV/PM
(Id)
Displays the value calculated for the motor excitation current (Id). Motor rated current
rated secondary current is 100%.

0.1%

U6-03
(54)
U6-04
(55)

ASR Input

U6-05
(59)

Output Voltage Reference


(Vq)

U6-06
(5A)

Output Voltage Reference


(Vd)

V/f

U6-07
(5F)

ASR Output

q-Axis ACR Output

V/f w PG

OLV

V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

CLV

Displays the input and output values when using ASR control.
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

10 V: Max frequency
10 V: Motor secondary
rated current

0.01%

CLV

10 V: 400 Vrms <1>

0.1 Vac

10 V: 400 Vrms <1>

0.1 Vac

10 V: 400 Vrms <1>

0.1%

110 V: 400 Vrms <1>

0.1%

Output voltage reference (Vq) for the q-Axis.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Output voltage reference (Vd) for the d-Axis.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Displays the output value for current control relative to motor secondary
current (q-Axis).
V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

U6-08
(60)

d-Axis ACR Output

U6-18
(7CD)

Speed Detection PG1


Counter

Monitors the number of pulses for speed detection (PG1).

U6-19
(7E5)

Speed Detection PG2


Counter

Monitors the number of pulses for speed detection (PG2).

Displays the output value for current control relative to motor secondary
current (d-Axis).
All Modes

All Modes

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

10 V: 65536

1 pulse

10 V: 65536

1 pulse

Parameter List

No.
(Addr.
Hex)

A
299

A.15 U: Monitors
No.
(Addr.
Hex)

Name

Description

U6-20
(7D4)

Frequency Reference Bias All Modes


(Up/Down 2)
Displays the bias value used to adjust the frequency reference.

U6-21
(7D5)

Offset Frequency

U6-22
(62)

Zero Servo Pulse


Movement

U6-25
(6B)

Feedback Control Output

U6-26
(6C)

Feed Forward Control


Output

U6-30
(7A)

Magnetic Flux Reference

All Modes

Displays the frequency added to the main frequency reference.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

V/f

V/f w PG

OLV

AOLV/PM

CLV/PM

CLV

Output monitor for the ASR speed loop.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

CLV

Output monitor for Feed Forward control.


V/f

V/f w PG

OLV

OLV/PM

AOLV/PM

CLV/PM

10 V: Max frequency

Unit
0.1%

0.1%

10 V: No. of pulses per


revolution

10 V: Motor secondary
rated current

0.01%

10 V: Motor secondary
rated current

0.01%

10 V: 100%

0.01%

CLV

Displays how far the rotor has moved from its last position in PG pulses
(multiplied by 4).
OLV/PM

Analog Output
Level

CLV

Displays the Magnetic Flux reference as a percent of total flux.

<1> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.

u U8: DriveWorksEZ Monitors


No.
(Addr.
Hex)
U8-01 to
U8-10
(1950 to
1959)
U8-11 to
U8-13
(195A to
195C)

300

Name

Description

Analog Output
Level

Unit

All Modes

DriveWorksEZ Custom
Monitor 1 to 10

DriveWorksEZ Custom Monitor 1 to 10

DriveWorksEZ Version
Control Monitor 1 to 3

DriveWorksEZ Version Control Monitor 1 to 3

All Modes

10 V: 100%

No signal output
available

0.01%

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.16 Control Mode Dependent Parameter Default Values

A.16 Control Mode Dependent Parameter Default Values


The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2). Changing
the control mode initializes these parameters to the values shown here.

u A1-02 (Motor 1 Control Mode) Dependent Parameters


Table A.2 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
Name

b2-01

DC Injection Braking Start Frequency

b2-04

DC Injection Braking Time at Stop

b3-01

Speed Search Selection at Start

b3-02

Speed Search Deactivation Current

b3-14

Bi-Directional Speed Search Selection

b5-15

PID Sleep Function Start Level

Setting Range

Resolution

0.0 to 10.0

Control Modes (A1-02)


V/f (0)

V/f w/PG (1)

OLV (2)

CLV (3)

0.1 Hz

0.5

0.5

0.5

0.5

0.00 to 10.00

0.01 s

0.50

0.50

0.50

0.50

0 to 1

0 to 200

1%

120

100

0 to 1

0.0 to

400.0 <1>

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

400.0 <1>

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

0.01 s

0.20

0.20

0.20

0.20

b6-01

Dwell Reference at Start

0.0 to

b6-03

Dwell Reference at Stop

0.0 to 400.0 <1>


400.0 <1>

C1-11

Accel/Decel Time Switching Frequency

C2-01

S-Curve Time at Acceleration Start

C3-01

Slip Compensation Gain

0.0 to 2.5

0.1

0.0

1.0

1.0

C3-02

Slip Compensation Primary Delay Time

0 to 10000

1 ms

2000

200

C4-01

Torque Compensation Gain

0.00 to 2.50

0.01

1.00

1.00

1.00

200 <3>

0.0 to

0.00 to 10.00

C4-02

Torque Compensation Primary Delay Time

0 to 10000

1 ms

200 <3>

20

C5-01

ASR Proportional Gain 1

0.00 to 300.00

0.01

0.20

20.00

C5-02

ASR Integral Time 1

0.000 to 10.000

0.001 s

0.200

0.500

C5-03

ASR Proportional Gain 2

0.00 to 300.00

0.01

0.02

20.00

C5-04

ASR Integral Time 2

0.000 to 10.000

0.001 s

0.050

0.500

C5-06

ASR Primary Delay Time Constant

0.000 to 0.500

0.001 s

0.004

C5-07

ASR Gain Switching Frequency

0.0 to

400.0 <1>

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

d3-01

Jump Frequency 1

0.0 to 150.0 <1>

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

d3-02

Jump Frequency 2

0.0 to

150.0 <1>

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

d3-03

Jump Frequency 3

0.0 to

150.0 <1>

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

d3-04

Jump Frequency Width

d5-02

Torque Reference Delay Time

E1-04

Maximum Output Frequency

E1-05

Maximum Voltage

E1-06
E1-07
E1-08

Middle Output Frequency Voltage

E1-09

Minimum Output Frequency

E1-10

Minimum Output Frequency Voltage

F1-01

PG 1 Pulses Per Revolution

F1-05

PG 1 Rotation Selection

F1-09

Overspeed Detection Delay Time

L1-01

Motor Overload Protection Selection

0.1

1.0 Hz

1.0 Hz

1.0 Hz

1.0 Hz

0 to 1000

1 ms

0.0 to

40.0 to 150.0

0.1 Hz

60.0

60.0

60.0

60.0

0.0 to 510.0 <6>

0.1 V

575 <7>

575 <7>

575

575

Base Frequency

0.0 to 150.0

0.1 Hz

60.0

60.0

60.0

60.0

Middle Output Frequency

0.0 to 150.0

0.1 Hz

3.0

3.0

3.0

3.0

0.0 to 510.0 <6>

0.1 V

15.0 <7>

15.0 <7>

15.0

15.0

L4-01

Speed Agreement Detection Level

L4-02

Speed Agreement Detection Width

L4-03

Speed Agreement Detection Level (+/-)

L4-04

Speed Agreement Detection Width (+/-)

L8-38

20.0 <5>

Carrier Frequency Reduction Selection

0.0 to 150.0

0.1 Hz

1.5

1.5

0.5

0.0

0.0 to 510.0 <6>

0.1 V

9.0

9.0

2.0

0.0

0 to 60000

1 ppr

600

600

600

600

0 to 1

0.0 to 2.0

0.1 s

1.0

0.0

0 to 4

0.0 to

150.0 <1>

0.0 to 20.0
-150.0 to

150.0 <8>

0.0 to 20.0
0 to 2

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.0 Hz

0.1 Hz

2.0

2.0

2.0

2.0
0.0 Hz

0.1

0.0 Hz

0.0 Hz

0.0 Hz

0.1 Hz

2.0

2.0

2.0

2.0

<4>

<4>

<4>

<4>

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Parameter List

No.

A
301

A.16 Control Mode Dependent Parameter Default Values


No.

Name

Setting Range

Resolution

0.00 to 2.00

0.01 s

Control Modes (A1-02)


V/f (0)

V/f w/PG (1)

OLV (2)

CLV (3)

0.50

0.50

0.50

0.50

L8-40

Carrier Frequency Reduction Off Delay


Time

o1-03

Digital Operator Display Selection

0 to 3

o1-04

V/f Pattern Display Unit

0 to 1

<1> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 100.0%) instead of in Hz.
<2> This setting value depends on a Maximum Applicable Motor Capacity in models CIMR-Ao2A0250 to 2A0415, CIMR-Ao4A0139 to 4A1200,
A1000 HHP, and CIMR-Ao5A0099 to 5A0242: 2.00 in Open Loop Vector Control, 0.05 in Closed Loop Vector Control.
<3> This setting value depends on a Maximum Applicable Motor Capacity: 1000 s in models CIMR-Ao2A0138 to 2A0415, CIMR-Ao4A0139 to
4A1200, A1000 HHP, and CIMR-Ao5A0099 to 5A0242
<4> Default setting is dependent on parameter C6-01, Drive Duty Selection.
<5> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (0.0 to 40.0%) instead of in Hz.
<6> Values shown are specific to 400 V class drives. Multiply the value by 1.4375 for 575 V class drives. Multiply the value by 1.725 for 690 V class
drives.
<7> This setting value depends on a Maximum Applicable Motor Capacity and V/f pattern selection in parameter E1-03.
<8> In AOLV/PM and CLV/PM control modes, the setting units and range are expressed as a percentage (-100.0 to 100.0%) instead of in Hz.

u E3-01 (Motor 2 Control Mode) Dependent Parameters


Table A.3 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
No.

Name

Setting Range

Resolution

Control Modes (E3-01)


V/f (0)

V/f w/PG (1)

OLV (2)

CLV (3)

C3-21

Motor 2 Slip Compensation Gain

0.0 to 2.5

0.1

0.0

1.0

1.0

C3-22

Motor 2 Slip Compensation Primary Delay


Time

0 to 10000

1 ms

2000

200

C5-21

Motor 2 ASR Proportional Gain 1

0.00 to 300.00

0.01

0.20

20.00

C5-22

Motor 2 ASR Integral Time 1

0.000 to 10.000

0.001 s

0.200

0.500

C5-23

Motor 2 Proportional Gain 2

0.00 to 300.00

0.01

0.02

20.00

C5-24

Motor 2 ASR Integral Time 2

0.000 to 10.000

0.001 s

0.050

0.500

7 <1>

7 <1>

7 <1>

C5-26

Motor 2 Carrier Frequency Selection

1 to F

7 <1>

E3-04

Motor 2 Maximum Output Frequency

40.0 to 150.0

0.1 Hz

60.0

60.0

60.0

60.0

Voltage <2>

E3-05

Motor 2 Maximum Output

0.0 to 510.0

0.2 V

400.0

400.0

400.0

400.0

E3-06

Motor 2 Base Frequency

0.0 to 150.0

0.1 Hz

60.0

60.0

60.0

60.0

E3-07

Motor 2 Mid Output Frequency

0.0 to 150.0

0.1 Hz

3.0

3.0

3.0

0.0

0.0 to 510.0

0.2 V

30.0

30.0

22.0

0.0

0.0 to 150.0

0.1 Hz

1.5

1.5

0.5

0.0

0.0 to 510.0

0.2 V

18.0

18.0

4.0

0.0

Voltage <2>

E3-08

Motor 2 Mid Output Frequency

E3-09

Motor 2 Minimum Output Frequency

E3-10

Motor 2 Minimum Output

Voltage <2>

<1> Default setting is determined by parameters o2-04, Drive Model Selection, and C6-01, Drive Duty Selection.
<2> Values shown here are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690
V class drives.

302

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.17 V/f Pattern Default Values

A.17 V/f Pattern Default Values


The following table shows the V/f pattern setting default values depending on the control mode (A1-02) and the V/f pattern
selection (E1-03 in V/f Control) for all HHP models:
400 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
575 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty,
690 V Class 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty.
Table A.4 E1-03 V/f Pattern Settings for Drive Capacity:
No.

Unit

V/f Control

E1-03

F
<1>

OLV

CLV

E1-04

Hz

50.0

60.0

60.0

72.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

90.0

120.0

150.0

60.0

60.0

60.0

E1-05
<3>

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

400.0

460.0

460.0

460.0

E1-06

Hz

50.0

60.0

50.0

60.0

50.0

50.0

60.0

60.0

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

60.0

60.0

E1-07

Hz

2.5

3.0

3.0

3.0

25.0

25.0

30.0

30.0

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

3.0

0.0

E1-08
<3>

24.0

24.0

24.0

24.0

70.0

100.0

70.0

100.0

30.0

40.0

30.0

40.0

24.0

24.0

24.0

27.6

25.4

0.0

E1-09

Hz

1.3

1.5

1.5

1.5

1.3

1.3

1.5

1.5

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

0.5

0.0

E1-10
<3>

12.0

12.0

12.0

12.0

10.0

12.0

10.0

12.0

14.0

18.0

14.0

22.0

12.0

12.0

12.0

13.8

4.6

0.0

Parameter List

<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<3> Values shown here are specific to 400 V class drives. Multiply the values by 1.4375 for 575 V class drives. Multiply the values by 1.725 for 690
V class drives.

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

303

A.18 Defaults by Drive Model and Duty Rating ND/HD

A.18 Defaults by Drive Model and Duty Rating ND/HD


The following tables show parameters and default settings that change with the drive model selection (o2-04) and drive duty
selection (C6-01).
Table A.5 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
Constant
No.

Name

Model Type

C6-01

ND/HD Select

o2-04
E2-11
(E4-11)

Unit

Default Settings
4200

4400

4600

4800

410C

HD

ND

HD

ND

HD

ND

HD

ND

HD

ND

Drive Model Selection

177
(B1H)

177
(B1H)

178
(B2H)

178
(B2H)

179
(B3H)

179
(B3H)

180
(B4H)

180
(B4H)

181
(B5H)

181
(B5H)

Inverter Rated Current

414.0

466.0

800.0

900.0

1200.0

1350.0

1600.0

1800.0

2000.0

2250.0

KW

200.00

250.00

400.0

500.0

600.0

750.0

800.0

1000.0

1000.0

1250.0

Motor Rated Power

b3-04

V/f Gain during Speed Search

60

60

60

60

60

60

60

60

60

60

b3-06

Output Current 1 during


Speed Search

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

E2-01
(E4-01)

Motor Rated Current

400.0

400.0

800.0

800.0

1200.0

1200.0

1800.0

1800.0

2000.0

2500.0

E2-02
(E4-02)

Motor Rated Slip

Hz

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

E2-03
(E4-03)

Motor No-Load Current

80.0

80.0

160.0

160.0

240.0

240.0

360.0

360.0

400.0

500.0

E2-05
(E4-05)

Motor Line-to-Line
Resistance

12.000

12.000

8.500

8.500

7.000

7.000

6.000

6.000

5.500

5.000

E2-06
(E4-06)

Motor Leakage Inductance

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

E2-10
(E4-10)

Motor Iron Loss for Torque


Compensation

L2-02

Momentary Power Loss RideThrough Time

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-03

Momentary Power Loss


Minimum Baseblk Time

2.0

2.0

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

L2-04

Momentary Power Loss


Voltage Recovery Time

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

L8-02

Overheat Alarm Level

125

125

125

125

125

125

125

125

125

125

L8-38

Carrier Frequency Reduction


Selection

Table A.6 575 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
Constant
No.

Name

Model Type

C6-01

ND/HD Select

o2-04
E2-11
(E4-11)

Unit

Default Settings
5300

5600

5900

5C00

5F00

HD

ND

HD

ND

HD

ND

HD

ND

HD

ND

Drive Model Selection

225
(E1H)

225
(E1H)

226
(E2H)

226
(E2H)

227
(E3H)

227
(E3H)

228
(E4H)

228
(E4H)

229
(E5H)

229
(E5H)

Inverter Rated Current

414.0

466.0

800.0

900.0

1200.0

1350.0

1600.0

1800.0

2000.0

2250.0

KW

300.0

335.00

600.0

670.0

900.0

1005.0

1200.0

1340.0

1500.0

1675.0

Motor Rated Power

b3-04

V/f Gain during Speed Search

80

80

80

80

80

80

80

80

80

80

b3-06

Output Current 1 during


Speed Search

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

E2-01
(E4-01)

Motor Rated Current

350.0

350.0

700.0

700.0

1050.0

1050.0

1400.0

1400.0

1750.0

1750.0

E2-02
(E4-02)

Motor Rated Slip

Hz

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

E2-03
(E4-03)

Motor No-Load Current

70.0

70.0

140.0

140.0

210.0

210.0

280.0

280.0

350.0

350.0

E2-05
(E4-05)

Motor Line-to-Line
Resistance

14.000

14.000

10.000

10.000

8.000

8.000

7.000

7.000

6.000

6.000

304

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

A.18 Defaults by Drive Model and Duty Rating ND/HD


Constant
No.

Name

Model Type

C6-01

ND/HD Select

o2-04

Unit

Default Settings
5300

5600

5900

5C00

5F00

HD

ND

HD

ND

HD

ND

HD

ND

HD

ND

Drive Model Selection

225
(E1H)

225
(E1H)

226
(E2H)

226
(E2H)

227
(E3H)

227
(E3H)

228
(E4H)

228
(E4H)

229
(E5H)

229
(E5H)

Inverter Rated Current

414.0

466.0

800.0

900.0

1200.0

1350.0

1600.0

1800.0

2000.0

2250.0

E2-06
(E4-06)

Motor Leakage Inductance

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

E2-10
(E4-10)

Motor Iron Loss for Torque


Compensation

L2-02

Momentary Power Loss RideThrough Time

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-03

Momentary Power Loss


Minimum Baseblk Time

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-04

Momentary Power Loss


Voltage Recovery Time

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

L8-02

Overheat Alarm Level

130

130

130

130

130

130

130

130

130

130

L8-38

Carrier Frequency Reduction


Selection

Table A.7 YAI 690 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
Constant
No.

Name

Model Type

C6-01

ND/HD Select

o2-04
E2-11
(E4-11)

Default Settings
Note: 690 V class default values when o2-09 = 1

Unit
6300

6600

6900

6C00

6F00

HD

ND

HD

ND

HD

ND

HD

ND

HD

ND

Drive Model Selection

241
(F1H)

241
(F1H)

242
(F2H)

242
(F2H)

243
(F3H)

243
(F3H)

244
(F4H)

244
(F4H)

245
(F5H)

245
(F5H)

Inverter Rated Current

414.0

466.0

800.0

900.0

1200.0

1350.0

1600.0

1800.0

2000.0

2250.0

KW

300.0

335.00

600.0

670.0

900.0

1005.0

1200.0

1340.0

1500.0

1675.0

Motor Rated Power


V/f Gain during Speed Search

80

80

80

80

80

80

80

80

80

80

b3-06

Output Current 1 during


Speed Search

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

E2-01
(E4-01)

Motor Rated Current

350.0

350.0

700.0

700.0

1050.0

1050.0

1400.0

1400.0

1750.0

1750.0

E2-02
(E4-02)

Motor Rated Slip

Hz

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

E2-03
(E4-03)

Motor No-Load Current

70.0

70.0

140.0

140.0

210.0

210.0

280.0

280.0

350.0

350.0

E2-05
(E4-05)

Motor Line-to-Line
Resistance

14.000

14.000

10.000

10.000

8.000

8.000

7.000

7.000

6.000

6.000

E2-06
(E4-06)

Motor Leakage Inductance

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

E2-10
(E4-10)

Motor Iron Loss for Torque


Compensation

L2-02

Momentary Power Loss RideThru Time

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-03

Momentary Power Loss


Minimum Baseblk Time

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-04

Momentary Power Loss


Voltage Recovery Time

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

L8-02

Overheat Alarm Level

130

130

130

130

130

130

130

130

130

130

L8-38

Carrier Frequency Reduction


Selection

2
Parameter List

b3-04

A
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

305

A.18 Defaults by Drive Model and Duty Rating ND/HD


Table A.8 YEC 690 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
Constant
No.

Name

Model Type

C6-01

ND/HD Select

o2-04
E2-11
(E4-11)

Default Settings
Note: 690 V class default values when o2-o9 = 0

Unit
6300

6600

6900

6C00

6F00

HD

ND

HD

ND

HD

ND

HD

ND

HD

ND

Drive Model Selection

241
(F1H)

241
(F1H)

242
(F2H)

242
(F2H)

243
(F3H)

243
(F3H)

244
(F4H)

244
(F4H)

245
(F5H)

245
(F5H)

Inverter Rated Current

360.0

414.0

700.0

800.0

1050.0

1200.0

1400.0

1600.0

1750.0

2000.0

KW

300.0

335.0

600.0

670.0

900.0

1005.0

1200.0

1340.0

1500.0

1675.0

Motor Rated Power

b3-04

V/f Gain during Speed Search

80

80

80

80

80

80

80

80

80

80

b3-06

Output Current 1 during


Speed Search

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

E2-01
(E4-01)

Motor Rated Current

350.0

350.0

700.0

700.0

1050.0

1050.0

1400.0

1400.0

1750.0

1750.0

E2-02
(E4-02)

Motor Rated Slip

Hz

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

E2-03
(E4-03)

Motor No-Load Current

70.0

70.0

140.0

140.0

210.0

210.0

280.0

280.0

350.0

350.0

E2-05
(E4-05)

Motor Line-to-Line
Resistance

14.000

14.000

10.000

10.000

8.000

8.000

7.000

7.000

6.000

6.000

E2-06
(E4-06)

Motor Leakage Inductance

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

20.0

E2-10
(E4-10)

Motor Iron Loss for Torque


Compensation

L2-02

Momentary Power Loss RideThrough Time

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-03

Momentary Power Loss


Minimum Baseblk Time

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

L2-04

Momentary Power Loss


Voltage Recovery Time

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

L8-02

Overheat Alarm Level

130

130

130

130

130

130

130

130

130

130

L8-38

Carrier Frequency Reduction


Selection

306

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Appendix: B
MEMOBUS/Modbus Communications
B.1
B.2
B.3
B.4
B.5
B.6
B.7
B.8
B.9
B.10
B.11
B.12

MEMOBUS/MODBUS CONFIGURATION...........................................................308
COMMUNICATION SPECIFICATIONS................................................................309
CONNECTING TO A NETWORK.........................................................................310
MEMOBUS/MODBUS SETUP PARAMETERS...................................................313
DRIVE OPERATIONS BY MEMOBUS/MODBUS................................................316
COMMUNICATIONS TIMING...............................................................................317
MESSAGE FORMAT............................................................................................318
MESSAGE EXAMPLES.......................................................................................320
MEMOBUS/MODBUS DATA TABLE..................................................................322
ENTER COMMAND..............................................................................................338
COMMUNICATION ERRORS..............................................................................339
SELF-DIAGNOSTICS...........................................................................................340

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

307

B.1 MEMOBUS/Modbus Configuration

B.1 MEMOBUS/Modbus Configuration


Drives can be controlled from a PLC or other master device via serial communications using the MEMOBUS/Modbus protocol.
MEMOBUS/Modbus communications can be configured using one master (PLC) and up to 31 slaves. The drive has slave
functionality only, and serial communication is normally initiated from the master and responded to by the slaves.
The master performs serial communications with only one slave at a time. The address or node for each slave must be set
beforehand so that the master can communicate with the slave at that address. A slave that receives a command from the master
will perform the specified function and then send a response back to the master.

MasterPLC or other

Slave (Drive)

Figure B.1 Connecting Multiple Drives to a PLC

308

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.2 Communication Specifications

B.2 Communication Specifications


MEMOBUS/Modbus specifications appear in the following table:
Item
Interface
Communications Cycle

Communication
Parameters

RS-422, RS-485
Asynchronous (Start-stop synchronization)
Communication Speeds
1.2; 2.4; 4.8; 9.6; 19.2; 38.4; 57.6; 76.8; 115.2 kbps
Available
Data length
8-bit (fixed)
Parity
Select even, odd, or none
Stop bit
1-bit (fixed)
MEMOBUS/Modbus (using RTU mode only)
31 drives

MEMOBUS/Modbus
Communications

Protocol
Max Number of Slaves

Specifications

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

309

B.3 Connecting to a Network

B.3 Connecting to a Network


This section explains how to connect the drive to a MEMOBUS/Modbus network and the network termination required for a
connection.

u Network Cable Connection


Follow the instructions below to connect the drive to a MEMOBUS/Modbus network.

1.

With the power shut off, connect the communications cable to the drive and the master. Use terminals TB5 for
MEMOBUS/Modbus.

S Send ()
S+ Send (+)
R Receive ()
R+ Receive (+)
IG Shield Ground
(TB4)

Figure B.2 Serial Communications Cable Connection Terminals (TB4)


Note:

2.
3.
4.
5.
6.
7.

Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for
the communications cables, and properly shielded clamps to prevent problems with noise. When using RS-485
communications, connect S+ to R+, and S- to R- as shown in the RS-485 diagram.

Check or set the termination resistor selection at all slaves. Use the description in Network Termination on page
311 for slaves that are A1000 HHP drives.
Switch the power on.
Set the parameters needed for serial communications (H5-01 through H5-12) using the digital operator.
Shut the power off and wait until the display on the digital operator goes out completely.
Turn the power back on.
The drive is now ready to begin communicating with the master.

u Wiring Diagram for Multiple Connections


Figure B.3 and Figure B.4 explain the wiring diagrams for multiple connections using MEMOBUS/Modbus communication.

310

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.3 Connecting to a Network

n RS-485 Interface
R
R+
S
S+
IG

PLC

S
S+
R
R+
IG

S2

S
S+
R
R+
IG

S2

S
S+
R
R+
IG

S2

Drive

OFF

Drive

OFF

Drive

ON

Figure B.3 RS-485 Interface


Note:

1. Turn on the DIP switch on the drive that is located at the end of the network. All other slave devices must have this DIP switch set to
the OFF position.
2. Set H5-07 to 1 when using the RS-485 interface.

n RS-422 Interface
PLC

R
R+
S
S+
IG

S
S+
R
R+
IG

S2

S
S+
R
R+
IG

S2

S
S+
R
R+
IG

S2

Drive

OFF

Drive

OFF

Drive

ON

Figure B.4 RS-422 Interface

u Network Termination

MEMOBUS/Modbus
Communications

The two ends of the MEMOBUS/Modbus network line have to be terminated. The drive has a built in termination resistor that
can be enabled or disabled using DIP switch S2. If a drive is located at the end of a network line, enable the termination resistor
by setting DIP switch S2 to the ON position. Disable the termination resistor on all slaves that are not located at the network
line end.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

311

B.3 Connecting to a Network

Dip Switch S2
OFF

ON

O
N

OFF: Factory Setting


Control Module

S-

S+

RS-422

or

RS-485

R-

R+

Dip
Switch
S2

Termination resistor (1/2W, 110 W)

Figure B.5 MEMOBUS/Modbus communication terminal and S2 DIP switch

312

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.4 MEMOBUS/Modbus Setup Parameters

B.4 MEMOBUS/Modbus Setup Parameters


u MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.

n H5-01: Drive Slave Address


Sets the drive slave address used for communications.
Note:

Cycle the power after changing this parameter to enable the new setting.

No.
H5-01

Name
Drive Slave Address

Setting Range

Default
1FH

Setting Range
0 to 8

Default
3

n H5-02: Communication Speed Selection


Sets the MEMOBUS/Modbus communications speed.
Note:

Cycle the power after changing this parameter to enable the new setting.

No.
H5-02

Name
Communication Speed Selection

H5-02
0
1
2
3
4

Communication Speed
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps

H5-02
5
6
7
8

Communication Speed
38400 bps
57600 bps
76800 bps
115200 bps

n H5-03: Communication Parity Selection


Sets the parity used for communications.
Note:

Cycle the power after changing this parameter to enable the new setting.

No.
H5-03

Name
Communication Parity Selection

Setting Range
0 to 2

Default
0

Setting Range
0 to 3

Default
3

Setting Range
0 or 1

Default
1

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

n H5-04: Stopping Method after Communication Error


Selects the stopping method after a communications error (CE) has occurred.
No.
H5-04

Name
Stopping Method after CE

Setting 0: Ramp to stop (uses the deceleration time currently enabled)


Setting 1: Fast Stop (uses the deceleration time in C1-09)
Setting 2: Coast to stop
Setting 3: Alarm only (continue operation)
MEMOBUS/Modbus
Communications

n H5-05: Communication Fault Detection Selection


Enables or disables the CE detection for communications.
No.
H5-05

Name
Communication Fault Detection Selection

Setting 0: Disabled

No communication error detection. The drive continues operation.


YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

313

B.4 MEMOBUS/Modbus Setup Parameters


Setting 1: Enabled

If the drive does not receive data from the master for longer than the time set to H5-09, then a CE fault will be triggered and
the drive will operate as determined by parameter H5-04.

n H5-06: Drive Transmit Wait Time


Sets the time the drive waits after receiving data from a master until responding data.
No.
H5-06

Name
Drive Transmit Wait Time

PLCDrive

Setting Range
5 to 65 ms

PLCDrive

DrivePLC

Command Message

Response Message

24 Bit length H5-06 setting

Default
5 ms

Command Message

Time (sec)

24 Bit length 5 ms

Figure B.6 Drive Transmit Wait Time Setting

n H5-07: RTS Control Selection


Enables or disables RTS control.
No.
H5-07

Name
RTS Control Selection

Setting Range
0, 1

Default
1

Setting 0: Disabled. RTS is always on.

Use this setting with point-to-point or multi-drop RS-422 communications.


Setting 1: Enabled. RTS switches while sending.

Use this setting when using RS-485 signals for communications or when using the RS-422 signals for point-to-point
communications.

n H5-09: CE Detection Time


Sets the time the communications must be lost before the drive triggers a CE fault.
No.
H5-09

Name
CE Detection Time

Setting Range
0.0 to 10.0 s

Default
2.0 s

n H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H


Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
No.
H5-10

Name
Unit Selection for MEMOBUS/Modbus Register 0025H

Setting Range
0, 1

Default
0

Setting 0: 0.1 V units


Setting 1: 1 V units

n H5-11: Communications Enter Function Selection


Selects whether an Enter command is necessary to change parameter values via MEMOBUS/Modbus communications. Refer
to Enter Command on page 338.

314

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.4 MEMOBUS/Modbus Setup Parameters


No.
H5-11

Name
Communications Enter Function Selection

Setting Range
0 or 1

Default
0

Setting 0: Enter command necessary

Parameter changes become effective after an Enter command. An Enter command must only be sent after the last parameter
change, not for each single parameter.
Setting 1: Enter command not necessary

Parameter value changes become effective immediately without the need to send an Enter command.

n H5-12: Run Command Method Selection


Selects the type of sequence used when the Run command source is set to MEMOBUS/Modbus communications
(b1-02, b1-16 = 2).
No.
H5-12

Name
Run Command Method Selection

Setting Range
0 or 1

Default
0

Setting 0: FWD/Stop, REV/Stop

Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive in the forward direction. Setting bit 1 will start and
stop the drive in reverse.
Setting 1: Run/Stop, FWD/REV

MEMOBUS/Modbus
Communications

Setting bit 0 of MEMOBUS/Modbus register will start and stop the drive. Setting bit 1 changes the direction.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

315

B.5 Drive Operations by MEMOBUS/Modbus

B.5 Drive Operations by MEMOBUS/Modbus


The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings. This
section explains the functions that can be used and related parameter settings.

u Observing the Drive Operation


A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter
settings (except for H5-ooparameters):
observe drive status and drive control terminal status from a PLC.
read and write parameters.
set and reset faults.
set multi-function inputs.
Note:

Input settings from the input terminals So and from MEMOBUS/Modbus communications are both linked by a logical OR operation.

u Controlling the Drive


Select an external reference and adjust the parameters in Table B.1 accordingly to start and stop the drive or set the frequency
reference using MEMOBUS/Modbus communications.
Table B.1 Setting Parameters for Drive Control from MEMOBUS/Modbus
Reference Source
External Reference 1
External Reference 2

Parameter
b1-01
b1-02
b1-15
b1-16

Name
Frequency Reference Selection 1
Run Command Selection 1
Frequency Reference Selection 2
Run Command Selection 2

Required Setting
2
2
2
2

Refer to b1-01: Frequency Reference Selection 1 on page 18 and Refer to b1-02: Run Command Selection 1 on page 19
for details on external reference parameter selections. Refer to Setting 2: External Reference 1/2 Selection on page 95 for
instructions on selecting external references 1 and 2.

316

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.6 Communications Timing

B.6 Communications Timing


To prevent overrun in the slave drive, the master should wait a certain time between sending messages to the same drive. In
the same way, the slave drive must wait before sending response messages to prevent an overrun in the master. This section
explains the message timing.

u Command Messages from Master to Drive


The master must wait for a specified time between receiving a response and resending the same type of command to the same
slave drive to prevent overrun and data loss. The minimum wait time depends on the command as shown in the table below.
Table B.2 Minimum Wait Time for Sending Messages

Command Type

Example
Control command (Run, Stop)
Set inputs/outputs
Read monitors and parameter values
Write parameters

Save changes using an Enter command

Minimum Wait Time


5 ms
50 ms

3 to 5 s <1>

<1> If the drive receives command type 1 data during the minimum wait time, it will perform the command and then respond. However, if it receives
a command type 2 or 3 during that time, either a communication error will result or the command will be ignored.
PLCDrive

DrivePLC

PLCDrive

Command message

Response message

Command message

24 bit length

Time

Master Send
Wait Time

Figure B.7 Minimum Wait Time for Sending Messages

u Response Messages from Drive to Master


If the drive receives a command from the master, it will process the data received and wait for the time set in H5-06 until it
responds. Increase H5-06 if the drive response causes overrun in the master.
PLCDrive

DrivePLC

PLCDrive

Command message

Response message

Command message

24 bit length

Time

H5-06
setting

MEMOBUS/Modbus
Communications

Figure B.8 Minimum Response Wait Time

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

317

B.7 Message Format

B.7 Message Format


u Message Content
In MEMOBUS/Modbus communications, the master sends commands to the slave, and the slave responds. The message
format is configured for both sending and receiving as shown below, and the length of data packets depends on the command
(function) content.

SLAVE ADDRESS
FUNCTION CODE
DATA
ERROR CHECK

u Slave Address
The slave address in the message defines the note the message is sent to. Use addresses between 0 and FF (hex). If a message
with slave address 0 is sent (broadcast), the command from the master will be received by all slaves. The slaves do not provide
a response to a broadcast type message.

u Function Code
The three types of function codes are shown in the table below.
Function
Code
03H
08H
10H

Function Name
Read MEMOBUS/Modbus registers
Loopback test
Write to multiple MEMOBUS/Modbus registers

Data Length (bytes)


Command Message
Response Message
Minimum
Maximum
Minimum
Maximum
8
8
7
37
8
8
8
8
11
41
8
8

u Data
Configure consecutive data by combining the MEMOBUS/Modbus register address (test code in case of a loopback test) and
the data the register contains. The data length changes depending on the command details.
A drive MEMOBUS/Modbus register always has a data length of two bytes. Data written into drive registers must also always
have a length of two bytes. Register data read out from the drive will always consist of two bytes.

u Error Check
The drive uses a CRC-16 (cyclic redundancy check, checksum method) for checking data validity. Use the procedure described
below when calculating the CRC-16 checksum for command data or when verifying response data.

n Command Data
When the drive receives data, it calculates the CRC-16 checksum from the data and compares it to the CRC-16 value received
within the message. Both must match before a command is processed.
An initial value of FFFFH (i.e., all 16 bits equal 1) must be used for CRC-16 calculations in the MEMOBUS/Modbus protocol.
Calculate the CRC-16 checksum using the following steps:

1.
2.
3.
4.
5.
6.
7.

318

The starting value is FFFFH.


Perform an XOR operation of this value and the slave address.
Right shift the result.
When the overflow bit of the shift operation becomes 1, perform an XOR operation of the result from step 3 above
and the fix value A001H.
Repeat steps 3 and 4 until eight shift operations have been performed.
After eight shift operations, perform an XOR operation with the result and the next data in the message (function code,
register address, data). Continue with steps 3 to 5 until the last data has been processed.
The result of the last shift or XOR operation is the checksum.
YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.7 Message Format


The example in Table B.3 shows the CRC-16 calculation of the slave address 02H and the function code 03H, yielding the
result 40D1H.
Note:

This example does not show the calculation for a complete MEMOBUS/Modbus command. Normally data would follow in the calculation.
Table B.3 CRC-16 Checksum Calculation Example

Description
Initial Value (FFFFH)
Address 02H
XOR w initial value
Shift 1
XOR w A001H
XOR result
Shift 2
XOR w A001H
XOR result
Shift 3
Shift 4
XOR w A001H
XOR result
Shift 5
Shift 6
XOR w A001H
XOR result
Shift 7
Shift 8
XOR w A001H
XOR result

Calculation
1111 1111 1111 1111
0000 0000 0000 0010
1111 1111 1111 1101
0111 1111 1111 1110
1010 0000 0000 0001
1101 1111 1111 1111
0110 1111 1111 1111
1010 0000 0000 0001
1100 1111 1111 1110
0110 0111 1111 1111
0011 0011 1111 1111
1010 0000 0000 0001
1001 0011 1111 1110
0100 1001 1111 1111
0010 0100 1111 1111
1010 0000 0000 0001
1000 0100 1111 1110
0100 0010 0111 1111
0010 0001 0011 1111
1010 0000 0000 0001
1000 0001 0011 1110

Overflow

Perform operations with next data (function code)

0
1

0
1

0
1

Description
Function Code 03H
XOR w result
Shift 1
XOR w A001H
XOR result
Shift 2
XOR w A001H
XOR result
Shift 3
Shift 4
XOR w A001H
XOR result
Shift 5
Shift 6
XOR w A001H
XOR result
Shift 7
XOR w A001H
XOR result
Shift 8
XOR w A001H
XOR result

Calculation
0000 0000 0000 0011
1000 0001 0011 1101
0100 0000 1001 1110
1010 0000 0000 0001
1110 0000 1001 1111
0111 0000 0100 1111
1010 0000 0000 0001
1101 0000 0100 1110
0110 1000 0010 0111
0011 0100 0001 0011
1010 0000 0000 0001
1001 0100 0001 0010
0100 1010 0000 1001
0010 0101 0000 0100
1010 0000 0000 0001
1000 0101 0000 0101
0100 0010 1000 0010
1010 0000 0000 0001
1110 0010 1000 0011
0111 0001 0100 0001
1010 0000 0000 0001
1101 0001 0100 0000
1101 0001 0100 0000
CRC-16
D140H
Continue from here with next data.

Overflow

0
1

0
1

n Response Data

MEMOBUS/Modbus
Communications

Perform a CRC-16 calculation on the response message data as described above as a validation check. The result should match
the CRC-16 checksum received within the response message.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

319

B.8 Message Examples

B.8 Message Examples


Below are some examples of command and response messages.

u Reading Drive MEMOBUS/Modbus Register Contents


Using the function code 03H (Read), a maximum of 16 MEMOBUS/Modbus registers can be read out at a time.
The following table shows message examples when reading status signals, error details, data link status, and frequency
references from the slave 2 drive.
Command Message
Slave Address
02H
Function Code
03H
Upper
00H
Starting No.
Lower
20H
Upper
00H
Data Quantity
Lower
04H
Upper
45H
CRC-16
Lower
F0H

Response Message (normal)


Slave Address
02H
Function Code
03H
Data Quantity
08H
Upper
00H
1st storage
register
Lower
65H
Next storage
register
Next storage
register
Next storage
register
CRC-16

Upper
Lower
Upper
Lower
Upper
Lower
Upper
Lower

Response Message (fault)


Slave Address
02H
Function Code
83H
Error Code
03H
Upper
F1H
CRC-16
Lower
31H

00H
00H
00H
00H
01H
F4H
AFH
82H

u Loopback Test
Function code 08H performs a loopback test that returns a response message with exactly the same content as the command
message. The response message can be used to check communications between the master and slave. User-defined test code
and data values can also be set.
The following table shows a message example when performing a loopback test with the slave 1 drive.
Command Message
Slave Address
01H
Function Code
08H
Upper
00H
Test Code
Lower
00H
Upper
A5H
Data
Lower
37H
Upper
DAH
CRC-16
Lower
8DH

Response Message (normal)


Slave Address
01H
Function Code
08H
Upper
00H
Test Code
Lower
00H
Upper
A5H
Data
Lower
37H
Upper
DAH
CRC-16
Lower
8DH

Response Message (fault)


Slave Address
01H
Function Code
89H
Error Code
01H
Upper
86H
CRC-16
Lower
50H

u Writing to Multiple Registers


Function code 10H allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process
works similar to reading registers, in that the address of the first register to be written and the data quantity are set in the
command message. The data to be written must be consecutive so that the register addresses are in order, starting from the
specified address in the command message. The data order must be high byte then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference of
60.0 Hz for the slave 1 drive.
If parameter values are changed using the Write command, an Enter command may be necessary to activate or save the data
depending on the setting of H5-11. Refer to H5-11: Communications Enter Function Selection on page 122 and Refer to
Enter Command on page 338 for detailed descriptions.

320

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.8 Message Examples


Command Message
Slave Address
01H
Function Code
10H
Upper
00H
Starting No.
Lower
01H
Upper
00H
Data Quantity
Lower
02H
Number of Bytes
04H
Upper
00H
Starting Data
Lower
01H
Upper
02H
Next Data
Lower
58H
Upper
63H
CRC-16
Lower
39H

Response Message (fault)


Slave Address
01H
Function Code
90H
Error Code
02H
Upper
CDH
CRC-16
Lower
C1H

Double the number of the data quantity for the number of bytes in the command message.

MEMOBUS/Modbus
Communications

Note:

Response Message (normal)


Slave Address
01H
Function Code
10H
Upper
00H
Starting No.
Lower
01H
Upper
00H
Data Quantity
Lower
02H
Upper
10H
CRC-16
Lower
08H

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

321

B.9 MEMOBUS/Modbus Data Table

B.9 MEMOBUS/Modbus Data Table


The table below lists all MEMOBUS/Modbus data. There are three types of data: command data, monitor data, and broadcast
data.

u Command Data
It is possible to both read and write command data.
Note:

Bits that are not used should be set to 0. Refrain from writing to reserved registers.

Register No.
0000H

Contents
Reserved
Operation Commands and Multi-function Inputs
H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run)
bit 0
H5-12 = 1: Run Command (0 = Stop, 1 = Run)
H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Reverse Run)
bit 1
H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse)
bit 2
bit 3
bit 4

0001H
bit 5

0002H
0003H
0004H
0005H
0006H
0007H
0008H

0009H

000AH
000BH to 000EH

322

External Fault (EF0)


Fault Reset
Multi-Function Input 1
Function is ComRef when H1-01 = 40 (Forward/Stop). Refer to d: Reference Settings on page 58 for
ComRef explanations.
Multi-Function Input 2
Function is ComCtrl when H1-02 = 41 (Reverse/Stop). Refer to d: Reference Settings on page 58 for
ComCtrl explanations.

bit 6
Multi-Function Input 3
bit 7
Multi-Function Input 4
bit 8
Multi-Function Input 5
bit 9
Multi-Function Input 6
bit A
Multi-Function Input 7
bit B
Multi-Function Input 8
bit C to F
Reserved
Frequency Reference Units are determined by parameter o1-03.
V/f Gain
Torque Reference/Torque Limit, 0.1% units, signed (Usable only if Torque Control is enabled)
Torque Compensation, 0.1% units, signed (Usable only if Torque Control is enabled)
PID Target, 0.01% units, signed
Analog Output Terminal FM Setting (10 V / 4000 H)
Analog Output Terminal AM Setting (10 V / 4000 H)
Settings for Multi-Function Digital Outputs
bit 0
Multi-Function Contact Output 1 (terminal M1-M2)
bit 1
Multi-Function Contact Output 2 (terminal M3-M4)
bit 2
Multi-Function Contact Output 3 (terminal M5-M6)
bit 3 to 5
Reserved
bit 6
Enables the function in bit 7
bit 7
Fault Contact Output (terminal MA/MB-MC)
bit 8 to F
Reserved
Pulse Output Terminal MP Setting, 1 Hz units, Setting Range: 0 to 32000
Reserved

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table


Register No.

0010H to 001AH
001BH
001CH
001DH

Contents
Control Selection Setting
bit 0
Reserved
bit 1
PID Setpoint Input
bit 2
Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
bit 3
Torque compensation input (enables the setting from MEMOBUS/Modbus)
bit 4 to B
Reserved
bit C
Enable Terminal S5 Input for Broadcast Data
bit D
Enable Terminal S6 Input for Broadcast Data
bit E
Enable Terminal S7 Input for Broadcast Data
bit F
Enable Terminal S8 Input for Broadcast Data
Reserved
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
Digital Output Option DO-A3 Output (Binary)

001EH to 001FH

Reserved

000FH

u Monitor Data
Monitor data can be read only.

0020H

0021H

Contents
Drive Status 1
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to bit D
bit E
bit F
Fault Contents 1
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F

During Run
During Reverse
Drive Ready
Fault
Data Setting Error
Multi-Function Contact Output (terminal M1-M2)
Multi-function Photocoupler output 1Terminal P1 - PC
Multi-function Photocoupler output 2Terminal P2 - PC
Reserved
ComRef status
ComCtrl status
Overcurrent (oC), Ground fault (GF)
Overvoltage (ov)
Drive Overload (oL2)
Overheat 1 (oH1), Drive Overheat Warning (oH2)
Dynamic Braking Transistor Fault (rr), Braking Resistor Overheat (rH)
Reserved
PID Feedback Loss (FbL / FbH)
EF to EF8: External Fault
CPFoo: Hardware Fault (includes oFx)
Motor Overload (oL1), Overtorque Detection 1/2 (oL3/oL4), Undertorque Detection 1/2 (UL3/
UL4)
PG Disconnected (PGo), PG Hardware Fault (PGoH), Overspeed (oS), Excessive Speed Deviation
(dEv)
Main Circuit Undervoltage (Uv)
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
Output Phase Loss (LF), Input Phase Loss (PF)
MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
Operator Connection Fault (oPr)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

323

MEMOBUS/Modbus
Communications

Register No.

B.9 MEMOBUS/Modbus Data Table


Register No.

0022H

0023H

U1-01 Frequency Reference

0024H

U1-02 Output Frequency <1>


U1-06 Output Voltage Reference, 0.1 V units (units are determined by parameter H5-10)
U1-03Output Current, 0.1 A units
U1-08 Output Power
U1-09 Torque Reference

0025H
0026H
0027H
0028H

0029H

002AH

002BH

324

Contents
Data Link Status
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6 to bit F

Fault Contents 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
Alarm Contents 1
bit 0, 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
U1-10 Input Terminal Status
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to bit F

Writing data or switching motors


Reserved
Upper or lower limit error
Data conformity error
Writing to EEPROM
Reserved
<1>

IGBT Short Circuit (SC)


Ground Fault (GF)
Input Phase Loss (PF)
Output Phase Loss (LF)
Braking Resistor Overheat (rH)
Reserved
Motor Overheat 2 (PTC input) (oH4)
Reserved
Reserved
Run Command Input Error (EF)
Drive Baseblock (bb)
Overtorque Detection 1 (oL3)
Heatsink Overheat (oH)
Overvoltage (ov)
Undervoltage (Uv)
Cooling Fan Error (FAn)
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Undertorque Detection 1/2 (UL3/UL4)
Motor Overheat (oH3)
PID Feedback Loss (FbL, FbH)
Reserved
Serial Communication Transmission Error (CALL)
Terminal S1 Closed
Terminal S2 Closed
Terminal S3 Closed
Terminal S4 Closed
Terminal S5 Closed
Terminal S6 Closed
Terminal S7 Closed
Terminal S8 Closed
Reserved

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table


Register No.

002DH

002EH
002FH
0030H
0031H
0032H
0033H
0034H
0035H
0036H, 0037H
0038H
0039H
003AH
003BH, 003CH

003DH

003EH
003FH
0040H to 004AH

During Run
Zero Speed
Speed Agree
User Speed Agree
Frequency Detection 1
Frequency Detection 2
Drive Ready
During Undervoltage
During Baseblock
Frequency Reference from Operator Keypad
Run Command from Operator Keypad
Over/Undertorque 1, 2
Frequency Reference Loss

bit D
During Fault Restart
bit E
Fault
bit F
Communication Timeout
U1-11 Output Terminal Status
bit 0
Multi-Function Contact Output 1 (terminal M1-M2)
bit 1
Multi-Function PHC output 1 (P1-PC)
bit 2
Multi-Function PHC output 2 (P2-PC)
bit 3 to 6
Reserved
bit 7
Fault Contact Output (terminal MA/MB-MC)
bit 8 to F
Reserved
Reserved
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
Reserved
DC Bus Voltage, 1 Vdc units
Torque Reference (U1-09), 1% units
Reserved
Product Code 1 [ASCII], Product Type (A0 for A1000)
Product Code 2 [ASCII], Region Code
Reserved
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
PID Input, 0.1% units, signed, 100% / max. output frequency
PID Output, 0.1% units, signed, 100% / max. output frequency
Reserved
Communications Error Contents <3>
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
Output Frequency

MEMOBUS/Modbus
Communications

002CH

Contents
Drive Status 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C

r/min <4>
0.01% units

Used for various monitors U1-oo. Refer to U: Monitors on page 292 for parameter details.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

325

B.9 MEMOBUS/Modbus Data Table


Register No.

004BH

004CH to 007EH
007FH
0080H to 0097H
0098H
0099H
009AH
009BH
009CH to 00AAH
00ABH
00ACH
00ADH
00AEH, 00AFH

During Run
During Zero Speed
During Reverse Run
During Fault Reset Signal Input
During Speed Agree
Drive Ready
Alarm
Fault

bit 8

During Operation Error (oPEoo)

bit 9
bit A
bit B
bit E
bit F

During Momentary Power Loss


Motor 2 selected
Reserved
ComRef status, NetRef status
ComCtrl status, NetCtrl status

Used for various monitors U1-oo, U4-oo, U5-oo and U6-oo. Refer to U: Monitors on page 292 for parameter details.
Alarm Code, Refer to Alarm Register Contents on page 337 for alarm codes.
Used for monitors U2-oo, U3-oo. Refer to U: Monitors on page 292 for parameter details and Refer to Fault Trace
Contents on page 335 for register value descriptions.
High Word of Accumulated Operation Time Monitor, 10 h units (U4-01)
Low Word of Accumulated Operation Time Monitor, 1 h units (U4-01)
High Word of Cooling Fan Operation Time Monitor (U4-03)
Low Word of Cooling Fan Operation Time Monitor (U4-03)
Reserved
Drive Rated Current

<2>

Motor Speed (U1-05)

r/min units <4>


0.01% units

Reserved
Register contains ASCII code of the option card.
DI-A3 = 0x01
DO-A3 = 0x02
AI-A3 = 0x03
AO-A3 = 0x04
PG-B3 = 0x11
PG-X3 = 0x12
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type
number.
Example: Register value is 5343H for SC if a SI-C3 option card is installed.

00B0H

Option Code Connected to


CN5-A

00B1H
00B2H
00B3H

Reserved
Option Code Connected to CN5-B
Option Code Connected to CN5-C

00B4H

Reserved

00B5H

Frequency Reference After


Soft-starter (U1-16)

00B6H
00B7H
00B8H
00B9H to 00BEH
00BFH

326

Contents
Drive status (U1-12)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7

Frequency Reference

r/min units <4>


0.01% units
r/min

<4>

0.01% units

Reserved
Lists the last two digits of operation error code oPEoo.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table

00C0H

00C1H

00C2H

Contents
Fault Contents 3
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Fault Contents 4
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Fault Contents 5
bit 0
bit 1
bit 2, 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B to E
bit F

Blown fuse (PUF)


Undervoltage (Uv1)
Control Power Supply Undervoltage (Uv2)
Soft Charge Circuit Fault (Uv3)
IGBT Short Circuit (SC)
Ground Fault (GF)
Overcurrent (oC)
Overvoltage (ov)
Heatsink Overheat (oH)
Heatsink Overheat (oH1)
Motor Overload (oL1)
Drive Overload (oL2)
Overtorque Detection 1 (oL3)
Overtorque Detection 2 (oL4)
Reserved
Reserved
External Fault at input terminal S3 (EF3)
External Fault at input terminal S4 (EF4)
External Fault at input terminal S5 (EF5)
External Fault at input terminal S6 (EF6)
External Fault at input terminal S7 (EF7)
External Fault at input terminal S8 (EF8)
Cooling Fan Error (FAn)
Overspeed (os)
Excessive Speed Deviation (dEv)
PG Disconnected (PGo)
Input Phase Loss (PF)
Output Phase Loss (LF)
Motor Overheat (PTC input) (oH3)
Digital Operator Connection Fault (oPr)
EEPROM Write Error (Err)
Motor Overheat Fault (PTC input) (oH4)
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Reserved
Control Fault (CF)
Zero Servo Fault (SvE)
Option External Fault (EF0)
PID Feedback Loss (FbL)
Undertorque Detection 1 (UL3)
Undertorque Detection 2 (UL4)
High Slip Braking Overload (oL7)
Reserved
Hardware Fault (includes oFx)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

MEMOBUS/Modbus
Communications

Register No.

327

B.9 MEMOBUS/Modbus Data Table


Register No.

00C3H

00C4H

00C5H

Contents
Fault Contents 6
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B to F
Fault Contents 7
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6, 7
bit 8
bit 9 to B
bit C
bit D
bit E
bit F
Fault Contents 8
bit 0
bit 1
bit 2
bit 3 to 9
bit A

00C6H

00C7H

328

bit B to D
bit E
bit F
Fault Contents 9
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5 to F
Reserved

Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
PG Hardware Fault (PGoH)
SI-T3 Watchdog Error (E5)
Reserved
Too many speed search restarts (SEr)
Reserved
PID Feedback Loss (FbH)
External Fault 1, input terminal S1 (EF1)
External Fault 2, input terminal S2 (EF2)
Mechanical Weakening Detection 1 (oL5)
Mechanical Weakening Detection 2 (UL5)
Current Offset Fault (CoF)
Reserved
DriveWorksEZ Fault (dWFL)
Reserved
Output Voltage Detection Fault (voF)
Reserved
Reserved
Reserved
Reserved
Reserved
Thermistor Disconnect (THo)
Reserved
Polarity Judge Timeout (dv7)
This is not available in A1000 HPP models.
Reserved
Power Unit Output Phase Loss 3 (LF3)
Current Unbalance (UnbC)
Gate Drive Board Undervoltage (Uv4)
Uv5MC/FANAbnormal low-voltage power supply
oH6Thermal converter
dFAnFAN abnormal diode module
EFAnFAN panel anomalies
Reserved

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table


Register No.

00C8H

00C9H

bit D
bit E
bit F
Alarm Contents 3
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Alarm Contents 4
bit 0
bit 1
bit 2 to 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B to F

Undervoltage (Uv)
Overvoltage (ov)
Heatsink Overheat (oH)
Drive Overheat (oH2)
Overtorque 1 (oL3)
Overtorque 2 (oL4)
Run Commands Input Error (EF)
Drive Baseblock (bb)
External Fault 3, input terminal S3 (EF3)
External Fault 4, input terminal S4 (EF4)
External Fault 5, input terminal S5 (EF5)
External Fault 6, input terminal S6 (EF6)
External Fault 7, input terminal S7 (EF7)
External Fault 8, input terminal S8 (EF8)
Cooling Fan Error (FAn)
Overspeed (oS)
Excessive Speed Deviation (dEv)
PG Disconnected (PGo)
Digital Operator Connection Fault (oPr)
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Serial Communication Transmission Error (CALL)
Motor Overload (oL1)
Drive Overload (oL2)
Reserved
Option Card External fault (EF0)
Motor 2 Switch command input during run (rUn)
Reserved
Serial Communication Transmission Error (CALL)
Undertorque Detection 1 (UL3)
Undertorque Detection 2 (UL4)
MEMOBUS/Modbus Test Mode Fault (SE)
Reserved
Motor Overheat 1 (PTC Input) (oH3)
Reserved
PID Feedback Loss (FbL)
PID Feedback Loss (FbH)
Reserved
Drive Disabled (dnE)
PG Disconnected (PGo)
Reserved
MEMOBUS/Modbus
Communications

00CAH

Contents
Alarm Contents 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

329

B.9 MEMOBUS/Modbus Data Table


Register No.

00CBH

Contents
Alarm Contents 5
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9

SI-T3 Watchdog Error (E5)


SI-T3 Station Address Setting Error (AEr)
SI-T3 Comm. Cycle Setting Error (CyC)
High Current Alarm (HCA)
Cooling Fan Maintenance Time (LT-1)
Soft Charge Bypass Relay Maintenance Time (LT-2)
Reserved
SI-S EEPROM Error (EEP)
External Fault 1 (input terminal S1) (EF1)
External Fault 2 (input terminal S2) (EF2)

bit A

Safe Disable Input (HbbF) <5>

bit B

Safe Disable Input (Hbb) <5>


Mechanical Weakening Detection 1 (oL5)

bit C

00CCH

00CDH

00CEH-00CFH

00D0H

330

bit D
bit E, F
Alarm Contents 6
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5 to 7
bit 8
bit 9 to F
bit 0 to 7
bit 8
bit 9
bit A
bit B to F
Reserved
CPF Contents 1
bit 0, 1
bit 2
bit 3
bit 4, 5
bit 6
bit 7
bit 8
bit 9, A
bit B
bit C
bit D
bit E
bit F

Mechanical Weakening Detection 2 (UL5)


Reserved
Output Voltage Detection Fault (VoF)
IGBT Maintenance Time (90%) (TrPC)
Capacitor Maintenance Time (LT-3)
IGBT Maintenance Time (50%) (LT-4)
Unused
Reserved
DriveWorksEZ Alarm (dWAL)
Reserved
Reserved
EFAn (Abnormal Fan Alarm)
Reserved
dFAn (Abnormal Fan Diode Module)
Reserved

Reserved
A/D Conversion Error (CPF02)
PWM Data Fault (CPF03)
Reserved
EEPROM Memory Data Error (CPF06)
Terminal Board Connection Error (CPF07)
EEPROM Serial Communications Fault (CPF08)
Reserved
RAM Fault (CPF11)
FLASH Memory Fault (CPF12)
Watchdog Circuit Exception (CPF13)
Control Circuit Fault (CPF14)
Reserved

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table

00D1H

00D2H

00D3H to 00D7H

00D8H

00D9H

00DAH to 00DBH

Contents
CPF Contents 2
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
bit 0
bit 1
bit 2
bit 3
bit 4 to 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
Reserved
oFA0x Contents (CN5-A)
bit 0
bit 1
bit 2
bit 3, 4
bit 5
bit 6
bit 7 to F
oFA1x Contents (CN5-A)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved

Clock Fault (CPF16)


Timing Fault (CPF17)
Control Circuit Fault (CPF18)
Control Circuit Fault (CPF19)
Hardware fault at power up (CPF20)
Hardware fault at communication start up (CPF21)
A/D Conversion Fault (CPF22)
PWM Feedback Fault (CPF23)
Drive Unit Signal Fault (CPF24)
Terminal board is not properly connected. (CPF25)
ASIC BB Circuit Error (CPF26)
ASIC PWM Setting Register Error (CPF27)
ASIC PWM Pattern Error (CPF28)
ASIC On-delay Error (CPF29)
ASIC BBON Error (CPF30)
ASIC Code Error (CPF31)
ASIC Start-up Error (CPF32)
Watch-dog Error (CPF33)
ASIC Power/Clock Error (CPF34)
External A/D Converter Error (CPF35)
Reserved
Control Circuit Error (CPF41)
Control Circuit Error (CPF42)
Control Circuit Error (CPF43)
Control Circuit Error (CPF44)
Control Circuit Error (CPF45)
Reserved

Option Compatibility Error (oFA00)


Option not properly connected (oFA01)
Same type of option card already connected (oFA02)
Reserved
A/D Conversion Error (oFA05)
Option Response Error (oFA06)
Reserved
Option RAM Fault (oFA10)
Option Operation Mode Fault (SLMOD) (oFA11)
Drive Receive CRC Error (oFA12)
Drive Receive Frame Error (oFA13)
Drive Receive Abort Error (oFA14)
Option Receive CRC Error (oFA15)
Option Receive Frame Error (oFA16)
Option Receive Abort Error (oFA17)
Reserved

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

MEMOBUS/Modbus
Communications

Register No.

331

B.9 MEMOBUS/Modbus Data Table


Register No.

00DBH

00DCH

00DDH

00DEH to 00DFH

332

Contents
oFA3x Contents (CN5-A)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
oFb0x Contents (CN5-B)
bit 0
bit 1
bit 2
bit 3, 4
bit 5
bit 6
bit 7 to F
oFb1x Contents (CN5-B)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved

Comm. ID Error (oFA30)


Model Code Error (oFA31)
Sumcheck Error (oFA32)
Comm. option timeout waiting for response (oFA33)
MEMOBUS Timeout (oFA34)
Drive timeout waiting for response (oFA35)
CI Check Error (oFA36)
Drive timeout waiting for response (oFA37)
Control Command Selection Error (oFA38)
Drive timeout waiting for response (oFA39)
Control Response Selection 1 Error (oFA40)
Drive timeout waiting for response (oFA41)
Control Response Selection 2 Error (oFA42)
Control Response Selection Error (oFA43)
Reserved
Option compatibility error (oFb00)
Option not properly connected (oFb01)
Same type of option card already connected (oFb02)
Reserved
A/D Conversion Fault (oFb05)
Option Response Error (oFb06)
Reserved
Option RAM Fault (oFb10)
Option Operation Mode Fault (SLMOD) (oFb11)
Drive Receive CRC Error (oFb12)
Drive Receive Frame Error (oFb13)
Drive Receive Abort Error (oFb14)
Option Receive CRC Error (oFb15)
Option Receive Frame Error (oFb16)
Option Receive Abort Error (oFb17)
Reserved

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table


Register No.

00E0H

00E1H

00E2H

bit D
bit E, F
oFC0x Contents (CN5-C)
bit 0
bit 1
bit 2
bit 3, 4
bit 5
bit 6
bit 7 to F
oFC1x Contents (CN5-C)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8 to F
Reserved

Comm. ID Error (oFb30)


Model Code Error (oFb31)
Sumcheck Error (oFb32)
Comm. option timeout waiting for response (oFb33)
MEMOBUS Timeout (oFb34)
Drive timeout waiting for response (oFb35)
CI Check Error (oFb36)
Drive timeout waiting for response (oFb37)
Control Command Selection Error (oFb38)
Drive timeout waiting for response (oFb39)
Control Response Selection 1 Error (oFb40)
Drive timeout waiting for response (oFb41)
Control Response Selection 2 Error (oFb42)
Control Response Selection Error (oFb43)
Reserved
Option compatibility error (oFC00)
Option not properly connected (oFC01)
Same type of option card already connected (oFC02)
Reserved
A/D Conversion Fault (oFC05)
Option Response Error (oFC06)
Reserved
Option RAM Fault (oFC10)
Option Operation Mode Fault (SLMOD) (oFC11)
Drive Receive CRC Error (oFC12)
Drive Receive Frame Error (oFC13)
Drive Receive Abort Error (oFC14)
Option Receive CRC Error (oFC15)
Option Receive Frame Error (oFC16)
Option Receive Abort Error (oFC17)
Reserved

MEMOBUS/Modbus
Communications

00E3H, 00E4H

Contents
oFb3x Contents (CN5-B)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

333

B.9 MEMOBUS/Modbus Data Table


Register No.

00E5H

00E6H to 00FFH

Contents
oFC3x Contents (CN5-C)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E, F
Reserved

Comm. ID Error (oFC30)


Model Code Error (oFC31)
Sumcheck Error (oFC32)
Comm. option timeout waiting for response (oFC33)
MEMOBUS Timeout (oFC34)
Drive timeout waiting for response (oFC35)
CI Check Error (oFC36)
Drive timeout waiting for response (oFC37)
Control Command Selection Error (oFC38)
Drive timeout waiting for response (oFC39)
Control Response Selection 1 Error (oFC40)
Drive timeout waiting for response (oFC41)
Control Response Selection 2 Error (oFC42)
Control Response Selection Error (oFC43)
Reserved

<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> The number of decimal places in the parameter value depends on the drive model and the ND/HD selection in parameter C6-01. This value has two
decimal places (0.01 A) if the drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if
the maximum applicable motor capacity is higher than 11 kW.
<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04, E4-04, or E5-05 depending on the motor being used.
<5> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.

u Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.

0001H

0002H

334

Contents
Digital Input Command
bit 0
bit 1
bit 2, 3
bit 4
bit 5
bit 6 to B
bit C
bit D
bit E
bit F
Frequency Reference

Forward Run (0: Stop 1: Run)


Direction Command (0: Forward, 1: Reverse)
Reserved
External Fault
Fault Reset
Reserved
Multi-Function Digital Input S5
Multi-Function Digital Input S6
Multi-Function Digital Input S7
Multi-Function Digital Input S8
30000/100%

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table

u Fault Trace Contents


The table below shows the fault codes that can be read out by MEMOBUS/Modbus commands from the U2-oo monitor
parameters.
Table B.4 Fault Trace / History Register Contents

000BH
000CH
000DH
000EH
000FH
0010H
0011H
0012H
0013H
0014H
0015H
0016H
0017H
0018H
0019H
001AH
001BH
001CH
001DH
001EH
001FH
0020H
0021H
0022H
0025H
0026H
0027H
0028H
0029H
002AH
0030H
0036H
0038H
003BH
0041H
0042H

Fault Name
Blown Fuse (PUF)
Undervoltage (Uv1)
Control Power Supply Undervoltage (Uv2)
Soft Charge Circuit Fault (Uv3)
Ground Fault (GF)
Overcurrent (oC)
Overvoltage (ov)
Heatsink Overheat (oH)
Heatsink Overheat (oH1)
Motor Overload (oL1)
Drive Overload (oL2)
Overtorque Detection 1 (oL3)
Overtorque Detection 2 (oL4)
Dynamic Braking Transistor (rr)
Braking Resistor Overheat (rH)
External Fault at Input Terminal S3 (EF3)
External Fault at Input Terminal S4 (EF4)
External Fault at Input Terminal S5 (EF5)
External Fault at Input Terminal S6 (EF6)
External Fault at Input Terminal S7 (EF7)
External Fault at Input Terminal S8 (EF8)
Drive Cooling Fan Failure (FAn)
Overspeed (oS)
Excessive Speed Deviation (dEv)
PG Disconnect (PGo)
Input Phase Loss (PF)
Output Phase Loss (LF)
Motor Overheat (PTC input) (oH3)
Digital Operator Connection (oPr)
EEPROM Write Error (Err)
Motor Overheat (PTC input) (oH4)
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Control Fault (CF)
Zero-Servo Fault (SvE)
Option External Fault (EF0)
PID Feedback Loss (FbL)
Undertorque Detection 1 (UL3)
Undertorque Detection 2 (UL4)
Hardware Fault (including oFx)
Output Current Imbalance (LF2)
PG Hardware Fault (PGoH)
Too Many Speed Search Restarts (SEr)
PID Feedback Loss (FbH)
External Fault 1, Input Terminal S1 (EF1)

Fault Code
0043H
0044H
0045H
0046H
0047H
0048H
0049H
004DH
0050H
0052H
0053H
0060H
0061H
0062H
0063H
0064H
0065H
0083H
0084H
0087H
0088H
0089H
008CH
008DH
008EH
008FH
0091H
0092H
0093H
0094H
0095H
0096H
0097H
0098H
0099H
009BH
009CH
009DH
009EH
009FH
00A0H
00A1H
00A2H
00A3H
00A4H

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Fault Name
External Fault 2, Input Terminal S2 (EF2)
Mechanical Weakening Detection 1 (oL5)
Mechanical Weakening Detection 2 (UL5)
Current Offset Fault (CoF)
PLC Detection Error 1 (PE1)
PLC Detection Error 2 (PE2)
DriveWorksEZ Fault (dWFL)
Output Voltage Detection Fault (voF)
Motor Overheat (NTC Input) ( oH5)
Node Setup Fault (nSE)
Thermistor Disconnect (THo)
Current Unbalance (UnbC)
Power Supply Module Undervoltage (Uv4)
Uv5MC/FANPower failure
oH6Thermal converter
dFAnFAN abnormal diode module
EFAn (Abormal FAN panel
A/D Conversion Error (CPF02)
PWM Data Fault (CPF03)
EEPROM Memory Data Error (CPF06)
Terminal Board Connection Error (CPF07)
EEPROM Serial Communication Fault (CPF08)
RAM Fault (CPF11)
Flash Memory Circuit Exception (CPF12)
Watchdog Circuit Exception (CPF13)
Control Circuit Fault (CPF14)
Clock Fault (CPF16)
Timing Fault (CPF17)
Control Circuit Fault (CPF18)
Control Circuit Fault (CPF19)
Hardware Fault at Power Up (CPF20)
Hardware Fault at Communication Start Up (CPF21)
A/D Conversion Fault (CPF22)
PWM Feedback Fault (CPF23)
Drive Unit Signal Fault (CPF24)
ASIC BB Circuit Error (CPF26)
ASIC PWM Setting Register Error (CPF27)
ASIC PWM Pattern Error (CPF28)
ASIC On-delay Error (CPF29)
ASIC BBON Error (CPF30)
ASIC Code Error (CPF31)
ASIC Start-up Error (CPF32)
Watch-dog Error (CPF33)
ASIC Power/Clock Error (CPF34)
External A/D Converter Error (CPF35)

335

MEMOBUS/Modbus
Communications

Fault Code
0001H
0002H
0003H
0004H
0006H
0007H
0008H
0009H
000AH

B.9 MEMOBUS/Modbus Data Table


Fault Code
00A9H
00AAH
00ABH
00ACH
00ADH
00AEH
0101H
0102H
0103H
0106H
0107H
0111H
0112H
0113H
0114H
0115H
0116H
0117H
0118H
0131H
0132H
0133H

336

Fault Name
Control Circuit Error (CPF40)
Control Circuit Error (CPF41)
Control Circuit Error (CPF42)
Control Circuit Error (CPF43)
Control Circuit Error (CPF44)
Control Circuit Error (CPF45)
Option Compatibility Error (oFA00)
Option Not Properly Connected (oFA01)
Same Type of Option Card Already Connected
(oFA02)
A/D Conversion Error (oFA05)
Option Response Error (oFA06)
Option RAM Fault (oFA10)
Option Operation Mode Fault (SLMOD) (oFA11)

0134H

Drive Receive CRC Error (oFA12)


Drive Receive Frame Error (oFA13)
Drive Receive Abort Error (oFA14)
Option Receive CRC Error (oFA15)
Option Receive Frame Error (oFA16)
Option Receive Abort Error (oFA17)
Comm. ID Error (oFA30)
Model Code Error (oFA31)
Sumcheck Error (oFA32)
Comm. Option Timeout Waiting for Response
(oFA33)

0135H
0136H
0137H
0138H
0139H
013AH
013BH
013CH
013DH

MEMOBUS Timeout (oFA34)


Drive Timeout Waiting for Response (oFA35)
CI Check Error (oFA36)
Drive Timeout Waiting for Response (oFA37)
Control Command Selection Error (oFA38)
Drive Timeout Waiting for Response (oFA39)
Control Response Selection 1 Error (oFA40)
Drive Timeout Waiting for Response (oFA41)
Control Response Selection 2 Error (oFA42)

Fault Code
013EH
0201H
0202H
0205H
0206H
0210H
0211H
0212H
0213H
0214H
0215H
0216H
0217H
0231H
0232H
0233H
0234H
0235H
0236H
0237H
0238H
0239H
023AH
023BH
023CH
023DH
023EH
0300H
0301H

Fault Name
Control Response Selection Error (oFA43)
Option Connection Error (oFb01)
Same Type of Option Card Already Connected
(oFb02)
A/D Conversion Error (oFb05)
Option Response Error (oFb06)
Option RAM Fault (oFb10)
Option Operation Mode Fault (SLMOD) (oFb11)
Drive Receive CRC Error (oFb12)
Drive Receive Frame Error (oFb13)
Drive Receive Abort Error (oFb14)
Option Receive CRC Error (oFb15)
Option Receive Frame Error (oFb16)
Option Receive Abort Error (oFb17)

0302H

Comm. ID Error (oFb30)


Model Code Error (oFb31)
Sumcheck Error (oFb32)
Comm. option Timeout Waiting for Response (oFb33)
MEMOBUS Timeout (oFb34)
Drive Timeout Waiting for Response (oFb35)
CI Check Error (oFb36)
Drive Timeout Waiting for Response (oFb37)
Control Command Selection Error (oFb38)
Drive Timeout Waiting for Response (oFb39)
Control Response Selection 1 Error (oFb40)
Drive Timeout Waiting for Response (oFb41)
Control Response Selection 2 Error (oFb42)
Control Response Selection Error (oFb43)
Option Compatibility Error (oFC00)
Option Not Properly Connected (oFC01)
Same Type of Option Card Already Connected
(oFC02)

0305H
0306H

A/D Conversion Error (oFC05)


Option Response Error (oFC06)

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.9 MEMOBUS/Modbus Data Table

u Alarm Register Contents


The table below shows the alarm codes that can be read out from MEMOBUS/Modbus register 007FH.
Table B.5 Alarm Register 007FH Contents
Fault Code
0001H
0002H
0003H
0004H
0005H
0006H
0007H
0008H
0009H
000AH
000BH
000CH
000DH
000EH
000FH
0010H
0011H
0012H
0014H
0015H
0016H
0017H
0018H
001AH
001BH
001DH
001EH
001FH
0020H

Fault Name
Undervoltage (Uv)
Overvoltage (ov)
Heatsink Overheat (oH)
Drive Overheat (oH2)
Overtorque 1 (oL3)
Overtorque 2 (oL4)
Run commands input error (EF)
Drive Baseblock (bb)
External Fault 3, input terminal S3 (EF3)
External Fault 4, input terminal S4 (EF4)
External Fault 5, input terminal S5 (EF5)
External Fault 6, input terminal S6 (EF6)
External Fault 7, input terminal S7 (EF7)
External Fault 8, input terminal S8 (EF8)
Cooling Fan Error (FAN)
Overspeed (oS)
Excessive Speed Deviation (dEv)
PG Disconnected (PGo)
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Serial Communication Transmission Error (CALL)
Motor Overload (oL1)
Drive Overload (oL2)
Option Card External Fault (EF0)
Motor Switch command input during run (rUn)
Serial Communication Transmission Error (CALL)
Undertorque Detection 1 (UL3)
Undertorque Detection 2 (UL4)
MEMOBUS/Modbus Test Mode Fault (SE)

Fault Code
0022H
0027H
0028H
002AH
002BH
0031H
0032H
0033H
0034H
0035H

Fault Name
Motor Overheat (oH3)
PID Feedback Loss (FbL)
PID Feedback Loss (FbH)
Drive Disabled (dnE)
PG Disconnected (PGo)
SI-T3 Watchdog Error (E5)
SI-T3 Station Address Setting Error (AEr)
SI-T3 Comm. Cycle Setting Error (CyC)
High Current Alarm (HCA)
Cooling Fan Maintenance Time (LT-1)

0036H
0038H
0039H
003AH

Capacitor Maintenance Time (LT-2)


SI-S EEPROM Error (EEP)
External Fault (input terminal S1) (EF1)
External Fault (input terminal S2) (EF2)

003BH

Safe Disable Input (HbbF) <1>

003CH

Safe Disable Input (Hbb) <1>


Mechanical Weakening Detection 1 (oL5)
Mechanical Weakening Detection 2 (UL5)
PLC Alarm (PA1)
PLC Alarm (PA2)
Output Voltage Detection Fault (voF)
IGBT Maintenance Time (90%) (TrPC)
Soft Charge Bypass Relay Maintenance Time (LT-3)
IGBT Maintenance Time (50%) (LT-4)
Motor Overheat (NTC Input) (oH5)
DriveWorksEZ Alarm (dWAL)
Thermistor Disconnect (THo)

003DH
003EH
003FH
0040H
0041H
0042H
0043H
0044H
0048H
0049H
004DH

MEMOBUS/Modbus
Communications

<1> Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to EN61800-5-1, ISO13849 Cat.
3, IEC/EN61508 SIL2, Insulation coordination: class 1.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

337

B.10 Enter Command

B.10 Enter Command


When writing parameters to the drive from the PLC using MEMOBUS/Modbus communication, parameter H5-11 determines
whether an Enter command must be issued to enable these parameters. This section describes the types and functions of the
Enter commands.

u Enter Command Types


The drive supports two types of Enter commands as shown in Table B.6. An Enter command is enabled by writing 0 to register
numbers 0900H or 0910H. It is only possible to write to these registers; attempting to read from these registers will cause an
error.
Table B.6 Enter Command Types
Register No.
0900H
0910H
Note:

Description
Simultaneously writes data into the EEPROM (non-volatile memory) of the drive and enables the data in RAM. Parameter
changes remain after cycling power.
Writes data in the RAM only. Parameter changes are lost when the drive is shut off.

The EEPROM can only be written to 100,000 times, so it is recommended to limit the number of times writing to the EEPROM. The Enter
command registers are write-only and if these registers are read, the register address will be invalid (Error code: 02H). An Enter command
is not required when reference or broadcast data are sent to the drive.

u Enter Command Settings when Upgrading the Drive


When replacing previous Yaskawa drive models with the A1000 and keeping the MEMOBUS/Modbus communications
settings, set parameter H5-11 in accordance with the Enter command configuration in the older drive. H5-11 determines
whether an Enter command is necessary to activate parameter changes in the drive.
If upgrading from a G7 or F7 series drive to an A1000, set parameter H5-11 to 0.
If upgrading from a V7 series drive to an A1000, set parameter H5-11 to 1.

n H5-11 and the Enter Command


An enter command is not required when writing registers 0000H to 001FH. Changes to those registers take effect immediately,
independent of the setting in parameter H5-11.
H5-11 Settings
H5-11 = 0
Drive being replaced
G7, F7
How parameter settings are enabled When the Enter command is received from the master.
Upper/lower limit check is performed, taking the settings
Upper/lower limit check
of related parameters into account.

V7
As soon as the value is changed.
Checks only the upper/lower limits of the parameters that
were changed.

affected. The settings of related parameters remain


Default value of related parameters Not
unchanged. They must be changed manually if needed.
Error handling when setting
Data is accepted even if one setting is invalid. The invalid
multiple parameters
setting will be discarded. No error message occurs.

Default settings of related parameters are changed


automatically.
Error occurs if only one setting is invalid. All data that
was sent are discarded.

338

H5-11 = 1

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

B.11 Communication Errors

B.11 Communication Errors


u MEMOBUS/Modbus Error Codes
A list of MEMOBUS/Modbus errors appears below.
When an error occurs, remove whatever caused the error and restart communications.
Error Name
Cause

Error Code
01H

02H

03H

Function Code Error


Attempted to set a function code from a PLC other than 03H, 08H, and 10H.
Register Number Error
A register number specified in the command message does not exist.
Attempted to send a broadcast message using other register numbers than 0001H or 0002H.
Bit Count Error
Read data or write data is greater than 16 bits. Invalid command message quantity.
In a write message, the Number of Data Items contained within the message does not equal twice the amount of data words
(i.e., the total of Data 1+ Data 2, etc.).

21H

Data Setting Error


Control data or parameter write data is outside the allowable setting range.
Attempted to write a contradictory parameter setting.

22H

Write Mode Error


During run, the user attempted to write a parameter that cannot be written to during run.
During an EEPROM memory data error (CPF06), the master attempted to write to a parameter other than A1-00 to A1-05,
E1-03, or o2-04.
Attempted to write to read-only data.

23H
24H

DC Bus Undervoltage Write Error


During an undervoltage situation, the master attempted to write to parameters that cannot be written to during undervoltage.
Write Error During Parameter Process
Master attempted writing to the drive while the drive was processing parameter data.

u Slave Not Responding


In the following situations, the slave drive will ignore the command message sent from the master, and not send a response
message:
When a communications error (overrun, framing, parity, or CRC-16) is detected in the command message.
When the slave address in the command message and the slave address in the drive do not match (remember to set the slave
address for the drive using H5-01).
When the gap between two blocks (8-bit) of a message exceeds 24 bits.
When the command message data length is invalid.
If the slave address specified in the command message is 00H, all slaves execute the write function, but do not return response messages
to the master.

MEMOBUS/Modbus
Communications

Note:

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

339

B.12 Self-Diagnostics

B.12 Self-Diagnostics
The drive has a built-in self-diagnosing function of the serial communication interface circuits. To perform the self-diagnosis
function, use the following procedure.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or
serious injury. Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply
is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least
one minute after all indicators are OFF and measure the DC bus voltage level to confirm safe level.

1.
2.
3.
4.

Turn on the power to the drive.


Note the present terminal S6 function selection setting (H1-06) and set it for the communications test mode
(H1-06 = 67).
Turn off the power to the drive.
With the power off, wire the drive as shown in the following diagram, connecting terminals R+ and S+, R- and S-, and
S6 and SC.

E(G) HC H1 H2 DM+ DM- IG R+ R- S+ SV+ AC V- A1 A2 A3 FM AM AC MP RP AC


S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

Figure B.9 Terminal Connections for Communication Self-Diagnostics

5.
6.
7.

Set jumper S3 to source mode (internal power supply).


Turn the power to the drive back on.
During normal operation, the drive will display Pass to indicate that the communications test mode is operating
normally.

When a fault occurs, the drive will display CE on the keypad display.
8. Turn off the power supply.
9. Remove the wire jumpers from terminal R+, R-, S+, S-, and S6-SC. Reset jumper S3 to its original position and set
terminal S6 to its original function.
10.Return to normal operation.

340

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Index
Numerics
2-Wire Initialization .........................................................11
3-Wire Initialization .........................................................11
3-Wire Sequence.............................................................11
3-Wire Sequence Wiring Diagram ........................................94
5th Most Recent Fault..................................................... 296

A
A/D Conversion Error..................................................... 181
A1-02 ........................................................................ 223
A1-02 (Motor 1 Control Mode) Dependent Parameters .............. 301
A1-04 ........................................................................ 221
A1-04, A1-05: Password and Password Setting .........................11
A1-05 ........................................................................ 221
Abnormal Diode Module Fan ...................................... 182, 200
Abnormal Panel Fan................................................. 183, 200
Accel/Decel Time.......................................................... 173
Accel/Decel Time Setting Units ...........................................47
Accel/Decel Time Switching Frequency .................................46
Acceleration Error ......................................................... 213
Acceleration Time ...........................................................45
Access Level Selection......................................................10
Action Selection below Minimum Output Frequency ..................22
Adjusted Slip Calculation Error ......................................... 211
Adjusting the ASR Parameters.............................................52
AEr........................................................................... 198
AFR.......................................................................... 154
AFR Gain ................................................................... 172
AFR Time Constant 1 ..................................................... 172
AFR Time Constant 2 ..................................................... 173
AI-A3 Settings ...............................................................85
Alarm Register 007FH Contents......................................... 337
Alarms and Errors ......................................................... 175
Ambient Temperature Setting...................................... 150, 282
Analog Filter Time Constant ............................................. 173
Analog Frequency Reference Fluctuation Limit.........................66
Analog Frequency Reference Sample/Hold..............................99
Analog Input Card Settings.................................................85
Analog Input Filter Time Constant ...................................... 115
Analog Input Option Card Bias ............................................86
Analog Input Option Card Gain ...........................................86
Analog Input Option Card Operation Selection .........................85
Analog Input Terminal Enable Selection ............................... 116
Analog Monitor Card Settings .............................................86
AO-A3 Settings ..............................................................86
ASR............................................................................52
ASR Gain Switching Frequency...........................................54

ASR Integral Limit ..........................................................55


ASR Integral Time...........................................................54
ASR Limit ....................................................................55
ASR Primary Delay Time Constant .......................................55
ASR Proportional Gain .....................................................54
Automatic Reduction Selection for Stall Prevention during Run...140,
279
Automatic Speed Regulator ................................................52
Auto Restart Fault Output Operation Selection........................ 143
Auto Restart Operation Selection........................................ 280
Auto-Tuning Codes........................................................ 211
Auto-Tuning Errors........................................................ 178
Auto-Tuning Fault Detection............................................. 211
Auto-Tuning Fault Solutions ............................................. 211
Auto-Tuning Mode Selection ...................................... 163, 290

B
b1-01......................................................................... 221
b1-02......................................................................... 221
b1-04......................................................................... 222
b2-02......................................................................... 226
b2-04......................................................................... 226
b5-09......................................................................... 226
b6-01 through b6-04....................................................... 173
Baseblock ................................................................... 198
Base Frequency ..............................................................75
Base Voltage .................................................................75
bb............................................................................. 198
Bi-Directional Speed Search Selection ...................................31
boL..................................................................... 180, 198
Braking Resistor Fault .................................................... 194
Braking Resistor Overheat................................................ 194
Braking Transistor Overload Fault ................................ 180, 198
Broadcast Messages ....................................................... 334
bUS .................................................................... 180, 198
bUS Error Detection Time..................................................89

C
C2-01 through C2-04...................................................... 173
C3-01 .................................................................. 172, 173
C3-02 ........................................................................ 173
C4-01 ........................................................................ 172
C4-02 .................................................................. 172, 173
C4-06 ........................................................................ 173
CALL........................................................................ 199
Cannot Change Parameter Settings...................................... 220
Cannot Reset ............................................................... 199
CANopen Communication Speed .........................................91

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

341

Index
CANopen Node ID Selection ...................................................90
CANopen Parameters ....................................................... 88, 90
Capacitor Maintenance......................................................... 296
Capacitor Maintenance Setting ......................................... 161, 287
Capacitor Maintenance Time.................................................. 202
Carrier Frequency.................................................................56
Carrier Frequency Reduction.................................................. 283
Carrier Frequency Reduction Off-Delay Time ............................. 152
Carrier Frequency Reduction Selection...................................... 151
Carrier Frequency Selection.....................................................57
CC-Link bUS Error Auto Reset.................................................90
CC-Link Communication Speed................................................90
CC-Link Node Address ..........................................................89
CC-Link Parameters......................................................... 88, 89
CE........................................................................... 180, 199
CE Detection Time ....................................................... 122, 314
CF ................................................................................. 180
Coast to stop .......................................................................20
Coast to Stop with Timer ........................................................21
Comm. option card connection error (CN5-A) ............................. 187
Command Messages from Master to Drive ................................. 317
Communication Error .......................................................... 216
Communication Fault Detection Selection ............................ 121, 313
Communication Option Card....................................................88
Communication Option Card Reference..................................... 298
Communication Option Station Number Setting Error (CC-Link, CANopen,
MECHATROLINK-II)......................................................... 198
Communication Parity Selection ....................................... 121, 313
Communications Enter Function Selection ........................... 122, 314
Communications Error Operation Selection ..................................88
Communication Speed Selection ....................................... 120, 313
Communications Timing ...................................................... 317
Comparing Parameter Settings................................................ 217
Compressor Application .........................................................16
Connected Machinery Vibrates When Motor Rotates ..................... 225
Connection of a Motor PTC ................................................... 127
Continuous Electrothermal Operation Selection ..................... 128, 276
Control Board Connection Error........................................ 181, 182
Control Circuit Error ..................................................... 181, 182
Control Fault .................................................................... 180
Control Method Selection .......................................................10
Control Method Selection Error .............................................. 208
Control Mode................................................................10, 292
Control Mode Dependent Parameter Default Values ...................... 301
Control Mode Mismatch ....................................................... 216
Control Power Supply Voltage Fault......................................... 196
Converter Heating .............................................................. 190
Conveyor Application............................................................14
Cooling Fan Maintenance ..................................................... 296
Cooling Fan Maintenance Setting (Operation Time) ...................... 287
Cooling Fan Maintenance Time .............................................. 202
Cooling Fan Operation Time.................................................. 296
Cooling Fan Operation Time Setting......................................... 161
CoPy .............................................................................. 216
Copy Allowed Selection ....................................................... 160
Copy Function................................................................... 160
Copy Function Errors .......................................................... 175
Copy Function Selection....................................................... 160
Copy Unit Error ................................................................. 216
CPEr .............................................................................. 216
342

CPF02 ............................................................................ 181


CPF03 ............................................................................ 181
CPF06 ............................................................................ 181
CPF07 ............................................................................ 181
CPF08 ............................................................................ 181
CPF11 to CPF14 ................................................................ 181
CPF16 to CPF19 ................................................................ 181
CPF20 ............................................................................ 181
CPF21 ............................................................................ 181
CPF22 ............................................................................ 182
CPF23 ............................................................................ 182
CPF24 ............................................................................ 182
CPF26 to CPF34 ................................................................ 182
CPyE ............................................................................. 216
CRC-16 .......................................................................... 318
CRC-16 Checksum Calculation Example ................................... 319
CrST .............................................................................. 199
CSEr .............................................................................. 216
Cumulative Operation Time................................................... 296
Cumulative Operation Time at 5th Most Recent Fault .................... 296
Cumulative Operation Time at Most Recent Fault ......................... 296
Cumulative Operation Time at Previous Fault.............................. 295
Cumulative Operation Time Selection................................. 161, 287
Cumulative Operation Time Setting ................................... 161, 287
Current Alarm ................................................................... 202
Current Detection Error ........................................................ 213
Current Detection Speed Search ................................................27
Current Fault .................................................................... 294
Current Unbalance.............................................................. 195
Cyclic Redundancy Check..................................................... 318

D
d2-01.............................................................................. 226
d3-01.............................................................................. 225
d3-01 through d3-04............................................................ 173
d3-04.............................................................................. 225
d-Axis ACR Output ............................................................ 299
DC Bus Overvoltage ........................................................... 204
DC Bus Pre-Charge Relay Maintenance Setting ........................... 161
DC Bus Undervoltage .......................................................... 196
DC Bus Voltage................................................................. 292
DC Bus Voltage at Previous Fault............................................ 295
DC Bus Voltage Setpoint during KEB....................................... 136
DC Injection Braking at Stop ................................................. 226
DC Injection Braking Current.............................................26, 226
DC Injection Braking Input Timing Diagram............................... 101
DC Injection Braking Start Frequency.........................................20
DC Injection Braking Time at Start ............................................20
DC Injection Braking Time at Stop ............................................26
DC Injection Braking to Stop ...................................................20
D Control ..........................................................................33
Deceleration Time ................................................................45
Deceleration Time at Stall Prevention during Acceleration......... 137, 279
Defaults by Drive Model Selection (o2-04) and ND/HD (C6-01) ....... 159
Delay Timers ......................................................................32
Derivative Time (D) ..............................................................36
Desired DC Bus Voltage during KEB ....................................... 277
dEv.......................................................................... 182, 199
DeviceNet Baud Rate Monitor..................................................92
DeviceNet Communication Speed..............................................91

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Index
DeviceNet Heartbeat Interval ...................................................92
DeviceNet Idle Mode Fault Detection .........................................91
DeviceNet MAC Address........................................................91
DeviceNet Network MAC ID ...................................................92
DeviceNet Parameters....................................................... 88, 91
DeviceNet PCA Setting ..........................................................91
DeviceNet PPA Setting ..........................................................91
DeviceNet Scaling Factors ......................................................92
dFAn........................................................................ 182, 200
dFPS .............................................................................. 216
DI-A3 Settings ....................................................................86
Diagnosing and Resetting Faults ............................................. 186
Digital Input Card Settings ......................................................86
Digital Input Option Card Input Selection ....................................86
Digital Input Option DI-A3 Data Length Selection ..........................86
Digital Input Reading ............................................................23
Digital Operator Display Selection..................................... 157, 286
Digital Operator Keypad Functions .......................................... 158
Digital Output Card Settings ....................................................87
Digital Output Option Card Terminal Function Selection ..................87
dnE................................................................................ 200
DO-A3 Output Mode Selection.................................................88
DO-A3 Settings ...................................................................87
Drive/kVA Selection ........................................................... 286
Drive Capacity Setting Fault .................................................. 207
Drive Disabled .................................................................. 200
Drive Does Not Allow Selection of Rotational Auto-Tuning ............ 223
Drive Duty Mode Selection .....................................................56
Drive Model Mismatch ........................................................ 216
Drive Model Selection ......................................................... 159
Drive Mode Unit Monitor Selection ................................... 157, 286
Drive Operation Status at Previous Fault.................................... 295
Drive Overheat Warning....................................................... 203
Drive Overload.................................................................. 191
Drive Slave Address...................................................... 120, 313
Drive Status...................................................................... 293
Drive Transmit Wait Time .............................................. 121, 314
Drive Unit Signal Fault ........................................................ 182
DriveWorksEZ Connection Parameters ..................................... 162
DriveWorksEZ Custom Monitor 1 to 10 .................................... 300
DriveWorksEZ Fault ........................................................... 183
DriveWorksEZ Function Selection.............................................16
DriveWorksEZ Monitors ...................................................... 167
DriveWorksEZ Parameters .................................................... 162
Droop Control Delay Time ......................................................43
Droop Control Gain ..............................................................43
During Frequency Output Time Chart ....................................... 112
During Run Time Chart........................................................ 104
dv1 ................................................................................ 183
dv2 ................................................................................ 183
dWAL ............................................................................ 183
Dwell Function..............................................................42, 173
Dwell Reference at Start .........................................................42
Dwell Reference at Stop .........................................................42
Dwell Time at Start...............................................................42
Dwell Time at Stop ...............................................................42
DWEZ Version Control Monitor 1 to 3...................................... 300
dWFL............................................................................. 183
Dynamic Braking Transistor .................................................. 194

E
E1-03 ............................................................................. 223
E1-04 ....................................................................... 223, 226
E1-08 ....................................................................... 172, 173
E1-09 ............................................................................. 221
E1-10 ....................................................................... 172, 173
E2-01 ............................................................................. 172
E2-02 ............................................................................. 172
E2-03 ....................................................................... 172, 212
E3-01 (Motor 2 Control Mode) Dependent Parameters ................... 302
E5 ................................................................................. 183
EEPROM Memory Data Error................................................ 181
EEPROM Write Error.......................................................... 184
EF ................................................................................. 200
EF0 ......................................................................... 183, 200
EF1 ......................................................................... 184, 200
EF2 ......................................................................... 184, 200
EF3 ......................................................................... 184, 200
EF4 ......................................................................... 184, 200
EF5 ......................................................................... 184, 201
EF6 ......................................................................... 184, 201
EF7 ......................................................................... 184, 201
EF8 ......................................................................... 184, 201
EFAn ....................................................................... 183, 200
End................................................................................ 216
End1 .............................................................................. 211
End2 .............................................................................. 211
End3 .............................................................................. 211
End4 .............................................................................. 211
End5 .............................................................................. 211
End6 .............................................................................. 211
End7 .............................................................................. 212
Energy Savings Constants Error .............................................. 210
Enter Command................................................................. 122
Enter command necessary ............................................... 122, 315
Enter command not necessary .......................................... 122, 315
Enter Command Settings when Upgrading the Drive...................... 338
Enter Command Types......................................................... 338
Er-01.............................................................................. 212
Er-02.............................................................................. 212
Er-03.............................................................................. 212
Er-04.............................................................................. 212
Er-05.............................................................................. 212
Er-08.............................................................................. 213
Er-09.............................................................................. 213
Er-10.............................................................................. 213
Er-11.............................................................................. 213
Er-12.............................................................................. 213
Er-13.............................................................................. 214
Er-14.............................................................................. 214
Er-15.............................................................................. 214
Er-17.............................................................................. 214
Er-18.............................................................................. 214
Er-19.............................................................................. 214
Er-20.............................................................................. 214
Er-21.............................................................................. 215
Err................................................................................. 184
Error Reading Data ............................................................. 217
Errors and Displays When Using the Copy Function...................... 178

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

343

Index
Error Writing Data.............................................................. 216
Excessive Motor Oscillation and Erratic Rotation ......................... 224
Excessive PID Feedback................................................. 185, 201
Excessive Speed Deviation Detection Delay Time ..........................84
Excessive Speed Deviation Detection Level ..................................84
Excessive V/f Setting........................................................... 211
Exhaust Fan Application.........................................................15
External Digital Operator Connection Fault ................................ 192
External Fault ............................................................. 184, 200
External Fault from Comm. Option Detection Selection....................88
External Fault from Comm. Option Operation Selection ...................88

Frequency Reference Loss Detection Selection ...................... 107, 279


Frequency Reference Lower Limit .............................................60
Frequency Reference Monitor Content During PID .........................41
Frequency Reference Selection ............................................... 234
Frequency Reference Selection 1.........................................18, 221
Frequency Reference Selection 2...............................................24
Frequency Reference Setting / Decimal Display ........................... 286
Frequency Reference Setting and User-Set Display ....................... 286
Frequency Reference Setting Hierarchy .......................................58
Frequency Reference Setting Method Selection...................... 159, 287
Frequency Reference Source Selection ...................................... 297
Frequency Reference Upper Limit .............................................60
F
Function Code................................................................... 318
FAn ............................................................................... 184 Functions for Terminals S1 to S8...............................................93
FAn Alarm Location Monitor................................................. 298 Fuse is Open ..................................................................... 193
Fast Stop Sequence ...............................................................98
Fast Stop Time ....................................................................46 G
Fault Causes and Solutions .................................................... 180 Gate Drive Board Undervoltage .............................................. 196
Fault Detection .................................................................. 180 GF................................................................................. 185
Fault Displays ................................................................... 180 Ground Fault .................................................................... 185
Fault History............................................................... 166, 218
H
Fault Reset Interval Time................................................ 143, 280
Fault Reset Methods............................................................ 175 H1 Multi-Function Digital Input Selections................................. 263
Fault Reset Operation Selection ........................................ 144, 280 H3-02 ................................................................. 224, 225, 226
Fault Restart ..................................................................... 111 H3-10 ....................................................................... 225, 226
Faults ............................................................................. 175 H3-11 ............................................................................. 226
Fault SlaveLocation Monitor.................................................. 295 H3-13 ....................................................................... 173, 225
Fault Trace................................................................. 166, 218 H3 Multi-Function Analog Input Settings................................... 271
FbH ......................................................................... 185, 201 Hbb ............................................................................... 201
FbL ......................................................................... 185, 201 HbbF.............................................................................. 201
Field Forcing ......................................................................71 HCA .............................................................................. 202
Field Forcing Limit ...............................................................72 HD ..................................................................................57
Field Forcing Selection ..........................................................71 Heatsink Cooling Fan Off-Delay Time ...................................... 150
Field Weakening ..................................................................71 Heatsink Cooling Fan Operation Delay Time .............................. 282
Field Weakening Frequency Limit .............................................71 Heatsink Cooling Fan Operation Selection............................ 150, 282
Field Weakening Level ..........................................................71 Heatsink Overheat ........................................................ 189, 203
Fine-Tuning Open Loop Vector Control .................................... 172 Heatsink Temperature.......................................................... 296
Fine-Tuning V/f Control and V/f Control with PG ........................ 172 Heavy Duty ........................................................................57
FJOG/RJOG Operation ..........................................................97 High Current Alarm Selection ................................................ 152
Forward/Reverse Run Command Input Error............................... 200 High Slip Braking .............................................................. 155
Forward Regenerative Torque Limit ................................... 147, 281 High Slip Suppression Current Level ........................................ 156
Forward Torque Limit.................................................... 147, 281 High-Slip Suppression Current Level........................................ 285
Frequency Detection 1 Time Chart........................................... 106 HSB............................................................................... 155
Frequency Detection 2 Time Chart........................................... 106 Hunting Prevention ............................................................. 154
Frequency Detection 3 Example with a Positive L3-04 Value ........... 109 Hunting Prevention Gain ...................................................... 172
Frequency Detection 4 Example with Positive L3-04 Value ............. 110 Hunting Prevention Gain Setting ....................................... 154, 284
Frequency Reduction Rate during Overheat Pre-Alarm............. 149, 283 Hunting Prevention Gain while in Reverse ........................... 154, 284
Frequency Reference .......................................................58, 292 Hunting Prevention Selection ........................................... 154, 284
Frequency Reference at Previous Fault ...................................... 294 Hunting Prevention Time Constant .................................... 154, 284
Frequency Reference at Reference Loss............................... 142, 279 HVAC Fan Application ..........................................................15
Frequency Reference Bias .......................................................64 Hybrid IC Failure ............................................................... 182
Frequency Reference Bias (Up/Down 2) .................................... 300 I
Frequency Reference Bias Accel/Decel .......................................65 I Control............................................................................33
Frequency Reference Bias Lower Limit .......................................64 iFEr ............................................................................... 216
Frequency Reference Bias Operation Mode Selection ......................65 IGBT Maintenance ............................................................. 296
Frequency Reference Bias Step.................................................64 IGBT Maintenance Setting .............................................. 161, 287
Frequency Reference Bias Upper Limit .......................................64 IGBT Maintenance Time (50%) .............................................. 202
Frequency Reference from MEMOBUS/Modbus Comm. ................ 297 IGBT Maintenance Time (90%) ............................................. 205
Frequency Reference Hold ......................................................62 IGBT Short Circuit or Ground Fault ......................................... 194
Frequency Reference Hold Function Selection ...............................62 Induction Voltage Error........................................................ 214
344

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Index
Initialization .......................................................................10
Initialization Required ......................................................... 208
Initialize Parameters..............................................................11
Input Phase Loss ................................................................ 193
Input Phase Loss Protection Selection ................................. 149, 282
Input Pulse Monitor ............................................................ 294
Input Terminal Status .......................................................... 292
Input Terminal Status at Previous Fault ..................................... 295
Input Voltage Setting.............................................................73
Inrush Prevention Circuit Fault ............................................... 196
Inrush Prevention Relay Maintenance Setting .............................. 287
Integral Limit Setting.............................................................36
Integral Operation during Accel/Decel ........................................55
Integral Operation during Accel/Decel for Motor 2..........................56
Integral Time Setting (I) .........................................................36

J
Jog Frequency Reference ........................................................58
Jump Frequency.............................................................61, 173
Jump Frequency Width ..........................................................61

K
KEB Acceleration Time ................................................. 136, 277
KEB Detection Time ........................................................... 136
KEB Function Related Adjustments ......................................... 135
KEB Operation Using a KEB Input .......................................... 132
KEB Operation Using L2-02, Without KEB Input......................... 133
KEB Operation Using L2-02 and KEB Input ............................... 133
KEB Operation Using L2-10, Without KEB Input......................... 134
KEB Operation Using L2-10 and KEB Input ............................... 134
KEB Operation Wiring Example ............................................. 134
KEB Ride-Thru End Detection ............................................... 132
KEB Ride-Thru Function ...................................................... 101
KEB Ride-Thru Start ........................................................... 132
kWh............................................................................... 297
kWh, Lower 4 Digits ........................................................... 297
kWh, Upper 5 Digits ........................................................... 297
kWh Monitor Initialization .................................................... 162
kWh Monitor Initial Value Selection ........................................ 288

L
L3-01 through L3-06 ........................................................... 174
L3-02 ....................................................................... 224, 226
L3-04 ............................................................................. 224
L3-06 ............................................................................. 224
L3-11 ............................................................................. 174
L7-01 through L7-04 ..................................................... 174, 225
L7-06 ............................................................................. 174
L7-07 ............................................................................. 174
L8-38 ............................................................................. 226
Language Selection...............................................................10
Leakage Inductance Alarm .................................................... 211
Leakage Inductance Error ..................................................... 214
LED Check ...................................................................... 296
LF ................................................................................. 185
LF2 ............................................................................... 186
LF3 ............................................................................... 186
Line-to-Line Resistance Error................................................. 212
LO/RE (LOCAL/REMOTE) Key Function Selection .......................24
LOCAL/REMOTE Key Function Selection ................................ 286
LOCAL/REMOTE Run Selection..............................................24

Loopback Test................................................................... 320


Loss of Reference Function ................................................... 142
LT-1 .............................................................................. 202
LT-2 .............................................................................. 202
LT-3 .............................................................................. 202
LT-4 .............................................................................. 202

M
Magnetic Flux Compensation Value ...........................................27
Maintenance Monitors ......................................................... 166
Maintenance Monitor Settings ................................................ 161
Master Speed Reference Lower Limit .........................................61
Maximum Output Frequency....................................................75
Maximum Voltage................................................................75
MC/FAN power malfunction.................................................. 197
Mechanical Weakening Detection............................................ 111
Mechanical Weakening Detection 1 ................................... 191, 204
Mechanical Weakening Detection 2 ......................................... 195
Mechanical Weakening Detection Operation ......................... 146, 281
Mechanical Weakening Detection Speed Level ...................... 146, 281
Mechanical Weakening Detection Start Time ........................ 146, 281
Mechanical Weakening Detection Time............................... 146, 281
MECHATROLINK-II Parameters .............................................88
MEMOBUS/Modbus Comm. Test Mode Complete ....................... 205
MEMOBUS/Modbus Communication Error.......................... 180, 199
MEMOBUS/Modbus Communications Reference......................... 297
MEMOBUS/Modbus communication terminal and S2 DIP switch ..... 312
MEMOBUS/Modbus Communication Test Mode Error .................. 205
MEMOBUS/Modbus Data Table............................................. 322
MEMOBUS/Modbus Error Code ............................................ 293
MEMOBUS/Modbus Error Codes ........................................... 339
MEMOBUS/Modbus Setup Parameters ..................................... 313
MEMOBUS/Modbus Specifications ......................................... 309
Message Format................................................................. 318
MessageID (INV)............................................................... 294
MessageID (OPR) .............................................................. 294
Middle Output Frequency .......................................................75
Middle Output Frequency 2 .....................................................75
Middle Output Frequency Voltage .............................................75
Middle Output Frequency Voltage 2 ...........................................75
Mid Output Voltage A ......................................................... 172
Minimum KEB Time........................................................... 136
Minimum Output Frequency ....................................................75
Minimum Output Frequency Voltage..........................................75
Minimum Output Voltage ..................................................... 172
Minimum Wait Time for Sending Messages................................ 317
Minor Alarms ................................................................... 175
Minor Fault ...................................................................... 212
Minor Fault and Alarm Displays ............................................. 177
Minor Faults ..................................................................... 175
Minor Faults and Alarms ...................................................... 175
Model, Voltage Class, Capacity Mismatch.................................. 217
Momentary Power Loss Minimum Baseblock Time................. 135, 277
Momentary Power Loss Operation Selection ...........................30, 277
Momentary Power Loss Ride-Thru .......................................... 131
Momentary Power Loss Ride-Thru Time ............................. 135, 277
Momentary Power Loss Voltage Recovery Ramp Time ............ 136, 277
Monitor Parameters....................................................... 119, 292
Most Recent Fault .............................................................. 296
Motor 1/Motor 2 Selection .................................................... 163

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

345

Index
Motor 1 Parameters...............................................................76
Motor 2 ASR Gain Switching Frequency .....................................56
Motor 2 ASR Integral Limit.....................................................56
Motor 2 ASR Integral Time .....................................................56
Motor 2 ASR Limit...............................................................56
Motor 2 ASR Primary Delay Time Constant .................................56
Motor 2 ASR Proportional Gain ................................................56
Motor 2 Base Frequency.........................................................79
Motor 2 Base Voltage ............................................................79
Motor 2 Control Mode Selection ...............................................79
Motor 2 Iron Loss.................................................................81
Motor 2 Leakage Inductance ....................................................81
Motor 2 Line-to-Line Resistance ...............................................81
Motor 2 Max Output Frequency ................................................79
Motor 2 Max Voltage ............................................................79
Motor 2 Mechanical Loss........................................................81
Motor 2 Mid Output Frequency.................................................79
Motor 2 Mid Output Frequency 2 ..............................................79
Motor 2 Mid Output Frequency Voltage ......................................79
Motor 2 Mid Output Frequency Voltage 2 ....................................79
Motor 2 Minimum Output Frequency..........................................79
Motor 2 Minimum Output Frequency Voltage ...............................79
Motor 2 Motor Iron-Core Saturation Coefficient 1 ..........................81
Motor 2 Motor Iron-Core Saturation Coefficient 2 ..........................81
Motor 2 Motor Poles .............................................................81
Motor 2 Parameters...............................................................80
Motor 2 Rated Current ...........................................................80
Motor 2 Rated No-Load Current................................................80
Motor 2 Rated Power.............................................................82
Motor 2 Rated Slip ...............................................................80
Motor 2 Slip Compensation Gain...............................................49
Motor 2 Slip Compensation Limit..............................................50
Motor 2 Slip Compensation Primary Delay Time............................49
Motor 2 Slip Compensation Selection during Regeneration ................50
Motor 2 Torque Compensation Gain...........................................51
Motor Base Frequency ................................................... 164, 290
Motor Base Speed ........................................................ 164, 290
Motor Data Error................................................................ 212
Motor d-Axis Current at Previous Fault ..................................... 295
Motor Direction at Power Up when Using Operator................. 160, 287
Motor Direction Error .......................................................... 213
Motor Does Not Rotate ........................................................ 221
Motor Excitation Current (ld) ................................................. 299
Motor Hunting and Oscillation Control Parameters ....................... 173
Motor Iron-Core Saturation Coefficient ..................................... 211
Motor Iron-Core Saturation Coefficient 1 .....................................77
Motor Iron-Core Saturation Coefficient 2 .....................................77
Motor Iron Loss ........................................................... 165, 291
Motor Iron Loss for Torque Compensation ...................................78
Motor is Too Hot ............................................................... 222
Motor Leakage Inductance ......................................................77
Motor Line-to-Line Resistance .................................................77
Motor Mechanical Loss ..........................................................77
Motor No-Load Current....................................................76, 164
Motor Overheat ................................................................. 203
Motor Overheat (NTC Input) ........................................... 190, 203
Motor Overheat Alarm (PTC Input).......................................... 189
Motor Overheat Alarm Operation Selection .......................... 128, 276
Motor Overheat Fault (PTC Input) ........................................... 190
Motor Overheat Fault Operation Selection............................ 128, 276
346

Motor Overload ................................................................. 190


Motor Overload Estimate (oL1) .............................................. 297
Motor Overload Protection Selection .................................. 111, 276
Motor Overload Protection Time ....................................... 127, 276
Motor Parameters .................................................................73
Motor Performance Fine-Tuning ............................................. 172
Motor Produces Insufficient Torque ......................................... 226
Motor Protection ................................................................ 125
Motor Protection Using a Positive Temperature Coefficient Thermistor
..................................................................................... 118
Motor PTC Characteristics .................................................... 128
Motor q-Axis Current at Previous Fault ..................................... 295
Motor Rated Current .................................................76, 164, 290
Motor Rated Power ...................................................78, 163, 290
Motor Rated Slip............................................................76, 164
Motor Rated Voltage ..................................................... 163, 290
Motor Rotates After the Drive Output is Shut Off ......................... 226
Motor Rotates Faster Than the Frequency Reference...................... 224
Motor Rotates in One Direction Only........................................ 222
Motor Secondary Current (Iq) ................................................ 299
Motor Selection ...................................................................98
Motor Selection 1/2............................................................. 290
Motor Speed ..................................................................... 292
Motor Speed at Previous Fault ................................................ 294
Motor Speed Error 2............................................................ 214
Motor Speed Fault .............................................................. 213
Motor Stalls During Acceleration or With Large Loads .................. 223
Motor Switch during Run...................................................... 205
Motor Temperature (NTC ..................................................... 298
Motor Temperature Input Filter Time.................................. 128, 276
Multi-Function Analog Inputs ..................................................67
Multi-Function Analog Input Selection Error............................... 208
Multi-Function Analog Input Terminal Settings ........................... 113
Multi-Function Analog Outputs ................................................52
Multi-Function Analog Output Terminal AM Bias ........................ 119
Multi-Function Analog Output Terminal AM Gain........................ 119
Multi-Function Analog Output Terminal AM Monitor Selection........ 119
Multi-Function Analog Output Terminal AM Signal Level Selection
..................................................................................... 120
Multi-Function Analog Output Terminal FM Bias......................... 119
Multi-Function Analog Output Terminal FM Gain ........................ 119
Multi-Function Analog Output Terminal FM Monitor Selection ........ 119
Multi-Function Analog Output Terminal FM Signal Level Selection
..................................................................................... 120
Multi-Function Digital Inputs ...................................................93
Multi-Function Digital Input Terminal Settings ..............................93
Multi-Function Digital Outputs ............................................... 103
Multi-Function Digital Output Terminal Settings .......................... 103
Multi-Function Input Selection Error ........................................ 207
Multi-Step Speed Selection......................................................19

N
n1-02.............................................................................. 172
n2-01.............................................................................. 172
n2-02.............................................................................. 172
n2-03.............................................................................. 173
ND ..................................................................................57
ndAT.............................................................................. 217
NetRef/ComRef Function Selection............................................89
Network Termination .......................................................... 310

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Index
Noise From the Drive or Motor Cables When the Drive is Powered On
..................................................................................... 225
No-Load Current Alarm ....................................................... 212
No-Load Current Error......................................................... 212
Normal Duty.......................................................................57
nSE ............................................................................... 186
Number of Auto Restart Attempts...................................... 143, 280
Number of Motor Poles ..............................................77, 164, 290
Number of Run Commands ................................................... 296
Number of Run Commands Counter Initialization......................... 162
Number of Speed Search Restarts ..............................................32

O
o2-01.............................................................................. 221
oC ................................................................................. 186
oFA00 ............................................................................ 187
oFA01 ............................................................................ 187
oFA03 to oFA06 ................................................................ 187
oFA10 ............................................................................ 187
oFA11 ............................................................................ 187
oFA12 to oFA17 ................................................................ 187
oFA30 to oFA43 ................................................................ 187
oFb00 ............................................................................. 188
oFb01 ............................................................................. 188
oFb02 ............................................................................. 188
oFb03 to oFb11 ................................................................. 188
oFb12 to oFb17 ................................................................. 188
oFC00 ............................................................................ 188
oFC01 ............................................................................ 188
oFC02 ............................................................................ 188
oFC03 to oFC11 ................................................................ 189
oFC12 to oFC17 ................................................................ 189
Offset Frequency............................................................72, 300
oH ........................................................................... 189, 203
oH1 ............................................................................... 189
oH2 ............................................................................... 203
oH3 ......................................................................... 189, 203
oH4 ............................................................................... 190
oH5 ......................................................................... 190, 203
oH6 ............................................................................... 190
oH Alarm Location Monitor .................................................. 298
oL1................................................................................ 190
oL2.......................................................................... 191, 226
oL2 Characteristics Selection at Low Speeds......................... 151, 282
oL3.......................................................................... 191, 204
oL4.......................................................................... 191, 204
oL5.......................................................................... 191, 204
oPE ............................................................................... 207
oPE01 ............................................................................ 207
oPE02 ............................................................................ 207
oPE03 ............................................................................ 207
oPE04 ............................................................................ 208
oPE05 ............................................................................ 208
oPE06 ............................................................................ 208
oPE07 ............................................................................ 208
oPE08 ............................................................................ 209
oPE09 ............................................................................ 209
oPE10 ............................................................................ 209
oPE13 ............................................................................ 210
oPE15 ............................................................................ 210

oPE16 ............................................................................ 210


oPE18 ............................................................................ 210
oPE Fault Parameter............................................................ 293
Open Loop Vector Control ........................................ 173, 224, 226
Open Loop Vector Control Mode Tuning ................................... 172
Open Loop Vector Control Mode Tuning Parameters ..................... 172
Operation Errors .......................................................... 175, 178
Operation Selection at Deviation (dEv)........................................84
Operation Selection at Overspeed (oS) ........................................83
Operation Selection at PG Open Circuit (PGo)...............................83
Operation Selection when Digital Operator is Disconnected ....... 160, 287
Operation Status Monitors..................................................... 166
Operator Programming Errors ................................................ 207
Operator Related Settings...................................................... 157
oPr ................................................................................ 192
Option card connection error (CN5-A) ...................................... 187
Option Card Connection Error at Option Port CN5-A..................... 187
Option Card Connection Error at Option Port CN5-C..................... 188
Option card error occurred at option port CN5-A .......................... 187
Option card error occurred at option port CN5-B .......................... 188
Option card error occurred at option port CN5-C .......................... 189
Option Card External Fault.............................................. 183, 200
Option Card Fault at Option Port CN5-A ................................... 187
Option Card Fault at Option Port CN5-B.................................... 188
Option Card Fault at Option Port CN5-C.................................... 188
Option Communication Error ........................................... 180, 198
Option Frequency Reference .................................................. 297
Option Settings....................................................................83
oS ........................................................................... 192, 204
Oscillation or Hunting.......................................................... 225
Output Current .................................................................. 292
Output Current 1 During Speed Search........................................31
Output Current at Previous Fault ............................................. 294
Output Current Imbalance ..................................................... 186
Output Frequency............................................................... 292
Output Frequency after Soft Start ............................................ 293
Output Frequency at Previous Fault.......................................... 294
Output Frequency is not as High as Frequency Reference ................ 226
Output Frequency Reduction During Overheat Alarm .................... 149
Output Ground Fault Detection Selection ............................. 150, 282
Output of speed control (ASR) (for Simple V/f PG)....................... 299
Output Phase Loss .............................................................. 185
Output Phase Loss Protection ................................................. 282
Output Phase Loss Protection Selection ..................................... 150
Output Power.................................................................... 292
Output Power at Previous Fault............................................... 295
Output Terminal Status ........................................................ 293
Output Terminal Status at Previous Fault ................................... 295
Output Voltage at Previous Fault ............................................. 294
Output Voltage Detection Fault......................................... 197, 206
Output Voltage Limit Operation Selection ....................................49
Output Voltage Reference ..................................................... 292
Output Voltage Reference (Vd)............................................... 299
Output Voltage Reference (Vq)............................................... 299
ov............................................................................ 192, 204
OV Alarm Location Monitor.................................................. 298
Overcurrent ...................................................................... 186
Overexcitation Deceleration................................................... 140
Overexcitation Deceleration Gain ...................................... 156, 284
Overexcitation Operation Selection .................................... 156, 285

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

347

Index
Overheat 1 (Heatsink Overheat) .............................................. 189
Overheat Alarm Level.................................................... 111, 282
Overheat Pre-Alarm Operation Selection ............................. 112, 282
Overspeed (for Control Mode with PG) ............................... 192, 204
Overspeed Detection Delay Time ..............................................83
Overspeed Detection Level......................................................83
Overtorque 1..................................................................... 204
Overtorque 2..................................................................... 204
Overtorque Detection 1 ........................................................ 191
Overtorque Detection 2 ........................................................ 191
Overtorque Detection Operation.............................................. 144
Overvoltage...................................................................... 192
Overvoltage Suppression Function ........................................... 141
Overvoltage Suppression Function Selection ............................... 141
ov Suppression Function Selection........................................... 278

P
Parameter Range Setting Error................................................ 207
Parameter Selection Error ..................................................... 209
Parameters for KEB Ride-Thru ............................................... 135
Parameters to Minimize Motor Hunting and Oscillation .................. 173
PASS ............................................................................. 205
Password ...........................................................................11
Password Setting..................................................................11
P Control ...........................................................................33
Peak Hold Current .............................................................. 297
Peak Hold Output Frequency ................................................. 297
PF ................................................................................. 193
PG 1 Division Rate for PG Pulse Monitor ....................................84
PG 1 Gear Teeth 1 ................................................................85
PG 1 Gear Teeth 2 ................................................................85
PG 1 Pulses Per Revolution .....................................................83
PG 1 Rotation Selection .........................................................84
PG 1 Signal Selection ............................................................85
PG 2 Division Rate for PG Pulse Monitor ....................................84
PG 2 Gear Teeth 1 ................................................................85
PG 2 Gear Teeth 2 ................................................................85
PG 2 Pulses Per Revolution .....................................................83
PG 2 Rotation Selection .........................................................84
PG 2 Signal Selection ............................................................85
PG-B3 Settings....................................................................83
PG Disconnect (for any control modes using a PG option card) ......... 193
PG Disconnect (for Control Mode with PG) ................................ 205
PG Hardware Fault (detected when using a PG-X3 option card) ... 193,
205
PG Number of Pulses Per Revolution........................................ 164
PGo ......................................................................... 193, 205
PGoH ....................................................................... 193, 205
PG Open-Circuit Detection Time...............................................83
PG Option Card Disconnection Detection 1 ..................................85
PG Option Card Disconnection Detection 2 ..................................85
PG Option Card Port for Motor 2 Selection...................................85
PG Speed Control Card Settings................................................83
PG-X3 Settings....................................................................83
Phase Order Selection ............................................................24
PID Accel/Decel Time ...........................................................39
PID Block Diagram...............................................................35
PID Control........................................................................33
PID Feedback ................................................................... 299
PID Feedback High Detection Level...........................................39
348

PID Feedback High Detection Time ...........................................39


PID Feedback Input Methods ...................................................34
PID Feedback Loss ....................................................... 185, 201
PID Feedback Loss Detection Selection.......................................38
PID Feedback Low Detection Level ...........................................38
PID Feedback Low Detection Time............................................38
PID Fine Tuning ..................................................................41
PID Function Setting .............................................................36
PID Input (feedback) ........................................................... 299
PID Input Limit ...................................................................40
PID Monitors .................................................................... 166
PID Offset Adjustment...........................................................36
PID Output....................................................................... 299
PID Output Fault................................................................ 226
PID Output Gain Setting.........................................................37
PID Output Level Selection .....................................................37
PID Output Limit .................................................................36
PID Output Lower Limit.........................................................40
PID Output Reverse Selection ..................................................37
PID Primary Delay Time Constant .............................................37
PID Setpoint ..................................................................... 299
PID Setpoint Display Digits.....................................................41
PID Setpoint Input Methods.....................................................33
PID Setpoint Scaling .............................................................40
PID Setpoint Selection ...........................................................40
PID Setpoint User Display ......................................................41
PID Setpoint Value ...............................................................40
PID Sleep ..........................................................................39
PID Sleep Delay Time ...........................................................39
PID Sleep Function Start Level .................................................39
PM Inductance Error ........................................................... 214
Power Unit Output Phase Loss 3 ............................................. 186
Predefined V/f Patterns ..........................................................74
Preset Reference Timing Diagram .............................................60
Previous Fault ................................................................... 294
PROFIBUS-DP Clear Mode Selection ........................................90
PROFIBUS-DP Data Format Selection........................................90
PROFIBUS-DP Node Address .................................................90
PROFIBUS-DP Parameters ................................................ 88, 90
Proportional Gain Setting (P) ...................................................36
PTC ............................................................................... 118
PUF ............................................................................... 193
Pulse Monitor Selection Error ................................................ 210
Pulse Train Input/Output....................................................... 103
Pulse Train Input Bias.......................................................... 124
Pulse Train Input Filter Time ................................................. 124
Pulse Train Input Gain ......................................................... 124
Pulse Train Input Minimum Frequency...................................... 124
Pulse Train Input Scaling ...................................................... 124
Pulse Train Input Terminal RP Function Selection ........................ 123
Pulse Train Monitor Scaling .................................................. 124
Pulse Train Monitor Selection ................................................ 124

Q
q-axis ACR Output ............................................................. 299

R
Ramp to stop ......................................................................20
Rated Current Setting Alarm .................................................. 211
Rated Slip Error ................................................................. 213

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Index
rdEr ............................................................................... 217
READ ............................................................................ 160
rEAd .............................................................................. 217
Reading Drive MEMOBUS/Modbus Register Contents .................. 320
Reading Parameter Settings ................................................... 217
Regenerative Torque Limit mode selection ................................. 282
Reset Communication Parameters..............................................89
Resistance Tuning Error ....................................................... 211
Response Messages from Drive to Master .................................. 317
Reverse Direction Output Example Time Chart............................ 110
Reverse Operation Selection ....................................................22
Reverse Prohibited Error....................................................... 214
Reverse Regenerative Torque Limit ................................... 147, 281
Reverse Torque Limit .................................................... 147, 281
rF .................................................................................. 194
rH ................................................................................. 194
rr................................................................................... 194
RS-422 Interface ................................................................ 311
RS-485 Interface ................................................................ 311
RTS Control Selection ................................................... 121, 314
rUn ................................................................................ 205
Run Command/Frequency Reference Source Selection Error............ 208
Run Command at Power Up.....................................................25
Run Command Method Selection ...................................... 122, 315
Run Command Selection ...................................................... 221
Run Command Selection 1 ................................................19, 234
Run Command Selection 2 ......................................................25
Run command selection while in Programming Mode ......................24
Run Command Source Selection ............................................. 297

S
Safe Disable Signal Input...................................................... 201
SC ................................................................................. 194
S-Curve Characteristics ....................................................47, 173
SE ................................................................................. 205
Self-diagnosing function of the serial communication interface circuits
..................................................................................... 340
SEr ................................................................................ 194
Serial Communications Cable Connection Terminals (TB4) ............. 310
Serial Communication Transmission Error ................................. 199
Single Drive KEB Ride-Thru 1 ............................................... 132
Slave Address ................................................................... 318
Slip Compensation................................................................47
Slip Compensation Gain ...................................................47, 173
Slip Compensation Limit ........................................................48
Slip Compensation Primary Delay Time ................................48, 173
Slip Compensation Selection during Regeneration ..........................48
Soft Charge Bypass Relay Maintenance..................................... 296
Soft Charge Bypass Relay Maintenance Time.............................. 202
Soft CLA Selection ............................................................. 282
Soft Starter Speed Reference at Previous Fault............................. 295
Software Current Limit Selection ............................................ 151
Software No. (PWM)........................................................... 294
Software No. of Master CPU (Flash) ........................................ 294
Software No. of Slave CPU (ROM).......................................... 294
Sound from Motor .............................................................. 226
Speed/Torque Control Switchover Time ......................................71
Speed Agree 1 Time Chart .................................................... 105
Speed Agree 2 Time Chart .................................................... 108
Speed Agreement Detection Level ..................................... 141, 279

Speed Agreement Detection Level (+/-) ............................... 142, 279


Speed Agreement Detection Selection....................................... 142
Speed Agreement Detection Width .................................... 141, 279
Speed Agreement Detection Width (+/-) .............................. 142, 279
Speed Control Integral Time 1 ................................................ 204
Speed Control Proportional Gain 1........................................... 204
Speed Deviation (for Control Mode with PG) .............................. 182
Speed Deviation (when using a PG option card) ........................... 199
Speed Estimation Type Speed Search..........................................28
Speed Feedback Detection Contol (AFR) Tuning.......................... 154
Speed Feedback Detection Control (AFR) Gain ..................... 154, 284
Speed Feedback Detection Control (AFR) Time Constant 1 ....... 155, 284
Speed Feedback Detection Control (AFR) Time Constant 2 ....... 155, 284
Speed Limit........................................................................70
Speed Limitation..................................................................68
Speed Limit Bias............................................................. 68, 70
Speed Limit Selection ............................................................70
Speed Search ......................................................................20
Speed Search Deactivation Current ............................................30
Speed Search Deceleration Time ...............................................30
Speed Search Delay Time .......................................................31
Speed Search Detection Compensation Gain .................................31
Speed Search Method Selection ................................................32
Speed Search Restart Current Level............................................31
Speed Search Restart Detection Time..........................................32
Speed Search Selection at Start .................................................30
Speed Search Wait Time.........................................................32
Stall Prevention ........................................................... 137, 174
Stall Prevention Detection Time.............................................. 141
Stall Prevention Level during Acceleration ........................... 138, 278
Stall Prevention Level during Run ..................................... 140, 278
Stall Prevention Limit during Acceleration ........................... 137, 278
Stall Prevention Selection during Acceleration....................... 137, 278
Stall Prevention Selection during Deceleration....................... 139, 278
Stall Prevention Selection during Run ................................. 140, 278
Stator Resistance Error......................................................... 214
STOP button Input.............................................................. 212
STOP Key Function Selection .......................................... 159, 286
Stopping Method after Communication Error ........................ 121, 313
Stopping Method Selection......................................................20
SvE ............................................................................... 195
Switching Between Torque and Speed Control...............................69

T
Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention
..................................................................................... 141
Task Complete .................................................................. 216
Terminal A1 Bias Setting...................................................... 114
Terminal A1 Function Selection.............................................. 113
Terminal A1 Gain Setting ..................................................... 114
Terminal A1 Signal Level Selection ......................................... 113
Terminal A2 Bias Setting...................................................... 115
Terminal A2 Function Selection.............................................. 115
Terminal A2 Gain Setting ..................................................... 115
Terminal A2 Signal Level Selection ......................................... 115
Terminal A3 Bias Setting...................................................... 115
Terminal A3 Function Selection.............................................. 115
Terminal A3 Gain Setting ..................................................... 115
Terminal A3 Signal Level Selection ......................................... 114
Terminal Board Connection Error............................................ 181

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

349

Index
Terminal Connections for Communication Self-Diagnostics............. 340
Terminal M1-M2 Function Selection ........................................ 103
Terminal M1-M2 Output Selection ............................................87
Terminal M3-M4 Output Selection ............................................88
Terminal P1-PC Output Selection ..............................................87
Terminal P2-PC Output Selection ..............................................87
Terminal P3-PC Output Selection ..............................................87
Terminal P4-PC Output Selection ..............................................87
Terminal P5-PC Output Selection ..............................................87
Terminal P6-PC Output Selection ..............................................87
Terminal V1 Monitor Bias ......................................................87
Terminal V1 Monitor Gain ......................................................87
Terminal V1 Monitor Selection.................................................87
Terminal V1 Signal Level .......................................................87
Terminal V2 Monitor Bias ......................................................87
Terminal V2 Monitor Gain ......................................................87
Terminal V2 Monitor Selection.................................................87
Terminal V2 Signal Level .......................................................87
Thermistor Disconnect ................................................... 195, 205
THo ......................................................................... 195, 205
Timer Function Off-Delay Time................................................32
Timer Function On-Delay Time ................................................32
Too Many Speed Search Restarts............................................. 194
Torque Compensation............................................................50
Torque Compensation at Forward Start........................................51
Torque Compensation at Reverse Start ........................................51
Torque Compensation Gain ...............................................50, 172
Torque Compensation Primary Delay Time ............................51, 172
Torque Compensation Primary Delay Time 2 ................................51
Torque Compensation Primary Delay Time Constant 1................... 173
Torque Compensation Primary Delay Time Constant 2................... 173
Torque Compensation Time Constant .........................................51
Torque Control ....................................................................66
Torque Control Block Diagram.................................................67
Torque Control Input Value Selection .........................................67
Torque Control Reference Sources.............................................67
Torque Control Selection ........................................................70
Torque Control Setting Error.................................................. 210
Torque Control Signal Polarity .................................................68
Torque Detection ............................................................... 107
Torque Detection Level 1................................................ 145, 280
Torque Detection Level 2................................................ 145, 280
Torque Detection Selection 1 ........................................... 145, 280
Torque Detection Selection 2 ........................................... 145, 280
Torque Detection Time 1 ................................................ 145, 280
Torque Detection Time 2 ................................................ 145, 280
Torque Limit .................................................................... 118
Torque Limit Control Method Selection during Accel/Decel ...... 147, 281
Torque Limit Enable Time delay at start .................................... 282
Torque Limit Integral Time Constant .................................. 147, 281
Torque Limits ................................................................... 174
Torque Reference ............................................................... 292
Torque Reference / Torque Limit Selection from Comm. Option .........89
Torque Reference at Previous Fault .......................................... 295
Torque Reference Delay Time ..................................................70
Torque Saturation Error........................................................ 214
Troubleshooting without Fault Display...................................... 220
TrPC .............................................................................. 205
Tuning Errors.................................................................... 175
Types of Alarms, Faults, and Errors ......................................... 175
350

U
U1-01 ....................................................................... 221, 223
U1-07 ............................................................................. 221
U1-09 ............................................................................. 221
U2, U3 Initialization............................................................ 162
U2, U3 Initial Value Selection ................................................ 287
U2-02 ............................................................................. 218
U2-03 through U2-17 .......................................................... 218
U4-05 ............................................................................. 206
UL3 ......................................................................... 195, 206
UL4 ......................................................................... 195, 206
UL5 ............................................................................... 195
UnbC ............................................................................. 195
UnbC Current Max Location Monitor ....................................... 298
Undertorque Detection 1................................................. 195, 206
Undertorque Detection 2................................................. 195, 206
Undertorque Detection Operation ............................................ 144
Undervoltage .................................................................... 206
Undervoltage 3 .................................................................. 196
Undervoltage 3 (Soft-Charge Bypass Circuit Fault) ....................... 196
Undervoltage Detection Level (Uv1) .................................. 136, 277
Unexpected Noise from Connected Machinery............................. 225
Unidirectional Speed Limit Bias................................................71
Unit Code ........................................................................ 159
Unit Selection for MEMOBUS/Modbus Register 0025H........... 122, 314
Up/Down 2 Function .............................................................62
Up/Down 2 Operations......................................................... 102
Up/Down Command Operation.................................................97
Up/Down Frequency Reference Limit Selection .............................66
User Monitor Selection after Power Up ............................... 157, 286
User Parameter Automatic Selection.....................................17, 233
User Parameter Default Value .......................................... 159, 286
User Parameters 1 to 32....................................................17, 233
User-Set Display Units Decimal Display.................................... 158
User-Set Display Units Maximum Value.................................... 158
User Set Speed Agree 1 Time Chart ......................................... 105
User Set Speed Agree 2 Example with a Positive L3-04 Value .......... 109
Uv ................................................................................. 206
Uv1 ............................................................................... 196
Uv2 ............................................................................... 196
Uv3 ............................................................................... 196
Uv4 ............................................................................... 196
Uv5 ............................................................................... 197
UV Alarm Location Monitor.................................................. 298

V
V/f Control Mode Tuning ..................................................... 172
V/f Control Mode Tuning Parameters ....................................... 172
V/f Control with Simple Speed Feedback ................................... 123
V/f Data Setting Error.......................................................... 209
V/f Gain During Speed Search..................................................31
V/f Pattern Defaults ............................................................ 303
V/f Pattern Display Unit ....................................................... 158
V/f Pattern for Motor 1...........................................................73
V/f Pattern for Motor 2...........................................................79
V/f Pattern Selection .......................................................73, 223
vAEr .............................................................................. 217
VERIFY.......................................................................... 160
vFyE .............................................................................. 217
voF .......................................................................... 197, 206

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

Index
voF Alarm Location Monitor ................................................. 298
Voltage Class, Capacity Mismatch .......................................... 217
vrFy ............................................................................... 217

W
Water Supply Pump Application ...............................................14
Watt Hour Output Example ................................................... 113
Watt Hour Output Unit Selection............................................. 112
Wiring Diagram for 2-Wire Sequence ....................................... 100
WRITE ........................................................................... 160
Writing Parameter Settings .................................................... 216
Writing to Multiple Registers ................................................. 320

Z
Zero Servo .........................................................................43
Zero Servo Completion Width ..................................................44
Zero Servo Fault ................................................................ 195
Zero Servo Gain...................................................................44
Zero-Speed Time Chart ........................................................ 105
Z Pulse Correction Error....................................................... 215
Z Pulse Fault .................................................................... 183
Z Pulse Noise Fault Detection ................................................ 183

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

351

Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.

352

Date of Publication

Revision
Number

Section

June 2011

Revised Content
First Edition. This manual supports A1000 HHP drive software
version VSL901012.

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

This Page Intentionally Blank

YASKAWA ELECTRIC SIEP YEAHHP 01 YASKAWA AC Drive A1000 HHP Programming Manual

353

YASKAWA AC Drive-A1000 HHP

High Performance, Large Capacity Vector Control Drive

Programming Manual
YASKAWA AMERICA, INC.

2121 Norman Drive South, Waukegan, IL 60085, U.S.A.


Phone: (800) YASKAWA (927-5292) or 1-847-887-7000 Fax: 1-847-887-7310
http://www.yaskawa.com

DRIVE CENTER (INVERTER PLANT)

2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan


Phone: 81-930-25-3844 Fax: 81-930-25-4369
http://www.yaskawa.co.jp

YASKAWA ELECTRIC CORPORATION

New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan
Phone: 81-3-5402-4502 Fax: 81-3-5402-4580
http://www.yaskawa.co.jp

YASKAWA ELTRICO DO BRASIL LTDA.

Avenda Fagundes Filho, 620 Bairro Saude, So Paulo, SP04304-000, Brasil


Phone: 55-11-3585-1100 Fax: 55-11-5581-8795
http://www.yaskawa.com.br

YASKAWA EUROPE GmbH

Hauptstrasse 185, 65760 Eschborn, Germany


Phone: 49-6196-569-300 Fax: 49-6196-569-398
http://www.yaskawa.eu.com

YASKAWA ELECTRIC UK LTD.

1 Hunt Hill Orchardton Woods, Cumbernauld, G68 9LF, United Kingdom


Phone: 44-1236-735000 Fax: 44-1236-458182
http://www.yaskawa.co.uk

YASKAWA ELECTRIC KOREA CORPORATION

7F, Doore Bldg. 24, Yeoido-dong, Yeoungdungpo-gu, Seoul, 150-877, Korea


Phone: 82-2-784-7844 Fax: 82-2-784-8495
http://www.yaskawa.co.kr

YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.

151 Lorong Chuan, #04-01, New Tech Park, 556741, Singapore


Phone: 65-6282-3003 Fax: 65-6289-3003
http://www.yaskawa.com.sg

YASKAWA ELECTRIC (SHANGHAI) CO., LTD.

No. 18 Xizang Zhong Road, 17F, Harbour Ring Plaza, Shanghai, 200001, China
Phone: 86-21-5385-2200 Fax: 86-21-5385-3299
http://www.yaskawa.com.cn

YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE


Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086 Fax: 86-10-8518-4082

YASKAWA ELECTRIC TAIWAN CORPORATION


9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003 Fax: 886-2-2505-1280

YASKAWA AMERICA, INC.

In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
2011 YASKAWA AMERICA, INC. All rights reserved.

MANUAL NO. SIEP YEAHHP 01


Published in U.S.A. June 2011 11-06 0 -0

You might also like