Apostila - Rainwater Catchment Systems
Apostila - Rainwater Catchment Systems
Apostila - Rainwater Catchment Systems
Catchment Systems
First Public Review (December 2012)
This draft has been recommended for public review by the ASPE Main Design Standards
Committee. To submit a comment on this proposed standard, go to the ASPE website at
aspe.org/PublicReview to access the comment form.
2012 American Rainwater Catchment System Association and American Society of Plumbing Engineers. All Rights
Reserved. Permission to reproduce or redistribute all or any part of this document must be obtained from the ASPE
Director of Standards at gpienta@aspe.org.
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Forward
(Informative)
This Rainwater Catchment Design and Installation Standard (hereinafter referred to as the
Standard) has been developed by a joint effort of the American Rainwater Catchment Systems
Association (ARCSA) and the American Society of Plumbing Engineers (ASPE), with
sponsorship support from the International Association of Plumbing and Mechanical Officials.
The purpose of this Standard is to assist engineers, designers, plumbers, builders/developers,
local government, and end users in safely implementing a rainwater catchment system. This
Standard is intended to apply to new rainwater catchment installations, as well as alterations,
additions, maintenance, and repairs to existing installations.
This Standard is intended to be consistent with, and complimentary to, nationally adopted codes
and regulations. However, designers/installers are advised to consult with the plumbing
authority having jurisdiction regarding local conditions, requirements, and restrictions.
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
The Standard
(Normative)
1.0
SCOPE
The scope of this Standard covers rainwater catchment systems that utilize the principle of
collecting and using precipitation from a rooftop and other hard, impervious surfaces. This
Standard does not apply to the collection of rainwater from vehicular parking or other similar
surfaces.
1.1
PERFORMANCE OBJECTIVES
1.1.1
1.2
a.
b.
Reduction of risk to the public from injury or loss of amenity due to a failure of
the supply, installation, maintenance, or operation of the rainwater catchment
system.
c.
The rainwater catchment system will assist in maintaining and enhancing the
quality of the environment while helping to ensure compliance with the intent of
relevant regulations and government officials.
UNITS OF MEASUREMENT
1.2.1
2.0
The objectives of this Standard are to provide guidance in how to provide and maintain a
healthy alternative to utility-provided water, and to optimize rainwater utilization, while
ensuring:
Values are stated in metric or the International System of Units (SI) with U.S. Customary
Units being referenced parenthetically. The SI units shall be considered as the standard.
REFERENCED STANDARDS
The standards referenced in this section are considered normative either by direct reference in this
Standard or through a general reference of this Section in the Standard:1
2.1
2.2
American Public Health Association, American Water Works Association, Water Environment
Federation
Standard Methods for the Examination of Water and Wastewater, 22nd Edition
1 Additional standard and guidance document references have been provided in Annex A for informational
purposes.
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
2.3
ASTM International
ASTM B32-08: Standard Specification for Solder Metal
ASTM B75/B75M-11: Standard Specifications for Seamless Copper Tube
ASTM B828-02 (2010): Standard Practice for Making Capillary Joints by Soldering of Copper
and Copper Alloy Tube and Fittings
ASTM D1785-12: Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe, Schedules
40, 80, and 120
ASTM D2241-09: Standard Specification for Poly(Vinyl Chloride) (PVC) Pressure Rated Pipe
(SDR Series)
ASTM D2466-06: Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings,
Schedule 40
ASTM D2467-06: Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings,
Schedule 80
ASTM D2657-07: Standard Practice for Heat Fusion Joining of Polyolefin Pipe and Fittings
ASTM D2661-11: Standard Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule
40 Plastic Drain, Waste, and Vent Pipe and Fittings
ASTM D2665-12: Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste,
and Vent Pipe and Fittings
ASTM D2855-96 (2010): Standard Practice for Making Solvent-Cemented Joints with
Poly(Vinyl Chloride) (PVC) Pipe and Fittings
ASTM D2949-10: Standard Specification for 3.25-in. Outside Diameter Poly(Vinyl Chloride)
(PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
ASTM D3261-10a: Standard Specification for Butt Heat Fusion Polyethylene (PE) Plastic
Fittings for Polyethylene (PE) Plastic Pipe and Tubing
ASTM D3311-11: Standard Specification for Drain, Waste, and Vent (DWV) Plastic Fittings
Patterns
ASTM D3350-12: Standard Specification for Polyethylene Plastics Pipe and Fittings Materials
ASTM F628-08: Standard Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40
Plastic Drain, Waste, and Vent Pipe With a Cellular Core
ASTM F714-12e1: Standard Specification for Polyethylene (PE) Plastic Pipe (DR-PR) Based on
Outside Diameter
ASTM F1866-07: Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Schedule 40
Drainage and DWV Fabricated Fittings
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
ASTM F1901-10: Standard Specification for Polyethylene (PE) Pipe and Fittings for Roof Drain
Systems
2.4
2.5
2.6
2.7
NSF International
NSF Protocol P151: Health Effects from Rainwater Catchment System Components
NSF/ANSI Standard 14-2011: Plastic Piping System Components and Related Materials
NSF/ANSI Standard 42-2010: Drinking Water Treatment Units -- Aesthetic Effects
NSF/ANSI Standard 53-2010: Drinking Water Treatment Units -- Health Effects
NSF/ANSI Standard 55-2009: Ultraviolet Microbiological Water Treatment Systems
NSF/ANSI Standard 58-2009: Reverse Osmosis Drinking Water Treatment Systems
NSF/ANSI Standard 60-2011: Drinking Water Treatment Chemicals -- Health Effects
NSF/ANSI Standard 61-2011: Drinking Water System Components -- Health Effects
2.8
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
3.0
3.1
Collection Parameters
3.1.1
3.1.2
3.2
a.
b.
All tank interior surfaces and equipment shall be washed clean before they are
put into service.
c.
For water storage volumes totaling less than 1,363 liters (360 gallons), or
intended for minor utility, irrigation, and garden use, no treatment is required.
d.
Water level control devices that control pumps, makeup water valves, etc., in
contact with the water supply shall be mercury-free devices.
e.
b.
Conveyance System
3.2.1
3.3
All piping and plumbing system materials and components used in the installation of a
rainwater catchment system shall comply with the applicable referenced standards
specified in Section 2 and be approved for the specific use per local plumbing code, or
be listed by an accredited certification body as available.
The roof drainage system or gutters and downspouts used to collect rainwater shall
comply with the following:
a.
b.
Gutter and downspout systems leading to the cistern shall be fitted with a debris
excluder or equivalent device.
Pre-filtration
3.3.1
All collected rainwater shall pass through a pre-filtration system before the rainwater
enters the cistern(s).
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
a.
The inlet to the pre-filter shall be provided with a debris screen that protects the
cistern from the intrusion of debris, vectors, and vermin. The debris screen shall
be corrosion resistant and shall have openings no larger than a nominal 0.15 cm
(1,500 microns) (1/16 in.).
Exception: Pre-filters with a self-cleaning design are not required to have the
aforementioned debris screen.
b.
If more than one cistern is used, a pre-filtration system shall be provided for each
cistern.
Exception: Where cisterns are interconnected to supply water in series, a single
pre filter is permitted
c.
3.3.2
3.4
First flush devices are optionally used to wash accumulated debris from the collection
surface before rainwater is allowed to enter the storage tank. When first flush devices are
used, these systems shall meet the following design requirements:
a.
b.
c.
Water drained from the first flush device shall be piped away from the storage
tank and terminate in a location so as not to cause damage to property or cause
erosion.
d.
e.
Cisterns / Storage
The following are the minimum requirements for cisterns. Additional requirements are provided
in Section 3.7 for potable water applications.
3.4.1
General
a. Cisterns may be used as rainwater collection points that help to minimize flood
damage, while providing a reservoir for later use. All rigid-bodied cisterns and all
cisterns over 1.22 m (4 ft) in height (rigid or flexible) shall have access to allow
inspection and cleaning.
3.4.2
Installation
a.
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
b.
Cisterns shall comply with the administrative authority having jurisdiction, local
building codes and ordinances, and/or as certified by a structural engineer.
c.
Above-grade plastic tanks used as cisterns shall be certified for the intended
application.
d.
(2)
e.
f.
Where the installation requires a foundation, the foundation shall be flat and shall
be designed to support the cisterns weight when the cistern is full consistent
with the bearing capability of adjacent soil.
g.
h.
i.
(1)
(2)
In a situation where the soil can become saturated, underground tanks shall be
ballasted, or otherwise secured, to prevent the tank from floating out of the
ground when empty. The combined weight of the tank and hold-down ballast
shall meet or exceed the buoyancy force of the tank, calculated as follows:
Example (SI):
For 3,785.4-liter tank, buoyant force will be 3,785.4 liters x (1 cubic foot/28.32
liters) x 62.4 (0.4536 kg/cubic foot) = 3,783.35 kg.
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Buoyancy force of cistern (kg) = 1,000 liters x 28.3 kg/liter = 28,300 kg.
If concrete is used for ballast, the volume needed will be:
Volume (cubic meters) = 28,300 kg x cubic meters/2,400 kg = 11.8 cubic meters.
Example (U.S.):
Buoyant force of cistern (lbs) = Volume (cubic feet) x 62.4 (lbs/cubic foot)
For 1,000-gallon tank, buoyant force will be 1,000 gallons x (1 cubic foot/7.48
gallons) x 62.4 (lbs/cubic foot) = 8,342 lbs.
If concrete is used as ballast, the volume needed will be:
Volume (cubic feet) = 8,342 lbs x cubic feet/150 lbs = 55.6 cubic feet (2.1 cubic
yards).
j.
Cisterns shall be provided with a means for draining and cleaning. Where gravity
drainage is not possible, provision for pumping water from the tank shall be
provided.
k.
3.4.3
Cistern inlets shall be provided to permit water to enter the tank with minimum
turbulence.
b.
The overflow outlet, or flap valve, shall be protected with a screen having
openings no greater than 0.3 cm (0.125 in.), or as otherwise appropriate, for
preventing the entrance of insects or vermin into the cistern.
(1)
(2)
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
3.5
PUMP
3.5.1
3.6
Where a pump is provided in conjunction with the rainwater harvesting system, the pump
shall meet the following provisions:
a.
The pump and all other pump components shall be certified and approved for use
with the appropriate potable or nonpotable water systems.
b.
The pump shall be capable of delivering a minimum of 205 kPa (15 psig)
residual pressure at the highest and /or most remote outlet served. Minimum
pump pressure shall allow for friction and other pressure losses. Maximum
pressures shall not exceed 653 kPa (80 psig). A pressure-reducing valve shall be
provided at water branch distribution piping if the pump is capable of exceeding
618 kPa (75 psig).
FILTRATION
Filtration shall meet the following provisions:
3.7
3.6.1
Where rainwater is used for outdoor nonpotable uses and for non-critical operations, such
as irrigation, washdown, etc., a final stage filtration system is not required.
3.6.2
Where rainwater is used for indoor nonpotable use, for laundry, toilets, urinals, process,
etc., the water shall be filtered as a safeguard against sediment or discoloration, and for
proper operation of valves or other devices.
PIPING
3.7.1
There shall be no direct connection of any rainwater harvesting pipe system and a public
utility-provided domestic potable water pipe system without an approved backflow
device.
3.7.2
Separation shall be maintained between potable and nonpotable water systems at all
times. Cross connections, without proper protection in accordance with local applicable
plumbing code, shall not be permitted.
3.7.3
a.
All material used as part of a rainwater harvesting system shall be certified for
the purpose intended, as designated by the local applicable code.
b.
Where rainwater harvesting pipe and potable water pipe are installed in the same
trench, wall cavity, or other location, the potable water pipe shall be separated by
a minimum distance of 30.5 cm (12 in.) above the rainwater harvesting pipe.
Underground pipes shall be installed below the local frost depth.
Piping Materials
a.
10
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
b.
3.7.4
Labeling
If a rainwater harvesting system is applied to any building, facility, or residence, it shall
be so indicated as follows:
a.
All rainwater-supplied fixtures, not specifically treated for potable water use,
shall be prominently labeled:
Nonpotable water piping shall be designated by colored bands and solid color
piping as specified by the authority having jurisdiction or national code agencies,
and labeled:
NONPOTABLE -- RAINWATER.
c.
3.7.5
Outlets and fixtures served with harvested rainwater shall be easily recognizable
by color or a symbol for nonpotable water.
Inspections
Rainwater harvesting systems are considered a private water system under the
responsibility of the building owner/operator, and shall be minimally inspected according
to the following schedule:
a.
b.
c.
In addition to testing required by the code for plumbing systems, the following
also apply:
d.
3.7.6
(1)
(2)
Piping. A flow test shall be performed through the system to the point of
water distribution and disposal. In addition, the water distribution system
shall be tested and proved tight at the operating pressure. Where the
manufacturer permits, a 446 kPa (50 psi) hydrostatic test may substitute
for the test above. All lines and components shall be watertight.
System Maintenance
It is the property owners responsibility to maintain the system components according to
manufacturers written recommendations.
11
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
3.7.7
Rainwater harvesting systems shall be maintained in functioning order for the life of the
system.
a.
b.
System Abandonment
If the owner of a rainwater harvesting system elects to cease use of, or fails to
properly maintain such system, the owner shall abandon the system. To abandon
the system, the system owner shall minimally:
(1) Remove or disable all system connecting piping to utility-provided water
system.
(2) Replace the rainwater harvesting pipe system with an approved potable water
supply pipe system. Where an existing potable pipe system is already in
place, fixtures may be re-connected to the existing system.
(3) Secure cistern from accidental access by sealing or locking tank inlets and
access points, and/or filling with sand or equivalent.
3.8
3.8.2
Collection surfaces for potable water applications shall made of non-toxic material and
meet the requirements noted in 3.1.1 above.
a.
Painted surfaces are only acceptable if paint has been certified to ensure the
toxicity level of the paint is acceptable for drinking water contact. Lead,
chromium or zinc based paints are not permitted.
b.
Enameled steel.
c.
d.
b.
c.
Lead flashing.
2 The use of bitumen/composition roofing or galvanized, zinc-coated metal is not recommended and should be used
with caution.
12
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
3.8.3
Cisterns
3.8.4
3.8.5
a.
Water entering the cistern shall be maintained at a quiescent flow in the cistern
by minimizing splashing and disturbance of sediment in bottom of cistern.
b.
For potable water applications, and recommended for maintaining good water
quality, the pipe entering the cistern shall terminate in a return bend elbow
pointed upward at the bottom of the tank, or equivalent calming device.
c.
Cistern outlets shall be provided with floating inlet to draw water from the cistern
just below the water surface, or the outlet shall be located at least 10 cm (4 in.)
above the bottom of the cistern.
d.
Cisterns shall be certified to NSF/ANSI Standard 61. Plastic tanks shall adhere to
the requirements of NSF/ANSI Standard 61 and be constructed of virgin plastic.
e.
f.
Filtration
a.
Carbon filtration may be provided for reduction of taste, odor, and organic
chemicals.
b.
Filtration and disinfection systems shall be located after water storage tank and as
close to the final point of use as possible.
c.
d.
Filters shall be adequately sized to extend service time and must be comply with
NSF/ANSI Standard 53.
Water Disinfection
a.
Chlorination may be used with an automated demand feed system, and if used,
shall enable adequate contact time and residual according to local health
authorities.
b.
Ozone may be used with an approved ozone system ensuring adequate contact
time with the ozone. Provision must be made to off- gas ozone to a safe
environment.
c.
13
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
3.9
Prior to Use
Prior to system operation, all debris will be removed from the collection surface and
piping system. The cistern and distribution piping shall be cleaned with a sanitizing
solution.
a.
b.
For private water systems, prior to placing the water system into service, water
quality testing, at a minimum, shall be performed for E. coli, total coliform, and
heterotrophic bacteria using the minimum quality standards provided in Table
3.1.
c.
Public System
(1)
(2)
(3)
POTABLE 1
99.9999% Reduction
Protozoan Cysts
< 10 NTU
99.9% Reduction
Viruses
-----------------
99.99% Reduction
PARAMETER
Turbidity
Potable water standard meets the United States Environmental Protection Agency (US EPA)
drinking water standard for pathogens.
Note: Monitoring requirements vary greatly from state to state. Consult state and local guidelines for
monitoring requirements.
14
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
3.9.2
The quality of the water for the intended application shall be verified at the point
of use in accordance with the minimum requirements of Table 3.1 complying
with the testing procedures set forth in the Standard Methods for the Examination
of Water and Wastewater.
b.
Nonpotable water shall be tested every 12 months. Potable water shall be tested
every three months.
c.
For a potable public water system, one sample shall be analyzed for applications
serving up to 1,000 persons. When the treated water shall serve 1,0002,500
persons, two samples shall be analyzed, and for 2,501 persons and up, three
samples shall be analyzed. Samples must come from the following locations
when additional taps for sampling are available:
(1) One sample from the same location as the positive sample;
(2) One sample within five service connections upstream;
(3) One sample within five service connections downstream; and
(4) For systems serving 251,000 persons, a fourth sample from any other
sampling site.
d.
4.0
DEFINITIONS
The following terms are defined in the manner in which they are intended to be used in the Standard.
Additional definitions of terms relevant to the scope of this standard that are not used in the body of the
Standard are provided in Annex C for informational purposes.
4.1
ACCREDITED: Verification that a certification body meets the requirements of ISO/IEC 17065
by a third-party agency operating in compliance with ISO/IEC 17011.
4.2
CERTIFIED: Verified compliance to a standard by a certification body that has been accredited
by third-party as having systems in compliance with ISO/IEC 17065.
4.3
CISTERN: The central storage component of the rainwater harvesting system. Also referred to as
a storage tank.
4.4
4.5
DEBRIS EXCLUDER: A screen or other device installed on the gutter or downspout system to
prevent the accumulation of leaves, needles, or other debris in the system.
15
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
4.6
DISINFECTION: Reduction of viable microorganisms to a level that is deemed suitable for the
intended application. Typical units of measure are colony forming units per deca-liter (cfu/dl).
4.7
4.8
GROUNDWATER: Water that has saturated into the ground and no longer flows across the
surface.
4.9
4.10
PIPING SYSTEM: Pipes and components that convey the harvested rainwater and distribute it to
various fixtures.
4.11
4.12
PRECIPITATION: Water that has precipitated from the atmosphere (e.g., rain, snow, mist, dew).
4.13
PRIVATE WATER SYSTEM: System used by less than 25 persons over a 60-day period, or
contain less than 15 plumbing fixtures.
4.14
4.15
PUBLIC SYSTEM: System used by 25 persons or more over a 60-day period, or contain 15
plumbing fixtures or more.
4.16
QUIESCENT INFLOW: Routing of rainwater into rainwater reservoirs so that the existing
sediment is not activated in the rainwater reservoir and an immediate sedimentation of solids is
possible.
4.17
4.18
4.19
4.20
ROOF DRAINAGE SYSTEM: A system, comprised of roof drains, overflow drains, scuppers,
gutters, and downspouts, used to convey the rainwater from the roof surface to the roof washer
and the cistern.
4.21
ROOF SURFACE: The surface rainwater harvesting systems rely on for the collection of
rainwater that has fallen on a building roof.
16
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
4.22
ROOF WASH OR ROOF WASHER: A device or method for removal of sediment and debris
from the collection surface by diverting initial rainfall from entry into the cistern(s). Also called a
first flush device.
4.23
4.24
4.25
4.26
STORM WATER: Natural precipitation that has contacted a surface at grade or below-grade and
has not been put to beneficial use.
4.27
STORM WATER CATCHMENT SYSTEM: A system that collects and stores storm water for
beneficial use.
4.28
4.29
SUN BARRIERS: A cover, or erected structure, specifically to shelter a cistern from the direct
rays of the sun.
4.30
SURFACE IRRIGATION: Water that is applied above ground level and is directly exposed to
the aboveground surface and/or air.
4.31
SUBSURFACE IRRIGATION:
topsoil.
4.32
SURFACE WATER: Rainwater that touches the ground and flows across the surface of the
ground (landscapes, driveways, roadway, parking surface, gully, creeks, streams etc.).
17
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Annex A
Additional Relevant Standards/Documents
(Informative)
1.
ASTM International
ASTM D638-10: Standard Test Method for Tensile Properties of Plastics
ASTM D695-10: Standard Test Method for Compressive Properties of Rigid Plastics
ASTM D1599-99(2011): Standard Test Method for Resistance to Short-Time Hydraulic Pressure
of Plastic Pipe, Tubing, and Fittings
ASTM D1600-08: Standard Terminology for Abbreviated Terms Relating to Plastics
ASTM E84-12b: Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM F412-12: Standard Terminology Relating to Plastic Piping Systems
2.
3.
4.
5.
6.
http://www.ncdc.noaa.gov/
18
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Annex B
Acceptable Piping Schematics
(Informative)
Figure 1: Aboveground Exterior Cistern for Potable and/or Nonpotable Water
Figure shows an aboveground application in a non-freeze environment. In an environment where
freezing is possible, the tank should be located in a heated environment, buried below the frost line, as
shown in Figures 2 and 3, or otherwise heated or winterized to accommodate freezing conditions without
system damage.
19
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
20
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
21
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
22
Medium Contamination
2.0 mm (0.08 in.)
Low Contamination2
0.5mm (0.02 in.)
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
There are many different styles of roof wash devices. The simplest versions involve filling a standpipe
section of piping that contains adequate volume, that once full, then overflows into the cistern. (See Figure
6.)
23
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
The volume of pre-wash for a nominal 4 in. (4.046 in. actual) diameter PVC pipe can be determined as
follows in Figure 7a.
Figure 7a. 4 in. PVC Pipe Storage Volume
Length : feet (meters)
1 (0.3)
2.6 (0.7)
3 (0.9)
7.6 (2.0)
5 (4.6)
12.5 (3.3)
10 (3.0)
25.4 (6.7)
15 (4.6)
38.1 (10.5)
The volume of pre-wash for a nominal 6 in. (6.065 in. actual) diameter PVC pipe can be seen in Figure 7b.
3 (.9)
17.0 (4.5)
5 (4.6)
28.4 (7.5)
10 (3.0)
56.8 (15.0)
15 (4.6)
85.2 (22.5)
End of Annex B
24
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Annex C
Reference Definitions
(Informative)
The following terms are commonly used in the rainwater catchment system industry, and the definitions
are provided for informational purposes.
AUXILIARY SUPPLY: A water supply arranged and protected from contamination that is available to
provide an alternate means of filling a cistern.
CALMING INLET: A device that permits water to enter a storage tank with minimal disturbance to
particles that may have settled to the bottom of the tank. See Quiescent Flow.
COLLECTION AREA: Area from which rainwater is collected for use in a rainwater harvesting system
(e.g. roof area).
DRY RUN PROTECTION: System for protecting the water pump against running dry.
EVAPORATION FIELD: Element in the ground that is filled with gravel, ballast, or special nonpermeable plastic elements and that stores rainwater that is fed into it on an intermediate basis before the
water evaporates into the atmosphere or seeps into the surrounding soil.
FIRE SPRINKLER RESERVE: Volume of water needed for fire protection that is not available for any
other use and accessible only by the fire pump.
HARVESTED WATER: Water gathered for the purpose of using for potable, nonpotable, or industrial
applications.
LEACH FIELD, EVAPORATION/TRANSPIRATION FIELD: Element in the ground that is filled with
gravel, ballast, or special permeable plastic elements and that stores rainwater that is fed into it on an
intermediate basis before the water seeps into the surrounding soil.
MINIMUM WATER VOLUME: Recoverable water volume that is constrained by the process such that
neither sediment nor scum can be sucked into the deliverable water.
OVERFLOW LEVEL: The highest level that water from a drainage system can rise.
OVERFLOW LINE: Line for leading away rainwater when the rainwater reservoir is full (e.g., into the
storm drain system or seepage system).
PRECIPITATION CHARACTERISTICS:
duration).
PROCESS WATER LINE: System of lines from the process water pump to the individual points at which
water is drawn.
PROCESS WATER PUMP: Pumps process water from the rainwater reservoir to the points at which it is
drawn.
25
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
PROCESS WATER REQUIREMENTS: Planning value for the process water amount that is expected to
be required in a specified period of time.
PUBLIC WATER SYSTEM: System that is used by 25 or more different persons over a 60-day period.
QUANTITY OF PRECIPITATION: Precipitation at a certain place, expressed as the water height over a
horizontal area for a span of time under consideration.
RAINWATER LINE: Supply, drainage, overflow, and emptying lines of a rainwater harvesting system.
RAINWATER YIELD: Net water volume (water inflow), determined over a certain period of time,
available for use as process water. Typically this is approximately 80% of theoretical collectable rainwater.
SUBSURFACE IRRIGATION: Water that is applied below ground level, and is not directly exposed to
the aboveground surface and/or surrounding air.
SUPPLEMENTAL SUPPLY: Equipment for providing a supplemental supply of drinking water or nondrinking water into process water systems.
SYSTEM CONTROL UNIT: Control unit for the automatic operation of the rainwater harvesting system.
TRANSFER PUMP: A mechanical device to transfer collected water from downspouts to remote cisterns.
USEFUL VOLUME: Volume that can be completely used during operation (Typically 8090% of storage
volume).
YIELD COEFFICIENT: Ratio of the rainwater annually flowing into the rainwater harvesting system to
the total amount of rainwater in the accompanying precipitation area , allowing for leakage, splashing,
evaporation, etc. (typically 0.750.90).
End of Annex C
26
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Annex D
Example of a Maintenance Form
(Informative)
End of Annex D
27
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Annex E
Calculation Procedure
(Informative)
Step 1: Estimate demand
Interior Water Requirement*: On average, a conserving American household uses 45.2 gallons per
person/day to operate toilets, showers, clothes washers, sinks, and other water -using fixtures and
appliances. Water demand can be minimized by using water efficient water fixtures. An example of how
to estimate water demand is shown as follows:
Fixture
Flow
Rate
(liters
per
use or
min)
**
6.0
Toilets
Shower
(liters /
minute)
6.3
5.3
33.31
Faucets
(liters /
minute)
6.3
8.1
50.91
Dishwasher
(19972001)
(liters/use)
17.0
0.1
1.70
Clothes
washer
(1998 2001)
(liters/use)
102.2
0.37
37.82
Total
Demand
*Source: "Handbook of Water Use and Conservation"
MA, ISBN I-931579-07-5
** Actual Flow (MFR)
28
Household
Total
Monthly
demand
( L)
Household
Total
Yearly
demand
( L)
2,809
33,823
99.90
3,028
36,469
152.70
4,626
55,733
5.11
155
1,866
113.45
3,437
41,409
463.83
14,055
169,300
Amy Vickers, 2001, Waterplow Press, Amherst,
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Fixture
Toilets
Shower
(based on 2.5
gal/min)
Faucets (based
on 2.5
gal/min)
Dishwasher
(1997- 2001)
(gal/use)
Clothes
washer (1998
- 2001)
(gal/use)
24.48
Household
Total
Monthly
demand
(gal)
742
Household
Total
Yearly
demand
(gal)
8,935
26.39
800
9,634
13.45
40.34
1,222
14,723
0.1
0.45
1.35
41
493
0.37
9.99
29.97
908
10,939
122.5
3,713
44,724
Flow
Rate (per
use or
min) **
Average #
uses/day or
min/day
per person
Daily
Demand/
person
(gal)
Number of
people in
household
Household
Total Daily
Demand/
(gal)
1.6
5.1
8.16
1.66
5.3
8.80
1.66
8.1
4.5
27
Total
Demand
*Source: "Handbook of Water Use and Conservation" Amy Vickers, 2001, Waterplow Press, Amherst, MA, ISBN I931579-07-5
** Actual Flow (MFR)
Irrigation Water Requirement: Water used to irrigate landscaping often equals or exceeds interior water
use. Supplemental irrigation water requirements can be greatly reduced by the use of 3 in. or more of top
mulch, selecting native plants or plants that thrive in regions with similar climate, and using passive
rainwater techniques. Because plant water needs vary greatly depending on soils, climate, plant size, etc. it
is recommended that a calculator for your region be referenced. For calculators, visit the ARCSA website
at www.arcsa.org.
Step 2: Sizing the Collection System
The collection surface is often dictated by architectural constraints, such as roof area, etc. The amount of
surface area, based on the needed water volume, is described as follows:
Surface Area (Square Feet) = Demand (Gallons) / 0.623 x Precipitation Density (inches) x system
efficiency
Note:
0.623 (gallons / square foot / inch) conversion factor = 7.48 (gallons / cubic foot) / 12 (inches per
foot). 1 inch of water covering 1 square foot of surface area = 2.358 L (0.623 gallons).
Surface area is horizontal projection of roof surface and not actual surface area (measure the area
the roof covers, not the actual roof).
29
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Precipitation density period is consistent with time period being considered (monthly, yearly, etc.).
This coefficient accounts for collection system loss from leakage, evaporation, roof composition,
etc. Roof coefficients are approximately 0.800.85.
30
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Tank size is not necessarily based on collecting total roof runoff. For example, the maximum water that
can be collected from a roof area of 20 square feet with a monthly rainfall of 4 in. will be about 40 gallons.
If the water demand is less than this, some overflow may occur while demand is still met. If water demand
is to be met throughout the month, the tank should be large enough so that Vt is never negative.
Calculations should be repeated using various tank sizes until Vt is 0 at the end of every month. The
greater the values of Vt over the whole year, the greater the security of meeting water demand when
rainfalls are below average or when dry periods are longer than normal.
The greater the security, the higher the cost of the tank.
Step 4: System Adjustment
To optimize performance and cost, going back through the calculation and modifying surface area and the
cistern storage capacity is recommended.
End of Annex E
31
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
Annex F
Average Rainfall Data (Informational)
32
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
33
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
34
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
35
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
36
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
37
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
38
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
39
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
40
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
41
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
42
ARCSA-ASPE_63_Draft3_Approved_for_public_review.docx
43