Air Con 03 Over
Air Con 03 Over
Air Con 03 Over
LECTURE
SUB - OBJECTIVE
At the end of this lesson the trainee will be able to:
learns the need for compressor unloading. He identifies hydraulic, pressure and
solenoid-operated bypass and suction cutoff unloaders, and identifies correct
unloader operation. He adjusts pressure-operated unloaders. He troubleshoots
and repairs solenoid-operated unloaders.
1.0 INTRODUCTION
When an air conditioning system is designed, a compressor capacity is selected to
handle the peak (maximum) load. In most systems the cooling load is constantly
changing, so the typical operating load for a compressor might be only 50% of the peak
load. If a compressor designed to handle a peak load operates at full capacity when the
load is only 50%, it will compress more refrigerant vapor than can be used by the
evaporator. This causes suction pressure to fall. Low suction pressure can cause oil
migration, freeze the evaporator, and/or cause erratic operating conditions which cause
compressor failure.
2.0 MATCHING COMPRESSOR CAPACITY AND LOAD
One way to match compressor capacity and system load is to cycle a compressor on
and off. But this is not the best solution. It involves frequent compressor starts and high
power consumption. It also causes wear and tear on the compressor and its electrical
components.
Another way to adjust compressor capacity to load is to use several smaller
compressors in parallel instead of one large one. As the load rises and drops,
additional compressors are switched on or off to meet it. The disadvantages of this
approach are high initial cost, a greater use of floor space, and increased maintenance
3.0 CAPACITY CONTROL DEVICES
The most efficient and least costly way to match compressor capacity and load is to use
capacity control devices. A capacity control device regulates the amount of refrigerant
going through the compressor. It can either be built into the compressor (compressor
internal) or separate from it (compressor external).
All compressor-internal methods of capacity control decrease a compressor's capacity
while keeping the compressor running.
ADVAANCED COURSE
COMPRESSOR OVERHAULING
ADVANCED COURSE
COMPRESSOR OVERHUALING
suction cutoff's cylinder head is flat. It has a cover plate and four bolts directly opposite
its capacity control valve.
operating temperature of a suction cutoff unloader is also reduced at part load, while
the bypass unloader's operating temperature remains the same.
ADVANCED COURSE
COMPRESSOR OVERHUALING
SOLENOID-OPERATED
PRESSURE-OPERATED
FIG. 1.4 SOLENOID-OPERATED AND PRESSURE-OPERATED CAPACITY
CONTROL VALVES
The pressure-operated control valve has a diaphragm that operates the poppet valve
and piston inside the valve body. But the solenoid-operated valve is activated by an
electric signal. Therefore, it does not have the diaphragm or control set point
adjustment nut. We will look first at the pressure-operated capacity control valve.
3.6.1.1 Pressure-Operated Capacity Control Valve
FIG. 1.5 shows a pressure-operated capacity control valve. This valve is easy to
recognize by its diaphragm and control set point adjustment nut. It can be used with
both bypass and suction cutoff unloaders.
ADVAANCED COURSE
COMPRESSOR OVERHAULING
The valve has two parts: (1) the basic valve (comprised of the control set point
adjustment nut, diaphragm, and valve body), and (2) the bypass piston. The bypass
piston is only used with the bypass unloader. When the control valve is used with the
suction cutoff unloader, the bypass piston is removed and discarded. FIG. 1.6 shows a
cutaway view of a pressure-operated control valve with the bypass piston. The valve
consists of: (1) control set point adjustment nut, (2) control set point spring, (3)
diaphragm, (4) poppet valve centering spring, (5) poppet valve drive spring, (6) poppet
valve, (7) bleed orifice, (8) pressure differential adjustment screw, (9) bypass piston,
and (10) bypass piston drive spring.
ADVANCED COURSE
COMPRESSOR OVERHUALING
The solenoid-operated control valve is also called an electric capacity control valve. As
shown in FIG. 1.7, it has a solenoid coil and wire leads. It operates with the unloader in
the same way as a pressure-operated valve, except it is electrically energized from an
external source (thermostat, pressurestat, or step controller). When the control valve is
energized, the compressor cylinder bank unloads.
The solenoid-operated valve is a simple on-off switch. The setting of the external
control device (which energizes the solenoid valve coil) determines the point of loading
and unloading.
ADVAANCED COURSE
COMPRESSOR OVERHAULING
ADVANCED COURSE
COMPRESSOR OVERHUALING
ADVAANCED COURSE
COMPRESSOR OVERHAULING
2. When the suction pressure rises to a point that is above the control set point spring
tension, the pressure against the diaphragm forces it to the left (point 1 in Part B of
FIG. 1.12) .
3. This movement of the diaphragm leaves a free space at the left of the poppet valve,
allowing the poppet valve drive spring to close (point 2, Part B) .
4. When the poppet valve closes, it prevents discharge gas from passing to the suction
side through the bypass passage (point 3, Part B) .
5. The discharge gas passing through the bleed orifice (point 4, Part B) builds up
pressure behind the bypass piston. When the discharge pressure becomes greater
than the force of the piston's internal spring the piston moves to the right point 5, Part B
6. The piston closes the port in the unloader head that allows discharge gas to vent to
the suction side of the cylinder (point 6, Part B).
7. Now that discharge gas cannot vent to the suction side of the cylinder, pressure
builds up in the high side of the head. This pressure overcomes the tension of the
spring inside the check valve, forcing the valve open (point 7, Part B).
8. Discharge gas can now enter the discharge manifold. The cylinder is loaded.
ADVANCED COURSE
COMPRESSOR OVERHUALING
3. With the poppet valve open (point 3, Part B) discharge gas passes through the
bypass passage into the suction manifold (point 4, Part B).
4. Venting discharge gas reduces pressure behind the bypass piston. This allows the
piston's internal spring to force the piston to the left (point 6, Part B).
5. The seating of the bypass piston against the control valve's body opens the bypass
port. This provides a path for the refrigerant gas to vent to the suction side of the
cylinder (point 5, Part B).
6. A reduction in discharge pressure allows the check valve's internal spring to move
the check valve upward and seat it against the valve plate. This isolates the cylinder
from the discharge manifold (point 7, Part B). The cylinder is now unloaded. As long as
the compressor operates, the cylinders without Unloaders keep the discharge manifold
at discharge pressure. However, the discharge gas cannot move the unloaded
cylinder's Bypass piston to close the port. This is because the open poppet Valve
bleeds the discharge gas to the suction side.
3.8.1 SUCTION CUTOFF UNLOADER OPERATION
FIG. 1.14 is a cutaway view of a suction cutoff unloader. Like the bypass unloader, it is
comprised of a capacity control valve, Unloader head and gasket, and valve plate.
The differences between the two unloaders are: (1) the bypass piston has been
removed from the control valve, and (2) unloading is achieved by a larger assembly
made up of a piston, piston arm, unloader valve body, and unloader valve spring. The
ADVAANCED COURSE
COMPRESSOR OVERHAULING
piston assembly is installed, removed, and serviced through the cover plate on the
opposite side of the unloader head from the capacity control valve.
This unloader entirely shuts off suction gas from the cylinder head when it is closed
(unloaded
ADVANCED COURSE
COMPRESSOR OVERHUALING
2. When the suction pressure rises to a point above the control set point spring
tension, the pressure against the diaphragm forces it to the left (point 1 in Part B of
FIG. 1.15).
3. This movement of the diaphragm leaves a free space at the left of the poppet valve,
allowing the poppet valve drive spring to move left and close (point 2, Part B).
4. When the poppet valve closes, it blocks off the bypass port (point 3, Part B). This
prevents discharge gas (point 4, Part B) from passing into the suction manifold.
5. With the bypass port blocked, the discharge pressure builds up in back of the
unloader piston (point 5, Part B). This forces the piston and valve body to the right. This
opens the suction port (point 6, Part B), allowing the suction gas to pass into the
cylinder bank. The cylinder is loaded.
3.8.3 UNLOADING THE SUCTION CUTOFF VALVE
The suction cutoff valve in Part A of FIG. 1.16 is loaded. Here is how the valve is
unloaded:
1. When the suction pressure drops below the set point of the control spring (point 1 in
Part B of FIG. 1.16) , the force of the spring is greater than the refrigerant vapor
pressure exerted on the control valve diaphragm (point 2, Part B).
2. The diaphragm moves to the right, pushing the poppet valve off its seat (point 3, Part
B) .
3. With the poppet valve open, discharge gas passes through the bypass passage into
the suction manifold (point 4, Part B).
4. Venting discharge gas reduces the pressure behind the unloader piston head (point
5, Part B). This allows the spring to move the valve body to the closed position (point 6,
Part B).
5. With the valve body in the closed position, suction gas can no longer enter the
cylinder head (point 7, Part B). The cylinder is unloaded.
ADVAANCED COURSE
COMPRESSOR OVERHAULING
The control set point is the point at which the cylinder loads. It is adjustable from 0 to
86 psig. Selecting a control set point depend on refrigerant used in the system, and
ambient conditions. The pressure differential between cylinder loading and unloading is
adjustable from 7.4 to 18.6 psig for bypass unloaders, and 6.3 to 15.8 for suction cutoff
unloaders. Following is the procedure for setting and adjusting the control set point and
pressure differential.
3.9 ADJUSTING THE CONTROL SET POINT
To adjust the control set point of a pressure operated unloader, follow these steps:
1. Turn the control set point adjustment nut clockwise to its bottom stop. In this
position the set point is 86 psig.(See FIG. 1.18.)
ADVANCED COURSE
COMPRESSOR OVERHUALING
2. Refer to the Control Set point Chart in FIG. 1.19. Find the pressure set point you
want in the left-hand column. For example, we have selected a set point of 57 psig
(point 1 in the chart).
3. Draw a horizontal line from the desired pressure to the solidline curve in the graph.
The dotted lines on both sides of the solid line indicate the tolerance.
4. At the point of intersection (point 2 in the chart) draw a vertical line down to the
bottom coordinate of the graph.
5. The point at which the vertical line intersects the bottom coordinate (point 3 in the
chart) is the number of counterclockwise turns required for the adjusting nut to obtain
the desired set point. In this instance it is four turns.
6. Turn the control set point adjustment nut counterclockwise four full turns to set the
control valve at 57 psig. Each full turn decreases the set point by 7 psig. This Control
Set Point Chart can be used for setting both bypass and suction cutoff unloaders.
3.10 ADJUSTING THE DIFFERENTIAL SET POINT
Adjusting the differential set point is almost the same as setting the control set point.
But there are two major differences:
(1) a screwdriver is used to adjust the differential set point, and
(2) the differential set point is different for bypass unloaders and suction cutoff
unloaders. (That is to say, there is one chart to use for bypass unloaders and another
chart for suction cutoff unloaders.)
ADVAANCED COURSE
COMPRESSOR OVERHAULING
To adjust the differential to the pressure at which you want the cylinder to unload, follow
these steps. The steps refer to FIG. 1.20 and to the Bypass Differential Curve Chart in
FIG. 1.21.
1. Turn the sealing cap.
2. Turn the differential adjusting screw counterclockwise to its backstop position, as
shown in FIG. 1.20. In this position, the differential is 7.4 psig for bypass unloaders and
6.3 psig for suction cutoff unloaders.
3. Refer to the Differential Set point Chart in FIG. 1.21.
The differential range is not the same for bypass and suction cutoff unloaders. Be sure
to use the right chart. Here, we are using the chart for bypass unloaders.
4. Locate the desired differential setting on the left side of the curve. In this instance,
we have chosen a differential setting of 8 (point 1 in the graph) . This means the
bypass cylinder will unload at 49 psig. (Remember, the set point is 57 psig, so 57 - 8 =
49 psig.)
5. Draw a horizontal line from the 8 to intersect the solid curve in the graph, as shown
at point 2.
6. Draw a vertical line down to the bottom of the graph to intersect with the lower
coordinate (point 3 on the graph). The vertical line intersects the lower coordinate at 1.
7. This means you must then turn the differential adjustment screw clockwise one
complete turn to obtain a differential pressure of 8 psig. When you complete the
adjustment, replace the sealing cap on the differential adjusting screw. This reduces the
possibility of refrigerant leakage.
ADVANCED COURSE
COMPRESSOR OVERHUALING
ADVAANCED COURSE
COMPRESSOR OVERHAULING
ADVANCED COURSE
COMPRESSOR OVERHUALING
FIG. 1.24 CHECK SOLENOID FOR MAGNETISM CHECK SOLENOID FOR CURRENT
ADVAANCED COURSE
COMPRESSOR OVERHAULING
ADVANCED COURSE
COMPRESSOR OVERHUALING
3. The increase in control oil pressure at the left side of the hydraulic relay piston, at 7,
causes it to move to the right.
2. See FIG. 1.28. As the needle valve moves towards the valve seat, the flow of control
oil to the crankcase through the oil drain, at 4, is reduced. This causes the control oil
pressure to increase as oil from the compressor oil pump circuit, at S, flows through the
orifice, at 6, to the hydraulic relay.
4. See FIG. 1.29. Moving the relay piston to the right allows the compressor oil pump,
at 8, to feed oil into the unloader power element, at 9. The pump oil pressure in the
unloader power element forces the piston upwards and pivots the lifting fork, at 10,
downwards. This causes the lifter pins, at 11, to drop, allowing the suction valve to seat
and load the cylinder.
ADVAANCED COURSE
COMPRESSOR OVERHAULING
5. See FIG. 1.31. Allowing the control oil to drain from the capacity control valve
reduces the pressure on the hydraulic relay piston, at 6.
6. This allows the piston to move to the left and stop the flow of oil from the oil pump to
the cylinders power element, at 7.
AIR CONDITION & REFRIGERATION
LESSONE 3 PAGE 22
ADVANCED COURSE
COMPRESSOR OVERHUALING
7. See FIG. 1.32. As the oil pump pressure to the power element drops, the unloader
piston, at 8, moves downward draining oil, at 9, to the crankcase.
8. The lifting fork, at 10, pivots upwards lifting the pins which cause the suction valve to
be raised off its seat. This is the unloaded condition. In this condition there is no
compression. The refrigerant is only moving back and forth between the cylinder and
the suction side of the compressor.
Look at the port above the adjusting stem in FIG. 1.33. This port is for a pneumatic
control connection, which resets the control point based on the operating conditions.
DO NOT plug this port if pneumatic control is not used.
2. Connect a gauge to the suction service valve and operate the compressor., The
suction pressure must be higher than the desired control point.
ADVAANCED COURSE
COMPRESSOR OVERHAULING
3. Close the suction service valve slowly, to lower the suction pressure. Keep closing
the service valve until the suction pressure drops to the desired control point pressure.
4. Turn the external adjusting stem clockwise until the first step of unloading is reached.
This is indicated by a change in the compressor sound level, a drop in the control oil
pressure, and a drop in the compressor current draw. One full clockwise turn of the
adjusting stem raises the control point approximately 10 psig with R-22 refrigerant.
5. Replace the cap on the adjusting stem to minimize refrigerant leakage after setting
the control point. Reopen the suction service valve.
6. The remaining steps of unloading are fixed and determined by the hydraulic relay.
3.13 TROLIBLESHOOTINC HYDRAULIC UNLOADER FAULT
Compressor dose not load. This could be due to:
1. Capacity control valve stuck open.
2. Lifter pins stuck in the up position.
3. Oil pressure too low.
4. Plugged/closed pneumatic opening.
Compressor dose not unload. This could be due to:
1. Lifter pins stuck in the down position.
2. Stuck hydraulic relay valve.
Rapid unloader cycling could be caused by a partially plugged control oil strainer.
3.14 TROUBLESHOOT MECHANICAL FAULTS
This module covers mechanical component malfunctions in reciprocating chillers.
Some symptoms covered in this module could be due to electrical problems.
ADVANCED COURSE
COMPRESSOR OVERHUALING
Symptom(s)
1.1 Electric system checks out okay,
but compressor does not start.
2. Defective valves
3. Loose compressor
3.15.2 UNLOADERS
1. Stuck check valve
2. Stuck piston assembly (suction
cutoff-type)
3. Defective control valve body
(both types)
4. Defective control valve body
and/or check valve; and/or piston
assembly (solenoid-type)
5. Capacity control valve stuck
open or lifter pins stuck in the up
position or plugged/closed
pneumatic opening (hydraulic type).
6. Stuck unloader element
or
lifter pins stuck in the down position
(hyd type).
7. Partially plugged control
oil
strainer (hyd type).
3.15.3 OIL
1. Too much oil in
2. Low oil level
ADVAANCED COURSE
COMPRESSOR OVERHAULING
ADVANCED COURSE
COMPRESSOR OVERHUALING
11. Turn the differential adjustment screw clockwise the full number of turns approved
by the Trainer in step 10.
12. Screw on the sealing cap of the differential adjustment screw.
13. Connect the compound gauge to the suction line.
14. Connect the clamp-on ammeter to the compressor.
15. Increase the suction pressure above the control set point by placing an artificial
load on the unit, if needed.
16. Check your adjustment by closing the suction service valve, slowly, until the unit
unloads. Unloading is indicated by a change in sound level and a drop in current draw.
17. Note the suction pressure that caused the unit to unload, then compare it to the
required 45 psig.
18. Note the suction pressure that caused the unit to load, then compare it to the set
point of 55 psig.
19. Report your findings to the Trainer and ask for your next assignment.
ADVAANCED COURSE
COMPRESSOR OVERHAULING
ADVANCED COURSE
COMPRESSOR OVERHUALING
EXERCISE B:
3.19 TROUBLESHOOT AND REPAIRA SOLENOID OPERATED UNLOADER STEPS
1. Check the operation of the external control source which energizes the unloader
solenoid. Replace if faulty.
2. Check the wiring for continuity between the control source and the solenoid. Replace
if defective.
3. Check the solenoid for proper operation. If there is power at its terminals but it does
not work, check the solenoid coil. Replace the coil if it is open or shorted.
4. Perform the following steps if all the electrical parts are' okay but the unloader still
does not work.
5. Remove the capacity control valve.
6. Check the strainer in the bleed orifice for blockage.
7. Make sure the check valve is moving freely (if you are working on a bypass-type
unloader).
8. Remove the cover plate from the unloader piston assembly (if you are working on a
suction cutoff-type unloader).
ADVAANCED COURSE
COMPRESSOR OVERHAULING
ADVANCED COURSE
COMPRESSOR OVERHUALING