Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Demand Factor-Diversity Factor-Utilization Factor-Load Factor - EEP

Download as pdf or txt
Download as pdf or txt
You are on page 1of 15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Home Technical Articles Article Categories Contact us Subscribe to articles Subscribe to downloads El.
Enginering Guides
EE General guides
Power Substations
Schneider Electric CTs
Siemens Basics of EE
ABB Drives Guides
Industry Automation
Relay control/protection
Alternative Energy
Electrical Software MS Excel Spreadsheets Electrical Design Docs Engineering Resources
Video Lectures Electrical Engineering
PLC Programming Training
Electric Testing and Maintenance (VIDEO)
Network Theorems and Laws
-

DemandFactorDiversityFactorUtilization
FactorLoadFactor
Originally published at Electrical Notes Articles

(1)Demandfactor
Demand Factor = Maximum demand of a system / Total connected load on the system
Demand factor is always less than one.
Example: if a residence having 6000W equipment connected has a maximum demand of
300W,Than demand factor = 6000W / 3300W = 55%.
The lower the demand factor, the less system capacity required to serve the connected load.
Feeder-circuit conductors should have an ampere sufficient to carry the load the ampere of the
feeder-circuit need not always be equal to the total of all loads on all branch-circuits connected to
it.
Remember that the demand factor permits a feeder-circuit ampere to be less than 100% of the
sum of all branch-circuit loads connected to the feeder.

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

1/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Example: One Machine Shop has


Fluorescent fixtures=1 No, 5kw each, Receptacle outlets =1 No, 1500w each.
Lathe=1No, 10 Hp, Air Compressor=1 No, 20 Hp, Fire Pump=1 No, 15 Hp.
After questioning the customer about the various loads, the information is further deciphered as
follows:
1. The shop lights are on only during the hours of 8 a.m. to 5 p.m.
2. The receptacle outlets are in the office only, and will have computers and other small loads
plugged into them.
3. The lathe is fully loaded for 5 minutes periods. The rest of the time is setup time. This
procedure repeats every 15 minutes.
4. The air compressor supplies air to air tools and cycles off and on about half the time.
5. The fire pump only runs for 30 minutes when tested which is once a month after hours.

Calculation:

Lighting Demand Factor = Demand Interval Factor x Diversity Factor.


= (15 minute run time/ 15 minutes) x 1.0 = 1.0
Lighting Demand Load = 5 kW x 1.0 = 5 kW
Receptacle Outlet Demand Factor = Demand Interval Factor x Diversity Factor
= (15 minute run time / 15 minutes) x 0.1 = 0.1
Receptacle Outlet Demand Load = 15 x 1500 watts x 0.1 = 2.25 kW
Lathe Demand Factor = Demand Interval Factor x Diversity Factor.
= (5 minute run time / 15 minutes) x 1.0 =0 .33
Lathe Demand Load = 10 hp x .746 x .33 = 2.46 kW
Air Compressor Demand Factor = Demand Interval Factor x Diversity Factor.
= (7.5 minute run time / 15 minutes) x 1.0 = 0.5
Air Compressor Demand Load = 20 hp x .746 x .5 = 7.46 kW
Fire Pump Demand Factor = Demand Interval Factor x Diversity Factor.
= (15 minute run time/ 15 minutes) x 0.0 = 0.0
Fire Pump Demand Load = 15 hp x .746 x 0.0 = 0.0 kW
Summary of Demand Loads :

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

2/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Equipment

kW

D.F.

Demand KW

Lighting

Receptacle Outlets

22.5

.1

2.25

Lathe

7.5

.33

2.46

Air Compressor

15

0.5

7.46

Fire Pump

11.25

0.0

0.0

TOTAL

61.25 Kw

17.17 Kw

(2)Diversityfactor/simultaneityfactor(Ks)
Diversity Factor = Sum of Individual Max. Demand. / Max. Demand on Power Station.
Diversity Factor = Installed load. / Running load.
Diversity factor is usually more than one. (Since the sum of individual max. demands >Max. Demand)
The load is time dependent as well as being dependent upon equipment characteristics. The
diversity factor recognizes that the whole load does not equal the sum of its parts due to this
time Interdependence (i.e. diverseness).
When the maximum demand of a supply is being assessed it is not sufficient to simply add
together the ratings of all electrical equipment that could be connected to that supply. If this is
done, a figure somewhat higher than the true maximum demand will be produced. This is
because it is unlikely that all the electrical equipment on a supply will be used simultaneously.
The concept of being able to De-rate a potential maximum load to an actual maximum demand is
known as the application of a diversity factor.
70% diversity means that the device in question operates at its nominal or maximum load level
70% of the time that it is connected and turned on.
If total installed full load ampere is twice your running load ampere then the diversity factor is
two.
If total installed full load ampere is four times your load a ampere then the diversity factor is
four.
If everything (all electrical equipment) was running at full load at the same time the diversity
factor is equal to One
Greater the diversity factor, lesser is the cost of generation of power.
Diversity factor in a distribution network is the ratio of the sum of the peak demands of the
individual customers to the peak demand of the network.
This will be determined by the type of service, i.e., residential, commercial, industrial and
combinations of such.
Example-I: A distribution feeder serves 5 houses, each of which has a peak demand of 5 KW.
http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

3/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

The feeder peak turns out to be 20 kw. The diversity is then 20/25 or 0.8. This results from the
timing differences between the individual heating/cooling, appliance usages in the individual
customers.
As supply availability decreases, the diversity factor will tend to increase toward 1.00. This can be
demonstrated when restoring service after outages (called cold starts) as the system initial surge
can be much greater than the historical peak loads.
Example-II: A sub-station has three outgoing feeders:
1.
2.
3.
4.

feeder 1 has maximum demand 10 MW at 10:00 am,


feeder 2 has maximum demand 12 MW at 7:00 pm and
feeder 3 has maximum demand 15 MW at 9:00 pm,
While the maximum demand of all three feeders is 33 MW at 8:00 pm.
Here, the sum of the maximum demand of the individual sub-systems (feeders) is 10 + 12 + 15
= 37 MW, while the system maximum demand is 33 MW. The diversity factor is 37/33 = 1.12.
The diversity factor is usually greater than 1 its value also can be 1 which indicates the maximum
demand of the individual sub-system occurs simultaneously.
Diversity is the relationship between the rated full loads of the equipment downstream of a
connection point, and the rated load of the connection point. To illustrate:

1. The building at these co-ordinates is fitted with a 100A main supply fuse.
2. The distribution board has 2no. 6A breakers, 1no. 20A breaker and 5no. 32A breakers, a total,
potentially, of 192A.
Not all these rated loads are turned on at once. If they were, then the 100A supply fuse would
rupture, as it cannot pass 192A. So the diversity factor of the distribution board can be said to be
192A/100A, or 1.92, or 52%.
Many designers prefer to use unity as the diversity factor in calculations for planning
conservatism because of plant load growth uncertainties. Local experience can justify using a
diversity factor larger than unity, and smaller service entrance conductors and transformer
requirements chosen accordingly.
The diversity factor for all other installations will be different, and would be based upon a local
evaluation of the loads to be applied at different moments in time. Assuming it to be 1.0 may, on
some occasions, result in a supply feeder and equipment rating that is rather larger than the local
installation warrants, and an over-investment in cable and equipment to handle the rated load
current. It is better to evaluate the pattern of usage of the loads and calculate an acceptable
diversity factor for each particular case.
In the case of the example given above, achieving a diversity of 1.0 or 100% would require well
over twice the cross-sectional area of copper cable to be installed in a deep trench underneath a
field, the rebuild of a feeder cabinet to larger dimensions, more substantial overhead supply
cables for a distance exceeding 2km northwards and a different tariff, where one pays rather
more for a kWh than at present. The investment required to achieve 1.0 simply isnt justifiable in
http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

4/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

this particular case.


Diversity factor is mostly used for distribution feeder size and transformer as well as to
determine the maximum peak load and diversity factor is always based on knowing the process.
You have to understand what will be on or off at a given time for different buildings and this
will size the feeder. Note for typical buildings diversity factor is always one. You have to estimate
or have a data records to create 24 hours load graph and you can determine the maximum
demand load for node then you can easily determine the feeder and transformer size.
The diversity factor of a feeder would be the sum of the maximum demands of the individual
consumers divided by the maximum demand of the feeder. In the same manner, it is possible to
compute the diversity factor on a substation, a transmission line or a whole utility system.
The residential load has the highest diversity factor. Industrial loads have low diversity factors
usually of 1.4, street light practically unity and other loads vary between these limits.

DiversityFactorindistributionNetwork
Diversity Factors
Elements of System
Residential

Commercial

General
Power

Large
Industrial

Between individual users

2.00

1.46

1.45

Between transformers

1.30

1.30

1.35

1.05

Between feeders

1.15

1.15

1.15

1.05

Between substations

1.10

1.10

1.10

1.10

From users to transformers

2.00

1.46

1.44

From users to feeder

2.60

1.90

1.95

1.15

From users to substation

3.00

2.18

2.24

1.32

From users to generating station

3.29

2.40

2.46

1.45

DiversityFactorfordistributionswitchboards

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

5/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Number of circuits

Diversity Factor (ks)

Assemblies entirely tested 2 and 3

0.9

4 and 5

0.8

6 to 9

0.7

10 and more

0.6

Assemblies partially tested in every case choose

DiversityFactorforaccordingtocircuitfunction(IEC60439)
Circuits Function

Diversity Factor (ks)

Lighting

0.9

Heating and air conditioning

0.8

Socket-outlets

0.7

Lifts and catering hoist


For the most powerful motor

For the second most powerful motor

0.75

For all motors

0.8

DiversityFactorforanapartmentblock

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

6/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Apartment

Diversity Factor (ks)

2 To 4

5To 19

0.78

10To 14

0.63

15To 19

0.53

20To 24

0.49

25To 29

0.46

30 To 34

0.44

35 To 39

0.42

40To 40

0.41

50 To Above

0.40

Example: 5 storey apartment building with 25 consumers, each having 6 kVA of installed load.
The total installed load for the building is: 36 + 24 + 30 + 36 + 24 = 150 kVA
The apparent-power supply required for the building is: 150 x 0.46 = 69 kVA
It is a matter of common experience that the simultaneous operation of all installed loads of a
given installation never occurs in practice, i.e. there is always some degree of diversity and this
fact is taken into account for estimating purposes by the use of a simultaneity factor / Diversity
Factor (ks).
The Diversity factor ks is applied to each group of loads (e.g. being supplied from a distribution
or sub-distribution board). The determination of these factors is the responsibility of the designer,
since it requires a detailed knowledge of the installation and the conditions in which the
individual circuits are to be exploited. For this reason, it is not possible to give precise values for
general application.
Designing Size of Electrical Switchgear by use of Demand Factor and Diversity
Factor:
Diversity factors are used by utilities for distribution transformer sizing and load predictions.
Demand factors are more conservative and are used by NEC for service and feeder sizing.
Demand factors and diversity factors are used in design.
For example, the sum of the connected loads supplied by a feeder is multiplied by the demand
factor to determine the load for which the feeder must be sized. This load is termed the
maximum demand of the feeder. The sum of the maximum demand loads for a number of sub
feeders divided by the diversity factor for the sub feeders will give the maximum demand load to
be supplied by the feeder from which the sub feeders are derived.
http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

7/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Example-1: Suppose We have four individual feeder-circuits with connected loads of 250 kVA,
200 kVA, 150 kVA and 400 kVA and demand factors of 90%, 80%, 75% and 85%
respectively.Use a diversity factor of 1.5.
Calculating demand for feeder-circuits
250 kVA x 90% = 225 kVA
200 kVA x 80% = 160 kVA
150 kVA x 75% = 112.5 kVA
400 kVA x 85% = 340 kVA
837.5 kVA
The sum of the individual demands is equal to 837.5 kVA.
If the main feeder-circuit were sized at unity diversity: kVA = 837.5 kVA 1.00 = 837.5
kVA.
The main feeder-circuit would have to be supplied by an 850 kVA transformer.
However, using the diversity factor of 1.5, the kVA = 837.5 kVA 1.5 = 558 kVA for the
main feeder.
For diversity factor of 1.5, a 600 kVA transformer could be used.
Example-2: A conveyor belt made up of six sections, each driven by a 2 kW motor. As
material is transported along this belt, it is first carried by section 1, and then each section
in succession until the final section is reached. In this simple example only one section of
conveyor is carrying material at any point in time. Therefore five motors are only handling
no-load mechanical losses (say .1 kW) keeping the belts moving whilst one motor is
handling the load (say 1 kW). The demand presented by each motor when it is carrying its
load is 1 kW, the sum of the demand loads is 6 kW but the maximum load presented by
the system at any time is only 1.5 kW.
Diversity factor =Sum of Individual Max. Demand / Max. Demand = 6 Kw / 1.5 Kw =4.
Demand Factor = Maximum demand / Total connected load = 1.5 Kw / 12 Kw = 0.125.

(3)Loadfactor
Load Factor = Average load. /Maximum load during a given period.
It can be calculated for a single day, for a month or for a year.
Its value is always less than one. Because maximum demand is always more than avg. demand.
It is used for determining the overall cost per unit generated. Higher the load factor, lesser will be the cost
per unit.
Load Factor = Load that a piece of equipment actually draws / Load it could draw (full load).
Example: Motor of 20 hp drives a constant 15 hp load whenever it is on.
The motor load factor is then 15/20 = 75%.
Load factor is term that does not appear on your utility bill, but does affect electricity costs.
Load factor indicates how efficiently the customer is using peak demand.
Load Factor = ( energy (kWh per month) ) / ( peak demand (kW) x hours/month )
http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

8/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

A high load factor means power usage is relatively constant. Low load factor shows that
occasionally a high demand is set. To service that peak, capacity is sitting idle for long periods,
thereby imposing higher costs on the system. Electrical rates are designed so that customers with
high load factor are charged less overall per kWh.
For Example
Customer A High Load Factor
82% load factor = (3000 kWh per month x 100%) / 5 kW x 730 hours/month.
Customer B Low Load Factor
41% load factor = (3000 kWh per month x 100%) / 10kW x 730 hours/month.
To encourage the efficient use of installed capacity, electricity rates are structured so the price per
kWh above a certain load factor is lower. The actual structure of the price blocks varies by rate.

(4)Utilizationfactor(Ku)
In normal operating conditions the power consumption of a load is sometimes less than that
indicated as its nominal power rating, a fairly common occurrence that justifies the application of
an utilization factor (ku) in the estimation of realistic values.
Utilization Factor = The time that a equipment is in use./ The total time that it could be
in use.
Example: The motor may only be used for eight hours a day, 50 weeks a year. The hours of
operation would then be 2000 hours, and the motor Utilization factor for a base of 8760 hours
per year would be 2000/8760 = 22.83%. With a base of 2000 hours per year, the motor
Utilization factor would be 100%. The bottom line is that the use factor is applied to get the
correct number of hours that the motor is in use.
This factor must be applied to each individual load, with particular attention to electric motors,
which are very rarely operated at full load. In an industrial installation this factor may be
estimated on an average at 0.75 for motors.
For incandescent-lighting loads, the factor always equals 1.
For socket-outlet circuits, the factors depend entirely on the type of appliances being supplied
from the sockets concerned.

Maximumdemand
Maximum demand (often referred to as MD) is the largest current normally carried by circuits,
switches and protective devices. It does not include the levels of current flowing under overload
or short circuit conditions.
Assessment of maximum demand is sometimes straightforward. For example, the maximum
demand of a 240 V single-phase 8 kW shower heater can be calculated by dividing the power (8
kW) by the voltage (240 V) to give a current of 33.3 A. This calculation assumes a power factor
of unity, which is a reasonable assumption for such a purely resistive load.
http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

9/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

There are times, however, when assessment of maximum demand is less obvious. For example, if
a ring circuit feeds fifteen 13 A sockets, the maximum demand clearly should not be 15 x 13 =
195 A, if only because the circuit protection will not be rated at more than 32 A. Some 13 A
sockets may feed table lamps with 60 W lamps fitted, whilst others may feed 3 kW washing
machines others again may not be loaded at all.
Lighting circuits pose a special problem when determining MD. Each lamp-holder must be
assumed to carry the current required by the connected load, subject to a minimum loading of
100 W per lamp holder (a demand of 0.42 A per lamp holder at 240 V). Discharge lamps are
particularly difficult to assess, and current cannot be calculated simply by dividing lamp power by
supply voltage. The reasons for this are:
1. Control gear losses result in additional current,
2. the power factor is usually less than unity so current is greater, and
3. Chokes and other control gear usually distort the waveform of the current so that it contains
harmonics which are additional to the fundamental supply current.
So long as the power factor of a discharge lighting circuit is not less than 0.85, the current
demand for the circuit can be calculated from:
current (A) = (lamp power (W) x 1.8) / supply voltage (V)
For example, the steady state current demand of a 240 V circuit supplying ten 65 W fluorescent
lamps would be: I = 10X65X1.8A / 240 = 4.88A
Switches for circuits feeding discharge lamps must be rated at twice the current they are required
to carry, unless they have been specially constructed to withstand the severe arcing resulting from
the switching of such inductive and capacitive loads.

(5)Coincidencefactor
The coincidence factor =Max. demand of a system / sum of the individual maximum
demands
The coincidence factor is the reciprocal of the diversity factor

DemandFactor&LoadFactoraccordingtoTypeofIndustries
Type of Industry

Demand
Factor

Load
Factor

Utilization
Factor (DF x
LF)

Arc Furnace

0.55

0.80

0.44

Induction Furnace

0.90

0.80

0.72

Steel Rolling mills

0.80

0.25

0.20

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

10/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Mechanical/ Electrical
a) Single Shift

0.45

0.25

0.11

b) Double Shift

0.45

0.50

0.22

Cycle Industry

0.40

0.40

0.16

Wire products

0.35

0.40

0.14

Auto Parts

0.40

0.50

0.20

Forgings

0.50

0.35

0.17

a) Working Season

0.60

0.65

0.39

b) Non-Working Season

0.25

0.15

0.04

0.70

0.80

0.56

b) Non-Working Season 0.05

0.30

0.01

Cold Storage

Rice Shellers
a) Working Season

Ice Candy Units


a) Working Season

0.50

0.65

0.32

b) Non-Working Season

0.50

0.10

0.05

a) Working Season

0.80

0.65

0.52

b) Non-Working Season

0.80

0.10

0.08

a) Working Season

0.70

0.25

0.17

b) Non-Working Season

0.10

0.10

0.01

Spinning Mills

0.60

0.80

0.48

Textile Industry

0.50

0.80

0.40

Dyeing and Printing

0.40

0.50

0.20

Ghee Mills

0.50

0.50

0.25

Oil Mills

0.70

0.50

0.35

Solvent Extraction Mills

0.45

0.50

0.22

Ice Factories

Cotton Ginning

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

11/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Plastic

0.60

0.25

0.11

Soap

0.50

0.25

0.12

Rubber (Foot Wear)

0.45

0.35

0.16

Distilleries

0.35

0.50

0.17

Chemical Industry

0.40

0.50

0.20

Gas Plant Industry

0.70

0.50

0.35

Pain and Colour Factory

0.50

0.40

0.20

Sugar

0.30

0.45

0.13

Paper

0.50

0.80

0.40

Flour Mills(Single Shift)

0.80

0.25

0.20

Atta Chakies

0.50

0.25

0.12

Milk Plants

0.40

0.80

0.32

Printing Presses

0.35

0.30

0.10

Repair Workshops

0.40

0.25

0.10

Bottling Plants

0.40

0.35

0.14

Radio Stations

0.55

.0.45

0.25

Telephone exchange

0.50

0.90

0.45

Public Water Works

0.75

0.40

0.30

Medical Colleges

0.60

0.25

0.15

Hospitals

0.25

0.90

0.22

Nursing Homes

0.50

0.50

0.25

Colleges and Schools

0.50

0.20

0.10

Hotels and Restaurants

0.75

0.40

0.30

Marriage Palaces

1.00

0.25

0.25

DemandFactor&LoadFactoraccordingtoTypeofBuildings:
Individual Facilities

Demand
Factor

Load Factor

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

12/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Communications buildings

60-65

70-75

Telephone exchange building

55-70

20-25

Air passenger terminal building

65-80

28-32

Aircraft fire and rescue station

25-35

13-17

Aircraft line operations building

65-80

24-28

Academic instruction building

40-60

22-26

Applied instruction building

35-65

24-28

Chemistry and Toxicology


Laboratory

70-80

22-28

Materials Laboratory

30-35

27-32

Physics Laboratory

70-80

22-28

Electrical and electronics systems


laboratory

20-30

3-7

Cold storage warehouse

70-75

20-25

General warehouse

75-80

23-28

Controlled humidity warehouse

60-65

33-38

Hazardous/flammable storehouse

75-80

20-25

Disposal, salvage, scrap building

35-40

25-20

Hospital

38-42

45-50

Laboratory

32-37

20-25

Dental Clinic

35-40

18-23

Medical Clinic

45-50

20-23

Administrative Office

50-65

20-35

Single-family residential housing

60-70

10-15

Detached garages

40-50

2-4

Apartments

35-40

38-42

Fire station

25-35

13-17

Police station

48-53

20-25

Bakery

30-35

45-60

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

13/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

Laundry/dry cleaning plant

30-35

20-25

K-6 schools

75-80

10-15

7-12 schools

65-70

12-17

Churches

65-70

5-25

Post Office

75-80

20-25

Retail store

65-70

25-32

Bank

75-80

20-25

Supermarket

55-60

25-30

Restaurant

45-75

15-25

Auto repair shop

40-60

15-20

Hobby shop, art/crafts

30-40

25-30

Bowling alley

70-75

10-15

Gymnasium

70-75

20-45

Skating rink

70-75

10-15

Indoor swimming pool

55-60

25-50

Theater

45-55

8-13

Library

75-80

30-35

Golf clubhouse

75-80

15-20

Museum

75-80

30-35

RecommendedEEarticles

AboutAuthor//
Jignesh Parmar
jiguparmar - Jignesh Parmar has completed his B.E(Electrical) from Gujarat University. He is member
of Institution of Engineers (MIE),India. Membership No:M-1473586.He has more than 12 years
http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

14/15

12/31/2014

DemandFactorDiversityFactorUtilizationFactorLoadFactor|EEP

experience in Transmission -Distribution-Electrical Energy theft detectionElectrical Maintenance-Electrical Projects (Planning-Designing-Technical


Review-coordination -Execution). He is Presently associate with one of the
leading business group as a Assistant Manager at Ahmedabad,India. He has
published numbers of Technical Articles in "Electrical Mirror", "Electrical
India", "Lighting India", "Industrial Electrix"(Australian Power Publications)
Magazines. He is Freelancer Programmer of Advance Excel and design useful
Excel base Electrical Programs as per IS, NEC, IEC,IEEE codes. He is
Technical Blogger and Familiar with English, Hindi, Gujarati, French
languages. He wants to Share his experience & Knowledge and help technical enthusiasts to find
suitable solutions and updating themselves on various Engineering Topics.

2014 EEP - Electrical Engineering Portal. All Rights Reserved | Privacy Policy | 34 queries in 0.266
seconds.
Powered by CsanyiGroup
SHARE

TOP
Get
PDF

http://electricalengineeringportal.com/demandfactordiversityfactorutilizationfactorloadfactor

15/15

You might also like