Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Selective Coordination Breaker Application Chart

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Selective Coordination Breaker Application Chart For Molded Case Circuit Breakers fed by Distribution Transformers

Application Note New Information January 2006

What is it?
Selective Coordination, as described in the 2005 National Electric Code (NEC) Article 100, states Localization of an overcurrent condition to restrict outages to the circuit or equipment affected, accomplished by the choice of overcurrent protective devices and their ratings or settings. Essentially in a selectively coordinated system only the breaker directly supplying the overloaded/faulted part of the system will open, thus allowing the rest of the system to operate. Selective coordination is required by NEC Article 620.62 for Elevators, Article 700.27 for Emergency system(s) and Article 701.18 for Legally required standby system(s) and by default Article 517.26 Application of Other Articles that did not change, thus, selective coordination is also required for essential electrical systems in health care facilities. When designing for selective coordination in these systems, if a three-phase dry type distribution transformer is utilized to step down the primary voltage to secondary voltage of 208Y/120 volt level, the following chart can be utilized to insure selective coordination.

Who benefits and why?


Designing a selectively coordinated system requires knowledge about the application, product standards, installation codes and the time current curves of the breakers being used. Testing must be completed and certified in order to identify a panel as selectively coordinated. The following chart is designed to assist application and design engineers in creating a system that meets 2005 NEC requirements for selective coordination.

How will this chart help in designing a selectively coordinated system?


Achieving selective coordination is straightforward when using the following selection table. Follow these steps to ensure that selective coordination is in place: Step 1: Determine the load requirements on the secondary side of the dry type transformer. Step 2: Select the required KVA rating and insure that the selected transformer has impedance greater than or equal to that shown in the chart.1 Step 3: Select the Cutler-Hammer recommended secondary main circuit breaker. Frame size, trip unit, and recommended settings are shown based on 125% of full load current (FLA) per NEC code. Step 4: Select the branch circuit breaker, based on required amperage. Those branch circuit breakers listed in the rows corresponding to the main breaker will provide selective coordination with the chosen secondary main circuit breaker. Selective coordination is based on utilizing selected breakers with appropriate adjustable trip settings.

Note: For some transformer kVA ratings, different types of Cutler-Hammer secondary Main Breakers are shown. The most cost effective secondary main breaker is shown first. Some larger secondary main breaker frame sizes are also shown for the same kVA rating for those applications requiring a wider range of branch breakers. In addition where applicable the existing Series C frame and the new physically smaller Series G frame breakers are shown.

Typical Cutler-Hammer transformer impedance data can be found in the Consulting Applications Guide (CAG) for General Purpose Transformers, TP-1 & K-Factor transformers. For Harmonic Mitigating and specialty transformers refer to Eaton Corp.

Example: Required kVA to serve the 208Y/120 volt load is 112.5 kVA and the largest branch breaker that will be required is 250 amperes. The least expensive recommended secondary main circuit breaker is the 400Ampere KD frame with a 400A/Trip setting. If a 100% rated secondary main breaker was desired, then a CKD would be selected. If a 400 ampere branch breaker was required, then either the series C type LD or the Series G type LG breaker could be selected with a 600 ampere trip unit set at 400 amperes. Table 1.1 PowR-Line 1A, 3A, 4B Panelboard Selective Coordination (Secondary Side of Distribution Transformers) @ 208Y / 120 Volt
Transformer
Secondary Transformer Full Load Let-through % Z (Min.) Current AIC (RMS) Note: (3) (FLA)

Secondary Main MCCB

Branch Breaker

KVA

Secondary Voltage

MCCB Type / Frame

Trip Unit

Branch Type that MCCB Trip Rating would be Selective Max. Frame 125% FLA [IT-Interchangeable Trip, Rating (NEC 450.3(B))
NIT-Non Interchangeable Trip]

Max Trip Rating

15

208Y/120

42

>3.8

1096

Series C [FDB or FD600V] (225A Frame)

Thermal / Magnetic (1)

52

60A

BAB

100A

<60A

30

208Y/120

83

>7.5

1110

Series C JD (250A Frame)

BAB Thermal / Magnetic (1) 104 125A [FDB (NIT) & FD (IT) 600V] BAB 104 125A [FDB (NIT) & FD (IT) 600V] BAB 156 250A T.U. Set @ 175A [FDB (NIT) & FD (IT) 600V] BAB

100A

<60A

225A

<100A

30

208Y/120

83

>3.7

2251

Electronic Series C (KES KD-80% CKD-100% Digitrip RMS (400A Frame) 310) (2)

100A

<60A

225A

<100A

45

208Y/120

125

>5.55

2251

Electronic Series C (KES KD-80% CKD-100% Digitrip RMS (400A Frame) 310) (2)

100A

<60A

225A

<100A

100A

<100A

75

208Y/120

208

>6.15

3385

Electronic Series C (KES KD-80% CKD-100% Digitrip RMS (400A Frame) 310) (2)

260

400A T.U. Set @ 300A

ED-240V, [FDB (NIT) & FD (IT) 600V] Series C JD BAB

225A

<225A

250A

<250A

100A

<100A

112.5

208Y/120

312

>9.2

3394

Electronic Series C (KES KD-80% CKD-100% Digitrip RMS (400A Frame) 310) (2)

390

400A T.U. Set @ 400A

ED-240V, [FDB (NIT) & FD (IT) 600V] Series C JD

225A

<225A

250A

<250A

112.5

208Y/120

312

>3.15

9913

Series C Electronic LD -80% (LES Digitrip CLD-100% RMS 310) (2) (600A Frame) Series G LG-80% Electronic (LT trip unit)

ED-240V, [FDB (NIT) & FD (IT) 600V] 390 600A T.U. Set @ 400A Series C JD Series C DK, KD-80% CKD-100%

225A

<225A

250A

<250A

400A

<400A

(Table 1.1 continued)


Series C Electronic LD -80% (LES Digitrip CLD-100% RMS 310) (2) (600A Frame) Series G LG-80% Electronic (LT trip unit) ED-240V, [FDB (NIT) & FD (IT) 600V] Series C JD Series C DK, KD-80% CKD-100% ED-240V, [FDB (NIT) & FD (IT) 600V] Series C ND-80% Electronic CND-100% (Digitrip Series G RMS 310) (2) NGS-80% (1200A Frame) Series C JD 520 1200A T.U. Set @ 600A Series C DK, KD-80% CKD-100% Series C LD-80% CLD-100% Series G L630E-80% ED-240V, [FDB (NIT) & FD (IT) 600V] Series C ND-80% Electronic CND-100% (Digitrip Series G RMS 310) (2) NGS-80% (1200A Frame) Series C JD 781 1200A T.U. Set @ 800A Series C DK, KD-80% CKD-100% Series C LD-80% CLD-100% Series G L630E-80% ED-240V, [FDB (NIT) & FD (IT) 600V] Series C ND-80% Electronic CND-100% (Digitrip Series G RMS 310) (2) NGS-80% (1200A Frame) Series C JD 1041 1200A T.U. Set @ 1200A Series C DK, KD-80% CKD-100% Series C LD-80% CLD-100% Series G L630E-80% 225A 250A <225A <250A

150

208Y/120

416

>4.2

9913

520

600A T.U. Set @ 600A

400A

<400A

225A

<225A

250A

<250A

150

208Y/120

416

>2.4

17348

400A

<400A

600A

<600A

600A

<600A

225A

<225A

250A

<250A

225

208Y/120

625

>3.5

17844

400A

<400A

600A

<600A

600A

<600A

225A

<225A

250A

<250A

300

208Y/120

833

>4.7

17717

400A

<400A

600A

<600A

600A

<600A

(Table 1.1 continued)


Series C RD-80% CRD-100% Series G RGU-80% Series C RD-80% CRD-100% Series G RGU-80%

500

208Y/120

1388

>6.3

22030

Electronic (Digitrip (2) RMS 310)

1735

2000A T.U. Set @ 2000A

QPHW, QBHW

100A

<100A

500

208Y/120

1388

>1.3

106759

Electronic (Digitrip (2) RMS 310)

1735

2000A T.U. Set @ 2000A

EDC-240V FDC-600V (2 & 3 Pole only)

225A

<225A

JD Series C RD-80% CRD-100% Series G RGU-80%

250A

<250A

500

208Y/120

1388

>2.4

57828

Electronic (Digitrip (2) RMS 310)

DK, KD-80% 1735 2000A T.U. Set @ 2000A Series C LD-80% CLD-100% Series G L630E-80%

400A

<250A

600A

<600A

600A

<600A

Notes: (1) Magnetic trip set to 10x (2) Digitrip OPTIM 550 electronic trip unit available (3) Typical Cutler-Hammer transformer impedance data can be found in the Consulting Applications Guide (CAG) for General Purpose Transformers, TP-1 & K-Factor transformers. For Harmonic Mitigating and specialty transformers refer to Eaton Corp.

IMPORTANT: Additional testing at 480Y/277 Vac and using other branch circuit breakers is in progress. Please contact Eaton Corporation for results.

National Electric Code and NEC are registered trademarks of the National Fire Protection Agency, Franklin, MA.

2006 Eaton Corporation All Rights Reserved Printed in USA January 2006

You might also like