P-752 Unit8 PDF
P-752 Unit8 PDF
P-752 Unit8 PDF
Precast Concrete - 1
Precast Concrete - 2
Precast Concrete - 3
Precast Concrete - 4
Precast Concrete - 5
B
40'-0"
C
24'-0"
D
24'-0"
E
24'-0"
F
40'-0"
4'-0"
24'-0"
24'-0"
Prestressed
hollow core
slabs
6'-0"
14'-0"
24'-0"
72'-0"
6'-8"
8" concrete
masonry wall
152'-0"
Precast Concrete - 6
HORIZONTAL DIAPHRAGMS
Structural diaphragms are horizontal or nearly horizontal
elements, such as floors and roofs, that transfer seismic inertial
forces to the vertical seismic force-resisting members.
Precast concrete diaphragms may be constructed using topped
or untopped precast elements depending on the Seismic Design
Category.
Reinforced concrete diaphragms constructed using untopped
precast concrete elements are not addressed specifically in the
Standard, in the Provisions, or in ACI 318.
Topped precast concrete elements, which act compositely or
noncompositely for gravity loads, are designed using the
requirements of ACI 318 Section 21.11.
Precast Concrete - 7
Precast Concrete - 8
Precast Concrete - 9
Fpx =
Fi
i=x
n
wi
w px
i= x
Precast Concrete - 10
Level
Roof
4
3
2
1
wi
(kips)
861
963
963
963
963
wi
i=x
(kips)
861
1,824
2,787
3,750
4,713
Fi
(kips)
175
156
117
78
39
Fi = Vi
i=x
(kips)
175
331
448
526
565
wpx
(kips)
807
855
855
855
855
Fpx
(kips)
164
155
137
120
103
Precast Concrete - 11
W1
W1
W2
F
40'-0"
3 at 24'-0" = 72'-0"
152'-0"
40'-0"
Precast Concrete - 13
Precast Concrete - 14
8.1
7
72'-0"
8.1
3
8.1
8
8.1
5
8.1
4
24'-0"
36'-0"
4'-0"
Precast Concrete - 15
Precast Concrete - 16
Joint Forces
Joint 1 Transverse forces:
Shear, Vu1 = 1.15 kips/ft (36 ft) = 41.4 kips
Moment, Mu1 = 41.4 kips (36 ft / 2) = 745 ft-kips
Chord tension force, Tu1 = M/d = 745 ft-kips / 71 ft
= 10.5 kips
Joint 2 Transverse forces:
Shear, Vu2 = 1.15 kips/ft (40 ft) = 46 kips
Moment, Mu2 = 46 kips (40 ft / 2) = 920 ft-kips
Chord tension force, Tu2 = M/d = 920 ft-kips / 71 ft
= 13.0 kips
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 17
Joint Forces
Joint 3 Transverse forces:
Shear, Vu3 = 46 kips + 0.86 kips/ft (24 ft) 38.3 kips = 28.3 kips
Moment, Mu3 = 46 kips (44 ft) + 20.6 kips (12 ft) - 38.3 kips (24
ft) = 1,352 ft-kips
Chord tension force, Tu3 = M/d = 1,352 ft-kips / 71 ft = 19.0 kips
Precast Concrete - 18
Precast Concrete - 19
Precast Concrete - 20
Precast Concrete - 21
Joint 5 Forces
Joint 5 Longitudinal forces:
Wall force, F = 153 kips / 8 = 19.1 kips
Wall shear along each side of wall, Vu5 = 19.1 kips [2(36 ft) / 152 ft]/2 = 4.5 kips
Collector force at wall end, Tu5 = Cu5 = 19.1 kips - 2(4.5 kips) = 10.1 kips
Precast Concrete - 22
Precast Concrete - 23
Precast Concrete - 24
(2) #4
(collector bars)
Interior Joint
31 2"
21 2" 2"
#3 x 4'-0" (behind)
at each joint
between planks
Anchorage
region for shear
reinforcement
Instructional Material Complementing FEMA 752, Design Examples
11 2" 21 2"
2"
2"
Precast Concrete - 25
Precast Concrete - 26
standard hooks
2'-2
"
#3 x
"
2'-2
#3x 2'-6"
embedded in grouted
edge cell of plank. Provide
2 sets for each plank.
standard hook
grouted into
each key joint
2" cover
71 2"
(2) #5 in
masonry
bond beam
(1) #5
continuous
in joint to
anchor hooks
Vertical
reinforcement
in wall
Precast Concrete - 27
Precast Concrete - 28
#3x 2'-6"
standard hook
grouted into
each key joint
2"
cover
(2) #5 bars
in joint
(chord bars)
(2) #5 in
bond beam
Precast Concrete - 29
Precast Concrete - 30
8.1
12
8.1
10
8.1
11
Precast Concrete - 31
WWF bend
down into
chord
3"
21 2" min
(concrete
topping)
3"
(2) #8 bars
(chord bars)
Prestressed
hollow core
plank with
roughened
top surface
21 2"
Grouted
chord / collector
element along exterior
edge of precast plank
Precast Concrete - 32
WWF
3"
(2) #8
(collector bars)
Vertical
reinforcement
#3x4'-0" at 16" to
lap with WWF
21 2"
3"
21 2"
1" clear
WWF 10 x 10
W4.5 x W4.5
(2) #8
collector bars
(2) #5 in
masonry
bond beam
Precast Concrete - 33
25'-0"
25'-0"
25'-0"
25'-0"
15'-0"
8'-0"
40'-0"
26 IT 28
precast
beams
8" precast
shear walls
40'-0"
120'-0"
40'-0"
25'-0"
Precast Concrete - 34
Value
I = 1.0
0.266
0.08
D
1.59
2.4
0.425
0.192
0.283
0.128
B
Bearing Wall System
Intermediate Precast Shear Walls
4
2.5
4
Precast Concrete - 35
Precast Concrete - 36
Base Shear
Equation 12.8-2:
S DS
0.283
CS = =
= 0.0708
R/I
41
except that it need not exceed the value from Standard Equation 12.8-3
computed as:
S D1
0.128
=
CS =
= 0.110
T ( R / I ) 0.29(4 / 1)
where T is the fundamental period of the building computed using the
approximate method of Standard Equation 12.8-7:
x
0.75
=
Ta C=
(0.02)(36)=
0.29sec
r hn
Precast Concrete - 37
12'-0"
95 kips
12'-0"
63.5 kips
12'-0"
31.5 kips
Grade
V = F = 190 kips
25'-0"
Precast Concrete - 38
12'-0"
12'-0"
95 kips
12'-0"
63.5 kips
12'-0"
31.5 kips
T
9"
12'-0"
23'-6"
9"
ME = (95 kips)(36 ft) + (63.5 kips)(24 ft) + (31.5 kips)(12 ft) = 5,320 ft-kips
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 39
Overturning
Using the load combinations described above, the vertical loads
for combining with the overturning moment are computed as:
Pmax = 1.26D + 0.5L + 0.2S = 397 kips
Pmin = 0.843D = 239 kips
The tension reinforcement can be found from a simple couple.
The effective moment arm is:
jd = 25 - 1.5 = 23.5 ft
=107kips
jd
2
23.5
2
Precast Concrete - 40
End Reinforcement
The required reinforcement is:
As = Tu/fy = (107 kips)/[0.9(60 ksi)] = 1.98 in2
Use two #9 bars (As = 2.0 in2) at each end with Type 2 couplers
for each bar at each panel joint. Since the flexural reinforcement
must extend a minimum distance, d, (the flexural depth) beyond
where it is no longer required, use both #9 bars at each end of
the panel at all three levels for simplicity
At this point a check per ACI 318 Section 16.5 will be made.
Bearing walls must have vertical ties with a nominal strength
exceeding 3 kips per foot and there must be at least two ties per
panel. With one tie at each end of a 25-foot panel, the demand
on the tie is:
Tu = (3 kip/ft)(25 ft)/2 = 37.5 kips
The two #9 bars are more than adequate for the ACI
requirement.
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 41
Precast Concrete - 42
As f y jd + Pmax ( jd / 2)
=
ME
5,320 ft-kips
1.41
Precast Concrete - 43
#5,see (c)
Welded wire
reinforcement
Plate 3 8x4x1'-0"
L4x3x516x0'-8"
LLH
4"
H.A.S.
Plate 1 2x12x1'-6"
Drypack
C8x18.75
Precast Concrete - 44
Weld at face plates, using Table 8-8 in AISC Manual (13th edition):
Vn= 0.75(1.73)(1.0)(4)(8)(2) = 83.0 kip
Bearing of concrete at steel channel:
fc = f(0.85f'c) = 0.65(0.85)(5 ksi) = 2.76 ksi
Precast Concrete - 45
Precast Concrete - 46
Precast Concrete - 47
Precast Concrete - 48
Precast Concrete - 49
12 DT at 8'-0" = 96'-0"
24LH03
at 4'-0" o.c.
48'-0"
15 DT at 8'-0" = 120'-0"
Joist girder
(typical)
48'-0"
24LH03
at 4'-0" o.c.
Steel tube
columns
3 DT at 8'-0" =
16'-0"
24'-0"
O.H.
door
5 DT at 8'-0" = 40'-0"
16'-0"
3 DT at 8'-0" =
O.H.
door
24'-0"
Precast Concrete - 50
Value
Occupancy Category II
I = 1.0
SS
1.5
S1
0.60
Site Class
Fa
1.0
Fv
1.3
SMS = FaSS
1.5
SM1 = FvS1
0.78
1.0
0.52
Wall Type
2.5
Cd
Precast Concrete - 51
Precast Concrete - 52
Flexible diaphragm
Equivalent lateral force method
Load combinations
Earthquake forces
Building weight
Base shear
Horizontal distribution without torsion for
flexible diaphragm
Precast Concrete - 53
8'-0"
Vlu
D1
D1
20'-0"
D2
2'-0"
2'-0"
2'-0"
2'-0"
DT leg
Vu = 4.25 kips/panel
Foundation
Vlu
T
Precast Concrete - 54
Precast Concrete - 55
Longitudinal Direction
The maximum tension for the connection at the base of the precast
panel to the concrete footing is governed by the seismic overturning
moment and the dead loads of the panel and the roof.
At the base:
ME = (4.25 kips)(20 ft) = 85.0 ft-kips
Dead loads:
SD = 2(1.08) + 7.73 = 9.89 kips
1.4D = 13.8 kips
0.7D = 6.92 kips
Compute the tension force due to net overturning based on an
effective moment arm, d, of 4.0 feet (the distance between the DT
legs). The maximum is found when combined with 0.7D:
Tu = ME/d - 0.7D/2 = 85.0/4 - 6.92/2 = 17.8 kips
Precast Concrete - 56
61
x
2"
My
t
L5x31 2x3 4x61 2
(LLV)
Tu '
Vu '
CG
Mx
Mz
Mz
yB
My
Mx
Fillet
weld "t"
1"
4"
Vu'
Fillet
weld
Tu '
Vu'
Tu '
Vu'
2516"
Tu '
k = 1316"
Location
of plastic
hinge
Precast Concrete - 57
6.5 ( 0.75)2
=
=
Fy Z 0.9 ( 50 )
0.9=
41.1in kips
bM n
4
Using ACI 318 Section 21.4.3, the tension force for the remainder
of this connection and the balance of the wall design are based
upon a probable strength equal to 150 percent of the yield strength.
Thus:
M n (1.5)
=
T pr
=
3.5 k
( 50 )( 6.5) (0.75)2 / 4 =
1.5
0.9(3.5 1.1875)
27.0kips
Precast Concrete - 58
T pr 27.0
=
1.52
=
Tu 17.8
The shear on the connection associated with this force in the angle is:
T pr
V pr = VE 4.25
=
1.52 = 6.46kips
Tu
Check the welds for the tension force of 27.0 kips and a shear force 6.46
kips.
Precast Concrete - 59
Py L3
19.83(2.313 )
y ,idealized
= =
= 0.0122
3
3EI 3 ( 29,000 ) (6.5 0.75 / 12)
Precast Concrete - 60
V pr + T pr
=
Precast Concrete - 61
15 y 15 ( 50 / 29,000 )
=
= 0.06897
p =
0.75 / 2
d /2
Lp
0.75
=
sh p L p L =
+=
0.012 0.112in.
+ y 0.06897 ( 0.75) 2.31
2
2
Precast Concrete - 62
Mz
My
X
Z
Precast Concrete - 63
Precast Concrete - 64
Ductile Connectors
For moment frames constructed using ductile
connections, ACI 318 requires that plastic hinges be
able to form in the connection region. All of the
requirements for special moment frames must still be
met, plus there is an increased factor that must be
used in developing the shear demand at the joint.
It is interesting to note that while Type 2 connectors
can be used anywhere (including in a plastic hinge
region) in a cast-in-place frame, these same
connectors cannot be used closer than h/2 from the
joint face in a ductile connection. The objective of
Type 2 connectors is that they relocate the yielding
away from the connector, into the bar itself.
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 65
Ductile Connectors
Type 2 coupler
Precast column
Precast Concrete - 66
Strong Connections
Lb
Lclr
(3) #10 t&b
(3) #14
hooks t&b
H col
lcoupler
hbeam
Plastic hinge
location
Type 2 coupler
hcol
Precast Concrete - 67
3.0
M n= As Fy d = 0.9 ( 3)(1.27 )( 60 ) 33
/ 12= 540 ft kips
2
2
Precast Concrete - 68
M u , joint = M pr
Lb hcol
Lclr
1.25
1.25
=
M pr M n = 540= 750 ft kips
0.9
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 69
30 36 / 12
= 843 ft kips
24
5.3
which is greater than the load at the connection (843 ftkips) when the plastic hinge develops.
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 70
Precast Concrete - 71
Precast Concrete - 72
Precast Concrete - 73
Questions
Precast Concrete - 74
Title slide
The presentation will cover examples of application of the provisions for earthquake
design to precast concrete systems.
Overview slide:
Scope of the chapter: This chapter illustrates the seismic design of precast
concrete members using the NEHRP Recommended Provisions (referred to
herein as the Provisions) for buildings in several different seismic design
categories.
Scope of the presentation: The presentation does not repeat the text that
describes provisions or procedures, but instead is focused on design examples
which illustrate these points through the applications of those provisions.
Horizontal diaphragms examples; 1st slide shows the floor plan that is used for the
example. The layout is the same used in Chapter 10, Sec. 10.2, which illustrates
the design of a five-story masonry residential building. The plan dimensions of the
floor are 152 ft x 72 ft. The interior portion of the plan includes walls spaced at 24 ft
in the transverse direction. The 40 ft bays at either end of the plan include walls
spaced at 24 ft in the longitudinal direction.
First slide to introduce the design of untopped precast diaphragms using hollow
core floor plank. The design is linked to the Chapter 10 masonry wall example for
SDC B using Birmingham., Alabama. The use of seismic acceleration parameters
for New York for SDC C differs from Chapter 10.
Weight used for the diaphragm design is given for floor and roof. The weight used
for the design of the diaphragm does not include the weight of walls parallel to the
direction of loading because the wall weight does not contribute to the inertial force
in the floor. That must be collected and distributed to the walls,
Equation 12.10-1 for the calculation of diaphragm design forces is provided in this
slide. Note that this equation is different from the equation for the vertical
distribution of base shear used for the design of the lateral force-resisting system.
That distribution must also be considered in the design of the diaphragm
The table with the values of the calculated diaphragm forces is given for the
Birmingham example.
The slide presents the calculation of the maximum and minimum limits for
diaphragm design forces. The maximum diaphragm design forces from the
provisions are significantly less than calculated by Eq. 12.10-1, and these governs
the design forces.
The load and reaction diagram from the example is shown to illustrate the support
provides by the walls to a continuous beam. The uniform diaphragm loads vary by
building segment because the transverse walls on the ends are included in the
distributed weights, but the supporting walls in the center section are not included in
the diaphragm load.
Based on the assumption that the diaphragm in this example is rigid, the reaction
forces on the four transverse walls are taken as equal. The slide shows the
calculation of the uniform lateral force in each section of the building based on the
diaphragm load for each section.
The plan view of the floor is repeated with the dimensions removed and the critical
regions for design identified with the numbered circles and arrows for reference to
detailed sections.
The slide bullet points describe the five critical regions shown in the previous slide.
These locations are used in the design example for the calculation of forces and to
illustrate the reinforcing detailing.
Calculations for joint forces at critical regions 1 and 2 are given. These calculations
follow simple principles of statics.
Calculation for joint forces at critical regions 3 and 4 (longitudinal) are given.
The slide repeats text from the Guide covering out-of-plane effects. Three slides are
included to show the requirements and calculations for out-of-plane forces at Joint
4. The first slide shows the calculation for minimum out-of-plane horizontal force.
The second slide for out-of-plane forces at joint 4 gives the calculations for
minimum masonry wall anchorage and minimum bearing wall anchorage
The third slide for Joint 4 illustrates the force calculation if the diaphragm is
considered flexible
Force calculations for Joint 5 are shown for longitudinal and transverse forces. The
transverse force effect is shear flow, calculated using VQ/I to determine the total
joint force.
The floor plan is shown with Joint 1 highlighted to identify the application of the
following calculations. This joint is the first interior transverse joint away from the
transverse wall between the outer and inner floor plates.
Calculations for Joint 1 reinforcement are provided. The design must provide
sufficient reinforcement for chord forces as well as shear friction connection forces.
The section of bars and placement is given. The selection of bars is given to satisfy
the steel area calculation.
Figures from the example that illustrate the placement of reinforcement are
provided in this slide. At the interior joint, two horizontal bars are place in the
grouted joint between the ends of plank and parallel with the support beam. In the
second figure, the flange of the plank is broken at he edge to open the edge core
and permit placement of #4 bars and grout in the core, filling the profile and joint to
the finished floor.
Floor plan with highlighting for joint 2 is shown to identify joint. This joint is the joint
between the outside diaphragm and the transverse wall between the outside and
inside floor plates.
Detail at Joint 2 is shown to show the placement of reinforcing in the masonry wall
an in an opened core of the hollow core plank. Note the detail shows diagonal bars
to transfer forces mostly in tension and compression rather than by dowel shear or
shear friction. The block just below the bearing in the masonry wall is a bond beam
with two #5 bars grouted in as part of the diaphragm reinforcement.
Floor plan is shown with Joint 4 highlighted. This joint is between the outside
diaphragm plank and the outside longitudinal wall,
The example for a topped precast floor is introduced with requirements of the
provisions for higher seismic design categories. The seismic force for this example
is compared to the SDC B example. Note also that it is the diaphragm force used
to determine the collector and transfer requirement, and not the distributed lateral
force used for the vertical elements of the lateral force-resisting system.
The floor plan showing walls and the diaphragm layout is shown for the SDC D
example. This is the same building layout used in the earlier examples but the joints
between the hollow core plank in the interior areas of the floor have been removed.
This reflects the presence of cast-in-place concrete topping with welded wire
reinforcement to carry diaphragm forces, so the location of these interior joints is
not a design consideration.
The detail along an edge of the hollow core plan with topping is shown to illustrate
the placement of reinforcement. (Calculation of diaphragm design forces follow the
same procedures used in the earlier example, and are not repeated due to limits in
time. Figures are provided to show the differences in reinforcement with the topped
system.) In this section, the flange above the outside core in the plan is broken
away to open the core to permit placement of the edge reinforcement. The cast-inplace concrete topping covers the top flange and also fills the core void with the
reinforcing bars.
Two details at interior joints with topping are shown to illustrate the placement of
reinforcement. (Calculation of diaphragm design forces follow the same procedures
used in the earlier example, and are not repeated due to limits in time. Figures are
provided to show the differences in reinforcement with the topped system.) At the
interior support beam, the space between the ends of the hollow core plank has the
reinforcing bars. The cast-in-place concrete topping concrete fills this joint and fills
part of the ends of the hollow cores as it flows away from the joint. Sometimes
plastic or crumpled paper dams are stuffed into the cores to limit the flow of the
joint concrete beyond the end of the plank. At the wall support, the wall cores are
shown reinforced and grouted for the plank bearing. The space between the ends
of the plank is grouted and excess concrete flows into the cores. The topping
concrete with transverse reinforcement is above this. The upper level of masonry
wall is built above the floor toppping and is ties to the wall below with vertical
reinforcement.
The precast walls are estimated to be 8 inches thick for building mass calculations.
These walls are normal-weight concrete with a 28-day compressive strength, f'c, of
5,000 psi. Reinforcing bars used at the ends of the walls and in welded connectors
are ASTM A706 (60 ksi yield strength). The concrete for the foundations and
below-grade walls has a 28-day compressive strength, f'c, of 4,000 psi.
Design example for intermediate precast walls in three-story office. Slide shows the
seismic parameters from the Table in the example.
The slide provides the description of the intent of design for the intermediate
precast concrete wall system. The design develops a ductile mechanism for energy
dissipation, and then designs other connection elements in the load path to remain
elastic.
Although it would be desirable to force yielding to occur in a significant portion of
the connections, it frequently is not possible to do so with common configurations of
precast elements and connections. The connections are often unavoidable weak
links. Careful attention to detail is required to assure adequate ductility in the
location of first yield and to preclude premature yielding of other connections.
Calculation of base shear from the equivalent lateral force equations of the
provisions is shown with the values determined in the example. Note that this force
is substantially larger than a design wind would be. If a nominal 20 psf were
applied to the long face and then amplified by a load factor of 1.6, the result would
be less than half this seismic force already reduced by an R factor of 4.
Vertical distribution of base shear is shown in the example calculations for the
entire structure.
The seismic lateral force ,Fx, at any level is determined in accordance with
Standard Section 12.8.3.
Since the period, T, is less than 0.5 seconds, k = l in both building directions. The
total lateral forces are calculated as:
Roof: Cvr = 0.50; Fr = 190 kips
Third Floor: Cv3 = 0.333; F3 = 127 kips
Second Floor: Cv2 = 0.167; F2 = 63 kips
Since torsion is assumed to be carried by the walls in the transverse direction, the
forces to each of two walls (as shown in the slide) in the direction under
consideration is half the total, and these are the forces illustrated in the figure.
The free-body diagram for one longitudinal wall is shown in Figure 8.2-4. The
tension connection at the base of the precast panel to the below-grade wall is
governed by the seismic overturning moment and the dead loads of the panel and
supported floors and roof. In this example, the weights for an elevator penthouse,
with a floor and equipment load at 180 psf between the shafts and a roof load at
20 psf, are included. The weight for the floors includes double tees, ceiling, and
partitions (total load of 70 psf) but not beams and columns. Floor live load is 50 psf,
except 100 psf is used in the elevator lobby. Roof snow load is 30 psf.
Design shear panels to resist overturning by means of reinforcing bars at each end
with a direct tension coupler at the joints.
The results of the calculation for overturning and selection of the end reinforcing is
covered on this slide.
Although the transverse direction walls are covered in the guide, they are not
covered here in the interest of time.
Notes on base shear design for the guide are covered here.
The joint opening would concentrate the shear stress on the small area of the drypacked joint that remains in compression. This distribution can be affected by the
shims used in construction. With care taken to detail the grouted joint, shear friction
can provide a reliable mechanism to resist this shear.
Base shear design is based 1.5 times the strength of the yielding connection in
accordance with the provisions.
The base shear connection is shown in the figure and is to be flexible vertically but
stiff horizontally in the plane of the panel. The vertical flexibility is intended to
minimize the contribution of these connections to overturning resistance, which
would simply increase the shear demand.
The figure illustrates a welded connection with an embedded plate with tail bars
developed in the wall and a foundation plate anchored with headed anchor studs.
The connection is made with two face plates, one on each side of the wall.
All of the links in the load path should be checked . The slide shows the
calculations for shear strength of the connection by checking this load path.
The bearing strength is considered in the load path, and the calculations for the
bearing strength limit of the connection are included.
Shear connection design summary is given and the selection of the number of
connections is shown in this slide.
The total demand moment, for which the entire system is proportioned, is 5,320 ftkips. Thus, these connections will add approximately 5 percent to the resistance,
and ignoring this contribution is reasonable. If a straight plate measuring 1/4 inch
by 8 inches (which would be sufficient) were used and if the welds and foundation
embedment did not fail first, the tensile capacity would be 72 kips each, a factor of
42 increase over the angles, and the shear connections would have the unintended
effect of more than doubling the flexural resistance, which would require a much
higher shear force to develop a plastic hinge at the wall base.
The design example is for a single story building with perimeter shear wall panels.
This example shows the design for intermediate precast concrete walls in SDC D.
The structure has 8-foot-wide by 12.5-inch-deep prestressed double tee (DT) wall
panels. The roof is light gage metal decking spanning to bar joists that are spaced
at 4 feet on center to match the location of the DT legs. The center supports for the
joists are joist girders spanning 40 feet to steel tube columns. The vertical seismic
force-resisting system is the precast/prestressed DT wall panels located around the
perimeter of the building. The average roof height is 20 feet, and there is a 3-foot
parapet.
The slide describes the precast building.
The figure shows a plan of the building. The building is 120 ft long and 96 ft wide.
The precast wall panels used in this building are typical DT wall panels commonly
found in many locations but not normally used in southern California. For these
wall panels, an extra 1/2 inch has been added to the thickness of the deck (flange).
This extra thickness is intended to reduce cracking of the flanges and provide cover
for the bars used in the deck at the base.
The wall panels are normal-weight concrete with a 28-day compressive strength of
f'c = 5,000 psi. Reinforcing bars used in the welded connections of the panels and
footings are ASTM A706 (60 ksi). The concrete for the foundations has a 28-day
compressive strength of f'c = 4,000 psi.
In Standard Table 12.2-1 the values for special reinforced concrete shear walls are
for both cast-in-place and precast walls. In Section 2.2, ACI 318 defines a special
structural wall as a cast-in-place or precast wall complying with the requirements of
21.1.3 through 21.1.7, 21.9 and 21.10, as applicable, in addition to the
requirements for ordinary reinforced concrete structural walls. ACI 318
Section 21.10 defines requirements for special structural walls constructed using
precast concrete, including that the wall must satisfy all of the requirements of ACI
318 Section 21.9.
Unfortunately, several of the requirements of ACI 318 Section 21.9 are problematic
for a shear wall system constructed using DT wall panels. Therefore, these walls
will be designed using the ACI category of intermediate precast structural walls.
Design parameter table for the example building using intermediate precast
concrete walls is given in the slide.
A summary of the requirements and design intent for intermediate precas.t concrete
shear walls is provided.
Yielding will develop in the dry connection at the base by bending in the horizontal
leg of the steel angle welded between the embedded plates of the DT and footing.
The horizontal leg of this angle is designed in a manner to resist the seismic
tension of the shear wall due to overturning and then yield and deform inelastically.
The connections on the two legs of the DT are each designed to resist 50 percent
of the shear. The anchorage of the connection into the concrete is designed to
satisfy the 1.5Sy requirements of ACI 318 Section 21.4.3. Careful attention to
structural details of these connections is required to ensure tension ductility and
resistance to large shear forces that are applied to the embedded plates in the DT
and footing.
Design assumptions and steps in calculation for lateral forces are listed:
The metal deck roof acts as a flexible horizontal diaphragm to distribute seismic
inertia forces to the walls parallel to the earthquake motion (Standard Sec.
12.3.1.1).
The building is regular both in plan and elevation.
The redundancy factor, , is determined in accordance with Standard
Section 12.3.4.2. For this structure, which is regular and has more than two
perimeter wall panels (bays) on each side in each direction, = 1.0. The structural
analysis to be used is the ELF procedure (Standard Sec. 12.8) as permitted by
Standard Table 12.6-1.
Orthogonal load combinations are not required for flexible diaphragms in Seismic
Design Category D (Standard Sec. 12.5.4).
The basic load combinations (Standard Sec. 12.4.2.3) require that seismic forces
and gravity loads be combined in accordance with the following factored load
combinations:
(1.2 + 0.2SDS)D rQE + 0.5L+ 0.2S
(0.9 - 0.2SDS)D rQE + 1.6H
At this flat site, both S and H equal 0. Note that roof live load need not be combined with
seismic loads, so the live load term, L, can be omitted from the equation. Therefore:
1.4D + rQE
0.7D - rQE
These load combinations are for the in-plane direction of the shear walls.
The earthquake force considerations are listed by bullet points due to the limited time for the
presentation. The detailed calculations can be found in the guide.
The total shear along each side of the building is V/2 = 46.75 kips. The maximum
shear on longitudinal panels (at the side with the openings) is:
Vlu = 46.75/11 = 4.25 kips
On each side, each longitudinal wall panel resists the same shear force as shown
in the free-body diagram of the figure, where D1 represents roof joist reactions and
D2 is the panel weight.
Base connection design yielding and design for overstrength of other connection
actions. The slide describes the connection and the actions considered.
Base connection tension from overturning moment and sustained gravity resistance
calculation is shown. Notes that 0.7D comes from the load combination (0.9-0.2SDS)
and 1.4 comes from (0.9+0.2SDS). These factors consider the vertical acceleration
effects.
The angle, which is the ductile element of the connection, is welded between the
plates embedded in the DT leg and the footing. This angle is an L53-1/23/4
0'-6-1/2" with the long leg vertical. The steel for the angle and embedded plates will
be ASTM A572, Grade 50. The horizontal leg of the angle needs to be long enough
to provide significant displacement at the roof, although this is not stated as a
requirement in either the Provisions or ACI 318. This will be examined briefly here.
The angle and its welds are shown in the figure.
Calculation of the bending in connection angle and tension resistance are shown in
the slide.
The calculation shows that the calculated strength is slightly less than the demand,
but providing a stronger angle (e.g., a shorter horizontal leg) will simply increase the
demands on the remainder of the assembly.
Using ACI 318 Section 21.4.3, the tension force for the remainder of this connection
and the balance of the wall design are based upon a probable strength equal to
150 percent of the yield strength.
The Provisions Section 21.4.4 (ACI 318 21.4.3) requires that connections that are
designed to yield be capable of maintaining 80 percent of their design strength at
the deformation induced by the design displacement. For yielding of a flat bar
(angle leg), this can be checked by calculating the ductility capacity of the bar and
comparing it to Cd. Note that the element ductility demand (to be calculated below
for the yielding angle) and the system ductility, Cd, are only equal if the balance of
the system is rigid. This is a reasonable assumption for the intermediate precast
structural wall system described in this example.
The idealized yield deformation of the angle is calculated as shown in the slide.
Weld design calculations are also based on providing the overstrength required.
Weld design calculations, continued. The displacement from plastic hinge rotation
is compared to yield deflection to determine the ductility of the connection
compared to the design displacement amplification factor.
Base connection detail from the design calculations. The figure shows anchorage of
the plate embedded in the double tee to include bars that project into the stem for
development.
Although the design examples continues with overstrength design of the precast
panel, the requirements for overstrength design of the provisions are limited to the
non-yielding elements of connections.
Figure showing offset of Type 2 splice from face of column for ductile connection
design. The figure shows a space between the end of the precast beam and the
face of the precast column that permits the offset of the splice to meet the distance
of h/2 from the face of the support. This space would be filled with cast-in-place
concrete to complete the joint.
Description and figure for strong connections with ductile region offset from face of
column. The figure shows splice couplers at the face of the column, but the
reinforcing must be proportioned to ensure sufficient strength in the region of the
splice so that yielding occurs in the beam beyond the ends.
A summary slide on the general considerations for the seismic design of precast
concrete structural systems.
A slide to recognize that precast systems based on jointed behavior rather than
emulation of monolithic cast-in-place concrete can also be used, but these are
beyond the scope of the provision.
Precast Concrete
8
Precast Concrete Design
Suzanne Dow Nakaki, S.E.
Originally developed by
Gene R. Stevens, P.E., and James Robert Harris, P.E., PhD
Precast Concrete - 1
Precast Concrete - 2
Precast Concrete - 3
Precast Concrete - 4
Precast Concrete - 5
B
40'-0"
C
24'-0"
D
24'-0"
E
24'-0"
F
40'-0"
4'-0"
24'-0"
Prestressed
hollow core
slabs
6'-0"
24'-0"
14'-0"
72'-0"
6'-8"
24'-0"
8" concrete
masonry wall
152'-0"
Precast Concrete - 6
HORIZONTAL DIAPHRAGMS
Structural diaphragms are horizontal or nearly horizontal
elements, such as floors and roofs, that transfer seismic inertial
forces to the vertical seismic force-resisting members.
Precast concrete diaphragms may be constructed using topped
or untopped precast elements depending on the Seismic Design
Category.
Reinforced concrete diaphragms constructed using untopped
precast concrete elements are not addressed specifically in the
Standard, in the Provisions, or in ACI 318.
Topped precast concrete elements, which act compositely or
noncompositely for gravity loads, are designed using the
requirements of ACI 318 Section 21.11.
Precast Concrete - 7
Precast Concrete - 8
Precast Concrete - 9
Fpx
Fi
i x
n
wi
wpx
ix
Precast Concrete - 10
Level
Roof
4
3
2
1
wi
(kips)
861
963
963
963
963
wi
i x
(kips)
861
1,824
2,787
3,750
4,713
Fi
(kips)
175
156
117
78
39
Fi Vi
i x
(kips)
175
331
448
526
565
wpx
(kips)
807
855
855
855
855
Fpx
(kips)
164
155
137
120
103
Precast Concrete - 11
W1
W1
W2
3 at 24'-0" = 72'-0"
152'-0"
40'-0"
40'-0"
Precast Concrete - 13
Precast Concrete - 14
8.1
7
8.1
6
72'-0"
8.1
3
8.1
8
8.1
5
8.1
4
36'-0"
24'-0"
4'-0"
Precast Concrete - 15
Precast Concrete - 16
Joint Forces
Joint 1 Transverse forces:
Shear, Vu1 = 1.15 kips/ft (36 ft) = 41.4 kips
Moment, Mu1 = 41.4 kips (36 ft / 2) = 745 ft-kips
Chord tension force, Tu1 = M/d = 745 ft-kips / 71 ft
= 10.5 kips
Joint 2 Transverse forces:
Shear, Vu2 = 1.15 kips/ft (40 ft) = 46 kips
Moment, Mu2 = 46 kips (40 ft / 2) = 920 ft-kips
Chord tension force, Tu2 = M/d = 920 ft-kips / 71 ft
= 13.0 kips
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 17
Joint Forces
Joint 3 Transverse forces:
Shear, Vu3 = 46 kips + 0.86 kips/ft (24 ft) 38.3 kips = 28.3 kips
Moment, Mu3 = 46 kips (44 ft) + 20.6 kips (12 ft) - 38.3 kips (24
ft) = 1,352 ft-kips
Chord tension force, Tu3 = M/d = 1,352 ft-kips / 71 ft = 19.0 kips
Precast Concrete - 18
Precast Concrete - 19
Precast Concrete - 20
Precast Concrete - 21
Joint 5 Forces
Joint 5 Longitudinal forces:
Wall force, F = 153 kips / 8 = 19.1 kips
Wall shear along each side of wall, Vu5 = 19.1 kips [2(36 ft) / 152 ft]/2 = 4.5 kips
Collector force at wall end, Tu5 = Cu5 = 19.1 kips - 2(4.5 kips) = 10.1 kips
Precast Concrete - 22
Precast Concrete - 23
Precast Concrete - 24
(2) #4
(collector bars)
Interior Joint
31 2"
21 2" 2"
#3 x 4'-0" (behind)
at each joint
between planks
11 2" 21 2"
2"
2"
Anchorage
region for shear
reinforcement
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 25
Precast Concrete - 26
standard hooks
"
#3 x
2'-2
#3x 2'-6"
em bedded in grouted
edge cell of plank. Provide
2 sets for each plank.
standard hook
grouted into
each key joint
2" cover
71 2 "
(2) #5 in
m asonry
bond beam
(1) #5
continuous
in joint to
anchor hooks
V ertical
reinforcem ent
in w all
Precast Concrete - 27
Precast Concrete - 28
#3x 2'-6"
standard hook
grouted into
each key joint
2"
cover
(2) #5 bars
in joint
(chord bars)
(2) #5 in
bond beam
Precast Concrete - 29
Precast Concrete - 30
10
8.1
13
8.1
12
8.1
11
Precast Concrete - 31
WWF bend
down into
chord
Prestressed
hollow core
plank with
roughened
top surface
3"
21 2" min
(concrete
topping)
3"
(2) #8 bars
(chord bars)
Grouted
chord / collector
element along exterior
edge of precast plank
212"
Precast Concrete - 32
WWF
3"
(2) #8
(collector bars)
Vertical
reinforcement
21 2"
3"
21 2"
1" clear
WWF 10 x 10
W4.5 x W4.5
(2) #8
collector bars
(2) #5 in
masonry
bond beam
Precast Concrete - 33
11
25'-0"
25'-0"
25'-0"
25'-0"
26 IT 28
precast
beams
15'-0"
8'-0"
40'-0"
120'-0"
40'-0"
25'-0"
40'-0"
8" precast
shear walls
Precast Concrete - 34
Value
I = 1.0
0.266
0.08
D
1.59
2.4
0.425
0.192
0.283
0.128
B
Bearing Wall System
Intermediate Precast Shear Walls
4
2.5
4
Precast Concrete - 35
Precast Concrete - 36
12
Base Shear
Equation 12.8-2:
CS
S DS
0.283
0.0708
R/I
41
except that it need not exceed the value from Standard Equation 12.8-3
computed as:
S D1
0.128
CS
0.110
T ( R / I ) 0.29(4 / 1)
where T is the fundamental period of the building computed using the
approximate method of Standard Equation 12.8-7:
Precast Concrete - 37
12'-0"
95 kips
12'-0"
63.5 kips
12'-0"
31.5 kips
Grade
V = F = 190 kips
25'-0"
Precast Concrete - 38
12'-0"
12'-0"
9 5 k ip s
D
12'-0"
6 3 . 5 k ip s
D
12'-0"
3 1 . 5 k ip s
D
T
9"
1 2 '- 0 "
2 3 '- 6 "
C
9"
ME = (95 kips)(36 ft) + (63.5 kips)(24 ft) + (31.5 kips)(12 ft) = 5,320 ft-kips
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 39
13
Overturning
Using the load combinations described above, the vertical loads
for combining with the overturning moment are computed as:
Pmax = 1.26D + 0.5L + 0.2S = 397 kips
Pmin = 0.843D = 239 kips
The tension reinforcement can be found from a simple couple.
The effective moment arm is:
jd = 25 - 1.5 = 23.5 ft
Tu
107kips
jd
2
23.5
2
Precast Concrete - 40
End Reinforcement
The required reinforcement is:
As = Tu/fy = (107 kips)/[0.9(60 ksi)] = 1.98 in2
Use two #9 bars (As = 2.0 in2) at each end with Type 2 couplers
for each bar at each panel joint. Since the flexural reinforcement
must extend a minimum distance, d, (the flexural depth) beyond
where it is no longer required, use both #9 bars at each end of
the panel at all three levels for simplicity
At this point a check per ACI 318 Section 16.5 will be made.
Bearing walls must have vertical ties with a nominal strength
exceeding 3 kips per foot and there must be at least two ties per
panel. With one tie at each end of a 25-foot panel, the demand
on the tie is:
Tu = (3 kip/ft)(25 ft)/2 = 37.5 kips
The two #9 bars are more than adequate for the ACI
requirement.
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 41
Precast Concrete - 42
14
As f y jd Pmax ( jd / 2)
ME
5,320 ft-kips
Precast Concrete - 43
#5,see (c)
Welded wire
reinforcement
Plate 3 8x4x1'-0"
L4x3x516x0'-8"
LLH
4"
H.A.S.
Plate 1 2x12x1'-6"
Drypack
C8x18.75
Precast Concrete - 44
Weld at face plates, using Table 8-8 in AISC Manual (13th edition):
Vn= 0.75(1.73)(1.0)(4)(8)(2) = 83.0 kip
Bearing of concrete at steel channel:
fc = f(0.85f'c) = 0.65(0.85)(5 ksi) = 2.76 ksi
Precast Concrete - 45
15
Precast Concrete - 46
Precast Concrete - 47
Precast Concrete - 48
16
Precast Concrete - 49
12 DT at 8'-0" = 96'-0"
24LH03
at 4'-0" o.c.
48'-0"
15 DT at 8'-0" = 120'-0"
Joist girder
(typical)
48'-0"
24LH03
at 4'-0" o.c.
Steel tube
columns
3 DT at 8'-0" =
16'-0"
24'-0"
O.H.
door
5 DT at 8'-0" = 40'-0"
16'-0"
3 DT at 8'-0" =
O.H.
door
24'-0"
Precast Concrete - 50
Value
Occupancy Category II
I = 1.0
SS
1.5
S1
0.60
Site Class
Fa
1.0
Fv
1.3
SMS = FaSS
1.5
SM1 = FvS1
0.78
1.0
0.52
Wall Type
2.5
Cd
Precast Concrete - 51
17
Precast Concrete - 52
Flexible diaphragm
Equivalent lateral force method
Load combinations
Earthquake forces
Building weight
Base shear
Horizontal distribution without torsion for
flexible diaphragm
Precast Concrete - 53
8'-0"
Vlu
D1
D1
20'-0"
D2
2'-0"
2'-0"
2'-0"
2'-0"
DT leg
Vu = 4.25 kips/panel
Foundation
Vlu
T
Precast Concrete - 54
18
Precast Concrete - 55
Longitudinal Direction
The maximum tension for the connection at the base of the precast
panel to the concrete footing is governed by the seismic overturning
moment and the dead loads of the panel and the roof.
At the base:
ME = (4.25 kips)(20 ft) = 85.0 ft-kips
Dead loads:
SD = 2(1.08) + 7.73 = 9.89 kips
1.4D = 13.8 kips
0.7D = 6.92 kips
Compute the tension force due to net overturning based on an
effective moment arm, d, of 4.0 feet (the distance between the DT
legs). The maximum is found when combined with 0.7D:
Tu = ME/d - 0.7D/2 = 85.0/4 - 6.92/2 = 17.8 kips
Precast Concrete - 56
61 2"
My
t
L5x31 2x3 4x61 2
(LLV)
Tu'
Fillet
weld
Tu'
Vu '
CG
Mx
Mz
Mz
Mx
yB
My
Fillet
weld "t"
1"
4"
Vu'
Vu'
T u'
Vu'
25 16"
Tu '
k = 1316"
Location
of plastic
hinge
Precast Concrete - 57
19
6.5 0.752
41.1in kips
4
b M n 0.9 Fy Z 0.9 50
Using ACI 318 Section 21.4.3, the tension force for the remainder
of this connection and the balance of the wall design are based
upon a probable strength equal to 150 percent of the yield strength.
Thus:
T pr
2
M n (1.5) 50 6.5 (0.75) / 4
1.5 27.0kips
3.5 k
0.9(3.5 1.1875)
Precast Concrete - 58
Tpr
Tu
27.0
1.52
17.8
The shear on the connection associated with this force in the angle is:
V pr VE
T pr
Tu
Check the welds for the tension force of 27.0 kips and a shear force 6.46
kips.
Precast Concrete - 59
Py
y ,idealized
2
M n 50 6.5 (0.75 ) / 4
19.8kips
2.25
L
Py L3
3EI
19.83(2.313 )
0.0122
3 29,000 (6.5 0.753 / 12)
Precast Concrete - 60
20
Precast Concrete - 61
15 y
d /2
15 50 / 29,000
0.06897
0.75 / 2
Lp
0.75
sh p L p L
0.012 0.112in.
y 0.06897 0.75 2.31
2
2
Precast Concrete - 62
Mz
My
X
Z
Precast Concrete - 63
21
Precast Concrete - 64
Ductile Connectors
For moment frames constructed using ductile
connections, ACI 318 requires that plastic hinges be
able to form in the connection region. All of the
requirements for special moment frames must still be
met, plus there is an increased factor that must be
used in developing the shear demand at the joint.
It is interesting to note that while Type 2 connectors
can be used anywhere (including in a plastic hinge
region) in a cast-in-place frame, these same
connectors cannot be used closer than h/2 from the
joint face in a ductile connection. The objective of
Type 2 connectors is that they relocate the yielding
away from the connector, into the bar itself.
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 65
Ductile Connectors
Type 2 coupler
Precast column
Precast Concrete - 66
22
Strong Connections
Lb
Lclr
(3) #10 t&b
(3) #14
hooks t&b
H col
hbeam
lcoupler
Plastic hinge
location
Type 2 coupler
hcol
Precast Concrete - 67
As Fy
0.85 f c'b
3 1.27 (60)
3.0in.
0.85 5 (18)
3.0
M n As Fy d 0.9 31.27 60 33
/ 12 540 ft kips
2
2
Precast Concrete - 68
M u , joint M pr
M pr M n
Lb hcol
Lclr
1.25
540
1.25
750 ft kips
0.9
Precast Concrete - 69
23
30 36 / 12
843 ft kips
24
As Fy
0.85 f c'b
3 2.25 (60)
5.3in.
0.85 5 (18)
5.3
/ 12 921 ft kips
M n As Fy d 0.9 3 2.25 60 33
2
2
which is greater than the load at the connection (843 ftkips) when the plastic hinge develops.
Instructional Material Complementing FEMA 752, Design Examples
Precast Concrete - 70
Precast Concrete - 71
Precast Concrete - 72
24
Precast Concrete - 73
Questions
Precast Concrete - 74
25