Abb Pr221ds Lsi

Download as pdf or txt
Download as pdf or txt
You are on page 1of 229

Technical catalog

ABB
molded case
circuit breakers
UL 489 and CSA C22.2 Standard

Preliminary - 1SDC210003D0202

Tmax, Isomax, Emax: IndustrialIT enabled!


IndustrialIT is the solution developed by ABB for the all-

certification and is fully entitled to join the ProtectIT suite

round integration of a companys activities, where each

of products.

product is seen as part of a complete solution. Products

These circuit breakers combine with about 700 products

and technologies are grouped into

in the ranges of distribution boards, thus

functional categories (Suites), each

enabling complete switchboards to be

of which measures,

assembled using all IndustrialIT-certified

controls, optimizes and

components. Moreover, T4 and T5

supports a specific

feature e-plug communication

block of activities, and

interface, which allows Integration

they can ensure

to IndustrialIT systems.

coordinated interaction

Tmax, Isomax and Emax circuit

thanks to the platform

breaker can be integrated with the

created by ABB (AIP: Aspect Integrator Platform).

configurable ABB products in a system: this

In addition to interactivity between certified products,

compatibility has always been a fundamental premise of

every certified product also guarantees the ready

the ABB design process. Mass customization, i.e. the

availability of all the information needed for it to

mass production of components customized to meet a

function - technical characteristics, installation

given buyers specific needs is already feasible, as

instructions, use and maintenance instructions,

IndustrialIT certification demonstrates.

environmental certificates and declarations, all updated

Yet again, ABB is ahead of the field in offering a better

to the latest version a considerable advantage for the

and better customer service!

user*.
The whole range of Tmax and Isomax molded case and
Emax power circuit breakers has obtained IndustrialIT

* All product technical data and related documentation can be found in


Internet and is accessible to the customer. The standard documentation
is in English, but there are local language versions for each country where
a given product is marketed.

For further information, go to the Products and services/Industrial IT section on our web site: http://www.abb.com

OVERVIEW
MAIN
CHARACTERISTICS

THE RANGES

ACCESSORIES

CHARACTERISTIC CURVES
AND TECHNICAL
INFORMATION
WIRING DIAGRAMS

OVERALL
DIMENSIONS

C O M P L E T E A N D P E R F E C T LY I N T E G R AT E D
In the range of molded case circuit breakers conforming with the UL 489 and CSA C22.2 Standard, ABB proposes an
entire range which covers current ratings between 15 A and 2500 A and interrupting ratings, at 480 V AC, which can
reach 150 kA.
The ranges available are as follows:
circuit breakers for power distribution (fitted with thermomagnetic or electronic trip units starting from 100 A)
circuit breakers with adjustable magnetic only trip units for motor protection (MCP: Motor Control Protection)
molded case switches for use as isolators or switching devices for lines, busbars or parts of a plant (MCS:
Molded Case Switch)
With the introduction of the new Tmax UL series, a single-pole circuit breaker with interrupting rating of 18 kA
at 277 V AC is available on the American market for the first time.

480 V
All ABB circuit breakers in accordance with the
UL 489 and CSA C22.2 Standard can be
used in installations with wye or delta
distribution systems since use of the circuit
breaker at 480 V AC is guaranteed, even
for the smallest Tmax T1 size.

C O M PA C T D I M E N S I O N S
ABB molded case circuit breakers ensure
high performances in extremely small and
compact dimensions. Standardization of
the depth of the smaller sizes allows more
rational and less deep enclosure to be used
than in the past.

D O U B L E I N S U L AT I O N
Thanks to the double insulation technique,
with all ABB molded case circuit breakers*
the electrical accessories can be mounted
directly on field with the circuit breaker
installed: this allows considerable savings in
time and therefore in costs.
* Except for Isomax S8.

T GENERATION
Tmax has grown. ABB
experience in designing and
manufacturing molded case
circuit breakers has made it
possible to create circuit breakers
which, up to 600 A, allow any application to be
faced practically and simply.
The new Tmax have been thought up to work
together, to help you carry out selections and
correct sizing, to make installation simpler, but
above all to give you top level performances.
The latest generation technology is present for
the first time even in the smallest sizes.
With Tmax you have everything you need at
hand to make your job easier, from all types of
accessories and terminals. The T Generation grows,
and so does freedom.

TMAX.
BE FREE.

The Tmax T4 and T5 circuit


breakers have obtained the
prestigious INTEL Design 2003
Augusto Morello award in the
Product Technologies and
Production processes section.

TECHNOLOGY
It was not easy to find solutions which would allow the
Tmax circuit breakers to achieve such high performances
in such limited dimensions, but thanks to the
experience which has been recognised to a leader
such as ABB for decades, the objectives we had set

TMAX.
BE FREE TO
RIDE THE MOST
ADVANCED
TECHNOLOGY.

ourselves have been achieved. So this has meant


being able to equip such a small circuit breaker
as the T2 with an electronic trip unit, to fit the
circuit breakers with new arcing chambers
which allow the arc extinction time to be
reduced, or, still further, to provide double
insulation for ever greater safety right from the
smallest size. A complete series of latest
generation trip units is available, from the
electronic to the thermomagnetic or magnetic
only ones - all interchangeable.
The new Tmax T4 and T5 are an example of the
great technology expressed by this family of circuit
breakers with high breaking capacity and high
limitation of the specific let-through energy.
Being free is also all this.

SIZING
All the circuit breakers in the Tmax family come from
optimisation of installation sizing. With T1,T2 and T3
you can find the ideal product for sizing an installation
up to 225 A, and with T4 and T5 up to 600 A.
Furthermore, with the latter, high selectivity values
are obtained for optimal coordination with other
circuit breakers. You can also choose the best

TMAX.
BE FREE TO
CHOOSE
OPTIMAL SIZING.

solution for motor protection with the motor


control protection (MCP).
Higher performances in less space. More
applications up to 600 A. Easier selection of the
circuit breakers and accessories. Optimal sizing of
the installation and better protection of cables,
busbar ducts and supports. Less space required in
the switchgear and in the metal structures.
Less oversizing and therefore lower costs.
Less time for coordinating the installations.
Fewer stock complications. With Tmax, all the
solutions needed can be chosen, as well as that
of feeling freer to choose.

INSTALLATION
Having circuit breakers available with smaller dimensions
than all the others on the market undoubtedly offers
great advantages - more space for cabling operations and
simpler installation, therefore notable savings in time -

TMAX.
BE FREE TO
DRIBBLE ROUND
ALL INSTALLATION
DIFFICULTIES.

five sizes, just two depths - 2.76 inches (70 mm) for
T1, T2, T3 and 4.07 inches (103.5 mm) for T4
and T5, and the latter also have the same height.
They are also available in all the versions: fixed,
plug-in and draw out and, thanks to special kits,
passing from a fixed circuit breaker to a plug-in/
draw out one is childs play. Flexibility of use over
the whole series is ensured by the complete range
of connection terminals and by the large number
of accessories.
Being free also means having much more time
for yourself.

1 0 0 % U L R AT E D C I R C U I T B R E A K E R S
The 100% rated versions for Isomax circuit breakers are available thanks to the excellent thermal sizing of
the latter.

A L L T H E A P P L I C AT I O N S
ABB offers the right solution for any application up to 2500 A thanks to Isomax S6, S7 and S8 circuit
breakers, perfectly integrated with the Tmax family:
MCCB: S6, S7 and S8 molded case circuit breakers for power distribution;
MCP: S6, S7 and S8 circuit breakers with magnetic only trip unit for motor control protection;
MCS: S6, S7 and S8 molded case switches for using as isolators or switching devices for lines, busbars or
parts of plants.

M A X I M U M V E R S AT I L I T Y
Isomax circuit breakers can be fitted with a wide range of
terminals for every kind of connections. Modular design
also makes installation and assembly extremely simple.

COMPLETE RANGE OF ACCESSORIES


Isomax circuit breakers are complemented by a
complete range of accessories to satisfy the widely
differing operational and automation requirements.
Accessories are standardized for groups of circuit
breakers to streamline storage logistics and simplify
installation.
Isomax circuit breakers can be customized as required
under conditions of absolute safety.
All the accessories can be mounted with simple
operations without exposing the main contacts (except for
the Isomax S8).

Circuit breakers for power distribution


Electrical characteristics

Tmax T1 1P

Tmax T1 Tmax T2

Tmax T3

UL 489 CSA C22.2


Frame size
Number of poles
Rated voltage

AC (50-60Hz)
DC

[A]
[Nr]
[V]
[V]

AC 240 V
277 V
480 V
600 V
DC 250 V - 2 poles in series
500 V - 3 poles in series
500 V - 2 poles in series
600 V - 3 poles in series

[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]

Interrupting ratings

100
1
277
B

Trip units

Versions

100
3,4
480
S H
65 100

225
3,4
480
500
N S
50 65

22(2)

35 65

25 35

18(1)

25
25

TMF
TMD/TMA
ELT
MA
MCCB
MCS
MCP

100
3,4
480
500
N
50(2)

25 35
25 35

Tmax T1 1P

Tmax T1 Tmax T2

Tmax T3

IEC 60947-2
Rated uninterrupted current, Iu
Number of poles
Rated service voltage, Ue

AC (50-60Hz)
DC
Rated ultimate short circuit breaking capacity, Icu
AC (50-60 Hz)
220/230 V
380/415 V
440 V
500 V
690 V
DC
250V - 2 poles in series
250V - 3 poles in series
500V - 2 poles in series
500V - 3 poles in series
750V - 3 poles in series
Trip units
TMF
TMD/TMA
ELT
MF
MA

[A]
[Nr]
[V]
[V]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]

160
1
240
125
B
25

L
120
85
75
50
10
85
100

250
3,4
690
500
N S
50 85
36 50
25 40
20 30
5
8
36 50
40 55

16 25 36

36 50 70 85

36 50

5.12/130
3.54/90
4.72/120
2.76/70
25000
240
8000
120

5.9/150
4.13/105
5.51/140
2.76/70
25000
240
8000
120

B
25
16
10
8
3
16
20

160
3,4
690
500
C
40
25
15
10
4
25
30

N
50
36
22
15
6
36
40

N
65
36
30
25
6
36
40

160
3,4
690
500
S H
85 100
50 70
45 55
30 36
7
8
50 70
55 85

UL 489 CSA C22.2 and IEC 60947-2


Dimensions

Mechanical life
Electrical life @ 415 V AC

(1)
(2)
(3)

In15A = 10kA @ 277 V AC


In15A = 35 kA @ 240 V AC, 14 kA @ 480 V AC
Please ask ABB for 600 A availability

H
W 1p or 3p
W 4p
D

[in/mm]
[in/mm]
[in/mm]
[in/mm]
[No.operations]
[No. Hourly operations]
[No.operations]
[No. Hourly operations]

5.12/130
1/25.4
2.76/70
25000
240
8000
120

TMF = Thermomagnetic trip unit with fixed thermal


and magnetic threshold

5.12/130
3/76
4/102
2.76/70
25000
240
8000
120

TMD = Thermomagnetic trip unit with adjustable


thermal threshold and fixed magnetic
threshold

Tmax T4

Tmax T5

Isomax S6

250
3,4
600
600
N S H L V
65 100 150 200 200

400 - 600(3)
3,4
600
600
N S H L V
65 100 150 200 200

800
2,3,4
600
600
N H L
65 150 200

1200
2,3,4
600

1600, 2000, 2500


3
600

H
100

V
125

25 35
18 25

65 100 150
35 65 85

25 35 65 100 150
18 25 35 65 85

50 65 100
25 35 42

65
50

100
85

25 35
16 25

50 65 100
35 50 65

25 35 50 65 100
16 25 35 50 65

35 50 65
20 35 50

Tmax T4

Tmax T5

Isomax S6

250 - 320
3,4
690
750
S H L
85 100 200
50 70 120
40 65 100
30 50 85
25 40 70
50 70 120

400 - 630
3,4
690
750
S H L
85 100 200
50 70 120
40 65 100
30 50 85
25 40 70
50 70 120

N
70
36
30
25
20
36

V
300
200
180
150
80
200

N
70
36
30
25
20
36

V
300
200
180
150
80
200

N
65
35
30
25
20
35

630 - 800
3,4
690
750
S H L
85 100 200
50 65 100
45 50 80
35 40 65
22 25 30
50 65 100

Isomax S7

Isomax S7
1250 - 1600
3,4
690
S
85
50
40
35
20

H
100
65
55
45
25

L
200
100
80
70
35

Isomax S8

Isomax S8
2000, 2500, 3200
3,4
690
H
85
85
70
50
40

V
120
120
100
70
50

25 36 50 70 100

25 36 50 70 100

20 35 50 65

16 25 36 50 70

16 25 36 50 70

16 20 35 50

8.07/205
5.51/140
7.24/184
4.07/103.5
20000
120
7000(400A)-5000(630A)
60

10.55/268
8.27/210
11.02/280
4.07/103.5
20000
120
7000(630A)-5000(800A)
60

15.98/406
8.27/210
11.02/280
5.45/138.5
10000
120
7000(1250A)-5000(1600A)
20

15.75/400
15.98/406
21.89/556
9.53/242
10000
20
2500(2500A)-1500(3200A)
20(2500A)-10(3200A)

8.07/205
4.13/105
5.51/140
4.07/103.5
20000
240
8000(250A)-6000(320A)
120

TMA = Thermomagnetic trip unit with adjustable


thermal and magnetic threshold

MF
MA

= Magnetic fixed trip unit


= Magnetic adjustable trip unit

ELT = Electronic trip unit

Circuit breakers for specific


applications in accordance with
IEC 60947-2
Tmax T1 1P Tmax T1

Tmax T2

Tmax T3

160
3/4
690

225
3/4
690

Circuit breakers for distribution AC-DC


Rated uninterrupted current
Numbers of poles
Rated voltage
Icu

Ics/Icu @ 380/415 V AC %
Dimensions fixed version (3p)

380/415 V AC
440 V AC
690 V AC

[A]
Nr
[V]
[kA rms]
[kA rms]
[kA rms]
[kA rms]

160
1
240
B
25*

H
W
D

[in-mm]
[in-mm]
[in-mm]

5.12-130
1-25.4
2.76-70

(AC) 50-60Hz

160
3/4
690
B
C
N
16
25
36
10
15
22
3
4
6
100 100 50
5.12-130
3-76
2.76-70

N
36
30
6
100

S
H
50
70
45
55
7
8
100 100
5.12-130
3.54-90
2.76-70

L
85
75
10
75

N
S
36
50
25
40
5
8
75
50
5.0-150
4.13-105
2.76-70

T2

T3

160
3
1100
690

250
3
100200
690

Circuit breakers for motor protection


Iu
Poles
In
Ue
Trip unit

[A]
[A]
[V]
Adjustable magnetic only (612xIn)
Electronic
PR221DS-I
PR222/MP (IEC 60947-4-1)
PR212/P-I
PR212/MP (IEC 60947-4-1)

T1D

T3D

3/4
160
690
8
800
2.8
2

3/4
250
690
8
800
5.3
3.6

Switch-disconnectors
Poles
Ith
Ue
Uimp
Ui
Icm
Icw (1s)
* For In 16A and In 20A: Icu @ 220/230 V AC = 16 KA

[Nr]
[A]
[V]
[KV]
[V]
[KA]
[KA]

N
36
30
20
100

Tmax T4

Tmax T5

Isomax S6

Isomax S7

Isomax S8

250
3/4
690
S
H
L
50
70 120
40
65 100
25
40
70
100 100 100
8.07/205
4.13/105
4.07/103.5

400-630
3/4
690
S
H
L
50
70 120
40
65 100
25
40
70
100 100 100
8.07/205
5.51/140
4.07-103.5

800
3/4
690

1250-1600
3/4
690
S
H
L
50
65 100
40
55
80
20
25
35
100 75
50
16-406
8.27-210
5.45-138.5

2000-2500-3200
3/4
690
H
V
85 120
70 100
40
50
50
50
15.75-400
15.98-406
9.25-235

V
200
180
80
100

N
36
30
20
100

V
200
180
80
100

N
35
30
20
100

S
H
50
65
45
50
22
25
100 100
14.25-268
8.27-210
4.07-103.5

L
100
80
30
75

T4

T5

S7

250
3
80250
690

400
3
320-400
690

1250-1600
3
10001600
690

T4D

T5D

S6D

S7D

S8D

3/4
250-320
690
8
800
5.3
3.6

3/4
400-630
690
8
800
11
6

3/4
800
690
8
800
30
15

3/4
1000-1250-1600
690
8
800
52.5
25

3/4
2000-2500-3200
690
8
800
85
40

Main characteristics

1
Index
General information ........................................................................................................... 1/3

Construction characteristics
Modularity of the series ....................................................................................................... 1/4
Distinguishing features of the series .................................................................................... 1/6

ABB

1/1

General information

7
22
21

1
19

18
23

20

4
1

17
16
5

15
14
6

10
2

12
9

13

1/2

11

ABB

The ABB family of molded case circuit breakers in conformity with


UL 489 and CSA C22.2 No. 5.1 Standard - Tmax and Isomax - is
divided into different, perfectly integrated, ranges (Tmax T1B 1p,
T1, T2, T3, T4, T5 and Isomax S6, S7, S8), able to cover a range
of service currents from 15 to 2500 A.
The power distribution circuit breakers are available, with UL 489
and CSA C22.2 approval, in the fixed, plug-in or draw out, twopole, three-pole and four-pole versions.
The Tmax T1 circuit breaker is also available in the single pole
Tmax T1B 1p version, with an interrupting rating of 18 kA at 277 V
AC. The circuit breakers can be selected among different interrupting rating levels from 22 kA to 150 kA at 480 V AC and from
18 kA up to 85 kA at 600 V AC.

24

Starting from the fixed version circuit breaker, all the other versions used for various requirements are obtained by means of
mounting conversion kits.
The following are available:
kit for converting a fixed circuit breaker into the moving part of
a plug-in and draw out one
circuit breaker fixed parts for plug-in and draw out circuit
breakers
conversion kit for the connection terminals.

25

26

27

1SDC210141F0023

28

ABB

Various accessories are also available:


1. Breaking unit (1)
2. Trip units (1)
3. Front
4. Auxiliary contacts - AUX (2)
5. Undervoltage release - UVR (2)
6. Shunt trip - SOR (2)
7. Terminal covers
8. Front for lever operating mechanism - FLD
9. Direct rotary handle - RHD (2)
10. Stored energy motor operator - MOE (2)
11. Key lock - KLF
12. Early auxiliary contact - AUE
13. Transmitted rotary handle - RHE (2)
14. Front terminal for copper cable - FC Cu
15. Front extended terminal - EF
16. Multi-cable terminal (only for T4) - MC
17. Front terminal for copper-aluminium - FC CuAl (UL listed)
18. Front extended spread terminal - ES
19. Rear orientated terminal - R
20. Conversion kit for plug-in/draw out versions (2)
21. Guide of fixed part in the draw out version (2)
22. Fixed part - FP (2)
23. Auxiliary position contact - AUP
24. Phase separators
25. PR010T
26. TT1
27. Racking out crank
28. Residual current release.
(1) UL file E93565
(2) UL file E116596

1/3

Construction characteristics
Distinguishing features of the series

Compliance with Standards and company


Quality System
The Tmax and Isomax circuit breakers and their electrical accessories conform to the UL 489 (Underwriters Laboratories Incorporated) and CSA C22.2 No.5.1 (Canadian Standard Association)
North American Standards, and to the international IEC 60947-2
Standards and comply with the EC directive:
Low Voltage Directives (LVD) no. 73/23 EEC
Electromagnetic Compatibility Directive (EMC) no.89/336 EEC.
Certification of conformity with the above-mentioned product
Standards is carried out, in respect of the European EN 45011
Standard, by the Italian certification body ACAE (Association for
Certification of Electrical Apparatus), a member of the European
LOVAG organization (Low Voltage Agreement Group).
The ABB test laboratory is accredited by SINAL (certificate no.
062/2002).
The ABB Quality System complies with the international ISO 9001
- 2000 Standard (model for quality assurance in design, development, construction, installation and service) and with the equivalent European EN ISO 9001 and Italian UNI EN ISO 9001 Standards.
The independent certifying Body is RINA S.p.A. ABB obtained its
first certification with three-year validity in 1990, and has now
reached its fourth reconfirmation.
The new Tmax series has a hologram on the front, obtained using
special anti-imitation techniques, which guarantees the quality and
that the circuit breaker is an original ABB product.
Attention to protection of the environment and to health and safety
in the work place is another priority commitment for ABB and, as
confirmation of this, the company environmental management system has been certified by RINA in 1997, in conformity with the
international ISO 14001 Standard. This certification has been integrated in 1999 with the Management System for Healt and Safety
in the workplace, according to OHSAS 18001 (British Standards),
obtaining one of the first certification of integrated management
System, QES (Quality, Environment, Safety) issued by RINA.
ABB - the first industry in the electromechanical section in Italy to
obtain this recognition - thanks to a revision of the production process with an eye to ecology, has been able to reduce the consumption of raw materials and waste from processing by 20%.
ABBs commitment to safeguarding the environment is also shown
in a concrete way by the Life Cycle Assessments of its products
carried out directly by the ABB Research and Development in collaboration with the ABB Research Center. Selection of materials,
processes and packing materials is made optimising the true environmental impact of the product, also foreseeing the possibility
of its being recycled.

1SDC210142F0023

1/4

ABB

Double insulation*
This construction characteristic consists of the presence of double insulation between the live power
parts (excluding the terminals) and the front parts of the apparatus where the operator works during
normal operation of the installation. The seat of each electrical accessory is completely segregated
from the power circuit, thereby preventing any risk of contact with live parts, and, in particular, the
operating mechanism unit is completely insulated in relation to the powered circuits. As a consequence most accessories are field installable.
Furthermore, the insulation distances, both between the live internal parts and in the terminal connection area, comply with what is foreseen by the UL 489 Standard and are higher than those
required by the international IEC Standards.
1SDC210143F0023

* Except for Isomax S8

The operating lever always indicates the exact position


of the circuit breaker moving contacts, thereby
guaranteeing safe and reliable signals in compliance
with the prescriptions of the IEC 60417-2 Standard
(I = Closed; O = Open; yellow-green line = Open due to
release trip). The circuit breaker operating mechanism
has trip free operation. Trip unit intervention automatically opens the moving contacts: to close them again,
the operating mechanism must be reset by pushing
the operating lever from the intermediate position into
the lowest open position.

1SDC210144F0023

Positive operation

Isolation behaviour

1SDC210145F0023

In the open position, the circuit breaker


guarantees circuit isolation in compliance
with the IEC 60947-2 Standard. The oversized insulating distances guarantee there
are no leakage currents and dielectric
resistance to any overvoltages between
input and output. For plug in and draw out
version circuit breakers, in the racked-out
position, the power and auxiliary circuits are
insulated, guaranteeing that no part is live. By means of special socket-plugs, it is possible to carry
out blank tests under these conditions, operating the circuit breaker in complete safety.

ABB

1/5

Construction characteristics
Distinguishing features of the series

Operating temperature
The Tmax and Isomax circuit breakers can be used in ambient
conditions where the surrounding air temperature varies between
13 F and +158 F (25 C and +70 C) and stored in ambient
with temperatures between 40 F and + 158 F (40 C and
+70 C). The circuit breakers fitted with thermomagnetic trip unit
have their thermal element set for a reference temperature of
104 F (40 C).
For temperatures other than 104 F (40 C), with the same setting,
there is a variation of the thermal threshold as shown in the tables
on page 4/36 and 4/37.
The electronic PR211/P, PR212/P, PR221DS and the new
PR222DS/P electronic trip units do not undergo any variations in
performance as the temperature varies but, in the case of temperatures exceeding 104 F (40 C), the maximum setting for protection against overloads, L, must be reduced, as indicated in the
derating graphs on page 4/35, to take into account the heating
phenomena which occur in the copper parts of the circuit breaker
passed through by the phase current. For temperature above
158 F (70 C) the circuit breaker performances are not guaranteed.

1SDC210146F0023

Altitude
Up to an altitude of 6600 ft (2000 m) the Isomax and Tmax do not
undergo any alterations in their rated performances. As the altitude increases, the atmospheric properties are altered in terms of
composition, dielectric resistance, cooling capacity and pressure.
For this reason, the rated voltage and the nominal
current at this altitudes must be derated to the values shown in
the table.

1/6

Altitude [ft] 6600

9900 13200 16500

Rated
voltage

[V]

600

522

435

348

Continuous
current
rating
%

100

98

93

90

ABB

Electromagnetic compatibility

1SDC210147F0023

With the use of the PR211/P, PR212/P, PR221DS and PR222DS/P


electronic trip units and the RC211, RC212, RC221, RC222 and
RC223 electronic residual current releases, operation of the protections is guaranteed in the presence of interferences caused by electronic apparatus, atmospheric disturbances or electrical discharges.
No interference with other electronic apparatus near the place
of installation is generated either. This is in compliance with the
IEC 60947-2 Appendix F Standards and European Directive
No. 89/336 regarding EMC electromagnetic compatibility.

Tropicalization

1SDC210148F0023

Circuit breakers and accessories in the ABB family of molded


case circuit breakers have been tested in compliance with the
IEC 60068-2-30 Standard, carrying out two cycles at 131 F
(55 C) with the variant 1 method (clause 6.3.3). The suitability
of their use under the most severe environmental conditions is
therefore ensured with the hot-humid climate defined in
climatograph 8 of the IEC 60721-2-1 Standards thanks to:
insulating cases made of synthetic resins reinforced with glass
fibers;
anti-corrosion treatment of the main metallic parts
Fe/Zn 12 galvanization (ISO 2081), protected by a conversion layer mainly consisting of chromates (ISO 4520)
application of anti-condensation protection for electronic trip units and relative accessories.

Resistance to shocks and vibrations


The circuit breakers are unaffected by vibrations generated mechanically and due to electromagnetic effects, in compliance with the IEC 60068-2-6 Standards and the regulations of the major
classification organizations:
ABS (American Bureau of Shipping)*
RINA
Det Norske Veritas
Bureau Veritas
Lloyds register of shipping
Germanischer Lloyd.
The Isomax and Tmax circuit breakers are also tested, according to the IEC 60068-2-27 Standard,
to resist shocks up to 12g.
Please contact ABB for information regarding the types of circuit breakers approved, the performances approved and their relative validity.
*Most of ABB circuit breakers are certified with ABS approval, according to IEC 60947-2; the whole Tmax family has ABS
approval according both with IEC 60947-2 and UL 489.

ABB

1/7

Construction characteristics
Distinguishing features of the series

Installation
Molded case circuit breakers can be installed in
the switchboards, mounted in any horizontal, vertical or lying down position on the back plate or on
rails, without undergoing any derating of their rated
characteristics(1). ABB circuit breakers can be installed easily in all types of switchboards, above all
thanks to the possibility of being supplied either by
top or bottom terminals, without jeopardising the
apparatus functionality(2).
Apart from fixing on the base plate, T1, T2 and T3 can also be installed on DIN 50022 rails, thanks to
the special fixing brackets. Furthermore, the depth of 2.76 inches (70 mm) takes Tmax T3 to the
same standard as the two smaller sizes, making assembly of circuit breakers up to 225 A in standard
switchboards even simpler. In fact, it is possible to prepare standardised support structures, facilitating the design stage and construction of the switchboard metalwork.

1SDC210151F0023

1SDC210150F0023

(1) Isomax S8 can be mounted just in vertical position.


(2) Isomax S8 can be supplied only from the top

Racking-out with the door closed

1SDC210152F0023

With Tmax T4 and T5 and Isomax S6 and S7 in the draw out version, the circuit breaker can be
racked-in and out with the compartment door closed, thereby increasing operator safety and allowing rationalisation of low voltage arc proof switchboards. Racking out can only be carried out with
the circuit breaker open (for obvious safety reasons), using a special racking-out crank supplied with
the conversion kit from fixed circuit
breaker to moving part of draw out
circuit breaker.

1/8

ABB

The ranges

Index
Circuit breakers for power distribution
Electrical characteristics ........................................................................................................ 2/2
General characteristics .......................................................................................................... 2/4
Thermomagnetic trip units ..................................................................................................... 2/6
Electronic trip units ................................................................................................................ 2/8

Motor control protection circuit breakers: MCP


Magnetic and electronic overcurrent trip units .................................................................... 2/18

Molded case switches: MCS


Electrical characteristics ...................................................................................................... 2/20

ABB

2/1

Circuit breakers for power distribution


Electrical characteristics

2
Frame size
Numbers of poles
Rated voltage
Test voltage (1min) 50-60 Hz
Interrupting ratings

Trip units
Dimensions fixed version (3p)

Mechanical life
Weights (fixed 3p)

[A]
Nr
(AC) 50-60Hz
[V]
(DC)
[V]
[V]
[kA rms]
240 V AC
[kA rms]
277 V AC
[kA rms]
480 V AC
[kA rms]
600 V AC
[kA rms]
250 V DC (2 poles in series) [kA rms]
500 V DC (3 poles in series) [kA rms]
500 V DC (2 poles in series) [kA rms]
600 V DC (3 poles in series) [kA rms]
Thermomagnetic
Electronic
H
[in-mm]
W
[in-mm]
D
[in-mm]
[operations]
[lbs]

T1 1P

T1

T2

T3

100
1
277

100
3-4
480
500
3000
N
50 (2)

100
2-3-4 (3)
480
500
3000
S
H
65
150

225
2-3-4 (3)
480
500
3000
N
S
50
65

35

25

35

25
25

35
35

3000
B
18 (1)

22

65

25
25

5.12-130
1-25.4
2.76-70
25000
1.06

5.12-130
3-76
2.76-70
25000
2.34

5.12-130
3.54-90
2.76-70
25000
2.86

5.9-150
4.13-105
2.76-70
25000
5.45

Note: for S6 4 poles only for N versions


(1)
In 15A = 10 KA @ 277 V AC
(2)
In 15A = 35 KA @ 240 V AC 14 KA @ 277/480 V AC
(3)
Ask ABB for two-pole version availability
(4)
Please ask ABB for 600 A availability

2/2

ABB

T4

T5

S6

S7

S8

N
65

V
200

N
65

800
2-3-4
600
600
3000
H
150

1600-2000-2500
3
600

V
200

400-600 (4)
2-3-4 (3)
600
600
3500
S
H
L
100
150
200

1200
2-3-4
600

N
65

250
2-3-4 (3)
600
600
3500
S
H
L
100
150
200

L
200

3000
H
100

3000
V
125

25
18

35
25

100
65

150
85

25
18

35
25

100
65

150
85

50
25

65
35

100
42

65
50

100
85

25
16

35
25

50
65
35
50

8.07/205
4.13/105
4.07/103.5
20000
6.18

100
65

25
16

35
25

50
65
35
50

8.07/205
5.51/140
4.07-103.5
20000
8.55

100
65

35
20

16-406
8.27-210
5.45-138.5
10000
37.5

15.75-400
15.98-406
9.25-235
10000
135

ABB

65
35

65
35

50
65
35
50

14.25-268
8.27-210
4.07-103.5
20000
22

2/3

Circuit breakers for power distribution


General characteristics

General characteristics
The ABB family of molded case circuit breakers, complying with
the UL 489 and CSA C22.2 No. 5.1 Standards, is divided into
different sizes, with an application range from 15 to 2500 A and
interrupting ratings up to 150 kA at 480 V AC.
Selection of the size allows the basic electrical characteristics to
be identified simply and immediately, whereas selection of the
overcurrent trip unit is made according to the type of application
required.
Furthermore, for the first time ABB has also developed a molded
case circuit breaker with a single-pole construction characteristic:
T1B 1p. This is a 100 A frame size circuit breaker, able to operate
at rated voltages up to 277 V AC.
For protection of alternating current networks, the following are
available:
Tmax T1B 1p, T1, T2, T3 and T4 (15 A, 20 A) circuit breakers,
equipped with TMF thermomagnetic trip units, with fixed thermal and magnetic threshold (I3 = 10 x In);
Tmax T4 (up to 50 A) circuit breaker equipped with TMD
thermomagnetic trip units with adjustable thermal threshold
(I1 = 0.71 x In) and fixed magnetic threshold (I3 = 10 x In).
T4, T5 and Isomax S6 circuit breakers with TMA thermomagnetic trip units, with adjustable thermal threshold (I1 = 0.71 x
In) and adjustable magnetic threshold (I3 = 510 x In).
T2 with PR221DS electronic trip unit
T4 and T5 with PR221DS, PR222DS/P and PR222DS/PD electronic trip unit
Isomax S6, S7 and S8 with PR211/P and PR212/P electronic
trip unit.

Interchangeability
Tmax T4 and T5 circuit breakers can be equipped either
with TMD or TMA thermomagnetic trip units, PR221DS,
Trip unit
TMF
Circuit breakers
In [A]
15
20
T4 250

T5 400
T5 600

PR222DS/P and PR222DS/PD


electronic trip units. Thanks to
their simplicity of assembly, the
end customer can, in fact,

change the type of trip unit extremely rapidly, according to


their own requirements and
needs: in this case, correct as-

TMD

TMA

30

40

50

80

100

125

150

200

250

300

400

600

= complete circuit breaker already coded


= circuit breaker to be assembled (separate codes of the circuit breaker part plus trip unit)

2/4

ABB

Tmax T2 and T3 offer a magneticonly trip unit: I3 = 612 x In.


Finally, Tmax T1, T2, T3, T4 and
T5 and Isomax S6 circuit breakers fitted with thermomagnetic
trip units can also be used in
direct current plants, with an application range from 15 to 800 A
and a minimum operating voltage
of 24 V DC.

Range of application of the alternating and


direct current circuit breakers
Trip unit
AC
T1B 1p
T1
T2

Range [A]

S8

TMF
TMF
TMF
PR221DS
TMF
TMF/TMD/TMA
PR221DS
PR222DS/P
PR222DS/PD
TMA
PR221DS
PR222DS/P
PR222DS/PD
TMA
PR211/P
PR212/P
PR211/P
PR212/P
PR212/P

15100
15100
15100
25100
60225
15250
100250
100250
100250
300-400-600
300-400-600
300-400-600
300-400-600
600-800
400800
400800
1000-1200
1000-1200
16002500

DC
T1
T2
T3
T4
T5
S6

TMF
TMF
TMF
TMF/TMD/TMA
TMA
TMA

15100
15100
60225
15250
300-400-600
800

T3
T4

T5

S6

S7

TMF = Fixed thermomagnetic trip unit


TMD = Thermomagnetic trip unit with adjustable thermal and fixed magnetic threshold
TMA = Thermomagnetic trip unit with adjustable thermal and adjustable magnetic threshold
ELT = Electronic trip unit

sembly is under the customers


responsibility. Above all, this
means into increased flexibility
of use of the circuit breakers

with considerable savings in


terms of costs thanks to better
rationalisation of stock management.

PR221DS-LS/I or I
100

150

250

300

PR222DS/P-LSI or LSIG

400

600

150

250

300

ABB

100

400

PR222DS/PD-LSI or LSIG
600

100

150

250

300

400

600

2/5

Circuit breakers for power distribution


Thermomagnetic trip units

Thermomagnetic trip units


Tmax T1B 1p, T1, T2, T3, T4 and T5, and Isomax S6 circuit breakers
can be fitted with thermomagnetic trip unit and are used in protection
of alternating current networks or direct current networks with a range
of application from 15 A to 800 A. They allow protection against overloads with a thermal device (fixed threshold for T1B 1P, T1, T2, T3, T4
up to 20 A; adjustable threshold between 0.71 x In for T4, T5 and
S6), made using the bimetal technique, and protection against

Thermomagnetic trip unit TMF, TMD and TMA

TMD
Thermal threshold
Adjustable from 0.7 to 1 x In

Magnetic threshold
1SDC210170F0023

Fixed (I3 = 10 x In)

TMA

Thermal threshold
Adjustable from 0.7 to 1 x In

Magnetic threshold
Adjustable from 5 to 10 x In

TMF = thermomagnetic trip unit with fixed


thermal threshold (I1 = In) and fixed
magnetic thresold (I3 = 10 x In).
TMD = thermomagnetic trip unit with adjustable
thermal threshold (I1 = 0,71 x In) and
fixed magnetic threshold (I3 = 10 x In).
TMA = thermomagnetic trip unit with adjustable
thermal threshold (I1 = 0.71 x In)
and adjustable magnetic threshold
(I3 = 510 x In).

2/6

1SDC210172F0023

ABB

short-circuit with a magnetic device (fixed threshold for T1 1P, T1, T2,
T3 and T4 up to 50 A, adjustable threshold between 510 x In for T4,
T5 and S6; Isomax S6 can also offer a fixed magnetic threshold of
2.5 x In).
The four-pole circuit breakers are always supplied with the neutral
protected by the trip unit and protection of the neutral at 100% of the
phase setting.

Thermomagnetic trip units


In [A]

15

20

25

30

35

40

50

60

70

80

90

100

125

150

175

200

225

250

300

400

600

800

Neutral [A]

15

20

25

30

35

40

50

60

70

80

90

100

125

150

175

200

225

250

300

400

600

800

T1 (I1=In)

T2 (I1=In)

T3 (I1=In)

T4 (I1=In)

T4 (I1=0.7...1xIn)

T5 400 (I1=0.7...1xIn)

T5 600 (I1=0.7...1xIn)

S6 (I1=0.7...1 x In)

T1
I3 [A]

1000 1000 1000 1000

1000 1500 1500 1500 1500 1500 1500

Neutral [A]

1000 1000 1000 1000

1000 1500 1500 1500 1500 1500 1500

T2, T3
I3 [A]

500

500

500

500

500

500

500

600

700

800

900 1000 1250 1500 1750 2000 2250

Neutral [A]

500

500

500

500

500

500

500

600

700

800

900 1000 1250 1500 1750 2000 2250

I3 [A]

500

500

500

500

500

400
800

500 625 750


1000 1250 1500

1000
2000

1250 1500 2000 3000 4000


2500 3000 4000 6000 8000

Neutral [A]

500

500

500

500

500

400
800

500 625 750


1000 1250 1500

1000
2000

1250 1500 2000 3000 4000


2500 3000 4000 6000 8000

T4, T5, S6

S6
I3 = 2.5 x In [A]

ABB

1500 2000

2/7

Circuit breakers for power distribution


Electronic trip units

General characteristics
Tmax T2, T4 and T5 circuit breakers for uses in alternating current
can be equipped with PR221DS, the new PR222DS/P and
PR222DS/PD electronic trip units. On the other hand, Isomax S6,
S7 and S8 can be fitted with PR211/P and PR212/P. The electronic technology used to realise these trip units guarantees great
reliability, trip precision and immunity to electromagnetic components in compliance with the standards on the matter. The power
supply required for correct operation is supplied directly by the trip
units current transformers and tripping is always guaranteed, even
under single-phase load conditions and in correspondence with
the minimum setting.
The protection trip units are made up of the current transformers
(three or four depending on the number of conductors to be
protected), the protection unit (PR221DS, PR222DS/P,
PR222DS/PD, PR211/P or PR212/P), and of a trip coil with demagnetisation, which acts directly on the circuit breaker operating
mechanism unit. It is possible to test the trip coil by means of the
TT1 device. A positive test will trip the breaker.
The current transformers are housed inside the trip unit box and
supply the energy required for correct operation of the protection
and the signal needed to detect the current. They are available
with primary rated current as indicated in the table.

Characteristics of PR221DS, PR222DS/P, PR211/P, PR212/P electronic trip units


Operating temperature
Relative humidity
Service Frequency
Electromagnetic compatibility (LF and HF)
Electrostatic discharges
Radiated electromagnetic field
Short-time transients
Mean time between failure (MTBF)
Characteristics of the signalling contact
Maximum interrupted current
Maximum interrupted voltage
Breaking capacity
Contact/contact insulaton
Contact/coil insulation

2/8

-13 F...+158 F (-25 C...+70 C)


90%
45...66 Hz able to measure harmonics up to 550 Hz
IEC 60947-2 Annex F
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
15 years (at 113 F/45 C)
(for PR211/P and PR212/P only)
0.5 A
24 V DC/AC
3W/VA
500 V AC
1000 V AC

ABB

Current transformers
PR221DS

In [A]

25

60

100

T2

150

250

T4

300

400

120300
3003000
3003000

160400
4004000
4004000

T5 400

T5 600
L
S
I

PR222DS/P or
PR222DS/PD

In [A]

1025
25250
25250

2460
60600
60600

40100
1001000
1001000

60150
1501500
1501500

100

150

250

T4

100250
2502500
2502500
300

400

120300
1803000
4503600
60300

160400
2404000
6004800
80400

T5 400

PR211/P

600

In [A]

400

600

800

160400

240600

320800

4001000

4801200

6004800

9007200

12009600

150012000

180014400

60150
901500
2251800
30150

100250
1502500
3753000
50250

1000

In [A]
S6

400

600

800

S7

1000

1200

4001000

4801200

S8
320800

1600

240600
3606000
9007200
120600

40100
601000
1501200
20100

S7

ABB

240600
6006000
6006000

T5 600
L
S
I
G

S6

PR212/P

600

1200

2000

2500

6401600

8002000

10002500

160400

240600

4004000

6006000

8008000

100010000

120012000

160016000

200020000

250025000

6004800

9007200

12009600

150012000

180014400

240019200

300024000

375030000

80400

120600

160800

2001000

2401200

3201600

4002000

5002500

2/9

Circuit-breakers for power distribution


Electronic trip units

PR221DS - Tmax T2, T4 and T5


The PR221DS trip unit, available for T2, T4 and T5, provides protection functions against overload L,
and short-circuit S or I (version PR221DS-LS/I): with this version, you can choose between protection S or I simply by moving the dip-switch. Alternatively, the version with only the function of protection against instantaneous short-circuit I is available (version PR221DS-I).
The PR221DS for Tmax T2 has some differences if compared with the one used with T4 and T5.
With Tmax T2, the trip unit is not interchangeable, protection against overload L can be set manually
at I1 = 0.41 x In, with 16 thresholds by means of a dip switch on the front of the circuit breaker, and
it is possible to select between 2 trip curves 3s at 6 x I1 and 6s at 6 x I1.
On the other side, with Tmax T4 and T5, the trip unit is interchangeable; furthermore, protection L
can be set manually at I1 = 0.41 x In with 16 thresholds by means of a dip switch and it is possible
to select between 2 different trip curves 3s at 6 x I1 and 12s at 6 x I1.

2
PR221DS-LS/I

Protection S
Against short-circuit with
delayed trip

Dip-switches for setting the


neutral (only for T4 and T5)

Protection L

Socket for
TT1 test unit

Against overload

1SDC210173F0023

Protection I

2/10

Against short-circuit with


instantaneous trip

ABB

The protection function against short-circuit with delayed trip S, with inverse short time delay and trip
characteristic with inverse time (I2t = const), can be set to I2 = 110 x In with 15 thresholds. This
protection is selectable as an alternative to protection function I. The protection time delay can be
selected by adjusting the dip switches on one of the two available curves (0.1s at 8 x In, 0.25s at
8 x In).
The protection function against instantaneous short-circuit I can be adjusted to I3 = 110 x In with
15 thresholds.
Concerning to neutral protection, for Tmax T2 the protection of the neutral is set to 100% of the
phase protection setting, whereas for T4 and T5 it is possible to select the protection threshold OFF,
50% or 100% directly from the front of the trip unit by means of the specific dip switch.

2
PR221DS - Protection functions and settings
Protection functions

CANNOT BE
EXCLUDED

CAN BE
EXCLUDED

CAN BE
EXCLUDED
(1)

Against overload with long inverse time delay trip and trip
characteristic according to an
inverse time curve (I2t=constant)

Trip curves(1)

I1 = 0.40 - 0.44 - 0.48 - 0.52 0.56 - 0.60 - 0.64 - 0.68 0.72 - 0.76 - 0.80 - 0.84 0.88 - 0.92 - 0.96 - 1 x In
Release between 1.1...1.3 x I1
(IEC 60947-2 and UL 489)

at 6 x I1
t1 = 3s

Against short-circuit with inverse


short time delay trip and trip characteristic with inverse time
(I2t=constant) (selectable as an alternative to protection function I)

I2 = 1 - 1,5 - 2 - 2,5 - 3 - 3,5 - 4,5 5,5 - 6,5 - 7 - 7,5 - 8 - 8,5 - 9 10 x In


Tolerance: 10% (T4-T5)
10% up to 2 x In (T2)
20% above 2 x In (T2)

Against short-circuit with instantaneous trip (selectable as


an alternative to protection function S)

I3 = 1 - 1,5 - 2 - 2,5 - 3 - 3,5 - 4,5 5,5 - 6,5 - 7 - 7,5 - 8 - 8,5 - 9 10 x In


Tolerance: 10% (T4-T5)
20% (T2)

These tolerances hold in the following conditions:


self-powered relay at full power and/or auxiliary supply;
two or three-phase power supply.

ABB

Trip threshold

Tolerance:

at 6 x I1
t1 = 6s
only for T2

at 6 x I1
t1 = 12s
only for
T4, T5

10% up to 6 x In;
20% above 6 x In
a 8 x In
t2 = 0,1s

a 8 x In
t2 = 0,25s

Tolerance: 10% up to 6 x In (T4-T5)


20% above 6 x In (T4-T5)
20% (T2)
istantaneous 25ms

peak factor peak = 2 (L and S with current 3 In; I)


rms

2/11

Circuit breakers for power distribution


Electronic trip units

PR222DS/P - Tmax T4 and T5


The PR222DS/P trip unit, available for T4 and T5, has protection
functions against overload L, delayed S and instantaneous I shortcircuit (version PR222DS/P-LSI) and, alternatively, as well as the
functions L, S, I also has protection against earth fault G (version
PR222DS/P-LSIG).
Function L, which cannot be excluded, can be set manually to
I1 = 0.41 x In with 32 thresholds by means of the dip switches or
electronically by means of the PR010T test and configuration unit:
in this case the thresholds are 61 (steps of 0.01 In). Furthermore,
it is possible to select among 4 different trip curves: 3s at 6 x I1, 6s
at 6 x I1, 9s at 6 x I1, 12s at 6 x I1 for T4 In = 250 A and T5 = 600 A,
and 18s at 6 x I1 for all the other settings.
The protection function against short-circuit with delayed trip S,
with inverse short time delay and trip characteristic with inverse
time (I2t = const) can be set to I2 = 0.610 x In with 15 thresholds
by means of the dip switches or electronically by means of the
PR010T test and configuration unit, with 95 thresholds (steps of
0.1 x In). The time delay of the protection can be selected either
manually by adjusting the dip switch to one of the 4 curves available (with delay of 0.05s at 8 x In, 0.1s at 8 x In, 0.25s at 8 x In or
0.5s at 8 x In) or electronically by means of PR010T between 0.05
and 0.5s at 8 x In with 46 thresholds (steps of 0.01s).
The protection function against instantaneous short-circuit I
can be adjusted to I3(1) = 1.512 x In with 15 thresholds, by means
of the dip switches or electronically by means of the PR010T test
and configuration unit, with 86 thresholds (steps of 0.1 x In).
The function of protection against earth fault G is adjustable either
manually, by means of dip switches, to I4 = 0.21 x In, with
7 thresholds or electronically with PR010T, with 81 thresholds (steps
of 0.01 In). It is also possible to select among 4 different trip curves:
0.1 s at 3.25 x I4, 0.2s at 2.25 x I4, 0.4s at 1.6 x I4 and 0.8s at
1.25 x I4, or to set the trip time electronically between 0.1 and 0.8s
with 71 thresholds (steps of 0.01s).
Concerning to neutral protection, it is possible to select the protection threshold OFF, 50% or 100% directly from the front of the
release by means of the specific dip switch.
Furthermore, on the front of the trip unit, signalling of pre-alarm
and alarm of protection L is available. The pre-alarm threshold
value is equal to 0.9 x I1 (cannot be modified or excluded).

(1)

2/12

For T5 In = 600 A I3max = 10 x In

ABB

PR222DS/PD
Apart from the protection functions against overload L, delayed S and instantaneous I
short-circuit (version PR222DS/
PD-LSI) or, alternatively,
Communication functions
Protocol

plus the extra protection G


(version PR222/PD-LSIG), the
PR222DS/PD trip unit, available
for T4 and T5, also has the dialogue unit integrated with
PR222DS/P

Physical medium
Speed (maximum)
Measurement functions
Phase currents
Neutral
Earth
Signalling functions
L pre-alarm and alarm LED
L alarm output contact (2)
Data available
State of the circuit-breaker (open, closed)
Mode (local, remote)
Protection parameters set
Alarms
Protections: L, S, I, G
Release control for failed fault
Maintenance
Total number of operations
Total number of trips
Number of trip tests
Number of manual operations
Number of trips for each individual
protection function
Record of last trip data
Commands
Circuit breaker opening/closing
(with motor operator)
Alarm reset
Circuit breaker reset (with motor operator)
Setting the protection curves and thresholds
Safety function
Automatic opening in the case of failed
release for fault (with motor operator)
Events
Changes in circuit breaker state,
in the protections and all the alarams
(1)
(2)

PR222DS/PD
Modbus RTU
standard
EIA RS485
19200bps

(1)
(1)
(1)

(1)

(1)
(1)

(1)

Modbus RTU protocol.


PR222PD allows Tmax T4 and
T5 circuit breakers to be integrated in a communication network based on the Modbus
RTU protocol. The devices use
the EIA RS485 standard as the
physical means for data transmission at a maximum transmission speed of 19200 bit/sec.
If the power for protection function is supplied directly by the
current transformers of the release, communication is only
possible with an auxiliary power
supply of 24 V DC.
All the information provided by
the trip unit (measurement functions, alarms, maintenance
data, state of the circuit breaker)
can be consulted both locally,
directly on the front of the circuit breaker, and remotely by
means of supervision and control systems.
The PR222DS/PD trip unit can
be associated with the AUX-E
auxiliary contacts in electronic
version, to know the state of the
circuit breaker (open/closed),
and with AUX-E plus MOE-E
motor operator (the AUX-E are
compulsory when MOE-E is to
be used) to remotely control circuit breaker opening and closing as well.

With PR010/T unit


Typical contact: MOS photo Vmax: 48 V DC/30 V AC
Imax: 50 mA DC/35 mA AC

Auxiliary power supply - Electrical characteristics


Auxiliary power supply (galvanically insulated)
Maximum ripple

ABB

PR222DS/PD
24 V DC 20%
5%

Inrush current @ 24 V

1 A for 30 ms

Rated current @ 24 V

100 mA

Rated power @ 24 V

2.5 W

2/13

Circuit breakers for power distribution


Electronic trip units

PR222DS/P
Protection I

Protection S

Against short-circuit
with instantaneous trip

Against short-circuit
with delayed trip

Protection L
Against overload

Protection G
Socket for test
TT1 test unit

Against earth fault


Dip-switches for
setting the neutral

1SDC210174F0023

Socket for connection of


PR010/T test unit

Selection for electronic


or manual setting

PR222DS/PD

Protection I

Protection S

Against short-circuit
with instantaneous trip

Against short-circuit
with delayed trip

Protection L
Against overload

Protection G
Socket for test
TT1 test unit

Against earth fault


Dip-switches for
setting the neutral

Socket for connection of


PR010/T test unit

1SDC210175F0023

Selection for local


or remote setting

2/14

Selection for electronic


or manual setting

ABB

PR222DS/P and PR222DS/PD - Protection functions and settings


Protection functions

CANNOT BE
EXCLUDED

CAN BE
EXCLUDED

Against overload with long inverse time delay trip and trip
characteristic according to an
inverse time curve (I2t= constant)

Against short-circuit
with inverse short
time delay trip and
trip characteristic
with inverse time
(I2t= constant) or definite time

Trip curves(1)

Trip threshold
Manual setting
I1 = 0.40 - 0.42 - 0.44
0.48 - 0.50 - 0.52
0.56 - 0.58 - 0.60
0.64 - 0.66 - 0.68
0.72 - 0.74 - 0.76
0.80 - 0.82 - 0.84
0.88 - 0.90 - 0.92
0.96 - 0.98 - 1 x In

0.46
0.54
0.62
0.70
0.78
0.86
0.94

Electronic setting
at 6 x I1
t1 = 318s (step 0.5s)(2)

Release between 1.1...1.3 x I1


(IEC 60947-2 and UL 489)

Tolerance: 10%

I2t=const ON Electronic setting


I2 = 0.6010 x In (step 0.1 x In)

Against short-circuit with


instantaneous trip
CAN BE
EXCLUDED

at 6 x I1
t1 = 9s

Electronic setting
I1= 0.401 x In (step 0.01 x In)

Manual setting
I2 = 0.6 - 1.2 - 1.8 - 2.4 - 3.0 3.6 - 4.2 - 5.8 - 6.4 - 7.0 7.6 - 8.2 - 8.8 - 9.4 - 10 x In

I2t=const OFF

Manual setting
at 6 x I1
at 6 x I1
t1 = 3s
t1 = 6s

Manual setting
at 8 x In
at 8 x In
t2 = 0.05s
t2 = 0.1s

at 8 x In
t2 = 0.25s

at 6 x I1
t1 = 18s(2)

2
at 8 x In
t2 = 0.5s

Electronic setting
at 8 x In
t2 = 0.050.5s (step 0.01s)

Tolerance: 10%

Tolerance: 10% (4)

Manual setting
I2 = 0.6 - 1.2 - 1.8 - 2.4 - 3.0 3.6 - 4.2 - 5.8 - 6.4 - 7.0 7.6 - 8.2 - 8.8 - 9.4 - 10 x In

Manual setting
t2 = 0.1s
t2 = 0.05s

Electronic setting
I2 = 0.6010 x In (step 0.1 x In)

Electronic setting
t2 =0.050.5s (step 0.01s)

Tolerance: 10%

Tolerance: 10%(4)

Manual setting
I3 = 1.5 - 2.5 - 3 - 4 - 4.5 - 5 5.5 - 6.5 - 7 - 7.5 - 8 - 9 9.5 - 10.5 - 12 x In (3)

t2 = 0.25s

t2 = 0.5s

istantaneous 25 ms

Electronic setting
I3 = 1.512 x In (step 0.1 x In) (3)
Tolerance: 10%

CAN BE
EXCLUDED

(1)

Against earth fault with inverse


short time delay trip and trip
characteristic according to an
inverse time curve (I2t= constant)

These tolerances hold in the following conditions:


self-powered relay at full power and/or auxiliary supply;
two or three-phase power supply
sinusoidal wave forms with peak factor 1.41
peak factor peak = 2 (L 3 In; S, I, G)
rms

ABB

Manual setting
I4 = 0.2 - 0.25 - 0.45 - 0.55 0.75 - 0.8 - 1 x In

Manual setting
up to
up to
2.25 x I4
3.15 x I4
t4 = 0.1s
t4 = 0.2s

Electronic setting
I4 = 0.21 x In (step 0.01 x In)

Electronic setting
t4 = 0.1...0.8 x In (step 0.01s)

Tolerance: 10%

Tolerance: 20%

(2)
(3)
(4)

up to
1.6 x I4
t4 = 0.4s

up to
1.10 x I4
t4 = 0.8s

for T4 In = 250 A and T5 In = 600 A t1 = 12s


for T4 In = 250 A and T5 In = 600 A I3max = 10 x In
tolerance: 10 ms up to t2 = 0.1s

2/15

Circuit breakers for power distribution


Electronic trip units

PR211/P - Isomax S6 and S7


PR211/P trip unit (available for Isomax S6 and S7) provides protection functions against overload L
and instantaneous short-circuit I, and is available in the versions with functions I and LI.
Function L, which cannot be excluded, can be set manually to I1 = 0.41 x In by means of the dip
switches on the front of the circuit-breaker. Furthermore, it is possible to select among 4 different trip
curves: 3s at 6 x I1, 6s at 6 x I1, 12s at 6 x I1 and 18s at 6 x I1.
The protection function against instantaneous short-circuit I can be adjusted to I3 = 1.512 x In by
means of the dip switches.
Neutral protection is set to 50% of the phase protection. Ask ABB for the 100% version.

PR212/P - Isomax S6, S7 and S8


PR212/P trip unit (available from Isomax S6 to S8) provides protection functions against overload L,
delayed short-circuit S and instantaneous short-circuit I, and against earth fault G. It is available in
the versions PR212/P with functions LSI and LSIG.

PR211/P
Protection L
Against overload
Socket for
TT1 test unit

Protection I

1SDC210466F0003

Against short-circuit with


instantaneous trip

PR212/P
Protection I
Dip-switch for
setting the neutral

Against short-circuit with


instantaneous trip

Protection G

Protection S

Against earth fault

Against short-circuit
with delayed trip

Socket for connection of


PR010/T Test unit

Protection L
Against overload
Socket for
TT1 test unit

2/16

1SDC210467F0003

Selection for electronic


or manual setting

ABB

Function L, which cannot be excluded, can be set manually to I1 = 0.41 x In by means of the dip
switches on the front of the circuit-breaker. Furthermore, it is possible to select among 4 different trip
curves: 3s at 6 x I1, 6s at 6 x I1, 12s at 6 x I1 and 18s at 6 x I1.
The protection function against short-circuit with delayed trip S, with inverse short time delay and trip
characteristic with inverse time (I2t = const), can be set to I2 = 110 x In by means of the dip
switches or electronically by means of the PR010T test and configuration unit. The time delay of the
protection can be selected either manually by adjusting the dip switch to one of the 4 curves available (with delay of 0.05s at 8 x In, 0.1s at 8 x In, 0.25s at 8 x In or 0.5s at 8 x In) or electronically by
means of PR010T between 0.05 and 0.5s at 8 x In. The protection functions against instantaneous
short-circuit I and earth fault G can be adjusted respectively to I3 = 1.512 x In and I4 = 0.21 x In,
by means of the dip switches or electronically by means of the PR010T.
For four-pole circuit breakers, protection of the neutral can be set to 50% or 100% of the phase
protection setting, by means of dip-switches on the front of the trip unit.
Setting the adjustment parameters of the protection functions is carried out directly from the front of
the trip unit or remotely, thanks to the use of the PR212/D (IEC only) dialogue unit, available with
Modbus or LON communication protocols.

PR211/P and PR212/P - Protection functions and settings


Protection function

Trip threshold

Against overload with inverse long time delay and


trip characteristic according to a time dependent
CANNOT BE
2
EXCLUDED curve (I t = constant)

Against short-circuit with


inverse short time delay
and trip characteristic
with dependent time
CAN BE
(I2t = constant) or indeEXCLUDED
pendent time

Against short-circuit with


adjustable instantaneous
trip

Trip curves
A
B

I1 = 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.95 1 x In - PR211/P


0.4 - 0.5 - 0.55 - 0.6 - 0.65 0.7 - 0.75 - 0.8 - 0.85 - 0.875 0.9 - 0.925 - 0.95 - 0.975 1 x In - PR212/P
Release between 1.051.30 x I1
(IEC 60947-2 and UL 489)

at 6 x I1
at 6 x I1
at 6 x I1
at 6 x I1
t1 = 3s
t1 = 6s
t1 = 12s
t1 = 18s
(tolerance: + 10% up to 2 x In; + 20% above 2 x In)

I2t=const
ON

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In
Tolerance 10%

at 8 x In
at 8 x In
t2 = 0.05s t2 = 0.1s
(tolerance: + 20% )

at 8 x In
t2 = 0.25s

at 8 x In
t2 = 0.5s

I2t=const
OFF

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In
Tolerance 10%

t2 = 0.05s t2 = 0.1s
(tolerance: + 20% )

t2 = 0.25s

t2 = 0.5s

I3 = 1.5 - 2 - 4 - 6 - 8 - 10 - 12 x In
Tolerance 20%

CAN BE
EXCLUDED

Against earth fault with


short inverse time delay
and trip characteristic according to a dependent
CAN BE
time curve (I2t = constant)
EXCLUDED

ABB

I4 = 0.2 - 0.3 -0.4 - 0.6 - 0.8 - 0.9 1xIn


Tolerance 20%

up to
up to
up to
up to
3.25 x I4
2.25 x I4
1.6 x I4
1.25 x I4
t4 = 100ms t4 = 200ms t4 = 400ms t4 = 800ms
(tolerance: + 20% )

2/17

Motor control protection circuit breakers: MCP


Magnetic and electronic trip units

General characteristics

MCP
Frame size
Poles
Ratings
Interrupting ratings
240 V AC
480 V AC
600 V AC
500 V DC
600 V DC
Trip unit
Adjustable
magnetic only (612 x In)
Electronic
PR221DS-I
PR211/P-I

1SDC210178F0023

MCP circuit breakers are used to protect three phase asynchronous motors.
The traditional system used for this purpose is based on three
different devices: a circuit breaker for protection against short-circuit, a thermal relay for protection against overload and phase
loss or unbalance of phase, and a contactor for motor switching.
All this has to take into account the problems that arise at the
moment of the motor starting.
In particular, when selecting these devices, different factors must
be taken into consideration, such as:
the motor power
the diagram and type of starting
the type of motor: with cage rotor or with wound rotor
the fault current at the point of the network where the motor is
installed.

T2

T3

T4

T5

S6

S7

S8

100
3
20100
S H
65 150
35 65

225
3
100200
S
65
35

250
3
100-150-250
N S H L
65 100 150 200
25 35 65 100
18 25 55 65

400-600*
3
300-400-600
N S H L
65 100 150 200
25 35 65 100
18 25 35 35

N
65
50
25

800
3
800
H
150
65
35

L
200
100
42

1200
3
1000-1200
H
100
65
50

1600-2000-2500
3
1600-2000-2500
V
120
100
85

35

* Please ask ABB for 600 A availability

2/18

ABB

ABB offers two different protection types:


a magnetic only trip unit (MA) for Tmax T2 and T3, with adjustable threshold between 612 x In
an electronic trip unit with only an instantaneous short-circuit
protection function I, PR221DS-I for Tmax T2, T4 and T5, and
PR211/P-I for Isomax S6, S7 and S8. For PR221DS-I, protection I is adjustable between 110 x In, whereas the range for
PR211/P is 1.512 x In.

Electronic trip units


In [A]
T2
T4
T5
S6
S7
S8

25

60

100

150

250

300

400

600

800

1000

1200

1600

2000

2500

2400

19200

3000

24000

3750

30000

Trip current function I


I3 [A]

25

250

60

600

100

1000

150

1500

250

2500

300

3000

400

4000

600

6000

1200

1600

1500

12000

1800

14400

PR221DS-I (Tmax T2, T4 and T5) - Protection functions and settings


Protection function

Trip threshold

Against short-circuit with adjustable instantaneous trip

I2t=const
ON

I3 = 1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5 - 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 - 9 - 10 x In


Tolerance 20%

PR211/P (Isomax S6S8) - Protection functions and settings


Protection function

Trip threshold

Against short-circuit with adjustable instantaneous trip

I3 = 1.5 - 2 - 4 - 6 - 8 - 10 - 12 x In
Tolerance 20%

MA - Magnetic only trip unit

I3 = 612 x In

In [A]

20

50

100

T2

T3
I3 [A]

ABB

120240

300600

125

150

200

6001200

7501500

9001800

12002400

2/19

Molded case switches: MCS


Electrical characteristics

General characteristics
The MCS can be used as general circuit breakers in sub-switchboards, as switching and isolation parts for lines, busbars or groups
of apparatus, or as bus-ties. They can be part of general isolation
devices of groups of machines or of complexes for motor operation and protection.
The MCS are derived from the corresponding circuit breakers, of
which they keep the overall dimensions, versions, fixing systems
and the possibility of mounting accessories.
The MCS up to 1200 A are available in three-pole and four-pole
versions, whereas the 2500 A size is only available in the threepole version.
All the molded case switches in accordance with UL 489 and CSA
C22.2 Standards are self protected.

MCS
Rating
[A]
Poles
[No]
Magnetic override
[A]
Rated Voltage
AC (50-60 Hz) [V]
DC [V]

T1N-D

T3S-D

T3S-D

T4H-D

S6H-D

S7H-D

S8V-D

100
3-4
1000

150
3-4
1500

225
3-4
2250

250
3-4
3000

T5H-D
600*
3-4
5000 6000

800
3-4
10000

1200
3-4
20000

2500
3
35000

480
500

480
500

480
500

600
600

600
600

600
600

600
600

600
600

400

* Please ask ABB for 600 A availability

2/20

ABB

Accessories

Index
Versions and types .................................................................................................................. 3/3
Connection terminals .............................................................................................................. 3/7
Service releases .................................................................................................................... 3/14
Electrical signals .................................................................................................................... 3/20
Remote controls .................................................................................................................... 3/26
Operating mechanisms with locks ......................................................................................... 3/30
Residual current releases (IEC only) ....................................................................................... 3/37
Accessories for electronic trip units ....................................................................................... 3/41
Installation and testing accessories ....................................................................................... 3/46
Spare parts ........................................................................................................................... 3/47
Controller for automatic transfer switch - ATS010 (IEC only) .................................................. 3/48

ABB

3/1

Accessories

1SDC210200F0023

3/2

ABB

Accessories
Versions and types

Fixed

1SDC210201F0023

Fixed ABB molded case circuit breakers, in accordance with


UL/CSA standards up to 2500 A, are available in the two-pole,
three-pole and four-pole version up to 1200 A and only in the
three-pole version from 1600 A up to 2500 A.
The circuit breakers have:
single depth of 2.76 (70 mm) up to 225 A and 4.07
(103.5 mm) from 150 to 800 A
standardized front 1.77 (45 mm) up to 225 A
possibility of assembly on back plate or on DIN rail up to 225 A
(except T1B 1p)
thermomagnetic or electronic trip units
UL file: E93565 for circuit breakers and MCP; CSA file: LR54280
UL file: E116595 for MCS; CSA file: LR54280.

1SDC210202F0023

Plug-in

ABB

The plug-in version circuit breaker consists of:


fixed part to be installed directly on the back plate of the
cubicle
moving part, obtained from the fixed circuit breaker with addition of the isolating contacts (in correspondence with the connection terminals), of the rear frame (for fixing the fixed part),
and of the terminal covers.
Circuit breaker removal is carried out by unscrewing the top and
bottom fixing screws. A special lock prevents circuit breaker racking in and racking out with the contacts in the closed position.
Tmax T2 T3, T4 and T5 circuit breakers, starting from the fixed
version, can be changed into the various types using the conversion kits.

3/3

Accessories
Versions and types

1SDC210203F0023

Draw out

The draw out version circuit breaker consists of:


fixed part to be installed directly on the back plate of the cubicle with the side group mounted on the fixed part to allow the
racking-out/racking-in movement
moving part, obtained from the fixed circuit breaker with addition of the isolating contacts (in correspondence with the connection terminals), of the rear frame (for fixing the fixed part),
and of the terminal covers
accessory to be mounted on the front of the circuit breaker,
with selection between front flange for lever operating mechanism, motor operator and rotary handle operating mechanism;
application of one of these accessories allows the circuit breaker
lock to be made in the withdrawn position.
Racking-in/racking-out of the moving part is carried out by means
of the special crank supplied with the conversion kit of the fixed
circuit breaker into moving part of draw out circuit breaker. The
special mechanism allows the circuit breaker to be racked out in
the isolated position (with power and auxiliary circuits disconnected)
with the compartment door closed, increasing the safety of the
operation.
Once racked out or removed, the circuit breaker can be operated
in open or closed position and, by means of the special connectors, blank operating tests of the auxiliary control circuits can be
carried out.

Versions available

3/4

F
Fixed

P
Plug-in

W
Draw out

T1B 1p

T1

T2

T3

T4

T5

S6

S7

S8

ABB

Conversion kit into part of plug-in for


T2, T3, T4 and T5
(UL file: E116596)

1SDC210204F0023

Allows conversion of a fixed circuit breaker with front terminals into


the moving part of a plug-in circuit breaker. The kit consists of:
isolating contacts
anti-racking out safety device
assembly nuts and screws
terminals covers.
The circuit breaker is completed with the fixed part.
When the circuit breaker has electrical accessories mounted (SOR,
UVR, MOS, AUX, AUE), the socket-plug connectors can also be
ordered for isolation of the relative auxiliary circuits.

T2-T3

1SDC210206F0023

1SDC210205F0023

1SDC210207F0023

T4-T5
T2-T3

T4-T5

ABB

This allows the fixed circuit breaker with front terminals to


be converted into the moving part of a draw out circuit
breaker. The kit consists of isolating contacts, frame, and
assembly nuts and screws. The circuit breakers in the draw
out version must be completed, alternatively, with one of
the following accessories:
front for lever operating mechanism
rotary handle operating mechanism
motor operator
terminal covers
in order to prevent the racking-out operation with the circuit breaker
closed. The circuit breaker is completed with the fixed part.

1SDC210209F0023

1SDC210208F0023

Conversion kit into moving part of draw out


circuit breaker for Tmax T4, T5 and Isomax
S6 and S7

3/5

Accessories
Versions and types

Fixed part
(UL file: E116596)

1SDC210210F0023

The fixed part completes the circuit breaker in the plug-in or draw
out version. For plug-in or draw out version circuit breakers, different positions are available:
plug-in: plugged-in, unplugged
draw out version: racked-in/racked-out, removed.
The fixed part for draw out version is fitted with a guide for supporting the moving part during the isolation or withdrawal operations. For Isomax S6 and S7 circuit breakers, there are two guides.
For Tmax T2 and T3 circuit breakers, the fixed parts are available,
in the standard version, with front terminals (F): a distinguishing
characteristic of these two sizes of circuit breakers is the possibility of equipping the fixed parts with the same kit of terminals, terminal covers and phase separators, used for the fixed circuit breakers. With Tmax T4 and T5, codes of fixed parts are available with
different types of terminals (EF, HR, VR). The fixed parts with EF
terminals, moreover, can be also equipped with ES, FC Cu and
FC CuAl terminals.

Conversion kit for fixed part of plug-in into


fixed part of draw out for Tmax T4 and T5

1SDC210211F0023

A guide for converting the fixed part of a plug-in version circuit


breaker into the fixed part of a draw out version circuit breaker is
available for Tmax T4 and T5 circuit breakers.

1SDC210212F0023

Racking out crank

3/6

This allows racking out and racking in of the circuit breaker in the
draw out version into the fixed part, with the door closed. The
crank handle is the same for the whole range of circuit breakers
and is automatically supplied with the fixed part of draw out circuit
breakers or with the conversion kit for fixed part of plug-in into
fixed part of draw out.

ABB

Accessories
Connection terminals
The basic version of the circuit breakers is supplied with:
lugs for copper and aluminium cables (FC CuAl) for the Tmax T1 circuit breaker
front terminals (F) for Tmax T2, T3, T4, T5 and Isomax S6, S7 and S8 circuit breakers.
Different types of terminals are also available and these can be combined in various ways (top of one
type, bottom of a different type), allowing the circuit breaker to be connected to the plant in the most
suitable way for the installation requirements.
The following distinctions can be made between:
front terminals, which allow connection of cables or busbars by acting directly from the front of
the circuit breaker
rear terminals, which allow installation in switchboards with rear access to both cable and busbar
connections. For Tmax T2, T3, T4 and T5 the rear terminals are adjustable.
Terminals are available for direct connection of bare copper or aluminium cables (UL listed) and
terminals for connection of busbars or cables terminated with cable terminals.
An important feature of the Tmax T2 and T3 circuit breakers is that all the different types of terminals
can be mounted either on the fixed version circuit breaker or on the fixed part of the plug-in circuit
breaker. On the other hand, T4 and T5 fixed part can mount EF, HR or VR terminals, and, moreover,
fixed part with EF terminals can be equipped also with ES, FC Cu and FC CuAl terminals.
The information needed to make the connections is given for each type of terminal on page 3/9 and
following. The minimum and maximum cross-section of the cables, which can be tightened in the
terminals and the diameter of the terminal, are indicated for connection with bare cables. Flat bars of
different size and composition are recommended for connections with busbars. The required minimum depth is also indicated, if it is different to the one recommended.
The torque values to be applied to the tightening screws for cable terminals and to the screws used
to connect the busbars to the flat bar terminals are given.

ABB

The terminal covers are applied to the terminals of the circuit breaker
to prevent accidental contact with live parts.
The following are available:
low terminal covers (LTC), which guarantee IP40 degree of
protection for fixed circuit breakers with rear terminals and for
moving parts of plug-in or draw out circuit breakers
high terminal covers (HTC), for fixed circuit breakers with front,
front extended, front for cables and rear terminals; guarantee
IP40 degree of protection
terminal covers for fixed parts, of plug-in or draw out circuit
breakers for T4, T5, S6 and S7 circuit breakers, guarantee IP40
degree of protection on the front with moving part connected.
They are available in a single version. The fixed parts of plug-in
T2 and T3 circuit breakers can use the same terminal covers
as the corresponding fixed circuit breakers. For fixed parts
of T4 and T5 400, the proper terminal covers (TC-FP) are
available.
The degrees of protection indicated are valid for circuit breaker
installed in switchboards.

1SDC210214F0023

1SDC210213F0023

Insulating terminal covers

3/7

Accessories
Connection terminals

1SDC210215F0023

Phase separating partitions

These allow the insulation characteristics between the phases at


the connections to be increased. They are mounted from the front,
even with the circuit breaker already installed.
Two versions are available for Tmax circuit breakers:
3.94 (100 mm) high
7.87 (200 mm) high.
The H = 3.94 (100 mm) phase separators are supplied as standard with front extended type terminals (EF), whereas those with
H = 7.87 (200 mm) are standard with the front extended spread
type of terminals (ES).
They are incompatible with both the high and low insulating terminal covers.
The fixed parts of plug-in Tmax circuit breakers can use the same
phase separating partitions as the corresponding fixed circuit breakers. With the phase separating partitions mounted, a special kit is
available on request to reach IP40 degree of protection from the
front of the circuit breaker.
Moreover, it is possible to mount the phase separating partitions
between two circuit breakers or fixed parts side by side.
Phase separating partitions must always be requested for Isomax
S6 and S7 circuit breakers. They are always an alternative to the
high or low terminal covers.

Screws for sealing the terminal covers

1SDC210217F0023

1SDC210216F0023

These are applied to the terminal covers of fixed circuit breakers


or to the moving parts of plug-in or draw out circuit breakers. They
prevent removal of both the high and low terminal covers and can
be locked with a wire and lead seal.

3/8

Kit for taking up the auxiliary power supply


Special kits are available with the Tmax T2, T3, T4 and T5 circuit
breakers for taking up the auxiliary power supply directly from the
connection terminals. They can only be combined with the front
terminals for copper cables (FC Cu) or with the front terminals (F)
for T3, T4 and T5.

ABB

Connection terminals

EF

ES

FC Cu

FC CuAl(1)

RC

HR

VR

MC

Front

Extended
front

Front
extended
spread

Front
for copper
cables

Front for
copper and
aluminium
cables(3)

Rear(4)

Rear
for Cu/Al
cables

Rear
flat
horizontal

Rear
flat
vertical

Multi-cable
terminals

F(2)
F-P
F-P
F-P-W
F-P-W

F(2)
F-P
F-P
F-P-W
F-P-W
F
F

P-W
P-W
W
F-W
F

(1)

UL listed
(2)
Standard supply

F-P
F-P
F-P-W
F-P(5)-W(5)
F
F

(3)

(5)

External and standard versions


(4)
Orientated for Tmax and threaded for Isomax

Front terminals - F

S6
1SDC210229F0023

T1-T5

F
F-P
F-P
F
F
F

P-W
P-W
W
F-W

F = Fixed
P = Plug-in
W = Draw-out

Only for T5 600

S7
1SDC210230F0023

F
F-P
F-P
F-P-W
F-P-W
F-W
F-W

F - P(2)
F - P(2)
F(2)
F(2)
F(2)
F(2)
F(2)

1SDC210230F0023

T1
T2
T3
T4
T5
S6
S7
S8

Allow connection of busbars or cables terminated with cable terminals


Type
T2
T3
T4
T5
S6
S7
S8 2000
S8 2500

Version
F-P
F-P
F
F
F
F
F
F

Pieces
1
1
1
1
2
2
3
4

Busbars/cable terminals [in-mm]


Tightening [Ibin-Nm]
W
H
D

B
0.79-20 0.3-7.5
0.2-5
0.26-6.5
54-6
0.94-24 0.37-9.5 0.31-8
0.33-8.5
71-8
0.98-25 0.37-9.5 0.31-8
0.33-8.5
161-18
1.38-35 0.43-11 0.40-10 0.41-10.5
250-28
1.97-50 0.47-12 0.20-5
2 x 0.27-7
80-9
1.97-50 0.79-20 0.31-8
2 x 0.43-11
161-18
3.94-100

0.20-5
4 x 0.59-15
625-70
3.94-100

0.20-5
4 x 0.59-15
625-70

high
R
R
R
R
R

Terminal covers
low
fixed part
R

Phase separators
R
R
R
R
R
R

A = Tightening the terminal onto the circuit breaker


B = Tightening of the cable/busbar onto the terminal
R = On request
S = Standard

ABB

3/9

Accessories
Connection terminals

PF S6
1SDC210230F0023

PF S7
1SDC210230F0023

S7
1SDC210230F0023

S6 800

1SDC210230F0023

T1-T5
1SDC210231F0023

Front extended terminals - EF

Allow connection of busbars or cables terminated with cable terminals

T1
T2
T3
T4

F
F-P
F-P
F
P-W
F
P-W
F-W
F-W

T5
S6
S7

Pieces
1
1
1
1
1
2
2
2
2

Busbars [in-mm]
Cable terminals [in-mm] Tightening [Ibin-Nm]
W
D

A
B(1)
0.59-15 0.20-5 0.33-8.5
0.59-15 0.33-8.5
63-7
80-9
0.79-20 0.16-4 0.33-8.5
0.79-20 0.33-8.5
54-6
80-9
0.79-20 0.24-6 0.39-10
0.79-20 0.39-10
71-8
161-18
0.79-20 0.39-10 0.39-10
0.79-20 0.39-10
161-18
161-18
0.79-20 0.39-10 0.31-8
0.79-20 0.31-8

80-9
1.18-30 0.27-7 0.43-11
1.18-30 0.43-11
252-28
161-18
1.18-30 0.59-15 0.39-10
1.18-30 0.39-10

161-18
1.97-50 0.20-5 0.55-14
1.97-50 0.55-14
80-9
268-30
1.97-50 0.31-8 4 x 0.43-11 1.97-50 4 x 0.43-11
402-45
161-18

T1-T5

S6
1SDC210232F0023

Front extended spread terminals - ES

Terminal covers
high low fixed part
R

R
R

R
R
R

Phase separators

Terminal covers
high low fixed part

Phase separators

S
S
S
S
R
S
R
R
R

S7
1SDC210230F0023

Version

1SDC210230F0023

Type

Allow connection of busbars or cables terminated with cable terminals

(1)

Type

Version

Pieces

T2
T3
T4
T5
S6
S7

F-P
F-P
F-P-W
F-P(1)-W(1)
F
F

1
1
1
1
1
1

Busbars [in-mm]
Cable terminals [in-mm] Tightening [Ibin-Nm]
W
D

A
B
1.18-30 0.16-4 0.41-10.5
1.18-30
0.41-10.5
54-6
161-18
1.18-30 0.16-4 0.41-10.5
1.18-30
0.41-10.5
71-8
161-18
1.18-30 0.24-6 0.41-10.5
1.18-30
0.41-10.5
161-18
161-18
1.57-40 0.39-10 0.43-11
0.43-11
0.43-11
252-28
161-18
3.54-90 0.31-8 3 x 0.51-13 4x1.77-45 0.51-13
80-9
268-30
3.54-90 0.59-15 3 x 0.51-13 4x1.77-45 0.51-13
402-45
179-30

S
S
S
S

Only for T5 600

A = Tightening the terminal onto the circuit breaker


B = Tightening of the cable/busbar onto the terminal
R = On request
S = Standard

3/10

ABB

1SDC210233F0023

Front terminals for copper cables - FC Cu

Allow connection of bare copper cables directly to the circuit breaker

T1/T1P F
F
T2
F-P
F-P
T3
F-P
F-P
T4
F-P-W
F-P-W
T5
F-P-W
F-P-W
F

1
2
1
2
1
2
1
2
1
2
2

Cable [AWG or Kcmil-mm2]


rigid
flexible
142/0-2.570
141-2.550

141-2.550
183/0-195
182/0-170

180-150
10350-6185
10300-6150

102/0-670
14350-2.5185
14300-2.5150

143/0-2.595
6500-16240
6500-16300

6300-16150

1350-50185

Tightening [Ibin-Nm]
A
B

62-7

62-7

62-7

62-7

89-10

89-10

89-10

89-10

222-25

222-25
161-18 279-31

0.47-12
0.47-12
0.55-14
0.55-14
0.71-18
0.71-18
0.71-18
0.71-18
1.1-28
1.1-28
0.85-21.5

T2-T5 Standard

Terminal covers
high low
fixed part
R
R

R
R

R
R
R
R
R
R
R
R
R
R
R
R
R
R
S
R
R
S
R
R
S
R
R
S
S

T4-T5 External

Phase separators
R
R
R
R
R
R
R
R
R
R

S6 800
1SDC210235F0023

1SDC210234F0023

Front terminals for copper/aluminium cables - FC CuAl (UL listed)

[in-mm]

S7
1SDC210236F0023

Version Pieces

1SDC210236F0023

Type

Allow connection of bare copper or aluminium cables directly to the circuit breaker (solid aluminium cables cannot be used)
Type

Assembly

Version

Pieces

T1 1P/T1 standard

T2
T3

F-P
F-P
F-P
F-P-W
F
F
F
F-P-W
F
F
F

1
1
1
1
1
2
2
1
3
2
4

T4
T5

S6
S7

standard
standard
standard
standard
standard
external
external
standard
standard
standard
standard

Cable
[AWG or Kcmil-mm2]
rigid
1410-2.56
8.0-10
61/0-1650
141/0-2.550
141/0-2.550
4300-25150
10350-6185
141/0-2.550
3/0250-95120
3/0500-95240
250500-120240
2/0400-70185
250500-120240
4/0500-95240

Tightening [Ibin-Nm]
A
20-2.5
40-4.5
45-5
80-9
80-9
80-9
274-31
50-5.6
274-31
274-31
380-43
80-9
44-5
311-35

[in-mm]

50-5.6
50-5.6
200-22.6
80-9
80-9
159-18
159-18
159-18
383-43
276-31
383-43

Terminal covers
low
R

fixed part

0.37-9.5

high
R

0.39-10
0.67-17
0.7-18
0.39-9.9
0.61-15.5
0.84-21.5
0.84-21.5
0.75-9
0.87-22
0.85-21.5

R
R
R
R
R
S
S
R
S
S
S

R
R
R
R
R

R
R
R
S

Phase separators
R

R
R
R
R
R
R
R
R

A = Tightening the terminal onto the circuit breaker


B = Tightening of the cable/busbar onto the terminal
R = On request
S = Standard

ABB

3/11

Accessories
Connection terminals

1SDC210237F0023

Rear orientated terminals for Tmax - R

Allow connection of busbars or cable terminal at the rear


Version

T2
T3
T4
T5

Pieces

F-P
F-P
F
F

1
1
1
2

Busbars [in-mm]
W
D

0.79-20 0.16-4 0.33-8.5


0.79-20 0.24-6 0.33-8.5
0.79-20 0.39-10 0.33-8.5
1.18-30 0.27-7 0.43-11

Tightening [Ibin-Nm]
A
B
54-6
80-9
54-6
80-9
54-6
80-9
161-18 161-18

Threaded rear terminals for Isomax - R

Terminal covers
high
low

Phase separators

1SDC210236F0023

Type

S6

Allow connection of busbars at the rear


Type

Version Pieces

S6

Busbars [in-mm]
W
D

1.97-50 0.20-5 0.98-25

Cable terminals [in-mm] Tightening [Ibin-Nm]


L

A
B
1.97-50 0.98-25
161-18 890-100

Rear terminals for copper/aluminium cables for Isomax - RC

Terminal covers
high low fixed part

Phase separators

S6 800
1SDC210236F0023

Allow connection of copper or aluminium cables directly to the circuit breaker


Type

S6

Version Pieces

Cable terminals
[AWG or Kcmil-mm2]
2/0300-70150

Tightening [Ibin-Nm]
A
80-9

B
276-31

[in-mm]

0.689-17.5

Terminal covers
high
S

low

fixed part

Phase separators

A = Tightening the terminal onto the circuit breaker


B = Tightening of the cable/busbar onto the terminal
R = On request
S = Standard

3/12

ABB

S7
1SDC210236F0023

1SDC210236F0023

1SDC210239F0023

S6

1SDC210236F0023

S7
1SDC210238F0023

Rear flat horizontal and vertical


terminals - HR/VR

Allow connection of busbars at the rear.


Type
T1
T4
T5 400
T5 600
S6
S7
S8 2000
S8 2500

Version Pieces
F
P-W
P-W
P-W
W
F-W
F
F

1
1
1
2
2
2
3
4

Busbars [in-mm]
W
D

0.55-14 0.20-5 0.24-6.2


0.79-20 0.39-10 0.39-10
0.98-25 0.39-10 0.47-12
1.57-40 0.59-15 0.43-11
1.97-50 0.20-5 0.55-14
1.97-50 0.31-8 4 x 0.43-11
3.94-100 0.20-5 4 x 0.59-15
3.94-100 0.20-5 4 x 0.59-15

Cable terminal [in-mm]


L

0.55-14 0.24-6.2
0.79-20 0.39-10
0.98-25 0.47-12
1.57-40 0.43-11
1.97-50 0.55-14

Tightening [Ibin-Nm]
A
B
63-7
45-5
161-18

161-18

161-18

267-30

179-20

625-70

625-70

Terminal covers
high low fixed part

Phase separators

Note: for T1 and S8 only the terminals are available.

1SDC210240F0023

Multi-cable terminals for Tmax - MC

Allow connection of cables directly to the circuit breaker


Type

Version

T4

Pieces
max
6

Cable [AWG or Kcmil-mm2]


flexible
rigid
144-2.525
144-2.535

Tightening [Ibin-Nm]
A
B
161-18 62-7

Terminal covers
high low fixed part
S

Phase separators

A = Tightening the terminal onto the circuit breaker


B = Tightening of the cable/busbar onto the terminal
R = On request
S = Standard

ABB

3/13

Accessories
Service releases

The shunt trip and undervoltage releases, housed and fixed in a slot on the left-hand side of the
circuit breaker, are always alternative to each other. They are supplied in the pre-cabled version with
39.4 (1 m) long cables for Tmax T1, T2 and T3 circuit breakers, or socket-plug connectors, still with
39.4 (1 m) long cables, for T4 and T5. For Isomax S6 and S7, the power supply is made by means
of special connectors.
Assembly is carried out by pressure into the appropriate seat located in the left-hand part of the
circuit breaker and fixing with the screw provided.

SOR - Shunt trip

This allows circuit breaker opening by means of an electrical


command. Operation of the release is guaranteed for a voltage
between 75% and 110% of the value of the rated power supply
voltage Un, both in AC and DC. It is always fitted with an auxiliary
limit contact.
Furthermore, PS-SOR opening coils with permanent operation are
also available for T4 and T5, with a much lower power consumption and these can be continuously supplied: in this case they are
not, in fact, fitted with an auxiliary limit contact. Again for these
coils, either the pre-cabled or uncabled version can be selected.
T4-T5

1SDC210242F0023

T1-T2-T3

1SDC210243F0023

1SDC210241F0023

(UL file: E116596)

S8

1SDC210244F0023

1SDC210245F0023

S6-S7

3/14

ABB

SOR - Electrical characteristics


Absorbed power on inrush
Tmax T1, T2, T3

Tmax T4 and T5

Version

AC [VA]

DC [W]

AC [VA]

DC [W]

12 V DC

50

150

2430 V AC

50

50

150

150

4860 V AC/DC

60

60

150

150

110127 V AC-110125 V DC

50

50

150

150

220240 V AC-220250 V DC

50

50

150

150

380440 V AC

55

150

480500 V AC

55

150

Opening times [ms]

15

15

15

15

Absorbed power on inrush


Isomax S6, S7

Isomax S8

Version

AC [VA]

DC [W]

AC [VA]

12 V DC

150

150

150

200

150
150

24 V AC/DC

DC [W]

30 V DC

48 V AC/DC

150

200

150

60 V DC

150

100127 V AC/DC
110120 V AC-110125 V DC
127150 V AC

200

150

150

150

200

160 V DC-150180 V AC

200

150

200250 V AC/DC

200

150

220240 V AC-220250 V DC

150

150

480 V AC

150

200

15

380500 V AC
Opening times [ms]

PS-SOR - Electrical characteristics


Absorbed power on inrush
Tmax T4 and T5
Version

ABB

AC [VA]

DC [W]

24-30 V DC

110120 V AC

3/15

Accessories
Service releases

1SDC210246F0023

UVR - Undervoltage release


(UL file: E116596)
This opens the circuit breaker due to a power supply failure of the
release or to voltage drops to values of less than 0.7 x Un with a
trip range from 0.69 to 0.35 x Un.
After tripping, the circuit breaker can be closed again starting from
a voltage higher than 0.85 x Un. With the undervoltage release
de-energized, it is not possible to close the circuit breaker.

T1-T2-T3

T4-T5

1SDC210247F0023

1SDC210243F0023

S8

1SDC210244F0023

1SDC210248F0023

S6-S7

3/16

ABB

UVR - Electrical characteristics


Power consumption during permanent operation
Tmax T1, T2, T3
Version

Tmax T4 and T5

AC [VA]

DC [W]

AC [VA]

1.5

1.5

48 V AC/DC

60 V AC/DC

110127 V AC-110125 V DC

220240 V AC-220250 V DC

2.5

2.5

380440 V AC

480500 V AC

Opening times [ms]

15

15

25

25

2430 V AC/DC

DC [W]

Power consumption during permanent operation


Isomax S6, S7
AC [VA]

DC [W]

AC [VA]

DC [W]

24 V DC

15

24 V AC

10

30

30 V DC

15

30 V AC

30 (50 Hz)

48 V AC

10

30 (50 Hz)

48 V DC

15

60 V DC

15

60 V AC

30 (50 Hz)

100 V AC

30 (50 Hz)

110115 V AC

30 (60 Hz)

110115 V AC

30 (50 Hz)

125127 V AC

30 (60 Hz)

110125 V DC

15

120 V AC

10

30

30 (50 Hz)

125 V DC

240 V AC

10

250 V DC

480 V AC

127130 V AC

10

208220 V AC

30 (60 Hz)

220 V AC

30 (50 Hz)

220250 V DC

15

230240 V AC

30 (50 Hz)

277 V AC

30 (60 Hz)

240 V AC

30

380 V AC

30 (60 Hz)

380400 V AC

30 (50 Hz)

440 V AC

30 (60 Hz)

480 V AC

30

500 V AC

30 (50 Hz)

25

25

25

25

Opening times [ms]

ABB

Isomax S8

Version

3/17

Accessories
Service releases

Closing coil

1SDC210250F0023

1SDC210249F0023

Used with Isomax S8 circuit breaker, this allows circuit breaker


closing by means of an electrical contact. Operation of the release is guaranteed for a voltage between 80% and 110% of the
value of the rated power supply voltage Un, both in AC and in DC.

3
Closing coil
Isomax S8
Absorbed power on inrush
Version

AC [VA]

24 V DC

220

24 V AC (50Hz)

200

24 V AC (60Hz)

200

30 V DC
30 V AC (50Hz)

220
200

48 V DC
48 V AC (50Hz)

220
200

60 V DC

220

60 V AC (50Hz)

200

100 V AC (50Hz)-110115 V AC (60Hz)

200

110115 V AC (50Hz)-125127 V AC (60Hz)

200

110125 V DC

220

120 V AC (60Hz)

200

127130 V AC (50Hz)

200

208220 V AC (60Hz)

200

220 V AC (50Hz)

200

220250 V DC

220

230240 V AC (50Hz)-277 V AC (60Hz)

200

240 V AC (60Hz)

200

310 V DC

3/18

DC [W]

220

380 V AC (60Hz)

200

380400 V AC (50Hz)-440 V AC (60Hz)

200

415440 V AC-480 V AC (60Hz)

200

500 V AC (50Hz)

200

Opening times [ms]

25

25

ABB

1SDC210251F0023

UVD - Time delay device for undervoltage


release
The undervoltage release can be combined with an external electronic power supply time delay device, which allows circuit breaker
opening to be delayed in the case of a drop or failure in the power
supply voltage of the release itself, according to preset and adjustable delays, in order to prevent unwarranted trips caused by
temporary malfunctions. The delay device must be combined with
an undervoltage release with the same corresponding voltage. This
time delay device can also be combined either with the Tmax
T1T5 or Isomax circuit breakers.

Extension for testing releases

1SDC210252F0023

Available for Tmax T4 and T5 and Isomax S6 and S7 circuit breakers, this allows supply to the service releases with the circuit breaker
in the racked out position. It is therefore possible to carry out blank
operating tests of the circuit breaker in safe conditions, i.e. isolated in relation to the power circuits.

ABB

1SDC210255F0023

These allow the shunt trip or undervoltage release to be connected


to the power supply circuit. They are available in the following versions:
for Isomax S6 and S7 fixed circuit breakers
for Isomax S6 and S7 draw out circuit breakers.
Assembly is by means of pressure into special slots in the left side
of the circuit breaker.
Cables of different lengths (UL/CSA) are available.
Socket-plugs with 3, 6 or 12 poles and cable kit (UL/CSA) with a
length of 78.8 (2 meters) are available for Tmax: the socket-plugs
are necessary only for plug-in version.

1SDC210254F0023

1SDC210253F0023

Connectors for service releases for Isomax

3/19

Accessories
Electrical signals

These allow information relative to the circuit breaker status to be taken outside the circuit breaker.
Installation of these accessories takes place directly from the front of the circuit breaker, in special
slots on the right-hand side of the circuit breaker, completely segregated from the live parts, with
increased operator safety.
They are supplied in the pre-cabled version with 39.4 (1 m) long cables for the T1, T2 and T3 circuit
breakers, or socket-plug connectors, still with 39.4 (1 m) long cables, for T4 and T5. For Isomax S6
and S7, the power supply is made by means of special connectors.

AUX - Auxiliary contacts and bell alarm


1SDC210256F0023

(UL file: E116596)

These carry out electrical signalling of the operating state of the


circuit breaker:
open/closed, which indicates the position of the main contacts
bell alarm, which signals the circuit breaker open due to one
of the following reasons:
overload or short circuit
shunt trip
UVR
residual current release
emergency opening pushbutton of the motor operator
operation of the circuit breakers test pushbutton.
Auxiliary contacts can be supplied (according to the type) in the
pre-cabled version with 1 m long cables for T1, T2 and T3 or with
connectors, still with 1m long cables, for T4, T5, S6 and S7.

Electrical characteristics
Tmax T1, T2, T3
Power supply voltage
AC (50 - 60Hz) [V]

Breaking capacity

DC [V]

Resistive load [A]

Inductive load [A]

24

10

48

1.2

0.7

110

0.45

0.3

220

0.35

0.2

250

Isomax S6, S7
Power supply voltage
AC (50 - 60Hz) [V]

Breaking capacity

DC [V]

Ohmic load [A]

125

0.3

250

0.15

250

400

3
Isomax S8

Power supply voltage


AC (50 - 60Hz) [V]

DC [V]
220

3/20

Breaking capacity
Ohmic load [A]
1

380

500

ABB

The auxiliary contacts are available for use with different voltages either in direct or alternating current:
T1, T2, T3, T4 and T5 (AUX) 250 V AC/DC
In the pre-cabled and uncabled version:
1 contact for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm
3 contacts for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm.
T4 and T5 (AUX) 400 V AC
Only in the pre-cabled version:
1 contact for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm
2 contacts for signalling (on changeover) open/closed.
T1, T2, T3, T4 and T5 (AUX) 24 V DC
Gold-plated in the pre-cabled and uncabled version for T4 and T5 and only in the uncabled version
for T1, T2 and T3:
3 contacts for signalling (on changeover) open/closed plus 1 contact (on changeover) for bell alarm.
T4 and T5 with PR222DS/PD (AUX-SA) 250 V AC
Only in the pre-cabled version:
1 contact for bell alarm.
T4 and T5 (AUX-MO)
Only in the pre-cabled version, to be combined with the MOE or MOE-E motor operator:
1 contact for signalling the operating mode of the circuit breaker with the motor operator: manual
or remote.
T4 and T5 with PR222DS/PD electronic trip unit (AUX-E)
Only in the pre-cabled version and only combined with the PR222DS/PD, they communicate the
state of the circuit breaker to the electronic trip unit.
1 contact for signalling (on changeover) open/closed + 1 contact (on changeover) for bell alarm.
S6 and S7 (AUX) 250-400 V AC/125-250 V DC
In the pre-cabled and uncabled version:
1 contact during open/closed changeover + 1 bell alarm
2 contacts for signalling (on changeover) open/closed
1 open signal +1 closed signal +1 bell alarm.
S8 (AUX) 380-500 V AC/220 V DC
In the pre-cabled and uncabled version:
3 contacts during open/closed changeover + 1 bell alarm
1 bell alarm.
Signals
T1, T2, T3
2 open/closed contacts on changeover

T4, T5

S6, S7

1 open/closed contact on changeover + 1 bell alarm

3 open/closed contacts on changeover + 1 bell alarm

1 circuit breaker open signal + 1 circuit breaker closed signal + 1 bell alarm

3 open/closed contacts on changeover + 1 bell alarm

1 bell alarm

1 signalling electronic release trip (with PR222DS/PD-AUX-SA)

1 contact signalling manual/remote (AUX-MO)


early auxiliary contacts (AUE) (2 for Tmax, 1 for Isomax)

auxiliary position contacts for signalling circuit breaker racked-in/out (AUP)*


(max 3 for Tmax; max 5 for Isomax)

1 open/closed contact on changeover + a contact


(on changeover) for bell alarm (AUX-E; for PR222DS/PD, IEC only)

ABB

S8

3/21

Accessories
Electrical signals

The auxiliary contacts for the Tmax circuit breakers and for Isomax
S6 and S7 are available, in accordance with IEC 60947-2 Standard, also in the gold-plated version for digital signals.
A change-over contact signalling residual current protection trip is
always supplied for the Tmax circuit breakers combined with the
RC221 and RC222 residual current releases (in accordance with
IEC 60947-2 Standard). Two change-over contacts for signalling
pre-alarm and alarm are also available with RC222.

AUX - Electrical characteristics


AUX 250 V - T1, T2, T3, T4 and T5
Power supply voltage

Service current In [A]


Category of utilisation (IEC 60947-5-1)
AC 14

DC 13

125 V

6A

0.3 A

250 V

5A

0.15 A

Protection with gG 10x38 type fuse (Imax 6 A)


AUX 400 V - T4, T5

Power supply voltage

Service current In [A]


AC

DC

125 V

0.5

250 V

12

0.3

AUX 24 V - T1, T2, T3, T4 and T5


Service current In [A]
AC

DC

24 V

0.3

0.75 mA

5V

1 mA

S6-S7

1SDC210258F0023

T4

1SDC210257F0023

T1-T2-T3

1SDC210259F0023

Power supply voltage

AUX-C 250 V AC/DC

3/22

ABB

Connectors for auxiliary contacts for Isomax

1SDC210260F0023

These allow the auxiliary contacts to be connected to the relative


power supply circuit.
For Isomax S6 and S7 circuit breakers, the auxiliary contacts
(fitted with plug connector) can only be supplied by means of the
specific connectors to be ordered specifying the size and version
of the circuit breaker (fixed or plug-in/draw out).
Assembly is carried out by mounting into special slots on the right
side of the circuit breaker.
Socket-plugs with 3, 6 or 12 poles and cable kit (UL/CSA) with a
length of 78.8 (2 m) are available. For Tmax: the socket-plugs are
necessary only for plug-in version.

1SDC210262F0023

1SDC210261F0023

1SDC210263F0023

Extension for testing auxiliary contacts

ABB

Available for Tmax T4 and T5, and Isomax S6 and S7 circuit


breakers, this allows the auxiliary contacts to be connected to the
relative power supply circuit with the circuit breaker in the
withdrawn position. With the circuit breaker in safe conditions, i.e.
isolated in relation to the power circuits, blank tests of circuit breaker
operation can be carried out.

3/23

Accessories
Electrical signals

1SDC210264F0023

AUE - Early auxiliary contacts


One auxiliary contact for Isomax S6 and S7 and two contacts for
Tmax T1, T2, T3, T4 and T5 allow the undervoltage release or a
control device to be supplied in advance, in relation to closing of
the main contacts, in compliance with the IEC 60204-1, and VDE
0113 Standards. They are mounted inside the direct rotary handle
operating mechanism.
For Isomax S6 and S7, the contact is supplied complete with a
socket connector with double slide for simultaneous connection
of the undervoltage release and of the consent contact itself. With
Tmax T1, T2 and T3, the early contacts are supplied in the cabled
version with cables 39.4 (1 m) long, complete with socket-plug
with 6 poles, whereas for T4 and T5 early contacts are provided
with socket-plug connectors with 39.4 (1 m) cables.

T1-T5

1SDC210265F0023

3/24

1SDC210267F0023

1SDC210266F0023

S6S7

ABB

For the fixed part of circuit breakers Tmax T2, T3, T4 and T5, and
Isomax S6 and S7 they provide electrical signalling of the circuit
breaker position in relation to the fixed part: racked-in, drawn out
and removed. They can only be connected by means of free wires
and are available in the following versions:
contacts signalling circuit breaker racked-in for Tmax and
Isomax circuit breakers
contacts signalling circuit breaker racked-out for Tmax T4 and
T5
contacts signalling circuit breaker racked-in for Tmax T4 and
T5 in 24 V DC
contacts signalling circuit breaker racked-out for Tmax T4 and
T5 in 24 V DC.
contacts signalling circuit breaker drawn-out for Isomax circuit
breakers.
A maximum of three contacts for Tmax and a maximum of five
contacts for S6 and S7, in any combination, can be installed on
the fixed part.
The circuit breaker position contacts are also available in the goldplated version for digital signals, also suitable for use for Un<24 V
voltages with the same type of signaling and versions (for Isomax).

ABB

1SDC210272F0023

S6-S7

T4-T5

1SDC210270F0023

T2-T3

1SDC210271F0023

1SDC210269F0023

1SDC210268F0023

AUP - Auxiliary position contacts

3/25

Accessories
Remote controls

These allow remote control of circuit breaker opening and closing and are particularly suitable for use
in electrical network supervision and control systems.
A selector allows changeover from automatic to manual operation. They are always fitted with a
padlock in the open position.

MOS - Solenoid operating mechanism for


Tmax T1, T2 and T3

1SDC210273F0023

(UL file: E116596)

This operates both opening and closing of the circuit breaker, acting directly on its lever. It is proposed in two versions, one sideby-side (IEC only), with T1 and T2, for installation on a panel or
DIN rail, the other on the front of the circuit breaker (UL file:
E116596), with T1, T2 and T3. The latter is complete with operating handle. The front version can also be used with plug-in circuit
breakers.
Coupling with the residual current release is only allowed for a
circuit breaker with solenoid operator side-by-syde, to allow access to the user interface of the residual current release from the
front of the switchgear.
Both versions can be used either in the three-pole or four-pole
version.
The solenoid operator is supplied complete with free cables 39.4
(1 m) long and socket-plug connector with 3 poles just for the
superimposed version.
The table gives the power supply voltage values Un [V].

Rated voltage, Un
AC
DC

[V]
[V]

Operating voltage
Inrush power consumption
Time

85110% Un
2500 [VA] / 1000 [W]
opening [s]
closing [s]

Mechanical life

110250
4860 / 110250

[no. Operations]
[no. Operations/h]

25000
240 (T1 and T2); 120 (T3)
IP30

[ms]

>100

1SDC210274F0023

Degree of protection, on the front


Minimum control impulse
time on opening and closing

< 0.1
< 0.1

3/26

ABB

Stored energy motor operator for Tmax T4


and T5 MOE and MOE-E
With the stored energy motor operator, it is possible to control
both opening and closing of the circuit breaker on which it is installed. During opening of the circuit breaker, the spring system is
recharged automatically: the
stored energy is exploited in this
MOE and MOE-E
Tmax T4 and T5
way to close the circuit breaker.
Rated voltage, Un
AC [V]
DC [V]
The motor operator is always

24
supplied complete with socket
4860
plug connectors with 39.4 (1m)
110125
110125
long cables and is always fitted
220250
220250
with a padlock. The connectors,
380

once inserted in the special slot


Operating voltage
85110% Un 85110% Un
Power consumption on inrush Ps
300 VA
300 W
on the right-hand side of the cirPower consumption in service Pc
150 VA
150 W
cuit breaker, extend in relation
Time
opening [s]
< 0.1
to the outline of the circuit
closing [s]
1.5
breaker itself.
resetting [s]
3
The device can be fitted both
Mechanical life
[no. operations]
20000
with a key lock in the open poDegree of protection, on the front
IP30
sition (with the same MOL-S
Minimum opening and
closing control time
[ms]
150
keys for groups of circuit breakers or different MOL-D keys) and
with a MOL-M key lock against
manual operation: in the former case, the lock in the open position
is both of electrical and mechanical type, in the latter case, only of
mechanical type, i.e. only closing from the front of the circuit breaker
(remote closing is allowed).
The motor operator is always fitted with an auxiliary contact to
signal auto or manual (not on changeover). On request, it can
also be fitted with an AUX-MO auxiliary contact (on changeover),
which provides a signal of its service state: auto (remote control
of the circuit breaker) or manual.
If the circuit breaker is fitted with PR222DS/PD electronic trip unit,
instead of MOE, it is necessary to use MOE-E motor operator: for
its use, the circuit breaker must be fitted with the AUX-E.

1SDC210276F0023

1SDC210275F0023

(MOE: UL file: E116596)

ABB

3/27

Accessories
Remote control

Stored energy motor operator for Isomax


S6 and S7 circuit breakers

1SDC210277F0023

(UL file: E116596)


With the stored energy operating mechanism, during circuit breaker
opening the release mechanism automatically pre-charges a
system of springs: the stored energy is used for closing the circuit
breaker. It is supplied complete with shunt opening release
(Ps=100VA/100W) and flange for the compartment door. The
table shows the power supply voltages values Un [V].
In case of interlocked circuit breakers, the key lock against manual
operation is necessary.

Motor operator for S6, S7


AC
Rated voltage, Un

DC

[V]

24

[V]

48

[V]
[V]
Operating frequency

240

250

5060

Operating voltage

85110% Un

85110% Un

Power consumption on inrush Ps

660 VA

600 W

Power consumption in service Pc

180 VA

Time constant
Duration
Mechanical life

[ms]

180 W
22

opening [s]

1.2

closing [s]

0.09

[no. operations]

10000 (S6) - 5000 (S7)

Degree of protection, on the front

IP30

Minimum duration of the opening


and closing command impulse [ms]

100

1SDC210278F0023

3/28

125

1SDC210279F0023

120

ABB

1SDC210280F0023

Geared motor for Isomax S8 circuit breaker


This allows the springs of the circuit breaker closing mechanism
to be charged automatically, immediately following a closing
operation. It includes a limit microswitch for electrical signalling of
closing springs charged.

The motor operators for S6 and S7 can only be supplied by means


of the specific connectors. They are of the slide type and allow
simultaneous connection of both the motor operator and the
auxiliary contacts to the relative power supply circuit. They are
an alternative to the corresponding connectors for the auxiliary
contacts only since they are housed in the same seat. They must
be ordered specifying the size and version of the circuit breaker
(fixed or plug-in/draw out).

1SDC210282F0023

1SDC210281F0023

Connectors for Isomax S6 and S7 motor


operators

1SDC210283F0023

Extension for testing motor operators

ABB

For Tmax T4 and T5 and Isomax S6 and S7 circuit breakers, this


allows both motor operators and the auxiliary contacts to be
connected to the relative power supply circuit with the circuit
breaker in the racked-out position. With the circuit breaker in safe
conditions, i.e. isolated in relation to the power circuits, blank
operating tests of the circuit breaker can be carried out. It must be
ordered specifying the size and version of the circuit breaker
(fixed or plug-in/draw out) and automatically excludes the corresponding extension for testing the auxiliary contacts.

3/29

Accessories
Operating mechanisms with locks

Rotary handle operating mechanism RHD/RHE

1SDC210285F0023

1SDC210284F0023

(UL file: E116596 for Tmax)

1SDC210286F0023

The rotary handle operating mechanism facilitates operation thanks


to its ergonomic handle. It is always fitted with a padlock in the open
position, which prevents the circuit breaker being closed. The padlock slot can take up to three padlocks stem 0.27
(7 mm) for T1, T2, T3 T4 and T5, and 0.24 (6 mm) for S6 and S7
(not supplied).
The rotary handle operating mechanism for Tmax is always fitted with
a compartment door lock and, on request, can be supplied with a
key lock in the open position; for S6 and S7, on request, it can be
supplied with a compartment door lock or key lock in the open position.
Application of the rotary handle operating mechanism is an
alternative to the motor operator and to the front interlocking plate for
Tmax T1, T2, T3 and to the front flange for the lever operating mechanism for Tmax T4, T5 and Isomax S6 and S7.
The rotary handle operating mechanism is available in either the direct version and in the transmitted version on the compartment door.
The position of the rotary handle indicates with certainty the
position of the contacts: open, closed and trip unit tripped. The trip
unit settings and the nameplate data remain accessible to the user.
For Isomax S6 and S7 circuit breakers, the direct rotary handle operating mechanism on the circuit breaker is always supplied complete
with flange for the compartment door.
The rotary handle operating mechanism in the emergency
version, complete with red-yellow handle and yellow plate,
suitable for machine tool control, is also available for all the circuit
breakers. For Tmax circuit breakers, the rotary handle operating
mechanisms can be ordered by building up by ordering the following
three devices:
rotary handle on the compartment door
transmission rod (19.68 / 500 mm)
base for circuit breaker
or, alternatively, by using the code of the ready-configured version.

Type of RH operating mechanism


T1, T2, T3

T4, T5

S6, S7

F/P

F/P

RHD

Direct

RHD_EM

Emergency direct

RHE

Transmitted with adjustable distance

19.68" - 500 mm

19.68" - 500 mm

19.68" - 500 mm

RHE_EM

Emergency transmitted with adjustable distance

19.68" - 500 mm

19.68" - 500 mm

RHE_S

Rod for transmitted adjustable handle

19.68" - 500 mm

RHE_B

Base for circuit breaker

RHE_H

Handle for transmitted RH with adjustable distance

RHE_H_EM Emergency handle for transmitted RH with adjustable distance

3/30

ABB

1SDC210288F0023

T2-T3

1SDC210287F0023

T4-T5

1SDC210290F0023

1SDC210291F0023

1SDC210289F0023

S6-S7

1SDC210292F0023

IP54 protection for rotary handle

ABB

Allows IP54 degree of protection to be obtained. It is available for


the transmitted rotary handle operating mechanism on the compartment door (RHE) for the Tmax and Isomax circuit breakers.

3/31

Accessories
Operating mechanisms with locks

S6-S7

1SDC210294F0023

This can be installed on Tmax T4 and T5, and on Isomax S6 and


S7 fixed, plug-in or draw out circuit breakers. In case of draw out
circuit breakers installed in compartments, it allows higher degree
of protection to be maintained for the whole isolation run of the
circuit breaker.
It is always fitted with a padlock in the open position (stem 0.24
- 6 mm up to three padlocks - not supplied) which prevents closing of the circuit breaker.
On request, it can be fitted with a key lock in the open position for
one or more circuit breakers and with the compartment door lock.
It is available in the following versions:
for fixed or plug-in circuit breaker
for draw out circuit breaker.
The front flange for lever operating mechanism is always an alternative to the motor operator, to the rotary handle and, for T4 and
T5, to the front display unit FDU.
For Isomax S6 and S7 circuit breakers, it is always
supplied complete with flange for the compartment
door. For T4 and T5, the same flange for compartment door already supplied with the circuit breaker or
the one supplied with the conversion kit for draw out
version can be used.

1SDC210295F0023

1SDC210293F0023

Front flange for lever operating mechanism


- FLD

3/32

1SDC210297F0023

This allows the mechanical closing operation of the circuit breaker


to be locked.
The following versions are available:
lock with different key for each circuit breaker
lock with the same key for groups of circuit breakers.
For Isomax S6 and S7 circuit breakers, different locks are supplied, for stored energy motor operator, for rotary handle or front
for lever operating mechanism.
For Tmax T1, T2 and T3, the key lock is available for the rotary
handle operating mechanism (RHL). Furthermore, it is also available in the version which allows the lock both in the open and in
the closed position: the lock in the closed position does not prevent tripping of the mechanism following a fault or a remote control command.
For T4 and T5 key locks in the open position are available either
with different keys (KLF-D) or with the same keys (KLF-S): in this
case, up to four different key numbering codes are available.

1SDC210298F0023

1SDC210296F0023

Key lock in open position

ABB

KLC - Key lock on the circuit breaker


1SDC210299F0023

Available for Tmax T1, T2 and T3, the key lock on the circuit breaker
allows the mechanical closing operation of the circuit breaker to
be locked and is installed directly on the front inside the slot in
correspondence with the left pole. It cannot be mounted with a
front operating mechanism, a rotary handle operating mechanism,
a motor operator, or RC221/RC222 residual current releases and,
only in the case of three-pole circuit breakers, with service releases
(UVR, SOR).
The key lock is the Ronis 622 type and is available in two versions:
standard type, with key only removable with the circuit breaker
locked (KLC)
special type, with key removable in both positions (KLC-S).

This prevents the compartment door being opened with the circuit breaker closed. It can be used with Isomax S6 and S7 circuit
breakers in the fixed, plug-in or draw out version and fitted with
rotary handle operating mechanism or front for lever operating
mechanism. It consists of two elements: one applied to the rotary
handle operating mechanism or to the front for the lever operating
mechanism, the other, consisting of a metal striker, to be applied
onto the compartment door.
For Tmax circuit breakers, the door lock is always supplied with
the rotary handle operating mechanism.

1SDC210301F0023

1SDC210300F0023

Compartment door lock

ABB

3/33

Accessories
Operating mechanisms with locks

3/34

1SDC210305F0023

1SDC210303F0023

Key locks or padlocks are available to be applied to the guide of


the fixed part of a draw out circuit breaker to prevent the moving
part from being racked-in. The following different versions are
available:
padlock, which can take up to three padlocks with stem 0.24
- 6 mm (not supplied);
key lock in the open position with different key for each circuit
breaker;
key lock in the open position between two or more circuit
breakers with the same key for groups of circuit breakers;
key lock of Ronis type (without key).
For T4 and T5 draw out circuit brakers, key or padlocks-locks are
available to be applied onto the rail of the fixed part, to prevent
racking-in of the withdrawable part.
Selection can be made among the following:
key lock with different keys (KLF-D FP)
key lock with the same keys for groups of circuit breakers
(KLF-S FP)
padlock, which can take up to three padlocks with 6 mm stem
, not supplied (PLL FP).

1SDC210304F0023

1SDC210302F0023

Lock for fixed part of draw out circuit


breakers - Tmax T4, T5 and Isomax S6, S7

ABB

PLL - Padlock for operating lever for Tmax


T1, T2, T3

1SDC210306F0023

This is applied to the Tmax T1, T2 and T3 covers to prevent the


lever closing or opening operations. It allows installation of up to a
maximum of three padlocks 0.24 - 7 mm (not supplied).
It is available in the following versions:
locking device only of the closing operation (it is applied with
circuit breaker ON/OFF)
locking device on the closing and opening operation according
to its assembly position. The lock on the opening operation
does not prevent release of the mechanism following a fault or
remote control command.
1SDC210307F0023

* UL file E116596

1SDC210308F0023

Operating mechanisms with locks

Sealable lock of thermal adjustment

T1

T2

T3

FDL_Key lock for fornt for lever operating mechanism


RHL_Key lock for rotary handle operating mechanism

KLC_Key lock on the circuit breaker

Compartment door lock

T4

T5

S6

S7

MOL-D and MOL-S_Key lock in open position for MOE and MOE-E

MOL-M_Key lock against manual operation for MOE and MOE_E

KLF-FP and PLL-FP_locks in open position for fixed parts


PLL_Padlock for operating lever

ABB

3/35

Accessories
Operating mechanisms with locks

Mechanical interlock between circuit breakers (for Tmax UL file E116596)

1SDC210309F0023

Tmax T1, T2, T3


For Tmax T1, T2 and T3 circuit breakers a front mechanical interlock (MIF) is available, which can be
applied on the front of two (UL file E116596) both three-pole and four-pole fixed version circuit
breakers, preventing simultaneous closing of the two circuit breakers. Fixing is carried out directly on
the back plate of the switchboard. The front interlocking plate allows installation of a padlock in order
to fix the position (possibility of fixing the O-O position as well). It is also possible to interlock three
circuit breakers, even of different sizes, by using a special plate, making the following interlocking
combinations: IOO-OIO-OOI-OOO.
Tmax T4, T5
The mechanical interlock for Tmax T4 and T5 allows installation of two circuit breakers on a single support
and, by means of special lever mechanism, makes them mechanically interdependent. Unlike the interlock used with T1, T2 and T3 which is frontal, this is a rear interlock consisting of a vertical or horizontal
frame group (MIR-HB or MIR-VB), made up of a metal frame and of the leverisms to interlock, and of two
plates (MIR-P) on which the circuit breakers are housed.

S6-S7

1SDC210310F0023

Isomax S6, S7

For Isomax S6 and S7 circuit breakers, the rear mechanical interlock allows installation of two circuit
breakers on a single support and, by means of a walking beam mechanism, makes them mechanically
inter-dependent. It prevents operation in parallel of two power supply sources (e.g.: normal - emergency).
It consists of a kit with levers and assembly accessories and a metallic support.
The mechanical interlock is available in the version for side-by-side circuit breakers and for superimposed
circuit breakers. Only circuit breakers of the same size and in the same version can be interlocked.

T1-T2-T3

1SDC210312F0023

1SDC210313F0023

1SDC210311F0023

S6-S7

Mechanical interlocks
Front interlock between two fixed circuit breakers

T1

T2

T3

Front interlock among three fixed circuit breakers

Rear interlock between two fixed or plug-in or


draw out circuit breakers side by side
Rear interlock between two fixed or plug-in or
draw out circuit breakers superimposed

3/36

T4

T5

S6

S7

ABB

Accessories
Residual current releases - IEC only

All the Tmax series of circuit breakers are preset for assembly combined with residual current releases. In particular, Tmax T1, T2 and T3 circuit breakers can be combined with the new version of
the RC221 or RC222 residual current releases, and four-pole T4 and T5 can be combined with
RC222 or RC223 to be installed below the circuit breaker.
Apart from the protection against overloads and short-circuits typical of circuit breakers, the residual
current circuit breakers which are derived from them also guarantee protection of people and against
earth fault currents, thereby ensuring protection against direct earth contacts, indirect contacts and
fire hazards.
The use of residual current circuit breakers allows continual monitoring of the state of insulation of
the plant, ensuring efficient protection against the risks of fire and explosion and, in the case of
devices with In 30 mA, ensuring the protection required by the Standards and by the accident
prevention prescriptions.
The residual current releases are constructed in compliance with the following Standards:
IEC 60947-2 appendix B
IEC 60255-3 (RCQ) and IEC 61000: for protection against unwarranted trips
IEC 60755 (RCQ): for insensitivity to the direct current components.

The RC221 and RC222 residual current releases can be installed


on the Tmax T1, T2 and T3 circuit breakers. The versions available
make their use possible both with three-pole and four-pole fixed
version circuit breakers.
They are constructed using electronic technology and act directly
on the circuit breaker by means of an opening solenoid, supplied
with the residual current release, to be housed in the special slot
made in the area of the left pole.
They do not require an auxiliary power supply since they are supplied directly from the network and their operation is guaranteed
even with only a single phase plus neutral or just two phases supplied with voltage and in the presence of one-direction pulsating
currents with continuous components.
All the possible connections are allowed as long as the connection of the neutral to the first pole on the left is guaranteed in the
four-pole version.
The RC221 and RC222 releases can be fed either from the load
or the line side.

1SDC210315F0023

1SDC210314F0023

RC221 and RC222 electronic residual


current releases for Tmax T1, T2 and T3

ABB

3/37

Accessories

1SDC210317F0023

1SDC210316F0023

Residual current releases - IEC only

The residual current releases are supplied complete with:


an opening solenoid to be housed in the area of the third pole,
complete with an auxiliary contact signalling residual current
release trip
a dedicated flange.
The bracket for fixing onto DIN rail is available on request.
The configuration contemplates insertion of the circuit breaker on
the structure of the corresponding residual current release, making access to the adjustments on the left-hand side of the circuit
breaker available, whilst the toroid is placed below.
The type of cable connection, which is made directly on the circuit
breaker, once the residual current release has been mounted,
thereby ensuring simplification and rationalization of the installation procedure, provides a distinguishing characteristic.
Only front terminals for copper cables (FC Cu) at the bottom are
mounted on the residual current releases. For this reason, when
the residual current release is ordered, the FCCu terminal semi-kit
is always supplied. Furthermore, for four pole T1, a version of the
RC222 residual current release is available in 200 mm modules.
This release keeps the same technical characteristics as the
normal RC222 for T1, T2 and T3 but, thanks to its reduced height,
allows installation in 200 mm modules. Its special shape also
allows a reduction in the overall dimensions when two or more
units are placed side by side.

1SDC210319F0023

1SDC210318F0023

RC222 residual current release for Tmax T4


and T5

3/38

With T4 and T5, in the four-pole version, it is possible to use an


RC222 residual current release below the circuit breaker.
This RC222 residual current release, in the fixed version, can
easily be converted into plug-in by adding the special conversion
kit. The device is constructed using electronic technology and acts
directly on the circuit breaker by means of an opening solenoid,
supplied with the residual current release, to be housed in the
special slot made in the left-hand pole area. It does not require an
auxiliary power supply as its supplied directly by the network and
its operation is guaranteed even with only a single phase plus neutral or two phases supplied with voltage and in the presence of
unidirectional pulsating currents with direct components.
The four-pole circuit breaker with residual current release can be
fitted with the electrical accessories normally available for the
circuit breaker.

ABB

RC221
Circuit breakers size
Type
Technology
Action

RC222

T1-T2-T3

T1-T2-T3

T4 and T5

L shaped

L shaped

Placed below

microprocessor-based

microprocessor-based

microprocessor-based

with solenoid

with solenoid

with solenoid

Primary service voltage (1)

[V]

85500

85500

85500

Operating frequency

[Hz]

4566

4566

4566

85500

85500

85500

Self-supply
Test operation range (1)
Rated service current

[A]

up to 250 A

up to 250 A

up to 630 A

Rated residual current trip

[A]

0.03 - 0.1 - 0.3 0.5 - 1 - 3

0.03 - 0.05 - 0.1 - 0.3 0.5 - 1 - 3 - 5 - 10

0.03 - 0.05 - 0.1 0.3 - 0.5 - 1 - 3 - 5 - 10

Time limt for non-trip

[s]

istantaneous

istantaneous - 0.1 - 0.2 0.3 - 0.5 - 1 - 2 - 3

istantaneous - 0.1 - 0.2 0.3 - 0.5 - 1 - 2 - 3

20%

20%

Local trip signalling

Trip coil with changeover contact for trip signalling

Input for remote opening

NO contact for pre-alarm signalling

NO contact for alarm signalling

Indication of pre-alarm from 25% In (tollerance 3%)

Tolerance over trip times

Automatic residual current reset

A type for pulsanting alternating current, AC for alternating current

Indication of alarm timing

Remote release device

Button for insulation test

Power supply from above and below

Assembly with three-pole circuit breakers

Assembly with four-pole circuit breakers

Selective type

Kit for conversion of circuit breaker with residual current release


from fixed to plug-in
(1)

Operation up to 50 V Phase-Neutral

1SDC210320F0023

RC223 (B type) residual current release for T4

ABB

Along with the family of residual current releases illustrated previously, ABB has developed the RC223 (B type) residual current
release, which can only be combined with the Tmax T4 four-pole
circuit breaker in the fixed or plug-in version. The range of operation of the primary line-to-line voltage varies between 110 V and
440 V, with operation starting from 55 V phase-neutral. It is characterised by the same types of reference as the RC222 (S and
AE type) release, but can also boast conformity with type B operation, which guarantees sensitivity to residual fault currents with
alternating, alternating pulsating and direct current components.
The reference Standards are: IEC 60947-1, IEC 60947-2 Appendix B, and IEC 60755. Apart from the signals and settings typical
of the RC222 residual current release, the RC223 also allows selection of the maximum threshold of sensitivity to the residual fault
frequency (3 steps: 400-700-1000 Hz).
3/39

Accessories
Residual current releases - IEC only

1SDC210321F0023

RCQ residual current relay


The Tmax T1, T2, T3 T4 and T5, and Isomax S6 and S7 circuit breakers can be combined with the
RCQ relay with separate toroid (to be installed externally on the line conductors) and these fulfill
requirements with thresholds up to 30 A trips and times up to 5 s or when the installation conditions
are particularly restrictive, such as with circuit breakers already installed, or limited space in the
circuit breaker compartment.
Thanks to the wide range of settings, the RCQ relay is suitable for applications where a system of
residual current protection coordinated with the various distribution levels. It is particularly recommended when low sensitivity residual current protection is required, such as in partial (current) or
total (chronometric) selective chains, and for high sensitivity applications (physiological sensitivity).
In case of drops in the auxiliary power supply voltage, the opening control intervenes after a minimum time of 100 ms and after the time set plus 100 ms.
The RCQ relay is suitable for use in the presence of alternating currents only (Type AC), for alternating
and/or pulsating current with direct components (Type A) and allows residual current selectivity to be
set up.
The RCQ relay is of the type with indirect action and acts on the circuit breaker release mechanism
by means of the shunt trip of the circuit breaker itself (to be ordered by the user), to be housed in the
special slot made on the left-hand pole of the circuit breaker.

3
Residual current relay

RCQ

Power supply voltage

AC [V]
DC [V]

80500
48125

[Hz]

50 60 Hz 10%

1st range of adjustments

[A]

0.03-0.05-0.1-0.3-0.5

2nd range of adjustments

[A]

1-3-5-10-30

[s]

0-0.1-0.2-0.3-0;5-0.7-1-2-3-5

Operating frequency
Trip threshold adjustment In

Trip time adjustment


Pre-alarm threshold adjustment

[%] x In

2575% x In

Range of use of closed transformers


Toroidal transformer 2.36 [60 mm]

[A]

0.0330

Toroidal transformer 4.33 [110 mm]

[A]

0.0330

Toroidal transformer 7.28 [185 mm]

[A]

0.130

Range of use of transformers which can be opened


Toroidal transformer 4.33 [110 mm]

[A]

0.0330

Toroidal transformer 7.09 [180 mm]

[A]

0.0330

Toroidal transformer 9.06 [230 mm]

[A]

Signalling for alarm pre-threshold

130
Yellow flashing LED 1 N.O. change-over contact
6 A - 250 V AC 50/60 Hz

Residual current relay trip signalling

Yellow magnetic flag change-over contacts (N.O. N.C.; N.O.)


6 A - 250 V AC 50/60 Hz

Remote opening control

N.O. contact
Trip time 15 ms

Connection to the toroidal transformer

3/40

By means of 4 twisted conductors. Maximum length: 1270 in

Dimensions L x H x D

[in]

3.78 x 3.78 x 5.18

Drilling for assembly on door

[in]

3.62 x 3.62

ABB

Accessories
Accessories for electronic trip units

PR212/D-M Modbus and PR212/D-L Lon


dialogue unit for S6 and S7- (IEC only)
The dialogue unit is a device which allows two-way communication from the circuit breaker to the outside and vice versa. ABB
has built two distinct dialogue units able to support two different
communication protocols: PR212/D-M (Modbus RTU protocol) and
PR212/D-L (LonTalk protocol by Echelon). Both units are housed
in external modules, which can be installed on DIN rails, and can
be used with the Isomax S6 and S7 circuit breakers fitted with
PR212/P electronic trip unit, both in the LSI and LSIG versions.
They must be supplied with a stabilized voltage of 24 V DC (20%
with maximum ripple 5%) and be earthed. Communication towards the outside is generally addressed to a supervision and
control unit, which has the task of collecting and storing the information regarding the part of the plant controlled.
In the case of an error in the serial communication due to a fault in
the dialogue unit or lack of auxiliary power supply, the PR212/P
protection unit works according to the last parameters set and, in
any case, in accordance with what has been set manually. The
PR212/D-M and PR212/D-L dialogue units are always fitted in
combination with the PR212/T actuator unit, which allows remote
closing or opening operation of the circuit breaker (Remote Control) by means of two digital outputs which can be disabled thanks
to the dip-switch (LOC/REM) positioned on LOC.

Information available

State of the circuit breaker: open; closed; tripped


installation alarms: pre-alarm L; tripped L-S-I-G-R-V-PTC
measurements: currents; N operations; N trips
reading and writing curves and trip thresholds: only manual reading (MAN), electronic or remote reading and writing (ELT)
circuit breaker commands: opening; closing; reset.

ABB

3/41

Accessories
Accessories for electronic trip units

PR212/T actuator unit for S6 and S7

1SDC210322F0023

The PR212/T actuator unit allows circuit breaker opening and closing
by means of the motor operator mounted on the circuit breaker. It is
always supplied in combination with the PR212/D dialogue unit for
Isomax S6 and S7. An auxiliary power supply with a stabilized voltage of 24 V DC (20%, with maximum ripple 5%) and earthed is
required for operation of the unit.
The PR212/D dialogue unit sends the digital opening and closing
commands, received from the supervision and control system, to the
inputs of the PR212/T actuator unit, which carries out circuit breaker
closing and opening by means of a power relay. The motor operator
of the circuit breaker (use the versions with power supply voltage at
110 V AC/DC or 220 V AC) must be connected to these relays.

TT1 Test unit

1SDC210323F0023

This allows control of tripping of the PR211/P, PR212/P, PR221DS


and PR222DS electronic trip unit and the trip test of the trip coil.
The device is supplied by means of a 12 V replaceable battery and
is fitted with a two-pole polarized connector-tracer point housed
on the bottom of the box, which allows connection of the device
to the test input bushings located on the bottom of the electronic
trip unit.
The limited dimensions of the accessory make it practically pockettype.

1SDC210324F0023

PR212/K signalling unit for S8

3/42

The PR212/K signalling unit, only available for Isomax S8, is able
to convert the digital signals supplied by the PR212/P - (LSIG)
protection unit into electric signals by means of normally open
electrical contacts. An auxiliary power supply is needed to operate the unit. It is connected to the internal bus of the protection
unit by means of a dedicated serial line over which the information
regarding the state of activation of the protection functions passes,
on the basis of which the relative power contacts are closed to
signal:
pre-alarm for protection function L (I>0.9 x I1)
protection function L, S, I, G trip
trip indication
communication error with protection unit.

ABB

PR020/K signalling unit


The PR020/K signalling unit can convert the signals received via
bus from the PR212/P (LSI or LSIG) or PR222DS/PD protection
units into electric signals by means of normally open electrical power
contacts.
An auxiliary power supply with a voltage stabilized at 24 V DC
(20% with maximum ripple 5%) and earthed is needed to operate the unit.
It is connected to the Internal Bus of the protection unit by means
of a dedicated serial line over which the information regarding the
state of activation of the protection functions passes, on the basis
of which the relative power contacts are closed.
In particular, the following signals are available:

PR212/P (LSI-LSIG) PR222DS/PD (LSI-LSIG)


K51

Signals

L alarm

S alarm

I alarm

G alarm

Bus K.O.

Trip indication

Trip indication

L pre-alarm

PR020/K
Maximum switching capacity

100 W / 1250 VA (resistive load)

Maximum switching voltage

130 V DC / 250 V AC

Maximum switching current

5A

Breaking power (UL/CSA) @ 30 V DC


(resistive load)
Breaking power (UL/CSA) @ 250 V DC
(resistive load)
Contact/coil insulation

3.3 A
5A
2000 V efficient (1 min. @ 50 Hz)

Alarm signalling remains active for the whole duration of the overload up to any trip unit intervention.
The protection trip signals remain active during the timing phase
and remain that way even after intervention of the trip unit.
A Reset pushbutton on the front of the unit allows the state of all
signals to be reset.
There are also two LEDs available on the unit for visually signalling
the following information:
Power ON: auxiliary power supply present
TX (Int Bus): flashing synchronized with the communication
activity with the Internal Bus, and eight LEDs dedicated to internal power releases status.
The table shows the characteristics of the signalling relays available in the PR020/K unit.

ABB

3/43

Accessories
Accessories for electronic trip units

1SDC210325F0023

PR010/T Test and Configuration Unit

The PR010/T unit is an instrument able to carry out the Test,


programming and parameter
readout functions for the protection units which equip the Tmax,
the Isomax S molded case circuit breakers and the Emax air
circuit breakers.
In particular, for circuit breakers
fitted with PR212/P and
PR222DS/P trip units, the test,
programming and readout parameter functions are available.
All the functions mentioned can
be carried out ON BOARD by
connection of the PR010/T unit
to the multipin front flange connector on the protection unit;
connection is guaranteed by
means of special interfacing cables supplied as standard with
the unit.
The human-machine interface is
guaranteed by using a membrane keyboard and a multi-line
alphanumerical display.
There are also two LEDs on the
unit which signal the following respectively:

POWER-ON and STAND BY


situation
situation of the battery charging state.
Two different types of Test
are provided: automatic and
manual.
By means of connection to the
PC (software provided), it is also
possible to upgrade the SW of
the PR010/T unit to allow adaptation of the Test unit to evolution of new products.
The most relevant test results
can also be stored in the unit itself and sent to the Personal
Computer on explicit request for
issue of report.
Both in automatic and manual
mode, the PR010/T unit is able
to test the following:
protection functions L, S, I, G
monitoring of correct operation of the microprocessor.
The same Tests can also be
repeated using the manual
method.
The PR010/T unit is of the portable type and operates with re-

chargeable batteries and/or with


an external power supply.
In its standard supply, the unit includes:
PR010/T Test unit complete
with rechargeable batteries
TT1 Test unit;
100...240 V AC/12 V DC external power supply
connection cables between
the unit and the multipin connector present on the ranges
of releases which equip the
Isomax S and the Emax series
connection cable between
the unit and the PC (serial
RS232)
power supply cable
instruction manual and software
plastic case.

1SDC210326F0023

EP 010 - FBP

3/44

It is the e-plug interface which can connect T4 and T5, equipped


with the PR222DS/PD electronic trip unit, to the field bus plug
system, allowing user to choose among several field bus system
(ASI, Device Net, Profibus).
It must be connected to the trip unit by means of the specific X3
connector.

ABB

1SDC210327F0023

Front display unit - FDU


The front display is a display unit of the setting currents, alarms and
parameters of the PR222DS/P and PR222DS/PD electronic trip units
of T4 and T5. The display unit can operate correctly with self-supply
with I 0.35 x In on at least one phase. If the display is used in
combination with the PR222DS/PD trip unit, and therefore with an
auxiliary power supply, it is also possible to detect the protection,
which has caused the trip unit intervention and the fault current.
It is not compatible with the front accessories: rotary handle operating mechanism, motor operator and front for lever operating mechanism.

CT ext

CT for external neutral


This is mounted onto the external neutral conductor and allows
protection against earth faults with three-pole circuit breakers. The
circuit breaker must be fitted with PR212/P LSIG, PR222DS/P
or PR222DS/PD trip units. The transformer must be connected to
the trip unit by means of the specific X3-X4 connectors, selected
according to the version of the circuit breaker and the type of protection trip unit used.

T4
[A]

T5
[A]

100

320

160

400

250

630

320

Connectors
Connectors X3 and X4 allow connection of the electronic trip unit
with external plant units or components. In fact, they are used to
make the L alarm signal available outside or to realise connection
to the PR020/K signalling unit. Both connectors are available for
fixed and plug-in or draw out version circuit breakers.
Connector

Function

Trip unit

X3

PR020/K

PR222DS/PD and PR211/P, PR212/P

X4

ABB

L alarm signal

PR222DS/P, PR222DS/PD PR211/P, PR212/P

Dialogue

PR222DS/PD, PR212/D

Auxiliary supply

PR222DS/P, PR222DS/PD

EP 010

PR222DS/PD

External neutral

PR222DS/P, PR222DS/PD, PR212/P

3/45

Accessories
Installation and testing accessories

Bracket for fixing on DIN rail

1SDC210329F0023

1SDC210328F0023

This is applied to the fixed circuit breaker and allows installation on


DIN rails (1.38/35 mm).
It simplifies assembly of circuit breakers up to 225 A (Tmax T1, T2
and T3, except for T1B 1p) in standard switchboards.
The bracket for fixing onto DIN rails is also available for Tmax
circuit breakers combined with RC221 and RC222 residual
current releases or with the solenoid operating mechanism of the
side-by-side type.

Flange for compartment door

S6-S7 fixed

S6-S7 draw out

1SDC210335F0023

1SDC210333F0023

3/46

S8

1SDC210334F0023

T1-T5

1SDC210332F0023

1SDC210331F0023

1SDC210330F0023

For Isomax S6 and S7 circuit breakers with the rotary handle operating mechanism, front for lever operating mechanism and motor operator, a special flange is supplied for the purpose.
All the flanges of the Tmax series (to be ordered) are of new conception and do not require the use of screws for their installation:
fixing is greatly simplified by means of a simple dove-tailing operation.
In the case of use of a rotary handle operating mechanism, solenoid operating mechanism or residual current releases, a special
dedicated flange is supplied.
For T4 and T5 draw out circuit breakers, the flange supplied with
the conversion kit must be used instead of the one supplied with
the fixed circuit breaker.

ABB

Accessories
Spare parts

Spare parts
With Tmax series, the following spare parts are available:
opening solenoid for the RC221 and RC222 residual current
releases
opening solenoid for PR221DS electronic trip unit
kit with washers, screws and plugs for assembly of the front
terminals (F)
flange for compartment door.
For further details, please ask the Service Division of ABB for the
spare parts catalogue.

ABB

3/47

Accessories
Controller for automatic transfer switch - ATS010

1SDC210336F0023

Control for automatic transfer switch - ATS010 (IEC only)

3/48

The ATS010 controller is the new network-group switching device offered by ABB. It is based on
microprocessor technology in compliance with the leading electromagnetic compatibility and environmental standards (EN 50178, EN 50081-2, EN 50082-2, IEC 60068-2-1, IEC 60068-2-2, IEC
60068-2-3).
The device is able to manage the entire switching procedure between the normal line and emergency line circuit breakers automatically, allowing great flexibility of settings.
In case of fault in the normal line voltage, in accordance with the delays set, the normal line circuit
breaker is opened, the generator started and the emergency line circuit breaker closed. Similarly,
when the normal line returns to range, the reverse switching procedure is automatically controlled.
It is especially suited for use in all emergency power supply systems requiring a solution that is ready
to install, easy to use and reliable.
Some of the main applications include: power supply for UPS (Uninterrupted Power Supply) units,
operating rooms and primary hospital services, emergency power supply for civilian buildings, airports, hotels, data banks and telecommunications systems, power supply of industrial lines for continuous processes.
The switching system consists of the ATS010 unit connected to two motor-driven and mechanically
interlocked circuit breakers. Tmax T4 and T5, and Isomax S6 and S7 circuit breakers can be used.
The built-in main sensor of the ATS010 device makes it possible to detect faults in the mains voltage.
The three inputs may be directly connected to the three phases of the normal power supply line for
networks with rated voltage up to 500 V AC. Networks with a higher voltage require the insertion of
potential transformers (PT), setting a rated voltage for the device that matches their secondary voltage (typically 100 V).
Two change-over contacts for each circuit breaker connect directly to the motor operator. The circuit
breaker connection is completed by wiring the status contacts: Open/Closed, Relay tripped, Rackedin (for draw out/plug-in circuit breakers).
That is why on every circuit breaker connected to the ATS010 unit, the following are included in
addition to the mechanical interlock accessories:
motor operator from 48 V to 110 V DC or up to 250 V AC
open/closed contact
relay tripped contact
racked-in contact (for draw out versions)
signal and mechanical lock for protection relay tripped.
On the motor operator for S6 and S7, the key lock is needed.
The ATS010 device is designed to ensure extremely high reliability for the system it controls. It contains various safety systems intrinsically related to software and hardware operation.
For software safety, a special logic prevents undesired operations, while a constantly operative watchdog system points out any microprocessor malfunctions via a LED on the front of the device.
Hardware safety allows integration of an electrical interlock via power relay, so that there is no need
to use an external electrical interlock system. The manual selector on the front of the device can also
control the entire switching procedure, even in the event of a microprocessor fault, by working electromechanically on the control relays.

ABB

General specifications
24 V DC 20%
48 V DC 10%
(maximum ripple 5%)
5 W @ 24 V DC
10 W @ 48 V DC
1.8 W @ 24 V DC
4.5 W @ 48 V DC
-25 C+70 C

Rated supply voltage


(galvanically insulated from earth)
Maximum absorbed power
Rated power (mains present and circuit breakers not controlled)
Operating temperature
Maximum humidity

90% without condensation

Storage temperature

-25 C+80 C

Protection rating

IP54 (front panel)

Protection rating

[mm]

Weight

144 x 144 x 85

[kg]

0.8

Setting range for thresholds and times


Minimum voltage

Un Min

-5%-30% Un

Maximum voltage

Un Max

+5%+30% Un

Fixed frequency thresholds

10%+10% fn

t1: opening delay of the normal line circuit breaker due to network error

(CB-N)

032s

t2: generator start-up delay due to network error

032s

t3: stopping delay of the generator

0254s

t4: switching delay due to network stop

0254s

t5: closing delay of the emergency line circuit breaker


after detecting the generator voltage

(CB-E)

032s

Operating sequence

VN ok
t1

CB-N on
GE start
Caption
VN
Main voltage
CB-N Normal line circuit breaker
closed
GE
Generator
VE
Emergency line voltage
CoCo Enable switching to emergency
line
CB-E Emergency line circuit breaker
closed
LOAD Disconnection of lower priority
connected loads

ABB

t3

t2

VE ok
CoCo on
CB-E on

t5

t4

LOAD off

3/49

Accessories
Controller for automatic transfer switch - ATS010

Side panel settings

3
Caption
1 Selectors to set the under- and overvoltage thresholds
2 Dip-switches to set:
rated voltage
normal single-phase or three-phase
line
mains frequency
switching strategy
3 Switching delay time settings for
T1T5

1SDC210337F0023

Front panel

2
1
5

7
4

1SDC210338F0023

3/50

Caption
1 Status of the ATS010 unit and logic
2 Operating mode selector
3 Normal line check
4 Normal line circuit breaker status
5 Voltage on the emergency line
6 Emergency line circuit breaker status
7 Generator status

ABB

Characteristic curves and


technical information

Index
Characteristic curves
Examples of curve readout .................................................................................................. 4/2
Trip curves for distribution
Circuit breakers with thermomagnetic trip units .................................................................. 4/4
Circuit breakers with electronic trip units ............................................................................ 4/11
Trip curves for MCP
Circuit breakers with magnetic only trip units ...................................................................... 4/17
Circuit breakers with PR221DS-I electronic trip unit ........................................................... 4/18
Specific let-through energy curves (1)
240 V .................................................................................................................................... 4/19
480 V .................................................................................................................................... 4/22
600 V .................................................................................................................................... 4/25

Limitation curves
240 V .................................................................................................................................... 4/27
480 V .................................................................................................................................... 4/30
600 V .................................................................................................................................... 4/33

Technical information
Temperature performances
Circuit breakers with electronic trip units ............................................................................ 4/35
Circuit breakers with thermomagnetic trip units .................................................................. 4/36
Power losses ...................................................................................................................... 4/38

(1)

ABB

For the T1 1P characteristic curves, please ask ABB directly

4/1

Examples of curve readout

Example 1

S6 N 800
t [s]

104

103

~141.6
102
~31
10

2 x I1
1

10-1

10-2

Example 2
Current-limiting
curves
The following figure shows the trend
of the Tmax T2H 100, In = 100 circuit breaker current-limiting curves.
The r.m.s. of the prospective symmetrical short-circuit current is indicated on the abscissa of the diagram, whereas the peak short-circuit current value is indicated on the
ordinates. The current-limiting effect
can be assessed by comparing, at
the same symmetrical short-circuit
current value, the corresponding
peak value at the prospective shortcircuit current (curve A) with the limited peak value (curve B).
The T2H 100 circuit breaker with In
100 thermomagnetic trip unit at a
voltage of 480 V, limits the shortcircuit current to 12.2 kA for a fault
current of 30 kA, with a reduction
of about 50.8 kA compared with the
peak value of the 63 kA prospective short-circuit current.
4/2

10

10-1

102
x I1

1SDC210001F0023

Considering a S6N 800 TMD


In = 800 A circuit breaker. By means
of the thermal adjustment trimmer,
the current threshold I1 is selected,
for example at 0.8 x In (640 A); the
magnetic trip threshold I3, adjustable from 5 to 10 x In, we select at
8 x In, equal to 6400 A.
It can be noted that, on the basis of
the conditions in which the overload
is presented, i.e. with the circuit
breaker at thermal running or not,
the thermal relay trip varies considerably. For example, for an overload
current of 2 x I1, the trip time is between 31 and 141.6 s for hot trip,
and between 141.6 and 885 s for
cold trip.
For fault current values higher than
6400 A, the circuit breaker trips instantaneously with the magnetic
protection.

~885

T2H 100
Ip [kA] 102

63

Curve A

50.8
Curve B
12.2
10

10-1
10-1

10

30

102

103
Is [kA]

1SDC210002F0023

Trip curves for


distribution (thermomagnetic trip unit)

ABB

Example 3

T4V 250

Specific let-through
energy curve

I t [(kA) s]

An example of reading the graph of


the specific let-through energy curve
of the T4V 250 In = 80 circuit
breaker at a voltage of 490 V is given
aside.
The prospective symmetrical shortcircuit current is indicated on the
abscissa of the diagram, whereas
the ordinates show the specific letthrough energy values expressed in
[kA]2s.
In correspondence with a short-circuit current of 100 kA, the circuit
breaker lets through a value of I2t
equal to 0.7 [kA] 2s (700000 A2s).

10

0.7

10-2
1

10

102

103
Irms [kA]

1SDC210003F0023

10-1

Abbreviations used
In =
I1 =
I3 =
Irms =

ABB

Ampre rating of the thermomagnetic or electronic trip unit


Long-time pick-up setting
instantaneous pick up setting
prospective symmetrical short-circuit current

4/3

Trip curves for distribution


Circuit breakers with thermomagnetic trip units

T1 100 - T1 100 1P TMF

t [s]

104

In = 15 70 A
103

102

10

10-1
40A
60A 30A
50A

20A
25A

15A

10-2
10-1

T1 100 - T1 100 1P TMF

10

102
x I1

104

In = 80 100 A
103

102

10

10-1
90A
100A

80A

10-2
10-1

4/4

10

102
x I1

1SDC210005F0023

t [s]

1SDC210004F0023

70A

ABB

T2 100 TMF

t [s]

104

In = 15 50 A
103

102

10

10-1
30A

35A

25A

20A
15A

10-2
10-1

T2 100 TMF

t [s]

10

102
x I1

1SDC210006F0023

40A
50A

104

In = 60 100 A
103

102

10

10-2
10-1

ABB

10

102
x I1

1SDC210007F0023

10-1

4/5

Trip curves for distribution


Circuit breakers with thermomagnetic trip units

T3 225 TMF

t [s]

104

In = 60 100 A
103

102

10

60100A

10-2
10-1

T3 225 TMF

10

102
x I1

104

In = 125 225 A
103

102

10

125225A

10-1

10-2
10-1

4/6

10

102
x I1

1SDC210009F0023

t [s]

1SDC210008F0023

10-1

ABB

T4 250 TMF/TMD

t [s]

In = 20 50 A
In = 15, 20 TMF
In = 30, 40, 50 TMD

104

103

102

10

In=15A I3=500A
In=20A I3=500A
In=30A I3=500A
In=40A I3=500A
In=50A I3=500A

10-2
10-1

10

102

103
x I1

1SDC210010F0023

10-1

T4 250 TMA
t [s]

104

In = 80 250 A
103

102

10

10-1

10-2
10-1

ABB

10

102
x I1

1SDC210011F0023

I3=510 x In

4/7

Trip curves for distribution


Circuit breakers with thermomagnetic trip units

T5 400/600* TMA

t [s]

104

In = 300 600 A
* Please ask ABB for 600 A availability

103

102

10

10-1

10-2
10-1

S6 800 TMD
In = 600 A
I3 = 2.5 In

10

102
x I1

10

102
x I1

104

103

102

10

600A

10-1

10-2
10-1

4/8

1SDC210013F0023

t [s]

1SDC210012F0023

I3=510 x In

ABB

S6 800 TMD

t [s]

In = 600 A
I3 = 5 10 In

104

103

102

10

600A

10-2
10-1

S6 800 TMD
In = 800 A
I3 = 2.5 In

t [s]

10

102
x I1

1SDC210014F0023

10-1

104

4
103

102

10

800A

10-2
10-1

ABB

10

102
x I1

1SDC210015F0023

10-1

4/9

Trip curves for distribution


Circuit breakers with thermomagnetic trip units

S6 800 TMD
In = 800 A
I3 = 5 10 In

t [s]

104

103

102

10

800A

10-2
10-1

10

102
x I1

1SDC210016F0023

10-1

4/10

ABB

Trip curves for distribution


Circuit breakers with electronic trip units

T2 100

t [s]

104

0,4-0,44-0,48-0,52-0,56-0,60-0,64-0,680,72-0,76-0,80-0,84-0,88-0,92-0,96-1

PR221DS-LS
1

0,4

L-I Functions

103
1,5

2,5

102

3,5
4,5

6,5 7 7,5 8 8,5 9 10


5,5

10
102

10-1

10-3
10-1

10-1

10

x In

T2 100

t [s]

104

0,4-0,44-0,48-0,52-0,56-0,60-0,64-0,680,72-0,76-0,80-0,84-0,88-0,92-0,96-1

PR221DS-LS
0,4

L-S Functions

10
Iu [kA]

1SDC210017F0023

10-2

103

1
1,5

B
102

2
2,5

3
3,5

4,5

6,5 7 7,5 8 8,5 9 10


5,5

10

102

B
1

10-1

10-3
10-1

ABB

10-1

10
x In

10
Iu [kA]

1SDC210018F0023

10-2

4/11

Trip curves for distribution


Circuit breakers with electronic trip units

T2 100

t [s]

104

6,5 7 7,5 8 8,5 9 10

PR221DS-I
1

I Function

1,5

2 2,5 3 3,5 4,5 5,5

103

102

10
102

10-1

10-3
10-1

10-1

10

x In

T4 250 - T5 400/600*

104

0,4-0,44-0,48-0,52-0,56-0,6-0,64-0,68-0,72-0,76-0,8-0,84-0,88-0,92-0,96-1

PR221DS
L-I Functions

0,4

103

1,5 2 2,5 3 3,5 4,5 5,5 6,5 7 7,5

8 8,5

9 10

* Please ask ABB for 600 A availability

102

10
102
1

T4

10-1

T5

10-2

10-3
10-1

4/12

10

x In

10
Iu [kA]

1SDC210005F0004

t [s]

10
Iu [kA]

1SDC210019F0023

10-2

ABB

T4 250 - T5 400/600*

t [s]

104

0,4-0,44-0,48-0,52-0,56-0,6-0,64-0,68-0,72-0,76-0,8-0,84-0,88-0,92-0,96-1

PR221DS
0,4

L-S Functions

103

1,5 2 2,5 3 3,5 4,5 5,5 6,5 7 7,5 8 8,5

9 10

* Please ask ABB for 600 A availability

102

10
102
1

10-1

T4

T5

10-3
10-1

T4 250 - T5 400/600*

t [s]

104

10

x In

10
Iu [kA]

1SDC210021F0023

10-2

0,4-0,42-0,44-0,46-0,48-0,5-0,52-0,54-0,56-0,58-0,6-0,62-0,64-0,66-0,680,7-0,72-0,74-0,76-0,78-0,8-0,82-0,84-0,86-0,88-0,9-0,92-0,94-0,96-0,98-1

PR222DS/P and
PR222DS/PD

0,4

1,2 1,8 2,4

3 3,6 4,2 5,8 6,4 7 7,6 8,2 8,8 9,4 10

103

L-S-I Functions
(I2t const = ON)
Note: For T5 In = 600 A I3max = 10 x In.

5,5
2,5 3

6,5
4,5

0,6

102

7
5

7,5
8

* Please ask ABB for 600 A availability

9
9,5

1,5

10

10,5
12

102

I2t ON

10-1

T4

T5

10-3
10-1

ABB

10

x In

10
Iu [kA]

1SDC210022F0023

10-2

4/13

Trip curves for distribution


Circuit breakers with electronic trip units

T4 250 - T5 400/600*

t [s]

104

0,4-0,42-0,44-0,46-0,48-0,5-0,52-0,54-0,56-0,58-0,6-0,62-0,64-0,66-0,680,7-0,72-0,74-0,76-0,78-0,8-0,82-0,84-0,86-0,88-0,9-0,92-0,94-0,96-0,98-1

PR222DS/P and
PR222DS/PD

1,8 2,4 3 3,6 4,2 5,8 6,4

0,4

7 7,6 8,2 8,8 9,4 10

103

L-S-I Functions
(I2t const = OFF)

2,5

5,5
6,5

4 4,5 5

102

Note: For T5 In = 600 A I3max = 10 x In.

7,5
8

* Please ask ABB for 600 A availability

1,2

0,6

9
9,5

1,5

10

10,5
12

102

I2t OFF

T4

T5

10-1

10-3
10-1

10
x In

T4 250 - T5 400/600*

104

PR222DS/P and
PR222DS/PD

0,2 0,25

103

0,45 0,55 0,75

0,8

G Function
* Please ask ABB for 600 A availability

102

10

1
I4=0.20.49 x In inhibition at 4 x In
I4=0.50.79 x In inhibition at 6 x In
I4=0.81.00 x In inhibition at 8 x In

10-1

10-2

10-3
10-1

4/14

10

102
x In

1SDC210024F0023

t [s]

10
Iu [kA]

1SDC210023F0023

10-2

ABB

S6 800 - S7 1200

t [s]

104

PR211/P
0,4

LI-I Functions

103

0,5
0,6

0,7 0,9 1
0,8 0,95

1,5

D
C
B

102

8 10 12

D
C
B

10

10-1

10-3
10-1

S6 800 - S7 1200 S8 1600/2000/2500

t [s]

10

104

102
x In

1SDC210025F0023

10-2

0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,80,85-0,875-0,9-0,925-0,95-0,975-1

PR212/P

0,4

103

L-S (I2t ON)-I Functions

1
1,5

D
C
B

102

8 10 12

10

D
C
B

A
D

10

C
B

I2t ON

10-1

10-3
10-1

ABB

10

102
x In

1SDC210026F0023

10-2

4/15

Trip curves for distribution


Circuit breakers with electronic trip units

S6 800 - S7 1200 S8 1600/2000/2500

t [s]

104

0,4-0,5-0,55-0,6-0,65-0,7-0,75-0,80,85-0,875-0,9-0,925-0,95-0,975-1

PR212/P

0,4

103
2

L-S (I t OFF)-I Functions


102

1
1,5

D
C
B

8 10 12

10

D
C
B

A
10

D
C

I2t OFF

10-1

B
A

10-3
10-1

t [s]

10

102
x In

10

102
x In

104

PR212/P

0,2

103

0,3

0,4

0,6

0,8

0,9

G Function
102

10

D
C
B

10-1

10-2

10-3
10-1

4/16

1SDC210028F0023

S6 800 - S7 1200 S8 1600/2000/2500

1SDC210027F0023

10-2

ABB

Trip curves for MCP


Circuit breakers with magnetic only trip units

T2-T3 100 MCP


t [s]

Adjustable magnetic
only trip unit
I3 = 612 x In

104

103

102

10

12

10-1

10-3
10-1

10

102
x In

1SDC210029F0023

10-2

ABB

4/17

Trip curves for MCP


Circuit breakers with PR221DS-I electronic trip unit

T2 100
t [s]

104

PR221DS-I
1

I Function

1,5

2 2,5 3 3,5 4,5 5,5 6,5 7 7,5 8 8,5 9 10

103

102
Overload limit

10
102

10-1

10-3
10-1

10

10-1

x In

T4 250 - T5 400/600*

104

PR221DS-I
I Function

1,7

2,5 3 3,5 4,5 5,2 6,5 7 7,5 8 8,5 9 10

103

* Please ask ABB for 600 A availability

102
Overload limit
T4 320 - T5 630

Overload limit
T4 250 - T5 400

10
102

10-1

10-2

10-3
10-1

10

10-1
x In

4/18

10
Iu [kA]

1SDC210006F0004

t [s]

10
Iu [kA]

1SDC210047F0004

10-2

ABB

Specific let-through energy curves

T1 100

I2t [(kA)2s]

240 V

90-100A
70-80A
40-50-60A
25-30A
20A
15A

10-2
1

T2 100

I2t [(kA)2s]

102

10

103
Irms [kA]

1SDC210033F0023

10-1

240 V

90-100A
70-80A

10-1

60A
40-50A
2535A
20A
15A

10-3
10-1

ABB

10

102

103
Irms [kA]

1SDC210034F0023

10-2

4/19

Specific let-through energy curves

T3 225

I2t [(kA)2s] 10

240 V

225A
200A
175A
125A
90-100A
70-80A
60A

10-1
1

T4 250

102

103
Irms [kA]

I2t [(kA)2s] 10

240 V

100-250A
80A
40-50A
20-25A

10-1

10-2
1

4/20

10

102

103
Irms [kA]

1SDC210036F0023

10

1SDC210035F0023

ABB

T5 400/600*
I2t [(kA)2s] 10

240 V
* Please ask ABB for 600 A availability

300-600A

10-1
1

S6 800 - S7 1200 S8 1600/2000/2500

10

103
Irms [kA]

102

1SDC210037F0023

I2t [(kA)2s] 103

240 V

S8

102

S7

S6

10

10-2
1

ABB

10

102

103
Irms [kA]

1SDC210038F0023

10-1

4/21

Specific let-through energy curves

T1 100

I2t [(kA)2s]

1
90-100A

480 V

70-80A
40-50-60A
25-30A
20A
15A

10-2
1

T2 100

480 V

90-100A
70-80A
60A
40-50A
2535A
20A

10-1

15A

10-2

10-3
10-1

4/22

10

102

103
Irms [kA]

1SDC210040F0023

I2t [(kA)2s]

102
Irms [kA]

10

1SDC210039F0023

10-1

ABB

T3 225

I2t [(kA)2s] 10

480 V

225A
200A
175A
125A
90-100A
70-80A
60A

10-1
1

T4 250

10

102

103
Irms [kA]

1SDC210041F0023

I2t [(kA)2s] 10

480 V

100-250A
80A
40-50A
20-25A

10-2
1

ABB

10

102

103
Irms [kA]

1SDC210042F0023

10-1

4/23

Specific let-through energy curves

T5 400/600*

I2t [(kA)2s] 10

480 V
* Please ask ABB for 600 A availability

300-600A

10-1
1

103
Irms [kA]

102

I2t [(kA)2s] 103

480 V

S8

102

S7

S6

10

10-1

10-2
1

4/24

10

102

103
Irms [kA]

1SDC210044F0023

S6 800 - S7 1200 S8 1600/2000/2500

10

1SDC210043F0023

ABB

T4 250

I2t [(kA)2s] 10

600 V

100-250A

80A
40-50A
20-25A

10-2
1

T5 400/600*

I2t [(kA)2s]

10

103
Irms [kA]

102

1SDC210045F0023

10-1

10

600 V
300-600A

* Please ask ABB for 600 A availability

10-1
1

ABB

10

102

103
Irms [kA]

1SDC210046F0023

4/25

Specific let-through energy curves

S6 800 - S7 1200 S8 1600/2000/2500

I2t [(kA)2s] 103

600 V

S8

102

S7

S6

10

10-2
1

10

102

103
Irms [kA]

1SDC210047F0023

10-1

4/26

ABB

Limitation curves

T1 100

Ip [kA]

102

240 V

90-100A
70-80A
40-50-60A

10

25-30A
20A

1
1

T2 100

Ip [kA]

10

103
Irms [kA]

102

1SDC210048F0023

15A

102

240 V

90-100A
70-80A
60A
40-50A

10

2535A
20A
15A

10-1
10-1

ABB

10

102

103
Irms [kA]

1SDC210049F0023

4/27

Limitation curves

T3 225

Ip [kA]

102

240 V
225A
200A
175A
125A
90-100A
70-80A
60A

1
1

T4 250

103
Irms [kA]

102

Ip [kA] 102

240 V

100-250A
80A

10

40-50A
20-25A

1
1

4/28

10

102

103
Irms [kA]

1SDC210051F0023

10

1SDC210050F0023

10

ABB

T5 400/600*

Ip [kA] 102

240 V
* Please ask ABB for 600 A availability

300-600A

1
1

S6 800 - S7 1200 -

Ip [kA]

10

103
Irms [kA]

102

1SDC210052F0023

10

103

S8 1600/2000/2500
240 V
S8
S7

102
S6

1
1

ABB

10

102

103
Irms [kA]

1SDC210053F0023

10

4/29

Limitation curves

T1 100
Ip [kA]

102

480 V

90-100A
70-80A
40-50-60A
25-30A

10

20A

1
1

T2 100

102
Irms [kA]

102

480 V

90-100A
70-80A
60A
40-50A
2535A
20A

10

15A

10-1
10-1

4/30

10

102

103
Irms [kA]

1SDC210031F0003

Ip [kA]

10

1SDC210030F0003

15A

ABB

T3 225

Ip [kA]

102

480 V
225A
200A
175A
125A
90-100A
70-80A
60A

1
1

T4 250

10

103
Irms [kA]

102

1SDC210056F0023

10

Ip [kA] 102

480 V

100-250A
80A
40-50A
20-25A

1
1

ABB

10

102

103
Irms [kA]

1SDC210057F0023

10

4/31

Limitation curves

T5 400/600*

Ip [kA] 102

480 V
* Please ask ABB for 600 A availability

300-600A

1
1

Ip [kA]

103
Irms [kA]

102

103

480 V

S8
S7

102
S6

10

1
1

4/32

10

102

103
Irms [kA]

1SDC210059F0023

S6 800 - S7 1200 S8 1600/2000/2500

10

1SDC210058F0023

10

ABB

T4 250

Ip [kA] 102

600 V

100-250A
80A
40-50A
20-25A

1
1

T5 400/600*

10

103
Irms [kA]

102

1SDC210060F0023

10

Ip [kA] 102

600 V
* Please ask ABB for 600 A availability

300-600A

1
1

ABB

10

102

103
Irms [kA]

1SDC210061F0023

10

4/33

Limitation curves

S6 800 - S7 1200 S8 1600/2000/2500

Ip [kA]

103

600 V
S8
S7

102

S6

1
1

10

102

103
Irms [kA]

1SDC210062F0023

10

4/34

ABB

Temperature performances
Circuit breakers with electronic trip units

PR221DS
PR211/P
PR212/P
PR222DS

Imax [xIn]
1.05
1
0.95
0.9
0.85
0.8
0.75
0.7

0.6
95/35

104/40

113/45

122/50

131/55

149/65
140/60
158/70
Ambient temperature [F/C]

1SDC210063F0023

0.65

ABB

4/35

Temperature performances
Circuit breakers with thermomagnetic trip units

Tmax T1 and T1 1P
In [A]

50 F / 10 C

68 F / 20 C

86 F / 30 C

104 F / 40 C

122 F / 50 C

140 F / 60 C

15

18

17

16

15

14

13

20

24

22

21

20

19

17

25

29

28

27

25

23

22

30

35

34

32

30

28

26

40

47

45

43

40

37

34

50

60

57

53

50

46

42

60

71

68

64

60

56

51

70

83

79

75

70

65

60

80

94

90

85

80

75

69

90

106

101

96

90

84

78

100

121

114

107

100

92

84

In [A]

50 F / 10 C

68 F / 20 C

86 F / 30 C

104 F / 40 C

122 F / 50 C

140 F / 60 C

15

18

17

16

15

14

12

20

24

23

21

20

18

17

25

30

28

27

25

23

21

30

35

33

32

30

28

26

35

40

39

37

35

33

31

40

46

44

42

40

38

35

50

56

54

52

50

48

45

60

71

68

64

60

56

51

70

83

79

75

70

65

60

80

96

91

86

80

74

67

90

109

103

97

90

83

75

100

115

110

105

100

95

89

In [A]

50 F / 10 C

68 F / 20 C

86 F / 30 C

104 F / 40 C

122 F / 50 C

140 F / 60 C

60

70

67

64

60

56

52

70

82

78

74

70

66

61

80

92

88

84

80

75

71

90

104

100

95

90

85

79

100

117

112

106

100

94

87

125

145

139

132

125

118

110

150

175

167

159

150

141

131

175

205

195

185

175

164

152

200

236

224

213

200

187

172

225

264

251

239

225

211

195

Tmax T2

Tmax T3

4/36

ABB

Tmax T4
In [A]

50 F / 10 C

68 F / 20 C

86 F / 30 C

104 F / 40 C

122 F / 50 C

140 F / 60 C

20

24

22

21

20

19

17

25

30

28

27

25

23

21

40

47

44

42

40

37

34

50

59

56

53

50

47

43

80

94

90

85

80

75

68

100

118

112

106

100

95

85

125

148

140

133

125

119

106

150

177

168

159

150

143

127

200

236

224

212

200

190

170

250

266

252

239

225

214

191

In [A]

50 F / 10 C

68 F / 20 C

86 F / 30 C

104 F / 40 C

122 F / 50 C

140 F / 60 C

300

241345

230328

220314

210300

200286

187267

400

325465

310442

295420

280400

265380

250355

600

483690

459656

440628

420600

400572

374534

In [A]

50 F / 10 C

68 F / 20 C

86 F / 30 C

104 F / 40 C

122 F / 50 C

140 F / 60 C

600

483690

459656

440628

420600

400572

374534

800

685965

640900

605855

560800

520740

470670

Tmax T5 400/600*

Isomax S6

* Please ask ABB for 600 A availability

ABB

4/37

Power losses

Type

T1 - T1B 1p

Trip unit

TMF

TMF
T2

ELT

4
T3

TMF

TMF

TMD

T4
TMA

ELT

TMA
T5
ELT
* Please ask ABB for 600 A availability

4/38

In [A]

P [W/pole]

15

1.3

20

1.3

25

2.0

30

1.8

40

2.6

50

3.7

60

3.9

70

5.3

80

4.8

90

6.1

100

6.8

15

1.0

20

1.7

25

1.6

30

2.4

35

3.0

40

2.8

50

3.2

60

4.6

70

4.7

80

5.4

90

6.9

100

7.7

10

0.5

25

1.0

63

3.5

100

8.0

60

3.9

70

4.2

80

4.8

90

5.0

100

5.3

125

6.6

150

7.4

175

11.6

200

13.2

225

15.0

15

3.6

20

3.6

30

3.6

40

3.8

50

3.9

80

4.6

100

5.2

125

5.7

150

6.9

200

9.9

250

13.7

100

1.7

150

3.9

200

10.7

300

12.3

400

19.5

600*

40.1

300

9.3

400

16.5

600*

37.1

ABB

Type

Trip unit
TMD

S6
ELT
S7
S8

ELT
ELT

In [A]

P [W/pole]

600

27.8

800

31.0

600

27.2

800

32.0

1200

49.2

1600

42.7

2000

67.2

2500

101.7

ABB

4/39

Wiring diagrams

Index
Wiring diagrams
Graphic symbols (IEC 60617 and CEI 3-14...3-26 Standards) .............................................. 5/2

Tmax T1T5
Information for reading .......................................................................................................... 5/3
Circuit diagrams ..................................................................................................................... 5/7
Electrical accessories ............................................................................................................ 5/9

Isomax S6, S7 and S8


Information for reading ........................................................................................................ 5/12
Circuit diagrams ................................................................................................................... 5/15
Electrical accessories .......................................................................................................... 5/16

ABB

5/1

Wiring diagrams
Graphic symbols (IEC 60617 and CEI 3-14...3-26 Standards)

Thermal effect

Connection of conductors

Position switch (limit


switch), break contact

Differential current relay

Electromagnetic effect

Terminal

Position switch (limit


switch) change-over break
before make contact

Phase-failure detection
relay in a three-phase
system

Delay

Plug and socket (male


and female)

Contactor (contact open


in the unoperated
position)

Locked-rotor detection
relay operating by
current sensing

Mechanical connection
(link)

Resistor (general symbol)

Circuit breaker
disconnector with
automatic release

Lamp, general symbol

Manually operated
control (general case)

Temperature dependent
resistor

Switch-disconnector (onload isolating switch)

Mechanical interlock
between two devices

Operated by turning

Motor (general symbol)

Operating device
(general symbol)

Operated by pushing

Induction motor, threephase, squirrel cage

Operated by electric
motor

Motor with series


energization

Thermal relay
M

Operated by key

Current transformer

Instantaneous
overcurrent or rate-ofrise relay

Operated by cam

Current transformer with four


threaded winding and with
one permanent winding with
one tapping

Overcurrent relay with


adjustable short time-lag
characteristic

Hearth, groung (general


symbol)

Make contact

Overcurrent relay with


inverse short time-lag
characteristic

Converter with galvanic


separator

Break contact

Overcurrent relay with


inverse long time-lag
characteristic

Conductors in a
screened cable, two
conductors shown

Change-over break
before make contact

Earth fault overcurrent


relay with inverse short
time-lag characteristic

Twisted conductors, two


conductors shown

Position switch (limit


switch), make contact

Phase-balance current
relay

5/2

ABB

Wiring diagrams
Information for reading Tmax T1T5

State of operation represented


The diagram is shown in the following conditions:
fixed, plug-in or draw out version circuit breaker (depending on type of circuit breaker), open and racked-in
contactor for motor starting open
circuits de-energized
releases not tripped
motor operator with springs charged (for T4 and T5).

Version
The diagram shows a circuit breaker or MCS in the plug-in version (only T2, T3, T4 and T5), but is also valid for the
fixed and draw out version circuit breakers or MCS.
With the fixed version circuit breakers or MCS, the applications indicated in figures 26-27-28-29-30-31 and 32
cannot be provided.

Caption
*
A1
A11
A12

=
=
=
=
=

A13

A14

A15
A2
A3
A4
D
H, H1
K
K51

=
=
=
=
=
=
=
=

M
M1
Q
Q/13
R
S1, S2
S3
S4/1-2
K51/18
S51/S
S75I/13

=
=
=
=
=
=
=
=
=
=
=

S751S/13 =

ABB

Figure number of the diagram


See note indicated by the letter
Circuit breaker applications
FDU unit (front display)
AUX-E type auxiliary contacts, with auxiliary relays for electrical signalling of circuit breaker
open and circuit breaker tripped
PR020/K type signalling unit, with auxiliary relays for electrical signalling of the protection
functions of electronic trip unit
MOE-E type actuation unit, with auxiliary relays for carrying out the commands coming from the
dialogue unit
PR212/CI type contactor control unit for motor starting
Applications of the solenoid operator or motor operator
Applications of the RC221 or RC222 type residual current release
Indication apparatus and connections for control and signalling, outside the circuit breaker
Electronic time-delay device of the undervoltage release (outside the circuit breaker)
Signalling lamps
Contactor for motor starting
Electronic trip unit:
PR221DS trip unit, with the following protection functions:
- L against overload with inverse long time delay
- S against short-circuit with inverse short time delay
- I against short-circuit with tempo of instantaneous trip
PR222DS/P or PR222DS/PD trip unit, with the following protection functions:
- L against overload with inverse long time delay
- S against short-circuit with inverse or definite short time delay
- I against short-circuit with instantaneous trip time
- G against earth fault with short time trip
Motor for circuit breaker opening and circuit breaker closing spring charging
Three-phase asynchronous motor
Main circuit breaker
Auxiliary circuit breaker contacts
Resistor (see note F)
Contacts controlled by the cam of the motor operator
Contact controlled by the key lock of the solenoid operator or motor operator
Contacts activated by the circuit breaker rotary handle (see note C)
Contacts for electrical signalling of the protection functions of the electronic trip unit
Contact for electrical signalling of overload in progress
Contacts for electrical signalling of circuit breaker in racked-in position (only provided with circuit
breakers in plug-in version)
Contacts for electrical signalling of circuit breaker in racked-out position (only provided with
circuit breakers in plug-in version)

5/3

Wiring diagrams
Information for reading Tmax T1T5

S87/1
S87/2
S87/3

= Contact for electrical signalling of RC222 type residual current release pre-alarm
= Contact for electrical signalling of RC222 type residual current release alarm
= Contact for electrical signalling of circuit breaker open due to RC221 or RC222 type residual
current release trip
SC
= Pushbutton or contact for closing the circuit breaker
SC3
= Pushbutton for motor starting
SO
= Pushbutton or contact for opening the circuit breaker
SO3
= Pushbutton for stopping the motor
SQ
= Contact for electrical signalling of circuit breaker open
SY
= Contact (bell alarm) for electrical signalling of circuit breaker open due to YO, YO1, YO2 or YU
thermomagnetic trip unit intervention (tripped position)
TI
= Toroidal current transformer
TI/L1
= Current transformer placed on phase L1
TI/L2
= Current transformer placed on phase L2
TI/L3
= Current transformer placed on phase L3
TI/N
= Current transformer placed on the neutral
W1
= Serial interface with the control system (EIA RS485 interface. See note D)
X1,X2,X5X9 = Connectors for the circuit breaker auxiliary circuits (in the case of circuit breakers in plug-in
version, removal of the connectors takes place simultaneously with that of the circuit breaker.
See note E)
X11
= Back-up terminal box
X3,X4
= Connectors for the circuits of the electronic trip unit (in the case of circuit breakers in the plug-in
version, removal of the connectors takes place simultaneously with that of the circuit breaker)
XA
= Interfacing connector of the PR222DS/P or PR222DS/PD trip unit
XA1
= Three-way connector for YO/YU (see note E)
XA10
= Three-way connector for solenoid operator
XA2
= Twelve-way connector for auxiliary contacts (see note E)
XA5
= Three-way connector for contact of electrical signalling of circuit breaker open due to trip
of the RC221 or RC222 type residual current release (see note E)
XA6
= Three-way connector for contact of electrical signalling of circuit breaker open due to trip
of the overcurrent release (see note E)
XA7
= Six-way connector for auxiliary contacts (see note E)
XA8
= Six-way connector for contacts operated by the rotary handle or for the motor operator
(see note E)
XA9
= Six-way connector for the electrical signalling of RC222 type residual current release pre-alarm
and alarm and for opening by means of the release itself (see note E)
XB,XC,XE
= Interfacing connectors of the AUX-E unit
XD
= Interfacing connector of the FDU unit
XF
= Interfacing connector of the MOE-E unit
X0
= Connector for the YO1 trip coil
X01
= Connector for the YO2 trip coil
XV
= Terminal boxes of the applications
YC
= Shunt closing release of the solenoid operator or motor operator
YO
= Shunt trip
YO1
= Shunt trip coil of the electronic trip unit
YO2
= Shunt trip coil of the RC221 or RC222 type residual current release
YO3
= Shunt trip of the solenoid operator
YU
= Undervoltage release (see note B).

5/4

ABB

Description of figures
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Fig. 5

=
=
=
=
=

Fig. 6

Fig. 7

Fig. 8
Fig. 9
Fig. 10
Fig. 11
Fig. 12
Fig. 21

=
=
=
=
=
=

Fig. 22

Fig. 23
Fig. 24
Fig. 25
Fig. 26
Fig. 27
Fig. 28
Fig. 29
Fig. 30
Fig. 31
Fig. 32

=
=
=
=
=
=
=
=
=
=

Fig. 41

Shunt trip.
Permanent shunt trip.
Instantaneous undervoltage release (see note B and F).
Undervoltage release with electronic time-delay device outside the circuit breaker (see note B).
Instantaneous undervoltage release in version for machine tools with one contact in series (see note
B, C, and F).
Instantaneous undervoltage release in version for machine tools with two contacts in series (see note
B, C, and F).
One changeover contact for electrical signalling of circuit breaker open due to RC221 or RC222
type residual current release trip.
RC222 type residual current release.
Two electrical signalling contacts for RC222 type residual current release pre-alarm and alarm.
Solenoid operator.
Stored energy motor operator.
One changeover contact for electrical signalling of motor operator locked with key.
Three changeover contacts for electrical signalling of circuit breaker open or closed and one
changeover contact for electrical signalling of circuit breaker open due to YO, YO1, YO2 and YU
thermomagnetic trip unit intervention (tripped position).
One changeover contact for electrical signalling of circuit breaker open or closed and a changeover
contact for electrical signalling of circuit breaker open due to YO, YO1, YO2 or YU thermomagnetic
trip unit intervention (tripped position).
Two changeover contacts for electrical signalling of circuit breaker open or closed.
One changeover contact for electrical signalling of circuit breaker open due to trip unit intervention.
One contact for electrical signalling of circuit breaker open due to trip unit intervention.
First position of circuit breaker changeover contact, for electrical signalling of racked-in.
Second position of circuit breaker changeover contact, for electrical signalling of racked-in.
Third position of circuit breaker changeover contact, for electrical signalling of racked-in.
First position of circuit breaker changeover contact, for electrical signalling of isolated.
Second position of circuit breaker changeover contact, for electrical signalling of isolated.
Third position of circuit breaker changeover contact, for electrical signalling of isolated.
Circuit of the current transformer on neutral conductor outside the circuit breaker (for plug-in version
circuit breaker).
Auxiliary circuits of the PR222DS/P electronic trip unit connected with FDU front display unit.

ABB

5/5

Wiring diagrams
Information for reading Tmax T1T5

Incompatibility
The circuits indicated by the following figures cannot be supplied at the same time on the same circuit breaker:
1-2-3-4-5-6
5 - 6 - 11
10 - 11
10 - 12
21 - 22 - 23
24 - 25
26 - 32

Notes
A) The circuit breaker is supplied fitted with the applications specified in the ABB order confirmation.
B) The undervoltage release is supplied for power supply branched on the supply side of the circuit breaker or
from an independent source: circuit breaker closing is only allowed with the release energised (the lock on
closing is made mechanically).
C) The S4/1 and S4/2 contacts shown in figures 5-6 open the circuit with the circuit breaker open and close it
again when a manual closing command is given by means of the rotary handle, in accordance with the
Standards regarding machine tools (in any case, closing does not take place if the undervoltage release is not
supplied).
D) For connection of the EIA RS485 serial line, see the following documentation:
ITSCE-RH0199 for MODBUS communication.
E) Connectors XA1, XA2, XA5, XA6, XA7, XA8 and XA9 are supplied on request. They are always supplied with
T2 and T3 circuit breakers in the plug-in version.
Connectors X1, X2, X5, X6, X7, X8 and X9 are supplied on request. They are always supplied with circuit
breakers in the plug-in version and with T4 and T5 circuit breakers in the fixed version.
F) Additional external resistor for undervoltage release supplied at 250 V DC, 380/440 V AC and 480/500 V AC.
G) In the case of fixed version circuit breaker with current transformer on external neutral conductor outside the
circuit breaker, when the circuit breaker is to be removed, it is necessary to short-circuit the terminals of the
TI/N transformer.
H) With MOS 110250 V AC, only use MOS-A for 200 V Un 250 V.
I) SQ and SY are opto-insulated contacts.

5/6

ABB

Wiring diagrams
Circuit diagram Tmax T1T5

Tmax T1T5

1SDC210370F0023

Three-pole circuit breaker with


magnetic trip unit

Three-pole or four-pole MCS


(on-load isolating switch)

Three-pole or four-pole circuit breaker with


PR222DS electronic trip unit

1SDC210371F0023

1SDC210370F0023

Two pole, three-pole or four-pole


circuit breaker with thermomagnetic
trip unit

1SDC210370F0023

1SDC210370F0023

State of operation

Three-pole or four-pole circuit breaker with


PR222DS/P or PR222DS/PD electronic
trip unit

Three-pole or four-pole circuit breaker with


RC221 or RC222 residual current release

ABB

1SDC210371F0023

5/7

Wiring diagrams
Circuit diagram Tmax T1T5

1SDC210372F0023

Tmax T1T5

Fixed version three-pole circuit breaker with current transformer on neutral conductor, external to circuit breaker

1SDC210372F0023

5
Plug-in or draw out version three-pole circuit breaker with current transformer
on neutral conductor, external to circuit breaker

5/8

ABB

Wiring diagrams
Electrical accessories Tmax T1T5

Tmax T1T5

1SDC210373F0023

Shunt opening and undervoltage releases

Residual current releases and remote controls

1SDC210374F0023

ABB

5/9

Wiring diagrams
Electrical accessories Tmax T1T5

Tmax T1T5

1SDC210375F0023

Auxiliary contacts

Position contacts

1SDC210376F0023

5/10

ABB

PR222DS/P electronic trip unit connected with the FDU front


display unit

1SDC210377F0023

FDU

ABB

5/11

Wiring diagrams
Information for reading Isomax S6, S7 and S8

State of the operation represented


The circuit is shown in the following conditions:
fixed, plug in or draw out circuit breaker (depending on type of circuit breaker), open and racked in
circuits de-energized
releases not tripped
motor operator with springs loaded (for S6-S7 circuit breakers).

Versions
The diagram indicates a circuit breaker or a MCS in draw out version but it may be applied to circuit breaker or a
MCS in the fixed version too.
Circuits given in figures 21-22-23-24-25-31-32-33-34-35 cannot be supplied with circuit breaker or MCS in fixed
version.

Caption

5/12

*
A1
A2
A4
A11
A12
A12/KC
A12/KO
A13

=
=
=
=
=
=
=
=
=
=

D
H1
K51

=
=
=

K51/1B
K51/YO1
KO

=
=
=

M
M1
Q
Q/O2
R1
S1

=
=
=
=
=
=

S2

S3

Reference number of diagram figure


See note indicated by the letter
Circuit breaker accessories
Motor operator accessories
Indicative devices and connections for control and signallings, external to the circuit breaker
Dialogue unit type PR212/D-L or PR212/D-M, for connection with a central control system
Actuating unit type PR212/T, with auxiliary relays for the execution of dialogue unit controls
Closing control of the actuating unit
Opening control of the actuating unit
Signalling unit type PR020/K, with auxiliary relays for electrical indication of the electronic trip
unit protective functions
Solid-state time-delaying device for undervoltage release (external to the circuit breaker)
Signalling lamp
Electronic trip unit:
PR211/P trip unit, with the following protective functions:
- L against overload with inverse long time-delay trip
- I against short-circuit with instantaneous trip
PR212/P trip unit, with the following protective functions:
- L against overload with inverse long time-delay trip
- S against short-circuit with inverse or definite short time-delay trip
- I against short-circuit with instantaneous trip
- G against earth fault with inverse short time-delay trip
Contacts for electrical indication of the electronic trip unit protective functions
Alarm indication of YO1 release tripped (bell alarm) for overcurrent and for trip test
Opening relay and spring charging device with a slay put make contact disengaged by a cam of
the motor operating mechanism when the circuit breaker reaches the open position and the
closing springs are charged
Motor for the circuit breaker opening and for the closing springs charging
Induction motor
Main circuit breaker
Circuit breaker auxiliary contacts
Thermistor
Contact operated by the cam of the motor operating mechanism: it closes when the circuit
breaker is in closed position and it opens when the circuit breaker is in open position (it does not
switch when the circuit breaker is in tripped position)
Contact operated by the cam of the motor operating mechanism: it opens when the circuit
breaker is in closed position and it closes when the circuit breaker is in open position (it does not
switch when the circuit breaker is in tripped position). The contact is also operated by the key
lock device (if provided)
Contact operated by the cam of the motor operating mechanism: it opens after closing of
contact KO and it closes when the circuit breaker is in open position (it does not switch when the
circuit breaker is in tripped position

ABB

S75I/15
S75S/15
SC
SC3
SO
SO1,SO2
SO3
SY
TI/L1
TI/L2
TI/L3
TI/N
W1
X1, X2
X3, X4
X5, X6
XO
XV
YC
YO
YO1
YU

= Contacts signalling circuit breaker in the connected position (provided with circuit breaker in
draw out version only. See note D)
= Contacts signalling circuit breaker in the isolated position (provided with circuit breaker in draw
out version only. See note D)
= Pushbutton or contact for circuit breaker closing
= Pushbutton for motor start
= Pushbutton or contact for circuit breaker opening
= Pushbutton or contact for circuit breaker opening
= Pushbutton for motor stop
= Contact signalling circuit breaker tripped through thermomagnetic, Y0, Y01, YU releases
operation (bell alarm)
= Current transformer located on the phase L1
= Current transformer located on the phase L2
= Current transformer located on the phase L3
= Current transformer located on neutral
= Serial interface with the remote supervision and control system (see note E)
= Connectors for the circuit breaker auxiliary circuits
= Connectors for the electronic trip unit circuits (in case of circuit breaker in draw out plug-in
version the racking-out of the connectors occur simultaneoustly with the one of the circuit breaker)
= Delivery terminal boards for the electronic trip unit circuits
= Connector for opening solenoid YO1
= Terminal boards of the accessories
= Closing coil
= Shunt trip
= Shunt trip of electronic trip unit
= Undervoltage release (see note B).

Description of figures
Fig. 1
Fig. 4
Fig. 6
Fig. 8
Fig. 11
Fig. 12

=
=
=
=
=
=

Fig. 13

Fig. 21
Fig. 22
Fig. 23
Fig. 24
Fig. 25
Fig. 31
Fig. 32
Fig. 33
Fig. 34
Fig. 35
Fig. 41
Fig. 48

=
=
=
=
=
=
=
=
=
=
=
=

Fig. 49

Fig. 50

Shunt trip
Instantaneous undervoltage release (see note B)
Undervoltage release with solid-state time-delaying device external to the circuit breaker (see note B)
Stored energy motor operator
Two change-over contacts signalling circuit breaker on/off
One change-over contact signalling circuit breaker on/off and one change-over contact signalling
circuit breaker tripped through thermomagnetic YO, YO1, YU releases operation (bell alarm)
One contact for electrical signalling of circuit breaker on, one contact for electrical signalling of circuit
breaker off and one contact for electrical signalling of circuit breaker not tripped through
thermomagnetic, YO, YO1, YU releases operation (not tripped position) to be used for example, for
the accept contact reported in fig. 8
First circuit breaker position contact, signalling the connected position (see note D)
Second circuit breaker position contact, signalling the connected position (see note D)
Third circuit breaker position contact, signalling the connected position (see note D)
Fourth circuit breaker position contact, signalling the connected position (see note D)
Fifth circuit breaker position contact, signalling the connected position (see note D)
First circuit breaker position contact, signalling the isolated position (see note D)
Second circuit breaker position contact, signalling the isolated position (see note D)
Third circuit breaker position contact, signalling the isolated position (see note D)
Fourth circuit breaker position contact, signalling the isolated position (see note D)
Fifth circuit breaker position contact, signalling the isolated position (see note D)
Contact signalling YO1 releases operated (for electrical characteristics of the contact see note G)
Auxiliary circuits of the electronic trip unit PR212/P connected to the dialogue unit type PR212/D-L
or PR212/D-M and to the actuating unit type PR212/T
Auxiliary circuits of the electronic trip unit PR212/P connected to the dialogue unit type PR212/D-L
or PR212/D-M, to signalling unit type PR020/K and to the actuating unit type PR212/T
Auxiliary circuits of the electronic trip unit PR212/P connected to signalling unit type PR020/K.

Note: figures are always valid for S6 and S7; figures 1, 4, 41, 48, 49 and 50 are also valid for S8.

ABB

5/13

Wiring diagrams
Information for reading Isomax S6, S7 and S8

Incompatibility
The combinations of circuits given in the figures below are not possible on the same circuit breaker:
1-4-6
11 - 12 - 13
21 - 31
22 - 32
23 - 33
24 - 34
25 - 35
48 - 49 - 50

Notes
A) Circuit breaker is supplied complete with the accessories listed in the ABB order acknowledgement only.
B) Undervoltage release is suitable for circuit breaker supply side feeding or for feeding from an independent
source: circuit breaker closes only if the undervoltage release is energized (lock on closing is achieved mechanically)
D) Circuit breaker can be equipped with S75I and S75S position contact, in whatever combination, with a
maximum of 5 total contacts
E) To connect the serial communication line to the remote supervision and control system, see following documentation:
ITSCE-RH0298.001 for Modbus
ITSCE-RH0297.001 for Lon
F) In case of circuit breaker in fixed version with current transformer on external conductor, in order to remove
the circuit breaker it is necessary to short-circuit the terminals of TI/N current transformer
G) Contact signalling electronic trip unit operated (see fig. 41) has the following electrical characteristics:
rated voltage = 24 V
breaking capacity (resistive load) = 3 W/VA
maximum current interrupted = 0.5 A.

5/14

ABB

Wiring diagrams
Circuit diagrams Isomax S6, S7 and S8

Isomax S6-S7-S8

1SDC210378F0023

State of operation

Two-pole, three-pole or four-pole S6-S7


circuit breaker with PR211/P electronic
trip unit

Two-pole, three-pole or four-pole S6-S7


circuit breaker with PR212/P electronic trip
unit

S6-S7-S8 MCP three-pole, with


PR211/P (I) trip unit

1SDC210379F0023

Two-pole, three-pole or
four-pole S6 circuit
breaker with thermomagnetic trip unit

5
S6-S7-S8 MCS threepole and four-pole

ABB

Fixed version three-pole S6-S7-S8 circuit breaker with


current transformer on neutral conductor, external to
circuit breaker

Draw out version three-pole S6-S7 circuit breaker with current transformer on neutral conductor, external to circuit breaker

5/15

Wiring diagrams
Electrical accessories Isomax S6, S7 and S8

Isomax S6-S7-S8

1SDC210380F0023

Service releases, stored energy motor operator and auxiliary contacts

Auxiliary contacts

1SDC210381F0023

5/16

ABB

1SDC210382F0023

PR212/P trip unit connected to the dialogue unit PR212/D and actuator
unit PR212/T

PR212/P trip unit connected to the dialogue unit PR212/D signalling


unit PR020/K and actuator unit PR212/T

1SDC210383F0023

ABB

5/17

Wiring diagrams
Electrical accessories Isomax S6, S7 and S8

Isomax S6-S7-S8

1SDC210384F0023

PR212/P trip unit connected to the signalling unit PR020/K

5/18

ABB

Overall dimensions

Index
Overall dimensions
Tmax T1 and single-pole Tmax T1
Fixed circuit breaker/terminals ............................................................................................... 6/2
Tmax T2
Fixed circuit breaker/terminals ............................................................................................... 6/4
Plug-in circuit breaker/terminals ............................................................................................ 6/7
Tmax T3
Fixed circuit breaker/terminals ............................................................................................. 6/10
Plug-in circuit breaker/terminals .......................................................................................... 6/13
Tmax T4
Fixed circuit breaker/terminals ............................................................................................. 6/16
Plug-in circuit breaker/terminals .......................................................................................... 6/19
Draw out circuit breaker/terminals ....................................................................................... 6/22
Tmax T5
Fixed circuit breaker/terminals ............................................................................................. 6/24
Plug-in circuit breaker/terminals .......................................................................................... 6/27
Draw out circuit breaker/terminals ....................................................................................... 6/31
Isomax S6
Fixed circuit breaker/terminals ............................................................................................. 6/35
Draw out circuit breaker/terminals ....................................................................................... 6/37
Isomax S7
Fixed circuit breaker/terminals ............................................................................................. 6/39
Draw out circuit breaker/terminals ....................................................................................... 6/41
Isomax S8
Fixed circuit breaker/terminals ............................................................................................. 6/43
Circuit breaker with residual current release
T1, T2 and T3 with residual current release - RC221/RC222 .............................................. 6/44
T4 and T5 with residual current release - RC221/RC222 .................................................... 6/47
Accessories
Tmax T1 - T2 - T3 ................................................................................................................ 6/49
Tmax T4 - T5 ........................................................................................................................ 6/53
Isomax S6 ............................................................................................................................ 6/60
Isomax S7 ............................................................................................................................ 6/64
Isomax S8 ............................................................................................................................ 6/68
Distances to be respected
Tmax .................................................................................................................................... 6/69
Isomax ................................................................................................................................. 6/70
ABB

6/1

Overall dimensions
Tmax T1 and single-pole Tmax T1

Fixed circuit breaker

[mm/in]

1SDC210401F0023

1SDC210402F0023

Fixing on DIN EN 50022 rail

1SDC210400F0023

Fixing on sheet

Without inserts

With inserts

1SDC210405F0023

1SDC210403F0023

5 Nm

0.8 Nm

1.4 Nm

T1 1P (SINGLE-POLE)

Depth of the switchboard in the


case of circuit breaker with
face extending from the compartment door, without flange

Bracket for fixing onto rail

Bottom terminal covers with


IP40 degree of protection

5
6/2

For front terminals

Without inserts

3 POLES

4 POLES

With inserts

1SDC210409F0023

Depth of the switchboard in the


case of circuit breaker with
face not extending from the
compartment door, with or
without flange

1SDC210408F0023

Drilling templates for support sheet

1SDC210407F0023

Caption

1SDC210406F0023

1SDC210404F0023

T1 1P (SINGLE-POLE)

T1 1P (SINGLE-POLE)

Insulating plate
ABB

Terminals

[mm/in]
Front for copper/aluminium cables - FC CuAl

71
2.8

9.5x9.5
0.37x0.37

17
0.67
45
1.77

1SDC210410F0023

104
4.09

52
2.05

11.5
0.45

25.5
1

84
3.31

>
_ 2
>
_ 0.08
>
_ 3
>
_ 0.12

103
4.06

1SDC210411F0023

Flange for the compartment door

1SDC210412F0023

Drilling templates of the compartment door

Without flange and


circuit breaker face flush
with door (3-4 POLES)
or extending (3 POLES)

Without flange and


circuit breaker face
extending (4 POLES)

1SDC210413F0023

With flange and


circuit breaker face flush
with door (3-4 POLES)

(SINGLE-POLE)
ABB

6/3

Overall dimensions
Tmax T2

Fixed circuit breaker

[mm/in]
Fixing on DIN EN 50022 rail

1SDC210415F0023

0.8 Nm

1SDC210418F0023

Drilling templates of the compartment door

1SDC210417F0023

Flange for the


compartment door

1SDC210416F0023

1SDC210414F0023

0.8 Nm

Fixing on sheet

With flange and


circuit breaker face
flush with door
(3-4 POLES)

Depth of the switchboard


in the case of circuit breaker
with face not extending from
the compartment door, with
or without flange

Depth of the switchboard


in the case of circuit breaker
with face extending from the
compartment door, without
flange

Bracket for fixing onto rail

Low terminal covers with


degree of protection IP40

Insulating plate

6/4

Without flange and


circuit breaker face
extending (4 POLES)

Drilling templates for support sheet


For rear terminals

For front terminals

1SDC210420F0023

Without flange and


circuit breaker face
extending (3 POLES)

1SDC210419F0023

Caption

Without flange and


circuit breaker face
flush with door
(3-4 POLES)

3 POLES

4 POLES

3 POLES

4 POLES

ABB

Terminals

[mm/in]
Front - F

Caption
Insulating base plate (compulsory)

Insulating barriers between


phases (compulsory)

2
6 Nm

1SDC210421F0023

Front for copper/aluminium cables FC CuAl 1/0 AWG/50 mm2

Front for copper cables - FC Cu

0.55x0.55
5.6 Nm

1SDC210422F0023

Caption
Insulating barriers between
phases (compulsory)

Insulating plate

Front extended spread - ES

18 Nm

1SDC210424F0023

6 Nm

1SDC210423F0023

ABB

6/5

Overall dimensions
Tmax T2

Terminals

[mm/in]

High terminal covers with


degree of protection IP40

Insulating barriers between


phases (compulsory without 1)

Front extended - EF

9 Nm
6 Nm

Caption
1

Low terminal covers with


degree of protection IP40

Insulating barriers between


phases

Rear - R
9 Nm

1SDC210426F0023

1SDC210425F0023

Caption

6/6

ABB

Plug-in

[mm/in]

circuit breaker

Fixing on sheet

Depth of the switchboard in


the case of circuit breaker
with face not extending
from the compartment
door, with or without flange

Depth of the switchboard in


the case of circuit breaker
with face extending from
the compartment door,
without flange

Fixed part

Moving part with terminal


covers, degree of protection
IP40

Drilling templates of the compartment door

1SDC210429F0023

1SDC210430F0023

Flange for
compartment door

1SDC210428F0023

1SDC210427F0023

Caption

With flange and


circuit breaker face
flush with door
(3-4 POLES)

Without flange and


circuit breaker face
flush with door
(3-4 POLES)

Without flange and


circuit breaker face
extending (3 POLES)

Without flange and


circuit breaker face
extending (4 POLES)

Drilling templates for support sheet


For front terminals

For rear terminals

3 POLES

ABB

4 POLES

1SDC210432F0023

1SDC210431F0023

3 POLES

4 POLES

6/7

Overall dimensions
Tmax T2

Terminals

[mm/in]
Front - F

1SDC210433F0023

6 Nm

Front for copper cables - FC Cu

Front for copper/aluminium cables FC CuAl 1/0 AWG/50 mm2

Caption

Front extended spread - ES

Insulating barriers between


phases (compulsory)

18 Nm

1SDC210436F0023

57.25

6 Nm

1SDC210435F0023

1SDC210434F0023

5.6 Nm

6/8

ABB

[mm/in]

High terminal covers with


degree of protection IP40

Insulating barriers between


phases (compulsory without 1)

9 Nm

6 Nm

Front extended - EF

Low terminal covers with


degree of protection IP40

Rear - R
9 Nm

Caption

1SDC210437F0023

Caption

1SDC210438F0023

ABB

6/9

Overall dimensions
Tmax T3

Fixed circuit breaker

[mm/in]

1SDC210440F0023

1SDC210441F0023

Fixing on DIN EN 50022 rail

1SDC210439F0023

Fixing on sheet

Caption
1

Depth of the switchboard in the case of circuit breaker with face


not extending from the compartment door, with or without flange

Depth of the switchboard in the case of circuit breaker with face


extending from the compartment door

Bracket for fixing on rail

Low terminal covers with degree of protection IP40

Insulating plate

Drilling templates of the compartment door

1SDC210443F0023

1SDC210442F0023

Flange for
compartment door

With flange and


circuit breaker face
flush with door
(3-4 POLES)

Without flange and


circuit breaker face
flush with door
(3-4 POLES)

Without flange and


circuit breaker face
extending (3 POLES)

Without flange and


circuit breaker face
extending (4 POLES)

Drilling templates for support sheet


For rear terminals

For front terminals

3 POLES
6/10

4 POLES

3 POLES

4 POLES

1SDC210445F0023

1SDC210444F0023

ABB

Terminals
Caption
1

[mm/in]
Front - F

Insulating base plate (compulsory)


8 Nm

1SDC210446F0023

Front for copper/aluminium cables - FC CuAl

71
2.8

84
3.31
79
3.11

58
2.28
9.3
0.37

12.5
0.49

FC CuAl

3
0.12

Caption
Insulating barriers between
phases (compulsory)

Insultating plate

103
4.06

Front extended spread - ES

8 Nm

2
0.08

300 Kcmil - 4 AWG

1SDC210448F0023

116
4.57

1SDC210447F0023

6.2
0.24

FC CuAl
1/0 - 14 AWG

45
1.77

Front for copper cables - FC Cu

18 Nm

1SDC210449F0023

ABB

6/11

Overall dimensions
Tmax T3

Terminals

High terminal covers with


degree of protection IP40

Insulating barriers between


phases (compulsory without 1)

Insulating plate

Front extended - EF

8 Nm
8 Nm

Caption
1

Low terminal covers with


degree of protection IP40

Insulating plate

1SDC210450F0023

Caption

[mm/in]

Rear - R

9 Nm
6 Nm

1SDC210451F0023

6/12

ABB

Plug-in

[mm/in]

circuit breaker

Fixing on sheet

Caption
Depth of the switchboard in
the case of circuit breaker
with face not extending
from the compartment
door, with or without flange

Depth of the switchboard in


the case of circuit breaker
with face extending from
the compartment door,
without flange

Fixed part

Moving part with terminal


covers, degree of protection
IP40

1SDC210455F0023

Drilling templates of the compartment door

1SDC210454F0023

Flange for
compartment door

1SDC210453F0023

1SDC210452F0023

With flange and


circuit breaker face
flush with door
(3-4 POLES)

Without flange and


circuit breaker face
flush with door
(3-4 POLES)

Without flange and


circuit breaker face
extending (3 POLES)

Without flange and


circuit breaker face
extending (4 POLES)

Drilling templates for support sheet


For front terminals

For rear terminals

3 POLES

4 POLES
3 POLES

ABB

4 POLES

1SDC210457F0023

1SDC210456F0023

6/13

Overall dimensions
Tmax T3

Terminals

[mm/in]
Front - F

Front for copper cables - FC Cu

1SDC210459F0023

1SDC210458F0023

8 Nm

Front for copper/aluminium cables FC CuAl 1/0 AWG/50 mm2

1SDC210460F0023

10
0.39

Caption
1

Front extended spread - ES

Insulating barriers between


phases (compulsory)

1SDC210461F0023

8 Nm

18 Nm

6/14

ABB

[mm/in]

High terminal covers with


degree of protection IP40

Insulating barriers between


phases (compulsory without 1)

18 Nm

8 Nm

Front extended - EF

Caption
1

1SDC210462F0023

Caption

Rear - R

Low terminal covers with


degree of protection IP40

9 Nm
6 Nm

1SDC210463F0023

ABB

6/15

Overall dimensions
Tmax T4

Fixed circuit breaker

[mm/in]
Fixing on sheet

Caption

Overall dimensions with


cabled auxiliary contacts
mounted
(only 3Q 1SY)

1SDC210465F0023

Drilling templates of the compartment door

1SDC210467F0023

1SDC210466F0023

Flange for
compartment door

1SDC210468F0023

Overall dimensions with


cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)

1SDC210464F0023

3-4 POLES

3-4 POLES

With flange

Without flange

Drilling templates for support sheet


For front terminals

For rear terminals

3 POLES

6/16

4 POLES

3 POLES

1SDC210472F0023

1SDC210471F0023

1SDC210469F0023

1SDC210470F0023

4 POLES

ABB

Terminals

[mm/in]

1SDC210473F0023

1SDC210474F0023

Front - F

Front for copper/aluminium cables - FC CuAl

Front terminals for cable


connection 2x150 mm2

Front terminals for multicable


connection

High terminal covers with


degree of protection IP40

1SDC210478F0023

Caption

Front extended spread - ES

ABB

1SDC210482F0023

1SDC210481F0023

Insulating barriers between


phases (compulsory)

1SDC210480F0023

1SDC210477F0023

Front multicable - MC

1SDC210479F0023

Caption

1SDC210476F0023

1SDC210475F0023

Front for copper cables - FC Cu

6/17

Overall dimensions
Tmax T4

Terminals

High terminal covers with


degree of protection IP40

Insulating barriers between


phases (compulsory without 1)

1SDC210483F0023

Front extended - EF

1SDC210484F0023

Caption

[mm/in]

Caption

1SDC210486F0023

Low terminal covers with


degree of protection IP40

1SDC210485F0023

Rear - R

1SDC210487F0023

6/18

ABB

Plug-in

[mm/in]

circuit breaker

Fixing on sheet

Moving part with terminal


covers, degree of protection
IP40

Overall dimensions with


cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)

Overall dimensions with


cabled auxiliary contacts
mounted
(only 3Q 1SY)

Drilling templates of the compartment door

1SDC210491F0023

1SDC210490F0023

Flange for
compartment door

1SDC210492F0023

Fixed part

1SDC210489F0023

1SDC210488F0023

Caption

With flange

Without flange

Drilling templates for support sheet


For front terminals

For rear terminals

4 POLES

3 POLES
ABB

1SDC210496F0023

3 POLES

1SDC210495F0023

1SDC210493F0023

1SDC210494F0023

4 POLES
6/19

Overall dimensions
Tmax T4

Terminals

[mm/in]

1SDC210497F0023

1SDC210498F0023

Front - EF

For Cu cables

For Cu Al cables

High terminal covers with


degree of protection IP40

1SDC210499F0023

Front for copper cables - FC Cu or for copper/aluminium cables - FC CuAl

1SDC210500F0023

Caption

6/20

ABB

1SDC210506F0023

ABB

1SDC210505F0023

1SDC210504F0023

1SDC210503F0023

1SDC210502F0023

1SDC210501F0023

[mm/in]

Rear flat vertical - VR

3-4 POLES

Rear flat horizontal - HR

3-4 POLES

6/21

Overall dimensions
Tmax T4

Draw out

[mm/in]

circuit breaker

Fixing on sheet

Caption

Moving part

Lock for compartment door


(available on request)

Overall dimensions with


cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)

1SDC210507F0023

Fixed part

1SDC210508F0023

1SDC210509F0023

isolating distance

Drilling templates of the compartment door

1SDC210511F0023

1SDC210510F0023

Flange for compartment


door

Drilling templates for support sheet

4 POLES

3 POLES

6/22

1SDC210514F0023

3 POLES

1SDC210513F0023

1SDC210512F0023

For rear terminals

1SDC210513F0023

For front terminals

4 POLES

ABB

ABB
1SDC210521F0023

1SDC210520F0023

1SDC210519F0023

1SDC210518F0023

1SDC210517F0023

Front for copper cables - FC Cu

1SDC210526F0023

Rear flat horizontal - HR

1SDC210525F0023

1SDC210523F0023

1SDC210522F0023

Front - EF

1SDC210527F0023

1SDC210524F0023

1SDC210516F0023

Terminals
[mm/in]

Front for copper/aluminium cables - FC CuAl

Rear flat vertical - VR

3-4 POLES

3-4 POLES

6/23

Overall dimensions
Tmax T5 (400 A)

Fixed circuit breaker

[mm/in]
Fixing on sheet

Caption

Overall dimensions with


cabled auxiliary contacts
mounted
(only 3Q 1SY)

1SDC210529F0023
1SDC210531F0023

Drilling templates of the compartment door

1SDC210530F0023

Flange for
compartment door

With flange (3-4 POLES)

1SDC210532F0023

Overall dimensions with


cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)

1SDC210528F0023

Without flange (3-4 POLES)

Drilling templates for support sheet


For front terminals

For rear terminals

4 POLES
3 POLES

6/24

1SDC210536F0023

1SDC210535F0023

3 POLES

1SDC210534F0023

1SDC210533F0023

4 POLES

ABB

Terminals

[mm/in]
Front for copper cables - FC Cu

Caption

Front for copper/aluminium cables


Cu/Al 300 mm2 FC CuAl

Caption

ABB

1SDC210539F0023
1SDC210542F0023

1SDC210541F0023

Front extended spread - ES

1SDC210545F0023

1SDC210544F0023

Insulating barriers between


phases (compulsory)

1SDC210543F0023

Front for copper/aluminium cables Cu/Al 2x240 mm2 - FC CuAl

High terminal covers with


degree of protection IP40

1SDC210540F0023

1SDC210538F0023

1SDC210537F0023

Front - F

6/25

Overall dimensions
Tmax T5 (400 A)

Terminals

High terminal covers with


degree of protection IP40

Insulating barriers between


phases (compulsory without 1)

1SDC210546F0023

Front extended - EF

1SDC210547F0023

Caption

[mm/in]

Caption

1SDC210549F0023

Low terminal covers with


degree of protection IP40

1SDC210548F0023

Rear - R

1SDC210550F0023

6/26

ABB

Plug-in
circuit breaker

[mm/in]
Fixing on sheet

Fixed part

Moving part with terminal


covers, degree of protection
IP40

Overall dimensions with


cabled accessories mounted
(SOR-C, UVR-C, RC221222)

Overall dimensions with


cabled auxiliary contacts
mounted (only 3Q 1SY)

1SDC210552F0023

1SDC210551F0023

Caption

ABB

6/27

Overall dimensions
Tmax T5 (400 A)

Plug-in

[mm/in]

circuit breaker

1SDC210557F0023

Drilling templates of the compartment door

1SDC210555F0023

1SDC210556F0023

Flange for
compartment door

With flange

Without flange

Drilling templates for support sheet

1SDC210558F0023

1SDC210559F0023

For front terminals

3 POLES

4 POLES

1SDC210561F0023

1SDC210560F0023

For rear terminals

3 POLES

Rear 400 A

6/28

4 POLES

32.5
1.28

128.5
5.06

143
5.63

172.5
6.79

64.5
2.54

ABB

Terminals

[mm/in]

1SDC210562F0023

1SDC210563F0023

Extended front - EF

Front terminals for cables Cu

Front terminals for cables


Cu/Al

High terminal covers with


degree of protection IP40

1SDC210566F0023

Front for cables Cu and Cu/Al - FC Cu - FC Cu/Al

1SDC210567F0023

Caption

ABB

6/29

Overall dimensions
Tmax T5 (400 A)

Terminals

[mm/in]

1SDC210573F0023

1SDC210571F0023

1SDC210572F0023

Rear flat horizontal - HR

1SDC210574F0023

1SDC210575F0023

Rear vertical - VR

1SDC210576F0023

6/30

ABB

Draw out
circuit breaker

[mm/in]
Fixing on sheet

Caption

Moving part with terminal


covers, degree of protection
IP40

Lock for compartment door


(available on request)

Overall dimensions with


cabled accessories mounted
(SOR-C, UVR-C,
RC221-222)

1SDC210586F0023

1SDC210585F0023

Fixed part

1SDC210584F0023

isolating distance

ABB

6/31

Overall dimensions
Tmax T5 (400 A)

Draw out
Flange for compartment
door

Drilling templates of the compartment door

1SDC210591F0023

1SDC210590F0023

circuit breaker

[mm/in]

Drilling templates for support sheet

1SDC210592F0023

1SDC210593F0023

For front terminals

3 POLES

4 POLES

1SDC210595F0023

1SDC210594F0023

For rear terminals

3 POLES

Rear 400 A

6/32

4 POLES

32.5
1.28

128.5
5.06

143
5.63

172.5
6.79

64.5
2.54

ABB

Terminals

[mm/in]

1SDC210597F0023

1SDC210596F0023

Extended front - EF

Front terminals for copper


cables

Front terminals for copper/


aluminium cables

Terminals with degree of


protection IP40

1SDC210600F0023

Front for cables Cu and Cu/Al 400 A- FC Cu - FC Cu/Al

1SDC210601F0023

Caption

ABB

6/33

Overall dimensions
Tmax T5 (400 A)

Terminals

[mm/in]

1SDC210607F0023

1SDC210606F0023

1SDC210605F0023

Rear flat horizontal - HR

1SDC210609F0023

1SDC210608F0023

Rear flat vertical - VR

1SDC210610F0023

6/34

ABB

Overall dimensions
Isomax S6

Fixed circuit breaker

[mm/in]
Terminal covers
(to be ordered when not included in the supply)

low

high
2.5
0.10

12
0.47

241
9.49

161
6.34

268
10.55 125.25
4.93

2
0.08

111.75
4.40

107
4.21
101.5
4

3
0.12

(3 POLES)

47
1.85

(4 POLES)

210
8.27
140
= 5.51 =

105
4.13

104.75
4.12

279.5
11

1SDC210619F0023

16.5
0.65

152 =
5.98
Mounting on
Y
sheet metal

14
0.55

Caption

9
0.35

1SDC210618F0023

103.5
4.07
159
6.26

Flange for compartment door

Tightening torque 2 Nm

Template for drilling sheet metal support


(minimum thickness of sheet metal: 0.12/3 mm)
For terminals:
For rear Cu/Al cables terminals - RC For rear threaded terminals - R
Front - F
Front extended - EF
Front for Cu/Al cables - FC CuAl
Y

301
11.85

111.75
4.40
241
9.49

35
1.38

8
35 0.31 M5/ 5.5
1.38
0.22

8
0.31 M5/ 5.5
0.22

35
1.38

(3 POLES)
(4 POLES)

Y
147
5.79
=
=
115
4.53 =
=

6
=

112
4.41
142
5.59

7
0.28

=
1SDC210623F0023

241.5
9.51

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 0.08/2 mm)

85.75
3.38
1SDC210621F0023

1SDC210620F0023

171.5
6.75

ABB

105
4.13

M5/ 5.5
0.22
R21.5
R0.85

M5/ 5.5
0.22

35
1.38

70
2.76
70
70
2.76 2.76

1SDC210622F0023

141.75
5.58

109.75
4.32
237
9.33

35
1.38

237
9.33

70
70
70
2.76 2.76 2.76

(4 POLES)

237
9.33
109.75
4.32

(4 POLES)

4 POLES

111.75
4.40
241
9.49

(3 POLES)

109.75
4.32

70
2.76
140
5.51

3 POLES
(3 POLES)

237
9.33
109.75
4.32

70
2.76
140
5.51

6/35

Overall dimensions
Isomax S6

Terminals

[mm/in]
Front - F
41.5
1.63

47
1.85

53.5
2.11

40
1.57
6.5
0.26

1SDC210624F0023

8
0.31

67
2.64

50
1.97

20
0.79

14
0.55

22.5 0.1
0.89 0.04

23
0.91 5 min.
1SDC210625F0023

Front extended - EF

12
0.47

Threaded rear - R

Front extended spread - ES

(low terminal covers included in the supply)

116 45
4.57 1.77
22.5
0.89
23
0.91

49.5 8
20
13 1.95 0.31 0.79
0.51
116.5
4.59

90
3.54

4.57
22.5
0.89

70
70
70
2.76 2.76 2.76

2.5
0.10

73
2.87
44
1.73

M24x2

Front for Cu/Al cables - FCCuAl

For rear Cu/Al cables - FCCuAl

(IP20 high terminal covers included in the


supply)

(IP20 high terminal covers included in the


supply)

1SDC210627F0023

45 116
1.77 4.57

1SDC210626F0023

116 Y

59
2.32
42
1.65

16.75
0.66

17.5
0.69
12
0.47

1SDC210628F0023

25
0.98

20
0.79

6/36

ABB

Draw out

[mm/in]

circuit breaker
Y

Flange for compartment door

Lock for compartment door


(to order)

5.5
0.22
14.5
0.57

Tightening torque 9 Nm

167
6.57
190
7.48
195.5
7.70

2
0.08

(4 POLES)
(3 POLES)

196
7.72

Moving part

273
152 10.75
5.98

58
145 2.28
5.71 89.5
3.52
208
8.19
133
5.24
295
11.61

Fixed part

isolating distance

140
5.51

280
11.02 210
8.27
70
70
70
2.76
2.76
2.76

96
3.78
123.5
4.86
193.5
7.62

131
5.16
136.5
5.37

1SDC210629F0023

27.5
1.08

Caption

Template for drilling sheet metal


support

Template for drilling compartment


door and fitting flange

(minimum thickness of sheet metal: 0.12/3 mm)

(thickness of sheet metal: 0.08/2 mm)

ABB

(4 POLES)
(3 POLES)
(4 POLES)

1SDC210630F0023

107
4.21
214
8.43
284
11.18

45
1.77

Nr. 5 8
0.31

9
39
1.54 0.35

90
3.54
161
6.34

45.5
1.79
120
4.72

77.5
3.05

8.5 (M8)
0.33

==

7
19.75
0.28 16
0.78
0.63
101
3.98
162.5
6.40
121
4.76
R min 200
7.87

1SDC210631F0023

Y
170
6.69
80.5
3.17

(4 POLES)

177
6.97

(4 POLES

7
0.28

X
86.5
3.41

4
0.16

(3 POLES)

R2
R0.08

57.5
2.26

77.5
3.05

140
5.51
210
8.27
70
2.76

6/37

Overall dimensions
Isomax S6

Terminals

[mm/in]
Front for S6 - F

31
1.22
10
0.39

70
2.76
3
0.12

14
0.55

70
2.76

70
2.76

40
1.57

1SDC210632F0023

158
6.22

20
0.79

Horizontal or vertical rear flat bar for S6 - HR


80.5
3.17
20
0.79

14
0.55

40
1.57

3
0.12

10
0.39

1SDC210633F0023

6/38

ABB

Overall dimensions
Isomax S7

Fixed circuit breaker

[mm/in]

Caption

Terminal covers

70
2.76

(4 POLES)
(3 POLES)

70
2.76

7
0.28

177
6.97

217
8.54

7
0.28

140
5.51
3
0.12

37
1.46

105
4.13

161
6.34

138.5
5.45
140.5
5.53
146.5
5.77
214.5
8.44

1SDC210634F0023

406
15.98

low

1SDC210635F0023

70
2.76

210
8.27
152
5.98

30.5
1.20

Tightening torque 2 Nm
7
0.28

37
1.46

Flange for compartment door

326
12.83

280
11.02

2
0.08

Template for drilling sheet metal support

Template for drilling


compartment door and
fitting flange

(Minimum thickness of sheet metal: 0.12/3 mm)


For flat rear terminals - R
For terminals:
Front - F
Front extended - EF
Front for Cu/Al cables - FC CuAl

(thickness of sheet metal:


0.08/2 mm)
Y

3 POLES

4 POLES

147
= 5.79 =
115
4.53

(3 POLES)

290
11.42

3.6 H12
0.14

ABB

1SDC210636F0023

M5/ 5.5
0.22

5.5 - M5
0.22

5.5 - M5
0.22

7
0.28

1SDC210637F0023

R40
R1.57

140
5.51
70 70 70
2.76 2.76 2.76

50
1.97
80
3.15

171.5
6.75

= =

70 70
2.76 2.76

203
7.99
315
12.40

R40
R1.57

70
2.76

378
14.88

203
7.99
315
12.40
171.5
6.75

35
1.38

3.6 H12
0.14

378
14.88

378
14.88

203
7.99

220
8.66

1SDC210638F0023

112
4.41

(4 POLES)

50
1.97
80
3.15

140
5.51

142
5.59

Y
70
2.76

6/39

Overall dimensions
Isomax S7

Terminals

[mm/in]
Front extended - EF
Y

70
2.76
22
0.87

10 10 10
0.39 0.39 0.39
50
33.5
1.97 11 1.32
22
0.43
0.87

97
3.82

38
1.50

70
2.76
50
1.97

39
1.54

15
0.59

11
0.43

1SDC210640F0023

Front extended spreaded - ES

21.4
0.84

45
1.77

116
4.57

78
3.07
57
2.24

116 Y
4.57
22.5
0.89
90
23
3.54 0.91

116
45
4.57 1.77
22.5
0.89

50
1.97

15
0.59

13
0.51

1SDC210642F0023

1SDC210641F0023

30.5
1.20

107
4.21

37
1.46

70
2.76

1SDC210639F0023

22
0.87
22
0.87

Front for Cu/Al cables for S7 1250 - FC CuAl

Y 70
70
2.76
2.76

70
2.76

71
2.80
107
4.21

140
5.51

22
0.87

Front - F

Raer horizontal or vertical flat terminals - HR or VR

70
2.76

70
2.76

16
0.63

70
2.76

85
3.35

11
0.43
14
0.55

6/40

22
0.87

1SDC210643F0023

B
22
0.87

50
1.97

315
12.40

171.5
6.75

ABB

Draw out

[mm/in]

circuit breaker
Y

Caption
241.5
9.51

Fixed part

Tightening torque 9 Nm

8.25
0.32
=

196
7.72

211.25
8.32

Lock for compartment door


(to be ordered)

(3 POLES)

406
15.98

2
0.08

270
10.63

Flange for compartment door

143.25
5.64

3
0.12

max

Moving part

(4 POLES)

210
8.27
140
5.51

160
6.30

140
5.51

280
11.02

27.5
1.08

96
3.78
123.5
4.86
193.5
7.62

218.5
8.60
247
9.72

isolating stroke

Template for drilling sheet metal


support or channel

Template for drilling compartment


door and fitting flange

(Minimum thickness of sheet metal: 0.12/3 mm)

(thickness of sheet metal: 0.08/2 mm)


4
0.16

Y
140
5.51
210
8.27

(3 POLES)

Y
170
6.69
80.5
3.17

(4 POLES)

70
2.76

==

45
1.77

9
39
1.54 0.35
177
6.97

161
6.34

107
4.21
(3 POLES)
(4 POLES)

1SDC210645F0023

214
8.43
284
11.18

Nr.5 8
0.31

19.75
0.78
101
3.98
162.5
6.40
121
4.76
R min. 200
7.87

16
0.63

7
0.28

1SDC210646F0023

8.5 (M8)
0.33

X
120
4.72

68.25
2.69

92.5
3.64

90
3.54

120.5
4.74

7
0.28

120.5
4.74

76
2.99

ABB

131
5.16
136.5
5.37

1SDC210644F0023

5.5
0.22

6/41

Overall dimensions
Isomax S7

Terminals

[mm/in]
Front - F
3
0.12

70
2.76

50
1.97
22
0.87

11
0.43

1SDC210647F0023

22
0.87

67
2.64

31
1.22
16
0.63

70
2.76

14
0.55

Y
70
2.76

Rear horizontal or vertical flat terminals - HR or VR


108
4.25
3
0.12
50
1.97

22
0.87

14
0.55

143.25
5.64

11
0.43

22
0.87

70
2.76

70
2.76

70
2.76

1SDC210648F0023

16
0.63

6/42

ABB

Overall dimensions
Isomax S8

Fixed circuit breaker

[mm/in]
380
14.96

120
4.72

150
5.91

120
4.72

236.5
9.31
=

Template for drilling


compartment door and
fitting flange

(Minimum thickness of sheet metal: 0.12/3 mm)

(Minimum thickness of sheet


metal: < 0.10/2.5 mm)
506
19.92

356
14.02
178
7.01

190
7.48

135
5.31

344
13.54

327
12.87

5
0.20

1SDC210650F0023

190
7.48
380
14.96

280
11.02

Nr. 8 9
0.35

20
0.79

161
6.34

280
11.02

309
12.17

161
6.34
309
12.17
161
6.34

0
R1 .39
R0

16

Nr. 8 9
0.35

R. min. 300
11.81

0.

0
R1 .39
R0

R
R0 10
.3
9

R
R0 10
.3
9

161
6.34

20
0.79

178
7.01

20
0.79

Minimum radius of rotation of


compartment door

20
0.79

286.5
11.28

4 POLES

Template for drilling sheet metal support

Hole for rear terminals only

Y
3 POLES

Caption

120
4.72
203
7.99

1SDC210649F0023

15
0.59

120
4.72

280
11.02
400
15.75

406
15.98

341
13.43

530
20.87

3 POLES

4 POLES

Terminals

[mm/in]
Front - F

Rear - R

20
0.79

20
0.79

40
= 1.57

40
1.57

80
3.15

324
12.76

120
4.72
115
4.53
85
3.35

6
65
2.56

40
1.57

80
3.15

150
5.91

120
120
4.72 Y 4.72

= 15

0.59
20
0.79 40
1.57
15
0.59
20
0.79

20
0.79

1SDC210651F0023

120
120
4.72 Y 4.72

20
0.79

40
= 1.57 =

15
0.59

150
5.91

65
2.56

40
1.57

20
0.79

80
3.15

324
12.76

20
0.79

ABB

20
0.79

Internal side of compartment


door

20
0.79

280
11.02

Circuit breaker mounting holes

2.5
0.10

242
9.53

20
0.79

400
15.75

Flange for compartment door

313
12.32

556
21.89

20
0.79

Caption

6/43

Overall dimensions
T1, T2 and T3 with residual current release - RC221/RC222

[mm/in]
Caption
Depth of the switchboard
with circuit breaker face
extending

Depth of the switchboard


with circuit breaker face
flush with door

Front terminals for cable


connection

Low terminal covers with


degree of protection IP40

Insulating plate

Front - F, fixing on sheet

1SDC210164F0003

T1

1SDC210165F0003

T2

T3

1SDC210166F0003

222
8.74

222
8.74

6/44

ABB

[mm/in]

Flange for the compartment door


T1

T2

T3

3 POLES

4 POLES

Drilling template for fixing sheet


T1 - T2 - T3
4 POLES

1SDC210655F0023

3 POLES

ABB

T1

124
4.88

107
4.21

53.5
2.11

78.1
3.07

25
0.98

53.1
2.09

T2

124
4.88

107
4.21

53.5
2.11

90
3.54

30
1.18

60
2.36

T3

141.5
5.57

122
4.80

61
2.40

102.5
4.04

35
1.38

67.5
2.66

6/45

Overall dimensions
T1, T2 and T3 with residual current release - RC221/RC222

[mm/in]

Drilling templates of the compartment door


Without flange
face extending

Without flange
face not extending

With flange
face not extending

T1

T1 - T2 - T3

3 POLES
T1 - T2 - T3

T2 - T3

4 POLES
T1 - T2 - T3

T1 - T2 - T3

1SDC210656F0023

T1 - T2 - T3

T1

18
0.71

108.2
4.26

94.1
3.70

23.5
0.93

113
4.45

78.1
3.07

39.1
1.54

T2

18
0.71

122
4.80

106
4.17

76
2.99

23.5
0.93

120
4.72

90
3.54

46
1.81

T3

13.5
0.53

137
5.39

118.5
4.67

83.5
3.29

19
0.75

127.4
5.02

102.5
4.04

53.5
2.11

6/46

ABB

Overall dimensions
T4 and T5 with residual current release - RC221/RC222

Fixed version

[mm/in]
Front - F, fixing on sheet

T4

1SDC210660F0023

1SDC210659F0023

1SDC210658F0023

1SDC210657F0023

T5 (400 A)

Caption

Flange for the


compartment door

Drilling templates of compartment door


and fitting flange

For residual current


release

For circuit breakers

With flange

1SDC210664F0023

1SDC210663F0023

1SDC210662F0023

Overall dimensions with


cabled auxiliary contacts
mounted (only 3Q 1SY)

1SDC210661F0023

Without flange

Drilling templates for support sheet


T4

T5

ABB

1SDC210666F0023

1SDC210665F0023

6/47

Overall dimensions
T4 and T5 with residual current release - RC221/RC222

Plug-in version

[mm/in]
Front - F, fixing on sheet

T4

1SDC210670F0023

1SDC210669F0023

1SDC210668F0023

1SDC210667F0023

T5 (400 A)

Caption
1

Fixed part

Mobile part

Overall dimensions with cabled auxiliary contacts mounted (only 3Q 1SY)

For residual current


release

With flange

1SDC210674F0023

1SDC210673F0023

For circuit breakers

Drilling templates of compartment door and fitting flange

1SDC210672F0023

1SDC210671F0023

Flange for the compartment door

Without flange

Drilling templates for support sheet


T4

6/48

1SDC210676F0023

1SDC210675F0023

T5

ABB

Overall dimensions
Accessories for Tmax T1 - T2 - T3

[mm/in]

Solenoid operator superimposed


T2

1SDC210679F0023

1SDC210678F0023

1SDC210677F0023

T1

Caption

T3

Depth of the switchboard


with operating mechanism
face extending

Depth of the switchboard


with operating mechanism
face flush with door

Low terminal covers with


degree of protection IP40

Insulating plate

1SDC210681F0023

1SDC210680F0023

Drilling templates of the compartment door

T1

33.5
1.32

18
0.71

23.5
0.93

T2

33.5
1.32

18
0.71

23.5
0.93

T3

29
1.14

13.5
0.53

19
0.75

ABB

1SDC210683F0023

1SDC210682F0023

Flange for compartment door

Without flange
Operating mechanism face
extending

Without flange
Operating mechanism face
flush with door

With flange
Operating mechanism face
flush with door

6/49

Overall dimensions
Accessories for Tmax T1 - T2 - T3

[mm/in]

Heights for door with maximum distance

470.5
18.52

1SDC210685F0023

1SDC210684F0023

Rotary handle operating mechanism on the compartment door

Caption
Transmission unit

Rotary handle operating


mechanism on the compartment door

Insulating plate
A

T1-T2

28
1.10

14
0.55

T3

32.5
1.28

9.5
0.37

with
7.01 with

1SDC210686F0023

60.5
2.38

with
with

Heights for door with minimum distance

Drilling template of the compartment door

1SDC210687F0023

6/50

Minimum rotation radius for


door fulcrum

ABB

[mm/in]

Rotary handle operating mechanism on circuit breaker


Rotary handle operating
mechanism on circuit
breaker

Insulating plate

T1-T2

67.7
2.67

28
1.10

53.2
2.09

60.5
2.38

T3

63.2
2.49

32.5
1.28

48.7
1.92

56
2.20

1SDC210689F0023

1SDC210688F0023

Caption

Drilling template of the compartment door

1SDC210690F0023

1SDC210691F0023

Drilling: see detail A

Flange for the compartment

1SDC210692F0023

ABB

6/51

Overall dimensions
Accessories for Tmax T1 - T2 - T3

[mm/in]

Mechanical interlock between circuit breakers


Front interlocking plate between two circuit breakers

1SDC210693F0023

305
12.01

Caption
Drilling templates of the
compartment door

Drilling templates for support sheet

Insulating plate

1SDC210694F0023

1SDC210695F0023

307
12.09

Front interlocking plate among three circuit breakers

1SDC210696F0023

470
18.5

6
C

T1

52.5
2.07

77.5
3.05

112.5
4.43

87.5
3.44

53.5
2.11

53.5
2.11

T2

50
1.97

80
3.15

115
4.53

85
3.35

53.5
2.11

53.5
2.11

T3

47.5
1.87

82.5
3.25

117.5
4.63

82.5
3.25

56.5
2.22

65.5
2.58

6/52

472
18.52

1SDC210698F0023

1SDC210697F0023

ABB

Overall dimensions
Accessories for Tmax T4 - T5

Fixed version
Caption

[mm/in]

Rotary handle assembly with


door lock device

Padlock device for open


position (maximum 3
padlocks to be provided by
the user)

IP54 protection (supplied on


request)

Minmax distance from the


front of the door without
accessory 4

Minmax distance from the


front of the door with
accessory 4

Dimension with AUE


connector (early making
contact)

1SDC210700F0023

Transmission unit

Drilling of compartment door

1SDC210702F0023

1SDC210701F0023

1SDC210699F0023

Rotary handle operating mechanism on the compartment door

Minimum rotation radius for door


fulcrum

Rotary handle operating mechanism on circuit breaker

Caption

Det. A

Dimension with AUE


connector (early making
contact)

Compartment door lock

Det. A
1SDC210705F0023

Padlock device for open


position (maximum 3
padlocks to be provided by
the user)

ABB

Flange for the


compartment door

1SDC210707F0023

1SDC210706F0023

Drilling template of the compartment door

1SDC210708F0023

1SDC210704F0023

Rotary handle operating


mechanism on circuit breaker

1SDC210703F0023

6/53

Overall dimensions
Accessories for Tmax T4 - T5

Fixed version

T4

T5

1SDC210710F0023

Drilling template of the compartment door

1SDC210713F0023

1SDC210712F0023

Flange for the


compartment door
(supplied as standard)

1SDC210711F0023

Overall dimensions with


cabled auxiliary contacts
mounted (only 3Q 1SY)

1SDC210709F0023

Motor operator

With flange

1SDC210714F0023

Caption

[mm/in]

Without flange

Drilling template for support sheet


T5

3 POLES

6/54

4 POLES

3 POLES

1SDC210718F0023

1SDC210716F0023

1SDC210715F0023

1SDC210717F0023

T4

4 POLES

ABB

[mm/in]
Caption

Front for lever operating mechanism

Front for lever operating


mechanism

Lock for the compartment


door (supplied on request)

T4

T5

Flange for the


compartment door
(supplied as standard)

1SDC210721F0023

1SDC210719F0023

1SDC210720F0023

Det. A

Drilling template for the compartment door


For drilling see detail A

1SDC210724F0023

1SDC210723F0023

1SDC210722F0023

1SDC210725F0023

Det. A

With flange

Without flange

Drilling template for support sheet

ABB

T4

35
1.38

70
2.76

17.5
0.69

T5

46.5
1.83

93
3.66

23.25
0.92

1SDC210726F0023

1SDC210727F0023

6
3 POLES

4 POLES

6/55

Overall dimensions
Accessories for Tmax T4 - T5

Fixed version
Caption
Interlocking mechanism

Circuit breaker coupling plate

Interlock between two circuit breakers placed side by side

1SDC210729F0023

1SDC210728F0023

[mm/in]

Caption

Drilling templates for fixing the circuit breaker on the support sheet

Drilling template for all


versions with rear terminals

1SDC210730F0023

6/56

ABB

[mm/in]

1SDC210733F0023

1SDC210732F0023

1SDC210731F0023

Interlock between two circuit breakers placed side by side

1SDC210735F0023

1SDC210736F0023

1SDC210734F0023

Type

Circuit breakers

N 1 T4 (F-P-W)
N 1 T4 (F-P-W)

N 1 T4 (F-P-W)

N 1 T4 (F-P-W)
N 1 T5/600* (P-W)

N 1 T5/400 (F-P-W) or T5/600* (F)


N 1 T5/400 (F-P-W) or T5/600* (F)

N 1 T5/400 (F-P-W) or T5/600* (F)


N 1 T5/600* (P-W)

N 1 T5/600* (P-W)
N 1 T5/600* (P-W)

N 1 T5/400 (F-P-W) or T5/600* (F)

Note:
(F) Fixed circuit breaker
(P) Plug-in circuit breaker
(W) Draw out circuit breaker
* Please ask ABB for 600 A availability

ABB

6/57

Overall dimensions
Accessories for Tmax T4 - T5

Draw out
version

[mm/in]

Motor operator
T4

T5 (400 A)

Flange for the


compartment door
(supplied as standard)

1SDC210739F0023

1SDC210738F0023

1SDC210737F0023

isolating distance

1SDC210742F0023

1SDC210741F0023

Drilling templates for the compartment


door and fitting flange

6/58

ABB

[mm/in]

Rotary handle operating mechanism on the circuit breakers


Caption
Padlock device for open
position (maximum 3
padlocks to be provided by
the user)

Lock for compartment door


(supplied on request)

Det. A

Dimension with AUE


connector (early making
contact)

1SDC210744F0023

1SDC210745F0023

1SDC210743F0023

isolating distance

Flange for the


compartment door

Drilling template for compartment


door and fitting flange
For drilling
1SDC210743F0023

see detail A

1SDC210747F0023

1SDC210746F0023

Det. A

ABB

6/59

Overall dimensions
Accessories for Isomax S6

[mm/in]

Drilling template for all versions


with rear terminals

Dimensions with draw out version mounted on right

46
1.81

R30
R1.18

10.5
0.41

9
0.35

Tightening torque 9 Nm

525
20.67

4
2

1SDC210748F0023.

288
11.34

103.5 65
4.07 2.56

Note See the various different versions for the dimensions of


the circuit breakers

284
11.18

350
13.78

Drilling template for mounting


circuit breaker on sheet metal

375
14.76

Y
=
650
25.59
= 70 70 70 120
70 70 70 =
2.76 2.76 2.76 4.72 2.76 2.76 2.76
=

101 129 101


3.98 5.08 3.98
331
13.03

Interlock device

273
10.75

Interlock between two horizontally-installed circuit breakers

13.5
0.53

Caption

Caption
1

Interlock between two vertically-installed circuit breakers

Interlock device

Drilling template for mounting


circuit breaker on sheet metal

Drilling template for all versions


with rear terminals

27.5
1.08

isolating distance

Y
51.5 70 70 70 48.5
2.03 2.76 2.76 2.76 1.91

=
=

9
0.35

273
10.75

Note See the various different versions for the dimensions of


the circuit breakers

R20
R0.79
280
11.02

26
1.02

109 129 109 101 109 129 109


4.29 5.08 4.29 3.98 4.29 5.08 4.29
779
30.67

525
20.67

Tightening torque 9 Nm

273
10.75

26
1.02

175
6.89

Dimensions with draw out version mounted on right

820
32.28

293
11.54

310
12.20

6/60

17
0.67
=

65
2.56

288
11.34

27.5
1.08

isolating distance

1SDC210749F0023

ABB

[mm/in]

Motor operator for fixed circuit breaker


2
0.08
23.5
0.93

81.250.1
3.200.004

Y
19.75
0.78

304
11.97

125.25
4.93

102.25
4.03

111.75
4.40

R8
R0.31

94.75
3.73

22.75
0.90

67
2.64

174
6.85

1220.1
R. min. 200 4.800.004
R. min. 7.87

96.5
3.80

140 =
5.51
215.5
8.48
285.5
11.24
=

1SDC210750F0023

338
13.31

270
10.63
192.25
7.57

8
0.31

81.250.1
3.200.004

319
12.56

159.5
6.28

91.5
3.60

198.5
7.81

72.25
2.84

Y
222.5
8.76

Caption
1

Flange for compartment door

Template for drilling compartment door

Dimensions with connectors

Note See the various different versions for the dimensions of


the circuit breakers

Motor operator for draw out circuit breakers


Y
222.5
8.76

81.250.1
3.200.004

Y
19.75
0.78

304
11.97

338
13.31

186.5
7.34

8
0.31

270
10.63

81.250.1
3.200.004

304

100.5
3.96

22.75
0.90

174
6.85
1220.1
R. min. 200 4.800.004
R. min. 7.87

23.5
0.93
2
0.08

= 140

247.5
9.74

5.51

Caption

ABB

108
4.25

117.5
4.63

1SDC210751F0023

91.5
3.60

159.5
6.28 319
12.56

isolating distance

72.25
2.84

27.5
1.08

Flange for compartment door

Template for drilling compartment door

Note See the various different versions for the dimensions of


the circuit breakers

6/61

Overall dimensions
Accessories for Isomax S6

[mm/in]

152
5.98
140
5.51

Lock for compartment door


(to order)
Drilling of compartment door

Flange for compartment door

Tightening torque 2 Nm

103.5
4.07

2
44.5 22
0.08 1.75 0.87
37
1.46

4
16
45
1.77
2.75
0.11
90
3.54

104.75
5.54

196
7.72

Rotary handle operating


mechanism on circuit breaker

140
5.51

Rotary handle operating mechanism on fixed circuit breaker

177
6.97
147
5.79

Caption

7
28

Note See the various different versions for the dimensions of


the circuit breakers

115
4.53
147
5.79
R. min. 200
R. min. 7.87

42.5
1.67

Drilling only required for version with rear terminals

Padlock device (maximum 3


padlocks max 0.24/6 mm
to be provided by customer
only for circuit breaker open
position)

2.8319.92/72...506 mm
(with IP54 protection min. 96)

Distance 6 -0.16/-4 mm
(shaft length)

63
2.48
19
0.75

22
0.87

1SDC210752F0023

241
9.49

41.5 Y
1.63

5
0.20

28
1.10

33
1.30

2
0.08

27
1.06

54
2.13

168
6.61

R min 200
R min 7.87

4
R min 200
R min 7.87

Drilling only required for version with rear terminals

8
0.31
M5/ 5.5
0.22

70
70
2.76 2.76

35
1.38

Y
70
70
70
2.76 2.76 2.76

104
4.09

237
9.33

70
2.76

106
4.17

4 POLES

241
9.49

104
4.09

237
9.33

3 POLES

105
4.13

35
1.38

133
5.24

Note See the various different versions for the dimensions of


the circuit breakers

6/62

106
4.17

104
4.09

23
0.91

133
5.24

Drilling template for mounting


circuit breaker on sheet metal

103.5
4.07

Minimum radius of rotation for


fulcrum of door

Y
105
4.13
41.5 31
1.63 1.22

237
9.33

Compartment door-mounted rotary handle mechanism with adjustable depth


for fixed circuit breaker

8
0.31
M5/ 5.5
0.22

35
1.38

X
1SDC210753F0023

35
1.38

46
1.81

Rotary handle assembly with


door lock device

8
0.31
M5/ 5.5
0.22

35
1.38

241
9.49

35
1.38

106
4.17

Transmission assembly

105
4.13

133
5.24

70
70
2.76 2.76

105
4.13
36 28
1.42 1.10

241
9.49

70
2.76

8
0.31
M5/ 5.5
0.22

Caption

70
70
70
2.76 2.76 2.76

4 POLES

106
4.17

104
4.09

133
5.24

237
9.33

3 POLES

ABB

[mm/in]
Caption

Padlock device for open position (maximum 3 padlocks


max. 0.24/6 mm to be provided by user)

45
1.77

Nr. 5 8
0.31

9
0.35
39
1.54
19.75
0.78
101
3.98
162.5
6.40
121
4.76
R. min. 200
R. min. 7.87
Y

91.5
3.60
123.5
4.86

37
1.46

222.5
8.76

131
5.16
136.5
5.37

42.5
1.67

Front flange for operating lever mechanism


Y

Front flange for operating lever


mechanism

Lock for compartment door (to


order)

Drilling of compartment door

Flange for compartment door

Tightening torque 2 Nm

104.75
4.12

152
5.98
140
5.51

103.5
4.07

37
1.46

2
0.08
4
0.16

Y
=
=
=

=
=

115

147
= 5.79 =
Y

1
42.5
1.67

= 4.53 =

3 POLES

75
2.95
40
1.57

70
70
2.76 2.76

70
70
70
2.76 2.76 2.76

Line
In

115
4.53

185
7.28
77
3.03
49
1.93

100 A
160 A
200 A
250 A
320 A
400 A

Load

X
6
5
1

1SDC210755F0023

241
9.49

8
0.31
M5/ 5.5
0.22

106
4.17

237
9.33
133
5.24 104
4.09

35
1.38

10
0.39

25
0.98

35
1.38

105
4.13

115
4.53
52.5
2.07

25
0.98

133
5.24

4 POLES

External neutral

241
9.49

70
2.76

104
4.09

237
9.33

106
4.17

Drilling only required for version


with rear terminals

8
0.31
M5/ 5.5
0.22

2.75
0.11

7
0.28

Note See the various different versions for the dimensions of


the circuit breakers

177
6.97
147
5.79

140
5.51

196
7.72

45
1.77

90
3.54

Caption

ABB

==

151
5.94

Note See the various different versions for the dimensions of


the circuit breakers

Y
170
6.69
80.5
3.17

1SDC210754F0023

4
0.16

22
0.87

177

Lock for compartment door (to


order)

2 44.5
0.08 1.75

90
3.54
161
6.34

Y
210
8.27

= 6.97 =

Rotary handle on circuit


breaker

196
7.72

Rotary handle operating mechanism on draw out circuit breaker

35
1.38

11
0.43

6/63

Overall dimensions
Accessories for Isomax S7

[mm/in]

Drilling template for all versions


with rear terminals

Dimensions with draw out version mounted on right

Tightening torque 9 Nm

5.5
0.22

9
0.35

40
1.57

550
21.65

40
1.57

1SDC210756F0023

336
13.23

140.5
5.53

6.5
0.26

65
2.56

7
0.28

9
.7
R0

420
16.54

406
15.98
450
17.72
=

Note See the various different versions for the dimensions of


the circuit breakers

6.5
0.26

300
11.81

407
16.02

300
11.81

Y
30
1.18

115
4.53

Drilling template for mounting


circuit breaker on sheet metal

117
4.61

Y
660
25.98
70 70 70 120 70 70 70
= 2.76 2.76 2.76 4.72 2.76 2.76 2.76 =

115
4.53

Interlock device

R
20

Interlock between two horizontally-installed circuit breakers

7
0.28

Caption

Drilling template for mounting


circuit breaker on sheet metal

Drilling template for all versions


with rear terminals

Tightening torque 9 Nm

Y
315
12.40

1
=

290
11.42=

7
0.28

875
34.45

7
0.28

408
16.06

166
6.54

1100
43.31

Note See the various different versions for the dimensions of


the circuit breakers

R30
R1.18

9
0.35

406
15.98
=

70 70

70

= 2.76 2.76 2.76 =

340
13.39

6/64

65
2.56

336
13.23

27.5
1.08

isolating distance

1SDC210757F0023

7
0.28

994
39.13

115
4.53

Interlock device

7
0.28

Interlock between two vertically-installed circuit breakers

406
15.98

Caption

27.5
1.08

isolating distance

ABB

[mm/in]

Motor operator for fixed circuit breaker

231.5
9.11

81.250.1
3.200.004

23.5
0.93

81.250.1
3.200.004
19.75
0.78

R8
R0.31

22.75
0.90

174
6.85
1220.1
4.800.004
R. min. 200
7.87

2
1SDC210758F0023

91
3.58

215.5
8.48
285.5
11.24

72.25
2.84

304
11.97

108.25
4.26

98.75
3.89

91.25
3.59

270
10.63

338
13.31

195.75
7.71

217
8.54

Nr. 7 8
0.31

319
12.56

7
0.28

2
0.08

159.5
6.28

Y
222.5
8.76
91.5
3.60
140
= 5.51 =

Caption
1

Flange for compartment door

Template for drilling compartment doorl

Dimensions with connectors

Note See the various different versions for the dimensions of


the circuit breakers

Motor operator for draw out circuit breaker


Y

isolating distance
7
0.28

81.250.1
3.200.004

72.25
2.84
R8
R0.31

97
3.82

104.5
4.11

114
4.49

304
11.97

338
13.31

190
7.48

270
10.63

Nr. 7 8
0.31

211.25
8.32

81.250.1
3.200.004
19.75
0.78

22.75
0.90
174
6.85

319
12.56

222.5
8.76
91.5
3.60
140
= 5.51 =

159.5
6.28

27.5
1.08

23.5
0.93

2
0.08

295.5
11.63

Caption

ABB

Flange for compartment door

Template for drilling compartment door

1SDC210759F0023

1220.1
4.800.004
R. min. 200
7.87
Y

Note See the various different versions for the dimensions of


the circuit breakers

6/65

Overall dimensions
Accessories for Isomax S7

[mm/in]

Rotary handle operating mechanism on fixed circuit breaker

=
=

Flange for compartment door

70
2.76
70 70
2.76 2.76

35
1.38
70 70 70
2.76 2.76 2.76
140
5.51

Rotary handle assembly with


door lock device

R40
R1.57

Compartment door-mounted rotary handle operating mechanism for fixed


circuit breaker
Y

41.5
1.63

Padlock device (maximum 3


padlocks max 0.24/6 mm
to be provided by customer
only for circuit breaker open
position)

Template for drilling compartment door

Drilling template for mounting


circuit breaker on sheet metal

105
4.13

28
1.10

211.25
8.32
X

90

27
1.06
54
2.13
R. min. 200
7.87

8
205
8.07

R. min. 200
7.87

Drilling only required for version with rear terminals


3 POLES

- 0.16/4 mm

Note See the various different versions for the dimensions of


the circuit breakers

33
1.30

50
1.97

6 4 POLES
378
14.88
197.25
7.77
315
12.40
165.75
6.53

Distance 7
(shaft lenght)

5
0.20

197.25
7.77
315
12.40
165.75
6.53

2
0.08

378
14.88

2.8319.92/72 ... 506 mm


(with IP54 protection min. 96)

41.5
1.63

23
0.91

63 22
2.48 0.87

31
1.22

36
1.42

Minimum radius of rotation for


fulcrum of door

105
4.13

19
0.75

105
4.13

5.5 - M5
0.22

70
2.76
70 70
2.76 2.76
5.5 - M5
0.22

220
8.66
Y

3.6 H12
0.14

80
3.15

R40
R1.57

35
1.38
70 70 70
2.76 2.76 2.76
140
5.51

R40
R1.57

290
11.42
Y

50
1.97

X
5.5 - M5
0.22
3.6 H12
0.14

1SDC210761F0023

28
1.10

Transmission assembly

50
1.97

4 4 POLES

1SDC210760F0023

50
1.97

406
15.98

Drilling only required for version with rear terminals


3 POLES

R40
R1.57

Caption

147
= 5.79 =
R. min. 200
7.87
Y

42.5
1.67

152
5.98

5.5 - M5
0.22

6/66

115

= 4.53 =

Tightening torque 2 Nm

2.75
0.11

7
0.28

Note See the various different versions for the dimensions of


the circuit breakers

46
1.81

45
1.77

378
14.88
197.25
7.77
315
12.40
165.75
6.53

90
3.54

Drilling template for mounting


circuit breaker on sheet metal

80
3.15

4
0.16

147
5.79

Drilling of compartment door

37
140.5 1.46
5.53

211.25
8.32

140
= 5.51 =

406
15.98

Lock for compartment door


(to order)

105
4.13

196
7.72
140
5.51

2 44.5 22
0.08 1.75 0.87

Rotary handle operating


mechanism on circuit breaker

378
14.88
197.25
7.77
315
12.40
165.75
6.53

177
6.97

Caption

ABB

[mm/in]

45
1.77

Note See the various different versions for the dimensions of


the circuit breakers

2
0.08

Y 105

4.13
=

140
5.51

36
1.42

140.5
5.53

4
0.16

2.75
0.11

Flange for compartment door

7
0.28

Tightening torque 2 Nm

115

= 4.53 =

147
= 5.79 =
42.5
1.67

152
5.98

Drilling only required for


version with rear terminals

50
1.97

External neutral

4
70
2.76
70 70
2.76 2.76

75
2.95
40
1.57

X
5.5 - M5
0.22

185
7.28
77
3.03
49
1.93

160 A

200 A
250 A
320 A
400 A

Line
In
100 A

Load

5.5 - M5
0.22

11
0.43

1SDC210763F0023

X
4

378
14.88
197.25
7.77
315
12.40
165.75
6.53

50
1.97

R40
R1.57

10
0.39

4 POLES

35
1.38
70 70 70
2.76 2.76 2.76
140
5.51

52.5
2.07

25
0.98

=
=

R40
R1.57

115
4.53

3 POLES
378
14.88
197.25
7.77
315
12.40
165.75
6.53

Note See the various different versions for the dimensions of


the circuit breakers

ABB

45
1.77

Front flange for operating lever mechanism

90
3.54

Drilling template for mounting


circuit breaker on sheet metal

42.5
1.67

115
4.53

211.25
8.32

Drilling of compartment door

37
1.46

131
5.16
136.5
5.37

406
15.98

222.5
8.76

16
19.75
0.63
0.78
101
3.98
162.5
6.40
121
4.76
R. min. 200
7.87
Y

196
7.72
140
5.51

Lock for compartment door (to


order)

=
=

Front flange for lever operating


mechanism

Nr. 7 7
0.28

9
0.35

91.5
3.60
123.5
4.86

==

1SDC210762F0023

Caption

Y
170
6.69
80.5
3.17

25
0.98

Padlock device for open position (maximum 3 padlocks


max. 0.24/6 mm to be provided by user)

90
3.54
161
6.34

211.25
8.32

Lock for compartment door


(to order)

4
0.16

2 44.5 22
2 0.08 1.75 0.87

196
7.72

Y
210
8.27

177
6.97

Rotary handle operating


mechanism on circuit breaker

406
15.98

Rotary handle operating mechanism on draw out circuit breaker

177
6.97
147
5.79

Caption

6/67

Overall dimensions
Accessories for Isomax S8

[mm/in]

40
1.57
80
3.15
120
4.72

15
0.59
110
4.33
122
4.80

1SDC210764F0023

15
0.59

70
2.76

160
6.30
200
7.87

External neutral

6/68

ABB

Overall dimensions
Distances to be respected - Tmax

[mm/in]

Insulation distances for installation in metallic cubicle


A
[mm/in]

B
[mm/in]

C
[mm/in]

T1

25/0.98

20/0.79

20/0.79

T2

25/0.98

20/0.79

20/0.79

T3

50/1.97

25/0.98

20/0.79

T4

30*/1.18*

25/0.98

25*/0.98*

T5

30*/1.18*

25/0.98

25*/0.98*

For Ub 440 V: distance A 60 mm (2.36 inches);


distance C 45 mm (1.77 inches)

1SDC210765F0023

(*)

Minimum centre distance between two circuit breakers side by side or superimposed
For assembly side by side or superimposed, check that the connection busbars or cables do not reduce the
air insulation distance
Minimum centre distance for two circuit breakers side by side
Centre distance I [mm/in]

3 poles

4 poles

3 poles

4 poles

T1

76/2.99

102/4.02

76/2.99

102/4.02

T2

90/3.54

120/4.72

90/3.54

120/4.72

T3

105/4.13

140/5.51

105/4.13

140/5.51

T4

105/4.13

140/5.51

105/4.13

140/5.51

T5

140/5.51

184/7.24

140/5.51

184/7.24

1SDC210766F0023

Circuit breaker width [mm/in]

Minimum centre distance for superimposed circuit breakers


Caption

H [mm/in]

Connection - not insulated

T1

Insulated cable

T2

90/3.54

Cable terminal

T3

140/5.51

T4

160/6.30

T5

160/6.30

Note: The dimensions shown apply for operating


voltage Ub up to 690 V. The dimensions to be
respected must be added to the maximum
dimensions of the various different versions of
the circuit breakers, including the terminals.

ABB

6
1SDC210767F0023

60/2.36

6/69

Overall dimensions
Distances to be respected - Isomax

[mm/in]

Insulation distances for installation in metal compartment with wall to chassis


ground or wall to chassis ground protected with insulating plate
Wall to chassis ground [mm/in]
B

S6

35
1.38

100
3.94

25
0.98

20
0.79

S7

50
1.97

100
3.94

30
1.18

20
0.79

S8

200
7.87

200
7.87

30
1.18

120
4.72

off

(*) These distances are valid for operating voltages of > 440 V and for
circuit breakers with breaking capacity level L

1SDC210768F0023

A
A(*)
(Ub 415 V) (Ub 440 V)

Insulation distances for installation in insulated compartment


Insulated wall [mm/in]
B

S6

35
1.38

10
0.39

20
0.79

S7

50
1.97

10
0.39

20
0.79

S8

120
4.72

15
0.59

120
4.72

The dimensions shown apply for operating voltages Ub of up to


690 V.
The dimensions to be respected must be added to the maximum
dimensions of the various different versions of the circuit breakers, including
the terminals.

6/70

ABB

[mm/in]

Minimum distance between centres for two horizontally or vertically-installed


circuit breakers
For horizontal or vertical installation, make sure that the connection busbars or cables dont reduce the air
insulation distances.

Minimum distance between centres for horizontally-installed circuit breakers


Circuit breaker
width [mm/in]

I
[mm/in]

3 poles

4 poles

3 poles

4 poles

S6

210
8.27

280
11.02

210
8.27

280
11.02

S7

210
8.27

280
11.02

210
8.27

280
11.02

S8

435
17.13

585
23.03

435
17.13

585
23.03

(*) these are the distances to be respected for circuit breakers fitted
with a flange for the compartment door or side conductor outlets.
Y

on

on

off

off

l
Y

1SDC210769F0023

The distances between centres are for the installation of fixed


and plug in circuit breakers. When installing draw out S6 or S7
circuit breakers you should also take into account the dimensions of the metal supporting channel that needs to be fitted
between the guides of the fixed parts of two adjacent circuit
breakers.

Minimum distance between centres for vertically-installed circuit breakers


H [mm/in]
180
7.09

S7

180
7.09

S8

300
11.81

3
H

1SDC210770F0023

S6

1
2
3
ABB

Connection not insulated


Insulated cable
Cable terminals
6/71

ABB Inc.
1206, Hatton Road
Wichita Falls, TX 76302 - U.S.A.
Tel.: (888) 385-1221 - (940) 397-7000
Fax: (940) 397-7001

ABB Inc.
3299, boul. J.B. Deschamps
Lachine, QC H8T 3E4 - CANADA
Tel.: (514) 420-3100
Fax: (514) 420-3137

www.abb-control.com

www.abb.ca

1SDC210003D0202 - 09/2003
Printed in Italy
2000 - CAL

Due to possible developments of standards as well as of


materials, the characteristics and dimensions specified in the
present catalogue may only be considered binding after
confirmation by ABB Inc.