Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

VSI Vs CSI

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)

ISSN: 2278-1676 Volume 2, Issue 6 (Sep-Oct. 2012), PP 06-13


www.iosrjournals.org

Comparative Evaluation of VSI and CSI based Unified Power


Quality Conditioner
K.Vadirajacharya1, Pramod Agarwal2, H.O.Gupta3
(1.Electrical EnggDept, Dr.BATU,Lonere, India)
(2.,3Electrical Engg Dept,IIT Roorkee, India)

ABSTRACT: In recent years Unified Power Quality conditioner ( UPQC) is being used as universal
active power conditioning device to mitigate both current as well as voltage harmonics in a polluted
power system network. Both voltage source and current source inverter are in use for fabrication of
UPQC. Current source UPQC has unique advantages over generalized voltage source UPQC. This
paper presents a comparative analysis of voltage source and current source UPQC. A simple PI
controller and robust hystersis band PWM technique is used for derivation of reference and
switching signals respectively. The resultant compensation system eliminates voltage as well as
current harmonics with good dynamic response. Extensive simulation results using Mat lab / Simulink
for R-L load connected through an uncontrolled bridge rectifier is presented for performance
comparison.
Index Terms: CSI, current harmonics, hystersis controller, power quality conditioner, series active filter,
shunt active filter, UPQC, voltage harmonics, VSI.

I.

Introduction

The recent development in power electronics led to development of solid-state controllers, which are in
use with industry, commercial and domestic sectors extensively. The quality of power is being deteriorated due
to use of these electronic controllers, which in turn demands quality power from source [1]. Varieties of power
conditioning techniques are in use starting from passive filtering to active power conditioning [2]. Among
different new technical options available to improve power quality, Unified Power Quality Conditioner (UPQC)
has found to be more promising.[3]. It provides an important and flexible alternative to compensate both current
as well as voltage disturbances simultaneously by a single unit. It is generally configured with two bi-directional
converters connected back to back through an energy storage device [3]. Since its development, VSI based
UPQC was in use due to its compact size, flexibility to extend multilevel. Different configuration, principle of
operation and control of VSI based UPQC is discussed in depth in references [4-6].
With the availability of new IGBT with reverse blocking capability, the use of current source active
filters is increasing due to its inbuilt short circuit protection capability, higher efficiency at low power loads,
simple open loop current control and effective filtering of harmonics . A configuration and control aspect of
current source active power filter is discussed in references [7-8]. Performance of CSI based UPQC is
presented by Dusan Graovac etal in 2001[9]. A comparison of current and voltage source shunt active power
filters is discussed in past [10-13].
However, comparative analysis of current and voltage source UPQC was missing. This paper presents a
comprehensive analysis of current and voltage source UPQC using a simple PI controller for derivation of
reference signals. These reference signals are then compared in a robust hystersis controller for generation of
switching signals. The differences in system configuration and control strategy are presented in section II and
IV. The compensation strategy is discussed in section III. A comparative analysis of simulation results is
presented in section V.

II.

System Configuration

Unified Power Quality Conditioner comprises of two bidirectional converters connected back to back
through an energy storage element as shown in fig.1. The generalized UPQC consists of both series and shunt
(Voltage /Current) compensation elements. Each element consists of a bidirectional switch to accommodate for
voltage or current conversion as per requirement. One of bidirectional converter is connected to system bus in
series through a transformer termed as series active filter .It is controlled as voltage generator. It has capability
of voltage imbalance compensation, voltage regulation and harmonic compensation at the utility-consumer point
of common coupling (PCC). In addition to this, it provides harmonic isolation between a sub transmission
system and a distribution system. Another bidirectional converter is connected in parallel with load to the
system bus called shunt active filter.
www.iosrjournals.org

6 | Page

Comparative Evaluation of VSI and CSI based Unified Power Quality Conditioner
Series Transformer

Static
switch

AC
Line

Load

DC Link
Paralell
Series
bi-directional
bi-directional
converter
converter
DC
Capacitor

Fig.1. Conceptual diagram of UPQC.


It is controlled as a current generator. It absorb current harmonics, compensate for reactive power and
negative sequence current injected by the load. Third element of this power line conditioner is an energy storage
device.These bidirectional switches may be of Voltage Source Inverter (VSI) based or Current Source Inverter
(CSI) based. Each type of switch is having its own merits and demerits. In current source based UPQC a large
inductor is used as a DC link , while in voltage source UPQC a large capacitor is used as energy storage
element as shown in fig 2.2 and fig 2.3 respectively. This dc link will function as DC sources and hence does
not demand any external power source. However in order to maintain constant DC current/ voltage in the energy
storage element a small fundamental current is drawn to compensate active filter losses.
2.1. SYSTEM CONFIGURATION OF VSI BASED UPQC
A VSI based UPQC is built with two bridges of IGBT switches with anti parallel diode connected back
to back with a dc capacitor as energy storage device as shown in fig 2.
Rs
S5
Is

S7

S1

iL

S3

if

Vs
L2

L1
Cdc

C2

C1

Non
Linear
Load

Source
S8

S6

S4

S2

Fig.2. Schematic diagram of VSI based UPQC


The inductor Lf through which the inverter is connected to power supply network via series
transformer, ensures firstly the controllability of the active filter currents and secondly act as first order passive
filter attenuating the high frequency ripples generated by the inverter. This filter may also be formed with third
order (LCL) type. The voltage of dc capacitor used as energy storage device should be so high that the filter
currents can be controlled to draw the load current harmonics through the supply filter. The theoretical
minimum value for the voltage is the peak of the supply line-to-line voltage.
2.2. SYSTEM CONFIGURATION OF CSI BASED UPQC
A CSI based UPQC is built with two bridges of IGBT switches connected back to back through an
inductor of sufficiently large value as shown in fig.3.
Series injection transformer
Programmable
voltage source

DC link inductor

Ldc
T4

T4

T2

T6

T2

T6

Lsh

LS
FRD4

FRD6

FRD4

FRD2

FRD6

FRD2

Csh
CS
T3

T1

FRD1

T5

FRD 3

T3

T1

FRD1

FRD5

FRD 3

T5

FRD5

Shunt active filter

Series active filter

UPQC

Fig. 3. Schematic diagram of CSI based UPQC


The series filter is connected to AC mains supply through a series transformer of suitable rating and a
second order low pass filter formed by C f and Lf. The size of filter capacitor must be selected carefully to make
sure that no low-order harmonics are close to the resonant frequency of the LC tank circuit. The switches are
under bidirectional voltage stress and maximum values of these are the peak value of the supply line to-line
www.iosrjournals.org

7 | Page

Comparative Evaluation of VSI and CSI based Unified Power Quality Conditioner
voltage [10]. A Fast Recovery Diode of similar rating is required to connect in series with each switch as to limit
reverse voltage blocking. The use of series diode can be avoided by using reverse blocking IGBT. The energy
storage element a dc inductor Ldc is designed to limit the dc current ripple to a specified value to limit ripples in
Idc The theoretical minimum dc link current is zero , but the current should be at least as high as the peak value
of the compensating current. A R-L load connected through diode rectifier bridge will act as non-linear load to
verify the system performance.

III.

Compensation Strategy

The equivalent circuit diagram of an UPQC is as shown in fig 4 Vs is the supply voltage, Vc, and ic are
the series compensation voltage , shunt compensation current and VL, iL are the load voltage and load current
respectively [ 15]
Vc
IL
+
IC
+
Z
Vs
Fig.4. Equivalent circuit diagram of UPQC
The source voltage may contain positive, negative, zero as well as harmonic components. The per phase voltage
of the system can be expressed as :

Vsa V1 pa V1na V10 a Vka Sin(kt ka )

(1)

k 2

Where V1pa is the fundamental frequency positive sequence component, V1na andV10a are the negative and zero
sequence components respectively. The last term of equation represents the harmonic content in the voltage. In
order for the load voltage to perfectly sinusoidal and balanced, the series filter should produce a voltage equal
to

Vah V1na V10 a Vka Sin(kt ka )

(2)

k 2

Further the functions of the shunt active filter is to provide compensation of the load harmonic current, load
reactive power demand and also to maintain DC link current constant. The per phase load current of shunt active
filter is expressed as

ial ia1 p Cos(t 1 ) ia ln ialk

(3)

k 2

ial ia1 p CostCos1 ia1 p SintSin1 ia ln ialk

(4)

k 2

In order to compensate harmonic current and reactive power demand the shunt active filter should produce a
current of i ah i a1 p SintSin1 i a ln

i
k 2

(5)

alk

So the source current will be

ias ial iah ia1 p CostCos1

(6)

This is a perfect harmonic free sinusoidal current in phase with voltage.

IV.

CONTROL STRATEGY

The control strategy has been implemented in two parts:


4.1. SERIES FILTER CONTROL
In both current source and voltage source UPQC, the series filter is controlled by similar hystersis band
voltage control. A series active filter acts as controlled voltage source by imposing high impedance for the
harmonic currents, blocking their flow from both loads to source and source to load directions. The source
voltage may contain zero, negative sequence as well as harmonic component, which need to be eliminated by
series compensator. In order for the load voltage to perfectly sinusoidal and balanced, the series filter should
produce a voltage equal to equation (2). The reference load voltages are obtained by multiplying a PLL based
unit vector templates with a constant equal to peak amplitude of fundamental input voltage [13]. Unit vector
templates for different phases are obtained with proper phase delay as follows:
www.iosrjournals.org

8 | Page

Comparative Evaluation of VSI and CSI based Unified Power Quality Conditioner

u a Sint

u b Sin(t 120 0 )

u c Sin(t 120 0 )

(7)

V * fa Vsa Vm.u a

V * fb Vsb Vm u b

V * fc Vsc Vm u c

(8)

These compensation signals are compared with actual signals at the terminals of series filter, the error
is then taken to hystersis controller to generate the required gating signal for series filter. The control block
diagram of series filter is as shown in fig 5

Gating signal generator


Current
Control Unit

Gating
Signal

Vsa* Vsb* Vsc*


Vsa
Vsb
Vsc

PLL based
Unit Vector
Template

Reference
Voltage
Generator
Vm
Fig.5.Control block diagram of series filter.

4.2. SHUNT FILTER CONTROL


The main purpose of the shunt active filter is to absorb current harmonics, compensate for reactive
power and negative sequence current injected by the load. In addition, it controls current / voltage of the DC link
to a desired value.
4.2.1. VOLTAGE SOURCE UPQC

Isa
Isb
Isc

Gating signal generator


Current
Control Unit

Gating
signal

Vsa* Vsb* Vsc*


Vsa
Vsb
Vsc

PLL based
Unit Vector
Template

Reference
Current
Generator
PI
Controller

Vdc
V*dc

Fig.6.VSI based UPQC shunt filter controller


www.iosrjournals.org

9 | Page

Comparative Evaluation of VSI and CSI based Unified Power Quality Conditioner
In case of voltage source UPQC, the dc link voltage is sensed and compared with the reference dc link
voltage. A PI controller then processes this error. Output signal from PI controller is regarded as magnitude of
three phase reference currents. Reference supply currents are then obtained by multiplying unit vectors template
with magnitude of reference current. The source current must be equal to this reference supply currents. In order
to follow this reference current signal, the source currents are sensed and compared with reference current
signals. The error generated is then processed by hystersis current controller with suitable band, generating
gating signals for shunt filter [13]. The control diagram of VSI based shunt filter controller is as shown in fig.6

Idc

Isa Isb Isc

vsa
vsb
vsc

i
a-b-c i
to v

PI

HCC

Idc*
p(t)
LPF

Calculation
of p and q q(t)

p'(t)
++

Isa*

Gating signal

4.2.2. CURRENT SOURCE UPQC


In case of CSI based UPQC , the dc link current is sensed and compared with reference dc link current.
A PI controller then processes the error. The output signal from PI controller is regarded as switching power
losses of shunt active filter, and is added to real power loss component to derive reference source current using
equations 9- 15.These reference currents are then compared with actual source current in a hystersis controller
band to derive the switching signals of shunt inverter. The schematic block diagram of shunt filter controller is
shown in fig.7

Isb*
to
a - b- c Isc*

Fig.7. CSI based UPQC shunt filter controller

v 1 1 2 1 2
v
3 2 3
0

v
a
vb
2
vc

(9)

ia
i 1 1 2 1 2
ib
i
3 2 3 2
0
ic

(10)

Instantaneous active and reactive power in orthogonal co-ordinates are calculated as follows

p (t ) v a (t )ia (t ) vb (t )ib (t ) vc (t )ic (t )


p (t ) v (t )i (t ) v (t )i (t )
q (t ) v (t )i (t ) v (t )i (t )
In matrix form it is given as

p v
q v

v i
v i

(11)

From (9) the values of p and q can be expressed in terms of dc components plus the ac components as follows

p p ~
p
~
qq q

Where
p is the dc component of the instantaneous power p, and is related to, the fundamental active current.
www.iosrjournals.org

10 | Page

Comparative Evaluation of VSI and CSI based Unified Power Quality Conditioner

~p is the ac component of the imaginary power p, and is related to the harmonic current caused by the ac
component of the instantaneous real power.
q is the dc component of the imaginary instantaneous power q, and is related to the reactive power generated
by the fundamental components of voltage and current.
q~ is the ac component of the instantaneous imaginary power q, and is related to the harmonic current caused
by the ac component of instantaneous reactive power .
To compute harmonic free unity power factor, 3-phase currents, compensating powers pc and qc are selected as

pc p ploss

(12)

qc 0

Where ploss is the instantaneous active power corresponding to the switching loss and resistive loss of
shunt active filter. Total instantaneous active power is calculated by adding real power loss due to switching as
shown in fig.7 [12].The orthogonal components of the fundamental current are obtained as follows.

i v
i v

v pc
v q c

(13)

The a-b-c components of fundamental reference current are obtained as follows.

0
i * sa 2 3
*
i
i sb 1 3 1 3 i
i * sc 1 3 1 3

(14)

The control of both VSI and CSI based UPQC is realized using hystersis band PWM technique.
Among various PWM techniques, the hystersis band control is used very often because of its simplicity of
implementation, fast response and does not need any knowledge of load parameters. The basic implementation
of hystersis control is based on deriving the switching signals from comparison of the signal error with a fixed
tolerance band.

V.

Comparison Based On Simulation Results

To verify the performance, both VSI based and CSI based UPQC model is developed using above
equations in MATLAB / SIMULINK. A threephase diode rectifier with an RL load is employed as nonlinear
load. All the compensators are implemented using equivalent discrete blocks. Shunt filter is switched on at 0.05
sec, while series filter is switched on at 0.1 sec to verify the performance of indusial filters. Controlled switches
are assumed ideal. The system parameters are selected as given in table 1
TABLE-1
SYSTEM PARAMETER
Supply
3.50Hz,100Vp-p with
20% of 5th harmonics
Load(Non-linear)
(10+j7.85)
Line inductance
50H
Line resistance
0.01
Switching frequency
~20kHz
Sample time
1sec
Smoothing inductance 1mH
The filter parameters for VSI and CSI based UPQC are selected as given in table 2
TABLE-2
FILTER PARAMETER
VSI
CSI
DC Link Capacitance
450F
DC Link inductance
Series filter reactance LSC
5mH., 0.1 Series filter reactance Csc
Shunt filter reactance Lsh
5mH, 0.4
Shunt filter reactance Csh
The performance of shunt and series filter of VSI based UPQC is shown in fig 8 and
based UPQC is presented in fig 10 and fig.11 respectively.
www.iosrjournals.org

450mH
0.4F,1
240F,1
fig.9, while that of CSI

11 | Page

Comparative Evaluation of VSI and CSI based Unified Power Quality Conditioner

Fig .8. Source voltage, load voltage ,compensation voltage and dc link voltage of VSI based UPQC.

Fig..9 Source current, load current and filter current of VSI based UPQC
The performance of UPQC for voltage harmonic correction is depend upon the series filter
performance. The load voltage is same as source voltage, till the series filter is switched on. The instant at which
series filter is switched on ie at 0.1 sec, the load voltage becomes pure sinusoidal as indicated in fig.8 and fig.9.
Hence compensating for voltage harmonics present in the system and thus, corrects the system voltage to be
pure sinusoidal at PCC irrespective of voltage distortions present at the source. The performance difference
between VSI and CSI based UPQC is that the THD of load voltage at PCC improves to 1.15% in case of VSI
while in CSI it improves to 1.13% from 20% of 5th harmonic distortion at source which is well below the IEEE
recommended harmonic

Fig.10. Source voltage, load voltage and filter voltage of CSI based UPQC

Fig.11 Source current, load current, filter current and DC link current of CSI based UPQC
www.iosrjournals.org

12 | Page

Comparative Evaluation of VSI and CSI based Unified Power Quality Conditioner
Further, the capability of UPQC for current harmonics correction and reactive power compensation is adjudged by
the performance of shunt filter. The shunt filter performs satisfactorily only under balanced voltage conditions, which can be
verified from fig 9 and fig. 11 in which even though shunt filter is switched on at 0.5 sec, because of voltage unbalance fails
to compensates satisfactorily for current harmonics. However, after series filter is switched on, the shunt filter starts to
compensate for current harmonics. With the integrated operation of shunt and series filter, the THD of source current in VSI
configuration improves from 15.62% to 1.62, however in case of CSI the THD of source current improves from 15.55%
to 1.01% again which is well below IEEE 519 standards. A comparative harmonic spectrum analysis of both VSI and CSI is
presented in table 3.

TABLE-3
HARMONIC SPECTRUM ANALYSIS
Harmonic
order
Fundamental
5th
7th
11th
13th
17th
19th
THD(%)

Amplitude
Is
CSI
VSI
14.7 14.3
0.06 0.12
0.02 0.04
0.03 0.04
0.03 0.04
0.01 0.03
0.01 0.04
1.01 1.62

IL
CSI
13.6
1.90
0.86
0.28
0.21
0.12
0.09
15.5

VSI
13.3
1.90
0.87
0.27
0.21
0.12
0.09
15.6

Vs
CSI
100
20.0
0.0
0.0
0.0
0.0
0.0
20.0

VSI
100
20.0
0.0
0.0
0.0
0.0
0.0
20.0

VL
CSI
87.8
0.86
0.32
0.16
0.10
0.01
0.04
1.13

VSI
87.5
0.72
0.42
0.13
0.16
0.03
0.05
1.15

From the above table it is clear that CSI performance better than VSI with respect to harmonic filtration
at the designated load. The transient stability of the system is adjudged by DC link oscillations present in the
filtering system. VSI based UPQC has problem of slow control of converter as compare to that of CSI based
UPQC that is evident from fig 5.1 and fig 5.4. VSI based UPQC takes 100ms to reach dc link voltage to a stable
value, while CSI based UPQC reaches stable value with in 50 ms indicating superior functionalities over VSI
counterpart.

VI.

CONCLUSION

The performance of CSI and VSI based UPQC is studied. Both the system is operated at a switching
frequency of 20 kHz approximately, and is connected to same type of supply system. For the study purpose both
systems are connected to a nonlinear load of (10+j7.85) through a diode rectifier. The study reveals that the
performance of CSI based UPQC is better as compared with VSI based UPQC. At a fixed switching frequency,
the THD of source current and load voltage of CSI based UPQC is less than that of VSI based UPQC.
Moreover, the increased oscillations in VSI based system may result in poor transient stability. Hence, it is
concluded that the performance of CSI based UPQC is better in comparison with that of VSI based UPQC.

References
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]

S.L.Clark, P.Famouri and W.L.Cooley, "Elimination of supply harmonics: an evolution of current compensation and active filtering
methods", IEEE, IAS 94, Denver, Colorado, USA,Oct.1994, pp-1699-1704
Bhim Singh,Kamal.A.H., and Ambrish Chandra, A Review of Active Filters for Power Quality improvement, IEEE Transactions
on Industrial Electronics,Vol-46,No-5, October 1999,pp 960-971.
Vadirajacharya.K, Pramod Agarwa and H.O.Gupta, A Simple Control Strategy for Unified Power Quality Conditioner Using
Current Source Inverter 8th International Power Engineering Conference IPEC2007 3-6 December 2007, Singapore
H. Fujita, H. Akagi, Unified Power Quality Conditioner: The Integration of Series and Shunt Active Filter, IEEE Trans. on Power
Electronics, vol.13, no.2, March 1998, pp.315-322.
M.Ardes, K.Heuman and E.Watanabe, An Universal active power line conditioner, IEEE Transactions on Power delivery ,
Volume13, No2,Apr 1998,pp545-551
Ghosh and G. Ledwich, A unified power quality conditioner (UPQC) for simultaneous voltage and current compensation,
Electric Power Systems Research, Vol. 59,2001, pp. 55-63
Y.Hayashi, N. Sato and K. Takahashi, A novel control of a current source active filter for ac power system harmonic
compensation, IEEE Transactions on Industry Application, Vol.27, No.2, Mar/Apr 1997, pp.380-385
Salo. M., Tuusa. H., A new control system with a control delay compensation for a current-source active power filter IEEE
Transactions on Industrial Electronics, vol 52,No.6. Dec 2005 pp1616-1624
D.Graovac, V. Katic, Alfred Rufer, Jovan Kne evi Baldor ASR GmbH, Unified Power Quality Conditioner based on Current
Source Converter topology EPE 2001 Graz ,pp 1-9
M. Salo, & H.Tuusa, Comparison of voltage-source and current-source shunt active power filters, IEEE 36th Annual PES
Conference, PESC05, June 12-16, 2005, Recife, Brazil. pp. 2571-2577
L. Benchaita, S. Saadate and A Salem nia, A comparison of voltage source and current source shunt active filter by simulat ion
and experimentation IEEE Transactions on Power Systems, Vol.14, No.2, May 1999, pp 642-647.
H. L Yunus and R. M. Bass, Comparison of VSI and CSI topologies for single phase active power filter, IEEE PESC96, pp.
1892-1899.
V. Khadkikar, P. Agarwal, A. Chandra, A.O. Bany and T.D. Nguyen, A Simple New Control Technique For Unified Power
Quality Conditioner (UPQC), 2004 11th International Conference on Harmonics and Quality of Power, Lake Placid, New York,
USA, Sept 12-15 2004, pp 289-293.

www.iosrjournals.org

13 | Page

You might also like