1.0 GENERAL
1.1
SUMMARY
This specification shall define the electrical and mechanical characteristics and requirements for a continuousduty, single-phase, solid-state uninterruptible power system (UPS). The UPS shall provide high-quality mains
power for sensitive, electronic equipment loads. The UPS is not designed to support large inductive or half-wave
rectified loads, for example: motors, compressors, vacuum pumps, electric drills, laser printers and hair dryers.
1.2
STANDARDS
The UPS shall be designed in accordance with applicable sections of the current revision of the following
documents. Where a conflict arises between these documents and statements made herein, the statements in this
specification shall govern.
230V Nominal Units
Safety-IEC62040-1:2008 version
Emission (Low limits - conducted and radiated):
IEC/EN/AS 62040-2 2nd Ed (Cat2 - Table 1)
CISPR22 Class A (RFI)
IEC/EN/AS61000-3-12 (Harmonics)
Immunity (High commercial and light industry immunity levels for enclosure, power, signal and control
ports):
IEC/EN/AS 62040-2 2nd Ed (Cat 2 - Table 6) for IEC/EN/AS
61000-4-2 Electrostatic discharge
61000-4-3 Radiated E-RFI fields
61000-4-4 Fast E transients
61000-4-5 Surges/Lightning
61000-4-6 Conducted RFI
Transportation and Shipping- ISTA Procedure 1A Certification
C-Tick (Liebert in Australia / New Zealand will pursue certification)
WEEE and RoHS (6 of 6)
The 230 VAC UPS units shall be TUV listed and shall bear the CE compliance mark and Australia C-tick (C)
mark.
Guide Specifications
Liebert GXT3-10000RT230
1.3
SYSTEM DESCRIPTION
Watts
VAC Output
10000
9000
Guide Specifications
Liebert GXT3-10000RT230
GXT3-5000RT230
GXT3-6000RT230
176 5.0VAC
188 5.0VAC
159 5.0VAC
171 5.0VAC
139 5.0VAC
151 5.0VAC
100 5.0VAC
112 5.0VAC
185 5.0VAC
197 5.0VAC
167 5.0VAC
179 5.0VAC
139 5.0VAC
151 5.0VAC
100 5.0VAC
112 5.0VAC
L/L Transfer
L/L Comeback
L/L Transfer
L/L Comeback
L/L Transfer
L/L Comeback
L/L Transfer
L/L Comeback
230V Models
280 5.0VAC
268 5.0VAC
B. Frequency: The UPS shall auto-sense mains frequency of 50Hz or 60Hz when first powered up and shall use
this frequency as the default output frequency. Once started the mains frequency operating window shall be
40-70Hz without going to batteries. The UPS shall be capable of cold start with a default output frequency of
50Hz.
C. Mains Power Factor: >0.99 lagging at rated load.
D. Mains Current reflected distortion: 5% THD maximum at rated load.
E. Mains Current Ratings:
UPS Model #
VA
Watt
Hz
VAC
Total Amps
GXT3-10000RT230
10000
10000
10000
9000
9000
9000
50
50
50
220
230
240
45.5
43.5
41.7
F. Surge Protection: The UPS shall utilize metal oxide varistors (MOVs) rated at 510V.
G. Electrical Specifications:
UPS Model
Recommended
(Maximum)
External
Overcurrent
Protection
Recommended
Wire (Including
Earth Ground Wire)
(75C Copper Wire)
GXT3-10000RT230
63A
10mm (6AWG)
Maximum Wire
Accepted by
Terminal Block
2
16mm (4AWG)
Terminal
Tightening
Torque
2.26 Nm
(20 in-lb)
Guide Specifications
Liebert GXT3-10000RT230
105% to 130%
131% to 150%
151% to 200%
1 minute
10 seconds
1 second
At least 5 cycles
H. Voltage Transient Response: 7% on-line or Battery mode for 0-100-0 % loading of the UPS, 4% on-line
or Battery mode for 20-100-20 % loading of the UPS.
I. Transient Recovery Time: To nominal voltage within 166 milliseconds.
J. Efficiency: 92% AC-AC
Guide Specifications
Liebert GXT3-10000RT230
1.4
ENVIRONMENTAL CONDITIONS
A. Ambient Temperature
Operating: 0C to 40C (32F to 104F)
Storage: -15C to +50C (5F to 122F)
GXT3-240RTVBATT: 20C (68F) for optimum battery storage.
Battery systems should not be stored for extended periods above 25C (77F).
B. Relative Humidity
Operating: 0 to 95% non-condensing
Storage: 0 to 95% non-condensing
C. Altitude
Up to 1000m (3,281 ft) at 30C (86F) without power derating when operated within the temperature
specified in Section 1.4, Item A. Ambient temperature shall be derated by 5C (9F) for each additional 500m
(1,640 ft.) above 3,000m (9,843 ft.).
D. Audible Noise
Noise generated by the UPS under normal operation shall not exceed 55dBA at 1 meter (3.2 ft.) from the rear
50 dBA, at 1 meter (3.2 ft.) from the front or sides.
E. Electrostatic Discharge
The UPS shall be able to withstand an electrostatic discharge compliant to EN61000-4-2, level 4, Criteria A,
without damage and shall not affect the connected load.
1.5
USER DOCUMENTATION
The specified UPS system shall be supplied with a Safety Warning Sheet. The UPS and Configuration Program
user manual shall be on an included CD. The user manual shall include installation drawings and instructions, a
functional description of the equipment with block diagrams, safety precautions, illustrations, step-by-step
operating procedures, general maintenance guidelines, troubleshooting information and product specifications.
1.6
WARRANTY
The UPS shall be warranted against defects in materials and workmanship for two (2) years. Optional one (1) and
three (3) year full coverage extended warranties shall be available from Emerson Network Power.
1.7
QUALITY ASSURANCE
Guide Specifications
Liebert GXT3-10000RT230
2.0 PRODUCT
2.1
FABRICATION
All materials and components making up the UPS shall be new, of current manufacture and shall not have been in
prior service except as required during factory testing. All relays shall be provided with dust covers.
2.1.1 Wiring
Wiring practices, materials and coding shall be in accordance with the requirements the standards listed in
Section 1.2 and other applicable codes and standards. All wiring shall be copper.
2.1.2 Cabinet
The UPS unit shall be composed of: mains PFC converter, battery charger, dual-inverter, mains filter and internal
bypass circuit; and batteries consisting of the appropriate number of sealed battery cells; and shall be housed in a
rack-tower NEMA type 1 enclosure and shall meet the requirements of IP20. The UPS cabinet shall be cleaned
and painted RAL 7021 Black.
Rack Dimensions
W x D x H, in. (mm)
Tower Dimensions
W x D x H, in. (mm)
Weight
lb. (kg)
70 (154.3)
65 (143.3)
2.1.4 Cooling
The UPS shall be forced air cooled by internally mounted, continuous fans. Fan power shall be provided from the
internal DC supply. Air intake shall be through the front of the unit, and air exhaust shall be out the rear of the
unit.
Guide Specifications
Liebert GXT3-10000RT230
2.2
COMPONENTS
Guide Specifications
Liebert GXT3-10000RT230
2.2.2 Inverters
2.2.2.1 General
The UPS inverters shall be of a pulse-width-modulated (PWM), IGBT design capable of providing the specified
mains output. The inverters shall convert DC power from the mains rectifier output or the battery into precise
sinewave mains power for supporting the critical load.
2.2.2.2 Overload
The inverter shall be capable of supplying current and voltage for overloads exceeding 100%, and 105-130% for
1 minute, 131-150% 10 seconds, 151-200% for 1 seconds, and up to >200% for 5 cycles of full load current. A
visual indicator and audible alarm shall indicate overload operation. For greater currents or longer time duration,
the inverter shall have electronic current-limiting protection on the output to prevent damage to components. The
inverter shall be self-protecting against any magnitude of connected output overload. Inverter control logic shall
sense and disconnect the inverter from the critical mains load without the requirement to clear protective devices.
2.2.2.3 Inverter DC Protection
The inverter shall be protected by the following DC shutdown levels:
DC Overvoltage Shutdown
DC Undervoltage Shutdown (End of Discharge)
2.2.2.4 Output Frequency
An oscillator shall control the output frequency of the UPS. The inverter shall maintain the output frequency to
0.1Hz of nominal frequency during Battery mode, Frequency Converter mode or when otherwise not
synchronized to the mains source.
2.2.2.5 Output Protection
The UPS inverter shall employ electronic current limiting circuitry for protection during Normal mode and
battery operation and the UPS shall employ mains circuit breaker protection during Bypass mode operation.
Guide Specifications
Liebert GXT3-10000RT230
Guide Specifications
Liebert GXT3-10000RT230
2.3
The UPS shall feature an automatic battery test with the factory default test interval set at every 2 weeks. The
battery test shall ensure the capability of the battery to supply power to the inverter while loaded. If the battery
fails the test, the UPS shall display a warning alarm to indicate the internal batteries need replaced and resume
operation without disturbing the load. The battery test feature shall be user accessible by the push button on the
front of the unit.
2.4
BYPASS
2.4.1 General
A bypass circuit shall be provided as an integral part of the UPS. The bypass shall have a make-before-break
transfer, shall have a maximum detect and transfer time of 4-6 milliseconds and shall be a double-pole device.
The bypass shall be configured to wrap around the PFC converter, battery charger, DC-DC converter, inverter and
battery. The bypass circuit shall use the rear-panel mounted UPS mains circuit breaker and route bypass power
through the UPS mains filters and surge suppression circuit. The bypass circuit default position shall be in the
Bypass mode (mains).
2.5
INTERNAL BATTERY
Valve-regulated, non-spillable, lead acid cells shall be used as a stored-energy source for the specified UPS
system. The battery kit shall be internal to the UPS cabinet and sized to support the inverter at rated load and
power factor with an ambient temperature of 25C (77F) for a minimum of 5 minutes reserve time. The expected
life of the battery shall be 3-5 years or a minimum 250 complete discharge cycles at ambient temperature of 25C
(77F). To promote battery service life and eliminate over-discharge of the battery, the end-of-discharge DC
shutdown voltage shall be automatically adjusted by the microprocessor based upon the percentage load at the
onset of battery operation.
2.6
OUTPUT DISTRIBUTION
Output distribution shall be integral to the UPS cabinet and located on the rear of the unit. Distribution shall be
provided with break-before-make maintenance bypass switch to allow for complete shutdown and isolation of the
UPS for service without powering down the connected loads. Maximum transfer time of the maintenance bypass
switch shall be 4-6ms. Standard output distribution configuration shall be:
Distribution
Model
PD2-CE10HDWRMBS
Mains
Connection
Output Load
Connections
Maintenance
Bypass
Hardwire Terminals,
2-wire-plus-ground,
8AWG max
Included
10
Guide Specifications
Liebert GXT3-10000RT230
2.7
ON-BOARD COMMUNICATION
The Liebert GXT3 shall offer multiple communication options such as:
A. USB: All models shall work with the Power Management system in Microsoft Windows 2000, Windows
XP, Windows Vista, Linux and Mac OS X.
B. Remote Emergency Power Off (REPO): The UPS shall be equipped with rear-panel terminal connections
for interface with either a normally open (N.O.) or normally closed (N.C.) field-supplied switch. The remote
emergency power off function shall allow the user to disable all UPS outputs in an emergency situation.
Connections must not exceed NEC Class 2 limits. Activation of the REPO circuit shall disable the UPS until
the following occurs:
REPO contacts are reset.
User restart of the UPS using the front control panel.
C. Terminal Block Communication: includes 8 pins
Pin
1&2
3&4
5&6
7&8
Definition
Low Battery Warning
On Battery Warning
Any Mode Shutdown
Battery Mode Shutdown
2.8
The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field-install optional
Liebert IntelliSlot communication cards. Liebert IntelliSlot cards may be installed during any state of UPS
operation (On, Standby or Off states). Available Liebert IntelliSlot options are described below.
Liebert IntelliSlot Web Card (IS-WEBCARD)
The optional Liebert IntelliSlot Web Card shall deliver SNMP and Web management to the UPS when
connected to any 10 or 100 Mbit Ethernet network. The card shall support 10 and 100 Mbit Ethernet and
shall provide for in-the-field upgrade of SNMP firmware. The kit shall include the Liebert IntelliSlot card,
MIB, configuration cable and user manual. Once the card is installed, serial communication shall be disabled
in the DB9F connector; however, the photo-coupler signals (On Battery and Low Battery) shall remain
active.
Liebert IntelliSlot Relay Interface Card (RELAYCARD-INT)
The optional Liebert IntelliSlot Relay Interface Card shall provide contact closure for remote monitoring of
alarm conditions in the UPS, delivering signals for On Battery, On Bypass, Low Battery, Summary Alarm,
UPS Fault and On UPS. The contacts shall be rated for 24VAC or 24VDC at 1A. Connection shall be to a
DB25F connector with cable provided by the end user.
11
Guide Specifications
Liebert GXT3-10000RT230
2.9
An included Microsoft Windows-based (Windows 95 or later) Configuration Program and cable shall allow
configuration of UPS features and operating parameters to meet specific application requirements, if required.
Options that are configurable via this program shall include:
Select one of five output voltages to match mains voltages of 220/230/240.
Enable / Disable Auto-Restart.
Select frequency converter operation with a fixed output frequency of 50 or 60Hz. Bypass is disabled
during Frequency Converter mode.
Set the Low Battery Warning alarm time from 2 to 30 minutes.
Disable the Auto-Battery test.
Set the Auto-Battery test interval to 7, 14, 21 or 28 days.
Select the number of external battery cabinets connected to the UPS to adjust the remaining run-time
calculations reported by the UPS Liebert software products.
Modify the shutdown setting of the Any Mode Shutdown.
12
Guide Specifications