8000 & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS
1.0 GENERAL
1.1 SUMMARY
This specification shall define the electrical and mechanical characteristics and requirements for a continuousduty, single-phase, solid-state uninterruptible power system (UPS). The UPS shall provide high-quality AC power for sensitive, electronic equipment loads. The UPS is not designed to support large inductive or half-wave rectified loads, for example: motors, compressors, vacuum pumps, electric drills, laser printers and hair dryers.
1.2
STANDARDS
The UPS shall be designed in accordance with applicable sections of the current revision of the following documents. Where a conflict arises between these documents and statements made herein, the statements in this specification shall govern. 208V Nominal Units y UL Standard 1778, c-UL y CSA 22.2 No. 107.1 y NEMA Type 1 Enclosure y FCC Part 15, Class A y CISPR22 Class A (RFI) y IEC 61000-3-12 (Harmonics) y IEC/EN/AS 62040-2 2nd Ed (Cat 2 - Table 6): y EN61000-4-2, Level 4, Criteria A y EN61000-4-3, Level 3, Criteria A y EN61000-4-4, Level 4, Criteria A y EN61000-4-5, Level 3, Criteria A y EN61000-4-6 y ANSI C62.41, Category A y EN61000-4-5, Level 3, Criteria A y RoHS (6 by 6) y ISTA Procedure 1A
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
1.3
SYSTEM DESCRIPTION
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
10000RT208 models
VA 5000 4500 4000 10000 10000 10000 9000 10000 8000 Watts 4500 4050 3600 9000 9000 9000 8100 9000 7200 VAC Output 115 / 120 / 127 110 100 120 / 208 (120 or 240 degree only) 120 / 208 (180 degree only) 127 / 220 (120 or 240 degree only) 110 / 220 (180 degree only) 115 / 230 (180 degree only) 100 / 200 (180 degree)
C. Internal Battery: Valve-regulated, non-spillable, lead acid cells. D. Battery Reserve Time: Minimum 4 minutes with an ambient temperature of 77F (25C). E. Battery Recharge: The UPS shall contain a battery recharge rate designed to prolong battery life. Recharge time for UPS internal batteries shall be 3 hours maximum to 90% capacity after a complete discharge into full load.
SL-23189_REV1_08-10 3 Guide Specifications
Liebert GXT3-8000/10000RT208
B. Frequency: The UPS shall auto-sense input frequency of 50Hz or 60Hz when first powered up and shall use this frequency as the default output frequency. Once started the input frequency operating window shall be 40-70Hz without going to batteries. The UPS shall be capable of cold start with a default output frequency of 60Hz. C. Input Power Factor: >0.99 lagging at rated load. D. Input Current reflected distortion: 5% THD maximum at rated load. E. Input Current Ratings:
UPS Model # VA 5000 5000 5000 4500 4000 6000 5600 6000 5400 Watt 4000 4000 4000 3600 3200 5400 4800 4800 4320 Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 VAC 120/240 115/230 120/208 110/220 100/200 120/240 115/230 120/208 110/220 L1 20.8 21.7 20.8 20.8 21.7 27.2 25.5 24.5 24.5 L2 20.8 21.7 20.8 20.8 21.7 27.2 25.5 24.5 24.5 Total Amps 41.6 43.5 41.7 41.5 43.5 54.3 51 48.9 49
GXT3-8000RT208
GXT3-10000RT208
F. Surge Protection: The UPS shall utilize metal oxide varistors (MOVs) rated at 175V, 150 Joules minimum connected L1-N and L2-N; 300V, 150 Joules minimum connected L1-G, L2-G and N-G.
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
1.3.3.2 AC Output, UPS Inverters A. Voltage Configuration: 50/60Hz, single-phase, 3-wire-plus-ground. Default setting 120/208V. Output L-N voltage shall be selectable via the included UPS configuration program. Optional settings shall be 100/200V, 110/220V, 115/230V, 120/208V, 120/240V or 127/220V. The UPS shall adjust sinewave amplitude and/or phase-angle relationship of the inverters to produce the selected voltage to match the input. Note: At 100/200V setting, the UPS shall be derated to 80% of the rated 120/208V capacity; at 110/220V, the UPS shall be derated to 90% of the rated 120/208V capacity. B. Voltage Regulation: L1-N and L2-N: 3% steady state. L1-L2: 5% steady state. C. Frequency Regulation: 3.5Hz synchronized to utility / mains. 0.1Hz free running or on battery operation. D. Frequency Slew Rate: 1.0Hz per second maximum E. Load Power Factor Range: 0.65 lagging to 1.0 (unity) F. Voltage Distortion: Sinusoidal Waveform; 3% total harmonic distortion (THD) into a 100% linear load; 5% THD into a 100% non-linear load with a crest factor ratio of 3:1. G. Inverter Overload Capability:
Overload Percent 105% to 130% 131% to 150% 151% to 200% >200% (impact load) Duration Inverter shall support rated load 1 minute 10 seconds 1 second At least 5 cycles
H. Voltage Transient Response: 7% on-line or Battery mode for 0-100-0 % loading of the UPS, 4% on-line or Battery mode for 20-100-20 % loading of the UPS. I. Transient Recovery Time: To nominal voltage within 166 milliseconds. J. Efficiency: 91% AC-AC
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
1.4
ENVIRONMENTAL CONDITIONS
A. Ambient Temperature Operating: 32F to 104F (0C to 40C) for altitudes 0 to 5,000 feet (0 to 1500 meters) above sea level. 32F to 95F (0C to 30C) for altitudes 5,000 to 10,000 feet (1500 to 3000 meters) above sea level. Storage: 5F to 122F (-15C to +50C) GXT3-288RTVBATT and GXT3-288RTVBATKIT: 68F (20C) for optimum battery storage. Battery systems should not be stored for extended periods above 77F (25C) B. Relative Humidity Operating: 0 to 95% non-condensing. Storage: 0 to 95% non-condensing. C. Altitude 10,000ft. (3,000m) max, without power derating when operated within the temperature specified in Section 1.4, Item A. Ambient temperature shall be derated by 9F (5C) for each additional 1600ft. (500m) above 10,000ft. (3,000m). D. Audible Noise Noise generated by the UPS under normal operation shall not exceed 55dBA when measured at 3.2ft. (1m) from the surface of the UPS. E. Electrostatic Discharge The UPS shall be able to withstand an electrostatic discharge compliant to EN61000-4-2, level 4, Criteria A, without damage and shall not affect the connected load.
1.5
USER DOCUMENTATION
The specified UPS system shall be supplied with a Safety Warning Sheet. The UPS and Configuration Program user manual shall be on an included CD. The user manual shall include installation drawings and instructions, a functional description of the equipment with block diagrams, safety precautions, illustrations, step-by-step operating procedures, general maintenance guidelines, troubleshooting information and product specifications.
1.6
WARRANTY
The UPS shall be warranted against defects in materials and workmanship for two (2) years. Optional one (1) and three (3) year full coverage extended warranties shall be available from Emerson Network Power.
1.7
QUALITY ASSURANCE
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
2.0 PRODUCT
2.1 FABRICATION
All materials and components making up the UPS shall be new, of current manufacture and shall not have been in prior service except as required during factory testing. All relays shall be provided with dust covers.
2.1.1 Wiring
Wiring practices, materials and coding shall be in accordance with the requirements the standards listed in Section 1.2 and other applicable codes and standards. All wiring shall be copper.
2.1.2 Cabinet
The UPS unit shall be composed of: input PFC converter, battery charger, dual-inverter, input filter and internal bypass circuit; and batteries consisting of the appropriate number of sealed battery cells; and shall be housed in a rack-tower NEMA type 1 enclosure and shall meet the requirements of IP20. The UPS cabinet shall be cleaned, primed and painted RAL 7021 Black. The internal battery unit shall be shipped separately and shall be installed during the UPS installation process.
* Specified weights include the standard two (2) internal battery kits, Part Number GXT3-288RTBKIT.
2.1.4 Cooling
The UPS shall be forced air cooled by internally mounted, continuous fans. Fan power shall be provided from the internal DC supply. Air intake shall be through the front of the unit, and air exhaust shall be out the rear of the unit.
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
2.2
COMPONENTS
2.2.2 Inverters
2.2.2.1 General The UPS inverters shall be of a pulse-width-modulated (PWM), IGBT design capable of providing the specified AC output. The inverters shall convert DC power from the input rectifier output or the battery into precise sinewave AC power for supporting the critical AC load. 2.2.2.2 Overload The inverter shall be capable of supplying current and voltage for overloads exceeding 100% and up to 201% of full load current. A visual indicator and audible alarm shall indicate overload operation. For greater currents or longer time duration, the inverter shall have electronic current-limiting protection on the output to prevent damage to components. The inverter shall be self-protecting against any magnitude of connected output overload. Inverter control logic shall sense and disconnect the inverter from the critical AC load without the requirement to clear protective devices. 2.2.2.3 Inverter DC Protection The inverter shall be protected by the following DC shutdown levels: y DC Overvoltage Shutdown y DC Undervoltage Shutdown (End of Discharge) 2.2.2.4 Output Frequency An oscillator shall control the output frequency of the UPS. The inverter shall maintain the output frequency to 0.1Hz of nominal frequency during Battery mode, Frequency Converter mode or when otherwise not synchronized to the utility/mains source. 2.2.2.5 Output Protection The UPS inverter shall employ electronic current limiting circuitry for protection during Normal mode and battery operation and shall employ input circuit breaker protection during Bypass mode operation.
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
2.3
The UPS shall feature an automatic battery test with the factory default test interval set at every 2 weeks. The battery test shall ensure the capability of the battery to supply power to the inverter while loaded. If the battery fails the test, the UPS shall display a warning alarm to indicate the internal batteries need replaced and resume operation without disturbing the load. The battery test feature shall be user accessible by the push button on the front of the unit.
SL-23189_REV1_08-10
Guide Specifications
Liebert GXT3-8000/10000RT208
2.4
BYPASS
2.4.1 General
A bypass circuit shall be provided as an integral part of the UPS. The bypass shall have a make-before-break transfer, shall have a maximum detect and transfer time of 4-6 milliseconds and shall be a double-pole device. The bypass circuit shall be designed to ensure the simultaneous transfer of the L1 and L2 poles. The bypass shall be configured to wrap around the PFC converter, battery charger, DC-DC converter, inverter and battery. The bypass circuit shall use the rear-panel mounted UPS input circuit breaker and route bypass power through the UPS input filters and surge suppression circuit. The bypass circuit default position shall be in the Bypass mode (utility).
2.5
INTERNAL BATTERY
Valve-regulated, non-spillable, lead acid cells shall be used as a stored-energy source for the specified UPS system. The battery kit shall be internal to the UPS cabinet and sized to support the inverter at rated load and power factor with an ambient temperature of 77F (25C) for a minimum of 5 minutes reserve time. The expected life of the battery shall be 3-5 years or a minimum 250 complete discharge cycles at ambient temperature of 77F (25C). To promote battery service life and eliminate over-discharge of the battery, the end-of-discharge DC shutdown voltage shall be automatically adjusted by the microprocessor based upon the percentage load at the onset of battery operation.
2.6
OUTPUT DISTRIBUTION
Output distribution shall be integral to the UPS cabinet and located on the rear of the unit. The output distribution shall provide the capability to re-configure the UPS input and output connections via a removable sheet metal power distribution box. Distribution options shall be available with break-before-make maintenance bypass switch to allow for complete shutdown and isolation of the UPS for service without powering down the connected loads. Maximum transfer time of the maintenance bypass switch shall be 4-6ms. Standard output distribution configurations shall be:
Distribution Model PD2-101 PD2-102 PD2-103 PD2-104 PD2-105 PD2-106 Utility Input Connection Hardwired Input 60A Hardwired Input 60A Hardwired Input 60A Hardwired Input 60A Hardwired Input 60A Hardwired Input 60A Output Load Connections Output - (8) 5-20R (T-Slot), (2) L6-30R Output - (4) 5-20R (T-Slot), (4) L6-20R Output - (4) 5-20R (T-Slot), (4) L6-30R Output - (4) 5-20R (T-Slot), (2) L6-30R, (2) L6-20R Output - (4) 5-20R (T-Slot), (2) L5-30R, (2) L5-20R Output - (4) L5-20R, (4) L6-20R Maintenance Bypass Included Included Included Included Included Included
SL-23189_REV1_08-10
10
Guide Specifications
Liebert GXT3-8000/10000RT208
2.7
ON-BOARD COMMUNICATION
The Liebert GXT3 shall offer multiple communication options such as: A. USB: All models shall work with the Power Management system in Microsoft Windows 2000, Windows XP, Windows Vista, Linux and Mac OS X. B. Remote Emergency Power Off (REPO): The UPS shall be equipped with rear-panel terminal connections for interface with either a normally open (N.O.) or normally closed (N.C.) field-supplied switch. The remote emergency power off function shall allow the user to disable all UPS outputs in an emergency situation. Connections must not exceed NEC Class 2 limits. Activation of the REPO circuit shall disable the UPS until the following occurs: y REPO contacts are reset. y User restart of the UPS using the front control panel. C. Terminal Block Communication: includes 8 pins
Pin 1&2 3&4 5&6 7&8 Definition Low Battery Warning On Battery Warning Any Mode Shutdown Battery Mode Shutdown
D. Liebert IntelliSlot Port Simultaneous communication shall be available via terminal block (EPO), USB and Liebert IntelliSlot.
2.8
The UPS shall include one Liebert IntelliSlot communication port to allow the operator to field-install optional Liebert IntelliSlot communication cards. Liebert IntelliSlot cards may be installed during any state of UPS operation (On, Standby or Off states). Available Liebert IntelliSlot options are described below. Liebert IntelliSlot Web Card (IS-WEBCARD) The optional Liebert IntelliSlot Web Card shall deliver SNMP and Web management to the UPS when connected to any 10 or 100 Mbit Ethernet network. The card shall support 10 and 100 Mbit Ethernet and shall provide for in-the-field upgrade of SNMP firmware. The kit shall include the Liebert IntelliSlot card, MIB, configuration cable and user manual. Once the card is installed, serial communication shall be disabled in the DB9F connector; however, the photo-coupler signals (On Battery and Low Battery) shall remain active. Liebert IntelliSlot Relay Interface Card (RELAYCARD-INT) The optional Liebert IntelliSlot Relay Interface Card shall provide contact closure for remote monitoring of alarm conditions in the UPS, delivering signals for On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS. The contacts shall be rated for 24VAC or 24VDC at 1A. Connection shall be to a DB25F connector with cable provided by the end user.
SL-23189_REV1_08-10
11
Guide Specifications
Liebert GXT3-8000/10000RT208
2.9
An included Microsoft Windows-based (Windows 95 or later) Configuration Program and cable shall allow configuration of UPS features and operating parameters to meet specific application requirements, if required. Options that are configurable via this program shall include: y Select one of five output voltages to match input voltages of 200/100, 220/110, 220/127, 230/115 or 240/120. y Enable / Disable Auto-Restart. y Select frequency converter operation with a fixed output frequency of 50 or 60Hz. Bypass is disabled during Frequency Converter mode. y Set the Low Battery Warning alarm time from 2 to 30 minutes. y Disable the Auto-Battery test. y Set the Auto-Battery test interval to 7, 14, 21 or 28 days. y Select the number of external battery cabinets connected to the UPS to adjust the remaining run-time calculations reported by the UPS Liebert software products. y Modify the shutdown setting of the Any Mode Shutdown.
SL-23189_REV1_08-10
12