Expackcolumn PDF
Expackcolumn PDF
Expackcolumn PDF
Water
Rotameter
Air
Rotameter
Blower
WaterValve
AirValve
WaterPump
Figure1.Schematicoflaboratorypackedcolumnwithairandwatercontrols.
Acrylic Column
Packing Height = 57 in
Column inside diameter = 13 in
Air is blown into the column below the packing. A valve and rotameter are used to control
and measure the airflow rate. The inlet air temperature and pressure are measured with a
thermocouple and manometer, respectively. A relative humidity meter and probe located at the
top of the column are used to measure the relative humidity and temperature of the exiting air.
The ambient pressure in the laboratory is measured with a barometer.
Water is circulated to the top of the column with a centrifugal pump. The water flow rate is
controlled with a valve and measured with a rotameter. A thermocouple is located in the pump
inlet line to measure the water inlet temperature.
HYDRAULICS
Investigate laboratory column flooding-velocities for an air-water system in the lab column
by generating a plot similar to the following graph.
Figure2.Exampleofpressuredropvs.superficialgasvelocityplottolocatefloodingvelocities
(SeaderandHenley,1996).
Plot the gas flooding velocity versus liquid mass velocity in a log-log plot
Gasfloodingvelocity,
lb/ft2h
Liquidmassvelocity,lb/ft2h
Figure3.Exampleofgasfloodingvelocityversesliquidmassvelocity.
Calculate the effective diameter (DP) for the packing using dry-gas pressure drop according
the Ergun equation:
2
P 150 u (1 ) 1.75 u (1 )
=
+
lT
D 2p 3
D p 3
2
Ergun:
(1)
Alternatively, determine the effective diameter (DP) and packing constant (CP) from the
Billet-Schultes dry-gas correlation.
P
a u 2
= f 3
lT
2
Billet-Schultes:
(2)
where a/3 is the dry-packing surface area per unit volume of bed void space:
6 (1 )
Dp
(3)
CP 64
1.8
+ 0.08
K w Re Re
(4)
a=
where the Reynolds number is corrected for bed porosity and wall effects:
Re =
uDP K w
(1 )
1
2 1
= 1+
Kw
3 1
Dp
DT
(5)
(6)
CP = packing constant
DP = effective packing diameter, m
DT = diameter of the tower, m
Kw = wall factor
lT = height of packing in the tower, m
u = superficial gas velocity, m/s
P = pressure drop, Pa
= void fraction in the packed column
= gas density, kg/m3
= dynamic viscosity of the gas, Pas
Calculate the packing factor, Fp, from the generalized pressure drop correlation (GDPC):
Figure4.Generalizedpressuredropcorrelation(GDPC)forrandomlypackedtowers(Seaderand
Henley,1996).
MASS TRANSFER
Use the HTUNTU method to calculate the specific gas film mass transfer coefficient, kya, from the
change in humidity of the gas phase:
lT = HTU NTU
(7)
where
HTU =
NTU =
yout
yin
G
kya
(8)
y yin
dy
= ln i
yi y
yi yout
(9)
(10)
EXPERIMENTAL PROCEDURE
A schematic of the experimental apparatus is shown in Figure 1. An image of the
experimental packed column is shown in Figure 5 below.
Figure5.Packedcolumn.
The column consists of two 13 inside diameter columns. The lower section of the column
is 3 feet tall and is the sump, which holds the water. The upper section of the column, which is 6
feet tall, holds the packing. The two sections are attached to each other with flanges. There is a
stainless steel mesh screen between the two columns with 1/4 square openings that supports the
packing in the upper column.
A centrifugal pump transfers the water from the sump to the top of the upper section. At the
top of the column, water is distributed onto the packing through a 60-degree high volume, full
cone, and clog-resistant spray nozzle. The water trickles down through the packing and drains
back into the sump. The water flow is measured with a variable area rotameter.
A Gast Regenair blower supplies air to the column. The airflow to the column is set by
manipulating one or two valves that release air to the lab. The airflow is measured with a
variable area rotameter. Two different measuring devices measure the pressure drop across the
column: a differential pressure meter and a water manometer.
A picture of the water pump and blower is shown in Figure 6.
Figure6.Regenairblowerandwaterpump.
1. Before starting the experiment check to ensure that the water control valve and the two
air control valves are closed.
2. Check to ensure the drain valve on the right bottom side of the sump is closed.
3. Fill the sump with water to within two inches of the bottom of the air inlet on the left side
of the column. Fill the sump with water using a water hose through the grey two-inch
PVC pipe in front of the column.
4. Set the scale on the water manometer so the scale is at zero at the bottom of the meniscus
on each tube.
5. Record the room temperature and barometric pressure.
6. If humidity meters are available record relative humidity and temperature measurements
from the meter at the blower inlet and the upper column outlet.
7. Start the air blower by pressing the start button on the panel located on the wall behind
the blower.
8. Open both air valves so the air entering the column is at a minimum.
9. If humidity meters are available record relative humidity and temperature measurements
from the meters at the blower inlet and the upper column outlet. Record the temperature
of the air entering the column (TC-1).
10. Start the water pump by turning the switch on the electrical strip to on.
11. Adjust the water flow so it is at the minimum flow (8 LPM).
12. Once steady state is reached at the minimum air and water flow record the relative
humidity and temperature from the humidity meter if available. Record the temperature
of the air entering the column (TC-1) and the temperature of the water at the pump inlet
ChE 3211
Name:
Date:
(print name)
LabNo.:Lab3TuesdayandThursdaymorning(9:3011:50AM)
(circleone)
Equipment
Out
In
Equipment
Stopwatch
Name:
(Signature)
Out
In